E E

E

VICINITY MAP

DEPARTMENT OF VETERANS AFFAIRS

NETWORK CONTRACTING ACTIVITY 8

MALCOM RANDALL VA MEDICAL CENTER

1601 SW ARCHER ROAD

GAINESVILLE, FL 32608

3603 NW 98TH STREET, SUITE B

GAINESVILLE, FLORIDA 32606

PH: (352) 474-6124

FAX. (352) 553-4437

COA: FL #29758

DESIGNED FOR:

Veterans Affairs Department of

DESIGNED BY:

PROJECT

LOCATION

PROJECT LOCATION MAP

PROJECT

LOCATION

G001

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

FINAL BID DOCUMENTS

U.S. Department of Veterans Affairs

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

321 4 5 6 7 8 10

EXPAND ELECTRICAL DISTRIBUTION

LAKE CITY, FLORIDA

573A4-18-601

APRIL 28, 2022Revisions: Date:

Office of Construction and Facilities Management

A

B

C

D

E

F

3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124 Fax: (352) 553-4437

COA: FL #29758

AKEA Design Proj. No. AD160-18

ARCHITECT / ENGINEER OF RECORDCONSULTANT

87OF

P R

O

FES S IO NA L ENGIN

EE

R

R O

BER T A . HA FFEM

A

N

L I C E N S E

F L O R I D A

PROJECT

LOCATION

Affiliated Engineers SE, Inc.

Tioga Town Center 12921 SW 1st Road Ste 205 Gainesville, Florida 32669 Tel 352.376.5500 Fax 352.375.3479

CA-5140 1

Robert A Haffema n

Date:

2022.04.29 06:25:31 -04'00'

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

FINAL BID DOCUMENTS

U.S. Department of Veterans Affairs

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

321 4 5 6 7 8 10

EXPAND ELECTRICAL DISTRIBUTION

LAKE CITY, FLORIDA

573A4-18-601

APRIL 28, 2022Revisions: Date:

Office of Construction and Facilities Management

A

B

C

D

E

F

3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124 Fax: (352) 553-4437

COA: FL #29758

AKEA Design Proj. No. AD160-18

ARCHITECT / ENGINEER OF RECORDCONSULTANT

87OF

P R

O

FES S IO NA L ENGIN

EE

R

R O

BER T A . HA FFEM

A

N

L I C E N S E

F L O R I D A G002 Affiliated Engineers SE, Inc.

Tioga Town Center 12921 SW 1st Road Ste 205 Gainesville, Florida 32669 Tel 352.376.5500 Fax 352.375.3479

CA-5140 2

Robert A Haffeman

Date:

2022.04.27 14:53:28 -04'00'

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FINAL BID DOCUMENTS

U.S. Department of Veterans Affairs

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

321 4 5 6 7 8 10

EXPAND ELECTRICAL DISTRIBUTION

LAKE CITY, FLORIDA

573A4-18-601

APRIL 28, 2022Revisions: Date:

Office of Construction and Facilities Management

APPROVED FOR CONSTRUCTION

A

B

C

D

E

F

3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124 Fax: (352) 553-4437

COA: FL #29758

AKEA Design Proj. No. AD160-18

Design, Inc.

ARCHITECT / ENGINEER OF RECORDCONSULTANT

FINAL BID DOCUMENTS

87OF

MDT MDT

C001

STATE OF

P R

O

FESS IO NA L ENGIN

E E

R

M

IC

HA EL D. T OOT LENo. 67818 L I C E N S E

F L O R I D A

Digitally signed by Michael D Tootle Date: 2022.04.27 15:32:44 -04'00'

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FINAL BID DOCUMENTS

U.S. Department of Veterans Affairs

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

321 4 5 6 7 8 10

EXPAND ELECTRICAL DISTRIBUTION

LAKE CITY, FLORIDA

573A4-18-601

APRIL 28, 2022Revisions: Date:

Office of Construction and Facilities Management

APPROVED FOR CONSTRUCTION

A

B

C

D

E

F

3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124 Fax: (352) 553-4437

COA: FL #29758

AKEA Design Proj. No. AD160-18

Design, Inc.

ARCHITECT / ENGINEER OF RECORDCONSULTANT

FINAL BID DOCUMENTS

87OF

SHEET NOTES

SHEET KEYNOTES

C002

STATE OF

P R

O

FESS IO NA L ENGIN

E E

R

M

IC

HA EL D. T OOTLENo. 67818 L I C E N S E

F L O R I D A

Date: 2022.04.27 15:33:35 -04'00'

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FINAL BID DOCUMENTS

U.S. Department of Veterans Affairs

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

321 4 5 6 7 8 10

EXPAND ELECTRICAL DISTRIBUTION

LAKE CITY, FLORIDA

573A4-18-601

APRIL 28, 2022Revisions: Date:

Office of Construction and Facilities Management

APPROVED FOR CONSTRUCTION

A

B

C

D

E

F

3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124 Fax: (352) 553-4437

COA: FL #29758

AKEA Design Proj. No. AD160-18

Design, Inc.

ARCHITECT / ENGINEER OF RECORDCONSULTANT

FINAL BID DOCUMENTS

87OF

C003

STATE OF

P R

O

FESS IO NA L ENGIN

E E

R

M

IC

HA EL D. T OOTLENo. 67818 L I C E N S E

F L O R I D A

Date: 2022.04.27 15:34:25 -04'00'

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FINAL BID DOCUMENTS

U.S. Department of Veterans Affairs

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

321 4 5 6 7 8 10

EXPAND ELECTRICAL DISTRIBUTION

LAKE CITY, FLORIDA

573A4-18-601

APRIL 28, 2022Revisions: Date:

Office of Construction and Facilities Management

APPROVED FOR CONSTRUCTION

A

B

C

D

E

F

3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124 Fax: (352) 553-4437

COA: FL #29758

AKEA Design Proj. No. AD160-18

Design, Inc.

ARCHITECT / ENGINEER OF RECORDCONSULTANT

FINAL BID DOCUMENTS

87OF

C100

STATE OF

P R

O

FESS IO NA L ENGIN

E E

R

M

IC

HA EL D. T OOT LENo. 67818 L I C E N S E

F L O R I D A

Date: 2022.04.27 15:37:24 -04'00'

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FINAL BID DOCUMENTS

U.S. Department of Veterans Affairs

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

321 4 5 6 7 8 10

EXPAND ELECTRICAL DISTRIBUTION

LAKE CITY, FLORIDA

573A4-18-601

APRIL 28, 2022Revisions: Date:

Office of Construction and Facilities Management

APPROVED FOR CONSTRUCTION

A

B

C

D

E

F

3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124 Fax: (352) 553-4437

COA: FL #29758

AKEA Design Proj. No. AD160-18

Design, Inc.

ARCHITECT / ENGINEER OF RECORDCONSULTANT

FINAL BID DOCUMENTS

87OF

C101

STATE OF

P R

O

FESS IO NA L ENGIN

E E

R

M

IC

HA EL D. T OOT LENo. 67818 L I C E N S E

F L O R I D A

Date: 2022.04.27 15:39:01 -04'00'

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FINAL BID DOCUMENTS

U.S. Department of Veterans Affairs

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

321 4 5 6 7 8 10

EXPAND ELECTRICAL DISTRIBUTION

LAKE CITY, FLORIDA

573A4-18-601

APRIL 28, 2022Revisions: Date:

Office of Construction and Facilities Management

APPROVED FOR CONSTRUCTION

A

B

C

D

E

F

3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124 Fax: (352) 553-4437

COA: FL #29758

AKEA Design Proj. No. AD160-18

Design, Inc.

ARCHITECT / ENGINEER OF RECORDCONSULTANT

FINAL BID DOCUMENTS

87OF

C200

STATE OF

P R

O

FESS IO NA L ENGIN

E E

R

M

IC

HA EL D. T OOT LENo. 67818 L I C E N S E

F L O R I D A

Date: 2022.04.27 15:39:50 -04'00'

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FINAL BID DOCUMENTS

U.S. Department of Veterans Affairs

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

321 4 5 6 7 8 10

EXPAND ELECTRICAL DISTRIBUTION

LAKE CITY, FLORIDA

573A4-18-601

APRIL 28, 2022Revisions: Date:

Office of Construction and Facilities Management

APPROVED FOR CONSTRUCTION

A

B

C

D

E

F

3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124 Fax: (352) 553-4437

COA: FL #29758

AKEA Design Proj. No. AD160-18

Design, Inc.

ARCHITECT / ENGINEER OF RECORDCONSULTANT

FINAL BID DOCUMENTS

87OF

C201

STATE OF

P R

O

FESS IO NA L ENGIN

E E

R

M

IC

HA EL D. T OOT LENo. 67818 L I C E N S E

F L O R I D A

Date: 2022.04.27 15:41:07 -04'00'

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FINAL BID DOCUMENTS

U.S. Department of Veterans Affairs

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

321 4 5 6 7 8 10

EXPAND ELECTRICAL DISTRIBUTION

LAKE CITY, FLORIDA

573A4-18-601

APRIL 28, 2022Revisions: Date:

Office of Construction and Facilities Management

APPROVED FOR CONSTRUCTION

A

B

C

D

E

F

3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124 Fax: (352) 553-4437

COA: FL #29758

AKEA Design Proj. No. AD160-18

Design, Inc.

ARCHITECT / ENGINEER OF RECORDCONSULTANT

FINAL BID DOCUMENTS

87OF

C300

STATE OF

P R

O

FESS IO NA L ENGIN

E E

R

M

IC

HA EL D. T OOT LENo. 67818 L I C E N S E

F L O R I D A

Date: 2022.04.27 15:42:33 -04'00'

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FINAL BID DOCUMENTS

U.S. Department of Veterans Affairs

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

321 4 5 6 7 8 10

EXPAND ELECTRICAL DISTRIBUTION

LAKE CITY, FLORIDA

573A4-18-601

APRIL 28, 2022Revisions: Date:

Office of Construction and Facilities Management

APPROVED FOR CONSTRUCTION

A

B

C

D

E

F

3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124 Fax: (352) 553-4437

COA: FL #29758

AKEA Design Proj. No. AD160-18

Design, Inc.

