This document comprises testing results and infrastructure analysis for the USMC Marsh Center's telecommunications cabling system at MCB Quantico. The testing evaluated voice and data cabling across two telecom rooms (East and West) serving the Recruiting Command Headquarters on the second deck, with a total of 883 panels tested across four categories (East Closet Voice, East Closet Data, West Closet Voice, West Closet Data). Overall pass rate was 79.01% with 625 panels passing, 149 failing, and 17 marginal results. Testing identified 92 unidentified cables and revealed systematic installation deficiencies, including 27 biscuits/bezels not attached to furniture on the east side and 32 on the west side.

The assessment recommends three primary corrective actions: properly measuring cubicle furniture cutout openings and installing matching bezels; replacing all jacks at the station side of cabling to ensure equal quality and correct failing/broken jacks; and conducting a comprehensive telecom room overhaul. Secondary recommendations address both telecom rooms' infrastructure deficiencies, including removing old equipment and cabling, upgrading cable management and support systems, adding cable tray over data racks, redressing blue cabling, and performing a phone switch audit to identify active analog lines. The facility requires three additional drop locations (bringing the total from 270 to 273 workstations) with CAT6 jacks totaling 810 CAT6 jacks/drops across all 270 workstation locations, with installation approval needed for these additions.

View the file

Other files

File Type Posted
SOW_ Data Port Repair Services.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

MCB Quantico Marsh Center Testing Statistics

Terminated on Panels Tested Pass Fail Marginal Tested Pass Fail Marginal

East Closet Voice 139 121 89 27 5 87.05% 73.55% 22.31% 4.13%

East Closet Data 276 249 205 37 7 90.22% 82.33% 14.86% 2.81%

West Closet Voice 156 142 93 46 3 91.03% 65.49% 32.39% 2.11%

West Closet Data 312 279 238 39 2 89.42% 85.30% 13.98% 0.72%

883 791 625 149 17 89.58% 79.01% 18.84% 2.15%

Cables Not Identified 92

East Side

(27) Biscuits/Bezels not attached to furniture

West Side

(32) Biscuits/Bezels not attached to furniture

Recommendations:

1) Properly measure the cut out openings in the cubicle furniture and install a bezel that matches the opening size

2) Replace all jacks at the station side of the cabling and retest. This will ensure all are equal quality and terminated correctly

It will also correct all of the failing/broken jacks.

3) Consider an overhaul of the telecom rooms. (See Telecom room overservations)

Additional drop locations needed per Mike Elliott (NEED APPROVAL TO INSTALL) changes total from 270 to 273

