Attach_2_Drawings.pdf
PDF 4 MB Posted
- Attached to
- Install Emergency Cooling Tower Makeup Water Federal contract opportunity
- Solicitation number
- FA252120B0020
About this file
This federal contract opportunity solicitation seeks bids for a firm-fixed price construction contract to install emergency cooling tower makeup water systems at Cape Canaveral Air Force Station. The project scope involves providing all labor, materials, and equipment to drill new wells, install pumping systems, and route water lines to critical facilities per technical specifications. The contract value is estimated between $500,000 to $1,000,000 with a 215-day period of performance. The solicitation is a 100% small business set-aside for NAICS code 237110. The issuing agency is the Department of the Air Force Space Command. Bids are due by the closing date specified in the solicitation.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| WD FL20200001 (04Sep2020).pdf | ||
| 20B0020_Supplemental_Drawings.pdf | ||
| Solicitation Amendment FA252120B00200001 SF 30.pdf | ||
| 20B0020_QandAs.pdf | ||
| Attach_7_45_SFS_Badge_Request_Form.pdf | ||
| Attach_6_DB_WD_FL20200001_(14Aug2020).pdf | ||
| Attach_3__Questions_Template.docx | DOCX document | |
| Attach_5_GPP_Forms.pdf | ||
| Attach_1_Tech_Specs.pdf | ||
| Attach_4_ CECC_Form_3052.xls | XLS spreadsheet | |
| Solicitation - FA252120B0020.pdf |
Show all 11
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
BASE OPERATIONS:
COMMUNICATIONS:
PROJECT MANAGER:
CHIEF, ENGINEERING FLIGHT:
USER:
SAFETY:
SECURITY FORCES:
ATO:
OTHER:
ENVIRONMENTAL:
FIRE:
A P P R O V E D
INSTALL EMERGENCY MAKEUP
WATER FOR CRITICAL FACILITIES
DRAWING INDEX
SHEET NUMBER SHEET TITLE REV
G-001 COVER SHEET
CIVIL
C-001 CIVIL GENERAL NOTES
C-002 ABBREVIATIONS, SYMBOLS, AND SCHEDULES
C-101 MORRELL OPERATIONS CENTER (MOC) - SITE PLAN
C-102 EASTERN PROCESSING FACILITY (EPF) - SITE PLAN
C-103 TECH SUPPORT FACILITY (TSF) - SITE PLAN
C-104 XY COMM BUILDING (XY) - SITE PLAN
C-501 CIVIL DETAILS I
C-502 CIVIL DETAILS II
C-701 PUMP SKID SYSTEM REQUIREMENTS
ELECTRICAL
E-001 ELECTRICAL GENERAL NOTES
E-101 MORRELL OPERATIONS CENTER (MOC) - ELECTRICAL SITE PLAN
E-102 EASTERN PROCESSING FACILITY (EPF) - ELECTRICAL SITE PLAN
E-103 TECH SUPPORT FACILITY (TSF) - ELECTRICAL SITE PLAN
E-104 XY COMM BUILDING (XY) - ELECTRICAL SITE PLAN
PERMIT(S)/ENVIRONMENTAL ACTIONS
REQUIRED PRIOR TO CONSTRUCTION
ERP/STORMWATER
FDEP/DRINKING WATER
FDEP/DOM. WASTE WATER ARCHEO./HISTORICAL
SURVEY/WILDLIFE
OTHER
NONE
FDEP/IND. WASTE WATER
IRP
FDEP/FUEL TANK
NOI/SWPPP
ASBESTOS
NOTE: IF IT IS SUSPECTED THAT ANY HAZARDOUS
MATERIAL NOT IDENTIFIED ON THESE DRAWINGS IS
REQUIRED TO BE DISTURBED IN ORDER TO PERFORM
THE CONTRACT WORK, LEAVE MATERIAL UNDISTURBED
AND IMMEDIATELY INFORM THE CONTRACTING OFFICER.
HEAVY METALS
YES NO
LEAD
PCB
NOT
VERIFIEDHAZARDOUS MATERIALSERP/WETLANDS/ DREDGE
& FILL
DBEH 18-1500
TRUE
NORTH
N
EASTERN PROCESSING
FACILITY (EPF)
LOCATION MAP
SCALE: N.T.S.
NOTE: PROJECT AREA DOES NOT REQUIRE FDEP NPDES PERMIT;
HOWEVER, A SWPPP IS REQUIRED.
MORRELL OPERATIONS
FACILITY (MOC)
TECH SUPPORT
FACILITY (TSF)
XY COMM BUILDING (XY)
A
B
2 3
C
D
1 2 3
4 5 6
AS
B
U
IL
T D
AT
E:
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
R
EV
IE
W
ED
B
Y:
D
AT
E:
4 5
M
AR
K D
ES
C
R
IP
TI
O
N D
AT
E
AP
PR
SHEET
IDENTIFICATION
C
D
A
B
U
SA
F
TH
C
IV
IL
E N
G
IN
EE
R
S Q
U
AD
R O
N , P
AF
B, F L
C O
N
TR
AC
T
N O
FA
-1 8-
D -0
TR
AC
ES
TE
C H
N
IC
AL
R
AN
G
E
AR
C H
IT
EC
T
EN
G
IN
EE
R
IN
G
SE
R
VI
C
ES
D
EL
IV
ER
Y N
O
Ne lso nE ng in ee ri ng Co rh od es b rit o
A
R
C
H
I T
E
S
AA
G-001
C O
VE
R
S H
EE
T
100%
DESIGN REVIEW ONLY
NOT FOR CONSTRUCTION
N
EL
SO
N
EN
G
IN
EE
R
IN
G
-1
2-
M J
O H
N
SO
N
J
TY
SO
N
B H
AR
VE
Y
D
BE
H
8-
XX
XX
XX
-X
X-
XX
D
BE
H
8-
IN
ST
AL
L
EM
ER
G
EN
C Y
M
AK
EU
P
W
AT
ER
F
O R
C R
IT
IC
AL
F
AC
IL
IT
IE
S
CAPE CANAVERAL AIR FORCE STATION
CAPE CANAVERAL, FLORIDA
X X X
XX
B
2 3
C
D
1 2 3
4 5 6
AS
B
U
IL
T D
AT
E:
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
R
EV
IE
W
ED
B
Y:
D
AT
E:
4 5
M
AR
K D
ES
C
R
IP
TI
O
N D
AT
E
AP
PR
SHEET
IDENTIFICATION
C
D
A
B
U
SA
F
TH
C
IV
IL
E N
G
IN
EE
R
S Q
U
AD
R O
N , P
AF
B, F L
C O
N
TR
AC
T
N O
FA
-1 8-
D -0
TR
AC
ES
TE
C H
N
IC
AL
R
AN
G
E
AR
C H
IT
EC
T
EN
G
IN
EE
R
IN
G
SE
R
VI
C
ES
D
EL
IV
ER
Y N
O
Ne lso nE ng in ee ri ng Co rh od es b rit
C-001
C
IV
IL
G
EN
ER
AL
N
O
TE
S
100%
DESIGN REVIEW ONLY
NOT FOR CONSTRUCTION
N
EL
SO
N
EN
G
IN
EE
R
IN
G
-1
2-
M J
O H
N
SO
N
J
TY
SO
N
B H
AR
VE
Y
D
BE
H
8-
XX
XX
XX
-X
X-
XX
D
BE
H
8-
IN
ST
AL
L
EM
ER
G
EN
C Y
M
AK
EU
P
W
AT
ER
F
O R
C R
IT
IC
AL
F
AC
IL
IT
IE
S
CONCRETE:
1. THE LATEST EDITION OF THE FOLLOWING ACI STANDARDS APPLY:
ACI 318 (CODE)
ACI 304 (PLACING)
ACI 306 (WINTER CONCRETE)
ACI 315/SP66 (DETAILING)
ACI 305 (HOT WEATHER CONCRETE)
ACI 347 (FORM WORK)
ACI 211.1 (MIX PROPORTIONING)
2. USE 3,000 PSI, TYPE I OR II, NORMAL WEIGHT, PORTLAND CEMENT CONCRETE.
3. DO NOT USE CALCIUM CHLORIDE IN ANY FORM.
4. SITE ADDED WATER IS PERMITTED PROVIDED MAX WATER TO CEMENT RATIO ARE NOT EXCEEDED; HOWEVER, NOT MORE THAN ONE GALLON OF WATER PER CUBIC YARD MAY BE USED TO ADJUST THE MIX AT THE JOB SITE.
5. CONSOLIDATE ALL CONCRETE, OTHER THAN SLABS ON GRADE USING MECHANICAL VIBRATING EQUIPMENT. DO NOT
OVER-CONSOLIDATE.
7. DO NOT PLACE CONCRETE DURING RAIN OR IF RAIN IS LIKELY TO OCCUR PRIOR TO CONCRETE HARDENING.
CIVIL GENERAL NOTES:
UNLESS OTHERWISE SPECIFIED, ALL WORK TO BE PERFORMED CONSISTENT WITH THE RULES AND REQUIREMENTS OF THE
FOLLOWING:
· CAPE CANAVERAL AIR FORCE STATION, CCAFS
· FLORIDA DEPARTMENT OF HEALTH IN BREVARD COUNTY
1. LOCATIONS, ELEVATIONS, AND DIMENSIONS OF EXISTING UTILITIES, STRUCTURES, AND OTHER FEATURES SHOWN ARE THE BEST INFORMATION AVAILABLE AT THE TIME OF PREPARATION OF THESE PLANS BUT DO NOT PURPORT TO BE ABSOLUTELY CORRECT.
THERE MAY BE OTHER UNKNOWN IMPROVEMENTS, SUCH AS UTILITIES, WHICH ARE WITHIN THE PROJECT AREA. THE CONTRACTOR TO VERIFY, PRIOR TO CONSTRUCTION, THE LOCATIONS, ELEVATIONS, AND DIMENSIONS OF ALL EXISTING UTILITIES, STRUCTURES, AND OTHER FEATURES (WHETHER OR NOT SHOWN ON THE PLANS) AFFECTING THE WORK.
2. CONDUCT A WILDLIFE SURVEY THROUGH 45 CES/CEIE AT LEAST TWO (2) WEEKS PRIOR TO ANY DEMOLITION OR GROUND
EXCAVATION.
3. OBTAIN WELL INSTALLATION PERMITS IN ACCORDANCE WITH SPECIFICATION SECTION 33 11 13.
4. REQUEST UTILITY LOCATES AND OBTAIN A CCAFS DIG PERMIT AF FORM 103 PRIOR TO CONSTRUCTION.
5. FIELD LOCATE ALL EXISTING UTILITIES AS TO SIZE, LOCATION, AND ELEVATION. CONTRACTOR TO NOTIFY THE CONTRACTING OFFICER OF ALL CONFLICTS PRIOR TO BEGINNING CONSTRUCTION. CONTRACTOR TO CONFIRM THE ACCURACY OF ALL SURVEY
AND OTHER GRADING DATA.
6. FIELD CONDITIONS MAY NECESSITATE SLIGHT ALIGNMENT AND GRADE DEVIATION OF THE PROPOSED CONSTRUCTION TO AVOID
OBSTACLES, AS AGREED TO BY THE CONTRACTING OFFICER.
7. WORK THE SCOPE CONTAINED ON THE CIVIL DRAWINGS IN COORDINATION WITH ALL OTHER DISCIPLINES TO LOCATE DEPRESSED SLABS, SLOPES, DRAINS, BOLT SETTINGS, AND GRADES. CALL ANY DISCREPANCIES TO THE ATTENTION OF THE CONTRACTING
OFFICER BEFORE PROCEEDING WITH THE WORK.
8. REVIEW THESE DRAWINGS AND VISIT THE SITE BEFORE CONSTRUCTION BEGINS TO COMPARE ALL EXISTING CONDITIONS TO WHAT IS SHOWN ON THE DRAWINGS. IF THERE ARE VARIANCES, NOTIFY THE CONTRACTING OFFICER.
9. VERIFY ALL EXISTING DIMENSIONS AND CONDITIONS PRIOR TO ORDERING ANY MATERIALS AND NOTIFY THE CONTRACTING
OFFICER IF DIFFERENT FROM WHAT IS SHOWN ON THE DRAWINGS.
10. ALL DETAILS AND SECTIONS SHOWN ON THE DRAWINGS ARE INTENDED TO BE TYPICAL AND CONSTRUED TO APPLY TO ANY SIMILAR SITUATION ELSEWHERE ON THE PROJECT, EXCEPT WHERE A DIFFERENT DETAIL IS SHOWN.
11. SCHEDULE A CONSTRUCTION COORDINATION MEETING WITH THE CONTRACTING OFFICER AND PROJECT STAKEHOLDERS TO REVIEW THE CONSTRUCTION SCHEDULE, CRITICAL MILESTONES AND OUTAGES AND REVIEW/CLARIFY REQUESTS FOR
INFORMATION.
12. SUBMIT SHOP DRAWINGS WITH COORDINATED TRADES TO THE CONTRACTING OFFICER FOR REVIEW AND APPROVAL PRIOR TO
THE START OF CONSTRUCTION.
