Attachment 1 - East Garage.pdf

PDF 2 MB Posted

Attached to
Y1LZ--FY21: NRM Tier 2 (Proj: 675-21-110) Install Parking Garage Guidance Sytem
Solicitation number
36C24821R0131
Issued by

About this file

This document package includes engineering drawings and specifications for a federal contract opportunity to install a parking garage guidance system at the Orlando VA Medical Center. The contractor will evaluate and replace outdated parking infrastructure including single space sensors, communication points, and interior/exterior signage displays. Interior signage will include aisle availability indicators. The contractor must provide a software system to monitor the garages. The work will be performed at the Lake Nona VA Medical Center campus in Orlando, Florida. The solicitation is set aside for Service-Disabled Veteran-Owned Small Businesses with a value between $1,000,000 to $5,000,000. The pre-solicitation notice was released on July 6, 2021 and interested parties should monitor beta.SAM.gov for the full solicitation releasing on or around July 20, 2021.

View the file

Other files

File Type Posted
LN Parking Comm 3.pdf PDF
DB Install Parking Garage RFIs (002).pdf PDF
LN Parking Comm 4.pdf PDF
BP3 Drawings Parking Garage - fragment.pdf PDF
LN Parking Comm 7.pdf PDF
LN Parking Communications 2.pdf PDF
LN Parking Comm 8.pdf PDF
LN Parking Comm 6.pdf PDF
36C24821R0131 0001.pdf PDF
LN Parking Communications 1.pdf PDF
LN Parking Comm 5.pdf PDF
Attachment 7 - Wage Determination.pdf PDF
Attachment 6 - EMR.docx DOCX document
Solicitation For 36C24821R0131.pdf PDF
Attachment 4 - Price Matrix.xlsx XLSX spreadsheet
Attachment 8 - LOS Solicitation Version.doc DOC document
Attchment 5 - Past Performance.pdf PDF
Attachment 2 - West Garage.pdf PDF
Attachment 3 - Specialized Experience Form.pdf PDF
Show all 19

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Existing Entry Sign

MS

LS

CP 1E

Requires 100-240VAC Ethernet to Network

CP 1 Existing

Entry Sign Existing Wire back to CP 1

CP 2E

Requires 100-240VAC Ethernet to Network

D ra w in g N o

Q -F re e

U n io n A v e n u e

S u d b u ry

M

A

P h o n e

-2

F a x

-9 w w w .q

-f re e .c o m

E n g in e e r

D ra ft s m a n

D a te

C h e c k e d

A p p ro v e d

R e v

S u b m it ta l N o

S u b m it ta l D a te

V A

O rl a n d o M e d ic a l C e n te r, E a s t G a ra g e

/1

/2

P G

S D e s ig n A p p ro v e d b y C u s to m e r

C u s to m e r S ig n a tu re

R E

V

A B

PGS - Wiring Details (Comm. Bus/24VDC) - 2 pairs of 18 AWG Purple Line

Gateway for wireless communication

Communication point

PGS -Details

CP

GW

Single Sided Level Sign (existing)LS

CP Enclosures Require 100-240 VAC Power

HC Single Space Sensor

Single Space Sensor

(Sensor Bus 0) - 2 pairs of 18 AWG Blue Line

(Sensor Bus 1) - 2 pairs of 18 AWG Red Line

(Sensor Bus 2) - 2 pairs of 18 AWG Green Line

Brown Line Loop Lead

AS Aisle Sign

In-Ground Induction Loop (existing)

Delineator

Communication point (existing)CP

(existing)

Entry Sign (existing)MS and Ethernet to customer’s network

Note: Network connection available on levels 1, 3, and 5

C u s to m e r P ro v id e d

D ra w in g P

-A G

.1

L e v e l

L S

AS

CP 3E

Requires 100-240VAC Ethernet to Network

CP 4E

Requires 100-240VAC Ethernet to Network

D ra w in g N o

Q -F re e

U n io n A v e n u e

S u d b u ry

M

A

P h o n e

-2

F a x

-9 w w w .q

-f re e .c o m

E n g in e e r

D ra ft s m a n

D a te

C h e c k e d

A p p ro v e d

R e v

S u b m it ta l N o

S u b m it ta l D a te

V A

O rl a n d o M e d ic a l C e n te r, E a s t G a ra g e

/1

/2

P G

S D e s ig n A p p ro v e d b y C u s to m e r

C u s to m e r S ig n a tu re

R E

V

A B

C u s to m e r P ro v id e d

D ra w in g P

-A G

.1

L e v e l A

PGS - Wiring Details (Comm. Bus/24VDC) - 2 pairs of 18 AWG Purple Line

Gateway for wireless communication

Communication point

PGS -Details

CP

GW

Single Sided Level Sign (existing)LS

CP Enclosures Require 100-240 VAC Power

HC Single Space Sensor

Single Space Sensor

(Sensor Bus 0) - 2 pairs of 18 AWG Blue Line

(Sensor Bus 1) - 2 pairs of 18 AWG Red Line

(Sensor Bus 2) - 2 pairs of 18 AWG Green Line

Brown Line Loop Lead

AS Aisle Sign

In-Ground Induction Loop (existing)

