Attachment 1 MCB Quantico 2nd Floor Testing Report.pdf
PDF 1 MB Posted
- Attached to
- MCRC Data Port Repair Services
- Solicitation number
- M9549226SS001
- Issued by
-
United States Marine Corps
About this file
This document comprises testing results and infrastructure analysis for the USMC Marsh Center's telecommunications cabling system at MCB Quantico. The testing evaluated voice and data cabling across two telecom rooms (East and West) serving the Recruiting Command Headquarters on the second deck, with a total of 883 panels tested across four categories (East Closet Voice, East Closet Data, West Closet Voice, West Closet Data). Overall pass rate was 79.01% with 625 panels passing, 149 failing, and 17 marginal results. Testing identified 92 unidentified cables and revealed systematic installation deficiencies, including 27 biscuits/bezels not attached to furniture on the east side and 32 on the west side.
The assessment recommends three primary corrective actions: properly measuring cubicle furniture cutout openings and installing matching bezels; replacing all jacks at the station side of cabling to ensure equal quality and correct failing/broken jacks; and conducting a comprehensive telecom room overhaul. Secondary recommendations address both telecom rooms' infrastructure deficiencies, including removing old equipment and cabling, upgrading cable management and support systems, adding cable tray over data racks, redressing blue cabling, and performing a phone switch audit to identify active analog lines. The facility requires three additional drop locations (bringing the total from 270 to 273 workstations) with CAT6 jacks totaling 810 CAT6 jacks/drops across all 270 workstation locations, with installation approval needed for these additions.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| SOW_ Data Port Repair Services.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
MCB Quantico Marsh Center Testing Statistics
Terminated on Panels Tested Pass Fail Marginal Tested Pass Fail Marginal
East Closet Voice 139 121 89 27 5 87.05% 73.55% 22.31% 4.13%
East Closet Data 276 249 205 37 7 90.22% 82.33% 14.86% 2.81%
West Closet Voice 156 142 93 46 3 91.03% 65.49% 32.39% 2.11%
West Closet Data 312 279 238 39 2 89.42% 85.30% 13.98% 0.72%
883 791 625 149 17 89.58% 79.01% 18.84% 2.15%
Cables Not Identified 92
East Side
(27) Biscuits/Bezels not attached to furniture
West Side
(32) Biscuits/Bezels not attached to furniture
Recommendations:
1) Properly measure the cut out openings in the cubicle furniture and install a bezel that matches the opening size
2) Replace all jacks at the station side of the cabling and retest. This will ensure all are equal quality and terminated correctly
It will also correct all of the failing/broken jacks.
3) Consider an overhaul of the telecom rooms. (See Telecom room overservations)
Additional drop locations needed per Mike Elliott (NEED APPROVAL TO INSTALL) changes total from 270 to 273
SINGLE WORK STATION LOCATION – 3
CAT6 JACKS/DROPS EACH
TOTAL OF 270 WORK STATION
LOCATIONS – 810 CAT6 JACKS/DROPS
SECURITY DESK
WORK AREA
SUPPLY
STORAGE
USMC Marsh Center 2nd Deck Recruiting Command HQ
NA
New
South/East Telecom Room
Old
Old
RU 45
RU 44
RU 43
RU 42
RU 41
RU 40
RU 39
RU 38
RU 37
RU 36
RU 35
RU 34
RU 33
RU 32
RU 31
RU 30
RU 29
RU 28
RU 27
RU 26
RU 25
RU 24
RU 23
RU 22
RU 21
RU 20
RU 19
RU 18
RU 17
RU 16
RU 15
RU 14
RU 13
RU 12
RU 11
RU 10
RU 9
RU 8
RU 7
RU 6
RU 5
RU 4
RU 3
RU 2
RU 1
Data Rack
RU 45
RU 44
RU 43
RU 42
RU 41
RU 40
RU 39
RU 38
RU 37
RU 36
RU 35
RU 34
RU 33
RU 32
RU 31
RU 30
RU 29
RU 28
RU 27
RU 26
RU 25
RU 24
RU 23
RU 22
RU 21
RU 20
RU 19
RU 18
RU 17
RU 16
RU 15
RU 14
RU 13
RU 12
RU 11
RU 10
RU 9
RU 8
RU 7
RU 6
RU 5
RU 4
RU 3
RU 2
RU 1
Voice Rack
RU 45
RU 44
RU 43
RU 42
RU 41
RU 40
RU 39
RU 38
RU 37
RU 36
RU 35
RU 34
RU 33
RU 32
RU 31
RU 30
RU 29
RU 28
RU 27
RU 26
RU 25
RU 24
RU 23
RU 22
RU 21
RU 20
RU 19
RU 18
RU 17
RU 16
RU 15
RU 14
RU 13
RU 12
RU 11
RU 10
RU 9
RU 8
RU 7
RU 6
RU 5
RU 4
RU 3
RU 2
RU 1
Cabinet 2 Post Rack
PP 1
PP 2
PP 3
LIU 12 STSM/12 STMM
LIU 12 SCMM
1RU Swith
APC
1a/b old data station cable
144a/b hubbell cat 5 panels
UPS
1-192
Switch pairs old voice station cables
RU 43
RU 42
RU 41
RU 40
RU 39
RU 38
RU 37
RU 36
RU 35
RU 34
RU 33
RU 32
RU 31
RU 30
RU 29
RU 28
RU 27
RU 26
RU 25
RU 24
RU 23
RU 22
RU 21
RU 20
RU 19
RU 18
RU 17
RU 16
RU 15
RU 14
RU 13
RU 12
RU 11
RU 10
RU 9
RU 8
RU 7
RU 6
RU 5
RU 4
RU 3
RU 2
PP 2
PP 3
PP 4
PP 5
PP 6
MCRC RCEN Router
MCRC RCEN SW1
MCRC RCEN SW2
MCRC RCEN SW3
MCRC RCEN SW4
USMC Marsh Center - 2 East Telecom Room Patch Panel Reference
276 Total
Data
2E-D 2E-D 2E-D 2E-D 2E-D 2E-D
025A 025B 026A 026B 027A 027B
Panel 3
Panel 4
Panel 5
Panel 6
30 31
36 37
42 43
010A 010B 011A 011B 012A 012B
013A 013B 014A 014B 015A 015B
016A 016B 017A 017B 018A 018B
019A 019B 020A 020B 021A 021B
022A 022B 023A 023B 024A 024B
001A 001B 002A 002B 003A 003B
004A 004B 005A 005B 006A 006B
007A 007B 008A 008B 009A 009B
249 Total
Tested
No Test
Passed
Failed
Marginal
028A 028B 029A 029B 030A 030B
031A 031B 032A 032B 033A 033B
034A 034B 035A 035B 036A 036B
037A 037B 038A 038B 039A 039B
040A 040B 041A 041B 042A 042B
043A 043B 044A 044B 045A 045B
046A 046B 047A 047B 048A 048B
Panel 1
Panel 2
049A 049B 050A 050B 051A 051B
052A 052B 053A 053B 054A 054B
055A 055B 056A 056B 057A 057B
058A 058B 059A 059B 060A 060B
061A 061B 062A 062B 063A 063B
064A 064B 065A 065B 066A 066B
067A 067B 068A 068B 069A 069B
070A 070B 071A 071B 072A 072B
073A 073B 074A 074B 075A 075B
076A 076B 077A 077B 078A 078B
079A 079B 080A 080B 081A 081B
082A 082B 083A 083B 084A 084B
085A 085B 086A 086B 087A 087B
088A 088B 089A 089B 090A 090B
091A 091B 092A 092B 093A 093B
094A 094B 095A 095B 096A 096B
097A 097B 098A 098B 099A 099B
100A 100B 101A 101B 102A 102B
103A 103B 104A 104B 105A 105B
106A 106B 107A 107B 108A 108B
109A 109B 110A 110B 111A 111B
112A 112B 113A 113B 114A 114B
115A 115B 116A 116B 117A 117B
118A 118B 119A 119B 120A 120B
121A 121B 122A 122B 123A 123B
124A 124B 125A 125B 126A 126B
127A 127B 128A 128B 129A 129B
130A 130B 131A 131B 132A 132B
133A 133B 134A 134B 135A 135B
136A 136B 137A 137B 138A 138B
1 6 7 12 13 18
19 24
2E-V
139 Total
Voice
2E-V 2E-V 2E-V 2E-V 2E-V 2E-V
044 045 046 047 048 049
121 Total
Tested
001 002 003 004 005 006
007 008 009 010 011 012
013 014 015 016 017 018
019 020 021 022 023 024
050 051 052 053 054 055
056 057 058 059 060 061
062 063 064 065 066 067
025 026 027 028 029 030
031 032 033 034 035 036
037 038 039 040 041 042
068 069 070 071 072 073
074 075 076 077 078 079
080 081 082 083 084 085
086 087 088 089 090 091
092 093 094 095 096 097
098 099 100 101 102 103
104 105 106 107 108 109
110 111 112 113 114 115
116 117 118 119 120 121
122 123 124 125 126 127
128 129 130 131 132 133
134 135 136 137 138 139
East/South Side of Bldg Outlet Notes Notes
9 Biscuit off furniture
10 Biscuit off furniture
11 Biscuit off furniture
12 Biscuit off furniture A&B Data are swapped
16 Biscuit off furniture
18 Biscuit off furniture
20 Biscuit off furniture
21 Biscuit off furniture
22 Biscuit off furniture
24 Biscuit off furniture Voice Jack - something stuck in it
30 Biscuit off furniture
33 Biscuit off furniture
37 Biscuit off furniture
42 Biscuit off furniture
49 Biscuit off furniture
50 Biscuit off furniture
54 Biscuit off furniture
55 Biscuit off furniture
56 Biscuit off furniture
58 Biscuit off furniture
76 Biscuit off furniture
79 Biscuit off furniture Voice Jack - something stuck in it
81 Biscuit off furniture
82 Biscuit off furniture
83 Biscuit off furniture
84 Biscuit off furniture
86 Biscuit off furniture
111 Voice jack missing
113 A Data jack missing
114 Voice Jack missing
115 No Faceplate
116 A&B Data are swapped
Failing Results Voice Diagnosis Possible Cause
1 Or/Wh, Wh/B, B/Wh open. Bad patch panel port or termination
3 Wh/Or, Wh/Br open Broken Jack/Pins/Termination
7 B/Wh open Broken Jack/Pins/Termination
