12456820Q0016

HVAC MAINTENANCE

STONEVILLE, MS

USDA FOREST SERVICE

SOUTHERN RESEARCH STATION

STATEMENT OF WORK

HVAC Preventative Maintenance Center for Bottomland Hardwoods Research Stoneville, MS I.

GENERAL

Contractor shall provide all labor, materials, and equipment to perform preventative maintenance services to the heating, ventilation, and cooling (HVAC) systems at the Center for Bottomland Hardwoods Research, located at 432 Stoneville Road, Stoneville, MS 38776. Work does not include repairs to inoperable equipment. Contractor will notify the Contracting Officer’s Representative if any HVAC component requires repair services that are not included in the scope of this preventative maintenance contract.

II. COVERED EQUIPMENT

Preventative maintenance tasks shall be performed on the following equipment in accordance with the equipment manufacturer’s specifications and common industry practice:

UNIT#/TYPE
BRAND
SERIAL #
MODEL #
LOCATION
01-AH
Carrier
4402F87504
39MN12A00304811SXS
Southern Hardwoods Lab Attic
01-Cond
Carrier
1713Q62788
38AKS028---501--
South side Southern Hardwoods Lab
02-AH
Carrier
4402F87476
39MN08A00304911SXS
Inside Southern Hardwoods Lab
02-Cond
Carrier
2802G00040
38ARS012---511--
South side Southern Hardwoods Lab
03-AH
Carrier
4402F87487
39MN08A00305011SXS
Southern Hardwoods Lab Attic
03-Cond
Carrier
3902F81529
38AKS014---520--
South side Southern Hardwoods Lab
04-AH
Carrier
4402F87495
39MN08A00305111SXS
Southern Hardwoods Lab Attic
04-Cond
Trane
142721YJYA
TTA120A300GA
South side Southern Hardwoods Lab
05-AH
Carrier
3508A69934
FA4CNF024
Southern Hardwoods Lab Attic
05-Cond
Carrier
0909E13777
24ABS324A310
South side Southern Hardwoods Lab
06-AH
Carrier
3202A64986
FB4ANF036
Southern Hardwoods Lab Attic
06-Cond
Carrier
2102E37568
38CKC036510
South side Southern Hardwoods Lab
07-AH
Carrier
3515A67850
FB4CNF024
Southern Hardwoods Lab Attic
07-Cond
Carrier
3515E03758
24ACC424A300
South side Southern Hardwoods Lab
08-AH
Carrier
4002A69869
FB4ANF024
Southern Hardwoods Lab Attic
08-Cond
Carrier
3202E23039
38CKC024340
North side Southern Hardwoods Lab
09-AH
Carrier
3602A64455
FB4ANF048
Southern Hardwoods Lab Attic
09-Cond
Carrier
3302E13017
38CKC048560
North side Southern Hardwoods Lab
10-AH
First Company
C08FC741544 232950
48MBQ4
Inside Carpentry Shop/Dorm
11-AH
Carrier
3402A69205
FB4ANF024
Inside Carpentry Shop/Dorm
11-Cond
Carrier
3202E23043
58CKC024340
West side Carpentry Shop/Dorm
12-Cond
Carrier
2102E10937
38CKC0340
West side Carpentry Shop/Dorm
13-Cond
Carrier
3302E13020
38CK0048560
West side Carpentry Shop/Dorm
14-AH
Carrier
2412U25396
40RUQA08A2A6A0A0A0
Inside Multipurpose Building
14-Cond
Carrier
2712C90189
38AUQA08AOA5A0A2CO
Outside Multipurpose Building
15-AH
Carrier
1812A89849
FE4ANB006
Inside Multipurpose Building
15-Cond
Carrier
0612E03711
25HNB936A300
Outside Multipurpose Building
16-AH
Payne
1704A70602
PF1MNB048
Inside Soils Preparation
16-Cond
Carrier
2404E43044
38CKC048370
Outside Soils Preparation
17-Cond
HTPG
W06A3268717003
HLH201H22E
Outside Soils Preparation
18-Cond
Bohn
Part # 89017001?
UNREADABLE
Outside Soils Preparation
19-AH
Payne
1204A84302
PF1MNB024
Inside Insectary
19-Cond
Carrier
0904E1515
38CKC024340
Outside Insectary
20-AH
Carrier
1613A90156
FX4DNF049
Inside Greenhouse 4
20-Cond
Carrier
2913E05843
24ABB348A340
Outside Greenhouse 4
21-AH
Carrier
3502A63261
FB4ANF030
Inside Climate Controlled Room
21-Cond
Bohn
030253A
RAC
Outside Greenhouse 4
Boiler-01
Ajax
61643
WNG-525
Southern Hardwoods Lab Mechanical Room
Boiler-02
Ajax
61644
WNG-525
Southern Hardwoods Lab Mechanical Room
Pump-01
Bell & Gossett
C240133-02 H71
e-90, 2AB, 6.625 BF

