Attachment 1 - Raypak Boiler Specs.pdf

PDF 34 KB Posted

Attached to
HVAC BOILER REPLACEMENT 4418 (Raypak)
Solicitation number
FA480925Q0094
Issued by

About this file

This document details specifications for a Raypak MVB (Modulating Vertical Hydronic) Boiler, Model # H7-503A, designed for indoor natural gas hydronic applications. The boiler features 500 MBH input with 431 MBH output, cast iron headers, a copper heat exchanger, and 86.2% thermal efficiency, with key technical capabilities including electronic modulation with a 7:1 turndown ratio, VERSA IC integrated controller with a 7" color touchscreen, and Raymote remote connectivity. Additional specifications include a 60 PSIG pressure relief valve, capability to cascade up to 8 boilers without an external sequencer, Modbus RTU BMS port, and SCAQMD Rule 1146.2 certification with low NOx emissions under 20 ppm.

The boiler has precise operational parameters, including a maximum outlet water temperature of 235°F, a minimum acceptable inlet water temperature of 120°F, and features like a 3-try stand ignition, F-10 LWCO fixed manual reset high limit, condensate unit, cast iron pump, and full safety diagnostics with status display lights. These comprehensive specifications align with the Air Force Air Combat Command's solicitation (FA480925Q0094) for an HVAC boiler replacement, which specifically requires this Raypak MVB Boiler model for installation.

View the file

Other files

File Type Posted
Brand Name Justification_Redacted.pdf PDF
Solicitation - FA480925Q0094.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

MVB Boiler - (Modulating Vertical Hydronic) Hydronic application indoor Model # H7-503A

Natural Gas

500 MBH Input /431 MBH Output

Cast Iron headers

Copper Heat Exchanger

60 PSIG Pressure Relief Valve

3 try stand ignition

F-10 LWCO Fixed manual reset high limit

Condensate unit

Cast Iron pump P-10

Cold Water Start P-64

86.2% Thermal efficiency at full rate

VERSA IC® Integrated controller with 7" color touchscreen display

Raymote™ remote connectivity provided standard

Electronic modulation, constant ratio 7:1 turndown

Full safety diagnostics with history

Status display lights

Cascade up to 8 boilers - no external sequencer required

Cascade in parallel or sequential modulation modes

Modbus RTU BMS Port

Maximum outlet water temperature: 235°F (113°F)

Minimum acceptable inlet water temperature: 120°F (49°F)

SCAQMD Rule 1146.2 certified, Low NOx < 20 ppm

File details come from the government source that posted it. Updated .