This document provides details for a federal contract solicitation to upgrade a domestic water system. The solicitation number is 36C24823R0083 and is being issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 8 to provide construction services under project 672-19-716. The opportunity is for hurricane hardening upgrades to the domestic water system at the VA Caribbean Healthcare System location in San Juan, Puerto Rico. An attachment to the solicitation includes 50 pages of construction drawings relevant to the required upgrade work. The response due date and award timing are not specified in the provided document.
View the file
Other files
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
NETWORK CONTRACTING OFFICE 8 (NCO8)
VA CARIBBEAN HEALTHCARE SYSTEM
ADMINISTRATIVE BUILDING SUITE #4M440
#10 CALLE CASIA
SAN JUAN PR 00921-3201
Veterans Affairs Department of
3603 NW 98TH STREET, SUITE B
GAINESVILLE, FLORIDA 32606
PH: (352) 474-6124
FAX. (352) 553-4437
COA: FL REG #29758
DESIGNED FOR:
Veterans AffairsVeterans AffairsVeterans Affairs Department of Veterans Affairs Department of
PROJECT
AREA
DESIGNED BY:
3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124
FAX: (352) 553-4437
COA: FL REG #29758
AKEA Project No. 170-19
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECTS/ENGINEERSCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
100%
CONSTRUCTION
DOCUMENTS
G001
PROJECT
LOCATION
SAN JUAN, PR
SAFETY ENGINEER SIGNATURE FIELD ADDED 11-29-21
William Rodriguez Arroyo
2021.11.29 11:10:53 -05'00'
SURVEYING AND MAPPING CONSULTANTS
B-17 Marginal Ext. Forest Hills, Bayamon, P.R., 00959
Tel. (787) 787-6010 Cel. 787-505-3190 info@antoniomelendezpr.com
TOPOGRAPHIC SURVEY
SURVEYORS NOTES:
ABBREVIATIONS: LEGEND
BORING LAYOUT
OF AN AREA LOCATED AT
THE HOSPITAL DE VETERANOS
SAN JUAN, PUERTO RICO
Sta. 1
Sta. 2
HORIZONTAL & VERTICAL CONTROL
3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124
FAX: (352) 553-4437
COA: FL REG #29758
AKEA Project No. 170-19
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECTS/ENGINEERSCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Design, Inc.
FOR CONSTRUCTION
BID DOCUMENTS
SAN JUAN, PUERTO RICO
SEPTEMBER 10, 2021
UPGRADE DOMESTIC
WATER SYSTEM FOR
HURRICANE HARDENING
672-19-716
WR MDT
100%
CONSTRUCTION
DOCUMENTS
C001
TOPOGRAPHIC SURVEY
BASE FILE
T2
KEY PLAN - SITE
NORTH
T1
SURVEY REFERENCE
STATION 1
SURVEY REFERENCE
STATION 2
STATE OF
P
R O
FESS IO NA L ENGIN
EE
R
M
IC
HA EL D. T OOTLENo. 67818 L I C E N S E
F L O R I D A
Date: 2021.09.09 18:11:09 -04'00' William Rodriguez Arroyo
2021.09.09 18:17:30 -04'00'
3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124
FAX: (352) 553-4437
COA: FL REG #29758
AKEA Project No. 170-19
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECTS/ENGINEERSCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Design, Inc.
FOR CONSTRUCTION
BID DOCUMENTS
SAN JUAN, PUERTO RICO
SEPTEMBER 10, 2021
UPGRADE DOMESTIC
WATER SYSTEM FOR
HURRICANE HARDENING
672-19-716
WR MDT
100%
CONSTRUCTION
DOCUMENTS
C002
GENERAL NOTES, CIVIL NOTES,
UTILITY NOTES
STATE OF
P
R O
FESS IO NA L ENGIN
EE
R
M
IC
HA EL D. T OOTLENo. 67818 L I C E N S E
F L O R I D A
Date: 2021.09.09 18:11:49 -04'00' William Rodriguez Arroyo
2021.09.09 18:37:25 -04'00'
Tel. (787) 787-6010 Cel. 787-505-3190 info@antoniomelendezpr.com
TOPOGRAPHIC SURVEY
SURVEYORS NOTES:
ABBREVIATIONS: LEGEND
BORING LAYOUT
OF AN AREA LOCATED AT
THE HOSPITAL DE VETERANOS
SAN JUAN, PUERTO RICO
Sta. 1
Sta. 2
HORIZONTAL & VERTICAL CONTROL
REFERENCE FOR
NEW CONSTRUCTION
3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124
FAX: (352) 553-4437
COA: FL REG #29758
AKEA Project No. 170-19
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECTS/ENGINEERSCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Design, Inc.
FOR CONSTRUCTION
BID DOCUMENTS
SAN JUAN, PUERTO RICO
SEPTEMBER 10, 2021
UPGRADE DOMESTIC
WATER SYSTEM FOR
HURRICANE HARDENING
672-19-716
WR MDT
100%
CONSTRUCTION
DOCUMENTS
C100
EXISTING CONDITIONS
T2
KEY PLAN - SITE
NORTH
T1
SURVEY REFERENCE
STATION 1
SURVEY REFERENCE
STATION 2
NEW TANK CENTER
STATE OF
P
R O
FESS IO NA L ENGIN
EE
R
M
IC
HA EL D. T OOTLENo. 67818 L I C E N S E
F L O R I D A
Date: 2021.09.09 18:12:40 -04'00'
William Rodriguez Arroyo
2021.09.09 18:20:27 -04'00'
Tel. (787) 787-6010 Cel. 787-505-3190 info@antoniomelendezpr.com
TOPOGRAPHIC SURVEY
SURVEYORS NOTES:
ABBREVIATIONS: LEGEND
BORING LAYOUT
OF AN AREA LOCATED AT
THE HOSPITAL DE VETERANOS
SAN JUAN, PUERTO RICO
Sta. 1
Sta. 2
HORIZONTAL & VERTICAL CONTROL
3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124
FAX: (352) 553-4437
COA: FL REG #29758
AKEA Project No. 170-19
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECTS/ENGINEERSCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Design, Inc.
FOR CONSTRUCTION
BID DOCUMENTS
SAN JUAN, PUERTO RICO
SEPTEMBER 10, 2021
UPGRADE DOMESTIC
WATER SYSTEM FOR
HURRICANE HARDENING
672-19-716
WR MDT
100%
CONSTRUCTION
DOCUMENTS
C200
DEMOLITION PLAN
T2
KEY PLAN - SITE
NORTH
T1
SURVEY REFERENCE
STATION 1
SURVEY REFERENCE
STATION 2
TANK CENTER
STATE OF
P
R O
FES S IO NA L ENGIN
EE
R
M
IC
HA EL D. T OOTLENo. 67818 L I C E N S E
F L O R I D A
Date: 2021.09.09 18:13:27
2021.09.09 18:21:34 -04'00'
Tel. (787) 787-6010 Cel. 787-505-3190 info@antoniomelendezpr.com
TOPOGRAPHIC SURVEY
SURVEYORS NOTES:
ABBREVIATIONS: LEGEND
BORING LAYOUT
OF AN AREA LOCATED AT
THE HOSPITAL DE VETERANOS
SAN JUAN, PUERTO RICO
Sta. 1
Sta. 2
HORIZONTAL & VERTICAL CONTROL
3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124
FAX: (352) 553-4437
COA: FL REG #29758
AKEA Project No. 170-19
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECTS/ENGINEERSCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Design, Inc.
