Attachment 1 - Oil Storage Tank - Specifications.pdf
PDF 36 KB Posted
- Attached to
- Above Ground Tank, B2141
- Solicitation number
- FA302024Q0085
About this file
This document is an attachment to a federal solicitation for the procurement of a 500-gallon Waste Evac Oil Storage System (or equal). The solicitation is issued by the Department of the Air Force, Air Education and Training Command as a Request for Quotes (RFQ) with a Firm Fixed Price (FFP) contract type. The contractor will be required to ship, unload, install, and test the oil storage tank, which must comply with the detailed specifications provided in Attachment 1. The solicitation has a Period of Performance of 120 Calendar Days after receipt of award, and all quotes must be valid through 30 September 2024. This requirement is a total set-aside for small business concerns under NAICS code 238220. A site visit is scheduled for 19 August 2024, and the solicitation will close at 2:00 PM CDT on 23 August 2024, with all questions due by 20 August 2024.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Spec sheet for Oil Storage Tank:
Requires contractor to test and install a 500-gallon Waste Evac Oil Storage System (BRAND
NAME OR EQUAL)
MODEL NUMBER: H500
Capacity (Gallons): 500
Dimensions: L 6’4” x W 4’0” x H 3’7”
Weight (Pounds): 1,500
Salient Characteristics:
Shipping, installation, and testing of the tank needs to be included
Oil Storage Tank MUST comply with “Attachment 1 – Oil Storage TANK _ Specifications”
Salient Characteristics:
• Moveable by forklift
• UL-listed double-wall tank
• 110% secondary containment
• 1” UL-listed air operated double diaphragm pump
• Air filter/regulator and pressure gauge
• Automatic air operated high level shut off valve with whistle
• Manual air inlet shutoff valve
• UL-listed ¾” x 8’ hardwall suction hose with in-line strainer and female quick connect adapter
• Male quick connect adapter
• 2” suction tube with kamlock and dust cap (for product withdrawal)
• Primary working vent
• Primary and secondary emergency vents
• Product level gauge
• Corrosion resistant exterior coating
• Product decals
• Leak monitoring port
• 6” fill hatch with screen
• Length must be less than 102 inches
• Width must be less than 64 inches
• 500 gallon storage capacity
File details come from the government source that posted it. Updated .