Attachment 01 - Drawings Expand Electrical Distribution (87 pages).pdf
PDF 39 MB Posted
- Attached to
- N061--Expand Electrical Distribution Federal contract opportunity
- Solicitation number
- 36C24823R0102
View the file
Other files for this federal contract opportunity
Show all 13
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
E E
E
VICINITY MAP
DEPARTMENT OF VETERANS AFFAIRS
NETWORK CONTRACTING ACTIVITY 8
MALCOM RANDALL VA MEDICAL CENTER
1601 SW ARCHER ROAD
GAINESVILLE, FL 32608
3603 NW 98TH STREET, SUITE B
GAINESVILLE, FLORIDA 32606
PH: (352) 474-6124
FAX. (352) 553-4437
COA: FL #29758
DESIGNED FOR:
Veterans Affairs Department of
DESIGNED BY:
PROJECT
LOCATION
PROJECT LOCATION MAP
PROJECT
LOCATION
G001
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
FINAL BID DOCUMENTS
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
321 4 5 6 7 8 10
EXPAND ELECTRICAL DISTRIBUTION
LAKE CITY, FLORIDA
573A4-18-601
APRIL 28, 2022Revisions: Date:
Office of Construction and Facilities Management
A
B
C
D
E
F
3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124 Fax: (352) 553-4437
COA: FL #29758
AKEA Design Proj. No. AD160-18
ARCHITECT / ENGINEER OF RECORDCONSULTANT
87OF
P R
O
FES S IO NA L ENGIN
EE
R
R O
BER T A . HA FFEM
A
N
L I C E N S E
F L O R I D A
PROJECT
LOCATION
Affiliated Engineers SE, Inc.
Tioga Town Center 12921 SW 1st Road Ste 205 Gainesville, Florida 32669 Tel 352.376.5500 Fax 352.375.3479
CA-5140 1
Robert A Haffema n
Date:
2022.04.29 06:25:31 -04'00'
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
FINAL BID DOCUMENTS
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
321 4 5 6 7 8 10
EXPAND ELECTRICAL DISTRIBUTION
LAKE CITY, FLORIDA
573A4-18-601
APRIL 28, 2022Revisions: Date:
Office of Construction and Facilities Management
A
B
C
D
E
F
3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124 Fax: (352) 553-4437
COA: FL #29758
AKEA Design Proj. No. AD160-18
ARCHITECT / ENGINEER OF RECORDCONSULTANT
87OF
P R
O
FES S IO NA L ENGIN
EE
R
R O
BER T A . HA FFEM
A
N
L I C E N S E
F L O R I D A G002 Affiliated Engineers SE, Inc.
Tioga Town Center 12921 SW 1st Road Ste 205 Gainesville, Florida 32669 Tel 352.376.5500 Fax 352.375.3479
CA-5140 2
Robert A Haffeman
Date:
2022.04.27 14:53:28 -04'00'
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FINAL BID DOCUMENTS
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
321 4 5 6 7 8 10
EXPAND ELECTRICAL DISTRIBUTION
LAKE CITY, FLORIDA
573A4-18-601
APRIL 28, 2022Revisions: Date:
Office of Construction and Facilities Management
APPROVED FOR CONSTRUCTION
A
B
C
D
E
F
3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124 Fax: (352) 553-4437
COA: FL #29758
AKEA Design Proj. No. AD160-18
Design, Inc.
ARCHITECT / ENGINEER OF RECORDCONSULTANT
FINAL BID DOCUMENTS
87OF
MDT MDT
C001
STATE OF
P R
O
FESS IO NA L ENGIN
E E
R
M
IC
HA EL D. T OOT LENo. 67818 L I C E N S E
F L O R I D A
Digitally signed by Michael D Tootle Date: 2022.04.27 15:32:44 -04'00'
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FINAL BID DOCUMENTS
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
321 4 5 6 7 8 10
EXPAND ELECTRICAL DISTRIBUTION
LAKE CITY, FLORIDA
573A4-18-601
APRIL 28, 2022Revisions: Date:
Office of Construction and Facilities Management
APPROVED FOR CONSTRUCTION
A
B
C
D
E
F
3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124 Fax: (352) 553-4437
COA: FL #29758
AKEA Design Proj. No. AD160-18
Design, Inc.
ARCHITECT / ENGINEER OF RECORDCONSULTANT
FINAL BID DOCUMENTS
87OF
SHEET NOTES
SHEET KEYNOTES
C002
STATE OF
P R
O
FESS IO NA L ENGIN
E E
R
M
IC
HA EL D. T OOTLENo. 67818 L I C E N S E
F L O R I D A
Date: 2022.04.27 15:33:35 -04'00'
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FINAL BID DOCUMENTS
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
321 4 5 6 7 8 10
EXPAND ELECTRICAL DISTRIBUTION
LAKE CITY, FLORIDA
573A4-18-601
APRIL 28, 2022Revisions: Date:
Office of Construction and Facilities Management
APPROVED FOR CONSTRUCTION
A
B
C
D
E
F
3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124 Fax: (352) 553-4437
COA: FL #29758
AKEA Design Proj. No. AD160-18
Design, Inc.
ARCHITECT / ENGINEER OF RECORDCONSULTANT
FINAL BID DOCUMENTS
87OF
C003
STATE OF
P R
O
FESS IO NA L ENGIN
E E
R
M
IC
HA EL D. T OOTLENo. 67818 L I C E N S E
F L O R I D A
Date: 2022.04.27 15:34:25 -04'00'
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FINAL BID DOCUMENTS
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
321 4 5 6 7 8 10
EXPAND ELECTRICAL DISTRIBUTION
LAKE CITY, FLORIDA
573A4-18-601
APRIL 28, 2022Revisions: Date:
Office of Construction and Facilities Management
APPROVED FOR CONSTRUCTION
A
B
C
D
E
F
3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124 Fax: (352) 553-4437
COA: FL #29758
AKEA Design Proj. No. AD160-18
Design, Inc.
ARCHITECT / ENGINEER OF RECORDCONSULTANT
FINAL BID DOCUMENTS
87OF
C100
STATE OF
P R
O
FESS IO NA L ENGIN
E E
R
M
IC
HA EL D. T OOT LENo. 67818 L I C E N S E
F L O R I D A
Date: 2022.04.27 15:37:24 -04'00'
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FINAL BID DOCUMENTS
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
321 4 5 6 7 8 10
EXPAND ELECTRICAL DISTRIBUTION
LAKE CITY, FLORIDA
573A4-18-601
APRIL 28, 2022Revisions: Date:
Office of Construction and Facilities Management
APPROVED FOR CONSTRUCTION
A
B
C
D
E
F
3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124 Fax: (352) 553-4437
COA: FL #29758
AKEA Design Proj. No. AD160-18
Design, Inc.
ARCHITECT / ENGINEER OF RECORDCONSULTANT
FINAL BID DOCUMENTS
87OF
C101
STATE OF
P R
O
FESS IO NA L ENGIN
E E
R
M
IC
HA EL D. T OOT LENo. 67818 L I C E N S E
F L O R I D A
Date: 2022.04.27 15:39:01 -04'00'
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FINAL BID DOCUMENTS
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
321 4 5 6 7 8 10
EXPAND ELECTRICAL DISTRIBUTION
LAKE CITY, FLORIDA
573A4-18-601
APRIL 28, 2022Revisions: Date:
Office of Construction and Facilities Management
APPROVED FOR CONSTRUCTION
A
B
C
D
E
F
3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124 Fax: (352) 553-4437
COA: FL #29758
AKEA Design Proj. No. AD160-18
Design, Inc.
ARCHITECT / ENGINEER OF RECORDCONSULTANT
FINAL BID DOCUMENTS
87OF
C200
STATE OF
P R
O
FESS IO NA L ENGIN
E E
R
M
IC
HA EL D. T OOT LENo. 67818 L I C E N S E
F L O R I D A
Date: 2022.04.27 15:39:50 -04'00'
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FINAL BID DOCUMENTS
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
321 4 5 6 7 8 10
EXPAND ELECTRICAL DISTRIBUTION
LAKE CITY, FLORIDA
573A4-18-601
APRIL 28, 2022Revisions: Date:
Office of Construction and Facilities Management
APPROVED FOR CONSTRUCTION
A
B
C
D
E
F
3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124 Fax: (352) 553-4437
COA: FL #29758
AKEA Design Proj. No. AD160-18
Design, Inc.
ARCHITECT / ENGINEER OF RECORDCONSULTANT
FINAL BID DOCUMENTS
87OF
C201
STATE OF
P R
O
FESS IO NA L ENGIN
E E
R
M
IC
HA EL D. T OOT LENo. 67818 L I C E N S E
F L O R I D A
Date: 2022.04.27 15:41:07 -04'00'
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FINAL BID DOCUMENTS
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
321 4 5 6 7 8 10
EXPAND ELECTRICAL DISTRIBUTION
LAKE CITY, FLORIDA
573A4-18-601
APRIL 28, 2022Revisions: Date:
Office of Construction and Facilities Management
APPROVED FOR CONSTRUCTION
A
B
C
D
E
F
3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124 Fax: (352) 553-4437
COA: FL #29758
AKEA Design Proj. No. AD160-18
Design, Inc.
ARCHITECT / ENGINEER OF RECORDCONSULTANT
FINAL BID DOCUMENTS
87OF
C300
STATE OF
P R
O
FESS IO NA L ENGIN
E E
R
M
IC
HA EL D. T OOT LENo. 67818 L I C E N S E
F L O R I D A
Date: 2022.04.27 15:42:33 -04'00'
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FINAL BID DOCUMENTS
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
321 4 5 6 7 8 10
EXPAND ELECTRICAL DISTRIBUTION
LAKE CITY, FLORIDA
573A4-18-601
APRIL 28, 2022Revisions: Date:
Office of Construction and Facilities Management
APPROVED FOR CONSTRUCTION
A
B
C
D
E
F
3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124 Fax: (352) 553-4437
COA: FL #29758
AKEA Design Proj. No. AD160-18
Design, Inc.