ARCHITECT / ENGINEER OF RECORDCONSULTANT

FINAL BID DOCUMENTS

87OF

C301

STATE OF

P R

O

FESS IO NA L ENGIN

E E

R

M

IC

HA EL D. T OOT LENo. 67818 L I C E N S E

F L O R I D A

Date: 2022.04.27 15:43:40 -04'00'

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FINAL BID DOCUMENTS

U.S. Department of Veterans Affairs

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

321 4 5 6 7 8 10

EXPAND ELECTRICAL DISTRIBUTION

LAKE CITY, FLORIDA

573A4-18-601

APRIL 28, 2022Revisions: Date:

Office of Construction and Facilities Management

APPROVED FOR CONSTRUCTION

A

B

C

D

E

F

3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124 Fax: (352) 553-4437

COA: FL #29758

AKEA Design Proj. No. AD160-18

Design, Inc.

ARCHITECT / ENGINEER OF RECORDCONSULTANT

FINAL BID DOCUMENTS

87OF

TYPICAL BOLLARD DETAIL

TYPICAL TEMPORARY

CONSTRUCTION FENCE DETAIL

GENERATOR/

STORAGE TANK

PROTECTION

TYPICAL OF 9

SEE C301

CIVIL DETAILS

NEW ASPHALT PAVEMENT MEETS

EXISTING ASPHALT PAVEMENT

ROAD SAWCUT AND REPAIR LOCATION

AS NEEDED FOR SITE RESTORATION

NOTE:

THIS DETAIL AS SHOWN, ONLY IF UTILITIES OR CONDUIT ARE INSTALLED OR MOVED.

DUCTBANK INSTALLATION SHALL ADDITIONALLY FOLLOW REQUIREMENTS FOR DUCTBANK

CONSTRUCTION AS WELL AS DETAIL (THIS SHEET) FOR PAVEMENT, CURB REPAIR, AND

SIDEWALK REPLACEMENT.

MDT MDT

FOR REPAIR TO EXISITNG

SITE SIDEWALKS

TYPICAL OPEN UTILITY TRENCH

PIPE LAYING DETAIL

C400

PEDESTRIAN SIDEWALK REPAIR AND

DOOR LANDINGS

CURB AND GUTTER

FOR DUCTBANK INSTALLATION

ROADWAY WIDTH 10-FEET

STATE OF

P R

O

FESS IO NA L ENGIN

E E

R

M

IC

HA EL D. T OOT LENo. 67818 L I C E N S E

F L O R I D A

Date: 2022.04.27 15:44:27 -04'00'

MATERIAL LEGEND ABBREVATIONS

& AND JAN. JANITOR

@ AT JT. JOINT

CENTER LINE

DIAMETER OR ROUND K.D. KNOCKED DOWN

# NUMBER kg KILOGRAM

KIT. KITCHEN

A.F.F. ABOVE FINISHED FLOOR K.P. KICK PLATE

A.C.T. ACOUSTIC CEILING TILE

ADJST. ADJUSTABLE LAM. LAMINATED

ADJ. ADJACENT LAV. LAVATORY

AGGR. AGGREGATE LG. LONG

A.H.U. AIR HANDLER UNIT LT. LIGHT

ALT. ALTERNATE

ALUM. ALUMINUM m. METER

ANGLE mm. MILIMETER

A.D. AREA DRAIN MAX. MAXIMUM

A.P. ACCESS PANEL MECH. MECHANICAL

MET./MTL. METAL

BM BEAM MFR. MANUFACTURER

BITUM. BITUMINOUS MH MANHOLE

BLDK. BLOCKING MIN. MINIMUM

BD. BOARD MIR. MIRROR

BOT. BOTTOM MISC. MISCELLANEOUS

BLDG. BUILDING M.O. MASONRY OPENING

°C DEGREES CELSIUS N NEWTON

CAB. CABINET N. NORTH

CPT. CARPET N.G.V.D. NATIONAL GEODETIC

C.B. CATCH BASIN VERTICAL DATUM

CEIL./CLG. CEILING N.I.C. NOT IN CONTRACT

CTR. CENTER NO. / # NUMBER

C.T. CERAMIC TILE N.T.S. NOT TO SCALE

CL. CLEAR

CLOS. CLOSET O.A. OVERALL

COL. COLUMN O.C. ON CENTER

CONC. CONCRETE O.D. OUTSIDE DIAMETER

CONC. BLK. CONCRETE BLOCK O.D. OVERFLOW DRAIN

C.M.U./CMU CONCRETE MASONRY UNIT OFF OFFICE

CONST. JT. CONSTRUCTION JOINT O'HD. DR. OVERHEAD DOOR

C.J. CONTROL JOINT OPG. OPENING

CORR. CORRIDOR OPP. OPPOSITE

C.S. COUNTER SINK O.S. OVERHEAD SCUPPER

DET. DETAIL P PASCAL

DIA. DIAMETER PL. PLATE

DIM. DIMENSION PLYWD. PLYWOOD

DIST. DISTANCE P. LAM. PLASTIC LAMINATE

DR. DOOR PR. PAIR

DBL. DOUBLE

DN. DOWN QTY. QUANTITY

D.S. DOWNSPOUT Q.T. QUARRY TILE

D. DRAIN

DWG. DRAWING R. RADIUS

D.F. DRINKING FOUNTAIN R. RISER

R.D. ROOF DRAIN

E.A. EACH REINF. REINFORCEMENT

E.W. EACH WAY REQ'D REQUIRED

E. EAST RM. ROOM

ELEC. ELECTRICAL

E.W.C. ELECTRIC WATER COOLER S. SOUTH

EL. ELEVATION S.C. SOLID CORE

ELEV. ELEVATOR SECT. SELECTION

EQ. EQUAL SHT. SHEET

EQUIP. EQUIPMENT SHWR. SHOWER

E.F. EXHAUST FAN SIM. SIMILAR

EXIST. EXISTING SPEC. SPECIFICATIONS

EXP. JT. / E.J. EXPANSION JOINT SQ. SQUARE

EXP. EXPOSED SQ. FT. SQUARE FEET

EXT. EXTERIOR S.S. STAINLESS STEEL

EXR. EXISTING TO REMAIN STL. STEEL

STOR. STORAGE

F.T. /' FEET STRUCT. STRUCTURAL

F.A. FIRE ALARM SUSP. SUSPENDED

F.D. FLOOR DRAIN SYM. SYMMETRICAL

FDN. FOUNDATION

F.E.C. FIRE EXTINGUISHER CABINET TEL. TELEPHONE

F.E. FIRE EXTINGUISHER TEMP. TEMPERED

FIN FINISH THR. THRESHOLD

F.H.C. FIRE HOSE CABINET T.O.M. TOP OF MASONRY

FIXT. FIXTURE T.O.S. TOP OF STEEL

FLASH. FLASHING TR. TREAD

FL. FLOOR TYP. TYPICAL

FLOUR. FLUORESCENT

FR. FRAME U. URINAL

FTG. FOOTING U.L. UNDERWRITERS LABORATORIES

FURR. FURRING U.N.O. UNLESS OTHERWISE NOTED

GA. GAUGE V. VENT

GALV. GLAVANIZED V.C.T. VINYL COMPOSITE TILE

GL. GLASS VERT. VERTICAL

G.B. GRAB BAR VEST. VESTIBULE

GYP. GYPSUM V.W.C. VINYL WALL COVERING

GWB/GYP. BD. GYPSUM BOARD

W. WEST

H. / HDW. HARDWARE w/ WITH

H.B. HOSE BIBB W.C. WATER CLOSET

H.C. HOLLOW CORE WO. WOOD

H.M. HOLLOW METAL WDW. WINDOW

HORIZ. HORIZONTAL W.G. WATER GUARD

HT. HEIGHT W.H. WATER HEATER

HVAC HEATING VENTILATION AND w/o WITHOUT

AIR CONDITIONING WP. WATER PROOF

W.R. WATER RESISTANT

I.D. INSIDE DIAMETER

INSUL. INSULATION

INT. INTERIOR

GENERAL NOTESDRAFTING SYMBOLS

1. ALL WORK SHALL CONFORM TO ALL APPLICABLE CODES, STANDARDS AND

GOVERNING AUTHORITIES.

2. THESE DRAWINGS ARE ISSUED IN CONJUNCTION WITH THE PROJECT MANUAL

OF THE DAME DATE, TITLE, AND PROJECT NUMBER AND TOGETHER ARE

REFERRED TO AS "CONTRACT DOCUMENTS."

3. REFER TO ARCHITECTURAL, STRUCTURAL, MECHANICAL, PLUMBING, FIRE

PROTECTION, AND ELECTRICAL DRAWINGS FOR COORDINATION OF WORK.

4. NOTES APPEAR ON A NUMBER OF DRAWINGS FOR DIFFERENT SYSTEMS AND

MATERIALS. REFERENCE ALL ISSUED CONTRACT DOCUMENTS TO APPLY

APPLICABLE NOTES, SYMBOLS AND ABBREVIATION TO BUILDING COMPONENTS.

5. DO NOT SCALE THE DRAWINGS.

6. THE CONTRACTOR SHALL VISIT THE SITE AND BECOME KNOWLEDGE OF

CONDITIONS. THE CONTRACTOR SHALL INVESTIGATE, VERIFY, AND BE

RESPONSIBLE FOR ALL THE REQUIREMENTS OF THE PROJECT AND SHALL

NOTIFY THE OWNER AND ARCHITECT OF ANY EXISTING CONDITIONS REQUIRING

INFORMATION BEFORE PROCEEDING WITH ANY WORK.

7. THE CONTRACTOR SHALL PROTECT ALL EXISTING SITE ELEMENTS FROM

DAMAGE DUE TO ALTERATION AND CONSTRUCTION OPERATIONS AND THEY

SHALL REPAIR OR REPLACE ELEMENTS DAMAGED DURING THE PROJECT.

8. ANY UTILITY SHUT-OFFS AS REQUIRED BY THE CONTRACTOR FOR

COMPLETION OF THE WORK SUCH AS ELECTRICAL, GAS, WATER, SEWER,

STEAM, ETC., MUST BE SCHEDULED WITH THE OWNER, ARCHITECT AND UTILITY

COMPANY PRIOR TO COMMENCING WORK.

