This document is a Sources Sought notice for an equipment building with an attached 30-foot tall tilt-up communications tower. The National Park Service (NPS) is seeking small business contractors capable of providing the specified equipment, which is described in detail in the attached specifications. The equipment includes an 8x8x8 foot communications shelter with Faraday cage technology, a 4-inch diameter collapsible tower, insulation, electrical components, HVAC, and other features. The project will be awarded under NAICS code 334330 - Radio and Television Broadcasting and Wireless Communications Equipment Manufacturing. Interested small businesses must respond by May 22, 2024 with information on their company profile, qualifications, and delivery timelines. The NPS will use the responses to inform its acquisition strategy, including the potential for a small business set-aside. This is strictly a market research effort, and no contract will be awarded based on these responses.
View the file
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Lake Mead National Recreation Area
Cottonwood Cove/Sand Hill Communications Site
Equipment Building and Tilt Up Tower
Specifications
The work involved with this project is to obtain an equipment building with an attached tilt up 30ft tall communications tower for the Cottonwood Cove, Sand Hill Communications Site. The communications building is to be delivered to the Sand Hill Communications Site at N35 29 13, W114 41 31 or approximately 10,000 Cottonwood Cove Road, Searchlight, NV. 89039.
Detailed description of project requirements are: Equal to a 8ft x 8ft x 8ft Pepro Shelter with a 30ft tall tilt up tower.
1. Provide an 8ft x 8ft x 8ft walk-in communications equipment building with a 30ft tall tilt up pipe style tower.
a. Enclosure to utilize Faraday Cage Technology for it’s construction
b. Tower is to be 4in diameter at the top of the tower
c. Tower is to be on a hinged base and the tower must be collapsible with a built in winching system to tilt the tower up and to lower it for antenna/cable installation.
d. Building walls and ceiling shall contain a minimum of 2in of insulation.
e. Building to AC power entry
f. Interior to have an 100Amp AC load center and base interior layout with a minimum of two interior AC outlets
g. Building to have two interior AC powered lights
h. Includes fire extinguisher with wall mount bracket
i. Includes basic first aid kit
j. Includes two nineteen inch equipment racks bolted to the floor
k. Equipment racks to have mounted buss bars
l. One exterior light at the entry door.
m. Building to have one entry door opposite the tilt up tower
n. Building to have 8 cable entry ports with 7 covers and one entry port for two LMR 400 cables.
o. One and One Half Ton HVAC unit
p. Building to have a Telco Box mounted to the exterior for Telco Cable connections
q. Tower to have three 4in standoffs and 3 antenna mounts for 4ft tall omni antennas.
r. Building to be mounted with four outriggers and concrete Ufer Ground pads in lieu of concrete foundation.