FOR CONSTRUCTION
BID DOCUMENTS
SAN JUAN, PUERTO RICO
SEPTEMBER 10, 2021
UPGRADE DOMESTIC
WATER SYSTEM FOR
HURRICANE HARDENING
672-19-716
WR MDT
100%
CONSTRUCTION
DOCUMENTS
C210
EROSION AND SEDIMENT CONTROL
T2
KEY PLAN - SITE
NORTH
T1
SURVEY REFERENCE
STATION 1
SURVEY REFERENCE
STATION 2
TANK CENTER
STATE OF
P
R O
FESS IO NA L ENGIN
EE
R
M
IC
HA EL D. T OOTLENo. 67818 L I C E N S E
F L O R I D A
Date: 2021.09.09 18:13:54
2021.09.09 18:19:17 -04'00'
Phone: (352) 474-6124
FAX: (352) 553-4437
COA: FL REG #29758
AKEA Project No. 170-19
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECTS/ENGINEERSCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Design, Inc.
FOR CONSTRUCTION
BID DOCUMENTS
SAN JUAN, PUERTO RICO
SEPTEMBER 10, 2021
UPGRADE DOMESTIC
WATER SYSTEM FOR
HURRICANE HARDENING
672-19-716
WR MDT
100%
CONSTRUCTION
DOCUMENTS
C220
EROSION AND SEDIMENT CONTROL
DETAILS
STATE OF
P
R O
FESS IO NA L ENGIN
EE
R
M
IC
HA EL D. T OOTLENo. 67818 L I C E N S E
F L O R I D A
Date: 2021.09.09 18:14:17 -04'00'
2021.09.09 18:22:41 -04'00'
Tel. (787) 787-6010 Cel. 787-505-3190 info@antoniomelendezpr.com
TOPOGRAPHIC SURVEY
SURVEYORS NOTES:
ABBREVIATIONS: LEGEND
BORING LAYOUT
OF AN AREA LOCATED AT
THE HOSPITAL DE VETERANOS
SAN JUAN, PUERTO RICO
Sta. 1
Sta. 2
HORIZONTAL & VERTICAL CONTROL
3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124
FAX: (352) 553-4437
COA: FL REG #29758
AKEA Project No. 170-19
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECTS/ENGINEERSCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Design, Inc.
FOR CONSTRUCTION
BID DOCUMENTS
SAN JUAN, PUERTO RICO
SEPTEMBER 10, 2021
UPGRADE DOMESTIC
WATER SYSTEM FOR
HURRICANE HARDENING
672-19-716
WR MDT
100%
CONSTRUCTION
DOCUMENTS
C300
TANK FOUNDATION FOOTPRINT
T2
KEY PLAN - SITE
NORTH
T1
SURVEY REFERENCE
STATION 1
SURVEY REFERENCE
STATION 2
TANK CENTER
BLDG CORNER
STATE OF
P
R O
FESS IO NA L ENGIN
EE
R
M
IC
HA EL D. T OOTLENo. 67818 L I C E N S E
F L O R I D A
Date: 2021.09.09 18:14:45 -04'00' William Rodriguez Arroyo
2021.09.09 18:42:24 -04'00'
Tel. (787) 787-6010 Cel. 787-505-3190 info@antoniomelendezpr.com
TOPOGRAPHIC SURVEY
SURVEYORS NOTES:
ABBREVIATIONS: LEGEND
BORING LAYOUT
OF AN AREA LOCATED AT
THE HOSPITAL DE VETERANOS
SAN JUAN, PUERTO RICO
Sta. 1
Sta. 2
HORIZONTAL & VERTICAL CONTROL
3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124
FAX: (352) 553-4437
COA: FL REG #29758
AKEA Project No. 170-19
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECTS/ENGINEERSCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Design, Inc.
FOR CONSTRUCTION
BID DOCUMENTS
SAN JUAN, PUERTO RICO
SEPTEMBER 10, 2021
UPGRADE DOMESTIC
WATER SYSTEM FOR
HURRICANE HARDENING
672-19-716
WR MDT
100%
CONSTRUCTION
DOCUMENTS
C310
TANK DIMENSIONS
T2
KEY PLAN - SITE
NORTH
T1
SURVEY REFERENCE
STATION 1
SURVEY REFERENCE
STATION 2
TANK CENTER
STATE OF
P
R O
FESS IO NA L ENGIN
EE
R
M
IC
HA EL D. T OOTLENo. 67818 L I C E N S E
F L O R I D A
Date: 2021.09.09 18:15:13 -04'00' William Rodriguez Arroyo
2021.09.09 18:40:54 -04'00'
Tel. (787) 787-6010 Cel. 787-505-3190 info@antoniomelendezpr.com
TOPOGRAPHIC SURVEY
SURVEYORS NOTES:
ABBREVIATIONS: LEGEND
BORING LAYOUT
OF AN AREA LOCATED AT
THE HOSPITAL DE VETERANOS
SAN JUAN, PUERTO RICO
Sta. 1
Sta. 2
HORIZONTAL & VERTICAL CONTROL
3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124
FAX: (352) 553-4437
COA: FL REG #29758
AKEA Project No. 170-19
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECTS/ENGINEERSCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Design, Inc.
FOR CONSTRUCTION
BID DOCUMENTS
SAN JUAN, PUERTO RICO
SEPTEMBER 10, 2021
UPGRADE DOMESTIC
WATER SYSTEM FOR
HURRICANE HARDENING
672-19-716
WR MDT
100%
CONSTRUCTION
DOCUMENTS
C320
SITE PLAN AT GRADE
T2
KEY PLAN - SITE
NORTH
T1
SURVEY REFERENCE
STATION 1
SURVEY REFERENCE
STATION 2
TANK CENTER
STATE OF
P
R O
FESS IO NA L ENGIN
EE
R
M
IC
HA EL D. T OOTLENo. 67818 L I C E N S E
F L O R I D A
Date: 2021.09.09 18:15:43 -04'00'
2021.09.09 18:39:25 -04'00'
Tel. (787) 787-6010 Cel. 787-505-3190 info@antoniomelendezpr.com
TOPOGRAPHIC SURVEY
SURVEYORS NOTES:
ABBREVIATIONS: LEGEND
BORING LAYOUT
OF AN AREA LOCATED AT
THE HOSPITAL DE VETERANOS
SAN JUAN, PUERTO RICO
Sta. 1
Sta. 2
HORIZONTAL & VERTICAL CONTROL
3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124
FAX: (352) 553-4437
COA: FL REG #29758
AKEA Project No. 170-19
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECTS/ENGINEERSCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Design, Inc.