8 Wh/Or, Br/Wh open Broken Jack/Pins/Termination
14 Gr/Wh, Wh/Br Bad patch panel port or termination
18 Wh/Br open Bad patch panel port or termination
25 Gr/Wh Bad patch panel port or termination
32 Wh/Or open Broken Jack/Pins/Termination. Possible cut cable
33 Return Loss - IDF Side Poor termination
34 Return Loss - Both Sides Poor termination
37 Wh/Or, Br/Wh open Broken Jack/Pins/Termination
38 Wh/Or open Broken Jack/Pins/Termination
39 Wh/Or open Bad patch panel port or termination
43 Return Loss - Both Sides Poor termination
45 Wh/Or, Or/Wh, Wh/Gr, Wh/Br open Bad patch panel port or termination
55 Wh/Gr, Gr/Wh open Bad patch panel port or termination
61 Wh/Or open Bad patch panel port or termination
63 Wh/Or, Gr/Wh, Wh/Br Broken Jack/Pins/Termination. Bad patch panel port or termination
64 Wh/Or open. Blue pair crossed Broken Jack/Pins/Termination
68 Wh/Or, Br/Wh open Broken Jack/Pins/Termination
69 Wh/Or open Broken Jack/Pins/Termination
71 Or/Wh open Broken Jack/Pins/Termination. Possible cut cable
78 Wh/Or open Broken Jack/Pins/Termination
80 Wh/Or open Broken Jack/Pins/Termination
86 Wh/Gr open Broken Jack/Pins/Termination
97 Green & Brown Pairs Crossed Poor Termination 110 Wh/Gr open Broken Jack/Pins/Termination
Marginal Results-Voice Diagnosis Possible Cause
30 Return Loss - IDF Side Poor Termination
36 Return Loss - IDF Side Poor Termination
52 Cross Talk - WAO Side Poor Termination
117 Cross Talk - WAO Side Poor Termination 129 Cross Talk - WAO Side Poor Termination
Data Diagnosis Possible Cause
10B Or/Wh, Wh/Gr open Bad patch panel port or termination
11B Wh/Gr, Wh/Br open Bad patch panel port or termination
12A Or/Wh open Bad patch panel port or termination
12B Wh/Br open Bad patch panel port or termination
18A Or/Wh, Wh/Or, Wh/Br open Bad patch panel port or termination
20B Or/Wh open Bad patch panel port or termination
22A Wh/Gr, Gr/Wh open Broken Jack/Pins/Termination. Bad patch panel port or termination
24B Wh/Or, B/Wh open Broken Jack/Pins/Termination. Bad patch panel port or termination
27A Or/Wh, Br/Wh open Bad patch panel port or termination
27B Or/Wh, Wh/Or, Gr/Wh open Bad patch panel port or termination
33A Gr/Wh Open Bad patch panel port or termination
34A Return Loss - Both Sides Poor Termination
34B Wh/Br open Bad patch panel port or termination
35B Wh/Or, Or/Wh, B/Wh open Bad patch panel port or termination
36A Or/Wh Open Bad patch panel port or termination
36B B/Wh open Bad patch panel port or termination
44B Wh/Br open Bad patch panel port or termination
45B Cross Talk - Both Sides Poor Termination
65A Wh/B open Broken Jack/Pins/Termination
68B B/Wh open Bad patch panel port or termination
73B Or/Wh open Bad patch panel port or termination
79B Cross Talk - WAO Side Poor Termination
7A Wh/Gr open Broken Jack/Pins/Termination
80B Cross Talk - WAO Side Poor Termination
84B Wh/Br open Bad patch panel port or termination
85A Wh/Or open Bad patch panel port or termination
86A Wh/Or open Bad patch panel port or termination
91A B/Wh open Broken Jack/Pins/Termination
92A Cross Talk - WAO Side Poor Termination
94A Cross Talk - WAO Side Poor Termination
105A Gr/Wh Open Broken Jack/Pins/Termination
108B Cross Talk - WAO Side Poor Termination
111B Gr/Wh Open Broken Jack/Pins/Termination
117A Wh/Or open Broken Jack/Pins/Termination
119A Cross Talk - WAO Side Poor Termination
129A Cross Talk - WAO Side Poor Termination 134A Or/Gr pairs reversed Poor Termination
Results-Data Diagnosis Possible Cause
10A
Cross Talk - WAO Side
Poor Termination
16A Return Loss - IDF Side Poor Termination
21A Cross Talk - WAO Side Poor Termination
32A Cross Talk - IDF Side Poor Termination
41B Return Loss - IDF Side Poor Termination
95A Cross Talk - WAO Side Poor Termination 112A Cross Talk - IDF Side Poor Termination
159 a/b
1a/b
North/West Telecom Room
Old Old
RU 43
RU 42
RU 41
RU 40
RU 39
RU 38
RU 37
RU 36
RU 35
RU 34
RU 33
RU 32
RU 31
RU 30
RU 29
RU 28
RU 27
RU 26
RU 25
RU 24
RU 23
RU 22
RU 21
RU 20
RU 19
RU 18
RU 17
RU 16
RU 15
RU 14
RU 13
RU 12
RU 11
RU 10
RU 9
RU 8
RU 7
RU 6
RU 5
RU 4
RU 3
RU 2
Data Rack
RU 43
RU 42
RU 41
RU 40
RU 39
RU 38
RU 37
RU 36
RU 35
RU 34
RU 33
RU 32
RU 31
RU 30
RU 29
RU 28
RU 27
RU 26
RU 25
RU 24
RU 23
RU 22
RU 21
RU 20
RU 19
RU 18
RU 17
RU 16
RU 15
RU 14
RU 13
RU 12
RU 11
RU 10
RU 9
RU 8
RU 7
RU 6
RU 5
RU 4
RU 3
RU 2
Voice Rack
RU 43
RU 42
RU 41
RU 40
RU 39
RU 38
RU 37
RU 36
RU 35
RU 34
RU 33
RU 32
RU 31
RU 30
RU 29
RU 28
RU 27
RU 26
RU 25
RU 24
RU 23
RU 22
RU 21
RU 20
RU 19
RU 18
RU 17
RU 16
RU 15
RU 14
RU 13
RU 12
RU 11
RU 10
RU 9
RU 8
RU 7
RU 6
RU 5
RU 4
RU 3
RU 2
RU 1
Cabinet 2 Post Rack
RU 45
RU 44
RU 43
RU 42
RU 41
RU 40
RU 39
RU 38
RU 37
RU 36
RU 35
RU 34
RU 33
RU 32
RU 31
RU 30
RU 29
RU 28
RU 27
RU 26
RU 25
RU 24
RU 23
RU 22
RU 21
RU 20
RU 19
RU 18
RU 17
RU 16
RU 15
RU 14
RU 13
RU 12
RU 11
RU 10
RU 9
RU 8
RU 7
RU 6
RU 5
RU 4
RU 3
RU 2
1RU Switch
1RU Switch
1RU Switch
1RU Switch
1RU Switch
1RU Switch
1RU Switch
UPS
UPS
LIU 12 STSM/12 STMM
LIU 12 SCMM
1-192
Switch pairs old voice station cables
USMC Marsh Center - 2 West Telecom Room Patch Panel Reference
1 6 7 12 13 18 19
312 Total
2W-D 2W-D 2W-D 2W-D 2W-D 2W-D
037A 037B 038A 038B 039A 039B
No Test
Passed
Failed
001A 001B 002A 002B 003A 003B
004A 004B 005A 005B 006A 006B
007A 007B 008A 008B 009A 009B
013A 013B 014A 014B 015A 015B
016A 016B 017A 017B 018A 018B
019A 019B 020A 020B 021A 021B
010A 010B 011A 011B 012A 012B
279 Total
Tested
022A 022B 023A 023B 024A 024B
025A 025B 026A 026B 027A 027B
028A 028B 029A 029B 030A 030B
031A 031B 032A 032B 033A 033B
034A 034B 035A 035B 036A 036B
040A 040B 041A 041B 042A 042B
043A 043B 044A 044B 045A 045B
046A 046B 047A 047B 048A 048B
Panel 4
Panel 5
Panel 6
Panel 7
24 24
049A 049B 050A 050B 051A 051B
052A 052B 053A 053B 054A 054B
055A 055B 056A 056B 057A 057B
058A 058B 059A 059B 060A 060B
061A 061B 062A 062B 063A 063B
064A 064B 065A 065B 066A 066B
067A 067B 068A 068B 069A 069B
070A 070B 071A 071B 072A 072B
073A 073B 074A 074B 075A 075B
076A 076B 077A 077B 078A 078B
079A 079B 080A 080B 081A 081B
082A 082B 083A 083B 084A 084B
085A 085B 086A 086B 087A 087B
088A 088B 089A 089B 090A 090B
091A 091B 092A 092B 093A 093B
094A 094B 095A 095B 096A 096B
097A 097B 098A 098B 099A 099B
100A 100B 101A 101B 102A 102B
103A 103B 104A 104B 105A 105B
106A 106B 107A 107B 108A 108B
109A 109B 110A 110B 111A 111B
112A 112B 113A 113B 114A 114B
115A 115B 116A 116B 117A 117B
118A 118B 119A 119B 120A 120B
121A 121B 122A 122B 123A 123B
124A 124B 125A 125B 126A 126B
127A 127B 128A 128B 129A 129B
130A 130B 131A 131B 132A 132B
133A 133B 134A 134B 135A 135B
136A 136B 137A 137B 138A 138B
139A 139B 140A 140B 141A 141B
142A 142B 143A 143B 144A 144B
145A 145B 146A 146B 147A 147B
148A 148B 149A 149B 150A 150B
151A 151B 152A 152B 153A 153B
154A 154B 155A 155B 156A 156B
1 6 7 12
13 18
19 24
156 Total
2W-V 2W-V 2W-V 2W-V 2W-V 2W-V
049 050 051 052 053 054
142 Total
Tested
001 002 003 004 005 006
007 008 009 010 011 012
055 056 057 058 059 060
6 7
12 13
18 19
30 31
36 37
42 43
013 014 015 016 017 018
025 026 027 028 029 030
031 032 033 034 035 036
037 038 039 040 041 042
061 062 063 064 065 066
019 020 021 022 023 024
043 044 045 046 047 048
067 068 069 070 071 072
073 074 075 076 077 078
079 080 081 082 083 084
085 086 087 088 089 090
091 092 093 094 095 096
097 098 099 100 101 102
103 104 105 106 107 108
109 110 111 112 113 114
115 116 117 118 119 120
121 122 123 124 125 126
127 128 129 130 131 132
133 134 135 136 137 138
139 140 141 142 143 144
145 146 147 148 149 150
151 152 153 154 155 156
West/North Side of Bldg Outlet Notes Notes
1 A&B are reversed
9 Biscuit not mounted
10 Biscuit not mounted
12 Biscuit not mounted B Data Missing
13 Biscuit not mounted
17 Biscuit not mounted
19 Biscuit not mounted
21 Biscuit not mounted
23 Biscuit not mounted
24 Data Cables Missing
29 Biscuit not mounted
33 Biscuit not mounted Data Cables Missing
43 Biscuit not mounted
44 Biscuit not mounted
45 Biscuit not mounted Jack loose
