Attachment 1 - Salient Characteristics.pdf

PDF 2 MB Posted

Attached to
B4625 TRANE CHILLER REPLACEMENT
Solicitation number
FA485526Q0011
Issued by

About this file

This is a product specification document for an air-cooled scroll chiller being provided for Cannon AFB Building 4625. The document details a Trane CGAM-60 chiller with a nominal cooling capacity of 60 tons, sized for chiller replacement at the military facility's Lubbock sales office. The unit is a 460-volt, 3-phase system featuring 4 compressors across 2 circuits and operates with R-454B refrigerant in compliance with ETL safety standards.

The chiller delivers a cooling capacity of 60.56 tons with an efficiency rating of 11.51 EER (Btu/W-h) and an Integrated Part Load Value (IPLV) of 17.74 EER. The evaporator operates with standard cooling using water as the working fluid, with entering and leaving fluid temperatures of 54°F and 44°F respectively, and a design flow of 144.8 gpm. The condenser configuration includes 6 fans rated for wide ambient conditions up to 95°F. Electrical specifications include a total power draw of 63.11 kW with a single-point MCA of 138 amperes and MOP of 175 amperes. The unit incorporates a dual high-head pump system with variable speed drive control and a 7.5 hp pump motor, operating head pressure of 64.8 ft H2O, and dual expansion tanks with 5-gallon volumes. The chiller is AHRI-certified to standards 550/590 (I-P) and meets ASHRAE 90.1-2019 minimum efficiency requirements for LEED compliance. Physical dimensions are 153.4 inches long by 88.4 inches wide by 84.8 inches high, with an operating weight of 6,184 pounds.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Air-Cooled Scroll

General Chiller Model CGAM

Unit Nominal Tons 60 Nominal Tons

Voltage 460 Volt 3 Phases

Refrigerant Refrigerant Charge R-454B

Number of Circuits 2

Number of Compressors 4

Agency Listing ETL Listed to US/Canadian Safety Std

Chiller Performance Cooling Capacity 60.56 tons

Cooling Efficiency 11.51 EER (Btu/W-h)

IPLV 17.74 EER (Btu/W-h)

Evaporator Evaporator Application Standard Cooling

Fouling Factor 0.000100 hr-sq ft-deg F/ Btu

Fluid Connection Size (Nominal) 3.000 in

Flow Switch Set Point Flow switch set point 60 cm/sec

Design Flow 144.8 gpm

Evaporator Head Loss 14.5 ft H2O

Strainer Head Loss 5.50 ft H2O

VPF Min Flow 88.42 gpm

Fluid Properties

Leaving Fluid Temperature 44.00 F

Entering Fluid Temperature 54.00 F

Fluid Type Water

Fluid Freeze Point 32.00 F

Fluid Storage 5.00 gal

Condenser Unit Application Wide Ambient

Number of Fans 6

Elevation 0.00 ft

Ambient Air Temperature 95.0 F

Electrical Unit Voltage 460 Volt 3 Phases

Compressor Starter Across the line

Incoming Line Connection Type Circuit breaker

Customer Wire Range (Per Phase) #4-4/0

Total Power 63.11 kW

FLA - Constant Speed Condenser Fan 3.30 A

VFD Controlled Input Amps 3.50 A

Short Circuit Rating 5000 A

MCA MOP

Single Point Power 138 A 175 A

Compressor RLA LRA

1A 25.00 A 155.00 A

1B 25.00 A 155.00 A

2A 25.00 A 155.00 A

2B 25.00 A 155.00 A

Job Name: Cannon AFB Building 4625 Chiller Replacement Quantity: 1

Prepared For: Sales Office: Lubbock

Unit Tag: CGAM-60 PP

2026/07/29 14:02:48 Page 1 of 18

Additional Electrical

Voltage FLA/MOP

Evaporator Heater 115V/1 PH 20.00 A

Programmable Relays 115V/1 PH 20.00 A

Pump System Pump Type Dual high head Pump Current 9.00 A

Pump Control Var speed drive Available Head Pressure at Water Connection 64.8 ft H2O

Pump Size 7.500 hp Expansion Tank Volume 5.00 gal

Acoustics

Acoustic Note 1 Acoustic Note 2 Acoustic Note 3

Sound power data collected per AHRI 370 methodology.