9. DETAILS SHOWN ARE INTENDED TO BE INDICATIVE OF THE PROFILE AND TYPE

OF DETAILING REQUIREMENTS FROM THE WORK, DETAILS NOT SHOWN ARE

SIMILAR IN CHARACTER TO THOSE SHOWN.

10. UNLESS NOTED OTHERWISE ALL FASTENERS AND FASTENING DEVICES ARE

TO BE CONCEALED IN ALL FINISHED SPACES.

11. ANY PIPING, DUCTS, CONDUITS, ETC. THAT PENETRATE FIRE RATED FLOOR

SLABS AND WALLS SHALL BE INSTALLED IN A MANNER THAT WILL PRESERVE

THE FIRE INTEGRITY OF THE FLOOR OR WALL. FIRE STOP RATINGS SHALL

MATCH RATINGS OF FLOORS OR WALLS WHERE PENETRATIONS OCCUR.

PROVIDE FIRE DAMPERS IN DUCTS PENETRATING FIRE-RATED WALLS AND

FLOORS TO MEET APPLICABLE BUILDING CODES.

12. ALL JOINTS OF ANY ELEMENT OF CONSTRUCTION WHICH ARE REQUIRED TO

HAVE A FIRE RESISTANCE RATING SHALL BE INSTALLED PER THE

MANUFACTURER'S PUBLISHED TESTED ASSEMBLIES, SHALL BE TIGHT AND

SHALL PREVENT THE PASSAGE OF SMOKE AND FLAME.

13. WHERE THE FIRE RATINGS OF WALLS ARE NOTED ON THE DRAWINGS, THE

FIRE RATING SHALL APPLY TO THE ENTIRE PERIMETER ENCLOSURE OF THE

ROOM OR SPACE FOR THE FULL LENGTH AND HEIGHT OF AREAS BEING

SEPARATED. EXTENDING TO THE UNDERSIDE OF THE FLOOR OR ROOF DECK.

14. PROVIDE FIRE STOPS TO SEPARATE WALL CAVITIES FROM HORIZONTAL

PLENUM AREAS AND BETWEEN FLOORS TO CLOSE OPENINGS. FIRE RATING OF

STOPS SHALL MATCH THE FIRE RATING OF VERTICAL SEPARATION OR FLOOR

CONSTRUCTION, WHICHEVER IS GREATER.

15. CONSTRUCTION AROUND CABINETS, PANELS AND BOXES RECESSED IN FIRE-

RATED FLOOR, WALL AND CEILING ASSEMBLIES SHALL MAINTAIN THE FIRE-

RATING NOTED IN THE DRAWINGS.

16. OPENINGS IN WALL , CEILING, FLOOR AND ROOF ASSEMBLIES SHALL BE

SEALED WITH PENETRATION SEALANT SYSTEM THAT MEET OR EXCEED THE

REQUIRED FIRE RATINGS.

17. ALL DISSIMILAR MATERIALS SHALL BE EFFECTIVELY ISOLATED FROM EACH

OTHER BY GASKETS OR COATINGS OR BOTH TO AVOID GALVANIC CORROSION

ACTION.

18. PATCH FIREPROOFING TO MATCH EXISTING.

19. PROVIDE PRESSURE TREATED WOOD WHERE WOOD IS CONTACT WITH

CONCRETE, EARTH, OR EXPOSED TO THE WEATHER, UNLESS NOTED

OTHERWISE.

20. SEE MECHANICAL, PLUMBING, FIRE PROTECTION, AND ELECTRICAL

DRAWINGS TO DETERMINE QUANTITIES OF DIFFUSERS, GRILLS, LIGHT

FIXTURES, SPRINKLER HEADS, ETC.

21. THE LOCATION OF CEILING MOUNTED DIFFUSERS, GRILLS, SPRINKLERS,

HEADS, FIXTURES, ETC. NOT SHOWN ON THE ARCHITECTURAL REFLECTED

CEILING PLAN MUST BE VERIFIED WITH THE DESIGN PROFESSIONAL, PRIOR TO

INSTALLATION.

22. PIPE AND COLUMN FURRING SHALL BE HELD AS CLOSE TO THE PIPING AND/OR

COLUMNS AS POSSIBLE, UNLESS NOTED OTHERWISE.

23. THE EXTENT OF THE WORK SHOWN ON THE PLANS AND DETAILS REFLECTS

THE BEST JUDGMENT OF THE ARCHITECT/ENGINEER, THE CONTRACTOR SHALL

FAMILIARIZE HIMSELF WITH THE EXISTING CONDITIONS AND ADVISE THE

ARCHITECT, IN WRITING, OF ANY SITUATION THAT WOULD NOT ALLOW HIM TO

PROCEED ON THE BASIS OF THESE DOCUMENTS.

24. THE ARCHITECT/ENGINEER'S SELECTION OF MATERIALS AND DETAILS DOES

NOT RELIEVE THE CONTRACTOR FROM VERIFYING WITH THE MATERIAL SUPPLIERS

THAT THE PROPOSED MATERIALS ARE CORRECT AND PROPER FOR THE INTENDED

APPLICATION AND USE.

25. CONCRETE FILLS ABOVE STRUCTURAL, SLABS SHALL BE REINFORCED. REFER

TO STRUCTURAL DRAWINGS FOR ADDITIONAL REQUIREMENTS.

26. UNLESS NOTED OTHERWISE, WHERE AN ARCHITECTURAL FINISHED FLOOR IS

TO BE PROVIDED (REQUIRED A DEPRESSED STRUCTURAL SLAB), THE FLOOR

ELEVATIONS ARE TO TOP THE FINISHED FLOOR. WHERE AN ARCHITECTURAL

FINISHED FLOOR IS INTENDED FOR SURFACE APPLICATION THE FLOOR

ELEVATIONS ARE TO TOP THE STRUCTURAL SLAB. REFER TO STRUCTURAL

DRAWINGS FOR LOCATION OF DEPRESSED SLABS.

27. UNLESS NOTED OTHERWISE, CONCRETE PAD WITH REINFORCING SHALL BE

INSTALLED UNDER ALL FLOOR MOUNTED MECHANICAL AND ELECTRICAL

EQUIPMENT. REFER TO MECHANICAL, ELECTRICAL, PLUMBING AND FIRE

PROTECTION DRAWINGS FOR THE EXTEND OF EQUIPMENT PADS. THE

CONTRACTOR SHALL COORDINATE THE SIZE, THICKNESS AND LOCATION OF THE

CONCRETE PADS WITH THE EQUIPMENT INSTALLER.

28. AT THOSE PLACES WHERE MATERIALS ARE APPLIED TO, OR ARE IN DIRECT

CONTACT WITH WORK INSTALLED BY ANOTHER SUBCONTRACTOR,

COMMENCEMENT OF WORK IMPLIES THE ACCEPTANCE OF THE SUBSTRATE AND

EXISTING CONDITIONS AS SUITABLE FOR THE APPLICATION INTENDED.

29. ALL WORK SHALL BE EXECUTED IN A WORKMANLIKE MANNER. CONSTRUCTION

OF NEW HORIZONTAL SURFACES SHALL BE LEVEL AND FLAT AND NEW VERTICAL

SURFACES SHALL BE CONSTRUCTED TO BE PLUMB, UNLESS OTHERWISE NOTED.

30. WHERE NOT INDICATED, PROVIDE BLOCKING IN WALLS, SOFFITS, AND CEILING

RECEIVING SIGNAGE, COAT HOOKS, LOCKERS, MARKER BOARDS, AND OTHER

MOUNTED ITEMS ACCORDING TO THE MANUFACTURER'S RECOMMENDATIONS.

31. CONTINUOUS PERIMETER FIRE SAFING BETWEEN FLOOR SHALL BE PROVIDED

AND COORDINATED WITH THE EXTERIOR WALL SYSTEMS AND ASSEMBLIES. THE

FIRE SAFINGS'S RATING SHALL MATCH OR EXCEED THAT OF THE FLOOR

CONSTRUCTION RATING.

32. CONTRACTOR TO CONFIRM AND FIELD VERIFY DIMENSIONS TO COORDINATE

WITH OWNER PROVIDED EQUIPMENT AND FURNISHINGS.

33. SUBSTITUTIONS OF MATERIALS MAY OCCUR IN ACCORDANCE WITH THE

CONTRACT DOCUMENTS, AND ONLY IF AUTHORIZED BY THE ARCHITECT.

34. CONTRACTOR SHALL PERFORM FIELD VERIFICATION OF ALL THE EXISTING

CONDITION THE SITE AND SHALL VERIFY THE LOCATION OF ALL EXISTING UTILITIES

AND SHALL COMPARE THE INFORMATION TO THE CONTRACTOR DOCUMENTS

PRIOR TO THE COMMENCEMENT OF ALL WORK. THE CONTRACTOR SHALL

IMMEDIATELY NOTIFY THE ARCHITECT IN WRITING OF ANY DISCREPANCIES.

35. ALL CONTRACTOR PROVIDED MATERIALS SHALL BE NEW AND DELIVERS AND

INSTALLED IN GOOD CONDITION AND WITHOUT ANY DEFECTS.

36. ANY WORK NOT CONFORMING TO THESE SPECIFICATIONS WILL BE REJECTED.

THE ARCHITECT OR THE OWNER MAY REJECT THE WORK AND REJECTED WORK

WILL BE REMOVED AND REPLACED AT NO ADDITIONAL COST TO THE OWNER.

37. ALL DIMENSIONS TO FINISH FACE OF SURFACE CENTERLINE OF COLUMN, OR TO

CENTERLINE OR FACE OF STUD UNLESS NOTED OTHERWISE.