ARCHITECT / ENGINEER OF RECORDCONSULTANT
FINAL BID DOCUMENTS
87OF
C301
STATE OF
P R
O
FESS IO NA L ENGIN
E E
R
M
IC
HA EL D. T OOT LENo. 67818 L I C E N S E
F L O R I D A
Date: 2022.04.27 15:43:40 -04'00'
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FINAL BID DOCUMENTS
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
321 4 5 6 7 8 10
EXPAND ELECTRICAL DISTRIBUTION
LAKE CITY, FLORIDA
573A4-18-601
APRIL 28, 2022Revisions: Date:
Office of Construction and Facilities Management
APPROVED FOR CONSTRUCTION
A
B
C
D
E
F
3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124 Fax: (352) 553-4437
COA: FL #29758
AKEA Design Proj. No. AD160-18
Design, Inc.
ARCHITECT / ENGINEER OF RECORDCONSULTANT
FINAL BID DOCUMENTS
87OF
TYPICAL BOLLARD DETAIL
TYPICAL TEMPORARY
CONSTRUCTION FENCE DETAIL
GENERATOR/
STORAGE TANK
PROTECTION
TYPICAL OF 9
SEE C301
CIVIL DETAILS
NEW ASPHALT PAVEMENT MEETS
EXISTING ASPHALT PAVEMENT
ROAD SAWCUT AND REPAIR LOCATION
AS NEEDED FOR SITE RESTORATION
NOTE:
THIS DETAIL AS SHOWN, ONLY IF UTILITIES OR CONDUIT ARE INSTALLED OR MOVED.
DUCTBANK INSTALLATION SHALL ADDITIONALLY FOLLOW REQUIREMENTS FOR DUCTBANK
CONSTRUCTION AS WELL AS DETAIL (THIS SHEET) FOR PAVEMENT, CURB REPAIR, AND
SIDEWALK REPLACEMENT.
MDT MDT
FOR REPAIR TO EXISITNG
SITE SIDEWALKS
TYPICAL OPEN UTILITY TRENCH
PIPE LAYING DETAIL
C400
PEDESTRIAN SIDEWALK REPAIR AND
DOOR LANDINGS
CURB AND GUTTER
FOR DUCTBANK INSTALLATION
ROADWAY WIDTH 10-FEET
STATE OF
P R
O
FESS IO NA L ENGIN
E E
R
M
IC
HA EL D. T OOT LENo. 67818 L I C E N S E
F L O R I D A
Date: 2022.04.27 15:44:27 -04'00'
MATERIAL LEGEND ABBREVATIONS
& AND JAN. JANITOR
@ AT JT. JOINT
CENTER LINE
DIAMETER OR ROUND K.D. KNOCKED DOWN
# NUMBER kg KILOGRAM
KIT. KITCHEN
A.F.F. ABOVE FINISHED FLOOR K.P. KICK PLATE
A.C.T. ACOUSTIC CEILING TILE
ADJST. ADJUSTABLE LAM. LAMINATED
ADJ. ADJACENT LAV. LAVATORY
AGGR. AGGREGATE LG. LONG
A.H.U. AIR HANDLER UNIT LT. LIGHT
ALT. ALTERNATE
ALUM. ALUMINUM m. METER
ANGLE mm. MILIMETER
A.D. AREA DRAIN MAX. MAXIMUM
A.P. ACCESS PANEL MECH. MECHANICAL
MET./MTL. METAL
BM BEAM MFR. MANUFACTURER
BITUM. BITUMINOUS MH MANHOLE
BLDK. BLOCKING MIN. MINIMUM
BD. BOARD MIR. MIRROR
BOT. BOTTOM MISC. MISCELLANEOUS
BLDG. BUILDING M.O. MASONRY OPENING
°C DEGREES CELSIUS N NEWTON
CAB. CABINET N. NORTH
CPT. CARPET N.G.V.D. NATIONAL GEODETIC
C.B. CATCH BASIN VERTICAL DATUM
CEIL./CLG. CEILING N.I.C. NOT IN CONTRACT
CTR. CENTER NO. / # NUMBER
C.T. CERAMIC TILE N.T.S. NOT TO SCALE
CL. CLEAR
CLOS. CLOSET O.A. OVERALL
COL. COLUMN O.C. ON CENTER
CONC. CONCRETE O.D. OUTSIDE DIAMETER
CONC. BLK. CONCRETE BLOCK O.D. OVERFLOW DRAIN
C.M.U./CMU CONCRETE MASONRY UNIT OFF OFFICE
CONST. JT. CONSTRUCTION JOINT O'HD. DR. OVERHEAD DOOR
C.J. CONTROL JOINT OPG. OPENING
CORR. CORRIDOR OPP. OPPOSITE
C.S. COUNTER SINK O.S. OVERHEAD SCUPPER
DET. DETAIL P PASCAL
DIA. DIAMETER PL. PLATE
DIM. DIMENSION PLYWD. PLYWOOD
DIST. DISTANCE P. LAM. PLASTIC LAMINATE
DR. DOOR PR. PAIR
DBL. DOUBLE
DN. DOWN QTY. QUANTITY
D.S. DOWNSPOUT Q.T. QUARRY TILE
D. DRAIN
DWG. DRAWING R. RADIUS
D.F. DRINKING FOUNTAIN R. RISER
R.D. ROOF DRAIN
E.A. EACH REINF. REINFORCEMENT
E.W. EACH WAY REQ'D REQUIRED
E. EAST RM. ROOM
ELEC. ELECTRICAL
E.W.C. ELECTRIC WATER COOLER S. SOUTH
EL. ELEVATION S.C. SOLID CORE
ELEV. ELEVATOR SECT. SELECTION
EQ. EQUAL SHT. SHEET
EQUIP. EQUIPMENT SHWR. SHOWER
E.F. EXHAUST FAN SIM. SIMILAR
EXIST. EXISTING SPEC. SPECIFICATIONS
EXP. JT. / E.J. EXPANSION JOINT SQ. SQUARE
EXP. EXPOSED SQ. FT. SQUARE FEET
EXT. EXTERIOR S.S. STAINLESS STEEL
EXR. EXISTING TO REMAIN STL. STEEL
STOR. STORAGE
F.T. /' FEET STRUCT. STRUCTURAL
F.A. FIRE ALARM SUSP. SUSPENDED
F.D. FLOOR DRAIN SYM. SYMMETRICAL
FDN. FOUNDATION
F.E.C. FIRE EXTINGUISHER CABINET TEL. TELEPHONE
F.E. FIRE EXTINGUISHER TEMP. TEMPERED
FIN FINISH THR. THRESHOLD
F.H.C. FIRE HOSE CABINET T.O.M. TOP OF MASONRY
FIXT. FIXTURE T.O.S. TOP OF STEEL
FLASH. FLASHING TR. TREAD
FL. FLOOR TYP. TYPICAL
FLOUR. FLUORESCENT
FR. FRAME U. URINAL
FTG. FOOTING U.L. UNDERWRITERS LABORATORIES
FURR. FURRING U.N.O. UNLESS OTHERWISE NOTED
GA. GAUGE V. VENT
GALV. GLAVANIZED V.C.T. VINYL COMPOSITE TILE
GL. GLASS VERT. VERTICAL
G.B. GRAB BAR VEST. VESTIBULE
GYP. GYPSUM V.W.C. VINYL WALL COVERING
GWB/GYP. BD. GYPSUM BOARD
W. WEST
H. / HDW. HARDWARE w/ WITH
H.B. HOSE BIBB W.C. WATER CLOSET
H.C. HOLLOW CORE WO. WOOD
H.M. HOLLOW METAL WDW. WINDOW
HORIZ. HORIZONTAL W.G. WATER GUARD
HT. HEIGHT W.H. WATER HEATER
HVAC HEATING VENTILATION AND w/o WITHOUT
AIR CONDITIONING WP. WATER PROOF
W.R. WATER RESISTANT
I.D. INSIDE DIAMETER
INSUL. INSULATION
INT. INTERIOR
GENERAL NOTESDRAFTING SYMBOLS
1. ALL WORK SHALL CONFORM TO ALL APPLICABLE CODES, STANDARDS AND
GOVERNING AUTHORITIES.
2. THESE DRAWINGS ARE ISSUED IN CONJUNCTION WITH THE PROJECT MANUAL
OF THE DAME DATE, TITLE, AND PROJECT NUMBER AND TOGETHER ARE
REFERRED TO AS "CONTRACT DOCUMENTS."
3. REFER TO ARCHITECTURAL, STRUCTURAL, MECHANICAL, PLUMBING, FIRE
PROTECTION, AND ELECTRICAL DRAWINGS FOR COORDINATION OF WORK.
4. NOTES APPEAR ON A NUMBER OF DRAWINGS FOR DIFFERENT SYSTEMS AND
MATERIALS. REFERENCE ALL ISSUED CONTRACT DOCUMENTS TO APPLY
APPLICABLE NOTES, SYMBOLS AND ABBREVIATION TO BUILDING COMPONENTS.
5. DO NOT SCALE THE DRAWINGS.
6. THE CONTRACTOR SHALL VISIT THE SITE AND BECOME KNOWLEDGE OF
CONDITIONS. THE CONTRACTOR SHALL INVESTIGATE, VERIFY, AND BE
RESPONSIBLE FOR ALL THE REQUIREMENTS OF THE PROJECT AND SHALL
NOTIFY THE OWNER AND ARCHITECT OF ANY EXISTING CONDITIONS REQUIRING
INFORMATION BEFORE PROCEEDING WITH ANY WORK.
7. THE CONTRACTOR SHALL PROTECT ALL EXISTING SITE ELEMENTS FROM
DAMAGE DUE TO ALTERATION AND CONSTRUCTION OPERATIONS AND THEY
SHALL REPAIR OR REPLACE ELEMENTS DAMAGED DURING THE PROJECT.
8. ANY UTILITY SHUT-OFFS AS REQUIRED BY THE CONTRACTOR FOR
COMPLETION OF THE WORK SUCH AS ELECTRICAL, GAS, WATER, SEWER,
STEAM, ETC., MUST BE SCHEDULED WITH THE OWNER, ARCHITECT AND UTILITY
COMPANY PRIOR TO COMMENCING WORK.
