This document provides answers to questions regarding solicitation number 89503323QWA000193 for Olinda Substation Battery Chargers issued by the Department of Energy. The specification in the solicitation contained conflicting information about the required AC input voltage for the battery chargers, stating both three phase 480 volt and three phase 240 volt inputs. This document clarifies that the correct input requirement is for a three phase 240 volt AC input voltage. It also confirms that the on-site voltage for the battery chargers is 240 volts AC.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Sol_89503323QWA000193.pdf | ||
| Sol_89503323QWA000193_Amd_0001.pdf | ||
| Attachment 1- Requirements Document.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
89503323QWA000193 Amendment 0001- Questions and Answers
1) The specification contains a conflicting AC input. On the second bullet point it calls out a three phase, 480 volt input but bullet point #13 the specification calls out a three phase 240 VAC input. Can you please clarify what AC input is required?
Answer: It is a 3 phase, 240 vac.
2) What is the on-site voltage? The spec calls for 240 and 480VAC, which is a mistake as it can only be one of both. Which one is correct?
Answer: It is a 3 phase, 240 vac.