A-5

A-8 1

A-5

A-5

A-5

0'-0"

ROOM

EXTERIOR ELEVATION SYMBOL

ELEVATION IDENTIFICATION

DRAWING WHERE ELEVATION IS SHOWN

INTERIOR ELEVATION SYMBOL

ELEVATION IDENTIFICATION

DRAWING WHERE ELEVATION IS VIEWING

DRAWING WHERE ELEVATION IS SHOWN

BUILDING SECTION SYMBOL

SECTION IDENTIFICATION

DRAWING WHERE SECTION IS VIEWING

DRAWING WHERE SECTION IS SHOWN

WALL SECTION SYMBOL

SECTION IDENTIFICATION

DRAWING WHERE SECTION IS VIEWING

DRAWING WHERE SECTION IS SHOWN

DETAIL SYMBOL

DETAIL IDENTIFICATION

DRAWING WHERE DETAIL IS SHOWN

NEW HEIGHT ELEVATION SYMBOL

ELEVATION IDENTIFICATION

LOCATION OF ELEVATION

EXISTING HEIGHT ELEVATION SYMBOL

ELEVATION IDENTIFICATION

LOCATION OF ELEVATION

ROOM IDENTIFICATION

ROOM NAME

ROOM NUMBER

WINDOW/LOUVER IDENTIFICATION

WINDOW IDENTIFICATION

STOREFRONT IDENTIFICATION

STOREFRONT IDENTIFICATION

DOOR IDENTIFICATION

DOOR IDENTIFICATION

CONCRETE: CAST-IN-PLACE/PRECAST

MORTAR

COMPACTED FILL

UNDISTURBED FILL

EARTHWORKS: GRAVEL

ELEVATION: INDICATION: GLASS

ACOUSTIC TILE

FINISHES: CARPETS & PADS

GYPSUM/WALL BOARD

RESILIENT FLOORING/

PLASTIC LAMINATE

PLASTIC

GLASS

GLASS BLOCK

STRUCTURAL GLASS

GYPSUM BOARD

BATT INSULATION

RIGID INSUALTION

BRICK

PLAN SECTION

CMU

GLAZED BRICK

STRUCTURAL: FACING TILE

ALUMINUM

BRASS/BRONZE

STEEL

GRANITE

RUBBLE

STUCCO ON LATH

WOOD: FINISH & TRIM

PLYWOOD/SM. SCALE

2 X WOOD BLOCKING

EXISTING CONST. TO REMAIN

EXISTING CONST. TO BE

REMOVED (AS NOTED)

OWNER FURNISHED

EQUIPMENT/FURNATURE (AS NOTED)

HIDDEN ITEMS (AS NOTED)

3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124 Fax: (352) 553-4437

COA: FL #29758

AKEA Design Proj. No. AD160-18

Design, Inc.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT / ENGINEER OF RECORDCONSULTANT

321 4 5 6 7 8 9 10

OF

FL. REG. NO.ARCHITECT-OF-RECORD

FINAL BID DOCUMENTS

APPROVED FOR CONSTRUCTION

Revisions: Date:

FINAL BID DOCUMENTS

THIS DOCUMENT CONTAINS A DIGITAL SIGNATURE AND

SEAL BY THE INDIVIDUAL NAMED AT RIGHT. PRINTED

COPIES OF THIS DOCUMENT ARE NOT CONSIDERED

SIGNED AND SEALED, AND THE DIGITAL SIGNATURE

MUST BE VERIFIED ON ANY ELECTRONIC COPIES.

4/

/2

3:

:4

PM

GENERAL INFORMATION EXPAND ELECTRICAL DISTRIBUTION

LAKE CITY, FLORIDA

573A4-18-601

JF RA

JENNIFER FONG AR97191

AG001

APRIL 28, 2022 13

Digitally signed by Jennifer R Fong Date: 2022.04.29 08:45:06-04'00'

BUILDING 37

BUILDING 93

BUILDING

SOUTH MARION STREET (U.S. 441)

BA

YA

A

VE

N U

E

DIVISION STREET

x x x x x x x x x x

F

F

F

AREA OF ARCHITECTURAL SCOPE

AREAS OF ARCHITECTURAL SCOPE

BUILDING

BUILDING

64ABC

BUILDING 86

BUILDING

BUILDING 74

A. ARCHITECTURAL SITE PLAN FOR REFERENCE ONLY.

SEE CIVIL AND ELECTRICAL FOR ADDITIONAL

INFORMATION

3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124 Fax: (352) 553-4437

COA: FL #29758

AKEA Design Proj. No. AD160-18

Design, Inc.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT / ENGINEER OF RECORDCONSULTANT

321 4 5 6 7 8 9 10

OF

FL. REG. NO.ARCHITECT-OF-RECORD

FINAL BID DOCUMENTS

APPROVED FOR CONSTRUCTION

Revisions: Date:

FINAL BID DOCUMENTS

THIS DOCUMENT CONTAINS A DIGITAL SIGNATURE AND

SEAL BY THE INDIVIDUAL NAMED AT RIGHT. PRINTED

COPIES OF THIS DOCUMENT ARE NOT CONSIDERED

SIGNED AND SEALED, AND THE DIGITAL SIGNATURE

MUST BE VERIFIED ON ANY ELECTRONIC COPIES.

4/

/2

3:

:4

PM

ARCHITECTURAL SITE PLAN EXPAND ELECTRICAL DISTRIBUTION

LAKE CITY, FLORIDA

573A4-18-601

JF RA

JENNIFER FONG AR97191

AS101

APRIL 28, 2022 14

N

SITE PLAN NOTES

LEGEND

1" = 50'-0"1 ARCHITECTURE SITE PLAN

Date: 2022.04.29 08:47:01-04'00'

NOTE:

CONTRACTOR SHALL REMOVE CEILING IN 40’

INCREMENTS TO FACILITATE THE INSTALLATION OF

THE CONDUIT FROM THE EMERGENCY EQUIPMENT

ROOM TO THE EES ROOM. REPLACE TILE WITH NEW

AT THE COMPLETION OF EACH INCREMENT.

PATH OF ELECTRICAL CONDUIT

BUILDING 84 EMERGENCY

ELEC ROOM

A187

SWITCHGEAR

A188

2' - 2 1/2"

2' - 2 1/2"

SEE NOTE FOR ELEC

CONDUIT PATH

BUILDING 86

3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124 Fax: (352) 553-4437

COA: FL #29758

AKEA Design Proj. No. AD160-18

Design, Inc.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT / ENGINEER OF RECORDCONSULTANT

321 4 5 6 7 8 9 10

OF

FL. REG. NO.ARCHITECT-OF-RECORD

FINAL BID DOCUMENTS

APPROVED FOR CONSTRUCTION

Revisions: Date:

FINAL BID DOCUMENTS

THIS DOCUMENT CONTAINS A DIGITAL SIGNATURE AND

SEAL BY THE INDIVIDUAL NAMED AT RIGHT. PRINTED

COPIES OF THIS DOCUMENT ARE NOT CONSIDERED

SIGNED AND SEALED, AND THE DIGITAL SIGNATURE

MUST BE VERIFIED ON ANY ELECTRONIC COPIES.

4/

/2

3:

:5

PM

1ST FLOOR RCP PLAN/

ELEC CONDUIT PATH LAYOUT EXPAND ELECTRICAL DISTRIBUTION

LAKE CITY, FLORIDA

573A4-18-601

JF RA

JENNIFER FONG AR97191

AS102

APRIL 28, 2022 15

GENERAL NOTES

KEY LEGEND

N

SCALE: 1" = 20'-0"1 BASEMENT - ELEC CONDUIT PATH

Date: 2022.04.29 09:01:12-04'00'

G R

ID

N :4 .3

G R

ID

E :2 .5

LA

T

IT

U D E '5 .8

LO

N G

IT

U D E '0 .4

S

IT

E

C O N T R O L P O

IN

T

S E T

N A

IL

(N O

ID

E N T

IF

IC

A T

IO

N

LA

T

IT

U D E '5 .8 N N A D '8

LO

N G

IT

U D E '0 .4 W N A D '8

E

LE

V A T

IO

N

.0 N A V D '8

W H E E L S T O P

(T Y P

IC

A L)

D

EW

A

LK

C O V E R E D

A R E A

PLANTER

F E N C E D

C O M P O U N D

AE302

AE302

D4

D4

D1

D14 D16D15

D6

D20

D17D17

D17

D17

D3D3

D5D5

D11D11

D5D5D5

D16TRANSFORMER

ROOM

GENERATOR

ROOM

D23

AE302

AE302

D9

D9

D9

D10D10

D9

DEMOLITION PLAN NOTES

1. SCREENED LINES AND PATTERNS INDICATE

EXISTING ELEMENTS TO REMAIN. HEAVY/DASHED

LINES INDICATE EXISTING ELEMENTS TO BE

REMOVED.

2. MAINTAIN CONSTRUCTION AREA UNDER NEGATIVE

PRESSURE RELATIVE TO ADJACENT OCCUPIED

AREAS. SEE SPECIFICATIONS FOR ADDITIONAL

INFECTION CONTROL REQUIREMENTS.

3. REMOVE EXISTING DEVICES AS SHOWN ON

ELECTRICAL AND MECHANICAL DRAWINGS. REPAIR

AND FINISH WALLS WHERE DEVICES ARE REMOVED.

4. REPLACE, REPAIR, AND EXTEND EXISTING

ELEMENTS (INCLUDING WALLS AND WALL FINISHES,

FLOORS AND FLOOR FINISHES, AND CEILINGS AND

CEILING FINISHES) IN AREAS OF WORK TO PROVIDE

INCONSPICUOUS TRANSITION BETWEEN EXISTING

AND NEW ELEMENTS.

5. SEQUENCE WORK AND PROVIDE TEMPORARY

PROTECTIVE MEASURES TO PROTECT THE EXISTING

BUILDING MATERIALS AND INTERIOR FROM THE

ELEMENTS; INCLUDING TEMPERATURE, WIND, AND

PRECIPITATON.

6. AFTER THE EXPANSION AREA IS DRIED-IN,

CONSTRUCT SOFT CONSTRUCTION BARRIERS

SHOWN IN CIVIL DRAWINGS, FOLLOWED BY NEW

PERIMETER PARTITIONS AND DOORS (NOTED WITH

AN * BY THE PARTITION TYPE TAG ON THE FLOOR

PLANS) TO SERVE AS A CONSTRUCTION BARRIER

FOR THE REMAINDER OF THE CONSTRUCTION

DURATION. COMPLY WITH VA'S INFECTION CONTROL

PLAN. SEE SAFETY REQUIREMENTS SPECIFICATION

FOR ADDITIONAL MEASURES REQUIRED.