46 Biscuit not mounted
54 Jacks loose
58 No biscuit, no label
59 Biscuit not mounted
61 Biscuit not mounted
64 B data is a white jack
65 A&B are reversed
66 A&B are reversed
67 A&B are reversed B Cable is missing
68 A&B are reversed
69 A & B are reversed
70 A & B are reversed
71 Voice and B Data are reversed
72 A & B are reversed
78 Not Labeled
86 Not Labeled
96 Behind Furniture
99 Biscuit not mounted
100 Biscuit not mounted
101 Biscuit not mounted
103 Biscuit not mounted
104 Biscuit not mounted
106 Biscuit not mounted Jacks loose
107 Biscuit not mounted Jacks loose
109 Biscuit not mounted
111 Cables are cut Voice cables missing
111 A&B are reversed Jacks loose
117 Biscuit not mounted
119 No biscuit B Jack Broken
120 Biscuit not mounted
125 Biscuit not mounted
126 Biscuit not mounted
132 No biscuit, no label
133 No biscuit, no label
139 Biscuit not mounted
140 Jacks loose
141 Biscuit not mounted
142 Biscuit not mounted
143 Biscuit not mounted
148 Broken Biscuit Behind Furniture
Voice Diagnosis Possible Cause
1 Wh/Or, Br/Wh open Broken Jack/Pins/Termination
8 Return Loss - Both ends Poor Termination
9 Wh/Or, Br/Wh open Broken Jack/Pins/Termination
10 Wh/Or, Br/Wh open Broken Jack/Pins/Termination
11 Wh/Or, Br/Wh open Broken Jack/Pins/Termination
13 Wh/Or, Or/Wh, Br/Wh open. Or/Wh, Wh/Gr Shorted Broken Jack/Pins/Termination. Poor termination at patch panel
15 Wh/Or open Broken Jack/Pins/Termination
16 Wh/Or, Br/Wh open Broken Jack/Pins/Termination
20 Wh/Or open Broken Jack/Pins/Termination
22 Wh/Or open Broken Jack/Pins/Termination
23 Wh/Or, Wh/Gr, Br/Wh open Broken Jack/Pins/Termination. Bad patch panel port or termination
24 Wh/Or, Or/Wh open Broken Jack/Pins/Termination. Bad patch panel port or termination
27 Wh/Or, Br/Wh open Broken Jack/Pins/Termination
29 Br/Wh open Broken Jack/Pins/Termination
31 Wh/Or, Br/Wh open Broken Jack/Pins/Termination
33 Or/Gr pairs reversed Poor Termination
40 Cross Talk - WAO Side Poor Termination
41 Wh/Or open Broken Jack/Pins/Termination
42 Wh/Br open Bad patch panel port or termination
45 Wh/Or, Br/Wh open Broken Jack/Pins/Termination
54 Wh/Or, Br/Wh open Broken Jack/Pins/Termination
55 Wh/Or, Br/Wh open Broken Jack/Pins/Termination
56 Wh/Or, Br/Wh open Broken Jack/Pins/Termination
57 Gr/Br pairs reversed Poor Termination
59 Wh/B, B/Wh, Wh/Gr, Gr/Wh open Broken Jack/Pins/Termination
60 Gr/Wh open Broken Jack/Pins/Termination
62 Wh/Or open Broken Jack/Pins/Termination
68 Wh/Or, Br/Wh open Broken Jack/Pins/Termination
70 Wh/Or, Br/Wh open Broken Jack/Pins/Termination
71 Br/Wh open Broken Jack/Pins/Termination
72 Wh/Or open Broken Jack/Pins/Termination
77 Cross Talk - WAO Side Poor Termination
99 Wh/Or open Broken Jack/Pins/Termination
103 Wh/Or open Broken Jack/Pins/Termination
105 Wh/Or open Broken Jack/Pins/Termination
109 Wh/Or open Broken Jack/Pins/Termination
110 Cross Talk - WAO Side Poor Termination
114 Wh/Or, Br/Wh open Broken Jack/Pins/Termination
118 Wh/Or open Broken Jack/Pins/Termination
119 Wh/Gr open Broken Jack/Pins/Termination
120 Wh/B open Broken Jack/Pins/Termination
123 Wh/Or open Broken Jack/Pins/Termination
124 Wh/Or open Broken Jack/Pins/Termination
126 Wh/Or, Br/Wh open Broken Jack/Pins/Termination
127 Wh/Or open Broken Jack/Pins/Termination 145 Br/Wh open Broken Jack/Pins/Termination
Marginal Results-Voice Diagnosis Possible Cause
19 Cross Talk - WAO Side Poor Termination
81 Cross Talk - WAO Side Poor Termination 91 Cross Talk - WAO Side Poor Termination
Data Diagnosis Possible Cause
1A Gr/Wh open Broken Jack/Pins/Termination
5B Cross Talk - WAO Side Poor Termination
9A B/Wh, Wh/Br open Broken Jack/Pins/Termination
25B Wh/B, B/Wh open Bad patch panel port or termination
26B Br/Wh open Bad patch panel port or termination
27B Green Pair Open at jack, Shorted at Patch Panel Broken Jack/Pins/Termination. Bad patch panel port or termination
36A Wh/Gr open Broken Jack/Pins/Termination
37B Or/Wh open Bad patch panel port or termination
42A Cross Talk - WAO Side Poor Termination
45A Cross Talk - WAO Side Poor Termination
47B Cross Talk - WAO Side Poor Termination
51B Gr/Wh open Bad patch panel port or termination
53A Wh/Or open Bad patch panel port or termination
54B Gr/Wh open Bad patch panel port or termination
57A Wh/B open, Green Pair crossed Broken Jack/Pins/Termination
57B Wh/B, B/Wh, Wh/Or open. Green Pair Crossed Broken Jack/Pins/Termination
58A Wh/Gr, Gr/Wh open Broken Jack/Pins/Termination
58B Wh/Or, Or/Wh open Bad patch panel port or termination
59A Wh/B, Wh/Gr open Broken Jack/Pins/Termination
59B Wh/B, Gr/Wh open Broken Jack/Pins/Termination
62B Wh/Gr, Gr/Wh open. Brown Pair Crossed Broken Jack/Pins/Termination
67A Blue and Brown Pairs Shorted Poor Termination
68A Cross Talk - WAO Side Poor Termination
68B Wh/Or, Or/Wh, Wh/Gr, Gr/Wh open Bad patch panel port or termination
69B Gr/Wh open Bad patch panel port or termination
72B Or/Wh, Wh/Gr open Bad patch panel port or termination
73A Wh/Or open Bad patch panel port or termination
73B Or/Wh open Bad patch panel port or termination
76B Wh/Gr open Broken Jack/Pins/Termination
78A Cross Talk - WAO Side Poor Termination
82B Wh/B open Broken Jack/Pins/Termination
97B Wh/Gr open Bad patch panel port or termination
98B Or/Wh open Bad patch panel port or termination
100A Wh/B, B/Wh open Broken Jack/Pins/Termination
106B Wh/B, Wh/Gr open Broken Jack/Pins/Termination
110B Cross Talk - WAO Side Poor Termination
118A Cross Talk - TR Side Poor Termination
120B B/Wh, Wh/Gr open Broken Jack/Pins/Termination 122A Cross Talk - WAO Side Poor Termination
Marginal Results-Data Diagnosis Possible Cause
13B Return Loss - IDF Side Poor Termination 80B Cross Talk - IDF Side Poor Termination
Telecom Room Notes
East
Temperature at center of room - 5' AFF
78.4 degrees Fahrenheit
Dimensions
10'11" x 9'11"
(2) 2-post racks with new Voice/Data Patch Panels
Neither rack is bolted down
Neither rack is bonded to ground
Newly installed ladder rack is not bonded to ground
Overhead cable tray does not support the new cable (blue)
Excessive slack hanging behind the patch panels on both racks
Cables are not labeled behind the panels with machine printed labels
Neither rack has sufficient vertical management for station cabling - rear, or patch cabling - front
UPS devices are sitting on the floor. Power cables are loose across the floor.
Telecom door is not secure
All existing white cable enters the room from floor trough.
(1) existing enclosed cabinet housing old data panels and fiber optic LIUs
(1) APC device and (1) 1ru switch.
This switch may be the connectivity for wireless access points
(1) existing/old 2-post rack.
This rack contains patch panels with single pair connectivity - most like old telephone switch ties
This rack also contains old voice station cable patch panels.
There are excessively long patch cables between the switch tie panel and the new voice panels
No cable management or support for these cables.
There is a considerable amount of trash/debris/abandoned equipment on the floor.
Telecom Room Recommendations.
Perform a phone switch audit to determined if there are any active analog lines still in use.
If there are no active switch ports, recommend removing all patch cables and the old rack and panels
Cut all old white cable back to the floor trough/entry to the telecom room if feasible
Determine where the wireless access point cable are terminated and migrate them to the new 2-post data
Migrate Fiber Optic LIUs from the enclosed cabinet to the new 2-post rack if there is sufficient slack in the
Migrate active equipment from the enclosed cabinet to the new 2-post rack.
Remove all old data cabling from the cabinet and cut back to the floor trough/entry to the telecom room if
Remove the old cabinet and 2-post rack from the room.
Add cable tray over top the new 2-post data rack to properly support the cable slack.
Redress/support all blue cabling - new voice and data.
