This document contains minimum salient characteristics for a 100 Ton Trane Air-Cooled Scroll Packaged Chiller with associated transport equipment and accessories.
The specifications detail a high-efficiency 100-ton chiller operating on R-454B refrigerant with 460/60/3 power requirements, factory-installed freeze protection, and AHRI certification. The unit includes features such as BACnet MS/TP interface, architectural louvered panels with hail guards, and a 10,000-amp SCCR circuit breaker. The equipment must be mounted on a low-profile flatbed trailer (24' x 102") with 10,000 lb tandem axles and a 3" pintle eye hitch. The package includes a 10 hp pump system (235 GPM @ 87 ft head), 4" chilled water piping with bypass, and various accessories including Camlock connectors, power cables, and mounting hardware. The warranty requires factory startup by Trane Service and includes first-year coverage for parts, labor, and refrigerant loss.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Solicitation - FA303025Q0010.pdf | ||
| Attachment 2 - 2024 HVAC Chiller JA - AQ Signed 10 Sep 24.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Minimum Salient Characteristics
100 Ton Trane Air-Cooled Scroll Packaged Chiller
Startup Included - Trane Service must start equipment for warranty to be honored.
100 nominal tons
460/60/3
High efficiency/performance
Refrigerant Charge R-454B
With factory installed freeze protec�on
Refrigerant isola�on valves (discharge valve)
ETL Listed to US/Canadian Safety Standard
ASHRAE 90.1/CSA C743 - 2019 Compliance
AHRI cer�fied.
Standard cooling applica�on (leaving water temperature greater than 42°F)
Grooved pipe connec�on
Factory insula�on 0.75"
Performance based on water.
Wide ambient opera�ng capability
Lanced aluminum fins
Across the line starter/direct online
Single point connec�on main line unit power – ancillary items require separate 110v power connec�on(s)
Circuit breaker
10,000-amp SCCR
Enclosure Type UL 60335 Rated for Outdoor Applica�ons
BACnet MS/TP Interface
Programmable quad relay alarm board
No Wireless Op�ons
Factory installed IFM Efector flow switch.
: (Three phase electrical connection/capability)
Factory installed water strainer.
Standard low noise fans
Architectural louvered panels – hail guards covering upper and lower sec�ons.
1st year en�re chiller parts labor, and refrigerant loss warranty
Factory start up and prestart inspec�on.
Low Profile Flatbed Trailer
3” Pintle Eye Hitch
Deck over approximately 24’ long x 102” wide
Straight deck with no ramps or pockets
10,000 lb. tandem axels
Primer + powder coat
Tool compartment
Spare �re and mount
10 hp pump with suc�on diffuser
TEFC NEMA Premium efficient motor
235 GPM @ 87 � head
Variable frequency drive
Furnish and install new transformer 208v /480v.
Weathershield to convert to type 3R enclosure.
4” chilled water piping from chiller to pump with bypass
Isola�on valves will be installed at the piping connec�ons to protect piping interior during transport.
Piping will include associated pressure gauges and thermometers.
120VAC connec�on for energizing oil heaters
DLO Camlock power connector for connec�on of temporary field wire
Accessories furnished:
(2) 50 � hose, 4” with Camlock connectors
(2) 4” male Camlock to ANSI 150 flange adapter
(2) 4” female Camlock to ANSI 150 flange adapter
(Quantity is in Parenthesis)
(14) 50 � sec�on of 4/0 power cable with Camlocs (3x Black, 3x Red, 3x Blue, 2x Green, 1x Brown, 1x Orange, 1x Yellow)