9. DETAILS SHOWN ARE INTENDED TO BE INDICATIVE OF THE PROFILE AND TYPE
OF DETAILING REQUIREMENTS FROM THE WORK, DETAILS NOT SHOWN ARE
SIMILAR IN CHARACTER TO THOSE SHOWN.
10. UNLESS NOTED OTHERWISE ALL FASTENERS AND FASTENING DEVICES ARE
TO BE CONCEALED IN ALL FINISHED SPACES.
11. ANY PIPING, DUCTS, CONDUITS, ETC. THAT PENETRATE FIRE RATED FLOOR
SLABS AND WALLS SHALL BE INSTALLED IN A MANNER THAT WILL PRESERVE
THE FIRE INTEGRITY OF THE FLOOR OR WALL. FIRE STOP RATINGS SHALL
MATCH RATINGS OF FLOORS OR WALLS WHERE PENETRATIONS OCCUR.
PROVIDE FIRE DAMPERS IN DUCTS PENETRATING FIRE-RATED WALLS AND
FLOORS TO MEET APPLICABLE BUILDING CODES.
12. ALL JOINTS OF ANY ELEMENT OF CONSTRUCTION WHICH ARE REQUIRED TO
HAVE A FIRE RESISTANCE RATING SHALL BE INSTALLED PER THE
MANUFACTURER'S PUBLISHED TESTED ASSEMBLIES, SHALL BE TIGHT AND
SHALL PREVENT THE PASSAGE OF SMOKE AND FLAME.
13. WHERE THE FIRE RATINGS OF WALLS ARE NOTED ON THE DRAWINGS, THE
FIRE RATING SHALL APPLY TO THE ENTIRE PERIMETER ENCLOSURE OF THE
ROOM OR SPACE FOR THE FULL LENGTH AND HEIGHT OF AREAS BEING
SEPARATED. EXTENDING TO THE UNDERSIDE OF THE FLOOR OR ROOF DECK.
14. PROVIDE FIRE STOPS TO SEPARATE WALL CAVITIES FROM HORIZONTAL
PLENUM AREAS AND BETWEEN FLOORS TO CLOSE OPENINGS. FIRE RATING OF
STOPS SHALL MATCH THE FIRE RATING OF VERTICAL SEPARATION OR FLOOR
CONSTRUCTION, WHICHEVER IS GREATER.
15. CONSTRUCTION AROUND CABINETS, PANELS AND BOXES RECESSED IN FIRE-
RATED FLOOR, WALL AND CEILING ASSEMBLIES SHALL MAINTAIN THE FIRE-
RATING NOTED IN THE DRAWINGS.
16. OPENINGS IN WALL , CEILING, FLOOR AND ROOF ASSEMBLIES SHALL BE
SEALED WITH PENETRATION SEALANT SYSTEM THAT MEET OR EXCEED THE
REQUIRED FIRE RATINGS.
17. ALL DISSIMILAR MATERIALS SHALL BE EFFECTIVELY ISOLATED FROM EACH
OTHER BY GASKETS OR COATINGS OR BOTH TO AVOID GALVANIC CORROSION
ACTION.
18. PATCH FIREPROOFING TO MATCH EXISTING.
19. PROVIDE PRESSURE TREATED WOOD WHERE WOOD IS CONTACT WITH
CONCRETE, EARTH, OR EXPOSED TO THE WEATHER, UNLESS NOTED
OTHERWISE.
20. SEE MECHANICAL, PLUMBING, FIRE PROTECTION, AND ELECTRICAL
DRAWINGS TO DETERMINE QUANTITIES OF DIFFUSERS, GRILLS, LIGHT
FIXTURES, SPRINKLER HEADS, ETC.
21. THE LOCATION OF CEILING MOUNTED DIFFUSERS, GRILLS, SPRINKLERS,
HEADS, FIXTURES, ETC. NOT SHOWN ON THE ARCHITECTURAL REFLECTED
CEILING PLAN MUST BE VERIFIED WITH THE DESIGN PROFESSIONAL, PRIOR TO
INSTALLATION.
22. PIPE AND COLUMN FURRING SHALL BE HELD AS CLOSE TO THE PIPING AND/OR
COLUMNS AS POSSIBLE, UNLESS NOTED OTHERWISE.
23. THE EXTENT OF THE WORK SHOWN ON THE PLANS AND DETAILS REFLECTS
THE BEST JUDGMENT OF THE ARCHITECT/ENGINEER, THE CONTRACTOR SHALL
FAMILIARIZE HIMSELF WITH THE EXISTING CONDITIONS AND ADVISE THE
ARCHITECT, IN WRITING, OF ANY SITUATION THAT WOULD NOT ALLOW HIM TO
PROCEED ON THE BASIS OF THESE DOCUMENTS.
24. THE ARCHITECT/ENGINEER'S SELECTION OF MATERIALS AND DETAILS DOES
NOT RELIEVE THE CONTRACTOR FROM VERIFYING WITH THE MATERIAL SUPPLIERS
THAT THE PROPOSED MATERIALS ARE CORRECT AND PROPER FOR THE INTENDED
APPLICATION AND USE.
25. CONCRETE FILLS ABOVE STRUCTURAL, SLABS SHALL BE REINFORCED. REFER
TO STRUCTURAL DRAWINGS FOR ADDITIONAL REQUIREMENTS.
26. UNLESS NOTED OTHERWISE, WHERE AN ARCHITECTURAL FINISHED FLOOR IS
TO BE PROVIDED (REQUIRED A DEPRESSED STRUCTURAL SLAB), THE FLOOR
ELEVATIONS ARE TO TOP THE FINISHED FLOOR. WHERE AN ARCHITECTURAL
FINISHED FLOOR IS INTENDED FOR SURFACE APPLICATION THE FLOOR
ELEVATIONS ARE TO TOP THE STRUCTURAL SLAB. REFER TO STRUCTURAL
DRAWINGS FOR LOCATION OF DEPRESSED SLABS.
27. UNLESS NOTED OTHERWISE, CONCRETE PAD WITH REINFORCING SHALL BE
INSTALLED UNDER ALL FLOOR MOUNTED MECHANICAL AND ELECTRICAL
EQUIPMENT. REFER TO MECHANICAL, ELECTRICAL, PLUMBING AND FIRE
PROTECTION DRAWINGS FOR THE EXTEND OF EQUIPMENT PADS. THE
CONTRACTOR SHALL COORDINATE THE SIZE, THICKNESS AND LOCATION OF THE
CONCRETE PADS WITH THE EQUIPMENT INSTALLER.
28. AT THOSE PLACES WHERE MATERIALS ARE APPLIED TO, OR ARE IN DIRECT
CONTACT WITH WORK INSTALLED BY ANOTHER SUBCONTRACTOR,
COMMENCEMENT OF WORK IMPLIES THE ACCEPTANCE OF THE SUBSTRATE AND
EXISTING CONDITIONS AS SUITABLE FOR THE APPLICATION INTENDED.
29. ALL WORK SHALL BE EXECUTED IN A WORKMANLIKE MANNER. CONSTRUCTION
OF NEW HORIZONTAL SURFACES SHALL BE LEVEL AND FLAT AND NEW VERTICAL
SURFACES SHALL BE CONSTRUCTED TO BE PLUMB, UNLESS OTHERWISE NOTED.
30. WHERE NOT INDICATED, PROVIDE BLOCKING IN WALLS, SOFFITS, AND CEILING
RECEIVING SIGNAGE, COAT HOOKS, LOCKERS, MARKER BOARDS, AND OTHER
MOUNTED ITEMS ACCORDING TO THE MANUFACTURER'S RECOMMENDATIONS.
31. CONTINUOUS PERIMETER FIRE SAFING BETWEEN FLOOR SHALL BE PROVIDED
AND COORDINATED WITH THE EXTERIOR WALL SYSTEMS AND ASSEMBLIES. THE
FIRE SAFINGS'S RATING SHALL MATCH OR EXCEED THAT OF THE FLOOR
CONSTRUCTION RATING.
32. CONTRACTOR TO CONFIRM AND FIELD VERIFY DIMENSIONS TO COORDINATE
WITH OWNER PROVIDED EQUIPMENT AND FURNISHINGS.
33. SUBSTITUTIONS OF MATERIALS MAY OCCUR IN ACCORDANCE WITH THE
CONTRACT DOCUMENTS, AND ONLY IF AUTHORIZED BY THE ARCHITECT.
34. CONTRACTOR SHALL PERFORM FIELD VERIFICATION OF ALL THE EXISTING
CONDITION THE SITE AND SHALL VERIFY THE LOCATION OF ALL EXISTING UTILITIES
AND SHALL COMPARE THE INFORMATION TO THE CONTRACTOR DOCUMENTS
PRIOR TO THE COMMENCEMENT OF ALL WORK. THE CONTRACTOR SHALL
IMMEDIATELY NOTIFY THE ARCHITECT IN WRITING OF ANY DISCREPANCIES.
35. ALL CONTRACTOR PROVIDED MATERIALS SHALL BE NEW AND DELIVERS AND
INSTALLED IN GOOD CONDITION AND WITHOUT ANY DEFECTS.
36. ANY WORK NOT CONFORMING TO THESE SPECIFICATIONS WILL BE REJECTED.
THE ARCHITECT OR THE OWNER MAY REJECT THE WORK AND REJECTED WORK
WILL BE REMOVED AND REPLACED AT NO ADDITIONAL COST TO THE OWNER.
37. ALL DIMENSIONS TO FINISH FACE OF SURFACE CENTERLINE OF COLUMN, OR TO
CENTERLINE OR FACE OF STUD UNLESS NOTED OTHERWISE.