SINGLE WORK STATION LOCATION – 3

CAT6 JACKS/DROPS EACH

TOTAL OF 270 WORK STATION

LOCATIONS – 810 CAT6 JACKS/DROPS

SECURITY DESK

WORK AREA

SUPPLY

STORAGE

USMC Marsh Center 2nd Deck Recruiting Command HQ

NA

New

South/East Telecom Room

Old

Old

RU 45

RU 44

RU 43

RU 42

RU 41

RU 40

RU 39

RU 38

RU 37

RU 36

RU 35

RU 34

RU 33

RU 32

RU 31

RU 30

RU 29

RU 28

RU 27

RU 26

RU 25

RU 24

RU 23

RU 22

RU 21

RU 20

RU 19

RU 18

RU 17

RU 16

RU 15

RU 14

RU 13

RU 12

RU 11

RU 10

RU 9

RU 8

RU 7

RU 6

RU 5

RU 4

RU 3

RU 2

RU 1

Data Rack

RU 45

RU 44

RU 43

RU 42

RU 41

RU 40

RU 39

RU 38

RU 37

RU 36

RU 35

RU 34

RU 33

RU 32

RU 31

RU 30

RU 29

RU 28

RU 27

RU 26

RU 25

RU 24

RU 23

RU 22

RU 21

RU 20

RU 19

RU 18

RU 17

RU 16

RU 15

RU 14

RU 13

RU 12

RU 11

RU 10

RU 9

RU 8

RU 7

RU 6

RU 5

RU 4

RU 3

RU 2

RU 1

Voice Rack

RU 45

RU 44

RU 43

RU 42

RU 41

RU 40

RU 39

RU 38

RU 37

RU 36

RU 35

RU 34

RU 33

RU 32

RU 31

RU 30

RU 29

RU 28

RU 27

RU 26

RU 25

RU 24

RU 23

RU 22

RU 21

RU 20

RU 19

RU 18

RU 17

RU 16

RU 15

RU 14

RU 13

RU 12

RU 11

RU 10

RU 9

RU 8

RU 7

RU 6

RU 5

RU 4

RU 3

RU 2

RU 1

Cabinet 2 Post Rack

PP 1

PP 2

PP 3

LIU 12 STSM/12 STMM

LIU 12 SCMM

1RU Swith

APC

1a/b old data station cable

144a/b hubbell cat 5 panels

UPS

1-192

Switch pairs old voice station cables

RU 43

RU 42

RU 41

RU 40

RU 39

RU 38

RU 37

RU 36

RU 35

RU 34

RU 33

RU 32

RU 31

RU 30

RU 29

RU 28

RU 27

RU 26

RU 25

RU 24

RU 23

RU 22

RU 21

RU 20

RU 19

RU 18

RU 17

RU 16

RU 15

RU 14

RU 13

RU 12

RU 11

RU 10

RU 9

RU 8

RU 7

RU 6

RU 5

RU 4

RU 3

RU 2

PP 2

PP 3

PP 4

PP 5

PP 6

MCRC RCEN Router

MCRC RCEN SW1

MCRC RCEN SW2

MCRC RCEN SW3

MCRC RCEN SW4

USMC Marsh Center - 2 East Telecom Room Patch Panel Reference

276 Total

Data

2E-D 2E-D 2E-D 2E-D 2E-D 2E-D

025A 025B 026A 026B 027A 027B

Panel 3

Panel 4

Panel 5

Panel 6

30 31

36 37

42 43

010A 010B 011A 011B 012A 012B

013A 013B 014A 014B 015A 015B

016A 016B 017A 017B 018A 018B

019A 019B 020A 020B 021A 021B

022A 022B 023A 023B 024A 024B

001A 001B 002A 002B 003A 003B

004A 004B 005A 005B 006A 006B

007A 007B 008A 008B 009A 009B

249 Total

Tested

No Test

Passed

Failed

Marginal

028A 028B 029A 029B 030A 030B

031A 031B 032A 032B 033A 033B

034A 034B 035A 035B 036A 036B

037A 037B 038A 038B 039A 039B

040A 040B 041A 041B 042A 042B

043A 043B 044A 044B 045A 045B

046A 046B 047A 047B 048A 048B

Panel 1

Panel 2

049A 049B 050A 050B 051A 051B

052A 052B 053A 053B 054A 054B

055A 055B 056A 056B 057A 057B

058A 058B 059A 059B 060A 060B

061A 061B 062A 062B 063A 063B

064A 064B 065A 065B 066A 066B

067A 067B 068A 068B 069A 069B

070A 070B 071A 071B 072A 072B

073A 073B 074A 074B 075A 075B

076A 076B 077A 077B 078A 078B

079A 079B 080A 080B 081A 081B

082A 082B 083A 083B 084A 084B

085A 085B 086A 086B 087A 087B

088A 088B 089A 089B 090A 090B

091A 091B 092A 092B 093A 093B

094A 094B 095A 095B 096A 096B

097A 097B 098A 098B 099A 099B

100A 100B 101A 101B 102A 102B

103A 103B 104A 104B 105A 105B

106A 106B 107A 107B 108A 108B

109A 109B 110A 110B 111A 111B

112A 112B 113A 113B 114A 114B

115A 115B 116A 116B 117A 117B

118A 118B 119A 119B 120A 120B

121A 121B 122A 122B 123A 123B

124A 124B 125A 125B 126A 126B

127A 127B 128A 128B 129A 129B

130A 130B 131A 131B 132A 132B

133A 133B 134A 134B 135A 135B

136A 136B 137A 137B 138A 138B

1 6 7 12 13 18

19 24

2E-V

139 Total

Voice

2E-V 2E-V 2E-V 2E-V 2E-V 2E-V

044 045 046 047 048 049

121 Total

Tested

001 002 003 004 005 006

007 008 009 010 011 012

013 014 015 016 017 018

019 020 021 022 023 024

050 051 052 053 054 055

056 057 058 059 060 061

062 063 064 065 066 067

025 026 027 028 029 030

031 032 033 034 035 036

037 038 039 040 041 042

068 069 070 071 072 073

074 075 076 077 078 079

080 081 082 083 084 085

086 087 088 089 090 091

092 093 094 095 096 097

098 099 100 101 102 103

104 105 106 107 108 109

110 111 112 113 114 115

116 117 118 119 120 121

122 123 124 125 126 127

128 129 130 131 132 133

134 135 136 137 138 139

East/South Side of Bldg Outlet Notes Notes

9 Biscuit off furniture

10 Biscuit off furniture

11 Biscuit off furniture

12 Biscuit off furniture A&B Data are swapped

16 Biscuit off furniture

18 Biscuit off furniture

20 Biscuit off furniture

21 Biscuit off furniture

22 Biscuit off furniture

24 Biscuit off furniture Voice Jack - something stuck in it

30 Biscuit off furniture

33 Biscuit off furniture

37 Biscuit off furniture

42 Biscuit off furniture

49 Biscuit off furniture

50 Biscuit off furniture

54 Biscuit off furniture

55 Biscuit off furniture

56 Biscuit off furniture

58 Biscuit off furniture

76 Biscuit off furniture

79 Biscuit off furniture Voice Jack - something stuck in it

81 Biscuit off furniture

82 Biscuit off furniture

83 Biscuit off furniture

84 Biscuit off furniture

86 Biscuit off furniture

111 Voice jack missing

113 A Data jack missing

114 Voice Jack missing

115 No Faceplate

116 A&B Data are swapped

Failing Results Voice Diagnosis Possible Cause

1 Or/Wh, Wh/B, B/Wh open. Bad patch panel port or termination

3 Wh/Or, Wh/Br open Broken Jack/Pins/Termination

7 B/Wh open Broken Jack/Pins/Termination

8 Wh/Or, Br/Wh open Broken Jack/Pins/Termination

14 Gr/Wh, Wh/Br Bad patch panel port or termination

18 Wh/Br open Bad patch panel port or termination

25 Gr/Wh Bad patch panel port or termination

32 Wh/Or open Broken Jack/Pins/Termination. Possible cut cable

33 Return Loss - IDF Side Poor termination

34 Return Loss - Both Sides Poor termination

37 Wh/Or, Br/Wh open Broken Jack/Pins/Termination

38 Wh/Or open Broken Jack/Pins/Termination

39 Wh/Or open Bad patch panel port or termination

43 Return Loss - Both Sides Poor termination

45 Wh/Or, Or/Wh, Wh/Gr, Wh/Br open Bad patch panel port or termination

55 Wh/Gr, Gr/Wh open Bad patch panel port or termination

61 Wh/Or open Bad patch panel port or termination

63 Wh/Or, Gr/Wh, Wh/Br Broken Jack/Pins/Termination. Bad patch panel port or termination

64 Wh/Or open. Blue pair crossed Broken Jack/Pins/Termination

68 Wh/Or, Br/Wh open Broken Jack/Pins/Termination

69 Wh/Or open Broken Jack/Pins/Termination

71 Or/Wh open Broken Jack/Pins/Termination. Possible cut cable

78 Wh/Or open Broken Jack/Pins/Termination

80 Wh/Or open Broken Jack/Pins/Termination

86 Wh/Gr open Broken Jack/Pins/Termination

97 Green & Brown Pairs Crossed Poor Termination 110 Wh/Gr open Broken Jack/Pins/Termination

Marginal Results-Voice Diagnosis Possible Cause

30 Return Loss - IDF Side Poor Termination

36 Return Loss - IDF Side Poor Termination

52 Cross Talk - WAO Side Poor Termination

117 Cross Talk - WAO Side Poor Termination 129 Cross Talk - WAO Side Poor Termination

Data Diagnosis Possible Cause

10B Or/Wh, Wh/Gr open Bad patch panel port or termination

11B Wh/Gr, Wh/Br open Bad patch panel port or termination

12A Or/Wh open Bad patch panel port or termination

12B Wh/Br open Bad patch panel port or termination

18A Or/Wh, Wh/Or, Wh/Br open Bad patch panel port or termination

20B Or/Wh open Bad patch panel port or termination

22A Wh/Gr, Gr/Wh open Broken Jack/Pins/Termination. Bad patch panel port or termination

24B Wh/Or, B/Wh open Broken Jack/Pins/Termination. Bad patch panel port or termination

27A Or/Wh, Br/Wh open Bad patch panel port or termination

27B Or/Wh, Wh/Or, Gr/Wh open Bad patch panel port or termination

33A Gr/Wh Open Bad patch panel port or termination

34A Return Loss - Both Sides Poor Termination

34B Wh/Br open Bad patch panel port or termination

35B Wh/Or, Or/Wh, B/Wh open Bad patch panel port or termination

36A Or/Wh Open Bad patch panel port or termination

36B B/Wh open Bad patch panel port or termination

44B Wh/Br open Bad patch panel port or termination

45B Cross Talk - Both Sides Poor Termination

65A Wh/B open Broken Jack/Pins/Termination

68B B/Wh open Bad patch panel port or termination

73B Or/Wh open Bad patch panel port or termination

79B Cross Talk - WAO Side Poor Termination

7A Wh/Gr open Broken Jack/Pins/Termination

80B Cross Talk - WAO Side Poor Termination

84B Wh/Br open Bad patch panel port or termination

85A Wh/Or open Bad patch panel port or termination

86A Wh/Or open Bad patch panel port or termination

91A B/Wh open Broken Jack/Pins/Termination

92A Cross Talk - WAO Side Poor Termination

94A Cross Talk - WAO Side Poor Termination

105A Gr/Wh Open Broken Jack/Pins/Termination

108B Cross Talk - WAO Side Poor Termination

111B Gr/Wh Open Broken Jack/Pins/Termination

117A Wh/Or open Broken Jack/Pins/Termination

119A Cross Talk - WAO Side Poor Termination

129A Cross Talk - WAO Side Poor Termination 134A Or/Gr pairs reversed Poor Termination

Results-Data Diagnosis Possible Cause

10A

Cross Talk - WAO Side

Poor Termination

16A Return Loss - IDF Side Poor Termination

21A Cross Talk - WAO Side Poor Termination

32A Cross Talk - IDF Side Poor Termination

41B Return Loss - IDF Side Poor Termination

95A Cross Talk - WAO Side Poor Termination 112A Cross Talk - IDF Side Poor Termination