FOR CONSTRUCTION
BID DOCUMENTS
SAN JUAN, PUERTO RICO
SEPTEMBER 10, 2021
UPGRADE DOMESTIC
WATER SYSTEM FOR
HURRICANE HARDENING
672-19-716
WR MDT
100%
CONSTRUCTION
DOCUMENTS
C330
GRADING PLAN
T2
KEY PLAN - SITE
NORTH
T1
SURVEY REFERENCE
STATION 1
SURVEY REFERENCE
STATION 2
TANK CENTER
STATE OF
P
R O
FESS IO NA L ENGIN
EE
R
M
IC
HA EL D. T OOTLENo. 67818 L I C E N S E
F L O R I D A
Date: 2021.09.09 18:16:08 -04'00' William Rodriguez Arroyo
2021.09.09 18:56:20 -04'00'
Tel. (787) 787-6010 Cel. 787-505-3190 info@antoniomelendezpr.com
TOPOGRAPHIC SURVEY
SURVEYORS NOTES:
ABBREVIATIONS: LEGEND
BORING LAYOUT
OF AN AREA LOCATED AT
THE HOSPITAL DE VETERANOS
SAN JUAN, PUERTO RICO
Sta. 1
Sta. 2
HORIZONTAL & VERTICAL CONTROL
3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124
FAX: (352) 553-4437
COA: FL REG #29758
AKEA Project No. 170-19
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECTS/ENGINEERSCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Design, Inc.
FOR CONSTRUCTION
BID DOCUMENTS
SAN JUAN, PUERTO RICO
SEPTEMBER 10, 2021
UPGRADE DOMESTIC
WATER SYSTEM FOR
HURRICANE HARDENING
672-19-716
WR MDT
100%
CONSTRUCTION
DOCUMENTS
C340
PAVING REPAIR AND
STRIPING PLAN
T2
KEY PLAN - SITE
NORTH
T1
SURVEY REFERENCE
STATION 1
SURVEY REFERENCE
STATION 2
TANK CENTER
STATE OF
P
R O
FESS IO NA L ENGIN
EE
R
M
IC
HA EL D. T OOTLENo. 67818 L I C E N S E
F L O R I D A
Date: 2021.09.09 18:16:38 -04'00' William Rodriguez Arroyo
2021.09.09 18:54:15 -04'00'
Phone: (352) 474-6124
FAX: (352) 553-4437
COA: FL REG #29758
AKEA Project No. 170-19
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECTS/ENGINEERSCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Design, Inc.
FOR CONSTRUCTION
BID DOCUMENTS
SAN JUAN, PUERTO RICO
SEPTEMBER 10, 2021
UPGRADE DOMESTIC
WATER SYSTEM FOR
HURRICANE HARDENING
672-19-716
WR MDT
100%
CONSTRUCTION
DOCUMENTS
TYPICAL BOLLARD DETAIL
TYPICAL TEMPORARY
CONSTRUCTION FENCE DETAIL
SIDEWALK
PROTECTION
ADJACENT TO
VEHICLE DRIVE
C350
CIVIL DETAILS
THIS DETAIL IS SHOWN TO INDICATE FOUNDATION RADIUS
OF 1'-6" GREATER THAN TANK RADIUS.
SEE STRUCTURAL DRAWINGS FOR FOUNDATION DESIGN
NEW ASPHALT PAVEMENT MEETS
EXISTING ASPHALT PAVEMENT
ROAD SAWCUT AND REPAIR LOCATION
AS NEEDED FOR SITE RESTORATION
STATE OF
P
R O
FESS IO NA L ENGIN
EE
R
M
IC
HA EL D. T OOTLENo. 67818 L I C E N S E
F L O R I D A
Date: 2021.09.09 18:17:22
2021.09.09 18:49:49 -04'00'
Phone: (352) 474-6124
FAX: (352) 553-4437
COA: FL REG #29758
AKEA Project No. 170-19
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECTS/ENGINEERSCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Design, Inc.
FOR CONSTRUCTION
BID DOCUMENTS
SAN JUAN, PUERTO RICO
SEPTEMBER 10, 2021
UPGRADE DOMESTIC
WATER SYSTEM FOR
HURRICANE HARDENING
672-19-716
WR MDT
100%
CONSTRUCTION
DOCUMENTS
C400
ELEVATION CROSS SECTIONS
EAST-WEST
3'
EXISTING CONDITION
DURING CONSTRUCTION
FINISH GRADE
14'
24'
14'
24'
SEE NOTE
C002
SEE NOTE
C002
SEE NOTE
C002
SEE NOTE
C002
STATE OF
P
R O
FESS IO NA L ENGIN
EE
R
M
IC
HA EL D. T OOTLENo. 67818 L I C E N S E
F L O R I D A
Date: 2021.09.09 18:17:56 -04'00'
2021.09.09 18:46:48 -04'00'
Tel. (787) 787-6010 Cel. 787-505-3190 info@antoniomelendezpr.com
TOPOGRAPHIC SURVEY
SURVEYORS NOTES:
ABBREVIATIONS: LEGEND
BORING LAYOUT
OF AN AREA LOCATED AT
THE HOSPITAL DE VETERANOS
SAN JUAN, PUERTO RICO
Sta. 1
Sta. 2
HORIZONTAL & VERTICAL CONTROL
3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124
FAX: (352) 553-4437
COA: FL REG #29758
AKEA Project No. 170-19
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECTS/ENGINEERSCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Design, Inc.
FOR CONSTRUCTION
BID DOCUMENTS
SAN JUAN, PUERTO RICO
SEPTEMBER 10, 2021
UPGRADE DOMESTIC
WATER SYSTEM FOR
HURRICANE HARDENING
672-19-716
WR MDT
100%
CONSTRUCTION
DOCUMENTS
C500
SITE SECURITY
FENCING AND BOLLARDS
T2
KEY PLAN - SITE
NORTH
T1
SURVEY REFERENCE
STATION 1
SURVEY REFERENCE
STATION 2
TANK CENTER
STATE OF
P
R O
FESS IO NA L ENGIN
EE
R
M
IC
HA EL D. T OOTLENo. 67818 L I C E N S E
F L O R I D A
Date: 2021.09.09 18:18:33 -04'00'
2021.09.09 18:45:17 -04'00'
COMMERCIAL CHAIN LINK FENCE
TYPICAL FENCE WITH TOP RAIL WITH
BARBED
WIRE
WITH
BARBED
WIRE
3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124
FAX: (352) 553-4437
COA: FL REG #29758
AKEA Project No. 170-19
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECTS/ENGINEERSCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Design, Inc.
FOR CONSTRUCTION
BID DOCUMENTS
SAN JUAN, PUERTO RICO
SEPTEMBER 10, 2021
UPGRADE DOMESTIC
WATER SYSTEM FOR
HURRICANE HARDENING
672-19-716
WR MDT
100%
CONSTRUCTION
DOCUMENTS
C501
FENCE DETAILS
STATE OF
P
R O
FESS IO NA L ENGIN
EE
R
M
IC
HA EL D. T OOTLENo. 67818 L I C E N S E
F L O R I D A
Date: 2021.09.09 18:19:50
2021.09.09 19:02:30 -04'00'
H
H
BANDS, RAIL ENDS & TIGHTENERS
POST TOPS
KNUCKLED SELVAGE
GATE FRAMES & HINGE
DOUBLE GATE
DETAIL A: TYPICAL CENTER REST
TYPICAL DROP ROD ASSEMBLY
RAIL SPLICE
FENCE MATERIALS
ORDINARY PIPE
GATE MATERIALS
3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124
FAX: (352) 553-4437
COA: FL REG #29758
AKEA Project No. 170-19
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECTS/ENGINEERSCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Design, Inc.