A-5
A-8 1
A-5
A-5
A-5
0'-0"
ROOM
EXTERIOR ELEVATION SYMBOL
ELEVATION IDENTIFICATION
DRAWING WHERE ELEVATION IS SHOWN
INTERIOR ELEVATION SYMBOL
ELEVATION IDENTIFICATION
DRAWING WHERE ELEVATION IS VIEWING
DRAWING WHERE ELEVATION IS SHOWN
BUILDING SECTION SYMBOL
SECTION IDENTIFICATION
DRAWING WHERE SECTION IS VIEWING
DRAWING WHERE SECTION IS SHOWN
WALL SECTION SYMBOL
SECTION IDENTIFICATION
DRAWING WHERE SECTION IS VIEWING
DRAWING WHERE SECTION IS SHOWN
DETAIL SYMBOL
DETAIL IDENTIFICATION
DRAWING WHERE DETAIL IS SHOWN
NEW HEIGHT ELEVATION SYMBOL
ELEVATION IDENTIFICATION
LOCATION OF ELEVATION
EXISTING HEIGHT ELEVATION SYMBOL
ELEVATION IDENTIFICATION
LOCATION OF ELEVATION
ROOM IDENTIFICATION
ROOM NAME
ROOM NUMBER
WINDOW/LOUVER IDENTIFICATION
WINDOW IDENTIFICATION
STOREFRONT IDENTIFICATION
STOREFRONT IDENTIFICATION
DOOR IDENTIFICATION
DOOR IDENTIFICATION
CONCRETE: CAST-IN-PLACE/PRECAST
MORTAR
COMPACTED FILL
UNDISTURBED FILL
EARTHWORKS: GRAVEL
ELEVATION: INDICATION: GLASS
ACOUSTIC TILE
FINISHES: CARPETS & PADS
GYPSUM/WALL BOARD
RESILIENT FLOORING/
PLASTIC LAMINATE
PLASTIC
GLASS
GLASS BLOCK
STRUCTURAL GLASS
GYPSUM BOARD
BATT INSULATION
RIGID INSUALTION
BRICK
PLAN SECTION
CMU
GLAZED BRICK
STRUCTURAL: FACING TILE
ALUMINUM
BRASS/BRONZE
STEEL
GRANITE
RUBBLE
STUCCO ON LATH
WOOD: FINISH & TRIM
PLYWOOD/SM. SCALE
2 X WOOD BLOCKING
EXISTING CONST. TO REMAIN
EXISTING CONST. TO BE
REMOVED (AS NOTED)
OWNER FURNISHED
EQUIPMENT/FURNATURE (AS NOTED)
HIDDEN ITEMS (AS NOTED)
3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124 Fax: (352) 553-4437
COA: FL #29758
AKEA Design Proj. No. AD160-18
Design, Inc.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT / ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
OF
FL. REG. NO.ARCHITECT-OF-RECORD
FINAL BID DOCUMENTS
APPROVED FOR CONSTRUCTION
Revisions: Date:
FINAL BID DOCUMENTS
THIS DOCUMENT CONTAINS A DIGITAL SIGNATURE AND
SEAL BY THE INDIVIDUAL NAMED AT RIGHT. PRINTED
COPIES OF THIS DOCUMENT ARE NOT CONSIDERED
SIGNED AND SEALED, AND THE DIGITAL SIGNATURE
MUST BE VERIFIED ON ANY ELECTRONIC COPIES.
4/
/2
3:
:4
PM
GENERAL INFORMATION EXPAND ELECTRICAL DISTRIBUTION
LAKE CITY, FLORIDA
573A4-18-601
JF RA
JENNIFER FONG AR97191
AG001
APRIL 28, 2022 13
Digitally signed by Jennifer R Fong Date: 2022.04.29 08:45:06-04'00'
BUILDING 37
BUILDING 93
BUILDING
SOUTH MARION STREET (U.S. 441)
BA
YA
A
VE
N U
E
DIVISION STREET
x x x x x x x x x x
F
F
F
AREA OF ARCHITECTURAL SCOPE
AREAS OF ARCHITECTURAL SCOPE
BUILDING
BUILDING
64ABC
BUILDING 86
BUILDING
BUILDING 74
A. ARCHITECTURAL SITE PLAN FOR REFERENCE ONLY.
SEE CIVIL AND ELECTRICAL FOR ADDITIONAL
INFORMATION
3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124 Fax: (352) 553-4437
COA: FL #29758
AKEA Design Proj. No. AD160-18
Design, Inc.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT / ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
OF
FL. REG. NO.ARCHITECT-OF-RECORD
FINAL BID DOCUMENTS
APPROVED FOR CONSTRUCTION
Revisions: Date:
FINAL BID DOCUMENTS
THIS DOCUMENT CONTAINS A DIGITAL SIGNATURE AND
SEAL BY THE INDIVIDUAL NAMED AT RIGHT. PRINTED
COPIES OF THIS DOCUMENT ARE NOT CONSIDERED
SIGNED AND SEALED, AND THE DIGITAL SIGNATURE
MUST BE VERIFIED ON ANY ELECTRONIC COPIES.
4/
/2
3:
:4
PM
ARCHITECTURAL SITE PLAN EXPAND ELECTRICAL DISTRIBUTION
LAKE CITY, FLORIDA
573A4-18-601
JF RA
JENNIFER FONG AR97191
AS101
APRIL 28, 2022 14
N
SITE PLAN NOTES
LEGEND
1" = 50'-0"1 ARCHITECTURE SITE PLAN
Date: 2022.04.29 08:47:01-04'00'
NOTE:
CONTRACTOR SHALL REMOVE CEILING IN 40’
INCREMENTS TO FACILITATE THE INSTALLATION OF
THE CONDUIT FROM THE EMERGENCY EQUIPMENT
ROOM TO THE EES ROOM. REPLACE TILE WITH NEW
AT THE COMPLETION OF EACH INCREMENT.
PATH OF ELECTRICAL CONDUIT
BUILDING 84 EMERGENCY
ELEC ROOM
A187
SWITCHGEAR
A188
2' - 2 1/2"
2' - 2 1/2"
SEE NOTE FOR ELEC
CONDUIT PATH
BUILDING 86
3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124 Fax: (352) 553-4437
COA: FL #29758
AKEA Design Proj. No. AD160-18
Design, Inc.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT / ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
OF
FL. REG. NO.ARCHITECT-OF-RECORD
FINAL BID DOCUMENTS
APPROVED FOR CONSTRUCTION
Revisions: Date:
FINAL BID DOCUMENTS
THIS DOCUMENT CONTAINS A DIGITAL SIGNATURE AND
SEAL BY THE INDIVIDUAL NAMED AT RIGHT. PRINTED
COPIES OF THIS DOCUMENT ARE NOT CONSIDERED
SIGNED AND SEALED, AND THE DIGITAL SIGNATURE
MUST BE VERIFIED ON ANY ELECTRONIC COPIES.
4/
/2
3:
:5
PM
1ST FLOOR RCP PLAN/
ELEC CONDUIT PATH LAYOUT EXPAND ELECTRICAL DISTRIBUTION
LAKE CITY, FLORIDA
573A4-18-601
JF RA
JENNIFER FONG AR97191
AS102
APRIL 28, 2022 15
GENERAL NOTES
KEY LEGEND
N
SCALE: 1" = 20'-0"1 BASEMENT - ELEC CONDUIT PATH
Date: 2022.04.29 09:01:12-04'00'
G R
ID
N :4 .3
G R
ID
E :2 .5
LA
T
IT
U D E '5 .8
LO
N G
IT
U D E '0 .4
S
IT
E
C O N T R O L P O
IN
T
S E T
N A
IL
(N O
ID
E N T
IF
IC
A T
IO
N
LA
T
IT
U D E '5 .8 N N A D '8
LO
N G
IT
U D E '0 .4 W N A D '8
E
LE
V A T
IO
N
.0 N A V D '8
W H E E L S T O P
(T Y P
IC
A L)
D
EW
A
LK
C O V E R E D
A R E A
PLANTER
F E N C E D
C O M P O U N D
AE302
AE302
D4
D4
D1
D14 D16D15
D6
D20
D17D17
D17
D17
D3D3
D5D5
D11D11
D5D5D5
D16TRANSFORMER
ROOM
GENERATOR
ROOM
D23
AE302
AE302
D9
D9
D9
D10D10
D9
DEMOLITION PLAN NOTES
1. SCREENED LINES AND PATTERNS INDICATE
EXISTING ELEMENTS TO REMAIN. HEAVY/DASHED
LINES INDICATE EXISTING ELEMENTS TO BE
REMOVED.
2. MAINTAIN CONSTRUCTION AREA UNDER NEGATIVE
PRESSURE RELATIVE TO ADJACENT OCCUPIED
AREAS. SEE SPECIFICATIONS FOR ADDITIONAL
INFECTION CONTROL REQUIREMENTS.
3. REMOVE EXISTING DEVICES AS SHOWN ON
ELECTRICAL AND MECHANICAL DRAWINGS. REPAIR
AND FINISH WALLS WHERE DEVICES ARE REMOVED.
4. REPLACE, REPAIR, AND EXTEND EXISTING
ELEMENTS (INCLUDING WALLS AND WALL FINISHES,
FLOORS AND FLOOR FINISHES, AND CEILINGS AND
CEILING FINISHES) IN AREAS OF WORK TO PROVIDE
INCONSPICUOUS TRANSITION BETWEEN EXISTING
AND NEW ELEMENTS.
5. SEQUENCE WORK AND PROVIDE TEMPORARY
PROTECTIVE MEASURES TO PROTECT THE EXISTING
BUILDING MATERIALS AND INTERIOR FROM THE
ELEMENTS; INCLUDING TEMPERATURE, WIND, AND
PRECIPITATON.
6. AFTER THE EXPANSION AREA IS DRIED-IN,
CONSTRUCT SOFT CONSTRUCTION BARRIERS
SHOWN IN CIVIL DRAWINGS, FOLLOWED BY NEW
PERIMETER PARTITIONS AND DOORS (NOTED WITH
AN * BY THE PARTITION TYPE TAG ON THE FLOOR
PLANS) TO SERVE AS A CONSTRUCTION BARRIER
FOR THE REMAINDER OF THE CONSTRUCTION
DURATION. COMPLY WITH VA'S INFECTION CONTROL
PLAN. SEE SAFETY REQUIREMENTS SPECIFICATION
FOR ADDITIONAL MEASURES REQUIRED.