Telecom Room Notes
West
Temperature at center of room - 5' AFF
78 degrees Fahrenheit
Dimensions
9'0" x 10'0"
(2) 2-post racks with new Voice/Data Patch Panels
Overhead cable tray does not support the new cable (blue)
Excessive slack hanging behind the patch panels on both racks
Cables are not labeled behind the panels with machine printed labels
Neither rack has sufficient vertical management for station cabling - rear, or patch cabling - front
UPS devices are sitting on the floor. Power cables are loose across the floor.
Telecom door is not secure
All existing white cable enters the room from floor trough.
(1) existing enclosed cabinet housing old data panels and fiber optic LIUs
(1) existing/old 2-post rack.
This rack contains patch panels with single pair connectivity - most like old telephone switch ties
This rack also contains old voice station cable patch panels.
There are excessively long patch cables between the switch tie panel and the new voice panels
No cable management or support for these cables.
There is a considerable amount of trash/debris/abandoned equipment on the floor.
Telecom Room Recommendations.
Perform a phone switch audit to determined if there are any active analog lines still in use.
If there are no active switch ports, recommend removing all patch cables and the old rack and panels
Cut all old white cable back to the floor trough/entry to the telecom room if feasible
Determine where the wireless access point cable are terminated and migrate them to the new 2-post data rack.
Migrate Fiber Optic LIUs from the enclosed cabinet to the new 2-post rack if there is sufficient slack in the cable.
Migrate active equipment from the enclosed cabinet to the new 2-post rack.
Remove all old data cabling from the cabinet and cut back to the floor trough/entry to the telecom room if feasible
Remove the old cabinet and 2-post rack from the room.
Add cable tray over top the new 2-post data rack to properly support the cable slack.
Redress/support all blue cabling - new voice and data.
Cable ID/ Test ID Summary Test Limit Length Headroom Date / Time 2E-D-001A PASS TIA Cat 6 Perm. Link 236 ft 2.0 dB (NEXT) 07/07/2026 10:58 AM 2E-D-001B PASS TIA Cat 6 Perm. Link 236 ft 4.5 dB (NEXT) 07/07/2026 10:59 AM 2E-D-002A PASS TIA Cat 6 Perm. Link 231 ft 4.2 dB (NEXT) 07/07/2026 10:38 AM 2E-D-002B PASS TIA Cat 6 Perm. Link 231 ft 3.7 dB (NEXT) 07/07/2026 10:38 AM 2E-D-003A PASS TIA Cat 6 Perm. Link 219 ft 8.2 dB (NEXT) 07/07/2026 02:48 PM 2E-D-003B PASS TIA Cat 6 Perm. Link 219 ft 2.3 dB (NEXT) 07/07/2026 02:49 PM 2E-D-005A PASS TIA Cat 6 Perm. Link 224 ft 4.0 dB (NEXT) 07/07/2026 10:43 AM 2E-D-005B PASS TIA Cat 6 Perm. Link 224 ft 6.6 dB (NEXT) 07/07/2026 10:45 AM 2E-D-006A PASS TIA Cat 6 Perm. Link 231 ft 7.8 dB (NEXT) 07/07/2026 10:47 AM 2E-D-006B PASS TIA Cat 6 Perm. Link 231 ft 2.4 dB (NEXT) 07/07/2026 10:48 AM 2E-D-007A FAIL TIA Cat 6 Perm. Link 236 ft N/A 07/07/2026 10:49 AM 2E-D-007B PASS TIA Cat 6 Perm. Link 236 ft 7.7 dB (NEXT) 07/07/2026 10:51 AM 2E-D-008A PASS TIA Cat 6 Perm. Link 207 ft 4.1 dB (NEXT) 07/07/2026 02:55 PM 2E-D-008B PASS TIA Cat 6 Perm. Link 208 ft 7.1 dB (NEXT) 07/07/2026 02:56 PM 2E-D-009A PASS TIA Cat 6 Perm. Link 204 ft 7.2 dB (NEXT) 07/07/2026 02:11 PM 2E-D-009B PASS TIA Cat 6 Perm. Link 204 ft 5.0 dB (NEXT) 07/07/2026 02:11 PM 2E-D-010A PASS* TIA Cat 6 Perm. Link 204 ft 1.0 dB (NEXT) 07/07/2026 02:13 PM 2E-D-010B FAIL TIA Cat 6 Perm. Link 0 ft N/A 07/07/2026 02:15 PM 2E-D-011A PASS TIA Cat 6 Perm. Link 198 ft 3.8 dB (NEXT) 07/07/2026 02:20 PM 2E-D-011B FAIL TIA Cat 6 Perm. Link 0 ft N/A 07/07/2026 02:22 PM 2E-D-012A FAIL TIA Cat 6 Perm. Link 0 ft N/A 07/07/2026 02:02 PM 2E-D-012B FAIL TIA Cat 6 Perm. Link 0 ft N/A 07/07/2026 02:03 PM 2E-D-013A PASS TIA Cat 6 Perm. Link 210 ft 1.7 dB (NEXT) 07/07/2026 11:01 AM 2E-D-013B PASS TIA Cat 6 Perm. Link 211 ft 5.2 dB (NEXT) 07/07/2026 11:02 AM 2E-D-014A PASS TIA Cat 6 Perm. Link 214 ft 4.9 dB (NEXT) 07/07/2026 10:39 AM 2E-D-014B PASS TIA Cat 6 Perm. Link 214 ft 6.2 dB (NEXT) 07/07/2026 10:40 AM 2E-D-015A PASS TIA Cat 6 Perm. Link 204 ft 4.8 dB (NEXT) 07/07/2026 02:36 PM 2E-D-015B PASS TIA Cat 6 Perm. Link 204 ft 5.9 dB (NEXT) 07/07/2026 02:37 PM 2E-D-016A PASS* TIA Cat 6 Perm. Link 199 ft 1.1 dB (NEXT) 07/07/2026 02:29 PM 2E-D-016B PASS TIA Cat 6 Perm. Link 200 ft 3.9 dB (NEXT) 07/07/2026 02:30 PM 2E-D-017A PASS TIA Cat 6 Perm. Link 204 ft 4.4 dB (NEXT) 07/07/2026 02:32 PM 2E-D-017B PASS TIA Cat 6 Perm. Link 204 ft 2.0 dB (NEXT) 07/07/2026 02:33 PM 2E-D-018A FAIL TIA Cat 6 Perm. Link 0 ft N/A 07/07/2026 01:48 PM 2E-D-018B PASS TIA Cat 6 Perm. Link 199 ft 6.6 dB (NEXT) 07/07/2026 01:48 PM 2E-D-019A PASS TIA Cat 6 Perm. Link 204 ft 6.1 dB (NEXT) 07/07/2026 01:55 PM 2E-D-019B PASS TIA Cat 6 Perm. Link 205 ft 6.3 dB (NEXT) 07/07/2026 01:56 PM 2E-D-020A PASS TIA Cat 6 Perm. Link 194 ft 2.9 dB (NEXT) 07/07/2026 01:50 PM 2E-D-020B FAIL TIA Cat 6 Perm. Link 0 ft N/A 07/07/2026 01:52 PM 2E-D-021A PASS* TIA Cat 6 Perm. Link 187 ft 0.4 dB (NEXT) 07/07/2026 01:44 PM 2E-D-021B PASS TIA Cat 6 Perm. Link 188 ft 2.0 dB (NEXT) 07/07/2026 01:45 PM 2E-D-022A FAIL TIA Cat 6 Perm. Link 1 ft N/A 07/07/2026 02:26 PM 2E-D-022B PASS TIA Cat 6 Perm. Link 187 ft 4.2 dB (NEXT) 07/07/2026 02:27 PM 2E-D-023A PASS TIA Cat 6 Perm. Link 193 ft 2.8 dB (NEXT) 07/07/2026 02:05 PM 2E-D-023B PASS TIA Cat 6 Perm. Link 192 ft 7.8 dB (NEXT) 07/07/2026 02:06 PM 2E-D-024A PASS TIA Cat 6 Perm. Link 189 ft 3.5 dB (NEXT) 07/07/2026 02:17 PM 2E-D-024B FAIL TIA Cat 6 Perm. Link 0 ft N/A 07/07/2026 02:18 PM 2E-D-025A PASS TIA Cat 6 Perm. Link 196 ft 4.6 dB (NEXT) 07/07/2026 02:08 PM 2E-D-025B PASS TIA Cat 6 Perm. Link 196 ft 4.1 dB (NEXT) 07/07/2026 02:09 PM 2E-D-026A PASS TIA Cat 6 Perm. Link 196 ft 3.3 dB (NEXT) 07/07/2026 01:32 PM 2E-D-026B PASS TIA Cat 6 Perm. Link 196 ft 5.6 dB (NEXT) 