13. GIVE ALL NOTICES AND COMPLY WITH ALL LAWS, ORDINANCES, RULES, REGULATIONS AND PERMIT CONDITIONS BEARING ON THE CONDUCT OF THE WORK AS DRAWN AND SPECIFIED. IF THE CONTRACTOR OBSERVES THAT THE DRAWINGS AND SPECIFICATIONS ARE AT VARIANCE, NOTIFY THE CONTRACTING OFFICER, IN WRITING, AND ANY NECESSARY CHANGES TO BE ADJUSTED, AS
PROVIDED IN THE AGREEMENT FOR CHANGES IN THE WORK.
14. THE CONTRACTOR IS RESPONSIBLE FOR THE ACTS AND OMISSIONS OF CONTRACTOR EMPLOYEES AND ALL THEIR SUBCONTRACTORS AND THEIR AGENTS AND EMPLOYEES AND OTHER PERSONS PERFORMING ANY OF THE WORK UNDER A
CONTRACT WITH THE CONTRACTOR.
15. IF THE CONTRACTOR DISCOVERS ANY ERRORS OR OMISSIONS IN THE PLANS, IMMEDIATELY NOTIFY THE CONTRACTING OFFICER.
16. PRESERVE AND PROTECT ALL PERMANENT REFERENCE MONUMENTS, PERMANENT CONTROL POINTS, PERMANENT BENCH MARKS AND PROPERTY CORNERS. IF THE MONUMENTS, POINTS OR MARKERS ARE DISTURBED, EMPLOY A FLORIDA REGISTERED LAND
SURVEYOR TO RESET OR REPLACE THEM.
17. THE CONTRACTOR IS RESPONSIBLE FOR MAKING ALL NECESSARY ARRANGEMENTS WITH THE U.S. AIR FORCE, PUBLIC UTILITIES, PUBLIC CARRIERS, SERVICE COMPANIES, AND OTHER AGENCIES HAVING JURISDICTION OWNING OR CONTROLLING ROADWAYS, WATER, SEWER, GAS, ELECTRICAL, AND TELEPHONE SUCH AS PAVEMENTS, PIPING, WIRES, CABLES, CONDUITS, POLES, GUYS OR OTHER SIMILAR FACILITIES, INCLUDING INCIDENTAL STRUCTURES THAT ARE ENCOUNTERED IN THE WORK SUCH THAT ITEMS MAY
BE PROPERLY SUPPORTED, PROTECTED OR LOCATED.
18. THE OWNER, OWNER'S AGENT AND INSPECTORS OF APPLICABLE GOVERNMENT JURISDICTIONS, TO AT ALL TIMES HAVE ACCESS TO THE WORK WHEREVER AND WHENEVER IT IS IN PREPARATION OR PROGRESS; AND THE CONTRACTOR TO PROVIDE PROPER
FACILITIES FOR SUCH ACCESS AND FOR THE INSPECTION.
19. IT IS THE CONTRACTOR'S RESPONSIBILITY TO TAKE ALL REASONABLE AND PRUDENT PRECAUTIONS TO ENSURE THAT ALL COMPLETED WORK, MATERIALS AND EQUIPMENT STORED ON SITE ARE SAFE AND SECURED FROM UNAUTHORIZED ACCESS, USE, THEFT, OR VANDALISM. SUCH PRECAUTIONS MAY INCLUDE INSTALLATION OF SIGNS, FENCES, OR POSTING OF SECURITY GUARDS.
20. PRIOR TO INITIATING ANY EXCAVATION (INCLUDING BUT NOT LIMITED TO DITCHES, STORMWATER PONDS, CANALS), INSTALL FENCES AND TAKE ALL OTHER REASONABLE AND PRUDENT STEPS TO ENSURE THAT ACCESS TO EXCAVATION BY UNAUTHORIZED
PERSONNEL IS PREVENTED.
21. AT ALL TIMES, USE ALL NORMALLY ACCEPTED AND REASONABLY EXPECTED SAFETY PRACTICES AND COMPLY WITH ALL FEDERAL, STATE AND LOCAL REGULATIONS, ORDINANCES AND GUIDELINES PERTAINING TO SAFE USE OF EQUIPMENT OR MATERIALS AS
PUBLISHED BY MANUFACTURER.
22. COMPLY WITH ALL FEDERAL OCCUPATIONAL HEALTH AND SAFETY ACT RULES AND REGULATIONS. COMPLY WITH ANY AND ALL APPLICABLE FEDERAL, STATE AND LOCAL LAWS AND REGULATIONS PERTAINING TO JOB SAFETY AND HEALTH.
23. ALL WORK PERFORMED UNDER THE CONTRACT, AND ALL EQUIPMENT, APPLIANCES, TOOLS AND LIKE ITEMS USED IN THE WORK TO CONFORM TO APPLICABLE SAFETY CODES AND REGULATIONS OF ANY PUBLIC OR OTHER AUTHORITY HAVING JURISDICTION. IN THE EVENT OF CONFLICTING REQUIREMENTS, THE MORE STRINGENT INTERPRETATION OR REGULATION GOVERNS. TAKE ALL REASONABLE PRECAUTIONS FOR THE SAFETY OF, AND PROVIDE ALL REASONABLE PROTECTION TO PREVENT DAMAGE, INJURY
OR LOSS TO:
A. ALL EMPLOYEES ON THE WORK AND ALL OTHER PERSONS WHO MAY BE AFFECTED;
B. ALL THE WORK AND ALL MATERIALS AND EQUIPMENT USED, WHETHER IN STORAGE ON OR OFF THE SITE, UNDER THE CARE, CUSTODY OR CONTROL OF THE CONTRACTOR OR ANY OF ITS SUBCONTRACTORS;
C. OTHER PROPERTY AT THE SITE OR ADJACENT TO IT, INCLUDING TREES, SHRUBS, LAWNS, WALKS, PAVEMENTS, ROADWAY, STRUCTURES AND UTILITIES NOT DESIGNATED FOR DEMOLITION DURING CONSTRUCTION.
25. ERECT AND MAINTAIN, AS REQUIRED BY EXISTING CONDITIONS AND PROGRESS OF THE WORK, ALL REASONABLE SAFEGUARDS FOR SAFETY AND ENVIRONMENTAL PROTECTION, INCLUDING POSTING DANGER SIGNS AND OTHER WARNINGS AGAINST HAZARDS, PROMULGATING SAFETY REGULATIONS AND NOTIFYING OWNERS AND USERS OF ADJACENT UTILITIES OF THE EXISTENCE OF
HAZARDS AND OF THE SAFETY OR ENVIRONMENTAL REGULATIONS.
26. PROVIDE ADEQUATE PROTECTION FOR PARTS IN WORKPLACE AND ADJACENT AREAS THAT ARE SUBJECT TO DAMAGE DUE TO
CONSTRUCTION. PROTECTION OF PARTS IS AT THE COST OF THE CONTRACTOR.