3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124 Fax: (352) 553-4437

COA: FL #29758

AKEA Design Proj. No. AD160-18

Design, Inc.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT / ENGINEER OF RECORDCONSULTANT

321 4 5 6 7 8 9 10

OF

FL. REG. NO.ARCHITECT-OF-RECORD

FINAL BID DOCUMENTS

APPROVED FOR CONSTRUCTION

Revisions: Date:

FINAL BID DOCUMENTS

THIS DOCUMENT CONTAINS A DIGITAL SIGNATURE AND

SEAL BY THE INDIVIDUAL NAMED AT RIGHT. PRINTED

COPIES OF THIS DOCUMENT ARE NOT CONSIDERED

SIGNED AND SEALED, AND THE DIGITAL SIGNATURE

MUST BE VERIFIED ON ANY ELECTRONIC COPIES.

4/

/2

3:

:1

PM

BUILDING 84 DEMO GEN. & TRAN.

FLOOR & ROOF PLANS EXPAND ELECTRICAL DISTRIBUTION

LAKE CITY, FLORIDA

573A4-18-601

JF RA

JENNIFER FONG AR97191

AD100

APRIL 28, 2022 16

N 1/4" = 1'-0"1

BUILDING 84 DEMO TRAN. & ELEC.

ROOMS FLOOR PLAN

SHEET KEYNOTES

1/4" = 1'-0"2

BUILDING 84 DEMO TRAN. & ELEC.

ROOMS ROOF PLAN

D1 REMOVE DOOR, FRAMES AND HARDWARE, REFER

TO DOOR SCHEDULE.

D3 REMOVE EXISTING GENERATOR AND METAL BASE

FRAME.

D4 REMOVE LOUVER/WINDOW, GLAZING, FRAMING

AND INFILL OPENING, REFER TO INFILL OPENING

DETAILS.

D5 REMOVE FUEL TANK, PIPING, STEEL LADDER,

PLATFORM, METAL FENCE AND BOLLARDS. CAP

PIPING AS NECESSARY FOR NEW CONSTRUCTION.

D6 RELOCATE EXISTING HEAT PUMP UNIT TO THE

ROOF, REFER TO NEW LAYOUT FOR NEW

LOCATION FOR THE HEAT PUMP.

D9 REMOVE FLUE STACKS AND EXHAUST FANS,

BLOCK OFF VENTS PENETRATIONS, EXISTING

ROOF CURBS TO REMAIN.

D10 REPLACE ENTIRE ROOFING SYSTEM, NEW ROOF TO

MATCH EXISTING ROOFING ASSEMBLY, ROOF

DRAINS TO REMAIN.

D11 REMOVE PARKING SPACES, CURBS AND

MODIFYING SITE WORK, REFER TO CIVIL

DRAWINGS.

D14 REMOVE AND RELOCATE FIRE EXTINGUSHIER

CABINET. REFER TO ARCHITECTURAL FLOOR

PLANS.

D15 DEMOLISH CONCRETE PLATFORM WITH STEPS AND

METAL HANDRAIL.

D16 EXISTING HVAC UNIT TO REMAIN, NO CHANGE.

D17 EXISTING CONCRETE PAD TO REMAIN.

D20 REMOVE EXISTING CONCRETE PAD.

D23 REMOVE EXISTING VCT AND CERAMIC TILES/CLEAN

THE FLOOR AND PAINT WITH CLEAR CONCRETE

SEALANT.

Date: 2022.04.29 09:02:44-04'00'

D18

D18

D18

D18

D17

D6

D19D18

D1

D1

D1 D8

D7

D4

D4

D4

TOILET STAFF

A127

LACTATION

ROOM

A130

WAITING ROOM

A125

CORRIDOR

C1-6

DENTAL CLINIC

A132

RECEPTION

A138

X-RAY

A141

OFFICE

A141A

OPERATORY #7

A145

OPERATORY #6

A147

OPERATORY #5

A149

BREAKROOM

A151A

ESCORT SERVICE

A131

W

U

X

D20

D16

TRANSFORMER

ROOM

D23

D19D19

D12D12

W

U

X

D24

D24

D24

D24

DEMOLITION PLAN NOTES

1. SCREENED LINES AND PATTERNS INDICATE

EXISTING ELEMENTS TO REMAIN. HEAVY/DASHED

LINES INDICATE EXISTING ELEMENTS TO BE

REMOVED.

2. MAINTAIN CONSTRUCTION AREA UNDER NEGATIVE

PRESSURE RELATIVE TO ADJACENT OCCUPIED

AREAS. SEE SPECIFICATIONS FOR ADDITIONAL

INFECTION CONTROL REQUIREMENTS.

3. REMOVE EXISTING DEVICES AS SHOWN ON

ELECTRICAL AND MECHANICAL DRAWINGS. REPAIR

AND FINISH WALLS WHERE DEVICES ARE REMOVED.

4. REPLACE, REPAIR, AND EXTEND EXISTING

ELEMENTS (INCLUDING WALLS AND WALL FINISHES,

FLOORS AND FLOOR FINISHES, AND CEILINGS AND

CEILING FINISHES) IN AREAS OF WORK TO PROVIDE

INCONSPICUOUS TRANSITION BETWEEN EXISTING

AND NEW ELEMENTS.

5. SEQUENCE WORK AND PROVIDE TEMPORARY

PROTECTIVE MEASURES TO PROTECT THE EXISTING

BUILDING MATERIALS AND INTERIOR FROM THE

ELEMENTS; INCLUDING TEMPERATURE, WIND, AND

PRECIPITATON.

6. AFTER THE EXPANSION AREA IS DRIED-IN,

CONSTRUCT SOFT CONSTRUCTION BARRIERS

SHOWN IN CIVIL DRAWINGS, FOLLOWED BY NEW

PERIMETER PARTITIONS AND DOORS (NOTED WITH

AN * BY THE PARTITION TYPE TAG ON THE FLOOR

PLANS) TO SERVE AS A CONSTRUCTION BARRIER

FOR THE REMAINDER OF THE CONSTRUCTION

DURATION. COMPLY WITH VA'S INFECTION CONTROL

PLAN. SEE SAFETY REQUIREMENTS SPECIFICATION

FOR ADDITIONAL MEASURES REQUIRED.

PMR STORAGE

AB10

PATIENT

CLOTHING ROOM

AB11

D2D2

W

U

3733 39

D12

W

U

3733 39

D12

3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124 Fax: (352) 553-4437

COA: FL #29758

AKEA Design Proj. No. AD160-18

Design, Inc.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT / ENGINEER OF RECORDCONSULTANT

321 4 5 6 7 8 9 10

OF

FL. REG. NO.ARCHITECT-OF-RECORD

FINAL BID DOCUMENTS

APPROVED FOR CONSTRUCTION

Revisions: Date:

FINAL BID DOCUMENTS

THIS DOCUMENT CONTAINS A DIGITAL SIGNATURE AND

SEAL BY THE INDIVIDUAL NAMED AT RIGHT. PRINTED

COPIES OF THIS DOCUMENT ARE NOT CONSIDERED

SIGNED AND SEALED, AND THE DIGITAL SIGNATURE

MUST BE VERIFIED ON ANY ELECTRONIC COPIES.

4/

/2

3:

:2

PM

BLDGS. 64 & 86 DEMO

BASEMENT, 1ST FLOOR PLAN &

RCP

EXPAND ELECTRICAL DISTRIBUTION

LAKE CITY, FLORIDA

573A4-18-601

JF RA

JENNIFER FONG AR97191

AD101

APRIL 28, 2022 17

N

SHEET KEYNOTES

1/4" = 1'-0"1

BUILDINGS 86 & 64

DEMO 1ST FLOOR PLAN (+186'-2")

1/4" = 1'-0"2

BUILDING 64 & 86 DEMO 1ST FLOOR

REFLECTED CEILING PLAN

D1 REMOVE DOOR, FRAMES AND HARDWARE, REFER

TO DOOR SCHEDULE.

D2 REMOVE WALL CONSTRUCTION.

D4 REMOVE LOUVER/WINDOW, GLAZING, FRAMING

AND INFILL OPENING, REFER TO INFILL OPENING

DETAILS.

D6 RELOCATE EXISTING HEAT PUMP UNIT TO THE

ROOF, REFER TO NEW LAYOUT FOR NEW

LOCATION FOR THE HEAT PUMP.

D7 REMOVE CONCRETE AIRWELL AND METAL GRATE,

BACKFILL PER STRUCTURAL.

D8 EXISTING LOUVER WILL BE FULLY RELOCATED AT

THE NEW FRONT WALL, REFER TO NEW LAYOUT

SHEET #AE201.

D12 REMOVE CEILING GRID, CEILNIG TILES, SOFFIT,

LIGHT FIXTURES, HVAC DIFFUSERS, REFER TO MEP

DRAWINGS.

D16 EXISTING HVAC UNIT TO REMAIN, NO CHANGE.

D17 EXISTING CONCRETE PAD TO REMAIN.

D18 EXISTING STRUCTURAL COL. TO REMAIN, NO

CHANGE.

D19 EXISTING CEILING, ACCESS PANELS, LIGHT

FIXTURES AND MEP TO REMAIN.

D20 REMOVE EXISTING CONCRETE PAD.

D23 REMOVE EXISTING VCT AND CERAMIC TILES/CLEAN

THE FLOOR AND PAINT WITH CLEAR CONCRETE

SEALANT.

D24 RELOCATE EXISTING CEILING LIGHT FIXTURES,

REFER TO NEW CEILING LAYOUT.

1/4" = 1'-0"3

BUILDING 64 DEMO

BASEMENT FLOOR PLAN

1/4" = 1'-0"5

BUILDING 64 DEMO BASEMENT FLOOR

REFLECTED CEILING PLAN

Date: 2022.04.29 09:00:24-04'00'

FWC FWC

N

N

N

FWC FWCFWC FWC

D10D10

OFFICE

A236

CLEAN UTILITY

A256

SEMI-PRIVATE

ROOM

A258

BATH

A258A

BATH

A261A

PRIVATE ROOM

A261

OFFICE

PHARMACY

A237

W

U

X

D1

D2

D21D21

3' - 9"7' - 6"

INFUSION CLINIC

A239

D16

D23

DEMOLITION PLAN NOTES

1. SCREENED LINES AND PATTERNS INDICATE

EXISTING ELEMENTS TO REMAIN. HEAVY/DASHED

LINES INDICATE EXISTING ELEMENTS TO BE

REMOVED.

