This submittal package provides technical specifications and performance data for replacement of evaporative cooling equipment at the VA Montana Healthcare System. Innovent Inc. proposes to remove existing equipment and install new direct evaporative cooling units and energy recovery units. The submittal includes specifications, drawings, fan curves and sound data for the ERU-1 and EVAP-1/2 units. Controls are standalone DDC controllers from Innovent programmed to sequence operation of fans, dampers and cooling based on temperature setpoints. This submittal package from Innovent Inc. responds to solicitation number 36C25922R0027 issued by the Department of Veterans Affairs for replacement of evaporative coolers at the VA facility in Montana.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| DB Construction Experience Sheet.docx | DOCX document | |
| 36C25922R0027_1.docx | DOCX document | |
| Past Performance Questionnaire.docx | DOCX document | |
| Drawings - VA-FT HAR AS-BLTS Laundry.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Issue 1 Job #: 2090011
Contractor’s representative: Engineer’s representative: Submitted by:
S. Conley Sales, Inc. S. Conley Sales, Inc. Innovent Inc.
317 Gallatin Park Dr. 317 Gallatin Park Dr. Mailing: 60 – 28th Ave N.
Bozeman, MT 59715 Bozeman, MT 59715 Shipping: 61 – 30th Ave. N.
(406) 585-7333 (406) 585-7333 Minneapolis, Minnesota 612-877-4800
Innovent Submittal
Date: May 8th, 2014
Project: Fort Harrison Lab & Laundry
Location: Fort Harrison, MT
Innovent Job #: 2090011
Submittal Issue: 1
Engineer:
Contractor:
Tag Innovent Model #
ERU-1 ERU-OU-PL-15000-208
EVAP-1 CAHU-4000-DV-208
EVAP-2 CAHU-4000-DV-208
Checklist / Approval
Innovent utilizes the submittal process to clarify our interpretation of the plans and specifications. Please review the submittal carefully as Innovent will manufacture the equipment as ordered per the approved submittal.
Approval Date
� Location of condensate drains
� Location of duct connections
� Fan rotation arrangement
� Location of coil connections
� Location of electrical panel
� Location of access doors
� Electrical service voltage
� Mounting (curb/slab)
Engineer’s Approval Stamp: Contractor’s Approval Stamp:
Architect’s Approval Stamp: Other Approval Stamp:
Contents
Section 1 / Engineering Data
Specification Sequence of Operation
Performance Data Summary Fan Curves
Drawings Unit Airflow Schematic Unit Drawing Base/Curb Detail Curb Detail Drawing Drain Connection/Trap Detail DEC Piping Schematic Unit Power Schematic
ETL Listing Report
ANSI/ U.L. 1995: Heating and Cooling Equipment
Innovent Standard Warranty
Section 2 / Components Provided By Others
ERU-1 ONLY
CASING PERFORMANCE:
• Leakage class rating of 5.0
• Maximum panel deflection shall not exceed L/250 at design total static pressure
• Minimum R-12 insulation value for walls, ceiling and flooring
• The panel insertion loss, per octave band, shall not be less than the following:
Frequency: 100 125 250 500 1000 2000 4000 8000 Insertion loss, dB: 24 16 30 32 33 34 63 60
CASING MATERIALS:
• 2 pcf polyurethane foam insulation in walls, ceiling and floor
• 10 ga. formed and welded steel base, coated with Innovent standard grey paint
• 2” double wall floor panels
• 18 ga. G90 galvanized inner floor
• 22 ga. G90 galvanized outer floor
• 16 ga. G90 galvanized and 0.080” aluminum frame
• 2” double wall casing panels
• 16 ga galvanized outer wall coated with high performance polyester finish, Innovent standard grey
• 22 ga. G90 galvanized inner wall
• Outdoor construction
• 18 ga. galvanized pitched roof coated with high performance polyester finish, Innovent standard grey
• Standing seams
• Roof extends beyond edge of unit
• Hoods with aluminum bird screen for exposed inlets and outlets
• Unit shall be shipped as a single piece of equipment
CASING ACCESS:
• Double wall access doors insulated with 2 pcf polyurethane foam
• Stainless steel piano hinges
• Aluminum frame
• Corrosion resistant compression latches
• Tool lockable access handles provided for all doors
• All other panels are fully removable unless otherwise identified on the unit drawings.
AIR TO AIR HEAT EXCHANGER:
• Cross flow flat plate type.
• 8 mil smooth aluminum plates separated by formed ribs
• Aluminum framing & end plates
• Stainless steel drain pans (must be trapped and freeze protected in the field by the installing contractor)
SUPPLY FAN & MOTORS:
• 12 blade airfoil plenum fan, welded aluminum wheel, galvanized steel frame
• AMCA certified ratings for sound and performance
• 1" deflection, seismic rated spring isolators
• L-50 250,000 hr pillow block bearings
• Fixed V-belt drive with service factor of 1.5 on motors larger than 10 HP or motors with VFDs
• Fan statically and dynamically balanced within 0.15 in/sec peak velocity
• Extended lube lines
• TEFC EPACT compliant motor
• Premium efficient
• Class F insulation
EXHAUST FAN & MOTORS:
• 12 blade airfoil plenum fan, welded aluminum wheel, galvanized steel frame
• AMCA certified ratings for sound and performance
• 1" deflection, seismic rated spring isolators
• L-50 250,000 hr pillow block bearings
• Fixed V-belt drive with service factor of 1.5 on motors larger than 10 HP or motors with VFDs
• Fan statically and dynamically balanced within 0.15 in/sec peak velocity
• Extended lube lines
• TEFC EPACT compliant motor
FILTERS:
OUTSIDE AIR:
• 2" pleated MERV 8 filter, 500 FPM maximum face velocity
• Side access
• Galvanized rack
RETURN AIR:
• 2" pleated MERV 8 filter, 500 FPM maximum face velocity
DAMPERS:
• Outside air heat exchanger face damper
• AMCA certified performance
• Electronically interlocked with bypass damper
• Formed galvanized blade with a leakage rating of 3 CFM at 1" wg
• 16 ga. galvanized frame
• Modulating actuator provided by Innovent
• Synthetic bearings
• Outside air heat exchanger bypass damper
• AMCA certified performance
• Electronically interlocked with face damper
• Formed galvanized blade with a leakage rating of 3 CFM at 1" wg
• 16 ga. galvanized frame
• Modulating actuator provided by Innovent
• Synthetic bearings
• Exhaust air gravity damper
• Tested in accordance with AMCA standard 500-D
• Formed aluminum blade
• .125" aluminum frame
ELECTRICAL:
• Single point 3-phase power connection with unit mounted disconnect
• Power wiring enclosed in conduit
• All wires terminated at the unit mounted NEMA 3R panel
• Unit is ETL listed per UL standard 1995 and CSA standard C22.2 #236
CONTROLS:
• Stand alone DDC controller provided by Innovent (factory programmed)
• BacNet MS/TP compatible
ACCESSORIES:
• 14" roof curb provided by Innovent for a flat roof. Curb will be shipped disassembled
WARRANTIES:
• Standard 1 year parts only warranty as described in the last page of this submittal.
EVAP-1, 2 ONLY
CASING PERFORMANCE:
• Leakage class rating of 5.0
• Maximum panel deflection shall not exceed L/250 at design total static pressure
• Minimum R-12 insulation value for walls, ceiling and flooring
• The panel insertion loss, per octave band, shall not be less than the following:
Frequency: 100 125 250 500 1000 2000 4000 8000 Insertion loss, dB: 24 16 30 32 33 34 63 60
CASING MATERIALS:
• 2 pcf polyurethane foam insulation in walls, ceiling and floor
• 10 ga. formed and welded steel base, coated with Innovent standard grey paint
• 2” double wall floor panels
• 18 ga. G90 galvanized inner floor
• 22 ga. G90 galvanized outer floor
• 16 ga. G90 galvanized and 0.080” aluminum frame
• 2” double wall casing panels
• 16 ga galvanized outer wall coated with high performance polyester finish, Innovent standard grey
• 22 ga. G90 galvanized inner wall
• Outdoor construction
• 18 ga. galvanized pitched roof coated with high performance polyester finish, Innovent standard grey
• Standing seams
• Roof extends beyond edge of unit
• Hoods with aluminum bird screen for exposed inlets and outlets
• Unit shall be shipped as a single piece of equipment
CASING ACCESS:
• Double wall access doors insulated with 2 pcf polyurethane foam
• Stainless steel piano hinges
• Aluminum frame
• Corrosion resistant compression latches
• Tool lockable access handles provided for all doors
• All other panels are fully removable unless otherwise identified on the unit drawings.
SUPPLY FAN & MOTORS:
• Forward curved blade, DWDI fan, galvanized wheel & housing, painted steel frame
• 1" deflection, seismic rated spring isolators
• L-50 200,000 hr pillow block bearings
• Adjustable V-belt drive with service factor of 1.2 on motors of 10 HP or less
• Extended lube lines
• TEFC EPACT compliant motor
FILTERS:
OUTSIDE AIR:
• 2" pleated MERV 8 filter, 500 FPM maximum face velocity
EVAP-1, 2 ONLY
DAMPERS:
• Outside air damper
• AMCA certified performance
• Formed galvanized blade with a leakage rating of 3 CFM at 1" wg
• 16 ga. galvanized frame
• Two-position actuator provided by Innovent
• Synthetic bearings
COOLING:
• Direct evaporative cooling (pad type)
• Cellulose impregnated media with 2” distribution pad
• Saturation efficiency a minimum of 89% at 500 FPM face velocity
• Spray manifold constructed of copper pipe
• Stainless steel sump pan with drain, overflow and makeup water connections
• Sump drain valve, mechanical float valve, makeup water supply valve, and makeup water drain valve provided by Innovent and installed by others
• See Evaporative Cooling Piping Schematic for additional information and field piping requirements
ELECTRICAL:
• Single point 3-phase power connection with unit mounted disconnect
• Power wiring enclosed in conduit
• All wires terminated at the unit mounted NEMA 3R panel
• Unit is ETL listed per UL standard 1995 and CSA standard C22.2 #236
CONTROLS:
• Stand alone DDC controller provided by Innovent (factory programmed)
• BacNet MS/TP compatible
• Controls provided by Innovent to be field mounted by others:
• Room temperature sensor
ACCESSORIES:
• 14" roof curb provided by Innovent for a flat roof. Curb will be shipped disassembled
WARRANTIES:
• Standard 1 year parts only warranty as described in the last page of this submittal.