27. FURNISH AND MAINTAIN ADEQUATE TRAFFIC CONTROL, BARRICADES AND FLAGMAN SERVICES AT ALL POINTS WHERE CONVEYING EQUIPMENT ENGAGED ON THE WORK REGULARLY ENTERS ONTO OR CROSSES TRAFFIC-CARRYING ROADS.
28. USE, HANDLE, TRANSPORT, AND DISPOSE OF ALL HAZARDOUS MATERIALS IN COMPLIANCE WITH ALL FEDERAL, STATE AND LOCAL
ENVIRONMENTAL, HEALTH OR SAFETY LAWS, AND REQUIREMENTS.
29. CONTRACTOR AND ITS SUBCONTRACTORS TO NOT CAUSE THE DISCHARGE, RELEASE OR DISPOSAL OF ANY HAZARDOUS MATERIAL CREATED BY THEIR WORK ON OR ABOUT THE JOB SITE. IN THE EVENT OF ANY SPILL, RELEASE OR ANY OTHER REPORTABLE OCCURRENCE, CONTRACTOR TO NOTIFY THE APPROPRIATE GOVERNMENTAL AGENCY IN ACCORDANCE WITH THE CONTRACTING OFFICER, AND TAKE SUCH ACTION AS MAY BE NECESSARY TO MINIMIZE THE DELETERIOUS EFFECT OF SUCH SPILL ON PERSONS OR PROPERTY. THE CONTRACTOR IS RESPONSIBLE FOR DISPOSAL OF ANY HAZARDOUS WASTE MATERIALS IN
ACCORDANCE WITH FEDERAL, STATE AND LOCAL REGULATIONS.
30. CONTRACTOR AND ITS SUBCONTRACTORS TO, UPON COMPLETION OF PERFORMANCE OF ALL DUTIES UNDER THIS CONTRACT, REMOVE ALL SUPPLIES, MATERIALS, AND WASTE CONTAINING ANY HAZARDOUS MATERIAL FROM THE JOB SITE. CONTRACTOR TO BEAR FULL FINANCIAL RESPONSIBILITY, AS BETWEEN THE PARTIES OF THIS CONTRACT, FOR THE COMPLIANCE OF CONTRACTOR
AND ITS SUBCONTRACTORS.
31. IN THE EVENT CONTRACTOR OR ITS SUBCONTRACTORS ENCOUNTER ON THE PREMISES ANY PIPELINE, UNDERGROUND STORAGE TANK OR OTHER CONTAINER, OF ANY KIND, THAT MAY CONTAIN A HAZARDOUS MATERIAL, OR ENCOUNTER MATERIAL REASONABLY BELIEVED TO BE A HAZARDOUS MATERIAL, IMMEDIATELY STOP WORK IN THE AREA AFFECTED AND REPORT THE
CONDITION TO CONTRACTING OFFICER IN WRITING.
32. "HAZARDOUS MATERIAL" MEANS ANY SUBSTANCE: (A) THE PRESENCE OF WHICH REQUIRES INVESTIGATION OR REMEDIATION UNDER ANY PRESENT FEDERAL, STATE OR LOCAL STATUTE, REGULATION, ORDINANCE, RULE, CODE, ORDER, ACTION, POLICY OR COMMON LAW, OR (B) WHICH IS OR BECOMES DEFINED AS A "HAZARDOUS WASTE," "HAZARDOUS SUBSTANCE," POLLUTANT OR CONTAMINANT UNDER ANY PRESENT FEDERAL, STATE OR LOCAL STATUTE, REGULATION, RULE OR ORDINANCE OR AMENDMENTS THERETO INCLUDING, WITHOUT LIMITATION, THE COMPREHENSIVE ENVIRONMENTAL RESPONSE COMPENSATION AND LIABILITY ACT (42 U.S.C. SECTIONS 9601 ET SEQ.) AND/OR THE RESOURCE CONSERVATION AND RECOVERY ACT (42 U.S.C. SECTIONS 6901 ET SEQ.), OR (C) WHICH IS TOXIC, EXPLOSIVE, CORROSIVE, FLAMMABLE, INFECTIOUS, RADIOACTIVE, CARCINOGENIC, MUTAGENIC, OR OTHERWISE HAZARDOUS AND IS REGULATED BY ANY GOVERNMENTAL AUTHORITY, AGENCY, DEPARTMENT, COMMISSION, BOARD, AGENCY OR INSTRUMENTALITY OF THE UNITED STATES, THE STATE IN WHICH THE PREMISES ARE LOCATED OR ANY POLITICAL SUBDIVISION THEREOF, OR (D) THE PRESENCE OF WHICH ON THE PREMISES CAUSES OR THREATENS TO CAUSE A NUISANCE UPON THE PREMISES OR TO ADJACENT PROPERTIES OR POSES OR THREATENS TO POSE A HAZARD TO THE HEALTH OR SAFETY OF PERSONS ON OR ABOUT THE PREMISES, OR (E) WHICH CONTAINS GASOLINE, DIESEL FUEL OR OTHER PETROLEUM HYDROCARBONS, OR (F) WHICH CONTAINS POLYCHLORINATED BIPHENYLS, ASBESTOS, LEAD OR UREA FORMALDEHYDE FOAM
INSULATION.
REINFORCING STEEL:
1. CONCRETE REINFORCEMENT STEEL INSTITUTE (CRSI) AND AMERICAN CONCRETE INSTITUTE (ACI) STANDARDS APPLY.
2. ENSURE ALL DEFORMED BARS CONFORM TO ASTM A615, GRADE 60 AND INSTALLED IAW ACI 315-99.
3. COLD BEND ALL REINFORCEMENT. DO NOT FIELD BEND REINFORCEMENT PARTIALLY EMBEDDED IN GROUT.
4. MECHANICAL SPLICES, CONFORMING TO ACI 318-14, SECTION 25.5.7 CAN BE SUBSTITUTED FOR LAP SPLICES AT NO ADDITIONAL COST. MECHANICAL SPLICES MUST DEVELOP 125% (MINIMUM) OF THE YIELD STRENGTH OF THE CONNECTING REBAR.
5. AT THE TIME OF CONCRETE PLACEMENT, ALL REINFORCEMENT MUST BE FREE OF DIRT, DEBRIS, CORROSION, OIL, NONMETALLIC COATINGS OR OTHER DELETERIOUS MATERIAL THAT REDUCE BOND STRENGTH WITH CONCRETE.