Delineator

Communication point (existing)CP

(existing)

Entry Sign (existing)MS and Ethernet to customer’s network

Note: Network connection available on levels 1, 3, and 5

AS

CP 5E

Requires 100-240VAC Ethernet to Network

CP 6E

Requires 100-240VAC Ethernet to Network

D ra w in g N o

Q -F re e

U n io n A v e n u e

S u d b u ry

M

A

P h o n e

-2

F a x

-9 w w w .q

-f re e .c o m

E n g in e e r

D ra ft s m a n

D a te

C h e c k e d

A p p ro v e d

R e v

S u b m it ta l N o

S u b m it ta l D a te

V A

O rl a n d o M e d ic a l C e n te r, E a s t G a ra g e

/1

/2

P G

S D e s ig n A p p ro v e d b y C u s to m e r

C u s to m e r S ig n a tu re

R E

V

A B

C u s to m e r P ro v id e d

D ra w in g P

-A G

.2

L e v e l

PGS - Wiring Details (Comm. Bus/24VDC) - 2 pairs of 18 AWG Purple Line

Gateway for wireless communication

Communication point

PGS -Details

CP

GW

Single Sided Level Sign (existing)LS

CP Enclosures Require 100-240 VAC Power

HC Single Space Sensor

Single Space Sensor

(Sensor Bus 0) - 2 pairs of 18 AWG Blue Line

(Sensor Bus 1) - 2 pairs of 18 AWG Red Line

(Sensor Bus 2) - 2 pairs of 18 AWG Green Line

Brown Line Loop Lead

AS Aisle Sign

In-Ground Induction Loop (existing)

Delineator

Communication point (existing)CP

(existing)

Entry Sign (existing)MS and Ethernet to customer’s network

AS

CP 7E

Requires 100-240VAC Ethernet to Network

CP 8E

Requires 100-240VAC Ethernet to Network

D ra w in g N o

Q -F re e

U n io n A v e n u e

S u d b u ry

M

A

P h o n e

-2

F a x

-9 w w w .q

-f re e .c o m

E n g in e e r

D ra ft s m a n

D a te

C h e c k e d

A p p ro v e d

R e v

S u b m it ta l N o

S u b m it ta l D a te

V A

O rl a n d o M e d ic a l C e n te r, E a s t G a ra g e

/1

/2

P G

S D e s ig n A p p ro v e d b y C u s to m e r

C u s to m e r S ig n a tu re

R E

V

A B

C u s to m e r P ro v id e d

D ra w in g P

-A G

.2

L e v e l A

PGS - Wiring Details (Comm. Bus/24VDC) - 2 pairs of 18 AWG Purple Line

Gateway for wireless communication

Communication point

PGS -Details

CP

GW

Single Sided Level Sign (existing)LS

CP Enclosures Require 100-240 VAC Power

HC Single Space Sensor

Single Space Sensor

(Sensor Bus 0) - 2 pairs of 18 AWG Blue Line

(Sensor Bus 1) - 2 pairs of 18 AWG Red Line

(Sensor Bus 2) - 2 pairs of 18 AWG Green Line

Brown Line Loop Lead

AS Aisle Sign

In-Ground Induction Loop (existing)

Delineator

Communication point (existing)CP

(existing)

Entry Sign (existing)MS and Ethernet to customer’s network

AS

CP 9E

Requires 100-240VAC Ethernet to Network

CP 10E

Requires 100-240VAC Ethernet to Network

D ra w in g N o

Q -F re e

U n io n A v e n u e

S u d b u ry

M

A

P h o n e

-2

F a x

-9 w w w .q

-f re e .c o m

E n g in e e r

D ra ft s m a n

D a te

C h e c k e d

A p p ro v e d

R e v

S u b m it ta l N o

S u b m it ta l D a te

V A

O rl a n d o M e d ic a l C e n te r, E a s t G a ra g e

/1

/2

P G

S D e s ig n A p p ro v e d b y C u s to m e r

C u s to m e r S ig n a tu re

R E

V

A B

C u s to m e r P ro v id e d

D ra w in g P

-A G

.3

L e v e l

PGS - Wiring Details (Comm. Bus/24VDC) - 2 pairs of 18 AWG Purple Line

Gateway for wireless communication

Communication point

PGS -Details

CP

GW

Single Sided Level Sign (existing)LS

CP Enclosures Require 100-240 VAC Power

HC Single Space Sensor

Single Space Sensor

(Sensor Bus 0) - 2 pairs of 18 AWG Blue Line

(Sensor Bus 1) - 2 pairs of 18 AWG Red Line

(Sensor Bus 2) - 2 pairs of 18 AWG Green Line

Brown Line Loop Lead

AS Aisle Sign

In-Ground Induction Loop (existing)