2. MAINTAIN CONSTRUCTION AREA UNDER NEGATIVE

PRESSURE RELATIVE TO ADJACENT OCCUPIED

AREAS. SEE SPECIFICATIONS FOR ADDITIONAL

INFECTION CONTROL REQUIREMENTS.

3. REMOVE EXISTING DEVICES AS SHOWN ON

ELECTRICAL AND MECHANICAL DRAWINGS. REPAIR

AND FINISH WALLS WHERE DEVICES ARE REMOVED.

4. REPLACE, REPAIR, AND EXTEND EXISTING

ELEMENTS (INCLUDING WALLS AND WALL FINISHES,

FLOORS AND FLOOR FINISHES, AND CEILINGS AND

CEILING FINISHES) IN AREAS OF WORK TO PROVIDE

INCONSPICUOUS TRANSITION BETWEEN EXISTING

AND NEW ELEMENTS.

5. SEQUENCE WORK AND PROVIDE TEMPORARY

PROTECTIVE MEASURES TO PROTECT THE EXISTING

BUILDING MATERIALS AND INTERIOR FROM THE

ELEMENTS; INCLUDING TEMPERATURE, WIND, AND

PRECIPITATON.

6. AFTER THE EXPANSION AREA IS DRIED-IN,

CONSTRUCT SOFT CONSTRUCTION BARRIERS

SHOWN IN CIVIL DRAWINGS, FOLLOWED BY NEW

PERIMETER PARTITIONS AND DOORS (NOTED WITH

AN * BY THE PARTITION TYPE TAG ON THE FLOOR

PLANS) TO SERVE AS A CONSTRUCTION BARRIER

FOR THE REMAINDER OF THE CONSTRUCTION

DURATION. COMPLY WITH VA'S INFECTION CONTROL

PLAN. SEE SAFETY REQUIREMENTS SPECIFICATION

FOR ADDITIONAL MEASURES REQUIRED.

D2 D13D1 D13

OFFICE - SOCIAL

WORKER

A333

CORRIDOR

C3-5

CLEAN UTILITY

A352

EQUIPMENT

ALCOVE

A337

PRIVATE

HOSPICE CARE

A354

D1

D2

D2

D2

D2

SERENITY PLACE

FAMILY ROOM

A334

SEMI-PRIVATE

HOSPIC CARE

A336A

W

U

3733 39

4' - 9" 7' - 6"

D16

D23

D23

D1

D13

OFFICE

A423

H.A.C.

A427

SUPPLY ROOM

A442

BATH

A446A

PANTRY

A445

EXAM ROOM

A446

D2

OPHTHALMOLOGY/

SURGERY PRE-OP

A424B

POD SURGICAL

COORDINATOR

A426

NURSE

FACILITATOR

A426A

STAFF

UROLOGIST -

UROLOGY

A424

W

U

3733 39

4' - 0" 3' - 3"

D16

D23

D8

D12D12

W

U

D12D12

D12D12

W

U

3733 39

D12D12

W

U

3733 39

3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124 Fax: (352) 553-4437

COA: FL #29758

AKEA Design Proj. No. AD160-18

Design, Inc.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT / ENGINEER OF RECORDCONSULTANT

321 4 5 6 7 8 9 10

OF

FL. REG. NO.ARCHITECT-OF-RECORD

FINAL BID DOCUMENTS

APPROVED FOR CONSTRUCTION

Revisions: Date:

FINAL BID DOCUMENTS

THIS DOCUMENT CONTAINS A DIGITAL SIGNATURE AND

SEAL BY THE INDIVIDUAL NAMED AT RIGHT. PRINTED

COPIES OF THIS DOCUMENT ARE NOT CONSIDERED

SIGNED AND SEALED, AND THE DIGITAL SIGNATURE

MUST BE VERIFIED ON ANY ELECTRONIC COPIES.

4/

/2

3:

:2

PM

BLDGS 64 & 86 DEMOLITION

2ND, 3RD & 4TH FLOORS PLAN EXPAND ELECTRICAL DISTRIBUTION

LAKE CITY, FLORIDA

573A4-18-601

JF RA

JENNIFER FONG AR97191

AD102

APRIL 28, 2022 18

SHEET KEYNOTES

N

1/4" = 1'-0"1 BLDG. 64 DEMO 2ND FLOOR

D1 REMOVE DOOR, FRAMES AND HARDWARE, REFER

TO DOOR SCHEDULE.

D2 REMOVE WALL CONSTRUCTION.

D8 EXISTING LOUVER WILL BE FULLY RELOCATED AT

THE NEW FRONT WALL, REFER TO NEW LAYOUT

SHEET #AE201.

D10 REPLACE ENTIRE ROOFING SYSTEM, NEW ROOF TO

MATCH EXISTING ROOFING ASSEMBLY, ROOF

DRAINS TO REMAIN.

D12 REMOVE CEILING GRID, CEILNIG TILES, SOFFIT,

LIGHT FIXTURES, HVAC DIFFUSERS, REFER TO MEP

DRAWINGS.

D13 REMOVE PLUMBING FIXTURES AND ACCESSORIES

CAP TO RECEIVE NEW FINISHES.

D16 EXISTING HVAC UNIT TO REMAIN, NO CHANGE.

D21 EXISTING EXHAUST FAN TO REMAIN, NO CHANGE.

D23 REMOVE EXISTING VCT AND CERAMIC TILES/CLEAN

THE FLOOR AND PAINT WITH CLEAR CONCRETE

SEALANT.

1/4" = 1'-0"2 BLDG. 64 DEMO 3RD FLOOR

1/4" = 1'-0"3 BLDG. 64 DEMO 4TH FLOOR

1/4" = 1'-0"5

BUILDING 64 DEMO 2ND FLOOR

REFLECTED CEILING PLAN

1/4" = 1'-0"6

BUILDING 64 DEMO 3RD FLOOR

REFLECTED CEILING PLAN

1/4" = 1'-0"7

BUILDING 64 DEMO 4TH FLOOR

REFLECTED CEILING PLAN

Date: 2022.04.29 09:02:09-04'00'

AE3013

AE301

AE302

30' - 0"

6'

8"

AE303

AE302

A6

SWITCHGEAR

A188

EMERGENCY

ELEC ROOM

A187

A2

A5

A7

ALIGN

ALIGN

A302

Sim

A302

Sim

A6A6A6A6A6

A6

6' - 4" 6' - 4" 6' - 4" 6' - 4" 6' - 4"

3'

0" 5'

0"

5'

0"

2'

6"

A15

4' - 0"

4'

6" 1'

0"

1'

0"

NEW CONC.

LANDING, STAIR &

METAL HANDRAIL

AE200

AE302

AE302

A5

A4A4

RELOCATED EXISTING

HEAT PUMP

EXISTING ROOF

SCUPPER TO REMAIN.

1. DIMENSIONS ARE TO: THE FACE OF FINISH OF

PARTITIONS, EXISTING ELEMENTS, EQUIPMENT,

MASONRY, OR CONCRETE; STRUCTURAL GRIDS;

AND CLEAR JAMB OPENING OF DOORS.

2. FIELD VERIFY ACTUAL CONDITIONS AND

DIMENSIONS TO EXISTING ELEMENTS. NOTIFY

ARCHITECT OF DISCREPANCIES AND

UNDOCUMENTED CONDITIONS THAT CONFLICT

WITH NEW WORK.

3. SEE A702 FOR TYPICAL FRAMING DETAILS

INCLUDING WALL PRIORITY AT PARTITION

INTERSECTIONS. SEE A302 FOR TYPICAL FRAMING

AT FIREPROOFED COLUMNS.

4. REFER TO MEP DRAWINGS FOR THE ELECTRICAL

AND MECHANICAL EQUIPMENT.

5. REFER TO STRUCTURAL DRAWINGS FOR THE

EXACT LOCATION OF COLUMNS, BEAMS AND

FRAMING SYSTEM.

LEGEND

FLOOR PLAN NOTES

DOOR OPENING 122

DOOR OPENING MARK

PARTITION TYPE IDENTIFICATION

SEE A701A3A

FEC

FIRE EXTINGUISHER

CABINET

ASTERISK INDICATES PARTITION TO

CONSTRUCT AT START OF

PROJECT - SEE DEMOLITION NOTES

ROOM NAMEROOM NAME

101 ROOM NUMBER

EXPANSION CONTROL JOINT CODES

EJ# - EXPANSION JOINT COVER

SEE DETAILS ON A501. NUMBERS ARE CODED TO JOINT

TYPE. FOR RATED JOINTS, PROVIDE CONTINUOUS

JOINT ASSEMBLY BETWEEN NEW AND EXISTING

CONSTRUCTION INCLUDING INSIDE AND OUTSIDE

CORNER TRANSITIONS AND JOINTS THROUGH

CONCEALED SPACES.

INDICATES AREA OF MINIMAL OR NO

CHANGES

BLOCKING IN GWB DRYWALL. ELEC ROOMS

GC. TO PROVIDE BLOCKING IN THE WALLS WHERE THE

ELECTRICAL PANELS WILL PLACED ON THE WALLS AS

REQUIRED.

SHEET KEYNOTES

1 HR FIRE RATED WALL

2 HR FIRE RATED WALL

INTERIOR ROOM SIGNS

NEW ROOM SIGNS TO MATCH EXISTING. GC TO FOLLOW VA

INSTRUCTIONS FOR INTERIOR ROOMSIGNS STANDARD.

BLDG84 FLR ELEV

174' - 8"

0'

7"

0'

7"0'

7"

2'

4' - 6"

1' - 0" 1' - 0"

CONC. LANDING

& STAIR

METAL

HANDRAIL

3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124 Fax: (352) 553-4437

COA: FL #29758

AKEA Design Proj. No. AD160-18

Design, Inc.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT / ENGINEER OF RECORDCONSULTANT

321 4 5 6 7 8 9 10

OF

FL. REG. NO.ARCHITECT-OF-RECORD

FINAL BID DOCUMENTS

APPROVED FOR CONSTRUCTION

Revisions: Date:

FINAL BID DOCUMENTS

THIS DOCUMENT CONTAINS A DIGITAL SIGNATURE AND

SEAL BY THE INDIVIDUAL NAMED AT RIGHT. PRINTED

COPIES OF THIS DOCUMENT ARE NOT CONSIDERED

SIGNED AND SEALED, AND THE DIGITAL SIGNATURE

MUST BE VERIFIED ON ANY ELECTRONIC COPIES.