6. SUPPORT REINFORCING STEEL IN STANDARD ACCESSORIES, HELD RIGIDLY AND ACCURATELY IN PLACE, AND PROTECT AGAINST DISPLACEMENT BEFORE AND DURING PLACEMENT OF CONCRETE. PROVIDE PRECAST CONCRETE BRICKS AT 2 FEET OC EACH WAY (MAX SPACING) FOR THE SUPPORT OF REINFORCING STEEL AND WIRE MESH AT THE FOUNDATIONS AND
SLAB-ON-GRADE.
7. PROVIDE FIBREGLASS REINFORCED PLASTIC OR PLASTIC COATED STEEL FOR ALL REINFORCEMENT CHAIR LEGS THAT REST
ON CONCRETE SURFACES AND WILL BE EXPOSED IN THE FINISH STRUCTURE.
CONCRETE PROTECTION FOR REINFORCEMENT:
STRUCTURAL SYSTEM
FOOTINGS (CAST AGAINST AND EXPOSED TO EARTH)
COVER
3 INCHES
2 INCHES
2 INCHES
1 1/2 INCHES
1 INCH
FOOTINGS AND WALLS (FORM CAST AND EARTH EXPOSED)
SLABS (EARTH EXPOSED)
SLABS (EXTERIOR EXPOSED)
SLABS (ABOVE GRADE)
1. DEWATER, AS REQUIRED, SUCH THAT THE EXCAVATIONS ARE FREE OF STANDING WATER AT THE TIME OF CONCRETE
PLACEMENT.
2. COMPACT SUBGRADE SOIL TO A MINIMUM OF 95% OF THE MAXIMUM MODIFIED PROCTOR DRY DENSITY IN ACCORDANCE WITH
ASTM D-1557.
3. CONSTRUCT ALL PORTIONS OF PAVEMENT AND CURBING IN ACCORDANCE WITH FDOT STANDARD DETAILS.
4. FOR ASPHALT ROAD BASE COURSE FOUR (4) INCHES OF #57 STONE IN FOUR INCH LIFTS AND PROVIDE THREE PASSES WITH
VIBRATORY PLATE COMPACTION.
5. FOR CONCRETE EQUIPMENT PAD BASE COURSE PLACE FOUR (4) INCHES OF #57 STONE IN FOUR INCH LIFTS AND PROVIDE
THREE PASSES WITH VIBRATORY PLATE COMPACTION.
6. FOR UTILITY BEDDING, HAUNCHING AND COVER PLACE CLEAN GRANULAR FILL IN SIX INCH LIFTS AND COMPACT TO A MINIMUM OF 95% OF THE MAXIMUM MODIFIED PROCTOR DRY DENSITY IN ACCORDANCE WITH ASTM D-1557.
7. FOR UTILITY TRENCH BACKFILL PLACE NATIVE BACKFILL IN 12-INCH LIFTS (MAX) AND COMPACT TO A MINIMUM OF 95% OF THE
MAXIMUM MODIFIED PROCTOR DRY DENSITY IN ACCORDANCE WITH ASTM D-1557.
8. INSTALL 10 MIL VAPOR BARRIER BETWEEN NEW CONCRETE AND BASE MATERIAL.
9. COORDINATE ALL NEW FOUNDATIONS WITH EXISTING CONDITIONS. REPORT ANY CONFLICTS TO THE CONTRACTING OFFICER
FOR PROPOSED SOLUTION.
10. FOR FOUNDATIONS SHOWN ON DRAWINGS THAT USE EARTH FORMING, ENSURE EXCAVATION AREA DOES NOT EXCEED THREE
INCHES IN EACH DIRECTION.
1. REMOVE ALL EXCAVATED MATERIAL AND CONSTRUCTION AND DEMOLITION DEBRIS FROM THE PROJECT SITE AND PROVIDE
PROPER DISPOSAL OF IN ACCORDANCE WITH FEDERAL, STATE AND LOCAL REQUIREMENTS.
2. ENSURE EROSION CONTROL MEASURES TAKEN ARE IN CONFORMANCE WITH CCAFS, AND ANY OTHER LOCAL, STATE, OR FEDERAL
AGENCIES HAVING JURISDICTION.
3. EROSION CONTROL MEASURES MUST BE INSTALLED PRIOR TO CONSTRUCTION COMMENCEMENT.
4. THE APPROPRIATE TURBIDITY AND EROSION CONTROL METHODOLOGIES SELECTED BY THE CONTRACTOR FOR THIS PROJECT SHOULD BE MADE FOLLOWING ASSESSMENT OF THE PLANS AND PROJECT SITE SPECIFIC FACTORS AND AFTER CONSULTATIONS AS NEEDED WITH THE CONTRACTING OFFICER AND APPROPRIATE AGENCIES. THE CONSTRUCTION SEQUENCING SHOULD BE THOUGHT OUT IN ADVANCE OF INITIATION TO PROVIDE ADEQUATE PROTECTION OF WATER QUALITY.
5. THE TYPE OF EROSION CONTROL BARRIERS USED ARE GOVERNED BY THE NATURE OF THE CONSTRUCTION OPERATION AND SOIL TYPE THAT WILL BE EXPOSED. SILTY AND CLAYEY MATERIAL MAY REQUIRE SOLID SEDIMENT BARRIERS TO PREVENT TURBID WATER DISCHARGE WHILE SANDY MATERIAL MAY NEED ONLY SILT SCREENS OR HAY BALES TO PREVENT EROSION. FLOATING TURBIDITY BARRIERS SHOULD GENERALLY BE USED IN OPEN WATER SITUATIONS. DIVERSION DITCHES OR SWALES MAY BE REQUIRED TO PREVENT TURBID STORMWATER RUNOFF FROM BEING DISCHARGED TO WETLANDS OR OTHER WATER BODIES. IT MAY BE NECESSARY TO EMPLOY A COMBINATION OF BARRIERS, DITCHES, AND OTHER EROSION/TURBIDITY CONTROL MEASURES
IF CONDITIONS WARRANT.
6. MAINTAIN THE EROSION CONTROL DEVICES THROUGHOUT THE DURATION OF CONSTRUCTION. SUCH DEVICES TO REMAIN UNTIL
SUFFICIENT GROUND COVER IS ESTABLISHED.
7. INSPECT THE SITE ROUTINELY AFTER RAINFALL EVENTS. EQUIPMENT SHOULD BE AVAILABLE AT THE SITE AT ALL TIMES TO MAKE
REPAIRS AS NECESSARY.
8. INSTALL TEMPORARY EROSION CONTROL BARRIERS IN COORDINATION WITH THE CONSTRUCTION OF THE PERMANENT EROSION CONTROL FEATURES TO THE EXTENT NECESSARY TO ASSURE ECONOMICAL, EFFECTIVE, AND CONTINUOUS CONTROL OF
EROSION AND WATER POLLUTION THROUGHOUT THE LIFE OF THE CONSTRUCTION PHASE.
