Attachment 01 - Salient Characteristics Sheet.docx

DOCX document 17 KB Posted

Attached to
Portable Deluge Sprinkler System Federal contract opportunity
Solicitation number
W911RX25QA075
Issued by
Department of the Army Materiel Command Mission and Installation Contracting Command Fort Hood

About this file

The file is a Salient Characteristics Sheet for a Portable Deluge Sprinkler System solicitation (W911RX25QA075) issued by the Department of the Army Materiel Command Mission and Installation Contracting Command Fort Hood. The solicitation requires contractors to provide a portable fire suppression system with specific technical specifications, including a 120-gallon water tank, high-speed UV/IR detectors, CPF-74B pilot operated valves, electrically supervised control circuits, and compliance with Class I, Div II safety standards.

The procurement will be evaluated on a Lowest Price Technically Acceptable basis, with technical and price factors given equal importance. To be considered for award, offerors must submit a completed Solicitation form, Salient Characteristics Sheet, and a Quote document with product details and pricing. Responses must be emailed to Contract Specialist Noah Younger at noah.w.younger.civ@army.mil. The system must meet or exceed all listed technical characteristics, including a system response time under 100 milliseconds, specific dimensional requirements (65" x 36" x 54"), and a weight of approximately 1,300 lbs when the water tank is full.

View the file

Other files for this federal contract opportunity

Other files attached to Portable Deluge Sprinkler System, newest first.
File Type Posted
Solicitation - W911RX25QA075.pdf PDF
Solicitation - W911RX25QA075.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Salient Characteristics for W911RX25Q0075: Portable Deluge Sprinkler System (Please fill out, sign, and return form with your quote) Company name: ___________________ Date: ______________________ Specifications/Salient Characteristics:

Please provide the required specifications for the Portable Deluge System.

Technical Evaluation Technical Evaluation will be performed on a MEET OR EXCEED basis.

Product proposals will be evaluated on the basis of the below listed salient characteristics. In order for a product to be given a rating of ‘Technically Acceptable’, it must MEET OR EXCEED all below listed salient characteristics.

Pictures will be accepted, but not in lieu of below filled-out table.

Salient Physical, functional, or performance characteristics are below:

Review Results:

Activity Required Specification and Salient Characteristics
Contractor Proposed Specifications

(Contractor Fills out) Does Not Meet/Meets/Exceeds Salient Characteristics (Contractor Fills out) Does Not Meet/Meets/Exceeds Salient Characteristics (Government Fills out)

System Response time less than 100 Milliseconds

2 High Speed UV/IR detectors with 20 foot cables and swivel clamps

4 CPF-74B Pilot operated valves with 20 foot hoses and swivel clamps

Single or dual zone operation

Electrically supervised control circuits for detection, solenoids, and monitoring devices

Visual and audible fault indications for low water pressure, low water level, RAM/detector fault, low battery condition

“System Ready” and AC Power indication

Self-contained, 120 gallon water tank pressurized by an on-board nitrogen supply

Uses Ram Modules for Solenoid operation with one button or automatic reset.

Nozzle flow rate of 25GPM per nozzle

Swivel castors and forklift guides provided for transport.

Dimensions: Length – 65” Width – 36” Height – 54”

Weight (Full Water Tank): approximately 1,300 lbs.

Uses on-board 24VDC power supply or can be plugged into 110-220 VAC

Meets requirements of Class I, Div II, Groups C and D, plus Class II, Div II, groups E, F, G.

For Government use only (contractors do not fill out) Reviewed by:

Name: _______________________________________________________________ Signature: ___________________________________________________________ Date: ________________________________________________________________ Technically Acceptable:

Yes _______ No _______

Comments: