N O A A L a J o l l a L a b o r a t o r y R e p l a c e m e n t P r o j e c t

G i b b e n s D r a k e S c o t t G o u l d E v a n s T r a n S y s t e m s H D R A | D W R B

Submittal Review Transmittal | 4041 Mill Street, Kansas City, Missouri 64111 t 816.931.6655 f 816.931.9640

Project: LaJolla Laboratory Replacement

Specification Description:

Solar PV As-Builts Revised Specification No. 005-16800-4

To: NOAA Western Acquisition Division Date Received: 4/5/2013

7600 Sand Point Way NE Date Returned: 4/8/2013 Seattle, WA 98115

GDS Project No:

201066.04

Contract For: NOAA Attention: Mark Eberling, COTR Contract Number: AB1330-10-CN-0114

To: Rudolph & Sletten

10955 Vista Sorrento Pkwy, #100 San Diego, CA 92130

Attention: Mike Samudio

Corrections or comments made relative to submittals during this review do not relieve the contractor from compliance with the drawings and specifications. This check is only for review of general conformance with the design concept of the project and general compliance with the information given in the contract document. The contractor is responsible for confirming and correcting all quantities and dimensions; selecting fabrication processes and techniques of construction; coordinating his work with that of other trades and performing his work in a safe and satisfactory manner.

Comments:

Spec No: Section Description: Action 005-16800-4 Solar PV As-Builts Revised AAP

AAP Approved AAN Approved as Noted ANR Approved as Noted-Resubmit DIS Disapproved I/O Information Only

Cc:

Gould Evans Gibbens Drake Scott TranSystems HDR ADWRB

GIBBENS DRAKE SCOTT, INC.

9201 E. 63rd Street, Suite 100 Raytown, Missouri 64133

Project Name: NOAA La Jolla Southwest Fisheries Lab Consolidation

Task Order: T0018

GDS Project No. 201066.04

Section Number: 16800 Description: Solar PV as-built resubmittal

Reference Submittal Number: 005-16800-4

GDS Shop Drawing Number: E21R4 x NO EXCEPTION TAKEN MAKE CORRECTIONS NOTED

REJECTED REVISE and RESUBMIT

REVIEWED FOR COMPLIANCE WITH CONTRACT DOCUMENTS AND

SPECIFICATIONS ONLY, AND NOT FOR APPROVAL OF CONSTRUCTION.

Comments:

Corrections or comments made relative to submittals during this review do not relieve the contractor from compliance with the drawings and specifications. This check is only for review of general conformance with the design concept of the project and general compliance with the information given in the contract document. The contractor is responsible for confirming and correcting all quantities and dimensions; selecting fabrication processes and techniques of construction; coordinating his work with that of other trades and performing his work in a safe and satisfactory manner.

Reviewed by:

Gerry Batrez

Date: 4/8/2013

Submittal Packages Detailed with Items and Reviewers

NOAA La Jolla Laboratory Replacement Project # 3141-0 Rudolph and Sletten

8901 La Jolla Shores Dr.

La Jolla, CA 92037

Tel:

Fax:

Solar PV As-Builts005-16800-4

Author Company Contact Author Package # Trade Importance

Rudolph and Sletten Dustin Matteson Solar Panels Normal

Items

Item No. Register No. Rev. Description Type Action Logged By Returned Closed

¨ ¨001 960115838.37 4 Solar PV As Builts As-Builts.

Reviewers

From Company To Company Sent Date DueDate Received Date +/- Action Sent For

Rudolph and Sletten - Dustin Matteson U.S. Department of Commerce, NOAA, Western Acquisition Division - NOAA Designer

4/4/2013 4/18/2013 In Review Review

Package Notes Reviewer General Comments

[10/29/2012 11:28 AM U.S. Department of Commerce, NOAA, Western Acquisition Division - NOAA Designer]

1. PV as-built contractor shall show the locations of all roof mounted PV disconnect switches, conduit routing and where conduits penetrate the roof and route to the inverter.

Revised As-Builts Issued to Address FDE's comments which were issued After the submittal resposne was received.

[3/14/2013 12:19 PM U.S. Department of Commerce, NOAA, Western Acquisition Division - NOAA Designer] Refer to Kim Parson’s comments throughout the submittal, make corrections and re-submit.

[4/3/2013 9:28 AM U.S. Department of Commerce, NOAA, Western Acquisition Division - NOAA Designer] The number of “combiners” does not match sheet to sheet. Drawing PV2.1 indentifies a different number of “combiners” than other drawings. Please correct and re-submit.

Prolog Converge Printed On: 4/4/2013 Page 1 of 1

SHEET INDEX

SHEET NUMBER DESCRIPTION

PV-1 NOTES & SYMBOLS / SHEET INDEX

PV-2 PHOTOVOLTAIC SINGLE LINE DIAGRAM

PV-2.1 ELECTRICAL CALCULATIONS

SL0 ROOF PLAN

SL1 RACKING DETAILS

PV-4 SPECIFICATION SHEETS

PV-5 PLACARDS

STRUCTURAL PACKAGE INCLUDED SEPARATELY

EQUIPMENT SCHEDULE

BUILDING MODULE INVERTER COMBINER

NOAA SHARP NU-U240F2 240W 826 TOTAL SATCON PVS-100 (100KW) 2 TOTAL SOLAR BOS CS75-06-16-4XF 11 TOTAL dustin.matteson

M

SPACE ONLY

INVERTER B

G

N

D

OFF

ON

G

N

D

N

G N D

INVERTER A

G

N

D

G N D

Shop Drawing Review Form-GE-LaJolla Submittal Review Transmitta Solar PV As-Built #4.pdf
20106604-E21R4-005-16800-4 PV as-built Shop Drawing Review.pdf
005-16800-4 Solar PV As-Builts Revised
Submittal Package Detail (23).pdf
NOAA La Jolla Laboratory Replacement

005-16800-4 NOAA- 4.4.13.pdf