9. SCHEDULE OPERATIONS SUCH THAT THE AREA OF UNPROTECTED, ERODIBLE EARTH EXPOSED AT ANY ONE TIME IS NOT LARGER THAN THE MINIMUM AREA NECESSARY FOR EFFICIENT CONSTRUCTION OPERATION AND ENSURE THE DURATION OF EXPOSED, UNCOMPLETED CONSTRUCTION TO THE ELEMENTS IS AS SHORT AS PRACTICABLE. GRADING OPERATIONS ARE TO IMMEDIATELY FOLLOW SCHEDULED AND COMPLETED CLEARING AND GRUBBING. PERMANENT EROSION CONTROL FEATURES ARE TO BE SCHEDULED AND PREFORMED IMMEDIATELY FOLLOW GRADING OPERATIONS IF CONDITIONS ON THE PROJECT AREA ALLOW.
10. EXPOSED SOILS SHOULD BE STABILIZED AS SOON AS POSSIBLE. THE CONTRACTOR IS RESPONSIBLE FOR SELECTING AND
PROVIDING THE TEMPORARY AND PERMANENT STABILIZATION METHODS.
11. INSTALL ENERGY DISSIPATERS, INCLUDING BUT NOT LIMITED TO RIP-RAP, GRAVEL, HAY BALES, VEGETATION OR GEOTEXTILES, AT
THE DISCHARGE POINT OF PIPES OR SWALES IF SCOURING IS OBSERVED.
12. IF VEHICLE OR EQUIPMENT WASHDOWN DEBRIS/AREAS IS REQUIRED, OBTAIN APPROVAL FROM THE CONTRACTING OFFICER.
13. STOCKPILE EXCAVATED MATERIAL IN SUCH A MANNER THAT PREVENTS DIRECT OFFSITE DISCHARGE FROM THE PROJECT SITE OR
INTO ANY ADJACENT WATER BODY, WETLAND, OR STORMWATER MANAGEMENT FACILITY.
14. CONSTRUCT ALL PROJECT FEATURES TO PREVENT EROSION AND SEDIMENTATION AND MAINTAIN THROUGHOUT THE LIFE OF
CONSTRUCTION.
15. ONGOING INSPECTIONS AND PERIODIC MAINTENANCE BY THE CONTRACTOR MUST OCCUR THROUGHOUT CONSTRUCTION AS OFTEN AS NECESSARY TO ENSURE THAT THE ABOVE METHODS ARE WORKING SUITABLY. THIS MAY BE NEEDED AS OFTEN AS DAILY IF CONDITIONS SO WARRANT. MAINTAIN A WRITTEN RECORD OF ALL EROSION CONTROL INSPECTIONS, INCIDENTS, AND MODIFICATIONS AND MUST MAKE ALL RECORDS AVAILABLE UPON REQUEST BY THE CONTRACTING OFFICER.
FOUNDATIONS:
EROSION AND TURBIDITY CONTROL GENERAL NOTES:
LAP SPLICE LENGTH - NORMAL WEIGHT CONCRETE, NO EPOXY
TO
P
BA
R
S O
TH
ER
BAR SIZES (#)
3 4 5 6 7 8 9 10 11
15" 20" 24" 29" 42" 48" 55" 65" 80"3" 15" 20" 24" 29" 46" 61" 77" 97" 120"2" 15" 20" 25" 36" 62" 81" 102" 130" 160"1 1/2" 18" 32" 50" 73" 106" 121" 136" 153" 170"3/4"
12" 15" 19" 23" 33" 37" 42" 50" 62"3" 12" 15" 19" 23" 36" 47" 59" 75" 92"2" 12" 15" 20" 28" 48" 62" 79" 100" 123"1 1/2" 14" 25" 39" 56" 81" 93" 105" 118" 131"3/4"
#3 #4 #5 #6 #7 #8 #9 #10 #11
DEFORMED REBAR
TYPE
STIRRUPS & TIES
OTHER BARS 2.25" 3" 3.75" 4.5" 5.25" 6" 9" 10.25" 11.25"
MIN INSIDE DIAMETER OF BEND
1.5" 2" 2.5" N/A N/A N/A N/A N/A N/A
REQUIRED EMBEDEMENT DEPTH OF STANDARD ACI HOOKS INTO CONCRETE
NORMAL WEIGHT
CONCETE TYPE BAR SIZES
4 5 6 7 8 9 10 113
8" 10" 12" 15" 17" 19" 22" 25" 27"
LEAST
CONCRETE
COVER AT BAR
DESCRIPTION
ACI MINIMUM STANDARD HOOK EXTENSION LENGTHS
#3 #4 #5 #6 #7 #8 #9 #10 #11
STIRRUPS & TIES
90° BEND PLUS 2.25" 3" 3.75" 4.5" 5.25" 6" 6.77" 7.62" 8.46"
STIRRUPS & TIES
135° BEND PLUS 3" 3" 3.75" 4.5" 5.25" 6" 6.77" 7.62" 8.46"
OTHER BARS 90°
BEND PLUS 4.5" 6" 7.5" 9" 10.5" 12" 13.75" 15.5" 7"
OTHER BARS 180°
BEND PLUS 2.5" 2.5" 2.5" 3" 3.5" 4" 4.75" 5.25" 5.75"
MECHANICAL GENERAL NOTES:
1. PROVIDE PIPE MARKER FOR ALL PIPING IN ACCORDANCE WITH THE DIVISION 22 SPECIFICATIONS.
2. PROVIDE VALVES AND FITTINGS AS THE SAME SIZE AS THE PIPING WHERE THEY ARE LOCATED UNLESS NOTED OTHERWISE.
3. INSTALL PLUMBING SYSTEMS IN ACCORDANCE WITH 2017 FLORIDA BUILDING CODE (FBC), PLUMBING (SIXTH EDITION).
4. COMPLY WITH UFC, IBC, AND STATE, COUNTY, CITY, AND LOCAL CODES AND ORDINANCES, SAFETY AND HEALTH CODES, NFPA CODES AND ALL OTHER APPLICABLE STANDARDS, CODES AND REQUIREMENTS WITH LATEST AMENDMENTS, INCLUDING BUT NOT
LIMITED TO 62-550.350, F.A.C. OPERATION AND MAINTENANCE OF PUBLIC WATER SYSTEMS.
5. INSTALL EQUIPMENT IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS.
6. FIELD-VERIFY AND COORDINATE DIMENSIONS PRIOR TO PROCUREMENT OR FABRICATION. COORDINATE THE WORK WITH OTHER TRADES INVOLVED. PROVIDE FIELD MODIFICATIONS SUCH AS OFFSETS IN PIPING NEEDED DUE TO OBSTRUCTIONS OR
INTERFERENCES AT NO ADDITIONAL COST.
