This document provides requirements for battery chargers to be procured by the Western Area Power Administration's Sierra Nevada Region. The battery chargers must meet technical specifications including a DC output filter to eliminate 100mV RMS without a battery, 480V 3-phase 60Hz AC input voltage, circuit breaker protection, remote communication capabilities via serial and ethernet adapters, enclosure as a NEMA Type-1 Style-5030 floor mount, 130V-200A DC output, microprocessor controlled SCR design, and a cabinet width of 30" or less. The chargers shall be delivered by coordination to Olinda Substation in Cottonwood, California by July 2023. The related federal contract opportunity is solicitation number 89503323QWA000193 for Olinda Substation Battery Chargers through the Department of Energy.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Sol_89503323QWA000193.pdf | ||
| Sol_89503323QWA000193_Amd_0001.pdf | ||
| Amend 0001_Questions and Answers.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Requirements Document Western Area Power Administration
Sierra Nevada Region July 2023
1. General
1.1 Scope
This Specification is for the ATEVO 3 phase 130V 200A battery chargers or equivalent.
2. Characteristics
The battery chargers shall meet the following characteristics:
DC Output Filter: eliminator 100 mV RMS w/o battery AC Input Voltage: 480Vac 3PH 60Hz, non-tappable AC Input Protection: 3-pole high 35 kAIC circuit breaker 80A BG3 DC Output Protection: 3-pole high 20 kAIC circuit breaker 300A LGL3 Remote Communication: (1) serial comm adapter & (1) ethernet adapter Enclosure: NEMA Type-1 Style-5030 floor-mount
OUTPUT: 130V-200A
Microprocessor Controlled SCR Filtered/Eliminator Battery Charger 200 Amp DC Output 130 Volt DC Output 60 HZ Input 240 Vac Input Three Phase Input Options Description Special Gnd. Bus External Temp Probe 100FT Alarms PACKAGE (low voltage, high voltage, +/- DC battery ground, DC output failure, AC input failure) Hydrogen Detection with Alarm DNP 3.0 Interface Module
2/C EQ IND / FAN CONTROL
Cabinet width must be 30” or less
3. Delivery The chargers shall be delivered Olinda Substation 18275 Gas Point Rd Cottonwood CA, 96022. The delivery date and time must be coordinated in advance with the contact listed below.
CONTACT FOR DELIVERY:
Jim Higgins, Office Ph. (916) 646-7330, Cell Ph. (916) 769-2360, Email: Higgins@wapa.gov.