159 a/b

1a/b

North/West Telecom Room

Old Old

RU 43

RU 42

RU 41

RU 40

RU 39

RU 38

RU 37

RU 36

RU 35

RU 34

RU 33

RU 32

RU 31

RU 30

RU 29

RU 28

RU 27

RU 26

RU 25

RU 24

RU 23

RU 22

RU 21

RU 20

RU 19

RU 18

RU 17

RU 16

RU 15

RU 14

RU 13

RU 12

RU 11

RU 10

RU 9

RU 8

RU 7

RU 6

RU 5

RU 4

RU 3

RU 2

Data Rack

RU 43

RU 42

RU 41

RU 40

RU 39

RU 38

RU 37

RU 36

RU 35

RU 34

RU 33

RU 32

RU 31

RU 30

RU 29

RU 28

RU 27

RU 26

RU 25

RU 24

RU 23

RU 22

RU 21

RU 20

RU 19

RU 18

RU 17

RU 16

RU 15

RU 14

RU 13

RU 12

RU 11

RU 10

RU 9

RU 8

RU 7

RU 6

RU 5

RU 4

RU 3

RU 2

Voice Rack

RU 43

RU 42

RU 41

RU 40

RU 39

RU 38

RU 37

RU 36

RU 35

RU 34

RU 33

RU 32

RU 31

RU 30

RU 29

RU 28

RU 27

RU 26

RU 25

RU 24

RU 23

RU 22

RU 21

RU 20

RU 19

RU 18

RU 17

RU 16

RU 15

RU 14

RU 13

RU 12

RU 11

RU 10

RU 9

RU 8

RU 7

RU 6

RU 5

RU 4

RU 3

RU 2

RU 1

Cabinet 2 Post Rack

RU 45

RU 44

RU 43

RU 42

RU 41

RU 40

RU 39

RU 38

RU 37

RU 36

RU 35

RU 34

RU 33

RU 32

RU 31

RU 30

RU 29

RU 28

RU 27

RU 26

RU 25

RU 24

RU 23

RU 22

RU 21

RU 20

RU 19

RU 18

RU 17

RU 16

RU 15

RU 14

RU 13

RU 12

RU 11

RU 10

RU 9

RU 8

RU 7

RU 6

RU 5

RU 4

RU 3

RU 2

1RU Switch

1RU Switch

1RU Switch

1RU Switch

1RU Switch

1RU Switch

1RU Switch

UPS

UPS

LIU 12 STSM/12 STMM

LIU 12 SCMM

1-192

Switch pairs old voice station cables

USMC Marsh Center - 2 West Telecom Room Patch Panel Reference

1 6 7 12 13 18 19

312 Total

2W-D 2W-D 2W-D 2W-D 2W-D 2W-D

037A 037B 038A 038B 039A 039B

No Test

Passed

Failed

001A 001B 002A 002B 003A 003B

004A 004B 005A 005B 006A 006B

007A 007B 008A 008B 009A 009B

013A 013B 014A 014B 015A 015B

016A 016B 017A 017B 018A 018B

019A 019B 020A 020B 021A 021B

010A 010B 011A 011B 012A 012B

279 Total

Tested

022A 022B 023A 023B 024A 024B

025A 025B 026A 026B 027A 027B

028A 028B 029A 029B 030A 030B

031A 031B 032A 032B 033A 033B

034A 034B 035A 035B 036A 036B

040A 040B 041A 041B 042A 042B

043A 043B 044A 044B 045A 045B

046A 046B 047A 047B 048A 048B

Panel 4

Panel 5

Panel 6

Panel 7

24 24

049A 049B 050A 050B 051A 051B

052A 052B 053A 053B 054A 054B

055A 055B 056A 056B 057A 057B

058A 058B 059A 059B 060A 060B

061A 061B 062A 062B 063A 063B

064A 064B 065A 065B 066A 066B

067A 067B 068A 068B 069A 069B

070A 070B 071A 071B 072A 072B

073A 073B 074A 074B 075A 075B

076A 076B 077A 077B 078A 078B

079A 079B 080A 080B 081A 081B

082A 082B 083A 083B 084A 084B

085A 085B 086A 086B 087A 087B

088A 088B 089A 089B 090A 090B

091A 091B 092A 092B 093A 093B

094A 094B 095A 095B 096A 096B

097A 097B 098A 098B 099A 099B

100A 100B 101A 101B 102A 102B

103A 103B 104A 104B 105A 105B

106A 106B 107A 107B 108A 108B

109A 109B 110A 110B 111A 111B

112A 112B 113A 113B 114A 114B

115A 115B 116A 116B 117A 117B

118A 118B 119A 119B 120A 120B

121A 121B 122A 122B 123A 123B

124A 124B 125A 125B 126A 126B

127A 127B 128A 128B 129A 129B

130A 130B 131A 131B 132A 132B

133A 133B 134A 134B 135A 135B

136A 136B 137A 137B 138A 138B

139A 139B 140A 140B 141A 141B

142A 142B 143A 143B 144A 144B

145A 145B 146A 146B 147A 147B

148A 148B 149A 149B 150A 150B

151A 151B 152A 152B 153A 153B

154A 154B 155A 155B 156A 156B

1 6 7 12

13 18

19 24

156 Total

2W-V 2W-V 2W-V 2W-V 2W-V 2W-V

049 050 051 052 053 054

142 Total

Tested

001 002 003 004 005 006

007 008 009 010 011 012

055 056 057 058 059 060

6 7

12 13

18 19

30 31

36 37

42 43

013 014 015 016 017 018

025 026 027 028 029 030

031 032 033 034 035 036

037 038 039 040 041 042

061 062 063 064 065 066

019 020 021 022 023 024

043 044 045 046 047 048

067 068 069 070 071 072

073 074 075 076 077 078

079 080 081 082 083 084

085 086 087 088 089 090

091 092 093 094 095 096

097 098 099 100 101 102

103 104 105 106 107 108

109 110 111 112 113 114

115 116 117 118 119 120

121 122 123 124 125 126

127 128 129 130 131 132

133 134 135 136 137 138

139 140 141 142 143 144

145 146 147 148 149 150

151 152 153 154 155 156

West/North Side of Bldg Outlet Notes Notes

1 A&B are reversed

9 Biscuit not mounted

10 Biscuit not mounted

12 Biscuit not mounted B Data Missing

13 Biscuit not mounted

17 Biscuit not mounted

19 Biscuit not mounted

21 Biscuit not mounted

23 Biscuit not mounted

24 Data Cables Missing

29 Biscuit not mounted

33 Biscuit not mounted Data Cables Missing

43 Biscuit not mounted

44 Biscuit not mounted

45 Biscuit not mounted Jack loose

46 Biscuit not mounted

54 Jacks loose

58 No biscuit, no label

59 Biscuit not mounted

61 Biscuit not mounted

64 B data is a white jack

65 A&B are reversed

66 A&B are reversed

67 A&B are reversed B Cable is missing

68 A&B are reversed

69 A & B are reversed

70 A & B are reversed

71 Voice and B Data are reversed

72 A & B are reversed

78 Not Labeled

86 Not Labeled

96 Behind Furniture

99 Biscuit not mounted

100 Biscuit not mounted

101 Biscuit not mounted

103 Biscuit not mounted

104 Biscuit not mounted

106 Biscuit not mounted Jacks loose

107 Biscuit not mounted Jacks loose

109 Biscuit not mounted

111 Cables are cut Voice cables missing

111 A&B are reversed Jacks loose

117 Biscuit not mounted

119 No biscuit B Jack Broken

120 Biscuit not mounted

125 Biscuit not mounted

126 Biscuit not mounted

132 No biscuit, no label

133 No biscuit, no label

139 Biscuit not mounted

140 Jacks loose

141 Biscuit not mounted

142 Biscuit not mounted

143 Biscuit not mounted

148 Broken Biscuit Behind Furniture

Voice Diagnosis Possible Cause

1 Wh/Or, Br/Wh open Broken Jack/Pins/Termination

8 Return Loss - Both ends Poor Termination

9 Wh/Or, Br/Wh open Broken Jack/Pins/Termination

10 Wh/Or, Br/Wh open Broken Jack/Pins/Termination

11 Wh/Or, Br/Wh open Broken Jack/Pins/Termination

13 Wh/Or, Or/Wh, Br/Wh open. Or/Wh, Wh/Gr Shorted Broken Jack/Pins/Termination. Poor termination at patch panel

15 Wh/Or open Broken Jack/Pins/Termination

16 Wh/Or, Br/Wh open Broken Jack/Pins/Termination

20 Wh/Or open Broken Jack/Pins/Termination

22 Wh/Or open Broken Jack/Pins/Termination

23 Wh/Or, Wh/Gr, Br/Wh open Broken Jack/Pins/Termination. Bad patch panel port or termination

24 Wh/Or, Or/Wh open Broken Jack/Pins/Termination. Bad patch panel port or termination

27 Wh/Or, Br/Wh open Broken Jack/Pins/Termination

29 Br/Wh open Broken Jack/Pins/Termination

31 Wh/Or, Br/Wh open Broken Jack/Pins/Termination

33 Or/Gr pairs reversed Poor Termination

40 Cross Talk - WAO Side Poor Termination

41 Wh/Or open Broken Jack/Pins/Termination

42 Wh/Br open Bad patch panel port or termination

45 Wh/Or, Br/Wh open Broken Jack/Pins/Termination

54 Wh/Or, Br/Wh open Broken Jack/Pins/Termination

55 Wh/Or, Br/Wh open Broken Jack/Pins/Termination

56 Wh/Or, Br/Wh open Broken Jack/Pins/Termination

57 Gr/Br pairs reversed Poor Termination

59 Wh/B, B/Wh, Wh/Gr, Gr/Wh open Broken Jack/Pins/Termination

60 Gr/Wh open Broken Jack/Pins/Termination

62 Wh/Or open Broken Jack/Pins/Termination

68 Wh/Or, Br/Wh open Broken Jack/Pins/Termination

70 Wh/Or, Br/Wh open Broken Jack/Pins/Termination

71 Br/Wh open Broken Jack/Pins/Termination

72 Wh/Or open Broken Jack/Pins/Termination

77 Cross Talk - WAO Side Poor Termination

99 Wh/Or open Broken Jack/Pins/Termination

103 Wh/Or open Broken Jack/Pins/Termination

105 Wh/Or open Broken Jack/Pins/Termination

109 Wh/Or open Broken Jack/Pins/Termination

110 Cross Talk - WAO Side Poor Termination

114 Wh/Or, Br/Wh open Broken Jack/Pins/Termination

118 Wh/Or open Broken Jack/Pins/Termination

119 Wh/Gr open Broken Jack/Pins/Termination

120 Wh/B open Broken Jack/Pins/Termination

123 Wh/Or open Broken Jack/Pins/Termination

124 Wh/Or open Broken Jack/Pins/Termination

126 Wh/Or, Br/Wh open Broken Jack/Pins/Termination

127 Wh/Or open Broken Jack/Pins/Termination 145 Br/Wh open Broken Jack/Pins/Termination

Marginal Results-Voice Diagnosis Possible Cause

19 Cross Talk - WAO Side Poor Termination

81 Cross Talk - WAO Side Poor Termination 91 Cross Talk - WAO Side Poor Termination

Data Diagnosis Possible Cause

1A Gr/Wh open Broken Jack/Pins/Termination

5B Cross Talk - WAO Side Poor Termination

9A B/Wh, Wh/Br open Broken Jack/Pins/Termination

25B Wh/B, B/Wh open Bad patch panel port or termination

26B Br/Wh open Bad patch panel port or termination

27B Green Pair Open at jack, Shorted at Patch Panel Broken Jack/Pins/Termination. Bad patch panel port or termination

36A Wh/Gr open Broken Jack/Pins/Termination

37B Or/Wh open Bad patch panel port or termination

42A Cross Talk - WAO Side Poor Termination

45A Cross Talk - WAO Side Poor Termination

47B Cross Talk - WAO Side Poor Termination

51B Gr/Wh open Bad patch panel port or termination

53A Wh/Or open Bad patch panel port or termination

54B Gr/Wh open Bad patch panel port or termination

57A Wh/B open, Green Pair crossed Broken Jack/Pins/Termination

57B Wh/B, B/Wh, Wh/Or open. Green Pair Crossed Broken Jack/Pins/Termination

58A Wh/Gr, Gr/Wh open Broken Jack/Pins/Termination

58B Wh/Or, Or/Wh open Bad patch panel port or termination

59A Wh/B, Wh/Gr open Broken Jack/Pins/Termination

59B Wh/B, Gr/Wh open Broken Jack/Pins/Termination

62B Wh/Gr, Gr/Wh open. Brown Pair Crossed Broken Jack/Pins/Termination

67A Blue and Brown Pairs Shorted Poor Termination

68A Cross Talk - WAO Side Poor Termination

68B Wh/Or, Or/Wh, Wh/Gr, Gr/Wh open Bad patch panel port or termination

69B Gr/Wh open Bad patch panel port or termination

72B Or/Wh, Wh/Gr open Bad patch panel port or termination

73A Wh/Or open Bad patch panel port or termination

73B Or/Wh open Bad patch panel port or termination

76B Wh/Gr open Broken Jack/Pins/Termination

78A Cross Talk - WAO Side Poor Termination

82B Wh/B open Broken Jack/Pins/Termination

97B Wh/Gr open Bad patch panel port or termination

98B Or/Wh open Bad patch panel port or termination

100A Wh/B, B/Wh open Broken Jack/Pins/Termination

106B Wh/B, Wh/Gr open Broken Jack/Pins/Termination

110B Cross Talk - WAO Side Poor Termination

118A Cross Talk - TR Side Poor Termination

120B B/Wh, Wh/Gr open Broken Jack/Pins/Termination 122A Cross Talk - WAO Side Poor Termination

Marginal Results-Data Diagnosis Possible Cause

13B Return Loss - IDF Side Poor Termination 80B Cross Talk - IDF Side Poor Termination

Telecom Room Notes

East

Temperature at center of room - 5' AFF

78.4 degrees Fahrenheit

Dimensions

10'11" x 9'11"

(2) 2-post racks with new Voice/Data Patch Panels

Neither rack is bolted down

Neither rack is bonded to ground

Newly installed ladder rack is not bonded to ground

Overhead cable tray does not support the new cable (blue)

Excessive slack hanging behind the patch panels on both racks

Cables are not labeled behind the panels with machine printed labels

Neither rack has sufficient vertical management for station cabling - rear, or patch cabling - front

UPS devices are sitting on the floor. Power cables are loose across the floor.

Telecom door is not secure

All existing white cable enters the room from floor trough.

(1) existing enclosed cabinet housing old data panels and fiber optic LIUs

(1) APC device and (1) 1ru switch.

This switch may be the connectivity for wireless access points

(1) existing/old 2-post rack.

This rack contains patch panels with single pair connectivity - most like old telephone switch ties

This rack also contains old voice station cable patch panels.

There are excessively long patch cables between the switch tie panel and the new voice panels

No cable management or support for these cables.

There is a considerable amount of trash/debris/abandoned equipment on the floor.

Telecom Room Recommendations.

Perform a phone switch audit to determined if there are any active analog lines still in use.

If there are no active switch ports, recommend removing all patch cables and the old rack and panels

Cut all old white cable back to the floor trough/entry to the telecom room if feasible

Determine where the wireless access point cable are terminated and migrate them to the new 2-post data

Migrate Fiber Optic LIUs from the enclosed cabinet to the new 2-post rack if there is sufficient slack in the

Migrate active equipment from the enclosed cabinet to the new 2-post rack.

Remove all old data cabling from the cabinet and cut back to the floor trough/entry to the telecom room if

Remove the old cabinet and 2-post rack from the room.

Add cable tray over top the new 2-post data rack to properly support the cable slack.

Redress/support all blue cabling - new voice and data.

Telecom Room Notes

West

Temperature at center of room - 5' AFF

78 degrees Fahrenheit

Dimensions

9'0" x 10'0"

(2) 2-post racks with new Voice/Data Patch Panels

Overhead cable tray does not support the new cable (blue)

Excessive slack hanging behind the patch panels on both racks

Cables are not labeled behind the panels with machine printed labels

Neither rack has sufficient vertical management for station cabling - rear, or patch cabling - front

UPS devices are sitting on the floor. Power cables are loose across the floor.