SEQUENCE OF OPERATION (ERU-1 ONLY)
The sequence of operation displayed below is Innovent's interpretation of what is required for this project. This is subject to review by controls contractor. Innovent will not be responsible for any costs associated with modification of this sequence after the equipment has shipped.
Energy recovery unit DDC specs
STAND ALONE DDC CONTROLLER.
• Provided with required sensors and programming.
• Factory programmed, mounted, and tested.
• User terminal with LCD readout for changing set points and monitoring unit operation.
• User terminal can be unit mounted or remote mounted and is connected by straight through six wire flat cable
SEQUENCE OF OPERATION. The Stand-alone DDC controller shall perform the following control sequence.
UNIT START COMMAND
• Actuators for the outside air heat exchanger face damper and outside air heat exchanger bypass damper are powered.
• DDC controller checks damper actuator end switch status.
• Exhaust fan starts after dampers are open (minimum of 120sec delay, adjustable).
• Supply fan starts 5sec (adjustable) after the exhaust fan.
• Face & bypass operation per below.
UNIT STOP COMMAND (OR DE-ENERGIZED)
• Fans are de-energized
• All damper actuators are de-energized and spring return to their fail position after a 120sec on delay.
DEFROST
• The outside air heat exchanger face & bypass dampers modulate (bypassing outside air around the heat exchanger) to maintain the exhaust air temperature above the defrost set point (set point=34°F).
SUPPLY TEMPERATURE SET POINT
• The unit shall not control to a supply temperature. Any time the existing air handler in the building is in operation, ERU-1 shall operate as a pre-cool/pre-heat for the existing air handler in the building
REMOTE ON/OFF. Unit DDC shall have an input allowing the unit to be started/stopped by others.
ALARM INDICATION. DDC shall have one digital output for remote indication of an alarm condition. (i.e. Blower current/differential pressure switch, damper end switches, freeze stat, fire stat, smoke, dirty filters…).
SEQUENCE OF OPERATION (EVAP-1, 2 ONLY)
The sequence of operation displayed below is Innovent's interpretation of what is required for this project. This is subject to review by controls contractor. Innovent will not be responsible for any costs associated with modification of this sequence after the equipment has shipped.
AHU unit DDC specs
STAND ALONE DDC CONTROLLER.
• Provided with required sensors and programming.
• Factory programmed, mounted, and tested.
• User terminal with LCD readout for changing set points and monitoring unit operation.
• User terminal can be unit mounted or remote mounted and is connected by straight through six wire flat cable
SEQUENCE OF OPERATION. The Stand-alone DDC controller shall perform the following control sequence.
UNIT START COMMAND
• Actuator for the outside air damper is powered.
• DDC controller checks damper actuator end switch status.
• Supply fan starts after damper is open (minimum of 120sec delay, adjustable).
• Cooling operation per below.
UNIT STOP COMMAND (OR DE-ENERGIZED)
• Fans are de-energized
• All damper actuators are de-energized and spring return to their fail position after a 120sec on delay.
COOLING
• Cooling lockout: The cooling will be locked out when the outside air is < 55°F - 2°F hysteresis, adjustable.
SUPPLY TEMPERATURE SET POINT
• The DDC controller will reset the supply temperature set point up & down between the values listed below, in order to maintain the room temperature set point (set point=72°F, adjustable).
• Supply discharge minimum set point: 64 °F, adjustable.
• Supply discharge maximum set point: 80 °F, adjustable.
EVAPORATIVE COOLING SUMP CONTROL.
• Sump drain-out set point: 40°F
• Drain-down: When the outside air temperature falls below the sump drain-out set point, the automatic drain-down system will be energized to drain all water from the evaporative cooling system.
• Sump fill: The sump will fill when the outside air temperature rises above the sump drain-out set point.
• A bleed off valve, positioned between the sump and spray distribution system, is provided to aid in scale build up control
OCCUPIED/UNOCCUPIED MODES.
• Occupied/Unoccupied mode shall be based on an internal 7-day time clock. The schedule shall be set by the end user.
• Occupied mode:
• Supply fan ON.
• Outside air damper open
• Cooling per above.
• Unoccupied mode:
• Supply fan OFF.
• Outside air damper closed.
• When the room thermostat falls out of its set point, a signal shall be sent to energize the unit. Unit shall then operate in occupied mode until signaled to return to unoccupied mode.