3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124 Fax: (352) 553-4437
COA: FL #29758
AKEA Design Proj. No. AD160-18
Design, Inc.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT / ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
OF
FL. REG. NO.ARCHITECT-OF-RECORD
FINAL BID DOCUMENTS
APPROVED FOR CONSTRUCTION
Revisions: Date:
FINAL BID DOCUMENTS
THIS DOCUMENT CONTAINS A DIGITAL SIGNATURE AND
SEAL BY THE INDIVIDUAL NAMED AT RIGHT. PRINTED
COPIES OF THIS DOCUMENT ARE NOT CONSIDERED
SIGNED AND SEALED, AND THE DIGITAL SIGNATURE
MUST BE VERIFIED ON ANY ELECTRONIC COPIES.
4/
/2
3:
:1
PM
BUILDING 84 DEMO GEN. & TRAN.
FLOOR & ROOF PLANS EXPAND ELECTRICAL DISTRIBUTION
LAKE CITY, FLORIDA
573A4-18-601
JF RA
JENNIFER FONG AR97191
AD100
APRIL 28, 2022 16
N 1/4" = 1'-0"1
BUILDING 84 DEMO TRAN. & ELEC.
ROOMS FLOOR PLAN
SHEET KEYNOTES
1/4" = 1'-0"2
BUILDING 84 DEMO TRAN. & ELEC.
ROOMS ROOF PLAN
D1 REMOVE DOOR, FRAMES AND HARDWARE, REFER
TO DOOR SCHEDULE.
D3 REMOVE EXISTING GENERATOR AND METAL BASE
FRAME.
D4 REMOVE LOUVER/WINDOW, GLAZING, FRAMING
AND INFILL OPENING, REFER TO INFILL OPENING
DETAILS.
D5 REMOVE FUEL TANK, PIPING, STEEL LADDER,
PLATFORM, METAL FENCE AND BOLLARDS. CAP
PIPING AS NECESSARY FOR NEW CONSTRUCTION.
D6 RELOCATE EXISTING HEAT PUMP UNIT TO THE
ROOF, REFER TO NEW LAYOUT FOR NEW
LOCATION FOR THE HEAT PUMP.
D9 REMOVE FLUE STACKS AND EXHAUST FANS,
BLOCK OFF VENTS PENETRATIONS, EXISTING
ROOF CURBS TO REMAIN.
D10 REPLACE ENTIRE ROOFING SYSTEM, NEW ROOF TO
MATCH EXISTING ROOFING ASSEMBLY, ROOF
DRAINS TO REMAIN.
D11 REMOVE PARKING SPACES, CURBS AND
MODIFYING SITE WORK, REFER TO CIVIL
DRAWINGS.
D14 REMOVE AND RELOCATE FIRE EXTINGUSHIER
CABINET. REFER TO ARCHITECTURAL FLOOR
PLANS.
D15 DEMOLISH CONCRETE PLATFORM WITH STEPS AND
METAL HANDRAIL.
D16 EXISTING HVAC UNIT TO REMAIN, NO CHANGE.
D17 EXISTING CONCRETE PAD TO REMAIN.
D20 REMOVE EXISTING CONCRETE PAD.
D23 REMOVE EXISTING VCT AND CERAMIC TILES/CLEAN
THE FLOOR AND PAINT WITH CLEAR CONCRETE
SEALANT.
Date: 2022.04.29 09:02:44-04'00'
D18
D18
D18
D18
D17
D6
D19D18
D1
D1
D1 D8
D7
D4
D4
D4
TOILET STAFF
A127
LACTATION
ROOM
A130
WAITING ROOM
A125
CORRIDOR
C1-6
DENTAL CLINIC
A132
RECEPTION
A138
X-RAY
A141
OFFICE
A141A
OPERATORY #7
A145
OPERATORY #6
A147
OPERATORY #5
A149
BREAKROOM
A151A
ESCORT SERVICE
A131
W
U
X
D20
D16
TRANSFORMER
ROOM
D23
D19D19
D12D12
W
U
X
D24
D24
D24
D24
DEMOLITION PLAN NOTES
1. SCREENED LINES AND PATTERNS INDICATE
EXISTING ELEMENTS TO REMAIN. HEAVY/DASHED
LINES INDICATE EXISTING ELEMENTS TO BE
REMOVED.
2. MAINTAIN CONSTRUCTION AREA UNDER NEGATIVE
PRESSURE RELATIVE TO ADJACENT OCCUPIED
AREAS. SEE SPECIFICATIONS FOR ADDITIONAL
INFECTION CONTROL REQUIREMENTS.
3. REMOVE EXISTING DEVICES AS SHOWN ON
ELECTRICAL AND MECHANICAL DRAWINGS. REPAIR
AND FINISH WALLS WHERE DEVICES ARE REMOVED.
4. REPLACE, REPAIR, AND EXTEND EXISTING
ELEMENTS (INCLUDING WALLS AND WALL FINISHES,
FLOORS AND FLOOR FINISHES, AND CEILINGS AND
CEILING FINISHES) IN AREAS OF WORK TO PROVIDE
INCONSPICUOUS TRANSITION BETWEEN EXISTING
AND NEW ELEMENTS.
5. SEQUENCE WORK AND PROVIDE TEMPORARY
PROTECTIVE MEASURES TO PROTECT THE EXISTING
BUILDING MATERIALS AND INTERIOR FROM THE
ELEMENTS; INCLUDING TEMPERATURE, WIND, AND
PRECIPITATON.
6. AFTER THE EXPANSION AREA IS DRIED-IN,
CONSTRUCT SOFT CONSTRUCTION BARRIERS
SHOWN IN CIVIL DRAWINGS, FOLLOWED BY NEW
PERIMETER PARTITIONS AND DOORS (NOTED WITH
AN * BY THE PARTITION TYPE TAG ON THE FLOOR
PLANS) TO SERVE AS A CONSTRUCTION BARRIER
FOR THE REMAINDER OF THE CONSTRUCTION
DURATION. COMPLY WITH VA'S INFECTION CONTROL
PLAN. SEE SAFETY REQUIREMENTS SPECIFICATION
FOR ADDITIONAL MEASURES REQUIRED.
PMR STORAGE
AB10
PATIENT
CLOTHING ROOM
AB11
D2D2
W
U
3733 39
D12
W
U
3733 39
D12
3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124 Fax: (352) 553-4437
COA: FL #29758
AKEA Design Proj. No. AD160-18
Design, Inc.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT / ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
OF
FL. REG. NO.ARCHITECT-OF-RECORD
FINAL BID DOCUMENTS
APPROVED FOR CONSTRUCTION
Revisions: Date:
FINAL BID DOCUMENTS
THIS DOCUMENT CONTAINS A DIGITAL SIGNATURE AND
SEAL BY THE INDIVIDUAL NAMED AT RIGHT. PRINTED
COPIES OF THIS DOCUMENT ARE NOT CONSIDERED
SIGNED AND SEALED, AND THE DIGITAL SIGNATURE
MUST BE VERIFIED ON ANY ELECTRONIC COPIES.
4/
/2
3:
:2
PM
BLDGS. 64 & 86 DEMO
BASEMENT, 1ST FLOOR PLAN &
RCP
EXPAND ELECTRICAL DISTRIBUTION
LAKE CITY, FLORIDA
573A4-18-601
JF RA
JENNIFER FONG AR97191
AD101
APRIL 28, 2022 17
N
SHEET KEYNOTES
1/4" = 1'-0"1
BUILDINGS 86 & 64
DEMO 1ST FLOOR PLAN (+186'-2")
1/4" = 1'-0"2
BUILDING 64 & 86 DEMO 1ST FLOOR
REFLECTED CEILING PLAN
D1 REMOVE DOOR, FRAMES AND HARDWARE, REFER
TO DOOR SCHEDULE.
D2 REMOVE WALL CONSTRUCTION.
D4 REMOVE LOUVER/WINDOW, GLAZING, FRAMING
AND INFILL OPENING, REFER TO INFILL OPENING
DETAILS.
D6 RELOCATE EXISTING HEAT PUMP UNIT TO THE
ROOF, REFER TO NEW LAYOUT FOR NEW
LOCATION FOR THE HEAT PUMP.
D7 REMOVE CONCRETE AIRWELL AND METAL GRATE,
BACKFILL PER STRUCTURAL.
D8 EXISTING LOUVER WILL BE FULLY RELOCATED AT
THE NEW FRONT WALL, REFER TO NEW LAYOUT
SHEET #AE201.
D12 REMOVE CEILING GRID, CEILNIG TILES, SOFFIT,
LIGHT FIXTURES, HVAC DIFFUSERS, REFER TO MEP
DRAWINGS.
D16 EXISTING HVAC UNIT TO REMAIN, NO CHANGE.
D17 EXISTING CONCRETE PAD TO REMAIN.
D18 EXISTING STRUCTURAL COL. TO REMAIN, NO
CHANGE.
D19 EXISTING CEILING, ACCESS PANELS, LIGHT
FIXTURES AND MEP TO REMAIN.
D20 REMOVE EXISTING CONCRETE PAD.
D23 REMOVE EXISTING VCT AND CERAMIC TILES/CLEAN
THE FLOOR AND PAINT WITH CLEAR CONCRETE
SEALANT.
D24 RELOCATE EXISTING CEILING LIGHT FIXTURES,
REFER TO NEW CEILING LAYOUT.
1/4" = 1'-0"3
BUILDING 64 DEMO
BASEMENT FLOOR PLAN
1/4" = 1'-0"5
BUILDING 64 DEMO BASEMENT FLOOR
REFLECTED CEILING PLAN
Date: 2022.04.29 09:00:24-04'00'
FWC FWC
N
N
N
FWC FWCFWC FWC
D10D10
OFFICE
A236
CLEAN UTILITY
A256
SEMI-PRIVATE
ROOM
A258
BATH
A258A
BATH
A261A
PRIVATE ROOM
A261
OFFICE
PHARMACY
A237
W
U
X
D1
D2
D21D21
3' - 9"7' - 6"
INFUSION CLINIC
A239
D16
D23
DEMOLITION PLAN NOTES
1. SCREENED LINES AND PATTERNS INDICATE
EXISTING ELEMENTS TO REMAIN. HEAVY/DASHED
LINES INDICATE EXISTING ELEMENTS TO BE
REMOVED.