Telecom door is not secure

All existing white cable enters the room from floor trough.

(1) existing enclosed cabinet housing old data panels and fiber optic LIUs

(1) existing/old 2-post rack.

This rack contains patch panels with single pair connectivity - most like old telephone switch ties

This rack also contains old voice station cable patch panels.

There are excessively long patch cables between the switch tie panel and the new voice panels

No cable management or support for these cables.

There is a considerable amount of trash/debris/abandoned equipment on the floor.

Telecom Room Recommendations.

Perform a phone switch audit to determined if there are any active analog lines still in use.

If there are no active switch ports, recommend removing all patch cables and the old rack and panels

Cut all old white cable back to the floor trough/entry to the telecom room if feasible

Determine where the wireless access point cable are terminated and migrate them to the new 2-post data rack.

Migrate Fiber Optic LIUs from the enclosed cabinet to the new 2-post rack if there is sufficient slack in the cable.

Migrate active equipment from the enclosed cabinet to the new 2-post rack.

Remove all old data cabling from the cabinet and cut back to the floor trough/entry to the telecom room if feasible

Remove the old cabinet and 2-post rack from the room.

Add cable tray over top the new 2-post data rack to properly support the cable slack.

Redress/support all blue cabling - new voice and data.

Cable ID/ Test ID Summary Test Limit Length Headroom Date / Time 2E-D-001A PASS TIA Cat 6 Perm. Link 236 ft 2.0 dB (NEXT) 07/07/2026 10:58 AM 2E-D-001B PASS TIA Cat 6 Perm. Link 236 ft 4.5 dB (NEXT) 07/07/2026 10:59 AM 2E-D-002A PASS TIA Cat 6 Perm. Link 231 ft 4.2 dB (NEXT) 07/07/2026 10:38 AM 2E-D-002B PASS TIA Cat 6 Perm. Link 231 ft 3.7 dB (NEXT) 07/07/2026 10:38 AM 2E-D-003A PASS TIA Cat 6 Perm. Link 219 ft 8.2 dB (NEXT) 07/07/2026 02:48 PM 2E-D-003B PASS TIA Cat 6 Perm. Link 219 ft 2.3 dB (NEXT) 07/07/2026 02:49 PM 2E-D-005A PASS TIA Cat 6 Perm. Link 224 ft 4.0 dB (NEXT) 07/07/2026 10:43 AM 2E-D-005B PASS TIA Cat 6 Perm. Link 224 ft 6.6 dB (NEXT) 07/07/2026 10:45 AM 2E-D-006A PASS TIA Cat 6 Perm. Link 231 ft 7.8 dB (NEXT) 07/07/2026 10:47 AM 2E-D-006B PASS TIA Cat 6 Perm. Link 231 ft 2.4 dB (NEXT) 07/07/2026 10:48 AM 2E-D-007A FAIL TIA Cat 6 Perm. Link 236 ft N/A 07/07/2026 10:49 AM 2E-D-007B PASS TIA Cat 6 Perm. Link 236 ft 7.7 dB (NEXT) 07/07/2026 10:51 AM 2E-D-008A PASS TIA Cat 6 Perm. Link 207 ft 4.1 dB (NEXT) 07/07/2026 02:55 PM 2E-D-008B PASS TIA Cat 6 Perm. Link 208 ft 7.1 dB (NEXT) 07/07/2026 02:56 PM 2E-D-009A PASS TIA Cat 6 Perm. Link 204 ft 7.2 dB (NEXT) 07/07/2026 02:11 PM 2E-D-009B PASS TIA Cat 6 Perm. Link 204 ft 5.0 dB (NEXT) 07/07/2026 02:11 PM 2E-D-010A PASS* TIA Cat 6 Perm. Link 204 ft 1.0 dB (NEXT) 07/07/2026 02:13 PM 2E-D-010B FAIL TIA Cat 6 Perm. Link 0 ft N/A 07/07/2026 02:15 PM 2E-D-011A PASS TIA Cat 6 Perm. Link 198 ft 3.8 dB (NEXT) 07/07/2026 02:20 PM 2E-D-011B FAIL TIA Cat 6 Perm. Link 0 ft N/A 07/07/2026 02:22 PM 2E-D-012A FAIL TIA Cat 6 Perm. Link 0 ft N/A 07/07/2026 02:02 PM 2E-D-012B FAIL TIA Cat 6 Perm. Link 0 ft N/A 07/07/2026 02:03 PM 2E-D-013A PASS TIA Cat 6 Perm. Link 210 ft 1.7 dB (NEXT) 07/07/2026 11:01 AM 2E-D-013B PASS TIA Cat 6 Perm. Link 211 ft 5.2 dB (NEXT) 07/07/2026 11:02 AM 2E-D-014A PASS TIA Cat 6 Perm. Link 214 ft 4.9 dB (NEXT) 07/07/2026 10:39 AM 2E-D-014B PASS TIA Cat 6 Perm. Link 214 ft 6.2 dB (NEXT) 07/07/2026 10:40 AM 2E-D-015A PASS TIA Cat 6 Perm. Link 204 ft 4.8 dB (NEXT) 07/07/2026 02:36 PM 2E-D-015B PASS TIA Cat 6 Perm. Link 204 ft 5.9 dB (NEXT) 07/07/2026 02:37 PM 2E-D-016A PASS* TIA Cat 6 Perm. Link 199 ft 1.1 dB (NEXT) 07/07/2026 02:29 PM 2E-D-016B PASS TIA Cat 6 Perm. Link 200 ft 3.9 dB (NEXT) 07/07/2026 02:30 PM 2E-D-017A PASS TIA Cat 6 Perm. Link 204 ft 4.4 dB (NEXT) 07/07/2026 02:32 PM 2E-D-017B PASS TIA Cat 6 Perm. Link 204 ft 2.0 dB (NEXT) 07/07/2026 02:33 PM 2E-D-018A FAIL TIA Cat 6 Perm. Link 0 ft N/A 07/07/2026 01:48 PM 2E-D-018B PASS TIA Cat 6 Perm. Link 199 ft 6.6 dB (NEXT) 07/07/2026 01:48 PM 2E-D-019A PASS TIA Cat 6 Perm. Link 204 ft 6.1 dB (NEXT) 07/07/2026 01:55 PM 2E-D-019B PASS TIA Cat 6 Perm. Link 205 ft 6.3 dB (NEXT) 07/07/2026 01:56 PM 2E-D-020A PASS TIA Cat 6 Perm. Link 194 ft 2.9 dB (NEXT) 07/07/2026 01:50 PM 2E-D-020B FAIL TIA Cat 6 Perm. Link 0 ft N/A 07/07/2026 01:52 PM 2E-D-021A PASS* TIA Cat 6 Perm. Link 187 ft 0.4 dB (NEXT) 07/07/2026 01:44 PM 2E-D-021B PASS TIA Cat 6 Perm. Link 188 ft 2.0 dB (NEXT) 07/07/2026 01:45 PM 2E-D-022A FAIL TIA Cat 6 Perm. Link 1 ft N/A 07/07/2026 02:26 PM 2E-D-022B PASS TIA Cat 6 Perm. Link 187 ft 4.2 dB (NEXT) 07/07/2026 02:27 PM 2E-D-023A PASS TIA Cat 6 Perm. Link 193 ft 2.8 dB (NEXT) 07/07/2026 02:05 PM 2E-D-023B PASS TIA Cat 6 Perm. Link 192 ft 7.8 dB (NEXT) 07/07/2026 02:06 PM 2E-D-024A PASS TIA Cat 6 Perm. Link 189 ft 3.5 dB (NEXT) 07/07/2026 02:17 PM 2E-D-024B FAIL TIA Cat 6 Perm. Link 0 ft N/A 07/07/2026 02:18 PM 2E-D-025A PASS TIA Cat 6 Perm. Link 196 ft 4.6 dB (NEXT) 07/07/2026 02:08 PM 2E-D-025B PASS TIA Cat 6 Perm. Link 196 ft 4.1 dB (NEXT) 07/07/2026 02:09 PM 2E-D-026A PASS TIA Cat 6 Perm. Link 196 ft 3.3 dB (NEXT) 07/07/2026 01:32 PM 2E-D-026B PASS TIA Cat 6 Perm. Link 196 ft 5.6 dB (NEXT) 07/07/2026 01:33 PM 2E-D-027A FAIL TIA Cat 6 Perm. Link 0 ft N/A 07/07/2026 01:36 PM 2E-D-027B FAIL TIA Cat 6 Perm. Link 0 ft N/A 07/07/2026 01:38 PM 2E-D-028A PASS TIA Cat 6 Perm. Link 194 ft 5.7 dB (NEXT) 07/07/2026 01:20 PM 2E-D-028B PASS TIA Cat 6 Perm. Link 194 ft 7.2 dB (NEXT) 07/07/2026 01:21 PM 2E-D-029A PASS TIA Cat 6 Perm. Link 187 ft 4.6 dB (NEXT) 07/07/2026 01:17 PM 2E-D-029B PASS TIA Cat 6 Perm. Link 187 ft 4.3 dB (NEXT) 07/07/2026 01:17 PM 2E-D-030A PASS TIA Cat 6 Perm. Link 168 ft 2.0 dB (NEXT) 07/07/2026 01:40 PM 2E-D-030B PASS TIA Cat 6 Perm. Link 167 ft 4.0 dB (NEXT) 07/07/2026 01:41 PM 2E-D-031A PASS TIA Cat 6 Perm. Link 174 ft 5.3 dB (NEXT) 07/07/2026 01:23 PM 2E-D-031B PASS TIA Cat 6 Perm. Link 174 ft 8.7 dB (NEXT) 07/07/2026 01:23 PM 2E-D-032A PASS* TIA Cat 6 Perm. Link 180 ft 0.3 dB (NEXT) 07/07/2026 01:26 PM 2E-D-032B PASS TIA Cat 6 Perm. Link 179 ft 6.9 dB (NEXT) 07/07/2026 01:27 PM 2E-D-033A FAIL TIA Cat 6 Perm. Link 1 ft N/A 07/07/2026 01:29 PM 2E-D-033B PASS TIA Cat 6 Perm. Link 185 ft 2.7 dB (NEXT) 07/07/2026 01:30 PM 2E-D-034A FAIL TIA Cat 6 Perm. Link 176 ft 3.1 dB (NEXT) 07/07/2026 12:41 PM 2E-D-034B FAIL TIA Cat 6 Perm. Link 0 ft N/A 07/07/2026 12:42 PM 2E-D-035A PASS TIA Cat 6 Perm. Link 169 ft 5.0 dB (NEXT) 07/07/2026 12:44 PM 2E-D-035B FAIL TIA Cat 6 Perm. Link 0 ft N/A 07/07/2026 12:45 PM 2E-D-036A FAIL TIA Cat 6 Perm. Link 0 ft N/A 07/07/2026 12:50 PM 2E-D-036B FAIL TIA Cat 6 Perm. Link 1 ft N/A 07/07/2026 12:50 PM 2E-D-037A PASS TIA Cat 6 Perm. Link 162 ft 3.0 dB (NEXT) 07/07/2026 12:47 PM 2E-D-037B PASS TIA Cat 6 Perm. Link 161 ft 6.6 dB (NEXT) 07/07/2026 12:47 PM 2E-D-038A PASS TIA Cat 6 Perm. Link 149 ft 6.9 dB (NEXT) 07/07/2026 12:37 PM 2E-D-038B PASS TIA Cat 6 Perm. Link 149 ft 3.7 dB (NEXT) 07/07/2026 12:37 PM 2E-D-039A PASS TIA Cat 6 Perm. Link 157 ft 6.5 dB (NEXT) 07/08/2026 09:48 AM 2E-D-039B PASS TIA Cat 6 Perm. Link 157 ft 6.5 dB (NEXT) 07/08/2026 09:49 AM 2E-D-041A PASS TIA Cat 6 Perm. Link 190 ft 3.9 dB (NEXT) 07/07/2026 01:13 PM