FOR CONSTRUCTION
BID DOCUMENTS
SAN JUAN, PUERTO RICO
SEPTEMBER 10, 2021
UPGRADE DOMESTIC
WATER SYSTEM FOR
HURRICANE HARDENING
672-19-716
WR MDT
100%
CONSTRUCTION
DOCUMENTS
C502
FENCE DETAILS
STATE OF
P
R O
FESS IO NA L ENGIN
EE
R
M
IC
HA EL D. T OOTLENo. 67818 L I C E N S E
F L O R I D A
Date: 2021.09.09 18:20:22
2021.09.09 18:58:22 -04'00'
Tel. (787) 787-6010 Cel. 787-505-3190 info@antoniomelendezpr.com
TOPOGRAPHIC SURVEY
SURVEYORS NOTES:
ABBREVIATIONS: LEGEND
BORING LAYOUT
OF AN AREA LOCATED AT
THE HOSPITAL DE VETERANOS
SAN JUAN, PUERTO RICO
Sta. 1
Sta. 2
HORIZONTAL & VERTICAL CONTROL
3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124
FAX: (352) 553-4437
COA: FL REG #29758
AKEA Project No. 170-19
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECTS/ENGINEERSCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Design, Inc.
FOR CONSTRUCTION
BID DOCUMENTS
SAN JUAN, PUERTO RICO
SEPTEMBER 10, 2021
UPGRADE DOMESTIC
WATER SYSTEM FOR
HURRICANE HARDENING
672-19-716
WR MDT
100%
CONSTRUCTION
DOCUMENTS
L100
LANDSCAPE: GRASSING PLAN
T2
KEY PLAN - SITE
NORTH
T1
SURVEY REFERENCE
STATION 1
SURVEY REFERENCE
STATION 2
TANK CENTER
STATE OF
P
R O
FESS IO NA L ENGIN
EE
R
M
IC
HA EL D. T OOTLENo. 67818 L I C E N S E
F L O R I D A
Date: 2021.09.09 18:20:48 -04'00' William Rodriguez Arroyo
2021.09.09 19:00:49 -04'00'
EX. SIDEWALK
P B
L A N D
IN
G
L A N D
IN
G
WALL & GALV. FENCE UNDER CONSTRUCTION
WALL & GALV. FENCE UNDER CONSTRUCTION
RAMP
Sta. 1
Sta. 2
UTILITY TRENCH
TRENCH
U T
IL
IT
Y
T R E N C H
UTILITY TRENCH
A101
NEW PUMP HOUSE
NEW STEEL TANK
(SEE STRUCTURAL)
3380 Trickum Road
Woodstock, GA. 30188 770-517-5507 voice 770-517-5508 fax
Bldg. 500, Ste. 100 www.ieiusa.com
INNOVATIVE
ENGINEERING
INCORPORATED
Design, Inc.
This drawing has been electronically signed and sealed by the individual named at right.
Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.
3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124
FAX: (352) 553-4437
COA: FL REG #29758
AKEA Project No. 170-19
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECTS/ENGINEERSCONSULTANT
321 4 5 6 7 8 9 10
PROFESSIONAL ENGINEER PR. LIC. NO.AKEA DESIGN: REGISTERED ARCHITECT
100%
CONSTRUCTION
DOCUMENTS
BID DOCUMENTS
FOR CONSTRUCTION
THOMAS H. GYLLSTROM, AIA
FL REG #AR0009098
-0 9-
5:
:5
ARCHITECTURAL SITE PLAN
UPGRADE DOMESTIC
WATER SYSTEM FOR
HURRICANE HARDENING
SAN JUAN, PUERTO RICO
672-19-716
THG JG
WILLIAM RODRIGUEZ 10209
A100
SEPTEMBER 10, 2021
1" = 10'-0"1 ARCHITECTURAL SITE PLAN
Revisions: Date: 19 OF 50
William Rodriguez Arroyo
2021.09.08 16:27:40 -04'00'
Digitally signed by Thomas H. Gyllstrom
AIA LEED AP
Date: 2021.09.09 10:49:22 -04'00'
Level 1 0' - 0"
PARAPET
10' - 0"
A101
B.O. ROOF
8' - 0"
L6
2'
8"
5' - 4"
4'
8"
7' - 5"20' - 0" 5' - 4"
35' - 4"
16"
7'
4"L8 L7 L3 L4
A101
A101
L4
A101
A101
15NOTE: ALL INTERIOR
SURFACES PT-1
STUCCO
L4
L3 L7 L8
Level 1 0' - 0"
PARAPET
10' - 0"
B.O. ROOF
8' - 0"
STUCCO
L6 L5
2" PVC PIPE SCUPPER & OVERFLOW
2" PVC PIPE SCUPPER & OVERFLOW
STUCCO
7'
4"
2' - 8" 3' - 4"
EF-1
16" x 16" R.O.
L2
Level 1 0' - 0"
PARAPET
10' - 0"
B.O. ROOF
8' - 0"
STUCCO
35' - 4"
1' - 4"
7'
4"
EF-2 - 16" x 16" R.O.
7'
4"L1 105 104
SCUPPER & OVERFLOW
SCUPPER & OVERFLOW
SLOPE CONCRETE ROOF
SLOPE CONCRETE ROOF
NOTE: CONCRETE SEALANT
RECOMMENDED
DOOR SCHEDULE NOTES
AND ABBREVIATIONS
DETAIL NUMBERS ARE ON A101
SEE 08 7100 FOR HARDWARE SETS
SEE 08 1710 FOR INTEGRATED DOOR ASSEMBLIES
ADO - AUTOMATIC DOOR OPENER
CR - CARD READER
HM - HOLLOW METAL
PR - PAIR
PP - PUSH PLATE, FOR ACTIVATING ADO's
DOOR
WIDTH
2" 2"
4" D
O O
R H
EI
G
H T
EQ
2" 2"
4" D
O O
R H
EI
G
H T
DOOR WIDTH
EQ
BACKER ROD AND
SEALANT, BOTH SIDES,
TYPICAL
CMU, REFERENCE STRUCTURAL
DRAWINGS FOR FILLED CMU CELL
REQUIREMENTS
DOOR AS SCHEDULED
MASONRY "T"-STRAP 3 PER JAMB
AT CMU WALL, TYP.
STUCCO FINISH
2"
6"
CONCRETE SLAB
RE: STRUCTURAL
DWGS.
ALUMINUM THRESHOLD
CONTINUOUS MASTIC BED
DOOR FRAME BEYOND
DOOR
JOINT SEALER
JOINT FILLER
CONCRETE
WALK
JT
SLOPE
SIDEWALK FOR
POSITIVE
DRAINAGE AWAY
FROM BUILDING
0' - 4"
0'
1"
REINFORCEMENT PLATE
FASTENED TO LOUVER &
PRECAST PANEL
INSECT AND BIRD SCREEN
LOUVER AS SCHEDULED
BACKER
ROD &
SEALANT
R.O.
DRIP EDGE
ANCHOR BOLTSTUCCO
FINISH
LOUVER AS SCHEDULED
R.O.
VERIFY W/ MFR.
0' - 0" MAX.