07/07/2026 01:33 PM 2E-D-027A FAIL TIA Cat 6 Perm. Link 0 ft N/A 07/07/2026 01:36 PM 2E-D-027B FAIL TIA Cat 6 Perm. Link 0 ft N/A 07/07/2026 01:38 PM 2E-D-028A PASS TIA Cat 6 Perm. Link 194 ft 5.7 dB (NEXT) 07/07/2026 01:20 PM 2E-D-028B PASS TIA Cat 6 Perm. Link 194 ft 7.2 dB (NEXT) 07/07/2026 01:21 PM 2E-D-029A PASS TIA Cat 6 Perm. Link 187 ft 4.6 dB (NEXT) 07/07/2026 01:17 PM 2E-D-029B PASS TIA Cat 6 Perm. Link 187 ft 4.3 dB (NEXT) 07/07/2026 01:17 PM 2E-D-030A PASS TIA Cat 6 Perm. Link 168 ft 2.0 dB (NEXT) 07/07/2026 01:40 PM 2E-D-030B PASS TIA Cat 6 Perm. Link 167 ft 4.0 dB (NEXT) 07/07/2026 01:41 PM 2E-D-031A PASS TIA Cat 6 Perm. Link 174 ft 5.3 dB (NEXT) 07/07/2026 01:23 PM 2E-D-031B PASS TIA Cat 6 Perm. Link 174 ft 8.7 dB (NEXT) 07/07/2026 01:23 PM 2E-D-032A PASS* TIA Cat 6 Perm. Link 180 ft 0.3 dB (NEXT) 07/07/2026 01:26 PM 2E-D-032B PASS TIA Cat 6 Perm. Link 179 ft 6.9 dB (NEXT) 07/07/2026 01:27 PM 2E-D-033A FAIL TIA Cat 6 Perm. Link 1 ft N/A 07/07/2026 01:29 PM 2E-D-033B PASS TIA Cat 6 Perm. Link 185 ft 2.7 dB (NEXT) 07/07/2026 01:30 PM 2E-D-034A FAIL TIA Cat 6 Perm. Link 176 ft 3.1 dB (NEXT) 07/07/2026 12:41 PM 2E-D-034B FAIL TIA Cat 6 Perm. Link 0 ft N/A 07/07/2026 12:42 PM 2E-D-035A PASS TIA Cat 6 Perm. Link 169 ft 5.0 dB (NEXT) 07/07/2026 12:44 PM 2E-D-035B FAIL TIA Cat 6 Perm. Link 0 ft N/A 07/07/2026 12:45 PM 2E-D-036A FAIL TIA Cat 6 Perm. Link 0 ft N/A 07/07/2026 12:50 PM 2E-D-036B FAIL TIA Cat 6 Perm. Link 1 ft N/A 07/07/2026 12:50 PM 2E-D-037A PASS TIA Cat 6 Perm. Link 162 ft 3.0 dB (NEXT) 07/07/2026 12:47 PM 2E-D-037B PASS TIA Cat 6 Perm. Link 161 ft 6.6 dB (NEXT) 07/07/2026 12:47 PM 2E-D-038A PASS TIA Cat 6 Perm. Link 149 ft 6.9 dB (NEXT) 07/07/2026 12:37 PM 2E-D-038B PASS TIA Cat 6 Perm. Link 149 ft 3.7 dB (NEXT) 07/07/2026 12:37 PM 2E-D-039A PASS TIA Cat 6 Perm. Link 157 ft 6.5 dB (NEXT) 07/08/2026 09:48 AM 2E-D-039B PASS TIA Cat 6 Perm. Link 157 ft 6.5 dB (NEXT) 07/08/2026 09:49 AM 2E-D-041A PASS TIA Cat 6 Perm. Link 190 ft 3.9 dB (NEXT) 07/07/2026 01:13 PM
2E-D-041B PASS* TIA Cat 6 Perm. Link 191 ft 3.9 dB (NEXT) 07/07/2026 01:15 PM
07/10/2026 02:48:19 PM Page 1 USMC Marsh Building Test Results.flw
2E-D-042A PASS TIA Cat 6 Perm. Link 187 ft 4.5 dB (NEXT) 07/07/2026 01:10 PM 2E-D-042B PASS TIA Cat 6 Perm. Link 187 ft 3.9 dB (NEXT) 07/07/2026 01:11 PM 2E-D-043A PASS TIA Cat 6 Perm. Link 162 ft 5.8 dB (NEXT) 07/07/2026 02:58 PM 2E-D-043B PASS TIA Cat 6 Perm. Link 161 ft 1.9 dB (NEXT) 07/07/2026 02:59 PM 2E-D-044A PASS TIA Cat 6 Perm. Link 146 ft 5.9 dB (NEXT) 07/07/2026 10:05 AM 2E-D-044B FAIL TIA Cat 6 Perm. Link 0 ft N/A 07/07/2026 10:06 AM 2E-D-045A PASS TIA Cat 6 Perm. Link 137 ft 1.1 dB (NEXT) 07/07/2026 09:58 AM 2E-D-045B FAIL TIA Cat 6 Perm. Link 1 ft -1.3 dB (NEXT) 07/07/2026 10:00 AM 2E-D-048A PASS TIA Cat 6 Perm. Link 169 ft 3.2 dB (NEXT) 07/07/2026 12:33 PM 2E-D-048B PASS TIA Cat 6 Perm. Link 169 ft 5.7 dB (NEXT) 07/07/2026 12:33 PM 2E-D-049A PASS TIA Cat 6 Perm. Link 172 ft 3.3 dB (NEXT) 07/07/2026 12:29 PM 2E-D-049B PASS TIA Cat 6 Perm. Link 172 ft 7.6 dB (NEXT) 07/07/2026 12:30 PM 2E-D-050A PASS TIA Cat 6 Perm. Link 151 ft 3.0 dB (NEXT) 07/07/2026 12:26 PM 2E-D-050B PASS TIA Cat 6 Perm. Link 151 ft 4.5 dB (NEXT) 07/07/2026 12:27 PM 2E-D-051A PASS TIA Cat 6 Perm. Link 157 ft 6.0 dB (NEXT) 07/07/2026 12:24 PM 2E-D-051B PASS TIA Cat 6 Perm. Link 157 ft 5.8 dB (NEXT) 07/07/2026 12:25 PM 2E-D-052A PASS TIA Cat 6 Perm. Link 157 ft 5.9 dB (NEXT) 07/07/2026 12:21 PM 2E-D-052B PASS TIA Cat 6 Perm. Link 158 ft 7.9 dB (NEXT) 07/07/2026 12:22 PM 2E-D-053A PASS TIA Cat 6 Perm. Link 165 ft 4.8 dB (NEXT) 07/07/2026 12:52 PM 2E-D-053B PASS TIA Cat 6 Perm. Link 165 ft 7.9 dB (NEXT) 07/07/2026 12:53 PM 2E-D-054A PASS TIA Cat 6 Perm. Link 173 ft 5.3 dB (NEXT) 07/07/2026 12:55 PM 2E-D-054B PASS TIA Cat 6 Perm. Link 173 ft 3.6 dB (NEXT) 07/07/2026 12:56 PM 2E-D-055A PASS TIA Cat 6 Perm. Link 172 ft 4.1 dB (NEXT) 07/07/2026 12:57 PM 2E-D-055B PASS TIA Cat 6 Perm. Link 172 ft 4.4 dB (NEXT) 07/07/2026 12:58 PM 2E-D-056A PASS TIA Cat 6 Perm. Link 152 ft 2.6 dB (NEXT) 07/07/2026 01:00 PM 2E-D-056B PASS TIA Cat 6 Perm. Link 152 ft 6.9 dB (NEXT) 07/07/2026 01:00 PM 2E-D-057A PASS TIA Cat 6 Perm. Link 158 ft 6.7 dB (NEXT) 07/07/2026 01:03 PM 2E-D-057B PASS TIA Cat 6 Perm. Link 158 ft 7.5 dB (NEXT) 07/07/2026 01:03 PM 2E-D-058A PASS TIA Cat 6 Perm. Link 159 ft 5.8 dB (NEXT) 07/07/2026 01:06 PM 2E-D-058B PASS TIA Cat 6 Perm. Link 159 ft 3.7 dB (NEXT) 07/07/2026 01:07 PM 2E-D-059A PASS TIA Cat 6 Perm. Link 144 ft 7.1 dB (NEXT) 07/07/2026 09:49 AM 2E-D-059B PASS TIA Cat 6 Perm. Link 147 ft 4.9 dB (NEXT) 07/07/2026 09:50 AM 2E-D-060A PASS TIA Cat 6 Perm. Link 139 ft 4.5 dB (NEXT) 07/07/2026 09:52 AM 2E-D-060B PASS TIA Cat 6 Perm. Link 139 ft 8.2 dB (NEXT) 07/07/2026 09:53 AM 2E-D-061A PASS TIA Cat 6 Perm. Link 135 ft 7.0 dB (NEXT) 07/07/2026 09:55 AM 2E-D-061B PASS TIA Cat 6 Perm. Link 133 ft 1.2 dB (NEXT) 07/07/2026 09:56 AM 2E-D-062A PASS TIA Cat 6 Perm. Link 139 ft 4.3 dB (NEXT) 07/07/2026 09:45 AM 2E-D-062B PASS TIA Cat 6 Perm. Link 138 ft 5.0 dB (NEXT) 07/07/2026 09:46 AM 2E-D-063A PASS TIA Cat 6 Perm. Link 132 ft 5.7 dB (NEXT) 07/07/2026 09:41 AM 2E-D-063B PASS TIA Cat 6 Perm. Link 130 ft 3.2 dB (NEXT) 07/07/2026 09:42 AM 2E-D-064A PASS TIA Cat 6 Perm. Link 125 ft 3.2 dB (NEXT) 07/07/2026 09:38 AM 2E-D-064B PASS TIA Cat 6 Perm. Link 125 ft 6.9 dB (NEXT) 07/07/2026 09:39 AM 2E-D-065A FAIL TIA Cat 6 Perm. Link 124 ft N/A 07/07/2026 09:33 AM 2E-D-065B PASS TIA Cat 6 Perm. Link 124 ft 2.9 dB (NEXT) 07/07/2026 09:34 AM 2E-D-066A PASS TIA Cat 6 Perm. Link 131 ft 6.3 dB (NEXT) 07/07/2026 09:29 AM 2E-D-066B PASS TIA Cat 6 Perm. Link 130 ft 6.2 dB (NEXT) 07/07/2026 09:30 AM 2E-D-067A PASS TIA Cat 6 Perm. Link 138 ft 6.4 dB (NEXT) 07/07/2026 09:26 AM 2E-D-067B PASS TIA Cat 6 Perm. Link 138 ft 4.5 dB (NEXT) 07/07/2026 