Delineator

Communication point (existing)CP

(existing)

Entry Sign (existing)MS and Ethernet to customer’s network

AS

CP 11E

Requires 100-240VAC Ethernet to Network

CP 12E

Requires 100-240VAC Ethernet to Network

D ra w in g N o

Q -F re e

U n io n A v e n u e

S u d b u ry

M

A

P h o n e

-2

F a x

-9 w w w .q

-f re e .c o m

E n g in e e r

D ra ft s m a n

D a te

C h e c k e d

A p p ro v e d

R e v

S u b m it ta l N o

S u b m it ta l D a te

V A

O rl a n d o M e d ic a l C e n te r, E a s t G a ra g e

/1

/2

P G

S D e s ig n A p p ro v e d b y C u s to m e r

C u s to m e r S ig n a tu re

R E

V

A B

C u s to m e r P ro v id e d

D ra w in g P

-A G

.3

L e v e l A

PGS - Wiring Details (Comm. Bus/24VDC) - 2 pairs of 18 AWG Purple Line

Gateway for wireless communication

Communication point

PGS -Details

CP

GW

Single Sided Level Sign (existing)LS

CP Enclosures Require 100-240 VAC Power

HC Single Space Sensor

Single Space Sensor

(Sensor Bus 0) - 2 pairs of 18 AWG Blue Line

(Sensor Bus 1) - 2 pairs of 18 AWG Red Line

(Sensor Bus 2) - 2 pairs of 18 AWG Green Line

Brown Line Loop Lead

AS Aisle Sign

In-Ground Induction Loop (existing)

Delineator

Communication point (existing)CP

(existing)

Entry Sign (existing)MS and Ethernet to customer’s network

AS

CP 13E

Requires 100-240VAC Ethernet to Network

CP 14E

Requires 100-240VAC Ethernet to Network

D ra w in g N o

Q -F re e

U n io n A v e n u e

S u d b u ry

M

A

P h o n e

-2

F a x

-9 w w w .q

-f re e .c o m

E n g in e e r

D ra ft s m a n

D a te

C h e c k e d

A p p ro v e d

R e v

S u b m it ta l N o

S u b m it ta l D a te

V A

O rl a n d o M e d ic a l C e n te r, E a s t G a ra g e

/1

/2

P G

S D e s ig n A p p ro v e d b y C u s to m e r

C u s to m e r S ig n a tu re

R E

V

A B

C u s to m e r P ro v id e d

D ra w in g P

-A G

.4

L e v e l

PGS - Wiring Details (Comm. Bus/24VDC) - 2 pairs of 18 AWG Purple Line

Gateway for wireless communication

Communication point

PGS -Details

CP

GW

Single Sided Level Sign (existing)LS

CP Enclosures Require 100-240 VAC Power

HC Single Space Sensor

Single Space Sensor

(Sensor Bus 0) - 2 pairs of 18 AWG Blue Line

(Sensor Bus 1) - 2 pairs of 18 AWG Red Line

(Sensor Bus 2) - 2 pairs of 18 AWG Green Line

Brown Line Loop Lead

AS Aisle Sign

In-Ground Induction Loop (existing)

Delineator

Communication point (existing)CP

(existing)

Entry Sign (existing)MS and Ethernet to customer’s network

CP 15E

Requires 100-240VAC Ethernet to Network

D ra w in g N o

Q -F re e

U n io n A v e n u e

S u d b u ry

M

A

P h o n e

-2

F a x

-9 w w w .q

-f re e .c o m

E n g in e e r

D ra ft s m a n

D a te

C h e c k e d

A p p ro v e d

R e v

S u b m it ta l N o

S u b m it ta l D a te

V A

O rl a n d o M e d ic a l C e n te r, E a s t G a ra g e

/1

/2

P G

S D e s ig n A p p ro v e d b y C u s to m e r

C u s to m e r S ig n a tu re

R E

V

A B

C u s to m e r P ro v id e d

D ra w in g P

-A G

.4

L e v e l A

PGS - Wiring Details (Comm. Bus/24VDC) - 2 pairs of 18 AWG Purple Line

Gateway for wireless communication

Communication point

PGS -Details

CP

GW

Single Sided Level Sign (existing)LS

CP Enclosures Require 100-240 VAC Power

HC Single Space Sensor

Single Space Sensor

(Sensor Bus 0) - 2 pairs of 18 AWG Blue Line

(Sensor Bus 1) - 2 pairs of 18 AWG Red Line

(Sensor Bus 2) - 2 pairs of 18 AWG Green Line

Brown Line Loop Lead

AS Aisle Sign

In-Ground Induction Loop (existing)

Delineator

Communication point (existing)CP

(existing)

Entry Sign (existing)MS and Ethernet to customer’s network

Page 1
Page 2
Page 3
Page 4
Page 5
Page 6
Page 7
Page 8

File details come from the government source that posted it. Updated .