BACKER ROD & SEALANT
METAL SILL FLASHING
WITH END DAM
(ALL 3 SIDES)
INSECT AND BIRD SCREEN
REINFORCEMENT PLATE
FASTENED TO LOUVER &
PRECAST PANEL
CMU, REFERENCE STRUCTURAL
DRAWINGS FOR FILLED CMU CELL
REQUIREMENTS
STUCCO FINISH
CALK, BOTH SIDES
DOOR PANEL AS
SCHEDULED
GROUT FILL FRAME
6"D O
O R
H
EI
G H
T
AS
S C
H
ED
DOOR FRAME AS
SCHEDULED
STUCCO
FINISH SEE STRUCTURAL FOR
REINFORCEMENT
4"
PRE-FINISHED METAL SILL
FLASHING WITH END DAM
(ALL 3 SIDES)
SEALANT
CMU, REFERENCE STRUCTURAL
DRAWINGS FOR FILLED CMU
CELL REQUIREMENTS
BEAD OF SEALANT
UNDER FLASHING, TYP.
INSECT AND
BIRD SCREEN
R.O.
REINFORCEMENT
PLATE FASTENED
TO LOUVER &
PRECAST PANEL
LOUVER AS
SCHEDULED
STUCCO FINISH
0' - 2"
2' - 0" 4' - 0"
2'
8" 2'
0"
2'
8" 7'
4"
18' - 0"
5'
4"
6' - 0"
6'
0"
1' - 4"3' - 4"7' - 4"
4'
0" 5'
4"
2'
8" 5'
4"
3'
4"
2' - 8" 4' - 0" 4' - 8" 4' - 0" 2' - 8"
6'
8" 7'
4"
6'
8"
A101
A101
A101
A101
A101
A101
4'
0"
8"
2'
8" 7'
4"
L5 L6
L1
L8
L7
L3
L4
L2
EF-2
EF-1
NOTE: SEE MECHANICAL
FOR EXHAUST FAN AND
LOUVER SCHEDULE.
3380 Trickum Road
Woodstock, GA. 30188 770-517-5507 voice 770-517-5508 fax
Bldg. 500, Ste. 100 www.ieiusa.com
INNOVATIVE
ENGINEERING
INCORPORATED
Design, Inc.
This drawing has been electronically signed and sealed by the individual named at right.
Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.
3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124
FAX: (352) 553-4437
COA: FL REG #29758
AKEA Project No. 170-19
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECTS/ENGINEERSCONSULTANT
321 4 5 6 7 8 9 10
PROFESSIONAL ENGINEER PR. LIC. NO.AKEA DESIGN: REGISTERED ARCHITECT
100%
CONSTRUCTION
DOCUMENTS
BID DOCUMENTS
FOR CONSTRUCTION
THOMAS H. GYLLSTROM, AIA
FL REG #AR0009098
-1 0-
4:
:4
NEW PUMP HOUSE
ARCHITECTURAL DRAWINGS
UPGRADE DOMESTIC
WATER SYSTEM FOR
HURRICANE HARDENING
SAN JUAN, PUERTO RICO
672-19-716
THG JG
WILLIAM RODRIGUEZ 10209
A101
SEPTEMBER 10, 2021
1/4" = 1'-0"4 SECTION 4
1/4" = 1'-0"3 SECTION 3
1/4" = 1'-0"8 NEW PUMP EAST ELEVATION
1/4" = 1'-0"7 NEW PUMP NORTH ELEVATION
1/4" = 1'-0"6 NEW PUMP SOUTH ELEVATION
1/4" = 1'-0"5 NEW PUMP HOUSE WEST ELEVATION
1/4" = 1'-0"2 NEW PUMP HOUSE ROOF PLAN
DOOR AND FRAME SCHEDULE
MARK
LEAF
TYPE
DOOR DOOR FRAME DETAIL
FIRE
RATING HARDWARE COMMENTS
SIZE
MAT'L STYLE MAT'L STYLE HEAD JAMB SILLWIDTH HEIGHT
103 SINGLE 3' - 0" 7' - 0" HM D1 HM F1 12 13 14 -
104 DOUBLE 7' - 0" 7' - 2" HM D2 HM F2 12 13 14 -
105 DOUBLE 7' - 0" 7' - 2" HM D2 HM F2 12 13 14 -
1/4" = 1'-0"9 DOOR TYPES
1/4" = 1'-0"10 FRAME TYPES
3" = 1'-0"13 EXTERIOR DOOR JAMB DETAIL
3" = 1'-0"14
THRESHOLD DETAIL - EXTERIOR
HOLLOW METAL
3" = 1'-0"15 LOUVER HEAD DETAIL
3" = 1'-0"16 LOUVER JAMB DETAIL
3" = 1'-0"12 DOOR HEAD DETAIL
3" = 1'-0"17 LOUVER SILL DETAIL
D-1 D-2 F-1 F-2
2'
SCALE : 1/4" = 1'-0"
0 4' 8'
FINISH SCHEDULE
FINISH CODE FINISH TYPE
MANUFACTURER
NAME
OTHER
ACCEPTABLE
MFR'S DESCRIPTION PRODUCT NAME
PRODUCT
NUMBER COLOR NOTES
PT-2 STUCCO 3M CRYLI COTE
FLOOR TROWELED NATURAL MATCH
EXISTING PUMP HOUSE
PT-1 PAINT SYSTEM BENJAMIN MOORE LATEX (SEE SPECS) SCRUB TOUGH TO BE COORDINATED WITH
VA INTERIOR DESIGNER
FIELD PAINT- ENTIRE
PUMP HOUSE
1 1/2" = 1'-0"11 SCUPPER/OVERFLOW DETAIL
1/4" = 1'-0"18 NEW PUMP HOUSE FLOOR PLAN
BUILDING ELEVATION NOTES:
PAINT INTERIOR AND EXTERIOR OF CMU AND CONCRETE
ROOF DECK WITH 1 COAT BLOCK FILLER AND 1 COAT
ELASTOMERIC PAINT. COLOR TBD.
PAINT HOLLOW METAL DOORS AND FRAMES WITH 1
COAT EXTERIOR PRIMER AND 2 COATS EXTERIOR GLOSS
ACRYLIC ENAMEL PAINT. COLOR TBD.
Revisions: Date:
Revision 1 10/05/2021 Revision 2 10/27/2021
Digitally signed by Thomas H.
Gyllstrom AIA LEED AP Date: 2021.11.04 10:24:00 -04'00'
2021.11.05 11:28:10 -04'00'
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECTS/ENGINEERSCONSULTANT
321 4 5 6 7 8 9 10
OF
100%
CONSTRUCTION
DOCUMENTS
3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124 Fax: (352) 553-4437
QBO: FL REG#29758
AKEA Project No. 170-19
Design, Inc.
BID DOCUMENTS
FOR CONSTRUCTION
STRUCTURAL NOTES
UPGRADE DOMESTIC
WATER SYSTEM FOR
HURRICANE HARDENING
SAN JUAN, PUERTO RICO
672-19-716
SLM DCASEPTEMBER 10, 2021Revisions: Date:
Sta. 2
Bo B B B B
RAMP
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECTS/ENGINEERSCONSULTANT
321 4 5 6 7 8 9 10
OF
100%
CONSTRUCTION
DOCUMENTS
3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124 Fax: (352) 553-4437
QBO: FL REG#29758
AKEA Project No. 170-19
Design, Inc.