09:27 AM 2E-D-068A PASS TIA Cat 6 Perm. Link 118 ft 6.3 dB (NEXT) 07/07/2026 09:22 AM 2E-D-068B FAIL TIA Cat 6 Perm. Link 1 ft N/A 07/07/2026 09:23 AM 2E-D-069A PASS TIA Cat 6 Perm. Link 112 ft 5.5 dB (NEXT) 07/07/2026 09:20 AM 2E-D-069B PASS TIA Cat 6 Perm. Link 112 ft 3.7 dB (NEXT) 07/07/2026 09:20 AM 2E-D-070A PASS TIA Cat 6 Perm. Link 104 ft 7.2 dB (NEXT) 07/07/2026 09:17 AM 2E-D-070B PASS TIA Cat 6 Perm. Link 105 ft 6.3 dB (NEXT) 07/07/2026 09:18 AM 2E-D-071A PASS TIA Cat 6 Perm. Link 113 ft 5.3 dB (NEXT) 07/07/2026 09:12 AM 2E-D-071B PASS TIA Cat 6 Perm. Link 114 ft 4.1 dB (NEXT) 07/07/2026 09:12 AM 2E-D-072A PASS TIA Cat 6 Perm. Link 123 ft 2.7 dB (NEXT) 07/07/2026 09:09 AM 2E-D-072B PASS TIA Cat 6 Perm. Link 123 ft 4.0 dB (NEXT) 07/07/2026 09:09 AM 2E-D-073A PASS TIA Cat 6 Perm. Link 105 ft 6.5 dB (NEXT) 07/07/2026 08:59 AM 2E-D-073B FAIL TIA Cat 6 Perm. Link 0 ft N/A 07/07/2026 09:00 AM 2E-D-074A PASS TIA Cat 6 Perm. Link 107 ft 8.6 dB (NEXT) 07/07/2026 08:56 AM 2E-D-074B PASS TIA Cat 6 Perm. Link 107 ft 5.6 dB (NEXT) 07/07/2026 08:57 AM 2E-D-076A PASS TIA Cat 6 Perm. Link 113 ft 6.6 dB (NEXT) 07/07/2026 12:13 PM 2E-D-076B PASS TIA Cat 6 Perm. Link 112 ft 7.2 dB (NEXT) 07/07/2026 12:15 PM 2E-D-077A PASS TIA Cat 6 Perm. Link 109 ft 6.8 dB (NEXT) 07/07/2026 12:10 PM 2E-D-077B PASS TIA Cat 6 Perm. Link 103 ft 4.9 dB (NEXT) 07/07/2026 12:11 PM 2E-D-078A PASS TIA Cat 6 Perm. Link 100 ft 4.9 dB (NEXT) 07/07/2026 12:07 PM 2E-D-078B PASS TIA Cat 6 Perm. Link 102 ft 6.5 dB (NEXT) 07/07/2026 12:07 PM 2E-D-079A PASS TIA Cat 6 Perm. Link 94 ft 5.7 dB (NEXT) 07/07/2026 10:25 AM 2E-D-079B FAIL TIA Cat 6 Perm. Link 92 ft -3.0 dB (NEXT) 07/07/2026 10:27 AM 2E-D-080A PASS TIA Cat 6 Perm. Link 104 ft 6.6 dB (NEXT) 07/07/2026 12:16 PM 2E-D-080B FAIL TIA Cat 6 Perm. Link 103 ft -0.6 dB (NEXT) 07/07/2026 12:18 PM 2E-D-081A PASS TIA Cat 6 Perm. Link 76 ft 4.0 dB (NEXT) 07/07/2026 08:26 AM 2E-D-081B PASS TIA Cat 6 Perm. Link 76 ft 1.1 dB (NEXT) 07/07/2026 08:29 AM 2E-D-082A PASS TIA Cat 6 Perm. Link 88 ft 5.8 dB (NEXT) 07/07/2026 08:32 AM 2E-D-082B PASS TIA Cat 6 Perm. Link 89 ft 5.7 dB (NEXT) 07/07/2026 08:34 AM 2E-D-083A PASS TIA Cat 6 Perm. Link 94 ft 3.5 dB (NEXT) 07/07/2026 08:36 AM
2E-D-083B PASS TIA Cat 6 Perm. Link 95 ft 2.6 dB (NEXT) 07/07/2026 08:36 AM
07/10/2026 02:48:19 PM Page 2
2E-D-084A PASS TIA Cat 6 Perm. Link 90 ft 5.6 dB (NEXT) 07/07/2026 08:40 AM 2E-D-084B FAIL TIA Cat 6 Perm. Link 0 ft N/A 07/07/2026 08:41 AM 2E-D-085A FAIL TIA Cat 6 Perm. Link 0 ft N/A 07/07/2026 08:45 AM 2E-D-085B PASS TIA Cat 6 Perm. Link 83 ft 5.0 dB (NEXT) 07/07/2026 08:45 AM 2E-D-086A FAIL TIA Cat 6 Perm. Link 0 ft N/A 07/07/2026 08:48 AM 2E-D-086B PASS TIA Cat 6 Perm. Link 76 ft 7.6 dB (NEXT) 07/07/2026 08:50 AM 2E-D-087A PASS TIA Cat 6 Perm. Link 142 ft 7.4 dB (NEXT) 07/09/2026 10:46 AM 2E-D-087B PASS TIA Cat 6 Perm. Link 142 ft 4.9 dB (NEXT) 07/09/2026 10:47 AM 2E-D-088A PASS TIA Cat 6 Perm. Link 142 ft 4.3 dB (NEXT) 07/09/2026 10:34 AM 2E-D-088B PASS TIA Cat 6 Perm. Link 143 ft 6.1 dB (NEXT) 07/09/2026 10:35 AM 2E-D-089A PASS TIA Cat 6 Perm. Link 142 ft 6.2 dB (NEXT) 07/09/2026 10:35 AM 2E-D-089B PASS TIA Cat 6 Perm. Link 142 ft 6.9 dB (NEXT) 07/09/2026 10:35 AM 2E-D-090A PASS TIA Cat 6 Perm. Link 142 ft 5.8 dB (NEXT) 07/09/2026 10:40 AM 2E-D-090B PASS TIA Cat 6 Perm. Link 142 ft 5.1 dB (NEXT) 07/09/2026 10:41 AM 2E-D-091A FAIL TIA Cat 6 Perm. Link 126 ft N/A 07/09/2026 10:29 AM 2E-D-091B PASS TIA Cat 6 Perm. Link 126 ft 6.9 dB (NEXT) 07/09/2026 10:29 AM 2E-D-092A FAIL TIA Cat 6 Perm. Link 125 ft -1.8 dB (NEXT) 07/09/2026 10:30 AM 2E-D-092B PASS TIA Cat 6 Perm. Link 126 ft 5.4 dB (NEXT) 07/09/2026 10:31 AM 2E-D-093A PASS TIA Cat 6 Perm. Link 127 ft 1.6 dB (NEXT) 07/09/2026 10:31 AM 2E-D-093B PASS TIA Cat 6 Perm. Link 127 ft 7.6 dB (NEXT) 07/09/2026 10:31 AM 2E-D-094A FAIL TIA Cat 6 Perm. Link 127 ft -0.9 dB (NEXT) 07/09/2026 10:32 AM 2E-D-094B PASS TIA Cat 6 Perm. Link 129 ft 3.2 dB (NEXT) 07/09/2026 10:32 AM 2E-D-095A PASS* TIA Cat 6 Perm. Link 128 ft 0.8 dB (NEXT) 07/09/2026 10:33 AM 2E-D-095B PASS TIA Cat 6 Perm. Link 127 ft 2.3 dB (NEXT) 07/09/2026 10:33 AM 2E-D-096A PASS TIA Cat 6 Perm. Link 127 ft 6.0 dB (NEXT) 07/09/2026 10:33 AM 2E-D-096B PASS TIA Cat 6 Perm. Link 128 ft 7.0 dB (NEXT) 07/09/2026 10:34 AM 2E-D-097A PASS TIA Cat 6 Perm. Link 113 ft 7.7 dB (NEXT) 07/09/2026 10:27 AM 2E-D-097B PASS TIA Cat 6 Perm. Link 114 ft 6.7 dB (NEXT) 07/09/2026 10:27 AM 2E-D-098A PASS TIA Cat 6 Perm. Link 114 ft 7.8 dB (NEXT) 07/09/2026 10:22 AM 2E-D-098B PASS TIA Cat 6 Perm. Link 114 ft 8.4 dB (NEXT) 07/09/2026 10:22 AM 2E-D-099A PASS TIA Cat 6 Perm. Link 114 ft 1.9 dB (NEXT) 07/09/2026 10:24 AM 2E-D-099B PASS TIA Cat 6 Perm. Link 113 ft 6.4 dB (NEXT) 07/09/2026 10:24 AM 2E-D-100A PASS TIA Cat 6 Perm. Link 112 ft 7.1 dB (NEXT) 07/09/2026 10:25 AM 2E-D-100B PASS TIA Cat 6 Perm. Link 112 ft 6.2 dB (NEXT) 07/09/2026 10:25 AM 2E-D-101A PASS TIA Cat 6 Perm. Link 112 ft 7.1 dB (NEXT) 07/09/2026 10:25 AM 2E-D-101B PASS TIA Cat 6 Perm. Link 113 ft 5.5 dB (NEXT) 07/09/2026 10:26 AM 2E-D-102A PASS TIA Cat 6 Perm. Link 112 ft 3.5 dB (NEXT) 07/09/2026 10:26 AM 2E-D-102B PASS TIA Cat 6 Perm. Link 112 ft 5.5 dB (NEXT) 07/09/2026 10:26 AM 2E-D-103A PASS TIA Cat 6 Perm. Link 126 ft 8.4 dB (NEXT) 07/09/2026 11:02 AM 2E-D-103B PASS TIA Cat 6 Perm. Link 127 ft 5.9 dB (NEXT) 07/09/2026 11:03 AM 2E-D-104A PASS TIA Cat 6 Perm. Link 155 ft 5.9 dB (NEXT) 07/09/2026 10:58 AM 2E-D-104B PASS TIA Cat 6 Perm. Link 154 ft 5.6 dB (NEXT) 07/09/2026 10:58 AM 2E-D-105A FAIL TIA Cat 6 Perm. Link 154 ft N/A 07/09/2026 10:53 AM 2E-D-105B PASS TIA Cat 6 Perm. Link 155 ft 5.2 dB (NEXT) 07/09/2026 10:55 AM 2E-D-106A PASS TIA Cat 6 Perm. Link 154 ft 6.1 dB (NEXT) 07/09/2026 10:55 AM 2E-D-106B PASS TIA Cat 6 Perm. Link 154 ft 4.9 dB (NEXT) 07/09/2026 10:54 AM 2E-D-107A PASS TIA