Attachment 1 - PDC Study Report.pdf

PDF 16 MB Posted

Attached to
Repair Backup Power - Hangar 11 Federal contract opportunity
Solicitation number
W50S6L21B0001
Issued by
Department of the Army Alaska Army National Guard

View the file

Other files for this federal contract opportunity

Other files attached to Repair Backup Power - Hangar 11, newest first.
File Type Posted
Bid Abstract - 21B0001.pdf PDF
W50S6L21B0001 Amendment 2 (SAM).pdf PDF
W50S6L21B0001 Amendment 1 (SAM).pdf PDF
Section 01000 General Requirements.pdf PDF
Site Visit Sign-in Sheet.pdf PDF
SOW - Repair Back-Up Power H11.pdf PDF
W50S6L21B0001.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Project Name:

Project #:

Date:

Calculated by:

Checked by:

DIRECT COST DESCRIPTION

UNIT EQ, MATERIAL

No. UNITS COST LABOR & OTH

OPTION A

25kW Generator (Exterior) 1.00 ea

60A/3P circuit breaker (LSIG) 1.00 ea

60A ATS (Interior) 1.00 ea

100A 480V Panel and feeder (75') 1.00 ea

30kVA transformer, NEMA 1 1.00 ea

100A 208V panel and feeder (20') 1.00 ea

Relocate branch circuits (about 15 averaging 75') 1.00 ea

Site changes (trenching, pad, bollards) 1.00 ea

Fuel Tank (1000 gallon double wall on pad) 1.00 ea

ADJUSTED SUBTOTALS

CONTRACTOR O&HP

ESTIMATING CONTINGENCY

TOTAL ESTIMATED COST

Engineer's Cost Estimate

Hangar 11 Backup Power

21007AN

May 7, 2021

BKH

RDP

QUANTITY ADJUSTED

P:\2021\21007AN-Hngr11_EBG\E\Calcs\JBER Hangar 11 Engineer's Cost EstimatePage 3

Project Name:

Project #:

Date:

Calculated by:

Checked by:

DIRECT COST DESCRIPTION

UNIT EQ, MATERIAL

No. UNITS COST LABOR & OTH

OPTION C

Remove MTS and portable generator connection 1.00 ea

Refeed panel DP11-114-1S 1.00 ea

100kW Generator (Exterior with weather enclosure) 1.00 ea

100A ATS (Exterior) 480V 1.00 ea

45kVA transformer on pad (Exterior NEMA 3R) 1.00 ea

200A ATS (Exterior) 208V 1.00 ea

Relocate service feeder (480V) 1.00 ea

Relocate service feeder (208V) 1.00 ea

Site changes (trenching, pad, bollards) 1.00 ea

Parts and Labor for breaker adjustment in MDP11-114-1 1.00 ea

Fuel Tank (1000 gallon double wall on pad) 1.00 ea

Adjust 480V Service Main Breaker and Relabel 1.00 ea

ADJUSTED SUBTOTALS

CONTRACTOR O&HP

ESTIMATING CONTINGENCY

TOTAL ESTIMATED COST $

Engineer's Cost Estimate

Hangar 11 Backup Power

21007AN

May 7, 2021

BKH

RDP

QUANTITY ADJUSTED

P:\2021\21007AN-Hngr11_EBG\E\Calcs\JBER Hangar 11 Engineer's Cost EstimatePage 3

Description

Option A Option B Option C

Hangar Doors 6000

CF-1 1743

CF-2 1743

CF-3 1743

RH-1 (x21) 3590

B-1 500

B-2 500

B-3 500

CP-1 1260

CP-2 1260

CP-3 1260

CP-4 2380

CP-5 2380

CP-6 250

CP-7 250

MUA-1 9135

MUA-2 9135

UH-FG-01 100

UH-FG-02 100

SF-FG-01 1176

Lighting DP11-114-2S-2,4 2059

Lighting LP11-10-1-15,17 1911

Lighting B-1,2,3,4 1500

Lighting B-1,3,4, 5 & C-1,3,4, 6 2400

Lighting C-1,2,3,4,5 1500

Lighting LP11-118-1-21 754

Lighting LP11-110-1-23,25 1922

Lighting LP11-118-1-23,25 2382

CUH-11-03 200

EF-11-01 860

CUH-11-04 200

UH-11-02 20

CUH-11-01 200

CUH-11-02 200

2 QUAD RECEPTS 720

SF-11-01 1660

Loads (W or VA)

UH-11-02 20

CUH-11-07 200

AHU-11-02 1180

EF-11-02 110

CUH-11-06 200

UH-11-06 10

2 QUAD RECEPTS 720

AHU-11-01 1180

QUAD RECEPT 360

SF-11-02 860

SF-11-03 1750

UH-11-04 20

EF-11-04 30

EF-11-03 30

2 QUAD RECEPTS 720

AHU-11-03 1660

Entire Building (2 normal services) -

Peak Load info from meter readings

36000 (208V) &

57000 (480V)

TOTALS 14819 72543 93000

20kw 75kw 100kw

25 93.75 125

30kVA 100kVA 125kVA

File details come from the government source that posted it. Updated .