BID DOCUMENTS
FOR CONSTRUCTION
STRUCTURAL DEMOLITION PLAN
UPGRADE DOMESTIC
WATER SYSTEM FOR
HURRICANE HARDENING
SAN JUAN, PUERTO RICO
672-19-716
SLM DCASEPTEMBER 10, 2021
Scale: 1/8"=1'-0"
4' 8' 16' 24'2'
Revisions: Date:
EX. SIDEWALK
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECTS/ENGINEERSCONSULTANT
321 4 5 6 7 8 9 10
OF
100%
CONSTRUCTION
DOCUMENTS
3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124 Fax: (352) 553-4437
QBO: FL REG#29758
AKEA Project No. 170-19
Design, Inc.
BID DOCUMENTS
FOR CONSTRUCTION
OVERALL SITE PLAN
UPGRADE DOMESTIC
WATER SYSTEM FOR
HURRICANE HARDENING
SAN JUAN, PUERTO RICO
672-19-716
SLM DCASEPTEMBER 10, 2021
Scale: 1/8"=1'-0"
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECTS/ENGINEERSCONSULTANT
321 4 5 6 7 8 9 10
OF
100%
CONSTRUCTION
DOCUMENTS
3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124 Fax: (352) 553-4437
QBO: FL REG#29758
AKEA Project No. 170-19
Design, Inc.
BID DOCUMENTS
FOR CONSTRUCTION
PUMP HOUSE FRAMING PLANS
UPGRADE DOMESTIC
WATER SYSTEM FOR
HURRICANE HARDENING
SAN JUAN, PUERTO RICO
672-19-716
SLM DCASEPTEMBER 10, 2021
1' 2'
Scale: 1/2"=1'-0"
6" 4' 6
8' 1' 2'
Scale: 1/2"=1'-0"
6" 4' 6
8'
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECTS/ENGINEERSCONSULTANT
321 4 5 6 7 8 9 10
OF
100%
CONSTRUCTION
DOCUMENTS
3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124 Fax: (352) 553-4437
QBO: FL REG#29758
AKEA Project No. 170-19
Design, Inc.
BID DOCUMENTS
FOR CONSTRUCTION
TANK FOUNDATION PLAN
UPGRADE DOMESTIC
WATER SYSTEM FOR
HURRICANE HARDENING
SAN JUAN, PUERTO RICO
672-19-716
SLM DCASEPTEMBER 10, 2021
Scale: 1/8"=1'-0"
4' 8' 16' 24'2'
Scale: 1/8"=1'-0"
CONTRACTOR NOTE:
TYPICAL KEYWAY DIMENSIONS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECTS/ENGINEERSCONSULTANT
321 4 5 6 7 8 9 10
OF
100%
CONSTRUCTION
DOCUMENTS
3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124 Fax: (352) 553-4437
QBO: FL REG#29758
AKEA Project No. 170-19
Design, Inc.
BID DOCUMENTS
FOR CONSTRUCTION
CONCRETE DETAILS
UPGRADE DOMESTIC
WATER SYSTEM FOR
HURRICANE HARDENING
SAN JUAN, PUERTO RICO
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECTS/ENGINEERSCONSULTANT
321 4 5 6 7 8 9 10
OF
100%
CONSTRUCTION
DOCUMENTS
3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124 Fax: (352) 553-4437
QBO: FL REG#29758
AKEA Project No. 170-19
Design, Inc.
BID DOCUMENTS
FOR CONSTRUCTION
CONCRETE DETAILS
UPGRADE DOMESTIC
WATER SYSTEM FOR
HURRICANE HARDENING
SAN JUAN, PUERTO RICO
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECTS/ENGINEERSCONSULTANT
321 4 5 6 7 8 9 10
OF
100%
CONSTRUCTION
DOCUMENTS
3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124 Fax: (352) 553-4437
QBO: FL REG#29758
AKEA Project No. 170-19
Design, Inc.
BID DOCUMENTS
FOR CONSTRUCTION
CONCRETE DETAILS
UPGRADE DOMESTIC
WATER SYSTEM FOR
HURRICANE HARDENING
SAN JUAN, PUERTO RICO
8" MASONRY REBAR LAP SPLICE
LENGTH FOR SINGLE BARS IN CELLS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECTS/ENGINEERSCONSULTANT
321 4 5 6 7 8 9 10
OF
100%
CONSTRUCTION
DOCUMENTS
3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124 Fax: (352) 553-4437
QBO: FL REG#29758
AKEA Project No. 170-19
Design, Inc.
BID DOCUMENTS
FOR CONSTRUCTION
MASONRY DETAILS
UPGRADE DOMESTIC
WATER SYSTEM FOR
HURRICANE HARDENING
SAN JUAN, PUERTO RICO
M200
PART. SITE PLAN AND FLOOR PLAN -
NEW PUMP STATION 3 - VENTILATION
T2
KEY PLAN - SITE
NORTH
T1
3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124
FAX: (352) 553-4437
COA: FL REG #29758
AKEA Project No. 170-19
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECTS/ENGINEERSCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
100%
CONSTRUCTION
DOCUMENTS
William Rodriguez Arroyo
2021.09.08 13:23:41 -04'00'
10" DCW
P100
PARTIAL SITE PLAN - EXISTING
CONDITIONS SCHEMATIC
T2
KEY PLAN - SITE
NORTH
T1
3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124
FAX: (352) 553-4437
COA: FL REG #29758
AKEA Project No. 170-19
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECTS/ENGINEERSCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
100%
CONSTRUCTION
DOCUMENTS
William Rodriguez Arroyo
2021.09.08 13:25:28
Phone: (352) 474-6124
FAX: (352) 553-4437
COA: FL REG #29758
AKEA Project No. 170-19
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECTS/ENGINEERSCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
100%
CONSTRUCTION
DOCUMENTS
P101
PARTIAL SITE PLAN -
DEMOLITION
T2
KEY PLAN - SITE
NORTH
T1
William Rodriguez Arroyo
2021.09.08 13:28:09
B
C
3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124
FAX: (352) 553-4437
COA: FL REG #29758
AKEA Project No. 170-19
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECTS/ENGINEERSCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
100%
CONSTRUCTION
DOCUMENTS
P200
ENLARGED PARTIAL SITE PLAN -
NEW WORK - STEEL TANK
T2
KEY PLAN - SITE
NORTH
T1
1 2
William Rodriguez Arroyo
2021.09.08 13:31:08
C
C C
P201
GENERAL PARTIAL SITE PLAN
T2
KEY PLAN - SITE
NORTH
T1
3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124
FAX: (352) 553-4437
COA: FL REG #29758
AKEA Project No. 170-19
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECTS/ENGINEERSCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
100%
CONSTRUCTION
DOCUMENTS
William Rodriguez Arroyo
2021.09.08 13:34:06
A
P202
PARTIAL PLANS AND SECTIONS -
EXISTING MAIN PUMP STATION
T2
KEY PLAN - SITE
NORTH
T1
3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124
FAX: (352) 553-4437
COA: FL REG #29758
AKEA Project No. 170-19
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECTS/ENGINEERSCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
100%
CONSTRUCTION
DOCUMENTS
B
A
C
William Rodriguez Arroyo
2021.09.08 13:37:24
P300
FLOW DIAGRAM - EXISTING
PIPING ARRANGEMENTS
3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124
FAX: (352) 553-4437
COA: FL REG #29758
AKEA Project No. 170-19
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECTS/ENGINEERSCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
100%
CONSTRUCTION
DOCUMENTS
William Rodriguez Arroyo
2021.09.08 13:39:18
Phone: (352) 474-6124
FAX: (352) 553-4437
COA: FL REG #29758
AKEA Project No. 170-19
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECTS/ENGINEERSCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
100%
CONSTRUCTION