Cat 6 Perm. Link 155 ft 2.9 dB (NEXT) 07/09/2026 10:55 AM 2E-D-107B PASS TIA Cat 6 Perm. Link 153 ft 7.9 dB (NEXT) 07/09/2026 10:56 AM 2E-D-108A PASS TIA Cat 6 Perm. Link 154 ft 4.0 dB (NEXT) 07/09/2026 10:56 AM 2E-D-108B FAIL TIA Cat 6 Perm. Link 154 ft -0.5 dB (NEXT) 07/09/2026 10:56 AM 2E-D-109A PASS TIA Cat 6 Perm. Link 154 ft 4.4 dB (NEXT) 07/09/2026 10:57 AM 2E-D-109B PASS TIA Cat 6 Perm. Link 154 ft 7.3 dB (NEXT) 07/09/2026 10:57 AM 2E-D-110A PASS TIA Cat 6 Perm. Link 140 ft 5.8 dB (NEXT) 07/09/2026 10:49 AM 2E-D-110B PASS TIA Cat 6 Perm. Link 140 ft 2.4 dB (NEXT) 07/09/2026 10:49 AM 2E-D-111A PASS TIA Cat 6 Perm. Link 142 ft 5.7 dB (NEXT) 07/09/2026 10:50 AM 2E-D-111B FAIL TIA Cat 6 Perm. Link 141 ft N/A 07/09/2026 10:51 AM 2E-D-112A PASS* TIA Cat 6 Perm. Link 132 ft 0.6 dB (NEXT) 07/10/2026 07:25 AM 2E-D-112B PASS TIA Cat 6 Perm. Link 132 ft 7.2 dB (NEXT) 07/10/2026 07:25 AM 2E-D-113B PASS TIA Cat 6 Perm. Link 133 ft 5.5 dB (NEXT) 07/10/2026 07:23 AM 2E-D-114A PASS TIA Cat 6 Perm. Link 132 ft 4.7 dB (NEXT) 07/10/2026 07:15 AM 2E-D-114B PASS TIA Cat 6 Perm. Link 132 ft 2.7 dB (NEXT) 07/10/2026 07:15 AM 2E-D-115A PASS TIA Cat 6 Perm. Link 154 ft 4.2 dB (NEXT) 07/10/2026 07:12 AM 2E-D-115B PASS TIA Cat 6 Perm. Link 152 ft 5.1 dB (NEXT) 07/10/2026 07:13 AM 2E-D-116A PASS TIA Cat 6 Perm. Link 150 ft 4.1 dB (NEXT) 07/10/2026 07:08 AM 2E-D-116B PASS TIA Cat 6 Perm. Link 152 ft 1.4 dB (NEXT) 07/10/2026 07:09 AM 2E-D-117A FAIL TIA Cat 6 Perm. Link 152 ft N/A 07/10/2026 07:06 AM 2E-D-117B PASS TIA Cat 6 Perm. Link 152 ft 5.5 dB (NEXT) 07/10/2026 07:06 AM 2E-D-118A PASS TIA Cat 6 Perm. Link 152 ft 2.7 dB (NEXT) 07/10/2026 07:05 AM 2E-D-118B PASS TIA Cat 6 Perm. Link 153 ft 5.2 dB (NEXT) 07/10/2026 07:04 AM 2E-D-119A FAIL TIA Cat 6 Perm. Link 160 ft -3.5 dB (NEXT) 07/08/2026 06:25 AM 2E-D-119B PASS TIA Cat 6 Perm. Link 159 ft 7.6 dB (NEXT) 07/08/2026 06:26 AM 2E-D-120A PASS TIA Cat 6 Perm. Link 166 ft 5.3 dB (NEXT) 07/08/2026 06:46 AM 2E-D-120B PASS TIA Cat 6 Perm. Link 165 ft 4.7 dB (NEXT) 07/08/2026 06:47 AM 2E-D-121A PASS TIA Cat 6 Perm. Link 165 ft 3.9 dB (NEXT) 07/08/2026 09:55 AM 2E-D-121B PASS TIA Cat 6 Perm. Link 165 ft 6.3 dB (NEXT) 07/08/2026 09:56 AM 2E-D-123A PASS TIA Cat 6 Perm. Link 120 ft 2.3 dB (NEXT) 07/10/2026 05:59 AM 2E-D-123B PASS TIA Cat 6 Perm. Link 119 ft 6.8 dB (NEXT) 07/10/2026 05:59 AM
2E-D-124A PASS TIA Cat 6 Perm. Link 120 ft 5.9 dB (NEXT) 07/10/2026 06:05 AM
07/10/2026 02:48:19 PM Page 3
2E-D-124B PASS TIA Cat 6 Perm. Link 120 ft 4.6 dB (NEXT) 07/10/2026 06:06 AM 2E-D-125A PASS TIA Cat 6 Perm. Link 98 ft 2.3 dB (NEXT) 07/10/2026 07:30 AM 2E-D-125B PASS TIA Cat 6 Perm. Link 98 ft 2.3 dB (NEXT) 07/10/2026 07:31 AM 2E-D-126A PASS TIA Cat 6 Perm. Link 96 ft 3.5 dB (NEXT) 07/10/2026 07:29 AM 2E-D-126B PASS TIA Cat 6 Perm. Link 96 ft 5.3 dB (NEXT) 07/10/2026 07:29 AM 2E-D-127A PASS TIA Cat 6 Perm. Link 89 ft 3.6 dB (NEXT) 07/10/2026 06:58 AM 2E-D-127B PASS TIA Cat 6 Perm. Link 90 ft 3.3 dB (NEXT) 07/10/2026 06:58 AM 2E-D-128A PASS TIA Cat 6 Perm. Link 85 ft 5.4 dB (NEXT) 07/10/2026 07:00 AM 2E-D-128B PASS TIA Cat 6 Perm. Link 85 ft 2.5 dB (NEXT) 07/10/2026 07:00 AM 2E-D-129A FAIL TIA Cat 6 Perm. Link 39 ft -0.6 dB (NEXT) 07/10/2026 07:40 AM 2E-D-129B PASS TIA Cat 6 Perm. Link 40 ft 4.5 dB (NEXT) 07/10/2026 07:38 AM 2E-D-130A PASS TIA Cat 6 Perm. Link 43 ft 4.0 dB (NEXT) 07/10/2026 07:41 AM 2E-D-130B PASS TIA Cat 6 Perm. Link 43 ft 1.7 dB (NEXT) 07/10/2026 07:41 AM 2E-D-134A FAIL TIA Cat 6 Perm. Link 84 ft N/A 07/07/2026 09:07 AM 2E-D-134B PASS TIA Cat 6 Perm. Link 84 ft 2.6 dB (NEXT) 07/07/2026 09:07 AM
07/10/2026 02:48:19 PM Page 4
Total Length: 33612 ft Number of Reports: 249 Number of Passing Reports: 212 Number of Failing Reports: 37 Number of Warning Reports: 0 Documentation Only: 0
07/10/2026 02:48:19 PM Page 5
2E-V-001 FAIL TIA Cat 6 Perm. Link 0 ft N/A 07/07/2026 10:58 AM 2E-V-002 PASS TIA Cat 6 Perm. Link 231 ft 5.8 dB (NEXT) 07/07/2026 10:24 AM 2E-V-003 FAIL TIA Cat 6 Perm. Link 218 ft N/A 07/07/2026 03:48 PM 2E-V-005 PASS TIA Cat 6 Perm. Link 224 ft 1.4 dB (NEXT) 07/07/2026 10:43 AM 2E-V-006 PASS TIA Cat 6 Perm. Link 231 ft 4.5 dB (NEXT) 07/07/2026 10:47 AM 2E-V-007 FAIL TIA Cat 6 Perm. Link 237 ft N/A 07/07/2026 10:50 AM 2E-V-008 FAIL TIA Cat 6 Perm. Link 209 ft N/A 07/07/2026 03:55 PM 2E-V-009 PASS TIA Cat 6 Perm. Link 206 ft 6.1 dB (NEXT) 07/07/2026 03:10 PM 2E-V-010 PASS TIA Cat 6 Perm. Link 204 ft 5.8 dB (NEXT) 07/07/2026 03:13 PM 2E-V-011 PASS TIA Cat 6 Perm. Link 199 ft 5.0 dB (NEXT) 07/07/2026 03:16 PM 2E-V-012 PASS TIA Cat 6 Perm. Link 193 ft 3.8 dB (NEXT) 07/07/2026 02:58 PM 2E-V-013 PASS TIA Cat 6 Perm. Link 211 ft 5.2 dB (NEXT) 07/07/2026 11:01 AM 2E-V-014 FAIL TIA Cat 6 Perm. Link 0 ft N/A 07/07/2026 10:41 AM 2E-V-015 PASS TIA Cat 6 Perm. Link 204 ft 5.5 dB (NEXT) 07/07/2026 03:36 PM 2E-V-016 PASS TIA Cat 6 Perm. Link 200 ft 6.4 dB (NEXT) 07/07/2026 03:29 PM 2E-V-017 PASS TIA Cat 6 Perm. Link 204 ft 5.9 dB (NEXT) 07/07/2026 03:32 PM 2E-V-018 FAIL TIA Cat 6 Perm. Link 0 ft N/A 07/07/2026 02:47 PM 2E-V-019 PASS TIA Cat 6 Perm. Link 206 ft 6.3 dB (NEXT) 07/07/2026 02:55 PM 2E-V-020 PASS TIA Cat 6 Perm. Link 196 ft 1.8 dB (NEXT) 07/07/2026 02:50 PM 2E-V-021 PASS TIA Cat 6 Perm. Link 189 ft 5.5 dB (NEXT) 07/07/2026 02:43 PM 2E-V-022 PASS TIA Cat 6 Perm. Link 187 ft 8.9 dB (NEXT) 07/07/2026 03:24 PM 2E-V-023 PASS TIA Cat 6 Perm. Link 194 ft 7.8 dB (NEXT) 07/07/2026 03:05 PM 2E-V-025 FAIL TIA Cat 6 Perm. Link 1 ft N/A 07/07/2026 03:08 PM 2E-V-026 PASS TIA Cat 6 Perm. Link 195 ft 9.1 dB (NEXT) 07/07/2026 02:32 PM 2E-V-027 PASS TIA Cat 6 Perm. Link 189 ft 6.4 dB (NEXT) 07/07/2026 02:35 PM 2E-V-028 PASS TIA Cat 6 Perm. Link 194 ft 6.1 dB (NEXT) 07/07/2026 02:19 PM 2E-V-029 PASS TIA Cat 6 Perm. Link 187 ft 6.4 dB (NEXT) 07/07/2026 02:17 PM 2E-V-030 PASS* TIA Cat 6 Perm. Link 169 