This document contains minimum salient characteristics for a 100 Ton Trane Air-Cooled Scroll Packaged Chiller with associated transport equipment and accessories.

The specifications detail a high-efficiency 100-ton chiller operating on R-454B refrigerant with 460/60/3 power requirements, factory-installed freeze protection, and AHRI certification. The unit includes features such as BACnet MS/TP interface, architectural louvered panels with hail guards, and a 10,000-amp SCCR circuit breaker. The equipment must be mounted on a low-profile flatbed trailer (24' x 102") with 10,000 lb tandem axles and a 3" pintle eye hitch. The package includes a 10 hp pump system (235 GPM @ 87 ft head), 4" chilled water piping with bypass, and various accessories including Camlock connectors, power cables, and mounting hardware. The warranty requires factory startup by Trane Service and includes first-year coverage for parts, labor, and refrigerant loss.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Minimum Salient Characteristics

100 Ton Trane Air-Cooled Scroll Packaged Chiller

Startup Included - Trane Service must start equipment for warranty to be honored.

100 nominal tons

460/60/3

High efficiency/performance

Refrigerant Charge R-454B

With factory installed freeze protec�on

Refrigerant isola�on valves (discharge valve)

ETL Listed to US/Canadian Safety Standard

ASHRAE 90.1/CSA C743 - 2019 Compliance

AHRI cer�fied.

Standard cooling applica�on (leaving water temperature greater than 42°F)

Grooved pipe connec�on

Factory insula�on 0.75"

Performance based on water.

Wide ambient opera�ng capability

Lanced aluminum fins

Across the line starter/direct online

Single point connec�on main line unit power – ancillary items require separate 110v power connec�on(s)

Circuit breaker

10,000-amp SCCR

Enclosure Type UL 60335 Rated for Outdoor Applica�ons

BACnet MS/TP Interface

Programmable quad relay alarm board

No Wireless Op�ons

Factory installed IFM Efector flow switch.

: (Three phase electrical connection/capability)

Factory installed water strainer.

Standard low noise fans

Architectural louvered panels – hail guards covering upper and lower sec�ons.

1st year en�re chiller parts labor, and refrigerant loss warranty

Factory start up and prestart inspec�on.

Low Profile Flatbed Trailer

3” Pintle Eye Hitch

Deck over approximately 24’ long x 102” wide

Straight deck with no ramps or pockets

10,000 lb. tandem axels

Primer + powder coat

Tool compartment

Spare �re and mount

10 hp pump with suc�on diffuser

TEFC NEMA Premium efficient motor

235 GPM @ 87 � head

Variable frequency drive

Furnish and install new transformer 208v /480v.

Weathershield to convert to type 3R enclosure.

4” chilled water piping from chiller to pump with bypass

Isola�on valves will be installed at the piping connec�ons to protect piping interior during transport.

Piping will include associated pressure gauges and thermometers.

120VAC connec�on for energizing oil heaters

DLO Camlock power connector for connec�on of temporary field wire

Accessories furnished:

(2) 50 � hose, 4” with Camlock connectors

(2) 4” male Camlock to ANSI 150 flange adapter

(2) 4” female Camlock to ANSI 150 flange adapter

(Quantity is in Parenthesis)

(14) 50 � sec�on of 4/0 power cable with Camlocs (3x Black, 3x Red, 3x Blue, 2x Green, 1x Brown, 1x Orange, 1x Yellow)