2E-D-041B PASS* TIA Cat 6 Perm. Link 191 ft 3.9 dB (NEXT) 07/07/2026 01:15 PM

07/10/2026 02:48:19 PM Page 1 USMC Marsh Building Test Results.flw

2E-D-042A PASS TIA Cat 6 Perm. Link 187 ft 4.5 dB (NEXT) 07/07/2026 01:10 PM 2E-D-042B PASS TIA Cat 6 Perm. Link 187 ft 3.9 dB (NEXT) 07/07/2026 01:11 PM 2E-D-043A PASS TIA Cat 6 Perm. Link 162 ft 5.8 dB (NEXT) 07/07/2026 02:58 PM 2E-D-043B PASS TIA Cat 6 Perm. Link 161 ft 1.9 dB (NEXT) 07/07/2026 02:59 PM 2E-D-044A PASS TIA Cat 6 Perm. Link 146 ft 5.9 dB (NEXT) 07/07/2026 10:05 AM 2E-D-044B FAIL TIA Cat 6 Perm. Link 0 ft N/A 07/07/2026 10:06 AM 2E-D-045A PASS TIA Cat 6 Perm. Link 137 ft 1.1 dB (NEXT) 07/07/2026 09:58 AM 2E-D-045B FAIL TIA Cat 6 Perm. Link 1 ft -1.3 dB (NEXT) 07/07/2026 10:00 AM 2E-D-048A PASS TIA Cat 6 Perm. Link 169 ft 3.2 dB (NEXT) 07/07/2026 12:33 PM 2E-D-048B PASS TIA Cat 6 Perm. Link 169 ft 5.7 dB (NEXT) 07/07/2026 12:33 PM 2E-D-049A PASS TIA Cat 6 Perm. Link 172 ft 3.3 dB (NEXT) 07/07/2026 12:29 PM 2E-D-049B PASS TIA Cat 6 Perm. Link 172 ft 7.6 dB (NEXT) 07/07/2026 12:30 PM 2E-D-050A PASS TIA Cat 6 Perm. Link 151 ft 3.0 dB (NEXT) 07/07/2026 12:26 PM 2E-D-050B PASS TIA Cat 6 Perm. Link 151 ft 4.5 dB (NEXT) 07/07/2026 12:27 PM 2E-D-051A PASS TIA Cat 6 Perm. Link 157 ft 6.0 dB (NEXT) 07/07/2026 12:24 PM 2E-D-051B PASS TIA Cat 6 Perm. Link 157 ft 5.8 dB (NEXT) 07/07/2026 12:25 PM 2E-D-052A PASS TIA Cat 6 Perm. Link 157 ft 5.9 dB (NEXT) 07/07/2026 12:21 PM 2E-D-052B PASS TIA Cat 6 Perm. Link 158 ft 7.9 dB (NEXT) 07/07/2026 12:22 PM 2E-D-053A PASS TIA Cat 6 Perm. Link 165 ft 4.8 dB (NEXT) 07/07/2026 12:52 PM 2E-D-053B PASS TIA Cat 6 Perm. Link 165 ft 7.9 dB (NEXT) 07/07/2026 12:53 PM 2E-D-054A PASS TIA Cat 6 Perm. Link 173 ft 5.3 dB (NEXT) 07/07/2026 12:55 PM 2E-D-054B PASS TIA Cat 6 Perm. Link 173 ft 3.6 dB (NEXT) 07/07/2026 12:56 PM 2E-D-055A PASS TIA Cat 6 Perm. Link 172 ft 4.1 dB (NEXT) 07/07/2026 12:57 PM 2E-D-055B PASS TIA Cat 6 Perm. Link 172 ft 4.4 dB (NEXT) 07/07/2026 12:58 PM 2E-D-056A PASS TIA Cat 6 Perm. Link 152 ft 2.6 dB (NEXT) 07/07/2026 01:00 PM 2E-D-056B PASS TIA Cat 6 Perm. Link 152 ft 6.9 dB (NEXT) 07/07/2026 01:00 PM 2E-D-057A PASS TIA Cat 6 Perm. Link 158 ft 6.7 dB (NEXT) 07/07/2026 01:03 PM 2E-D-057B PASS TIA Cat 6 Perm. Link 158 ft 7.5 dB (NEXT) 07/07/2026 01:03 PM 2E-D-058A PASS TIA Cat 6 Perm. Link 159 ft 5.8 dB (NEXT) 07/07/2026 01:06 PM 2E-D-058B PASS TIA Cat 6 Perm. Link 159 ft 3.7 dB (NEXT) 07/07/2026 01:07 PM 2E-D-059A PASS TIA Cat 6 Perm. Link 144 ft 7.1 dB (NEXT) 07/07/2026 09:49 AM 2E-D-059B PASS TIA Cat 6 Perm. Link 147 ft 4.9 dB (NEXT) 07/07/2026 09:50 AM 2E-D-060A PASS TIA Cat 6 Perm. Link 139 ft 4.5 dB (NEXT) 07/07/2026 09:52 AM 2E-D-060B PASS TIA Cat 6 Perm. Link 139 ft 8.2 dB (NEXT) 07/07/2026 09:53 AM 2E-D-061A PASS TIA Cat 6 Perm. Link 135 ft 7.0 dB (NEXT) 07/07/2026 09:55 AM 2E-D-061B PASS TIA Cat 6 Perm. Link 133 ft 1.2 dB (NEXT) 07/07/2026 09:56 AM 2E-D-062A PASS TIA Cat 6 Perm. Link 139 ft 4.3 dB (NEXT) 07/07/2026 09:45 AM 2E-D-062B PASS TIA Cat 6 Perm. Link 138 ft 5.0 dB (NEXT) 07/07/2026 09:46 AM 2E-D-063A PASS TIA Cat 6 Perm. Link 132 ft 5.7 dB (NEXT) 07/07/2026 09:41 AM 2E-D-063B PASS TIA Cat 6 Perm. Link 130 ft 3.2 dB (NEXT) 07/07/2026 09:42 AM 2E-D-064A PASS TIA Cat 6 Perm. Link 125 ft 3.2 dB (NEXT) 07/07/2026 09:38 AM 2E-D-064B PASS TIA Cat 6 Perm. Link 125 ft 6.9 dB (NEXT) 07/07/2026 09:39 AM 2E-D-065A FAIL TIA Cat 6 Perm. Link 124 ft N/A 07/07/2026 09:33 AM 2E-D-065B PASS TIA Cat 6 Perm. Link 124 ft 2.9 dB (NEXT) 07/07/2026 09:34 AM 2E-D-066A PASS TIA Cat 6 Perm. Link 131 ft 6.3 dB (NEXT) 07/07/2026 09:29 AM 2E-D-066B PASS TIA Cat 6 Perm. Link 130 ft 6.2 dB (NEXT) 07/07/2026 09:30 AM 2E-D-067A PASS TIA Cat 6 Perm. Link 138 ft 6.4 dB (NEXT) 07/07/2026 09:26 AM 2E-D-067B PASS TIA Cat 6 Perm. Link 138 ft 4.5 dB (NEXT) 07/07/2026 09:27 AM 2E-D-068A PASS TIA Cat 6 Perm. Link 118 ft 6.3 dB (NEXT) 07/07/2026 09:22 AM 2E-D-068B FAIL TIA Cat 6 Perm. Link 1 ft N/A 07/07/2026 09:23 AM 2E-D-069A PASS TIA Cat 6 Perm. Link 112 ft 5.5 dB (NEXT) 07/07/2026 09:20 AM 2E-D-069B PASS TIA Cat 6 Perm. Link 112 ft 3.7 dB (NEXT) 07/07/2026 09:20 AM 2E-D-070A PASS TIA Cat 6 Perm. Link 104 ft 7.2 dB (NEXT) 07/07/2026 09:17 AM 2E-D-070B PASS TIA Cat 6 Perm. Link 105 ft 6.3 dB (NEXT) 07/07/2026 09:18 AM 2E-D-071A PASS TIA Cat 6 Perm. Link 113 ft 5.3 dB (NEXT) 07/07/2026 09:12 AM 2E-D-071B PASS TIA Cat 6 Perm. Link 114 ft 4.1 dB (NEXT) 07/07/2026 09:12 AM 2E-D-072A PASS TIA Cat 6 Perm. Link 123 ft 2.7 dB (NEXT) 07/07/2026 09:09 AM 2E-D-072B PASS TIA Cat 6 Perm. Link 123 ft 4.0 dB (NEXT) 07/07/2026 09:09 AM 2E-D-073A PASS TIA Cat 6 Perm. Link 105 ft 6.5 dB (NEXT) 07/07/2026 08:59 AM 2E-D-073B FAIL TIA Cat 6 Perm. Link 0 ft N/A 07/07/2026 09:00 AM 2E-D-074A PASS TIA Cat 6 Perm. Link 107 ft 8.6 dB (NEXT) 07/07/2026 08:56 AM 2E-D-074B PASS TIA Cat 6 Perm. Link 107 ft 5.6 dB (NEXT) 07/07/2026 08:57 AM 2E-D-076A PASS TIA Cat 6 Perm. Link 113 ft 6.6 dB (NEXT) 07/07/2026 12:13 PM 2E-D-076B PASS TIA Cat 6 Perm. Link 112 ft 7.2 dB (NEXT) 07/07/2026 12:15 PM 2E-D-077A PASS TIA Cat 6 Perm. Link 109 ft 6.8 dB (NEXT) 07/07/2026 12:10 PM 2E-D-077B PASS TIA Cat 6 Perm. Link 103 ft 4.9 dB (NEXT) 07/07/2026 12:11 PM 2E-D-078A PASS TIA Cat 6 Perm. Link 100 ft 4.9 dB (NEXT) 07/07/2026 12:07 PM 2E-D-078B PASS TIA Cat 6 Perm. Link 102 ft 6.5 dB (NEXT) 07/07/2026 12:07 PM 2E-D-079A PASS TIA Cat 6 Perm. Link 94 ft 5.7 dB (NEXT) 07/07/2026 10:25 AM 2E-D-079B FAIL TIA Cat 6 Perm. Link 92 ft -3.0 dB (NEXT) 07/07/2026 10:27 AM 2E-D-080A PASS TIA Cat 6 Perm. Link 104 ft 6.6 dB (NEXT) 07/07/2026 12:16 PM 2E-D-080B FAIL TIA Cat 6 Perm. Link 103 ft -0.6 dB (NEXT) 07/07/2026 12:18 PM 2E-D-081A PASS TIA Cat 6 Perm. Link 76 ft 4.0 dB (NEXT) 07/07/2026 08:26 AM 2E-D-081B PASS TIA Cat 6 Perm. Link 76 ft 1.1 dB (NEXT) 07/07/2026 08:29 AM 2E-D-082A PASS TIA Cat 6 Perm. Link 88 ft 5.8 dB (NEXT) 07/07/2026 08:32 AM 2E-D-082B PASS TIA Cat 6 Perm. Link 89 ft 5.7 dB (NEXT) 07/07/2026 08:34 AM 2E-D-083A PASS TIA Cat 6 Perm. Link 94 ft 3.5 dB (NEXT) 07/07/2026 08:36 AM