2. MAINTAIN CONSTRUCTION AREA UNDER NEGATIVE
PRESSURE RELATIVE TO ADJACENT OCCUPIED
AREAS. SEE SPECIFICATIONS FOR ADDITIONAL
INFECTION CONTROL REQUIREMENTS.
3. REMOVE EXISTING DEVICES AS SHOWN ON
ELECTRICAL AND MECHANICAL DRAWINGS. REPAIR
AND FINISH WALLS WHERE DEVICES ARE REMOVED.
4. REPLACE, REPAIR, AND EXTEND EXISTING
ELEMENTS (INCLUDING WALLS AND WALL FINISHES,
FLOORS AND FLOOR FINISHES, AND CEILINGS AND
CEILING FINISHES) IN AREAS OF WORK TO PROVIDE
INCONSPICUOUS TRANSITION BETWEEN EXISTING
AND NEW ELEMENTS.
5. SEQUENCE WORK AND PROVIDE TEMPORARY
PROTECTIVE MEASURES TO PROTECT THE EXISTING
BUILDING MATERIALS AND INTERIOR FROM THE
ELEMENTS; INCLUDING TEMPERATURE, WIND, AND
PRECIPITATON.
6. AFTER THE EXPANSION AREA IS DRIED-IN,
CONSTRUCT SOFT CONSTRUCTION BARRIERS
SHOWN IN CIVIL DRAWINGS, FOLLOWED BY NEW
PERIMETER PARTITIONS AND DOORS (NOTED WITH
AN * BY THE PARTITION TYPE TAG ON THE FLOOR
PLANS) TO SERVE AS A CONSTRUCTION BARRIER
FOR THE REMAINDER OF THE CONSTRUCTION
DURATION. COMPLY WITH VA'S INFECTION CONTROL
PLAN. SEE SAFETY REQUIREMENTS SPECIFICATION
FOR ADDITIONAL MEASURES REQUIRED.
D2 D13D1 D13
OFFICE - SOCIAL
WORKER
A333
CORRIDOR
C3-5
CLEAN UTILITY
A352
EQUIPMENT
ALCOVE
A337
PRIVATE
HOSPICE CARE
A354
D1
D2
D2
D2
D2
SERENITY PLACE
FAMILY ROOM
A334
SEMI-PRIVATE
HOSPIC CARE
A336A
W
U
3733 39
4' - 9" 7' - 6"
D16
D23
D23
D1
D13
OFFICE
A423
H.A.C.
A427
SUPPLY ROOM
A442
BATH
A446A
PANTRY
A445
EXAM ROOM
A446
D2
OPHTHALMOLOGY/
SURGERY PRE-OP
A424B
POD SURGICAL
COORDINATOR
A426
NURSE
FACILITATOR
A426A
STAFF
UROLOGIST -
UROLOGY
A424
W
U
3733 39
4' - 0" 3' - 3"
D16
D23
D8
D12D12
W
U
D12D12
D12D12
W
U
3733 39
D12D12
W
U
3733 39
3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124 Fax: (352) 553-4437
COA: FL #29758
AKEA Design Proj. No. AD160-18
Design, Inc.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT / ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
OF
FL. REG. NO.ARCHITECT-OF-RECORD
FINAL BID DOCUMENTS
APPROVED FOR CONSTRUCTION
Revisions: Date:
FINAL BID DOCUMENTS
THIS DOCUMENT CONTAINS A DIGITAL SIGNATURE AND
SEAL BY THE INDIVIDUAL NAMED AT RIGHT. PRINTED
COPIES OF THIS DOCUMENT ARE NOT CONSIDERED
SIGNED AND SEALED, AND THE DIGITAL SIGNATURE
MUST BE VERIFIED ON ANY ELECTRONIC COPIES.
4/
/2
3:
:2
PM
BLDGS 64 & 86 DEMOLITION
2ND, 3RD & 4TH FLOORS PLAN EXPAND ELECTRICAL DISTRIBUTION
LAKE CITY, FLORIDA
573A4-18-601
JF RA
JENNIFER FONG AR97191
AD102
APRIL 28, 2022 18
SHEET KEYNOTES
N
1/4" = 1'-0"1 BLDG. 64 DEMO 2ND FLOOR
D1 REMOVE DOOR, FRAMES AND HARDWARE, REFER
TO DOOR SCHEDULE.
D2 REMOVE WALL CONSTRUCTION.
D8 EXISTING LOUVER WILL BE FULLY RELOCATED AT
THE NEW FRONT WALL, REFER TO NEW LAYOUT
SHEET #AE201.
D10 REPLACE ENTIRE ROOFING SYSTEM, NEW ROOF TO
MATCH EXISTING ROOFING ASSEMBLY, ROOF
DRAINS TO REMAIN.
D12 REMOVE CEILING GRID, CEILNIG TILES, SOFFIT,
LIGHT FIXTURES, HVAC DIFFUSERS, REFER TO MEP
DRAWINGS.
D13 REMOVE PLUMBING FIXTURES AND ACCESSORIES
CAP TO RECEIVE NEW FINISHES.
D16 EXISTING HVAC UNIT TO REMAIN, NO CHANGE.
D21 EXISTING EXHAUST FAN TO REMAIN, NO CHANGE.
D23 REMOVE EXISTING VCT AND CERAMIC TILES/CLEAN
THE FLOOR AND PAINT WITH CLEAR CONCRETE
SEALANT.
1/4" = 1'-0"2 BLDG. 64 DEMO 3RD FLOOR
1/4" = 1'-0"3 BLDG. 64 DEMO 4TH FLOOR
1/4" = 1'-0"5
BUILDING 64 DEMO 2ND FLOOR
REFLECTED CEILING PLAN
1/4" = 1'-0"6
BUILDING 64 DEMO 3RD FLOOR
REFLECTED CEILING PLAN
1/4" = 1'-0"7
BUILDING 64 DEMO 4TH FLOOR
REFLECTED CEILING PLAN
Date: 2022.04.29 09:02:09-04'00'
AE3013
AE301
AE302
30' - 0"
6'
8"
AE303
AE302
A6
SWITCHGEAR
A188
EMERGENCY
ELEC ROOM
A187
A2
A5
A7
ALIGN
ALIGN
A302
Sim
A302
Sim
A6A6A6A6A6
A6
6' - 4" 6' - 4" 6' - 4" 6' - 4" 6' - 4"
3'
0" 5'
0"
5'
0"
2'
6"
A15
4' - 0"
4'
6" 1'
0"
1'
0"
NEW CONC.
LANDING, STAIR &
METAL HANDRAIL
AE200
AE302
AE302
A5
A4A4
RELOCATED EXISTING
HEAT PUMP
EXISTING ROOF
SCUPPER TO REMAIN.
1. DIMENSIONS ARE TO: THE FACE OF FINISH OF
PARTITIONS, EXISTING ELEMENTS, EQUIPMENT,
MASONRY, OR CONCRETE; STRUCTURAL GRIDS;
AND CLEAR JAMB OPENING OF DOORS.
2. FIELD VERIFY ACTUAL CONDITIONS AND
DIMENSIONS TO EXISTING ELEMENTS. NOTIFY
ARCHITECT OF DISCREPANCIES AND
UNDOCUMENTED CONDITIONS THAT CONFLICT
WITH NEW WORK.
3. SEE A702 FOR TYPICAL FRAMING DETAILS
INCLUDING WALL PRIORITY AT PARTITION
INTERSECTIONS. SEE A302 FOR TYPICAL FRAMING
AT FIREPROOFED COLUMNS.
4. REFER TO MEP DRAWINGS FOR THE ELECTRICAL
AND MECHANICAL EQUIPMENT.
5. REFER TO STRUCTURAL DRAWINGS FOR THE
EXACT LOCATION OF COLUMNS, BEAMS AND
FRAMING SYSTEM.
LEGEND
FLOOR PLAN NOTES
DOOR OPENING 122
DOOR OPENING MARK
PARTITION TYPE IDENTIFICATION
SEE A701A3A
FEC
FIRE EXTINGUISHER
CABINET
ASTERISK INDICATES PARTITION TO
CONSTRUCT AT START OF
PROJECT - SEE DEMOLITION NOTES
ROOM NAMEROOM NAME
101 ROOM NUMBER
EXPANSION CONTROL JOINT CODES
EJ# - EXPANSION JOINT COVER
SEE DETAILS ON A501. NUMBERS ARE CODED TO JOINT
TYPE. FOR RATED JOINTS, PROVIDE CONTINUOUS
JOINT ASSEMBLY BETWEEN NEW AND EXISTING
CONSTRUCTION INCLUDING INSIDE AND OUTSIDE
CORNER TRANSITIONS AND JOINTS THROUGH
CONCEALED SPACES.
INDICATES AREA OF MINIMAL OR NO
CHANGES
BLOCKING IN GWB DRYWALL. ELEC ROOMS
GC. TO PROVIDE BLOCKING IN THE WALLS WHERE THE
ELECTRICAL PANELS WILL PLACED ON THE WALLS AS
REQUIRED.
SHEET KEYNOTES
1 HR FIRE RATED WALL
2 HR FIRE RATED WALL
INTERIOR ROOM SIGNS
NEW ROOM SIGNS TO MATCH EXISTING. GC TO FOLLOW VA
INSTRUCTIONS FOR INTERIOR ROOMSIGNS STANDARD.
BLDG84 FLR ELEV
174' - 8"
0'
7"
0'
7"0'
7"
2'
4' - 6"
1' - 0" 1' - 0"
CONC. LANDING
& STAIR
METAL
HANDRAIL
3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124 Fax: (352) 553-4437
COA: FL #29758
AKEA Design Proj. No. AD160-18
Design, Inc.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT / ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
OF
FL. REG. NO.ARCHITECT-OF-RECORD
FINAL BID DOCUMENTS
APPROVED FOR CONSTRUCTION
Revisions: Date:
FINAL BID DOCUMENTS
THIS DOCUMENT CONTAINS A DIGITAL SIGNATURE AND
SEAL BY THE INDIVIDUAL NAMED AT RIGHT. PRINTED
COPIES OF THIS DOCUMENT ARE NOT CONSIDERED
SIGNED AND SEALED, AND THE DIGITAL SIGNATURE
MUST BE VERIFIED ON ANY ELECTRONIC COPIES.