4/

/2

3:

:2

PM

BUILDING 84 PROPOSED TRAN. &

ELEC FLOOR & ROOF PLANS EXPAND ELECTRICAL DISTRIBUTION

LAKE CITY, FLORIDA

573A4-18-601

JF RA

JENNIFER FONG AR97191

AE200

APRIL 28, 2022 19

1/4" = 1'-0"1

BUILDING 84 PROP TRAN. & ELEC.

ROOMS FLOOR PLAN

N

A1 NEW FIRE RATED WALL CONSTRUCTION, REFER TO

WALL TYPES.

A2 NEW FIRE RATED DOOR, FRAMES AND HARDWARE,

REFER TO DOOR SCHEDULE.

A3 NEW SCUPPER, CONDUCTOR HEAD AND

DOWNSPOUT, REFER TO ROOFING DETAILS.

A4 NEW ROOF ASSEMBLY SYSTEM, REFER TO

ROOFING DETAILS.

A5 NEW HVAC EQUIPMENT, REFER TO HVAC

DRAWINGS.

A6 NEW STEEL BOLLARD.

A7 NEW CONCRETE PAD, REFER TO STRUCTURAL

DRAWINGS.

A12 NEW LIGHT FIXTURES, REFER TO ELECTRICAL

DRAWINGS.

A14 EXISTING RELOCATED LOUVER.

A15 INSTALL NEW FIRE EXTINGUISHER TYPE C.

1/4" = 1'-0"3 BUILDING 84 PROP ROOF PLAN

1/4" = 1'-0"4 LANDING & STAIR SECTION_BLDG 84

Date: 2022.04.29 08:46:09-04'00'

AE302

AE301 2

AE302

AE302

ELEC ROOM 1A

A186

AE301

A1

26' - 7 1/2"

ALIGN

ALIGN

B6M

A302

A302

Sim

ALIGN

A302

Sim

A302

Sim

A302

Sim

AE303

37.8

A302

Sim

A1

Z

Y

35.1

21' - 0"

Z.1

5'

6"

5'

4"

27' - 9"

189a

A2

A2

A1

A1

4"

X.5

8'

9"

1' - 1 5/8"9"

EES ROOM

A184

NEW

SUBSTATION

A185

6' - 0"

0'

6"

1/

2" 1'

1/ 2"

1' - 1 5/8" 26' - 7 3/8"

A302

Sim

A1

ELEC. CLOSET-1B

A189 DENTAL CLINIC

A132LACTATION

ROOM

A130

TOILET STAFF

A127

CORRIDOR

C1-7

RECEPTION

A138

X-RAY

A141

OFFICE

A141A

OPERATORY #7

A145

OPERATORY #6

A147

OPERATORY #5

A149

BREAKROOM

A151A

WAITING ROOM

A125

4' - 3 1/2" 7' - 0" 15' - 4"

28' - 10 1/2"

4' - 3 1/2" 7' - 0" 15' - 4"

8" 5' - 10" 8' - 9 3/4"

A14

CORRIDOR

C1-6

W

U

X

A5

A15

A15

A15

A501

Sim

A1

L1

A6K A6K

2' - 4"

1'

9"

A6K

3837.8

Z

Y

35.1

Z.1

X.5

A12

A12

A12

A12

A12

W

U

X

A12

A12

A12 A12

A12

ELEC. CLOSET-1B

A189

A12

A12

A12

A12

1. DIMENSIONS ARE TO: THE FACE OF FINISH OF

PARTITIONS, EXISTING ELEMENTS, EQUIPMENT,

MASONRY, OR CONCRETE; STRUCTURAL GRIDS;

AND CLEAR JAMB OPENING OF DOORS.

2. FIELD VERIFY ACTUAL CONDITIONS AND

DIMENSIONS TO EXISTING ELEMENTS. NOTIFY

ARCHITECT OF DISCREPANCIES AND

UNDOCUMENTED CONDITIONS THAT CONFLICT

WITH NEW WORK.

3. SEE A702 FOR TYPICAL FRAMING DETAILS

INCLUDING WALL PRIORITY AT PARTITION

INTERSECTIONS. SEE A302 FOR TYPICAL FRAMING

AT FIREPROOFED COLUMNS.

4. REFER TO MEP DRAWINGS FOR THE ELECTRICAL

AND MECHANICAL EQUIPMENT.

5. REFER TO STRUCTURAL DRAWINGS FOR THE

EXACT LOCATION OF COLUMNS, BEAMS AND

FRAMING SYSTEM.

LEGEND

FLOOR PLAN NOTES

DOOR OPENING 122

DOOR OPENING MARK

PARTITION TYPE IDENTIFICATION

SEE A701A3A

FEC

FIRE EXTINGUISHER

CABINET

ASTERISK INDICATES PARTITION TO

CONSTRUCT AT START OF

PROJECT - SEE DEMOLITION NOTES

ROOM NAMEROOM NAME

101 ROOM NUMBER

EXPANSION CONTROL JOINT CODES

EJ# - EXPANSION JOINT COVER

SEE DETAILS ON A501. NUMBERS ARE CODED TO JOINT

TYPE. FOR RATED JOINTS, PROVIDE CONTINUOUS

JOINT ASSEMBLY BETWEEN NEW AND EXISTING

CONSTRUCTION INCLUDING INSIDE AND OUTSIDE

CORNER TRANSITIONS AND JOINTS THROUGH

CONCEALED SPACES.

INDICATES AREA OF MINIMAL OR NO

CHANGES

BLOCKING IN GWB DRYWALL. ELEC ROOMS

GC. TO PROVIDE BLOCKING IN THE WALLS WHERE THE

ELECTRICAL PANELS WILL PLACED ON THE WALLS AS

REQUIRED.

SHEET KEYNOTES

1 HR FIRE RATED WALL

2 HR FIRE RATED WALL

INTERIOR ROOM SIGNS

NEW ROOM SIGNS TO MATCH EXISTING. GC TO FOLLOW VA

INSTRUCTIONS FOR INTERIOR ROOMSIGNS STANDARD.

PATIENT

CLOTHING ROOM

AB44

CLOTHING

STORAGE

AB11A

OFFICE

AB09A

CORRIDOR

A1

W

U

X

33 39

ELEC. CLOSET-B

AB10 A6K

A15

A703

Sim

A703

Sim

W

U

3733 39

ELEC CLOSET-B

AB10

3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124 Fax: (352) 553-4437

COA: FL #29758

AKEA Design Proj. No. AD160-18

Design, Inc.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT / ENGINEER OF RECORDCONSULTANT

321 4 5 6 7 8 9 10

OF

FL. REG. NO.ARCHITECT-OF-RECORD

FINAL BID DOCUMENTS

APPROVED FOR CONSTRUCTION

Revisions: Date:

FINAL BID DOCUMENTS

THIS DOCUMENT CONTAINS A DIGITAL SIGNATURE AND

SEAL BY THE INDIVIDUAL NAMED AT RIGHT. PRINTED

COPIES OF THIS DOCUMENT ARE NOT CONSIDERED

SIGNED AND SEALED, AND THE DIGITAL SIGNATURE

MUST BE VERIFIED ON ANY ELECTRONIC COPIES.

4/

/2

3:

:2

PM

BLDGS. 64 & 86 PROP BASEMENT

FLOOR, 1ST FLOOR & RCP PLANS EXPAND ELECTRICAL DISTRIBUTION

LAKE CITY, FLORIDA

573A4-18-601

JF RA

JENNIFER FONG AR97191

AE201

APRIL 28, 2022 20

1/4" = 1'-0"1

BLDGS. 64 & 86 PROPOSED

1ST FLOOR PLANS

N 1/4" = 1'-0"3

BLDGS. 64 & 86 PROP 1ST FLOOR

REFLECTED CEILING PLAN

A1 NEW FIRE RATED WALL CONSTRUCTION, REFER TO

WALL TYPES.

A2 NEW FIRE RATED DOOR, FRAMES AND HARDWARE,

REFER TO DOOR SCHEDULE.

A3 NEW SCUPPER, CONDUCTOR HEAD AND

DOWNSPOUT, REFER TO ROOFING DETAILS.

A4 NEW ROOF ASSEMBLY SYSTEM, REFER TO

ROOFING DETAILS.

A5 NEW HVAC EQUIPMENT, REFER TO HVAC

DRAWINGS.

A6 NEW STEEL BOLLARD.

A7 NEW CONCRETE PAD, REFER TO STRUCTURAL

DRAWINGS.

A12 NEW LIGHT FIXTURES, REFER TO ELECTRICAL

DRAWINGS.

A14 EXISTING RELOCATED LOUVER.

A15 INSTALL NEW FIRE EXTINGUISHER TYPE C.

1/4" = 1'-0"4

BLDG. 86 PROPOSED

BASEMENT FLOOR PLAN

1/4" = 1'-0"5

BUILDING 64 PROP BASEMENT FLOOR

REFLECTED CEILING PLAN

Date: 2022.04.29 08:47:42-04'00'

ROOF SLOPE 1/4"=12"

R O

O F

SL

O

PE

/4

A302

3835.1

ROOF SLOPE 1/4"=12"

R O

O F

SL

O

PE

/4

ROOF SLOPE 1/4"=12"

ROOF SLOPE 1/4"=12"

REPLACE ENTIRE ROOFING

SYSTEM, NEW ROOF TO MATCH

EXISTING ROOFING ASSEMBLY,

ROOF DRAINS TO REMAIN.