2E-D-083B PASS TIA Cat 6 Perm. Link 95 ft 2.6 dB (NEXT) 07/07/2026 08:36 AM

07/10/2026 02:48:19 PM Page 2

2E-D-084A PASS TIA Cat 6 Perm. Link 90 ft 5.6 dB (NEXT) 07/07/2026 08:40 AM 2E-D-084B FAIL TIA Cat 6 Perm. Link 0 ft N/A 07/07/2026 08:41 AM 2E-D-085A FAIL TIA Cat 6 Perm. Link 0 ft N/A 07/07/2026 08:45 AM 2E-D-085B PASS TIA Cat 6 Perm. Link 83 ft 5.0 dB (NEXT) 07/07/2026 08:45 AM 2E-D-086A FAIL TIA Cat 6 Perm. Link 0 ft N/A 07/07/2026 08:48 AM 2E-D-086B PASS TIA Cat 6 Perm. Link 76 ft 7.6 dB (NEXT) 07/07/2026 08:50 AM 2E-D-087A PASS TIA Cat 6 Perm. Link 142 ft 7.4 dB (NEXT) 07/09/2026 10:46 AM 2E-D-087B PASS TIA Cat 6 Perm. Link 142 ft 4.9 dB (NEXT) 07/09/2026 10:47 AM 2E-D-088A PASS TIA Cat 6 Perm. Link 142 ft 4.3 dB (NEXT) 07/09/2026 10:34 AM 2E-D-088B PASS TIA Cat 6 Perm. Link 143 ft 6.1 dB (NEXT) 07/09/2026 10:35 AM 2E-D-089A PASS TIA Cat 6 Perm. Link 142 ft 6.2 dB (NEXT) 07/09/2026 10:35 AM 2E-D-089B PASS TIA Cat 6 Perm. Link 142 ft 6.9 dB (NEXT) 07/09/2026 10:35 AM 2E-D-090A PASS TIA Cat 6 Perm. Link 142 ft 5.8 dB (NEXT) 07/09/2026 10:40 AM 2E-D-090B PASS TIA Cat 6 Perm. Link 142 ft 5.1 dB (NEXT) 07/09/2026 10:41 AM 2E-D-091A FAIL TIA Cat 6 Perm. Link 126 ft N/A 07/09/2026 10:29 AM 2E-D-091B PASS TIA Cat 6 Perm. Link 126 ft 6.9 dB (NEXT) 07/09/2026 10:29 AM 2E-D-092A FAIL TIA Cat 6 Perm. Link 125 ft -1.8 dB (NEXT) 07/09/2026 10:30 AM 2E-D-092B PASS TIA Cat 6 Perm. Link 126 ft 5.4 dB (NEXT) 07/09/2026 10:31 AM 2E-D-093A PASS TIA Cat 6 Perm. Link 127 ft 1.6 dB (NEXT) 07/09/2026 10:31 AM 2E-D-093B PASS TIA Cat 6 Perm. Link 127 ft 7.6 dB (NEXT) 07/09/2026 10:31 AM 2E-D-094A FAIL TIA Cat 6 Perm. Link 127 ft -0.9 dB (NEXT) 07/09/2026 10:32 AM 2E-D-094B PASS TIA Cat 6 Perm. Link 129 ft 3.2 dB (NEXT) 07/09/2026 10:32 AM 2E-D-095A PASS* TIA Cat 6 Perm. Link 128 ft 0.8 dB (NEXT) 07/09/2026 10:33 AM 2E-D-095B PASS TIA Cat 6 Perm. Link 127 ft 2.3 dB (NEXT) 07/09/2026 10:33 AM 2E-D-096A PASS TIA Cat 6 Perm. Link 127 ft 6.0 dB (NEXT) 07/09/2026 10:33 AM 2E-D-096B PASS TIA Cat 6 Perm. Link 128 ft 7.0 dB (NEXT) 07/09/2026 10:34 AM 2E-D-097A PASS TIA Cat 6 Perm. Link 113 ft 7.7 dB (NEXT) 07/09/2026 10:27 AM 2E-D-097B PASS TIA Cat 6 Perm. Link 114 ft 6.7 dB (NEXT) 07/09/2026 10:27 AM 2E-D-098A PASS TIA Cat 6 Perm. Link 114 ft 7.8 dB (NEXT) 07/09/2026 10:22 AM 2E-D-098B PASS TIA Cat 6 Perm. Link 114 ft 8.4 dB (NEXT) 07/09/2026 10:22 AM 2E-D-099A PASS TIA Cat 6 Perm. Link 114 ft 1.9 dB (NEXT) 07/09/2026 10:24 AM 2E-D-099B PASS TIA Cat 6 Perm. Link 113 ft 6.4 dB (NEXT) 07/09/2026 10:24 AM 2E-D-100A PASS TIA Cat 6 Perm. Link 112 ft 7.1 dB (NEXT) 07/09/2026 10:25 AM 2E-D-100B PASS TIA Cat 6 Perm. Link 112 ft 6.2 dB (NEXT) 07/09/2026 10:25 AM 2E-D-101A PASS TIA Cat 6 Perm. Link 112 ft 7.1 dB (NEXT) 07/09/2026 10:25 AM 2E-D-101B PASS TIA Cat 6 Perm. Link 113 ft 5.5 dB (NEXT) 07/09/2026 10:26 AM 2E-D-102A PASS TIA Cat 6 Perm. Link 112 ft 3.5 dB (NEXT) 07/09/2026 10:26 AM 2E-D-102B PASS TIA Cat 6 Perm. Link 112 ft 5.5 dB (NEXT) 07/09/2026 10:26 AM 2E-D-103A PASS TIA Cat 6 Perm. Link 126 ft 8.4 dB (NEXT) 07/09/2026 11:02 AM 2E-D-103B PASS TIA Cat 6 Perm. Link 127 ft 5.9 dB (NEXT) 07/09/2026 11:03 AM 2E-D-104A PASS TIA Cat 6 Perm. Link 155 ft 5.9 dB (NEXT) 07/09/2026 10:58 AM 2E-D-104B PASS TIA Cat 6 Perm. Link 154 ft 5.6 dB (NEXT) 07/09/2026 10:58 AM 2E-D-105A FAIL TIA Cat 6 Perm. Link 154 ft N/A 07/09/2026 10:53 AM 2E-D-105B PASS TIA Cat 6 Perm. Link 155 ft 5.2 dB (NEXT) 07/09/2026 10:55 AM 2E-D-106A PASS TIA Cat 6 Perm. Link 154 ft 6.1 dB (NEXT) 07/09/2026 10:55 AM 2E-D-106B PASS TIA Cat 6 Perm. Link 154 ft 4.9 dB (NEXT) 07/09/2026 10:54 AM 2E-D-107A PASS TIA Cat 6 Perm. Link 155 ft 2.9 dB (NEXT) 07/09/2026 10:55 AM 2E-D-107B PASS TIA Cat 6 Perm. Link 153 ft 7.9 dB (NEXT) 07/09/2026 10:56 AM 2E-D-108A PASS TIA Cat 6 Perm. Link 154 ft 4.0 dB (NEXT) 07/09/2026 10:56 AM 2E-D-108B FAIL TIA Cat 6 Perm. Link 154 ft -0.5 dB (NEXT) 07/09/2026 10:56 AM 2E-D-109A PASS TIA Cat 6 Perm. Link 154 ft 4.4 dB (NEXT) 07/09/2026 10:57 AM 2E-D-109B PASS TIA Cat 6 Perm. Link 154 ft 7.3 dB (NEXT) 07/09/2026 10:57 AM 2E-D-110A PASS TIA Cat 6 Perm. Link 140 ft 5.8 dB (NEXT) 07/09/2026 10:49 AM 2E-D-110B PASS TIA Cat 6 Perm. Link 140 ft 2.4 dB (NEXT) 07/09/2026 10:49 AM 2E-D-111A PASS TIA Cat 6 Perm. Link 142 ft 5.7 dB (NEXT) 07/09/2026 10:50 AM 2E-D-111B FAIL TIA Cat 6 Perm. Link 141 ft N/A 07/09/2026 10:51 AM 2E-D-112A PASS* TIA Cat 6 Perm. Link 132 ft 0.6 dB (NEXT) 07/10/2026 07:25 AM 2E-D-112B PASS TIA Cat 6 Perm. Link 132 ft 7.2 dB (NEXT) 07/10/2026 07:25 AM 2E-D-113B PASS TIA Cat 6 Perm. Link 133 ft 5.5 dB (NEXT) 07/10/2026 07:23 AM 2E-D-114A PASS TIA Cat 6 Perm. Link 132 ft 4.7 dB (NEXT) 07/10/2026 07:15 AM 2E-D-114B PASS TIA Cat 6 Perm. Link 132 ft 2.7 dB (NEXT) 07/10/2026 07:15 AM 2E-D-115A PASS TIA Cat 6 Perm. Link 154 ft 4.2 dB (NEXT) 07/10/2026 07:12 AM 2E-D-115B PASS TIA Cat 6 Perm. Link 152 ft 5.1 dB (NEXT) 07/10/2026 07:13 AM 2E-D-116A PASS TIA Cat 6 Perm. Link 150 ft 4.1 dB (NEXT) 07/10/2026 07:08 AM 2E-D-116B PASS TIA Cat 6 Perm. Link 152 ft 1.4 dB (NEXT) 07/10/2026 07:09 AM 2E-D-117A FAIL TIA Cat 6 Perm. Link 152 ft N/A 07/10/2026 07:06 AM 2E-D-117B PASS TIA Cat 6 Perm. Link 152 ft 5.5 dB (NEXT) 07/10/2026 07:06 AM 2E-D-118A PASS TIA Cat 6 Perm. Link 152 ft 2.7 dB (NEXT) 07/10/2026 07:05 AM 2E-D-118B PASS TIA Cat 6 Perm. Link 153 ft 5.2 dB (NEXT) 07/10/2026 07:04 AM 2E-D-119A FAIL TIA Cat 6 Perm. Link 160 ft -3.5 dB (NEXT) 07/08/2026 06:25 AM 2E-D-119B PASS TIA Cat 6 Perm. Link 159 ft 7.6 dB (NEXT) 07/08/2026 06:26 AM 2E-D-120A PASS TIA Cat 6 Perm. Link 166 ft 5.3 dB (NEXT) 07/08/2026 06:46 AM 2E-D-120B PASS TIA Cat 6 Perm. Link 165 ft 4.7 dB (NEXT) 07/08/2026 06:47 AM 2E-D-121A PASS TIA Cat 6 Perm. Link 165 ft 3.9 dB (NEXT) 07/08/2026 09:55 AM 2E-D-121B PASS TIA Cat 6 Perm. Link 165 ft 6.3 dB (NEXT) 07/08/2026 09:56 AM 2E-D-123A PASS TIA Cat 6 Perm. Link 120 ft 2.3 dB (NEXT) 07/10/2026 05:59 AM 2E-D-123B PASS TIA Cat 6 Perm. Link 119 ft 6.8 dB (NEXT) 07/10/2026 05:59 AM