REMOTE ON/OFF. Unit DDC shall have an input allowing the unit to be started/stopped by others.
SUPPLY DISCHARGE LOW LIMIT. If the supply discharge temperature drops below 40°F (adjustable), the DDC shall de-energize the unit after a preset time delay.
ALARM INDICATION. DDC shall have one digital output for remote indication of an alarm condition. (i.e. Blower current/differential pressure switch, damper end switches, supply discharge low limit/freeze stat, fire stat, smoke, dirty filters…).
TAG:
NOTE: THE ABOVE WINTER PERFORMANCE REFLECTS THE HX DEFROST CONDITION
ESP 1.50 O/A FILTER 0.30 HW COIL - CW COIL -
HX (ER) 1.03 O/A FINAL FILTER - STM COIL - DX COIL -
HX (PC) - S/A HEPA FILTER - FURNACE - DEC -
HX (RH) - FILTER LOADING - HGR COIL - LOUVER -
PLENUM 0.30 ELECTRIC HEATER - HUMIDIFIER - 3.13 "WC
ESP 1.50 E/A FILTER 0.30 IDEC - PLENUM 0.30
HX 1.00 E/A FILTER - LOUVER - 3.10 "WC
VOLTS PHASE FREQ. MCA
208 3 60 87.6
SIZE
TSP:
SUPPLY
TSP ("WC) RPM BHP MOTOR HP
1321 10.41 15QEM-30
75.0/50%
EAT(oF) / %RH
15,000
SUMMER EXHAUST AIR DATA
85.3
LAT (oF)
15,000
72.0/30%
INNOVENT PERFORMANCE DATA SUMMARY
34.0
CFM EAT/WB (oF) CFM
WINTER SUPPLY AIR DATA WINTER EXHAUST AIR DATA
ELEVATION: 4000 FT
LAT/WB (oF)
15,000 -20.0/-
SUMMER SUPPLY AIR DATA
15,000 95.0/76.0
23.0/14.7
84.6/73.0
BHP MOTOR HP
ENERGY RECOVERYAIR-TO-AIR HEAT EXCHANGER: CROSS FLOW FLAT PLATE
ERU-1
CFM
3.1315000
FAN/MOTOR ASSEMBLY:
FAN/MOTOR ASSEMBLY: EXHAUST
CFM SIZE TSP ("WC) RPM
10.32 15
TSP:
15000 QEM-30 3.10 1318
UNIT 100 N/A
ELECTRICAL INFORMATION: SINGLE POINT POWER
FUSING MOPCOMPONENT DISCONNECT ETL
LISTED125
TAG:
CFM FPM WBDE
4000 496 89%
NOTE: THE BLEED AND MAKEUP WATER FLOWS SHOWN ABOVE ARE BASED ON A CYCLES OF CONCENTRATION = 3
ESP 1.00 O/A FILTER 0.30 HW COIL - CW COIL -
HX (ER) - O/A FINAL FILTER - STM COIL - DX COIL -
HX (PC) - S/A HEPA FILTER - FURNACE - DEC 0.22
HX (RH) - FILTER LOADING - HGR COIL - LOUVER -
PLENUM 0.30 ELECTRIC HEATER - HUMIDIFIER - 1.82 "WC
VOLTS PHASE FREQ. MCA
208 3 60 11.3UNIT 30 N/A 20 LISTED
ELECTRICAL INFORMATION: SINGLE POINT POWER
COMPONENT DISCONNECT FUSING MOP ETL
LAT/WB MEDIA DEPTH BLEED-OFF (GPM) MAKE UP (GPM)
95.0/61.0 64.6/61.0 12" 0.11 0.32
TSP:
4000 ALTI 12-12 T2 1.82 1262 2.25 3
CFM SIZE TSP ("WC) RPM BHP MOTOR HP
FAN/MOTOR ASSEMBLY: SUPPLY
COOLING: DIRECT EVAPORATIVE MEDIA TYPE
EAT/WB
INNOVENT PERFORMANCE DATA SUMMARY
EVAP-1, EVAP-2 ELEVATION: 4000 FT
Sound Power by Octave Band Sound
Data
62.5 125 250 500 1000 2000 4000 8000 LwA dBA
Inlet 82 88 92 86 81 77 73 70 88 77
Outlet 86 91 96 93 88 83 78 74 94 82 LwA - A weighted sound power level, based on ANSI S1.4 dBA - A weighted sound pressure level, based on 11.5 dB attenuation per Octave band at 5.0 ft. dBA levels are not licensed by AMCA International
Requested Volume (CFM) 15,000 Actual Volume (CFM) 15,000 Drive Loss (%) -
External SP (in. wg) 3.13 Total SP (in. wg) 3.13 Static Efficiency (%) 71
Elevation (ft) 4,000 Operating Power (hp) 10.41
Airstream Temp. (F) 70 Fan RPM 1321
30-QEM-9-150
Chart Type: Operating Conditions kubly Typewriter
ERU-1 SUPPLY FAN CURVE
Sound Power by Octave Band Sound
Data
62.5 125 250 500 1000 2000 4000 8000 LwA dBA
Inlet 82 88 92 86 80 77 73 70 88 77
Outlet 86 91 95 93 88 83 78 74 94 82 LwA - A weighted sound power level, based on ANSI S1.4 dBA - A weighted sound pressure level, based on 11.5 dB attenuation per Octave band at 5.0 ft. dBA levels are not licensed by AMCA International
Requested Volume (CFM) 15,000 Actual Volume (CFM) 15,000 Drive Loss (%) -
External SP (in. wg) 3.1 Total SP (in. wg) 3.1 Static Efficiency (%) 71
Elevation (ft) 4,000 Operating Power (hp) 10.32
Airstream Temp. (F) 70 Fan RPM 1318
30-QEM-9-150
Chart Type: Operating Conditions kubly
ERU-1 EXHAUST FAN CURVE
Aeolus Plus 1.0.8 January 2013 Pg 1/1
Fan working conditions Free Inlet - Free Outlet Selected Fan ATLI 12 - 12 T2 Volume 4000 CFM Max Fan RPM 2115 1/min Total Pressure 2.23 In.W.G.