7. SUPPORT ALL EQUIPMENT AND PIPING AS DETAILED AND/OR SPECIFIED. PROVIDE ADDITIONAL SUPPORTS AS REQUIRED TO
PROVIDE A VIBRATION-FREE, RIGID INSTALLATION.
8. REFER TO TYPICAL DETAILS FOR PIPING AND INSTALLATION OF EQUIPMENT.
9. THE LOCATION AND/OR ELEVATION OF EXISTING UNDERGROUND PIPING, IF SHOWN ON THESE PLANS, ARE FOR REFERENCE ONLY.
THE INFORMATION IS NOT TO BE RELIED ON AS BEING EXACT OR COMPLETE. CALL THE APPROPRIATE UNDERGROUND PIPING COMPANY AT LEAST 72 HOURS BEFORE ANY EXCAVATION TO REQUEST EXACT FIELD LOCATION OF ALL UNDERGROUND PIPING.
NOTIFY THE CONTRACTING OFFICER OF ANY CONFLICTS BETWEEN EXISTING AND NEW UNDERGROUND PIPING.
GENERAL NOTES:
1. PUMPS AND WELLS.
A. PHASE PROJECT SUCH THAT WELLS CAN BE DRILLED AND TESTED TO DETERMINE WELL PRESSURE AND WATER QUALITY TO VALIDATE PUMP SUCTION HEAD PRIOR TO PUMP AND FILTER PROCUREMENT. SEE PUMP AND FILTER SCHEDULE.
B. CONFORM WATER PUMP ELECTRICAL CONTROL SYSTEMS TO NFPA 70, 70E AND LOCAL BUILDING CODES.
C. PROTECT THE PUMPING SYSTEM FROM ENVIRONMENTAL HAZARDS.
D. USE ELECTRIC MOTORS WITH A NOMINAL HORSEPOWER RATING GREATER THAN THE MAXIMUM HORSEPOWER REQUIREMENT OF THE PUMP DURING NORMAL OPERATION. PROVIDE MOTOR TO HAVE A SERVICE FACTOR OF AT LEAST 1.15.
2. PUMP INSTALLATION.
A. INSTALL PUMPS IN ACCORDANCE WITH MANUFACTURER’S RECOMMENDATIONS. SET PUMPS PLUMB AND SECURE TO A FIRM CONCRETE BASE. ENSURE NO STRAIN OR DISTORTION ON THE PIPE AND FITTINGS. SUPPORT PIPE AND FITTINGS TO
AVOID PLACING UNDUE STRAIN ON THE PUMP.
B. INSTALL PUMPS IN A MANNER TO AVOID LOSS OF PRIME. INSTALL SUCTION LINE TO PREVENT THE ACCUMULATION OF AIR POCKETS. ENSURE ALL CONNECTIONS AND REDUCTIONS IN SUCTION PIPE TO AVOID CAUSING AIR POCKETS AND
CAVITATION.
C. LOCATE PUMPS TO FACILITATE SERVICE AND EASE OF REMOVAL. PROVIDE APPROPRIATE FITTINGS TO ALLOW THE PUMP TO READILY BE PRIMED, SERVICED, AND DISCONNECTED. PROVIDE AN ENCLOSURE OF ADEQUATE SIZE AND STRENGTH, WITH PROPER VENTILATION, TO PROTECT THE PUMP FROM THE ELEMENTS.
3. HYDRAULIC CONTROL TUBING.
A. INSTALL TUBING IN TRENCHES FREELY AND SPACED TO PREVENT RUBBING AGAINST PIPE, FITTINGS, OR OTHER OBJECTS THAT COULD SCORE THE TUBING, AND WITH A MINIMUM 12-INCH DIAMETER LOOP AT ALL TURNS AND CONNECTIONS.
PROVIDE A MINIMUM DEPTH OF COVER OF 12 INCHES.
B. CONNECT TUBING WITH COUPLINGS AND COLLARS RECOMMENDED BY THE TUBING MANUFACTURER. MAKE ALL SPLICES IN VALVE BOXES. PREFILL TUBING WITH WATER, EXPELLING ENTRAPPED AIR AND TESTING FOR LEAKS PRIOR TO
INSTALLATION.
4. BACKFLOW PREVENTION METHODS
PROVIDE BACKFLOW PREVENTION ASSEMBLIES AT ALL WATER SUPPLY CROSS CONNECTIONS IN ACCORDANCE WITH UFC 3-230-01 AND COUNTY, MUNICIPAL OR OTHER APPLICABLE CODES. PROVIDE BACKFLOW PREVENTION ASSEMBLY TYPE WITH
THE HIGHEST DEGREE OF PROTECTION IN THE EVENT OF CONFLICTING REGULATIONS.
5. TRENCHING
MAINTAIN A MINIMUM 12 INCH SEPARATION BETWEEN WATER AND ELECTRIC UTILITIES IN TRENCHES. INSTALL A SINGLE
STRAND SOLID COPPER DETECTION WIRE WITH ALL BURIED NON-METALLIC PIPING.