DOCUMENTS
P301
FLOW DIAGRAM - NEW PIPING
ARRANGEMENTS
Revision 1 10/05/2021 Revision 2 - LEVEL INDICATOR & TRANSMITTER 10/27/2021
2021.10.27 15:51:15 -04'00'
MAIN POTABLE WATER SUPPLY PUMPS
(REFER TO SPECIFICATION SECTION 22 11 23)
NEW CENTRIFUGAL PUMPS AND CONTROLS (REPLACE EXISTING PUMPS: P-7, P-8, P-9, & P-10):
DESIGN CRITERIA
The process conditions considered for this design have been:
Fluid: Potable water Temperature: 80° F Specific gravity: 1.0
Maximum Required Flowrate Capacity: 900 gpm Required Discharge Pressure: 100 psig Total Number of Pumps: Four (4) units Number of Pumps for Required Capacity: Three (3) units Hydraulic Redundancy:
33% Type of suction: Flooded (storage tanks) Minimum Piping Size for Pump: 4.0” (7.56 fps velocity) Pumps' Type of Operation: Variable speed System's Installation: Indoor, NO direct sunlight exposure, 90 °F maximum ambient temperature Electrical Classification: Non-classified area, TEFC motors and NEMA 12 enclosure Electrical Feeder: 3 / 60 / 460 VAC Electrical Panel: Field Mounted Type of Control: PLC & Operator Interface Terminal (OIT)
Remote Communication: BACNET
BASIS OF DESIGN
To furnish:
Four (4) centrifugal multi-stage inline pumps One (1) quadruplex electrical panel for power and control purposes One (1) analog pressure transmitter to be installed in the common discharge manifold
Four (4) centrifugal multi-stage inline pumps each with capacity of 300 gpm at 231 ft TDH in order to meet a system's demand of 900 gpm @ 100 psig discharge pressure. The total maximum system capacity will be handled by three (3) identical pumps operating simultaneously; the fourth identical pump is for spare purposes providing 33% hydraulic redundancy.
The common discharge manifold includes an analog pressure transmitter. A PLC control unit will compare the pressure setting with the transmitter feedback and will regulate the pressure of the system varying the speed of the pump(s). The control system will adjust the kilowatt power delivered and used by any pump operating to match the system flow rate and pressure requirement at any time. The system will monitor the KW requirement of the motor and the quantity of pumps required to provide the system's demand. Lag pump(s) will ramp speed up to operating speed of the lead pump and then increase or reduce as necessary. Pumps operating in parallel will always operate at the same speed. Once the pressure of the system is stabilized and the RPM and KW measures are near the minimum for certain amount of time the lag pump will shut down until the lead pump provides the system's demand.
Pumps will alternate automatically based on pre-determined scheduled time every 24-hours period, cycles of operation or a fault associated to the pump(s) in operation whenever the HAND / OFF / AUTOMATIC selector switches are in automatic mode.
The system is connected to a flooded suction and requires a minimum pipe size of 4.00” from the storage tank to each pump.
The electrical panel includes a password protected operator interface terminal (OIT) the following features:
Main Screen: shows pumps status (OFF / ON / MANUAL / AUTOMATIC / FAULT, SPEED), discharge pressure (psig units)
Status Screen: shows status of the possible alarms (VFD fault, phase loss, low discharge pressure, discharge pressure transmitter communication fault, system stop).
Trend Screen: shows discharge pressure trend vs. time, energy consumption vs. time
Alarm Log: shows list of detected alarms with time / date details
Preventive Maintenance Screen: shows hour-meters and maintenance warnings with password protected reset function.
Setpoints Screen: shows the setpoints for discharge pressure, low discharge pressure alarm, high discharge pressure alarm, manual mode pre-set pump speed. Password protected for supervisor level.
For all above alarm conditions a visual and audible signal will be energized. To silence the audible alarm horn a SILENCER pushbutton is included but the alarm message will be energized until the associated situation is no longer present.
The heat computation for cooling purposes of the VFD panel has been designed using the following parameters:
Indoor installation No direct sunlight exposure 90°F maximum ambient temperature Maximum of three (3) pumps operating simultaneously
The system provides a BACNET gateway for communication with the BMS and the following I/O's for remote interface through terminal contacts:
One (1) dry-contact relay output for remote SYSTEM ON indication
One (1) dry-contact relay output for remote GENERAL FAULT indication
In addition, the panel includes the following features:
Managed Ethernet/IP switch with Network Address Translation (NAT) router connected to BACNET gateway
Panel-mounted program port (with Ethernet/IP communication port, 120 VAC simplex outlet) to reduce the risk of personal exposure of arc flash by reducing the need to access the enclosure
EQUIPMENT DESCRIPTION
NEW CENTRIFUGAL PUMPS AND CONTROLS (REPLACE EXISTING):
One (1) set of components for quadruplex potable water booster pump system (shipped loose and installed by others) consisting of the following components:
Centrifugal Pump: Four (4) Grundfos end-suction multi-stage centrifugal pumps model CR64-3-2A-G-A-E-HQQE, three (3) stages, able to handle 300 gpm @ 231 ft TDH, 4.0” ANSI Class 150# flanged suction / discharge connections, cast iron construction, 304 stainless steel impellers, 78.2% efficiency, 9.38 ft NPSHr, 27.2 HP required at design conditions, single cartridge mechanical seal (silicon carbide vs. silicon carbide faces, EPDM elastomers, 316 stainless steel metallic parts), motor (30 HP, 3500 rpm, TEFC enclosure, premium efficiency, inverter duty, 3/60/460 VAC, 35 FLA).
Pressure Transmitter (Common Discharge Manifold): One (1) Rosemount head pressure gage transmitter model 2088G2S22A1M4Q4, 0 - 150 psig pressure range, (1) 4-20 mADC Hart analog output, ½” MNPT process connection in 316L stainless steel construction, 316L stainless steel construction isolating diaphragm, silicone fill fluid, ½” FNPT electrical conduit connection, NEMA 4X LCD integral display with local operator interface, calibration certificate included, 316 stainless steel isolation ball valve with manual operation lever type.