Max Shaft Power 12.00 BHP Static Pressure 1.82 In.W.G.
Fan power 2.25 BHP Total Efficiency 62.2 % Moment of Inertia 3.37 lb ft² Static Efficiency 50.9 % Required Working Point •••• Fan Speed 1262 1/min
Temperature 68.0 °F Altitude 4000 ft
Aeolus Plus 1.0.8 January 2013 Pg 1/1
Fan working conditions Free Inlet - Free Outlet Selected Fan ATLI 12 - 12 T2 Volume 4000 CFM Max Fan RPM 2115 1/min Total Pressure 2.23 In.W.G.
Max Shaft Power 12.00 BHP Static Pressure 1.82 In.W.G.
Fan power 2.25 BHP Total Efficiency 62.2 % Moment of Inertia 3.37 lb ft² Static Efficiency 50.9 % Required Working Point •••• Fan Speed 1262 1/min
Temperature 68.0 °F Altitude 4000 ft
0 5000 10000 V[CFM]
0.00
5.00
10.00 p sta[In.W.G.]
0 0.1 0.5 1 2 3 p dyn[In.W.G.]
1000 2000 3000 4000 5000 6000 7000 8000 o.v.[ft/min]
RPM 2200
36% 50% 58% 60%
57%
50%
42%
32%
21%
11%
0% 0.2
1.5
5.0 7.5
15.0
20.0 area 1 area 2 area 3 kubly
EVAP-1,2 SUPPLY FAN CURVE
Monday, September 30, 2013 Aeolus Plus 1.0.8 January 2013
Customer -
Project - Description -
Your Ref. - Our Ref. -
Input data
Volume 4000 CFM Temperature 68.0 °F Density 0.064 lb/cu.ft
Static Pressure 1.82 In.W.G. Altitude 4000 ft Free Inlet - Free Outlet
Catalogue data
Selected Fan
ATLI 12 - 12 T2
n Max Pw Max J
1/min BHP lb ft²
2115 12.00 3.37
Fan Information o.v.
ft/min p tot In.W.G.
p sta In.W.G.
p dyn In.W.G.
tip speed ft/min
RPM
1/min eta Tot eta Sta
P fan
BHP
Min Mot.
BHP
P mot
BHP
Shaft diameter mm
2760 2.23 1.82 0.41 4228 1262 62.18 50.85 2.25 2.72 3.00 fm[Hz] 63 125 250 500 1000 2000 4000 8000 Tot.
Lw6 Total Sound Power Level at the free outlet - Lwmo Outlet Sound Power Level (free outlet) do not includes the effect of duct end correction
Level Lw6 77 76 78 79 80 75 72 65 86 dB
Level Lw6 (filter A) 51 60 69 76 80 76 73 64 84 dB(A)
Page 1 of 1AeolusPlus
9/30/2013file:///C:/Comefri/AeolusPlus/Support/DataSheet.htm kubly
EVAP-1,2 SUPPLY FAN DATA SHEET
INDICATES FIELD WIRED COMPONENT
B A
C M
S /T
P
GND
Wire type/size per BACnet
MS/TP recomendations.
Jumper pins
To BACnet MS/TP network.
CAREL PART #:PCO1000BAO
B A
C M
S /T
P
GND
Wire type/size per BACnet
MS/TP recomendations.
Jumper pins
To BACnet MS/TP network.
CAREL PART #:PCO1000BAO
AUTHORIZATION TO MARK
Applicant: Manufacturer:
Address: Address:
Country: Country:
Contact: Contact:
Phone: Phone:
FAX: FAX:
Email: Email:
Standard(s):
Product:
Brand Name:
James Regan James Regan
N/A N/A
Unison Comfort Technologies Valent, LLC 60 28th Avenue North Minneapolis, MN 55411
60 28th Avenue North Minneapolis, MN 55411
USA USA
(612) 877-4850 (612) 877-4850
(612) 877-4851 (612) 877-4851
Control Number: 3061909 Authorized by:
Party Authorized To Apply Mark: Same as Manufacturer Report Issuing Office: Columbus
Heating and cooling, energy recovery and dehumidification equipment Retrovent, Valent, Innovent, Greenheck, or Accurex for Thomas J. Patterson, Certification Manager
This document supersedes all previous Authorizations to Mark for the noted Report Number.