ft 4.9 dB (NEXT) 07/07/2026 02:40 PM 2E-V-031 PASS TIA Cat 6 Perm. Link 174 ft 4.0 dB (NEXT) 07/07/2026 02:23 PM 2E-V-032 FAIL TIA Cat 6 Perm. Link 181 ft N/A 07/07/2026 02:26 PM 2E-V-033 FAIL TIA Cat 6 Perm. Link 187 ft 6.3 dB (NEXT) 07/07/2026 02:29 PM 2E-V-034 FAIL TIA Cat 6 Perm. Link 177 ft 1.5 dB (NEXT) 07/07/2026 01:40 PM 2E-V-035 PASS TIA Cat 6 Perm. Link 169 ft 5.7 dB (NEXT) 07/07/2026 01:44 PM 2E-V-036 PASS* TIA Cat 6 Perm. Link 154 ft 4.6 dB (NEXT) 07/07/2026 01:49 PM 2E-V-037 FAIL TIA Cat 6 Perm. Link 161 ft N/A 07/07/2026 01:47 PM 2E-V-038 FAIL TIA Cat 6 Perm. Link 149 ft N/A 07/07/2026 01:36 PM 2E-V-039 FAIL TIA Cat 6 Perm. Link 0 ft N/A 07/08/2026 10:48 AM 2E-V-041 PASS TIA Cat 6 Perm. Link 191 ft 7.6 dB (NEXT) 07/07/2026 02:13 PM 2E-V-042 PASS TIA Cat 6 Perm. Link 188 ft 4.9 dB (NEXT) 07/07/2026 02:11 PM 2E-V-043 FAIL TIA Cat 6 Perm. Link 165 ft 0.0 dB (NEXT) 07/07/2026 03:58 PM 2E-V-044 PASS TIA Cat 6 Perm. Link 147 ft 7.2 dB (NEXT) 07/07/2026 09:58 AM 2E-V-045 FAIL TIA Cat 6 Perm. Link 0 ft N/A 07/07/2026 10:08 AM 2E-V-048 PASS TIA Cat 6 Perm. Link 170 ft 6.9 dB (NEXT) 07/07/2026 01:32 PM 2E-V-049 PASS TIA Cat 6 Perm. Link 170 ft 6.3 dB (NEXT) 07/07/2026 01:29 PM 2E-V-050 PASS TIA Cat 6 Perm. Link 149 ft 4.2 dB (NEXT) 07/07/2026 01:26 PM 2E-V-051 PASS TIA Cat 6 Perm. Link 156 ft 5.9 dB (NEXT) 07/07/2026 01:24 PM 2E-V-052 PASS* TIA Cat 6 Perm. Link 156 ft 0.6 dB (NEXT) 07/07/2026 12:21 PM 2E-V-053 PASS TIA Cat 6 Perm. Link 165 ft 6.8 dB (NEXT) 07/07/2026 01:52 PM 2E-V-054 PASS TIA Cat 6 Perm. Link 172 ft 7.6 dB (NEXT) 07/07/2026 01:55 PM 2E-V-055 FAIL TIA Cat 6 Perm. Link 0 ft N/A 07/07/2026 01:58 PM 2E-V-056 PASS TIA Cat 6 Perm. Link 151 ft 5.5 dB (NEXT) 07/07/2026 02:00 PM 2E-V-057 PASS TIA Cat 6 Perm. Link 156 ft 6.4 dB (NEXT) 07/07/2026 02:03 PM 2E-V-058 PASS TIA Cat 6 Perm. Link 158 ft 9.0 dB (NEXT) 07/07/2026 02:05 PM 2E-V-059 PASS TIA Cat 6 Perm. Link 142 ft 5.9 dB (NEXT) 07/07/2026 09:48 AM 2E-V-060 PASS TIA Cat 6 Perm. Link 138 ft 5.4 dB (NEXT) 07/07/2026 09:52 AM 2E-V-061 FAIL TIA Cat 6 Perm. Link 0 ft N/A 07/07/2026 09:54 AM 2E-V-062 PASS TIA Cat 6 Perm. Link 137 ft 6.2 dB (NEXT) 07/07/2026 09:44 AM 2E-V-063 FAIL TIA Cat 6 Perm. Link 0 ft N/A 07/07/2026 09:41 AM 2E-V-064 FAIL TIA Cat 6 Perm. Link 124 ft N/A 07/07/2026 09:36 AM 2E-V-065 PASS TIA Cat 6 Perm. Link 123 ft 6.3 dB (NEXT) 07/07/2026 09:32 AM 2E-V-066 PASS TIA Cat 6 Perm. Link 129 ft 6.2 dB (NEXT) 07/07/2026 09:29 AM 2E-V-067 PASS TIA Cat 6 Perm. Link 137 ft 2.8 dB (NEXT) 07/07/2026 09:26 AM 2E-V-068 FAIL TIA Cat 6 Perm. Link 112 ft N/A 07/07/2026 09:22 AM 2E-V-069 FAIL TIA Cat 6 Perm. Link 109 ft N/A 07/07/2026 09:19 AM 2E-V-070 PASS TIA Cat 6 Perm. Link 102 ft 7.3 dB (NEXT) 07/07/2026 09:15 AM 2E-V-071 FAIL TIA Cat 6 Perm. Link 112 ft N/A 07/07/2026 09:11 AM 2E-V-072 PASS TIA Cat 6 Perm. Link 120 ft 6.8 dB (NEXT) 07/07/2026 09:09 AM 2E-V-073 PASS TIA Cat 6 Perm. Link 103 ft 6.6 dB (NEXT) 07/07/2026 08:59 AM 2E-V-074 PASS TIA Cat 6 Perm. Link 105 ft 6.3 dB (NEXT) 07/07/2026 08:56 AM 2E-V-076 PASS TIA Cat 6 Perm. Link 112 ft 7.0 dB (NEXT) 07/07/2026 12:12 PM 2E-V-077 PASS TIA Cat 6 Perm. Link 108 ft 5.2 dB (NEXT) 07/07/2026 12:06 PM 2E-V-078 FAIL TIA Cat 6 Perm. Link 100 ft -9.0 dB (NEXT) 07/07/2026 12:05 PM 2E-V-080 FAIL TIA Cat 6 Perm. Link 103 ft N/A 07/07/2026 12:16 PM 2E-V-081 PASS TIA Cat 6 Perm. Link 75 ft 5.6 dB (NEXT) 07/07/2026 08:25 AM 2E-V-082 PASS TIA Cat 6 Perm. Link 86 ft 5.9 dB (NEXT) 07/07/2026 08:33 AM 2E-V-083 PASS TIA Cat 6 Perm. Link 92 ft 1.1 dB (NEXT) 07/07/2026 08:36 AM 2E-V-084 PASS TIA Cat 6 Perm. Link 89 ft 3.6 dB (NEXT) 07/07/2026 08:37 AM
2E-V-085 PASS TIA Cat 6 Perm. Link 82 ft 4.9 dB (NEXT) 07/07/2026 08:44 AM
07/10/2026
02:50:20 PM
2E-V-086 FAIL TIA Cat 6 Perm. Link 76 ft N/A 07/07/2026 08:48 AM 2E-V-087 PASS TIA Cat 6 Perm. Link 140 ft 7.2 dB (NEXT) 07/09/2026 11:31 AM 2E-V-088 PASS TIA Cat 6 Perm. Link 140 ft 3.6 dB (NEXT) 07/09/2026 11:35 AM 2E-V-089 PASS TIA Cat 6 Perm. Link 140 ft 4.9 dB (NEXT) 07/09/2026 11:35 AM 2E-V-090 PASS TIA Cat 6 Perm. Link 140 ft 5.2 dB (NEXT) 07/09/2026 11:36 AM 2E-V-091 PASS TIA Cat 6 Perm. Link 140 ft 6.5 dB (NEXT) 07/09/2026 11:36 AM 2E-V-092 PASS TIA Cat 6 Perm. Link 121 ft 4.5 dB (NEXT) 07/09/2026 11:27 AM 2E-V-093 PASS TIA Cat 6 Perm. Link 123 ft 6.5 dB (NEXT) 07/09/2026 11:29 AM 2E-V-094 PASS TIA Cat 6 Perm. Link 123 ft 5.4 dB (NEXT) 07/09/2026 11:29 AM 2E-V-095 PASS TIA Cat 6 Perm. Link 124 ft 6.7 dB (NEXT) 07/09/2026 11:29 AM 2E-V-096 PASS TIA Cat 6 Perm. Link 123 ft 6.4 dB (NEXT) 07/09/2026 11:30 AM 2E-V-097 FAIL TIA Cat 6 Perm. Link 123 ft N/A 07/09/2026 11:30 AM 2E-V-098 PASS TIA Cat 6 Perm. Link 110 ft 4.4 dB (NEXT) 07/09/2026 11:21 AM 2E-V-099 PASS TIA Cat 6 Perm. Link 110 ft 6.8 dB (NEXT) 07/09/2026 11:24 AM 2E-V-100 PASS TIA Cat 6 Perm. Link 110 ft 6.2 dB (NEXT) 07/09/2026 11:25 AM 2E-V-101 PASS TIA Cat 6 Perm. Link 109 ft 5.2 dB (NEXT) 07/09/2026 11:25 AM 2E-V-102 PASS TIA Cat 6 Perm. Link 110 ft 5.7 dB (NEXT) 07/09/2026 11:25 AM 2E-V-103 PASS TIA Cat 6 Perm. Link 110 ft 6.8 dB (NEXT) 07/09/2026 11:26 AM 2E-V-104 PASS TIA Cat 6 Perm. Link 123 ft 3.5 dB (NEXT) 07/09/2026 12:02 PM 2E-V-105 PASS TIA Cat 6 Perm. Link 152 ft 5.6 dB (NEXT) 07/09/2026 11:59 AM 2E-V-106 PASS TIA Cat 6 Perm. Link 151 ft 6.3 dB (NEXT) 07/09/2026 11:59 AM 2E-V-107 PASS TIA Cat 6 Perm. Link 152 ft 4.6 dB (NEXT) 07/09/2026 11:59 AM 2E-V-108 PASS TIA Cat 6 Perm. Link 151 ft 4.9 dB (NEXT) 07/09/2026 12:00 PM 2E-V-109 PASS TIA Cat 6 Perm. Link 152 ft 7.6 dB (NEXT) 07/09/2026 12:00 PM 2E-V-110 FAIL TIA Cat 6 Perm. Link 151 ft N/A 07/09/2026 12:01 PM 2E-V-112 PASS TIA Cat 6 Perm. Link 130 ft 5.8 dB (NEXT) 07/10/2026 08:25 AM 2E-V-113 PASS TIA Cat 6 Perm. Link 130 ft 5.9 dB (NEXT) 07/10/2026 08:19 AM 2E-V-115 PASS TIA Cat 6 Perm.
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .