This document provides technical specifications for a multi-megawatt electrolyzer power supply unit sought by the National Renewable Energy Laboratory on behalf of the Department of Energy. Key requirements include the ability to provide a minimum of 6 megawatts of independently controlled DC power output across three or more hydrogen electrolyzer stacks. The unit must be rated for outdoor use with ambient temperatures ranging from -30 to 40 degrees Celsius and humidity, withstand winds up to 155 mph, and operate at an altitude of 6,040 feet. Quotes should address safety certifications as well as the proposed design, controls, dimensions, installation requirements, efficiency ratings, service plans, production timelines, and pricing.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Page | 1

Attachment 1: Technical Specifications

Multi‐MW Elctrolyzer Power Supply Unit

Objective:

NREL intends to provide the Department of Energy (DOE) and industry with critical RD&D capabilities to accelerate and scale aggressive decarbonization goals for various sector such as steel, cement, transportation (on‐ and off‐road) etc. The procured rectifier will be an integral part of hydrogen research infrastructure and provide a testbed to demonstrate system integration, energy storage, grid services, and renewable hydrogen production. The goal here is to provide testbed to test electrolyzer stacks of up to 6 MW single stack, up to six stacks of 1 MW each, or various combinations in between.

Environmental Conditions:

The system will be primarily used outdoors and is expected to be located at NREL’s Flatirons Campus. The campus is at high altitude and incurs extreme weather. Unique specifications are included below.

Operations may be limited to specified environmental conditions; however, the unit(s) should be environmentally protected for outdoor installation and operation. Other exposures may include high winds and dusty conditions. The unit will need to be protected from lightning strikes.

Environmental conditions

Ambient temperatures: ‐300C to +400C

Humidity: full‐range, outdoor conditions, Arvada, Colorado

Elevation: 6040 ft above sea level

Winds: 155 mph ultimate wind speed

Required Specifications:

Input voltage: 3ph, 480VAC L‐L

Input frequency: 60 Hz +/‐ 5%

Unit shall use site provided 480V AC input without supplying additional transformer (i.e. NREL will provide input transformer) for main power

Total output power: minimum 6 MW

Ability to independently control voltage and current for three or more hydrogen electrolyzer stacks remotely

Output rated voltage greater than or equal to 500V DC

Isolated, floating DC output

DC voltage regulation: <1%

Target power factor: > 0.95

Survival ambient temperature: ‐300C to +400C

Operating ambient temperature: ‐100C to +400C

Protections: Remote interlock, overvoltage, overcurrent (DC output and AC input), overtemperature, short circuit

OSHA approved Nationally Recognized Testing Laboratory (NRTL) approval

Page | 2

Remote data acquisition and control capability

Preferred Capabilities:

Low current turndown –able to maintain high voltage output at low currents down to 5‐10% of rated operating current

Low voltage turndown – able to maintain high rated current at low voltages down to 250 VDC

High slew rate/response time 100ms or better

Outdoor rated, preferably NEMA 4 or NEMA 4X enclosure

Air cooling system

Ability to parallelize and/or serialize the units to achieve broader voltage and current range

Quotes must include:

Description of company’s experience in AC/DC conversion system

Description of technical capabilities of company’s AC/DC conversion system

Thermal management system attributes and maintenance requirements for storage mode during cold conditions

Specifications or design approach supporting installation and use of the unit in outdoor testing environment

Efficiency rating at full load and part load operation

Auxiliary/support power requirements (heaters, fans, telecom gear, etc.); specify if these components require an independent power feed(s).

Control and power module standby power consumption

Physical dimensions, weights, and connection methods of the complete system that aids with installation planning. Please address, o interface drawings and requirements o mounting and foundational requirements o electrical and thermal clearance requirements

Quotes should assume:

Physical installation at NREL site will be responsibility of NREL

Shipment method and costs should be included in cost and delivery timing o NREL’s Flatirons Campus Laboratories and Offices, National Renewable Energy Laboratory

19001 W 119th Ave, Arvada, CO 80007

Quotes should include:

description of company’s past performance and proof of demonstration description of any required persistent or temporary remote connections required for maintenance, operations, or telemetry description of standard operating modes and unique capabilities overload ratings and durations factory checkout testing procedures standards and certifications to which units and system comply production and delivery lead times

Page | 3 safety guidelines and unique features warranty options, ongoing support, license, or other fees

On‐site and remote technical support plan, response times, service, and maintenance contract options