This Authorization to Mark is for the exclusive use of Intertek's Client and is provided pursuant to the Certification agreement between Intertek and its Client. Intertek's responsibility and liability are limited to the terms and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in accordance with the agreement, for any loss, expense or damage occasioned by the use of this Authorization to Mark. Only the Client is authorized to permit copying or distribution of this Authorization to Mark and then only in its entirety. Use of Intertek’s Certification mark is restricted to the conditions laid out in the agreement and in this Authorization to Mark. Any further use of the Intertek name for the sale or advertisement of the tested material, product or service must first be approved in writing by Intertek. Initial Factory Assessments and Follow up Services are for the purpose of assuring appropriate usage of the Certification mark in accordance with the agreement, they are not for the purposes of production quality control and do not relieve the Client of their obligations in this respect.
Intertek Testing Services NA Inc.
545 East Algonquin Road, Arlington Heights, IL 60005
Telephone 800-345-3851 or 847-439-5667 Fax 312-283-1672
Standard for Safety for Heating and Cooling Equipment, ANSI/UL 1995, CAN/CSA C22.2 No.236-05 Third Edition, dated 02/18/2005 with revisions dated July 30, 2009 and Non-Recirculating Direct Gas-Fired Industrial Air Heaters ANSI Z83.4-2003/ CSA 3.7-2003 with addenda ANSI Z83.4a-2004/ CSA 3.7a-2004, ANSI Z83.4b-2006/ CSA 3.7b-2006
This authorizes the application of the Certification Mark(s) shown below to the models described in the Product(s) Covered section when made in accordance with the conditions set forth in the Certification Agreement and Listing Report. This authorization also applies to multiple listee model(s) identified on the correlation page of the Listing Report.
This document is the property of Intertek Testing Services and is not transferable. The certification mark(s) may be applied only at the location of the Party Authorized To Apply Mark.
Page 5 of 6 ATM for Report 3049027-001 ATM Issued: 16-Apr-2013 ED 16.3.15 (1-Jan-13) Mandatory
AUTHORIZATION TO MARK
Models:
Series ERU, LASER, LASER-1, LASER-2, NDHU, CAHU and DDHU Energy Recovery and Custom Air Handling Units.
Series RWC, RWCU, RAC, RACU, and WW Remote Condenser and Remote Condensing Units.
Model Series VPR under Brand names: Valent, Innovent, Greenheck or Accurex. VPR may be followed by E, X, P or C followed by 110, 210, 310, 350 or 450 followed by A, B, or X followed by I, J, T, or X, followed by any number followed by A, B, or C.
Series RCD air handling units under Brand names: Retrovent, Valent, Innovent, Greenheck or Accurex.
RCD fb 20, 25, 30, 40, 50, or 60 fb A,B,C, or D, fb 1, fb A-H, fb GH, GM, GL, EH, EM, EL, HW, ST, or AH fb 2-5, fb S or H, fb B,S,M,or N fb A-D, fb A-D, fb A-D, fb letters indicating other customer options
Page 6 of 6 ATM for Report 3049027-001 ATM Issued: 16-Apr-2013 ED 16.3.15 (1-Jan-13) Mandatory
CONFIDENTIAL February 2011
UNISON COMFORT TECHNOLOGIES TERMS & CONDITIONS OF SALE
ALL SALES ARE SUBJECT TO THESE UNISON COMFORT TECHNOLOGIES TERMS AND CONDITIONS OF SALES (“TERMS”) AND AS CONTAINED IN UNISON’S INVOICE AND ARE ALSO SUBJECT TO UNISON’S CREDIT AND OTHER POLICIES AND PROCEDURES, WHICH ARE
HEREBY INCORPORATED BY REFERENCE AND SUBJECT TO CHANGE.
1. TERMS TO GOVERN: These Terms shall be binding upon Unison Comfort Technologies, LLC and its subsidiaries and affiliates ("Seller") and the buyer (“Buyer”). No modification, amendment or change, whether in Buyer’s purchase order, shipping release forms or otherwise shall obligate Seller, unless authorized in writing by Seller. Any different or inconsistent terms and conditions of sale contained in Buyer’s forms, contracts or invoices are hereby superseded by these Terms.
2. ACCEPTANCE & PRICES: Any proposal offered by Seller to Buyer is valid for sixty (60) days. Upon the expiration of sixty (60) days, the proposal shall expire.
Pricing shall remain valid for Seller’s products (“Products”) shipped within one hundred and twenty (120) days from the date of Seller’s acceptance. Thereafter, prices are subject to change. Prices include transportation charges predicated on a single shipment and any partial shipments may result in additional cost to Buyer.
Seller reserves the right, at any time, to withdraw a bid, quote or a price that contains an error.
3. PAYMENT & TAXES: Upon credit approval, payment terms for Products shipped hereunder or labor performed will be thirty (30) days net with no retainages unless contrary terms appear on the face hereof or otherwise expressly agreed to in writing by Seller. Should Buyer default in the timely payment to Seller of sums due on an order, Seller is entitled to any remedies provided in these Terms or by law. If Buyer fails to pay any amounts when due, Buyer shall pay Seller interest thereon at a periodic rate of the lesser of one and one-half percent (1.5%) per month or the maximum allowable legal interest rate, along with all costs and expenses (including without limitation reasonable attorneys' fees and disbursements and Court costs) incurred by Seller. Buyer is responsible for all sales, customs, or use tax imposed by any governmental agency, including, but not limited to, Federal, State, Local or international agencies payable on the transaction under any applicable statute, except those taxes due as a result of Seller’s gross profits.
4. PERFORMANCE: Seller shall be obligated to furnish only the Products or labor described in the applicable purchase order or acknowledgement and agreed to in writing. The duty to perform under any order on the part of Seller and the price thereof is subject to the approval of its Credit Department, and is contingent upon the absence of strikes, accidents, floods, act(s) of terrorism, war, fires, fuel shortages, the inability to procure materials from the usual sources of supply, the requirements of the US Government (through the use of priorities or preference or any other manner) that Seller divert either the material or the furnished Product to the direct or indirect benefit of the US Government, or upon any like or unlike cause beyond the reasonable control of Seller. Upon disapproval of the Credit Department or upon the occurrence of any such event, Seller may delay performance or, at its option, renegotiate prices and terms and conditions of sale with Buyer. If Seller elects to renegotiate and Seller and Buyer are unable to agree on revised prices or terms, Seller may cancel without any liability.
5. SHIPMENT & RISK OF LOSS: Shipment dates are estimates only. Shipment shall be FOB factory with title passing to Buyer upon delivery to the carrier by Seller.
Seller specifically rejects any order containing a time is of the essence clause or liquidated damage penalties for late shipments. Risk of loss, including but is not limited to loss of goods from shortages, damages or transit delays, shall pass to Buyer when the Products have been delivered to any transportation carrier (excluding proprietary transportation facilities of Seller). Any claims for damage to, or loss or misdelivery or damage of the Products shall be filed with Seller.
6. CHANGES, CANCELLATION & RETURNS: Changes requested by Buyer following Seller’s acceptance of order must be approved by Seller in writing and may result in an increase in price deemed appropriate by Seller to recover all associated labor and material costs, including normal overhead and profit. If any portion of a Seller accepted order is cancelled by Buyer without default on the part of Seller or without Seller's written consent, Buyer shall be liable to Seller for cancellation charges including, but not limited to, Seller's incurred costs and such profit as would have been realized by Seller from the transaction had the agreement not been breached by Buyer. Products shall not be returned except by written permission of Seller pursuant to Seller’s return policy.
7. AUTHORITY OF AGENTS: No agent, employee or representative of Seller has the authority to bind Seller to any affirmation, representation or warranty concerning the Product or labor sold, except for Seller’s authorized agents, employees or representatives.
8. INDEMNITY: Seller shall protect and indemnify Buyer from and against all claims, damages, judgments and loss arising from infringement or alleged infringement of any United States patent by any of the articles or material delivered hereunder, provided that in the event of suit or threat of suit for patent infringement, Seller shall promptly be notified and given full opportunity to negotiate a settlement. Seller does not warrant against infringement by reason of Buyer's design of the articles or the use thereof in combination with other materials, or in the operation of any process.
In the event of litigation, Buyer agrees reasonably to cooperate with Seller. All parties concerned shall be entitled, in connection with any proceeding under the provisions of this Article, to be represented by counsel at their own expense. Seller shall also defend, indemnify and hold harmless Buyer from any third party personal injury, wrongful death or property damage caused solely by Seller’s negligent act(s).
Buyer shall defend, indemnify and hold Seller harmless from any personal injury, wrongful death or property damage caused by Buyer’s negligent or intentional act(s).