Sound power referenced to 1 pW; sound pressure referenced to 20 µPa.

Sound pressure values are at 10 meters from broadside of unit.

Physical

Dimensions

Length 153.400 in

Width 88.400 in

Height 84.800 in

Weights

Operating Weight 6184 lb

Shipping Weight 6013 lb

Circuits Refrigerant Charge Oil Charge

Circuit 1 51.0 lb 2.10 gal

Circuit 2 51.0 lb 2.10 gal

Standard Rating Performance and LEED Rating Cooling Capacity 60.56 tons

Rated Cooling Capacity 60.45 tons

Cooling Efficiency 11.51 EER (Btu/W-h)

Rated Cooling Efficiency 11.50 EER (Btu/W-h)

IPLV 17.74 EER (Btu/W-h)

Compressor Power 55.25 kW

Fan Motor Power 7.503 kW

Refrigerant Charge Circuit 1 51.0 lb

Refrigerant Charge Circuit 2 51.0 lb

ASHRAE 90.1 - 2019

This product meets the minimum efficiency requirements of ASHRAE Standard 90.1 (which are based on AHRI standard rating conditions with water) and, therefore, also meets the LEED "Minimum Energy Performance" prerequisite in the Energy and Atmosphere section.

The LEED Green Building Rating System™, developed by the U.S.

Green Building Council, provides independent, third-party verification that a building project meets green building and performance measures.

Regulatory Compliance

AHRI Certification

Certified in accordance with the AHRI Air-Cooled Water-Chilling Packages Certification Program, which is based on AHRI Standard 550/590 (I-P) and AHRI Standard 551/591 (SI). Certified units may be found in the AHRI Directory at www.ahridirectory.org

Publication Data Generation Date 7/29/2026

Trane Select Assist Version Number 2607

Job Name: Cannon AFB Building 4625 Chiller Replacement Quantity: 1

Prepared For: Sales Office: Lubbock

2026/07/29 14:02:48 Page 2 of 18

Job Name: Cannon AFB Building 4625 Chiller Replacement Quantity: 1

Prepared For: Sales Office: Lubbock

2026/07/29 14:02:48 Page 3 of 18

Prepared For: Sales Office: Lubbock

2026/07/29 14:02:48 Page 4 of 18

Prepared For: Sales Office: Lubbock

2026/07/29 14:02:48 Page 5 of 18

Prepared For: Sales Office: Lubbock

2026/07/29 14:02:48 Page 6 of 18

Prepared For: Sales Office: Lubbock

2026/07/29 14:02:48 Page 7 of 18

Prepared For: Sales Office: Lubbock

2026/07/29 14:02:48 Page 8 of 18

Prepared For: Sales Office: Lubbock

2026/07/29 14:02:48 Page 9 of 18

Prepared For: Sales Office: Lubbock

2026/07/29 14:02:48 Page 10 of 18

Prepared For: Sales Office: Lubbock

2026/07/29 14:02:48 Page 11 of 18

Prepared For: Sales Office: Lubbock

2026/07/29 14:02:48 Page 12 of 18

Prepared For: Sales Office: Lubbock

2026/07/29 14:02:48 Page 13 of 18

Prepared For: Sales Office: Lubbock

2026/07/29 14:02:48 Page 14 of 18

Prepared For: Sales Office: Lubbock

2026/07/29 14:02:48 Page 15 of 18

Prepared For: Sales Office: Lubbock

2026/07/29 14:02:48 Page 16 of 18

Prepared For: Sales Office: Lubbock

2026/07/29 14:02:48 Page 17 of 18

Prepared For: Sales Office: Lubbock

2026/07/29 14:02:48 Page 18 of 18

File details come from the government source that posted it. Updated .