2E-D-124A PASS TIA Cat 6 Perm. Link 120 ft 5.9 dB (NEXT) 07/10/2026 06:05 AM

07/10/2026 02:48:19 PM Page 3

2E-D-124B PASS TIA Cat 6 Perm. Link 120 ft 4.6 dB (NEXT) 07/10/2026 06:06 AM 2E-D-125A PASS TIA Cat 6 Perm. Link 98 ft 2.3 dB (NEXT) 07/10/2026 07:30 AM 2E-D-125B PASS TIA Cat 6 Perm. Link 98 ft 2.3 dB (NEXT) 07/10/2026 07:31 AM 2E-D-126A PASS TIA Cat 6 Perm. Link 96 ft 3.5 dB (NEXT) 07/10/2026 07:29 AM 2E-D-126B PASS TIA Cat 6 Perm. Link 96 ft 5.3 dB (NEXT) 07/10/2026 07:29 AM 2E-D-127A PASS TIA Cat 6 Perm. Link 89 ft 3.6 dB (NEXT) 07/10/2026 06:58 AM 2E-D-127B PASS TIA Cat 6 Perm. Link 90 ft 3.3 dB (NEXT) 07/10/2026 06:58 AM 2E-D-128A PASS TIA Cat 6 Perm. Link 85 ft 5.4 dB (NEXT) 07/10/2026 07:00 AM 2E-D-128B PASS TIA Cat 6 Perm. Link 85 ft 2.5 dB (NEXT) 07/10/2026 07:00 AM 2E-D-129A FAIL TIA Cat 6 Perm. Link 39 ft -0.6 dB (NEXT) 07/10/2026 07:40 AM 2E-D-129B PASS TIA Cat 6 Perm. Link 40 ft 4.5 dB (NEXT) 07/10/2026 07:38 AM 2E-D-130A PASS TIA Cat 6 Perm. Link 43 ft 4.0 dB (NEXT) 07/10/2026 07:41 AM 2E-D-130B PASS TIA Cat 6 Perm. Link 43 ft 1.7 dB (NEXT) 07/10/2026 07:41 AM 2E-D-134A FAIL TIA Cat 6 Perm. Link 84 ft N/A 07/07/2026 09:07 AM 2E-D-134B PASS TIA Cat 6 Perm. Link 84 ft 2.6 dB (NEXT) 07/07/2026 09:07 AM

07/10/2026 02:48:19 PM Page 4

Total Length: 33612 ft Number of Reports: 249 Number of Passing Reports: 212 Number of Failing Reports: 37 Number of Warning Reports: 0 Documentation Only: 0