9. LIMITED WARRANTY AND DISCLAIMER: Seller warrants that at the time of delivery and for a period of twelve (12) months from the initial startup (“Start-Up”) or eighteen (18) months from date of shipment, whichever is less, Products will be free from defects in material and manufacture provided that Products have been installed with proper Start-Up, maintained and operated under normal conditions for service in accordance with the instructions of Seller, and that Products have the capacities and ratings set forth in Seller's design specifications. No warranty is made against corrosion, erosion or deterioration. At Seller’s option, Seller's obligations and liabilities under this warranty are limited to repair of Products or replacement of components for Products not conforming to this warranty. Limited warranty does not cover labor for component replacement. Once Seller’s service department has been notified and approved any warranty related service work, Seller will repair or replace components as needed and ship FOB factory. Seller shall not be obligated to pay for the cost of lost refrigerant. Consumable parts and Products that are consumable in nature are explicitly excluded from this warranty. Consumables include, but are not limited to, belts, filters, and refrigerant. No warranty or liability whatever shall attach to Seller until full payment has been received. No warranty herein extended shall apply to repair or correction of conditions arising from improper or incorrectly connected air duct, piping, wiring, power supply, blown fuses, freezing, improper Product control when programmed by non-Seller controls, or personnel, or by anyone other than Seller employee or its representative. Operation of Products for temporary conditioning of a building during construction without the written consent of an officer of the Seller immediately voids any warranty coverage. If the Product is replaced, the replacement may not be new, but will be in good working order and at least functionally equivalent to the item or Product replaced. The replacement assumes the warranty status of the replaced Product. The warranty period does not start over. THIS LIMITED WARRANTY IS IMMEDIATELY VOIDED AND
CANCELLED BY ANY MISUSE, NEGLECT, FAILURE TO FOLLOW
INSTRUCTIONS, OR MANUALS OF INSTALLATION OR MAINTENANCE
REPAIR, SERVICE, RELOCATION OR ALTERATION TO OR OF, OR OTHER
TAMPERING WITH, THE PRODUCTS PERFORMED BY ANY PERSON OR
ENTITY OTHER THAN SELLER WITHOUT SELLER’S PRIOR WRITTEN
APPROVAL OR ANY USE OF REPLACEMENT PARTS NOT SUPPLIED BY
SELLER WITH RESPECT TO THE AFFECTED PRODUCTS. BACK CHARGES
RESULTING FROM CLAIMS UNDER THE WARRANTY SHALL BE
RECOGNIZED ONLY WHEN PREVIOUSLY AUTHORIZED IN WRITING BY
SELLER. THE WARRANTY AND LIABILITY SET FORTH HEREIN ARE IN LIEU
OF ALL OTHER WARRANTIES AND LIABILITIES WHETHER IN CONTRACT,
TORT, OR IN NEGLIGENCE, EXPRESSED OR IMPLIED, IN LAW OR IN FACT,
INCLUDING IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS
FOR A PARTICULAR USE. SELLER PROVIDES NO INDEPENDENT
WARRANTY FOR THIRD PARTY PRODUCTS OR COMPONENTS SOLD
TOGETHER OR INCORPORATED WITH SELLER’S PRODUCT(S).
10. LIABILITY DISCLAIMER: TO THE MAXIMUM EXTENT PERMITTED BY LAW,
SELLER’S TOTAL LIABILITY FOR CLAIMS, REGARDLESS OF THE FORM OF
ACTION OR THEORY OF LIABILITY (INCLUDING CONTRACT, TORT OR
WARRANTY), SHALL BE LIMITED TO THE FEES PAID TO SELLER BY BUYER
FOR THE PRODUCTS OR LABOR ALLEGED TO CAUSE THE DAMAGE. IN NO
EVENT SHALL SELLER BE LIABLE TO BUYER FOR ANY INCIDENTAL,
CONSEQUENTIAL, SPECIAL, PUNITIVE, OR INDIRECT DAMAGES OF ANY
KIND (INCLUDING, WITHOUT LIMITATION, LOST PROFITS, LOSS OF USE, OR
CLAIMS OF THIRD PARTIES) THAT MIGHT OCCUR AS A RESULT OF THE
PERFORMANCE OR BREACH OF THE AGREEMENT OR IN ANY WAY ARISING
OUT OF OR IN CONNECTION WITH THE AGREEMENT.
11. ASSIGNMENT: No right or interest may be assigned by Buyer, nor may any obligation or performance delegated by Buyer without Seller’s written permission.
Any attempted assignment or delegation shall be void and ineffective for all purposes. Seller may assign its rights or obligations under this Agreement in the event of a merger or change of control of Seller.
12. GOVERNING LAW: This agreement shall be governed and construed in accordance with the laws State of Minnesota. Buyer consents to jurisdiction in the Circuit Court of Hennepin County, Minnesota.
13. EXPORT CONTROLS: Buyer shall comply with the export laws and regulations of the United States and other applicable jurisdictions with regard to Products and labor. Buyer agrees it shall not export or enter into an agreement for the export any goods from Seller to any prohibited or embargoed country or to any denied, blocked or restricted person or entity including those so designated by the US Dept. of Commerce or Treasury.
14. MISCELLANEOUS: In the event that any provision of this Agreement is held invalid by the final judgment of any court of competent jurisdiction, the remaining provisions shall remain in full force and effect as if such invalid provision had not been included herein. The waiver or failure of either party to enforce the terms of this Agreement in one or multiple instances shall not constitute a waiver of that party’s rights under this Agreement with respect to other violations. The titles and headings used herein are for convenience only and do not constitute any part of this Agreement. Those sections of this Agreement, which by their nature are intended to survive, shall survive termination of this Agreement. The prevailing party may recover their attorney fees and reasonable out-of-pocket expenses.
File details come from the government source that posted it. Updated .