POTABLE WATER BOOSTER PUMPS (continued)
(REFER TO SPECIFICATION SECTION 22 11 23)
Electrical Panel (with Redundancy): One (1) electrical panel for power and control purposes with:
(1) NEMA 12 enclosure, 72” (H) x 36” (W) x 24” (D), carbon steel with ANSI-61 gray powder coated, single door, concealed hinges, 3-point latching mechanics, wall / surface mounted style
(2) NEMA 12 filtered exhaust fan, 860 cfm free air displacement, easy pull-out cleanable / reusable 10-micron filter, 1 /
60 / 120 VAC, 1.96 FLA
(1) main power distribution block with cover
(1) 500 VA 460/120 VAC control transformer
(1) 460 VAC phase monitor
(1) 600 VA uninterruptible power supply (UPS) for 120 VAC control circuit
(1) 1.3 amps / 24 VDC power supply for PLC and instruments
(1) 4 amps / 24 VDC power supply for OIT & Ethernet switch
(1) 8-port Managed Ethernet/IP switch with Network Address Translation (NAT) router
(1) ProSoft PS-QS-1010-0780 Quickserver gateway (Ethernet/IP to BACnet/IP), (1) Ethernet 10/100 RJ45 / (2) serial RS-485 terminal field connection, 24 VDC, 250 maximum points, DIN-rail mounted, BTL Mark approval
(1) panel-mounted program port with Ethernet/IP communication port, 120 VAC programmer's simplex outlet
(1) 2 poles / 2 amps miniature circuit breaker for control transformer
(1) 3 poles / 2 amps miniature circuit breaker for phase monitor
(1) 1 pole / 4 amps miniature circuit breaker for 120 VAC circuit
(4) 3 poles / 63 amps load switch with door-mounted rotary type lockable disconnect switch for LOTO purposes
(4) Allen Bradley variable frequency drive (VFD) model PowerFlex 525 sized for 30 HP / 3 / 60 / 460 VAC with integral alphanumeric human interface module (HIM), embedded Ethernet/IP communication module
(1) I/O Chassis for programmable logic controller (PLC) consisting of:
o (1) 7-slot ControlLogix chassis o (1) Allen Bradley 85-265 VAC power supply 10 amps @ 5V for ControlLogix o (1) Ethernet dual port 10-100M interface module (supports 128 TCP/IP connections, up to 8 axis), ring and linear topologies o (1) digital AC inputs module o (1) digital isolated relay output module o (1) analog current / voltage input module o (3) slot filler module for standard ControlLogix chassis
(1) Redundancy chassis consisting of:
o (1) 4-slot ControlLogix chassis o (1) Allen Bradley 85-265 VAC Power Supply 10 Amp @ 5V for ControlLogix o (1) ControlLogix 5570 controller with 2 MB memory o (1) Ethernet dual port 10-100M interface module (supports 128 TCP/IP connections, up to 8 axis), ring and linear topologies o (1) Ethernet 10-100M interface module o (1) ControlLogix redundancy module
(1) Allen Bradley PanelView Plus 7 Standard operator interface terminal (OIT), TFT color touchscreen, 10.4”, Ethernet/IP communication port, 24 VDC
(1) door-mounted maintained contact mushroom type twist-to-release pushbutton for SYSTEM STOP
(4) door-mounted 3-position selector switch for PUMP HAND / OFF / AUTOMATIC operation mode
(1) panel-mounted audible alarm horn
(1) panel-mounted tower light, (1) green beacon for SYSTEM ON indication, (1) red beacon for GENERAL FAULT indication
(1) dry-contact relay output for remote SYSTEM ON indication
(1) dry-contact relay output for remote GENERAL FAULT indication
(1) set of numbered terminal contacts, wire duct, wiring and phenolic labels
Manufacturer base of design: ENGINEERED, PARTS, AND SERVICES, INC.
RESERVED RESERVED
END OF SECTION
END OF SECTION
3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124
FAX: (352) 553-4437
COA: FL REG #29758
AKEA Project No. 170-19
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECTS/ENGINEERSCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
100%
CONSTRUCTION
DOCUMENTS
P600
POTABLE WATER EQUIPMENT
DATA
William Rodriguez Arroyo
2021.09.08 13:57:21
Maximum required flowrate capacity: 900 gpm
Required discharge pressure: 64 psig
Total number of pumps: Three (3) units
Number of pumps for required capacity: Two (2) units
Hydraulic redundancy: 50%
Type of suction: Flooded, inline type pressurized by PRASA
Piping material of construction: 304 stainless steel schedule 10
Size of Main Common Suction Manifold: 6.00”
Velocity of suction manifold at full capacity: 10.00 fps
Size of main common discharge manifold: 6.00”
Velocity of discharge manifold at full capacity: 10.00 fps
Pumps' type of operation: Variable speed
System's installation: Outdoor, NO direct sunlight exposure, 95 °F maximum ambient temperature
Electrical Classification: Non-classified area, TEFC motors and NEMA 4X enclosure in 304SS construction
Electrical Feeder: 3 Ph / 60 Hz / 460 VAC
Electrical Panel: Integral to skid
Type of Control: Programmable logic control (PLC) & operator interface terminal (OIT) TFT color touchscreen type by skid's manufacturer. Includes automatic ON/OFF butterfly valve for bypass resulting in energy savings when supply water source's pressure is above 40 psig
BASIS OF DESIGN & SEQUENCE OF OPERATION
To furnish one (1) skid-mounted triplex potable water booster system sized for 900 gpm @ 64 psig discharge pressure with NSF61 certified components. The total maximum system capacity will be handled by two (2) identical pumps operating simultaneously; the third identical pump is for spare purposes providing 50% hydraulic redundancy.
The common discharge manifold includes an analog pressure transmitter. A PLC control unit will compare the pressure setting with the transmitter feedback and will regulate the pressure of the system varying the speed of the pump(s). The control system will adjust the kilowatt power delivered and used by any pump operating to match the system flow rate and pressure requirement at any time. The system will monitor the KW requirement of the motor and the quantity of pumps required to provide the system's demand. Lag pump will ramp speed up to operating speed of the lead pump and then increase or reduce as necessary. Pumps operating in parallel will always operate at the same speed. Once the pressure of the system is stabilized and the RPM and KW measures are near the minimum for certain amount of time the lag pump will shut down until the lead pump provides the system's demand.
Pumps will alternate automatically based on pre-determined scheduled time every 24-hours period, cycles of operation, operational time or a fault associated to the pump(s) in operation whenever the HAND / OFF / AUTOMATIC selector switches are in automatic mode.
The system is connected to a flooded suction and requires a minimum pipe size of 6.00” the existing PRASA supply line to the skid's suction manifold. The suction manifold includes an analog pressure transmitter to protect the system against dry run conditions and monitor the suction pressure to operate the bypass automatic ON / OFF valve.
The electrical panel includes a password protected operator interface terminal (OIT) the following features:
Main Screen: shows pumps status (OFF / ON / MANUAL / AUTOMATIC / STAND-BY, FAULT), pump speed (Hz units) suction pressure (psig units), discharge pressure (psig units), discharge pressure setpoint (psig units), bypass valve status (OPEN / CLOSED / MANUAL / AUTOMATIC / FAULT)
Status Screen: shows status of the possible alarms (VFD fault, low energy consumption, broken pipe, phase loss, low suction pressure, suction pressure transmitter fault, low discharge pressure, discharge pressure transmitter fault, bypass valve position fault, system stop, PLC low battery).
Trend Screen: shows discharge pressure trend vs. time, energy consumption vs. time
Alarm Log: shows list of detected alarms with time / date details
Preventive Maintenance Screen: shows hour-meters and maintenance warnings with password protected reset function.
Setpoints Screen: shows the setpoints for discharge pressure, low suction pressure alarm, low discharge pressure alarm, high discharge pressure alarm, manual mode pre-set pump speed. Password protected for supervisor level.
For all above alarm conditions a visual and audible signal will be energized. To silence the audible alarm horn a SILENCER pushbutton is included but the alarm message will be energized until the associated situation is no longer present.
The heat computation…