07/10/2026 02:48:19 PM Page 5

2E-V-001 FAIL TIA Cat 6 Perm. Link 0 ft N/A 07/07/2026 10:58 AM 2E-V-002 PASS TIA Cat 6 Perm. Link 231 ft 5.8 dB (NEXT) 07/07/2026 10:24 AM 2E-V-003 FAIL TIA Cat 6 Perm. Link 218 ft N/A 07/07/2026 03:48 PM 2E-V-005 PASS TIA Cat 6 Perm. Link 224 ft 1.4 dB (NEXT) 07/07/2026 10:43 AM 2E-V-006 PASS TIA Cat 6 Perm. Link 231 ft 4.5 dB (NEXT) 07/07/2026 10:47 AM 2E-V-007 FAIL TIA Cat 6 Perm. Link 237 ft N/A 07/07/2026 10:50 AM 2E-V-008 FAIL TIA Cat 6 Perm. Link 209 ft N/A 07/07/2026 03:55 PM 2E-V-009 PASS TIA Cat 6 Perm. Link 206 ft 6.1 dB (NEXT) 07/07/2026 03:10 PM 2E-V-010 PASS TIA Cat 6 Perm. Link 204 ft 5.8 dB (NEXT) 07/07/2026 03:13 PM 2E-V-011 PASS TIA Cat 6 Perm. Link 199 ft 5.0 dB (NEXT) 07/07/2026 03:16 PM 2E-V-012 PASS TIA Cat 6 Perm. Link 193 ft 3.8 dB (NEXT) 07/07/2026 02:58 PM 2E-V-013 PASS TIA Cat 6 Perm. Link 211 ft 5.2 dB (NEXT) 07/07/2026 11:01 AM 2E-V-014 FAIL TIA Cat 6 Perm. Link 0 ft N/A 07/07/2026 10:41 AM 2E-V-015 PASS TIA Cat 6 Perm. Link 204 ft 5.5 dB (NEXT) 07/07/2026 03:36 PM 2E-V-016 PASS TIA Cat 6 Perm. Link 200 ft 6.4 dB (NEXT) 07/07/2026 03:29 PM 2E-V-017 PASS TIA Cat 6 Perm. Link 204 ft 5.9 dB (NEXT) 07/07/2026 03:32 PM 2E-V-018 FAIL TIA Cat 6 Perm. Link 0 ft N/A 07/07/2026 02:47 PM 2E-V-019 PASS TIA Cat 6 Perm. Link 206 ft 6.3 dB (NEXT) 07/07/2026 02:55 PM 2E-V-020 PASS TIA Cat 6 Perm. Link 196 ft 1.8 dB (NEXT) 07/07/2026 02:50 PM 2E-V-021 PASS TIA Cat 6 Perm. Link 189 ft 5.5 dB (NEXT) 07/07/2026 02:43 PM 2E-V-022 PASS TIA Cat 6 Perm. Link 187 ft 8.9 dB (NEXT) 07/07/2026 03:24 PM 2E-V-023 PASS TIA Cat 6 Perm. Link 194 ft 7.8 dB (NEXT) 07/07/2026 03:05 PM 2E-V-025 FAIL TIA Cat 6 Perm. Link 1 ft N/A 07/07/2026 03:08 PM 2E-V-026 PASS TIA Cat 6 Perm. Link 195 ft 9.1 dB (NEXT) 07/07/2026 02:32 PM 2E-V-027 PASS TIA Cat 6 Perm. Link 189 ft 6.4 dB (NEXT) 07/07/2026 02:35 PM 2E-V-028 PASS TIA Cat 6 Perm. Link 194 ft 6.1 dB (NEXT) 07/07/2026 02:19 PM 2E-V-029 PASS TIA Cat 6 Perm. Link 187 ft 6.4 dB (NEXT) 07/07/2026 02:17 PM 2E-V-030 PASS* TIA Cat 6 Perm. Link 169 ft 4.9 dB (NEXT) 07/07/2026 02:40 PM 2E-V-031 PASS TIA Cat 6 Perm. Link 174 ft 4.0 dB (NEXT) 07/07/2026 02:23 PM 2E-V-032 FAIL TIA Cat 6 Perm. Link 181 ft N/A 07/07/2026 02:26 PM 2E-V-033 FAIL TIA Cat 6 Perm. Link 187 ft 6.3 dB (NEXT) 07/07/2026 02:29 PM 2E-V-034 FAIL TIA Cat 6 Perm. Link 177 ft 1.5 dB (NEXT) 07/07/2026 01:40 PM 2E-V-035 PASS TIA Cat 6 Perm. Link 169 ft 5.7 dB (NEXT) 07/07/2026 01:44 PM 2E-V-036 PASS* TIA Cat 6 Perm. Link 154 ft 4.6 dB (NEXT) 07/07/2026 01:49 PM 2E-V-037 FAIL TIA Cat 6 Perm. Link 161 ft N/A 07/07/2026 01:47 PM 2E-V-038 FAIL TIA Cat 6 Perm. Link 149 ft N/A 07/07/2026 01:36 PM 2E-V-039 FAIL TIA Cat 6 Perm. Link 0 ft N/A 07/08/2026 10:48 AM 2E-V-041 PASS TIA Cat 6 Perm. Link 191 ft 7.6 dB (NEXT) 07/07/2026 02:13 PM 2E-V-042 PASS TIA Cat 6 Perm. Link 188 ft 4.9 dB (NEXT) 07/07/2026 02:11 PM 2E-V-043 FAIL TIA Cat 6 Perm. Link 165 ft 0.0 dB (NEXT) 07/07/2026 03:58 PM 2E-V-044 PASS TIA Cat 6 Perm. Link 147 ft 7.2 dB (NEXT) 07/07/2026 09:58 AM 2E-V-045 FAIL TIA Cat 6 Perm. Link 0 ft N/A 07/07/2026 10:08 AM 2E-V-048 PASS TIA Cat 6 Perm. Link 170 ft 6.9 dB (NEXT) 07/07/2026 01:32 PM 2E-V-049 PASS TIA Cat 6 Perm. Link 170 ft 6.3 dB (NEXT) 07/07/2026 01:29 PM 2E-V-050 PASS TIA Cat 6 Perm. Link 149 ft 4.2 dB (NEXT) 07/07/2026 01:26 PM 2E-V-051 PASS TIA Cat 6 Perm. Link 156 ft 5.9 dB (NEXT) 07/07/2026 01:24 PM 2E-V-052 PASS* TIA Cat 6 Perm. Link 156 ft 0.6 dB (NEXT) 07/07/2026 12:21 PM 2E-V-053 PASS TIA Cat 6 Perm. Link 165 ft 6.8 dB (NEXT) 07/07/2026 01:52 PM 2E-V-054 PASS TIA Cat 6 Perm. Link 172 ft 7.6 dB (NEXT) 07/07/2026 01:55 PM 2E-V-055 FAIL TIA Cat 6 Perm. Link 0 ft N/A 07/07/2026 01:58 PM 2E-V-056 PASS TIA Cat 6 Perm. Link 151 ft 5.5 dB (NEXT) 07/07/2026 02:00 PM 2E-V-057 PASS TIA Cat 6 Perm. Link 156 ft 6.4 dB (NEXT) 07/07/2026 02:03 PM 2E-V-058 PASS TIA Cat 6 Perm. Link 158 ft 9.0 dB (NEXT) 07/07/2026 02:05 PM 2E-V-059 PASS TIA Cat 6 Perm. Link 142 ft 5.9 dB (NEXT) 07/07/2026 09:48 AM 2E-V-060 PASS TIA Cat 6 Perm. Link 138 ft 5.4 dB (NEXT) 07/07/2026 09:52 AM 2E-V-061 FAIL TIA Cat 6 Perm. Link 0 ft N/A 07/07/2026 09:54 AM 2E-V-062 PASS TIA Cat 6 Perm. Link 137 ft 6.2 dB (NEXT) 07/07/2026 09:44 AM 2E-V-063 FAIL TIA Cat 6 Perm. Link 0 ft N/A 07/07/2026 09:41 AM 2E-V-064 FAIL TIA Cat 6 Perm. Link 124 ft N/A 07/07/2026 09:36 AM 2E-V-065 PASS TIA Cat 6 Perm. Link 123 ft 6.3 dB (NEXT) 07/07/2026 09:32 AM 2E-V-066 PASS TIA Cat 6 Perm. Link 129 ft 6.2 dB (NEXT) 07/07/2026 09:29 AM 2E-V-067 PASS TIA Cat 6 Perm. Link 137 ft 2.8 dB (NEXT) 07/07/2026 09:26 AM 2E-V-068 FAIL TIA Cat 6 Perm. Link 112 ft N/A 07/07/2026 09:22 AM 2E-V-069 FAIL TIA Cat 6 Perm. Link 109 ft N/A 07/07/2026 09:19 AM 2E-V-070 PASS TIA Cat 6 Perm. Link 102 ft 7.3 dB (NEXT) 07/07/2026 09:15 AM 2E-V-071 FAIL TIA Cat 6 Perm. Link 112 ft N/A 07/07/2026 09:11 AM 2E-V-072 PASS TIA Cat 6 Perm. Link 120 ft 6.8 dB (NEXT) 07/07/2026 09:09 AM 2E-V-073 PASS TIA Cat 6 Perm. Link 103 ft 6.6 dB (NEXT) 07/07/2026 08:59 AM 2E-V-074 PASS TIA Cat 6 Perm. Link 105 ft 6.3 dB (NEXT) 07/07/2026 08:56 AM 2E-V-076 PASS TIA Cat 6 Perm. Link 112 ft 7.0 dB (NEXT) 07/07/2026 12:12 PM 2E-V-077 PASS TIA Cat 6 Perm. Link 108 ft 5.2 dB (NEXT) 07/07/2026 12:06 PM 2E-V-078 FAIL TIA Cat 6 Perm. Link 100 ft -9.0 dB (NEXT) 07/07/2026 12:05 PM 2E-V-080 FAIL TIA Cat 6 Perm. Link 103 ft N/A 07/07/2026 12:16 PM 2E-V-081 PASS TIA Cat 6 Perm. Link 75 ft 5.6 dB (NEXT) 07/07/2026 08:25 AM 2E-V-082 PASS TIA Cat 6 Perm. Link 86 ft 5.9 dB (NEXT) 07/07/2026 08:33 AM 2E-V-083 PASS TIA Cat 6 Perm. Link 92 ft 1.1 dB (NEXT) 07/07/2026 08:36 AM 2E-V-084 PASS TIA Cat 6 Perm. Link 89 ft 3.6 dB (NEXT) 07/07/2026 08:37 AM

2E-V-085 PASS TIA Cat 6 Perm. Link 82 ft 4.9 dB (NEXT) 07/07/2026 08:44 AM

07/10/2026

02:50:20 PM

2E-V-086 FAIL TIA Cat 6 Perm. Link 76 ft N/A 07/07/2026 08:48 AM 2E-V-087 PASS TIA Cat 6 Perm. Link 140 ft 7.2 dB (NEXT) 07/09/2026 11:31 AM 2E-V-088 PASS TIA Cat 6 Perm. Link 140 ft 3.6 dB (NEXT) 07/09/2026 11:35 AM 2E-V-089 PASS TIA Cat 6 Perm. Link 140 ft 4.9 dB (NEXT) 07/09/2026 11:35 AM 2E-V-090 PASS TIA Cat 6 Perm. Link 140 ft 5.2 dB (NEXT) 07/09/2026 11:36 AM 2E-V-091 PASS TIA Cat 6 Perm. Link 140 ft 6.5 dB (NEXT) 07/09/2026 11:36 AM 2E-V-092 PASS TIA Cat 6 Perm. Link 121 ft 4.5 dB (NEXT) 07/09/2026 11:27 AM 2E-V-093 PASS TIA Cat 6 Perm. Link 123 ft 6.5 dB (NEXT) 07/09/2026 11:29 AM 2E-V-094 PASS TIA Cat 6 Perm. Link 123 ft 5.4 dB (NEXT) 07/09/2026 11:29 AM 2E-V-095 PASS TIA Cat 6 Perm. Link 124 ft 6.7 dB (NEXT) 07/09/2026 11:29 AM 2E-V-096 PASS TIA Cat 6 Perm. Link 123 ft 6.4 dB (NEXT) 07/09/2026 11:30 AM 2E-V-097 FAIL TIA Cat 6 Perm. Link 123 ft N/A 07/09/2026 11:30 AM 2E-V-098 PASS TIA Cat 6 Perm. Link 110 ft 4.4 dB (NEXT) 07/09/2026 11:21 AM 2E-V-099 PASS TIA Cat 6 Perm. Link 110 ft 6.8 dB (NEXT) 07/09/2026 11:24 AM 2E-V-100 PASS TIA Cat 6 Perm. Link 110 ft 6.2 dB (NEXT) 07/09/2026 11:25 AM 2E-V-101 PASS TIA Cat 6 Perm. Link 109 ft 5.2 dB (NEXT) 07/09/2026 11:25 AM 2E-V-102 PASS TIA Cat 6 Perm. Link 110 ft 5.7 dB (NEXT) 07/09/2026 11:25 AM 2E-V-103 PASS TIA Cat 6 Perm. Link 110 ft 6.8 dB (NEXT) 07/09/2026 11:26 AM 2E-V-104 PASS TIA Cat 6 Perm. Link 123 ft 3.5 dB (NEXT) 07/09/2026 12:02 PM 2E-V-105 PASS TIA Cat 6 Perm. Link 152 ft 5.6 dB (NEXT) 07/09/2026 11:59 AM 2E-V-106 PASS TIA Cat 6 Perm. Link 151 ft 6.3 dB (NEXT) 07/09/2026 11:59 AM 2E-V-107 PASS TIA Cat 6 Perm. Link 152 ft 4.6 dB (NEXT) 07/09/2026 11:59 AM 2E-V-108 PASS TIA Cat 6 Perm. Link 151 ft 4.9 dB (NEXT) 07/09/2026 12:00 PM 2E-V-109 PASS TIA Cat 6 Perm. Link 152 ft 7.6 dB (NEXT) 07/09/2026 12:00 PM 2E-V-110 FAIL TIA Cat 6 Perm. Link 151 ft N/A 07/09/2026 12:01 PM 2E-V-112 PASS TIA Cat 6 Perm. Link 130 ft 5.8 dB (NEXT) 07/10/2026 08:25 AM 2E-V-113 PASS TIA Cat 6 Perm. Link 130 ft 5.9 dB (NEXT) 07/10/2026 08:19 AM 2E-V-115 PASS TIA Cat 6 Perm.