4/
/2
3:
:2
PM
BUILDING 84 PROPOSED TRAN. &
ELEC FLOOR & ROOF PLANS EXPAND ELECTRICAL DISTRIBUTION
LAKE CITY, FLORIDA
573A4-18-601
JF RA
JENNIFER FONG AR97191
AE200
APRIL 28, 2022 19
1/4" = 1'-0"1
BUILDING 84 PROP TRAN. & ELEC.
ROOMS FLOOR PLAN
N
A1 NEW FIRE RATED WALL CONSTRUCTION, REFER TO
WALL TYPES.
A2 NEW FIRE RATED DOOR, FRAMES AND HARDWARE,
REFER TO DOOR SCHEDULE.
A3 NEW SCUPPER, CONDUCTOR HEAD AND
DOWNSPOUT, REFER TO ROOFING DETAILS.
A4 NEW ROOF ASSEMBLY SYSTEM, REFER TO
ROOFING DETAILS.
A5 NEW HVAC EQUIPMENT, REFER TO HVAC
DRAWINGS.
A6 NEW STEEL BOLLARD.
A7 NEW CONCRETE PAD, REFER TO STRUCTURAL
DRAWINGS.
A12 NEW LIGHT FIXTURES, REFER TO ELECTRICAL
DRAWINGS.
A14 EXISTING RELOCATED LOUVER.
A15 INSTALL NEW FIRE EXTINGUISHER TYPE C.
1/4" = 1'-0"3 BUILDING 84 PROP ROOF PLAN
1/4" = 1'-0"4 LANDING & STAIR SECTION_BLDG 84
Date: 2022.04.29 08:46:09-04'00'
AE302
AE301 2
AE302
AE302
ELEC ROOM 1A
A186
AE301
A1
26' - 7 1/2"
ALIGN
ALIGN
B6M
A302
A302
Sim
ALIGN
A302
Sim
A302
Sim
A302
Sim
AE303
37.8
A302
Sim
A1
Z
Y
35.1
21' - 0"
Z.1
5'
6"
5'
4"
27' - 9"
189a
A2
A2
A1
A1
4"
X.5
8'
9"
1' - 1 5/8"9"
EES ROOM
A184
NEW
SUBSTATION
A185
6' - 0"
0'
6"
1/
2" 1'
1/ 2"
1' - 1 5/8" 26' - 7 3/8"
A302
Sim
A1
ELEC. CLOSET-1B
A189 DENTAL CLINIC
A132LACTATION
ROOM
A130
TOILET STAFF
A127
CORRIDOR
C1-7
RECEPTION
A138
X-RAY
A141
OFFICE
A141A
OPERATORY #7
A145
OPERATORY #6
A147
OPERATORY #5
A149
BREAKROOM
A151A
WAITING ROOM
A125
4' - 3 1/2" 7' - 0" 15' - 4"
28' - 10 1/2"
4' - 3 1/2" 7' - 0" 15' - 4"
8" 5' - 10" 8' - 9 3/4"
A14
CORRIDOR
C1-6
W
U
X
A5
A15
A15
A15
A501
Sim
A1
L1
A6K A6K
2' - 4"
1'
9"
A6K
3837.8
Z
Y
35.1
Z.1
X.5
A12
A12
A12
A12
A12
W
U
X
A12
A12
A12 A12
A12
ELEC. CLOSET-1B
A189
A12
A12
A12
A12
1. DIMENSIONS ARE TO: THE FACE OF FINISH OF
PARTITIONS, EXISTING ELEMENTS, EQUIPMENT,
MASONRY, OR CONCRETE; STRUCTURAL GRIDS;
AND CLEAR JAMB OPENING OF DOORS.
2. FIELD VERIFY ACTUAL CONDITIONS AND
DIMENSIONS TO EXISTING ELEMENTS. NOTIFY
ARCHITECT OF DISCREPANCIES AND
UNDOCUMENTED CONDITIONS THAT CONFLICT
WITH NEW WORK.
3. SEE A702 FOR TYPICAL FRAMING DETAILS
INCLUDING WALL PRIORITY AT PARTITION
INTERSECTIONS. SEE A302 FOR TYPICAL FRAMING
AT FIREPROOFED COLUMNS.
4. REFER TO MEP DRAWINGS FOR THE ELECTRICAL
AND MECHANICAL EQUIPMENT.
5. REFER TO STRUCTURAL DRAWINGS FOR THE
EXACT LOCATION OF COLUMNS, BEAMS AND
FRAMING SYSTEM.
LEGEND
FLOOR PLAN NOTES
DOOR OPENING 122
DOOR OPENING MARK
PARTITION TYPE IDENTIFICATION
SEE A701A3A
FEC
FIRE EXTINGUISHER
CABINET
ASTERISK INDICATES PARTITION TO
CONSTRUCT AT START OF
PROJECT - SEE DEMOLITION NOTES
ROOM NAMEROOM NAME
101 ROOM NUMBER
EXPANSION CONTROL JOINT CODES
EJ# - EXPANSION JOINT COVER
SEE DETAILS ON A501. NUMBERS ARE CODED TO JOINT
TYPE. FOR RATED JOINTS, PROVIDE CONTINUOUS
JOINT ASSEMBLY BETWEEN NEW AND EXISTING
CONSTRUCTION INCLUDING INSIDE AND OUTSIDE
CORNER TRANSITIONS AND JOINTS THROUGH
CONCEALED SPACES.
INDICATES AREA OF MINIMAL OR NO
CHANGES
BLOCKING IN GWB DRYWALL. ELEC ROOMS
GC. TO PROVIDE BLOCKING IN THE WALLS WHERE THE
ELECTRICAL PANELS WILL PLACED ON THE WALLS AS
REQUIRED.
SHEET KEYNOTES
1 HR FIRE RATED WALL
2 HR FIRE RATED WALL
INTERIOR ROOM SIGNS
NEW ROOM SIGNS TO MATCH EXISTING. GC TO FOLLOW VA
INSTRUCTIONS FOR INTERIOR ROOMSIGNS STANDARD.
PATIENT
CLOTHING ROOM
AB44
CLOTHING
STORAGE
AB11A
OFFICE
AB09A
CORRIDOR
A1
W
U
X
33 39
ELEC. CLOSET-B
AB10 A6K
A15
A703
Sim
A703
Sim
W
U
3733 39
ELEC CLOSET-B
AB10
3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124 Fax: (352) 553-4437
COA: FL #29758
AKEA Design Proj. No. AD160-18
Design, Inc.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT / ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
OF
FL. REG. NO.ARCHITECT-OF-RECORD
FINAL BID DOCUMENTS
APPROVED FOR CONSTRUCTION
Revisions: Date:
FINAL BID DOCUMENTS
THIS DOCUMENT CONTAINS A DIGITAL SIGNATURE AND
SEAL BY THE INDIVIDUAL NAMED AT RIGHT. PRINTED
COPIES OF THIS DOCUMENT ARE NOT CONSIDERED
SIGNED AND SEALED, AND THE DIGITAL SIGNATURE
MUST BE VERIFIED ON ANY ELECTRONIC COPIES.
4/
/2
3:
:2
PM
BLDGS. 64 & 86 PROP BASEMENT
FLOOR, 1ST FLOOR & RCP PLANS EXPAND ELECTRICAL DISTRIBUTION
LAKE CITY, FLORIDA
573A4-18-601
JF RA
JENNIFER FONG AR97191
AE201
APRIL 28, 2022 20
1/4" = 1'-0"1
BLDGS. 64 & 86 PROPOSED
1ST FLOOR PLANS
N 1/4" = 1'-0"3
BLDGS. 64 & 86 PROP 1ST FLOOR
REFLECTED CEILING PLAN
A1 NEW FIRE RATED WALL CONSTRUCTION, REFER TO
WALL TYPES.
A2 NEW FIRE RATED DOOR, FRAMES AND HARDWARE,
REFER TO DOOR SCHEDULE.
A3 NEW SCUPPER, CONDUCTOR HEAD AND
DOWNSPOUT, REFER TO ROOFING DETAILS.
A4 NEW ROOF ASSEMBLY SYSTEM, REFER TO
ROOFING DETAILS.
A5 NEW HVAC EQUIPMENT, REFER TO HVAC
DRAWINGS.
A6 NEW STEEL BOLLARD.
A7 NEW CONCRETE PAD, REFER TO STRUCTURAL
DRAWINGS.
A12 NEW LIGHT FIXTURES, REFER TO ELECTRICAL
DRAWINGS.
A14 EXISTING RELOCATED LOUVER.
A15 INSTALL NEW FIRE EXTINGUISHER TYPE C.
1/4" = 1'-0"4
BLDG. 86 PROPOSED
BASEMENT FLOOR PLAN
1/4" = 1'-0"5
BUILDING 64 PROP BASEMENT FLOOR
REFLECTED CEILING PLAN
Date: 2022.04.29 08:47:42-04'00'
ROOF SLOPE 1/4"=12"
R O
O F
SL
O
PE
/4
A302
3835.1
ROOF SLOPE 1/4"=12"
R O
O F
SL
O
PE
/4
ROOF SLOPE 1/4"=12"
ROOF SLOPE 1/4"=12"
REPLACE ENTIRE ROOFING
SYSTEM, NEW ROOF TO MATCH
EXISTING ROOFING ASSEMBLY,
ROOF DRAINS TO REMAIN.