60 GPM, 45 FT

Southern Hardwoods Lab Mechanical Room

Pump Motor
US Motors
SM2112
P63ACG-1166
Southern Hardwoods Lab Mechanical Room
Pump-02
Bell & Gossett
C240133-02 H71
e-90, 2AB, 6.625 BF

60 GPM, 45 FT

Southern Hardwoods Lab Mechanical Room

Pump Motor
US Motors
SM2112
P63ACG-1166
Southern Hardwoods Lab Mechanical Room

III. WORK ITEMS

Contractor shall perform the following tasks at the required frequencies:

Task

Frequency

1. Clean condenser coils

2 times annually (spring and fall)

2. Check condenser operation

2 times annually (spring and fall)

3. Lubricate all pumps and check pump operations

4 times annually (once per quarter)

4. Clean pump and AHU pipe strainers

5. Check boiler, clean boiler per manufacturer’s specs

2 times annually (fall and winter)

6. Check boiler operations and safeties per mfgr. specs

2 times annually (fall and winter)

7. Check all HW flows and temperatures

8. Change all AHU belts, check belt alignment, clean drains and drain pans

1 time annually (spring)

9. Remove existing and install new pleated filters in all Air Handling Units

10. Provide all chemical treatment needed to maintain

HVAC fluids as required by the equipment manufacturer 4 times annually (once per quarter)

11. Document all services and provide copy to COR

4 times annually (once per quarter)

IV. EMERGENCY CALLS

The contractor shall respond to emergency repair calls within 24 hours after notification during normal business hours. The contractor shall prepare and submit a written report within two business days after the emergency call. The report shall include the date and time of the service call, the name of the responding technician, any minor repairs performed and/or recommended major repairs with estimated costs.

V. IDENTIFICATION OF NEEDED REPAIRS

Contractor shall notify the COR if any component or function of the HVAC system is found to be inoperable or defective during the preventative maintenance services or any emergency calls. Contractor shall not make any repairs outside the scope of this contract without approval of the Contracting Officer.

VI. MINOR REPAIRS

Minor repairs include work that can be accomplished within the time and costs associated with the initial service call. Minor repairs do not require prior approval of the Contracting Officer.

VII. SUBMITTALS

The following submittals must be provided for review and approval prior to beginning work. Any subsequent changes to the approved submittals must be resubmitted for review and approval a minimum of five (5) work days prior to the planned implementation of the change.

Personnel List. The Contractor shall furnish the CO a complete list of the name, address, and date of birth of each employee engaged in the performance of this contract. The Government may require additional information to establish the identity and legal employment status of each employee having access to Government buildings or facilities.

Maintenance Plan. The Contractor shall implement and maintain a documented maintenance plan, including a preventative maintenance checklist, that identifies all routine maintenance items and the recommend service intervals. The maintenance plan and checklist shall serve as the basis for the written report to be provided upon completion of each maintenance cycle. The contractor shall also maintain a comprehensive list of all maintenance and repair activities, along with dates that each service was recommended, if and when it was completed and any information relevant for future maintenance and repair of the systems.

VIII. HAZARDOUS MATERIALS

Contractor shall dispose of all waste generated in the performance of this contract in accordance with applicable laws and regulations. Contractor shall not disturb any pipe or duct insulation, or any other areas identified or suspected of containing asbestos or other hazardous materials.