CORRIDOR

C2-5

OFFICE

A236

CLEAN UTILITY

A256

SEMI-PRIVATE

ROOM

A258

BATH

A258A

BATH

A261A

PRIVATE ROOM

A261

BATH

A264B

ANTE ROOM

A264

ISOLATION /

PRIVATE ROOM

A264A

ELEC. CLOSET-2

A238

W

U

X

A2

A4

A1

A2

OFFICE/PHARMACY

A237

238 237

INFUSION CLINIC

A239

A5

A5

A3

A3

RELOCATED EXISTING

HEAT PUMP

A6K

A6K

1. DIMENSIONS ARE TO: THE FACE OF FINISH OF

PARTITIONS, EXISTING ELEMENTS, EQUIPMENT,

MASONRY, OR CONCRETE; STRUCTURAL GRIDS;

AND CLEAR JAMB OPENING OF DOORS.

2. FIELD VERIFY ACTUAL CONDITIONS AND

DIMENSIONS TO EXISTING ELEMENTS. NOTIFY

ARCHITECT OF DISCREPANCIES AND

UNDOCUMENTED CONDITIONS THAT CONFLICT

WITH NEW WORK.

3. SEE A702 FOR TYPICAL FRAMING DETAILS

INCLUDING WALL PRIORITY AT PARTITION

INTERSECTIONS. SEE A302 FOR TYPICAL FRAMING

AT FIREPROOFED COLUMNS.

4. REFER TO MEP DRAWINGS FOR THE ELECTRICAL

AND MECHANICAL EQUIPMENT.

5. REFER TO STRUCTURAL DRAWINGS FOR THE

EXACT LOCATION OF COLUMNS, BEAMS AND

FRAMING SYSTEM.

LEGEND

FLOOR PLAN NOTES

DOOR OPENING 122

DOOR OPENING MARK

PARTITION TYPE IDENTIFICATION

SEE A701A3A

FEC

FIRE EXTINGUISHER

CABINET

ASTERISK INDICATES PARTITION TO

CONSTRUCT AT START OF

PROJECT - SEE DEMOLITION NOTES

ROOM NAMEROOM NAME

101 ROOM NUMBER

EXPANSION CONTROL JOINT CODES

EJ# - EXPANSION JOINT COVER

SEE DETAILS ON A501. NUMBERS ARE CODED TO JOINT

TYPE. FOR RATED JOINTS, PROVIDE CONTINUOUS

JOINT ASSEMBLY BETWEEN NEW AND EXISTING

CONSTRUCTION INCLUDING INSIDE AND OUTSIDE

CORNER TRANSITIONS AND JOINTS THROUGH

CONCEALED SPACES.

INDICATES AREA OF MINIMAL OR NO

CHANGES

BLOCKING IN GWB DRYWALL. ELEC ROOMS

GC. TO PROVIDE BLOCKING IN THE WALLS WHERE THE

ELECTRICAL PANELS WILL PLACED ON THE WALLS AS

REQUIRED.

SHEET KEYNOTES

1 HR FIRE RATED WALL

2 HR FIRE RATED WALL

INTERIOR ROOM SIGNS

NEW ROOM SIGNS TO MATCH EXISTING. GC TO FOLLOW VA

INSTRUCTIONS FOR INTERIOR ROOMSIGNS STANDARD.

W

U

X

33 39

ELEC. CLOSET-2

A238

A12

A12

A12

3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124 Fax: (352) 553-4437

COA: FL #29758

AKEA Design Proj. No. AD160-18

Design, Inc.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT / ENGINEER OF RECORDCONSULTANT

321 4 5 6 7 8 9 10

OF

FL. REG. NO.ARCHITECT-OF-RECORD

FINAL BID DOCUMENTS

APPROVED FOR CONSTRUCTION

Revisions: Date:

FINAL BID DOCUMENTS

THIS DOCUMENT CONTAINS A DIGITAL SIGNATURE AND

SEAL BY THE INDIVIDUAL NAMED AT RIGHT. PRINTED

COPIES OF THIS DOCUMENT ARE NOT CONSIDERED

SIGNED AND SEALED, AND THE DIGITAL SIGNATURE

MUST BE VERIFIED ON ANY ELECTRONIC COPIES.

4/

/2

3:

:3

PM

BLDGS 64 & 86 PROPOSED

2ND FLOOR & ROOF PLAN & RCP EXPAND ELECTRICAL DISTRIBUTION

LAKE CITY, FLORIDA

573A4-18-601

JF RA

JENNIFER FONG AR97191

AE202

APRIL 28, 2022 21

1/4" = 1'-0"1

BLDG. 64 PROP FLOOR PLAN

& 86 PROP ROOF PLAN

A1 NEW FIRE RATED WALL CONSTRUCTION, REFER TO

WALL TYPES.

A2 NEW FIRE RATED DOOR, FRAMES AND HARDWARE,

REFER TO DOOR SCHEDULE.

A3 NEW SCUPPER, CONDUCTOR HEAD AND

DOWNSPOUT, REFER TO ROOFING DETAILS.

A4 NEW ROOF ASSEMBLY SYSTEM, REFER TO

ROOFING DETAILS.

A5 NEW HVAC EQUIPMENT, REFER TO HVAC

DRAWINGS.

A6 NEW STEEL BOLLARD.

A7 NEW CONCRETE PAD, REFER TO STRUCTURAL

DRAWINGS.

A12 NEW LIGHT FIXTURES, REFER TO ELECTRICAL

DRAWINGS.

A14 EXISTING RELOCATED LOUVER.

A15 INSTALL NEW FIRE EXTINGUISHER TYPE C.

N

1/4" = 1'-0"2

BUILDING 64 PROP

REFLECTED CEILING PLAN - 2ND FLOOR

Date: 2022.04.29 08:59:51-04'00'

FWC FWCFWC FWC

1. DIMENSIONS ARE TO: THE FACE OF FINISH OF

PARTITIONS, EXISTING ELEMENTS, EQUIPMENT,

MASONRY, OR CONCRETE; STRUCTURAL GRIDS;

AND CLEAR JAMB OPENING OF DOORS.

2. FIELD VERIFY ACTUAL CONDITIONS AND

DIMENSIONS TO EXISTING ELEMENTS. NOTIFY

ARCHITECT OF DISCREPANCIES AND

UNDOCUMENTED CONDITIONS THAT CONFLICT

WITH NEW WORK.

3. SEE A702 FOR TYPICAL FRAMING DETAILS

INCLUDING WALL PRIORITY AT PARTITION

INTERSECTIONS. SEE A302 FOR TYPICAL FRAMING

AT FIREPROOFED COLUMNS.

4. REFER TO MEP DRAWINGS FOR THE ELECTRICAL

AND MECHANICAL EQUIPMENT.

5. REFER TO STRUCTURAL DRAWINGS FOR THE

EXACT LOCATION OF COLUMNS, BEAMS AND

FRAMING SYSTEM.

LEGEND

FLOOR PLAN NOTES

DOOR OPENING 122

DOOR OPENING MARK

PARTITION TYPE IDENTIFICATION

SEE A701A3A

FEC

FIRE EXTINGUISHER

CABINET

ASTERISK INDICATES PARTITION TO

CONSTRUCT AT START OF

PROJECT - SEE DEMOLITION NOTES

ROOM NAMEROOM NAME

101 ROOM NUMBER

EXPANSION CONTROL JOINT CODES

EJ# - EXPANSION JOINT COVER

SEE DETAILS ON A501. NUMBERS ARE CODED TO JOINT

TYPE. FOR RATED JOINTS, PROVIDE CONTINUOUS

JOINT ASSEMBLY BETWEEN NEW AND EXISTING

CONSTRUCTION INCLUDING INSIDE AND OUTSIDE

CORNER TRANSITIONS AND JOINTS THROUGH

CONCEALED SPACES.

INDICATES AREA OF MINIMAL OR NO

CHANGES

BLOCKING IN GWB DRYWALL. ELEC ROOMS

GC. TO PROVIDE BLOCKING IN THE WALLS WHERE THE

ELECTRICAL PANELS WILL PLACED ON THE WALLS AS

REQUIRED.

SHEET KEYNOTES

1 HR FIRE RATED WALL

2 HR FIRE RATED WALL

INTERIOR ROOM SIGNS

NEW ROOM SIGNS TO MATCH EXISTING. GC TO FOLLOW VA

INSTRUCTIONS FOR INTERIOR ROOMSIGNS STANDARD.

A302

A6KOFFICE - SOCIAL

WORKER

A333

CORRIDOR

C3-5

CORRIDOR

C3-6

EQUIPMENT

ALCOVE

A337

CLEAN UTILITY

A352

PRIVATE

HOSPICE CARE

A354

WAITING ROOM

A334

ELEC CLOSET-3

A336

W

U

A2 A2

A1

334336

SEMI-PRIVATE

HOSPICE CARE

A240

BATH

A336A

A6K

A12

A12

W

U

3733 39

ELEC. CLOSET-3

A336

A12

A12

A302

A6K

H.A.C.

A427 SUPPLY ROOM

A442

BATH

A446A

PANTRY

A445

EXAM ROOM

A446

ELEC CLOSET-4

A424B

CORRIDOR

C4-6

W

U

A2

A1

424B

OFFICE

A423

POD SURGICAL

COORDINATOR

A426

NURSE

FACILITATOR

A426A

STAFF

UROLOGIST -

UROLOGY

A424

A6K

A12

A12

W

U

3733 39

ELEC. CLOSET-4

A424B

3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124 Fax: (352) 553-4437

COA: FL #29758

AKEA Design Proj. No. AD160-18

Design, Inc.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT / ENGINEER OF RECORDCONSULTANT

321 4 5 6 7 8 9 10

OF

FL. REG. NO.ARCHITECT-OF-RECORD

FINAL BID DOCUMENTS

APPROVED FOR CONSTRUCTION

Revisions: Date:

FINAL BID DOCUMENTS

THIS DOCUMENT CONTAINS A DIGITAL SIGNATURE AND

SEAL BY THE INDIVIDUAL NAMED AT RIGHT. PRINTED

COPIES OF THIS DOCUMENT ARE NOT CONSIDERED

SIGNED AND SEALED, AND THE DIGITAL SIGNATURE

MUST BE VERIFIED ON ANY ELECTRONIC COPIES.

4/

/2

3:

:3

PM

BUILDING 64 PROP 3RD, 4TH

FLRS & REFLECTED CEILING

PLANS

EXPAND ELECTRICAL DISTRIBUTION

LAKE CITY, FLORIDA

573A4-18-601

JF RA

JENNIFER FONG AR97191

AE2…