CORRIDOR
C2-5
OFFICE
A236
CLEAN UTILITY
A256
SEMI-PRIVATE
ROOM
A258
BATH
A258A
BATH
A261A
PRIVATE ROOM
A261
BATH
A264B
ANTE ROOM
A264
ISOLATION /
PRIVATE ROOM
A264A
ELEC. CLOSET-2
A238
W
U
X
A2
A4
A1
A2
OFFICE/PHARMACY
A237
238 237
INFUSION CLINIC
A239
A5
A5
A3
A3
RELOCATED EXISTING
HEAT PUMP
A6K
A6K
1. DIMENSIONS ARE TO: THE FACE OF FINISH OF
PARTITIONS, EXISTING ELEMENTS, EQUIPMENT,
MASONRY, OR CONCRETE; STRUCTURAL GRIDS;
AND CLEAR JAMB OPENING OF DOORS.
2. FIELD VERIFY ACTUAL CONDITIONS AND
DIMENSIONS TO EXISTING ELEMENTS. NOTIFY
ARCHITECT OF DISCREPANCIES AND
UNDOCUMENTED CONDITIONS THAT CONFLICT
WITH NEW WORK.
3. SEE A702 FOR TYPICAL FRAMING DETAILS
INCLUDING WALL PRIORITY AT PARTITION
INTERSECTIONS. SEE A302 FOR TYPICAL FRAMING
AT FIREPROOFED COLUMNS.
4. REFER TO MEP DRAWINGS FOR THE ELECTRICAL
AND MECHANICAL EQUIPMENT.
5. REFER TO STRUCTURAL DRAWINGS FOR THE
EXACT LOCATION OF COLUMNS, BEAMS AND
FRAMING SYSTEM.
LEGEND
FLOOR PLAN NOTES
DOOR OPENING 122
DOOR OPENING MARK
PARTITION TYPE IDENTIFICATION
SEE A701A3A
FEC
FIRE EXTINGUISHER
CABINET
ASTERISK INDICATES PARTITION TO
CONSTRUCT AT START OF
PROJECT - SEE DEMOLITION NOTES
ROOM NAMEROOM NAME
101 ROOM NUMBER
EXPANSION CONTROL JOINT CODES
EJ# - EXPANSION JOINT COVER
SEE DETAILS ON A501. NUMBERS ARE CODED TO JOINT
TYPE. FOR RATED JOINTS, PROVIDE CONTINUOUS
JOINT ASSEMBLY BETWEEN NEW AND EXISTING
CONSTRUCTION INCLUDING INSIDE AND OUTSIDE
CORNER TRANSITIONS AND JOINTS THROUGH
CONCEALED SPACES.
INDICATES AREA OF MINIMAL OR NO
CHANGES
BLOCKING IN GWB DRYWALL. ELEC ROOMS
GC. TO PROVIDE BLOCKING IN THE WALLS WHERE THE
ELECTRICAL PANELS WILL PLACED ON THE WALLS AS
REQUIRED.
SHEET KEYNOTES
1 HR FIRE RATED WALL
2 HR FIRE RATED WALL
INTERIOR ROOM SIGNS
NEW ROOM SIGNS TO MATCH EXISTING. GC TO FOLLOW VA
INSTRUCTIONS FOR INTERIOR ROOMSIGNS STANDARD.
W
U
X
33 39
ELEC. CLOSET-2
A238
A12
A12
A12
3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124 Fax: (352) 553-4437
COA: FL #29758
AKEA Design Proj. No. AD160-18
Design, Inc.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT / ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
OF
FL. REG. NO.ARCHITECT-OF-RECORD
FINAL BID DOCUMENTS
APPROVED FOR CONSTRUCTION
Revisions: Date:
FINAL BID DOCUMENTS
THIS DOCUMENT CONTAINS A DIGITAL SIGNATURE AND
SEAL BY THE INDIVIDUAL NAMED AT RIGHT. PRINTED
COPIES OF THIS DOCUMENT ARE NOT CONSIDERED
SIGNED AND SEALED, AND THE DIGITAL SIGNATURE
MUST BE VERIFIED ON ANY ELECTRONIC COPIES.
4/
/2
3:
:3
PM
BLDGS 64 & 86 PROPOSED
2ND FLOOR & ROOF PLAN & RCP EXPAND ELECTRICAL DISTRIBUTION
LAKE CITY, FLORIDA
573A4-18-601
JF RA
JENNIFER FONG AR97191
AE202
APRIL 28, 2022 21
1/4" = 1'-0"1
BLDG. 64 PROP FLOOR PLAN
& 86 PROP ROOF PLAN
A1 NEW FIRE RATED WALL CONSTRUCTION, REFER TO
WALL TYPES.
A2 NEW FIRE RATED DOOR, FRAMES AND HARDWARE,
REFER TO DOOR SCHEDULE.
A3 NEW SCUPPER, CONDUCTOR HEAD AND
DOWNSPOUT, REFER TO ROOFING DETAILS.
A4 NEW ROOF ASSEMBLY SYSTEM, REFER TO
ROOFING DETAILS.
A5 NEW HVAC EQUIPMENT, REFER TO HVAC
DRAWINGS.
A6 NEW STEEL BOLLARD.
A7 NEW CONCRETE PAD, REFER TO STRUCTURAL
DRAWINGS.
A12 NEW LIGHT FIXTURES, REFER TO ELECTRICAL
DRAWINGS.
A14 EXISTING RELOCATED LOUVER.
A15 INSTALL NEW FIRE EXTINGUISHER TYPE C.
N
1/4" = 1'-0"2
BUILDING 64 PROP
REFLECTED CEILING PLAN - 2ND FLOOR
Date: 2022.04.29 08:59:51-04'00'
FWC FWCFWC FWC
1. DIMENSIONS ARE TO: THE FACE OF FINISH OF
PARTITIONS, EXISTING ELEMENTS, EQUIPMENT,
MASONRY, OR CONCRETE; STRUCTURAL GRIDS;
AND CLEAR JAMB OPENING OF DOORS.
2. FIELD VERIFY ACTUAL CONDITIONS AND
DIMENSIONS TO EXISTING ELEMENTS. NOTIFY
ARCHITECT OF DISCREPANCIES AND
UNDOCUMENTED CONDITIONS THAT CONFLICT
WITH NEW WORK.
3. SEE A702 FOR TYPICAL FRAMING DETAILS
INCLUDING WALL PRIORITY AT PARTITION
INTERSECTIONS. SEE A302 FOR TYPICAL FRAMING
AT FIREPROOFED COLUMNS.
4. REFER TO MEP DRAWINGS FOR THE ELECTRICAL
AND MECHANICAL EQUIPMENT.
5. REFER TO STRUCTURAL DRAWINGS FOR THE
EXACT LOCATION OF COLUMNS, BEAMS AND
FRAMING SYSTEM.
LEGEND
FLOOR PLAN NOTES
DOOR OPENING 122
DOOR OPENING MARK
PARTITION TYPE IDENTIFICATION
SEE A701A3A
FEC
FIRE EXTINGUISHER
CABINET
ASTERISK INDICATES PARTITION TO
CONSTRUCT AT START OF
PROJECT - SEE DEMOLITION NOTES
ROOM NAMEROOM NAME
101 ROOM NUMBER
EXPANSION CONTROL JOINT CODES
EJ# - EXPANSION JOINT COVER
SEE DETAILS ON A501. NUMBERS ARE CODED TO JOINT
TYPE. FOR RATED JOINTS, PROVIDE CONTINUOUS
JOINT ASSEMBLY BETWEEN NEW AND EXISTING
CONSTRUCTION INCLUDING INSIDE AND OUTSIDE
CORNER TRANSITIONS AND JOINTS THROUGH
CONCEALED SPACES.
INDICATES AREA OF MINIMAL OR NO
CHANGES
BLOCKING IN GWB DRYWALL. ELEC ROOMS
GC. TO PROVIDE BLOCKING IN THE WALLS WHERE THE
ELECTRICAL PANELS WILL PLACED ON THE WALLS AS
REQUIRED.
SHEET KEYNOTES
1 HR FIRE RATED WALL
2 HR FIRE RATED WALL
INTERIOR ROOM SIGNS
NEW ROOM SIGNS TO MATCH EXISTING. GC TO FOLLOW VA
INSTRUCTIONS FOR INTERIOR ROOMSIGNS STANDARD.
A302
A6KOFFICE - SOCIAL
WORKER
A333
CORRIDOR
C3-5
CORRIDOR
C3-6
EQUIPMENT
ALCOVE
A337
CLEAN UTILITY
A352
PRIVATE
HOSPICE CARE
A354
WAITING ROOM
A334
ELEC CLOSET-3
A336
W
U
A2 A2
A1
334336
SEMI-PRIVATE
HOSPICE CARE
A240
BATH
A336A
A6K
A12
A12
W
U
3733 39
ELEC. CLOSET-3
A336
A12
A12
A302
A6K
H.A.C.
A427 SUPPLY ROOM
A442
BATH
A446A
PANTRY
A445
EXAM ROOM
A446
ELEC CLOSET-4
A424B
CORRIDOR
C4-6
W
U
A2
A1
424B
OFFICE
A423
POD SURGICAL
COORDINATOR
A426
NURSE
FACILITATOR
A426A
STAFF
UROLOGIST -
UROLOGY
A424
A6K
A12
A12
W
U
3733 39
ELEC. CLOSET-4
A424B
3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124 Fax: (352) 553-4437
COA: FL #29758
AKEA Design Proj. No. AD160-18
Design, Inc.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT / ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
OF
FL. REG. NO.ARCHITECT-OF-RECORD
FINAL BID DOCUMENTS
APPROVED FOR CONSTRUCTION
Revisions: Date:
FINAL BID DOCUMENTS
THIS DOCUMENT CONTAINS A DIGITAL SIGNATURE AND
SEAL BY THE INDIVIDUAL NAMED AT RIGHT. PRINTED
COPIES OF THIS DOCUMENT ARE NOT CONSIDERED
SIGNED AND SEALED, AND THE DIGITAL SIGNATURE
MUST BE VERIFIED ON ANY ELECTRONIC COPIES.
4/
/2
3:
:3
PM
BUILDING 64 PROP 3RD, 4TH
FLRS & REFLECTED CEILING
PLANS
EXPAND ELECTRICAL DISTRIBUTION
LAKE CITY, FLORIDA
573A4-18-601
JF RA
JENNIFER FONG AR97191
AE2…