B
2 3
C
D
1 2 3
4 5 6
AS
B
U
IL
T D
AT
E:
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
R
EV
IE
W
ED
B
Y:
D
AT
E:
4 5
M
AR
K D
ES
C
R
IP
TI
O
N D
AT
E
AP
PR
SHEET
IDENTIFICATION
C
D
A
B
U
SA
F
TH
C
IV
IL
E N
G
IN
EE
R
S Q
U
AD
R O
N , P
AF
B, F L
C O
N
TR
AC
T
N O
FA
-1 8-
D -0
TR
AC
ES
TE
C H
N
IC
AL
R
AN
G
E
AR
C H
IT
EC
T
EN
G
IN
EE
R
IN
G
SE
R
VI
C
ES
D
EL
IV
ER
Y N
O
Ne lso nE ng in ee ri ng Co rh od es b rit
C-002
AB
BR
EV
IA
TI
O
N S, S
YM
BO
LS
A N
D S
C H
ED
U
LE
S
100%
DESIGN REVIEW ONLY
NOT FOR CONSTRUCTION
N
EL
SO
N
EN
G
IN
EE
R
IN
G
-1
2-
M J
O H
N
SO
N
J
TY
SO
N
B H
AR
VE
Y
D
BE
H
8-
XX
XX
XX
-X
X-
XX
D
BE
H
8-
IN
ST
AL
L
EM
ER
G
EN
C Y
M
AK
EU
P
W
AT
ER
F
O R
C R
IT
IC
AL
F
AC
IL
IT
IE
S
A AMP
ACI AMERICAN CONCRETE INSTITUTE
APPOX APPROXIMATE
ASTM AMERICAN SOCIETY FOR TESTING AND MATERIALS
AWS AMERICAN WELDING SOCIETY
BLDG BUILDING
CCAFS CAPE CANAVERAL AIR FORCE STATION
CJ CONTROL JOINT
CRSI CONCRETE REINFORCEMENT STEEL INSTITUTE
CSJ CONSTRUCTION JOINT
CEIE CIVIL, ENVIRONMENTAL AND INFRASTRUCTURE ENGINEERING
CES CIVIL ENGINEERING SQUADRON
CFR CODE OF FEDERAL REGULATIONS
CONC CONCRETE
CRSI CONCRETE REINFORCEMENT STEEL INSTITUTE
DIP DUCTILE IRON PIPE
EMU EMERGENCY MAKE UP WATER
EOP EDGE OF PAVEMENT
EPF EASTERN PROCESSING FACILITY
ETR EXISTING TO REMAIN
EW EACH WAY
FAA FEDERAL AVIATION ADMINISTRATION
FAC FLORIDA ADMINISTRATIVE CODE
FBC FLORIDA BUILDING CODE
FDEP FLORIDA DEPARTMENT OF ENVIRONMENTAL PROTECTION
FDOT FLORIDA DEPARTMENT OF TRANSPORTATION
FE FLANGED END
FFE FINISH FLOOR ELEVATION
FL FLANGED
FT FOOT
GPM GALLON PER MINUTE
HP HORSEPOWER
HSS HOLLOW STRUCTURAL SECTION
HZ HERTZ
IBC INTERNATIONAL BUILDING CODE
LF LINEAR FEET
MAX MAXIMUM
MH MANHOLE
MIN MINIMUM
MOC MORRELL OPERATIONS CENTER
NAD 83 NORTH AMERICAN DATUM OF 1983
NAVD 88 NORTH AMERICAN VERTICAL DATUM OF 1988
NO NUMBER
NTS NOT TO SCALE
OC ON CENTER
OSHA OCCUPATIONAL SAFETY AND HEALTH ORGANIZATION
PH PHASE
PSIG POUNDS PER SQUARE INCH GAUGE
PVC POLYVINYL CHLORIDE
SCH SCHEDULE
SF SQUARE FEET
SS STAINLESS STEEL
TDH TOTAL DYNAMIC HEAD
TOS TOP OF SLAB
TSF TECH SUPPORT FACILITY
TYP TYPICAL
UFC UNITED FACILITIES CRITERIA
UG UNDERGROUND
UNO UNLESS NOTED OTHERWISE
V VOLT
XY XY COMM BUILDING
NEW CONCRETE BASE
EXISTING BASE GRADE
NEW PACKED GRAVEL
WATER
EXISTING SUBGRADE
NEW HAUNCHING
NEW BEDDING SAND
EXISTING TO BE DEMOED
SAWCUT
CENTERLINE
EXISTING WATER LINE
EXISTING COMM
ABANDON IN PLACE
EXISTING FORCEMAIN
EXISTING STORM SEWER
EXISTING FENCE
EXISTING STORM DRAIN
EXISTING NATURAL GAS
EXISTING ELECTRICAL
EMERGENCY MAKE UP WATER
SILT FENCE
END OF PIPE
RELIEF VALVE
PRESSURE SWITCH
PRESSURE GAUGE
SYMBOLS:ABBREVIATIONS:
DRAWING WHERE DETAIL IS SHOWN/REFERENCED
DETAIL BUBBLE
DETAIL REFERENCE NUMBER
SECTION DETAIL BUBBLE
DETAIL REFERENCE LETTER
C-501 B
A C-501
DETAIL PLAN REFERENCE NUMBER
DRAWING WHERE SECTION IS REFERENCED
REFERENCE SYMBOLS:
# FLAG NOTE
W
CANOPY
NO RP
AIP SLAB
NO RP
ANTENNA PAD
81915
ANTENNA PAD
81913
ELECTRICAL SUBSTATION PAD
81902
FUEL TANK PAD
81900-3
ANTENNA PAD
81914
ANTENNA PAD
81909
ANTENNA PAD
81916
NOAA PORT ANTENNA
81910
NATURAL GAS STATION 9
NO RP
AIP LIGHTNING PROTECTION TOWER PAD
81911
ANTENNA PAD
81918
ANTENNA PAD
81912
ANTENNA PAD
81917
MORRELL OPERATIONS CENTER
81900
GATE HOUSE
81901
LIGHTNING PROTECTION TOWERS
81911
WALL
WALL
WALL
WALL
WALL
WALL
WALL
WALL
MAIN
8 PVC
MAIN
8 PVC
MAIN
8 PVC
MAIN
6 TBD
MAIN
6 TBD
SERVICE
2 PVC
MAIN
8 PVC
MAIN
8 PVC
SERVICE
4 PVC
FIRE
8 PVC
MAIN
4 PVC
MAIN
8 PVC
SERVICE
4 PVC
FIRE
8 PVC
MAIN
6 PVC
TEE
TEE
TEE
TEE
TEE
TEE
TEE
TEE
TEE
TEE
TEE
TEE
TEE
TEE
VALVE
VALVE
VALVE
VALVE
VALVE
VALVE
BACKFLOW
BACKFLOW
VALVE
VALVE
VALVE
BACKFLOW
BACKFLOW
VALVE
VALVE
HYDRANT
HS-22-03
HYDRANT
HS-22-04
HYDRANT
HS-22-05
LIFT STATION
81904
VALVE
M-S22-06
C.O.
C.O.
M-S22-05
M-S22-04 M-S22-03
4x7.5x7
MH-570
4x7x4x10x6
MH-595A
4x7.5x7
MH-594D2
4x9x6
MH-595
4x9x6
MH-596
4x7.5x7
MH-595B
4x7.5x7
MH-594B
4x7.5x7
MH-594D1
C
C
C
C
C
C C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C C
C C
C
C C
C
C
C
C
CC
C
C C
C
C
E
E
E
E
E
E
E
E
E
E
E E
E E
E
E
E
E
E
E
E
E
E
NG
NG
NG
NG
NG
X
XX
X
X
X
X X
X X
X X
X X
X
X
X
X X
X X
X X
X X
X X X X X X X X X X X
X X
X X
X X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X X
X X
X X
XXXXXXXXXXX
X
X X
X X
X X
X
X
X
X
X
X X
X X
X X
X X
X
X
X
X X
C
C
X
X
X
MAIN
8 PVC
MAIN
8 PVC
MAIN
8 PVC
MAIN
6 TBD
MAIN
6 TBD
SERVICE
2 PVC
MAIN
8 PVC
MAIN
8 PVC
SERVICE
4 PVC
FIRE
8 PVC
MAIN
4 PVC
MAIN
8 PVC
SERVICE
4 PVC
FIRE
8 PVC
MAIN
6 PVC
8'' W
8'' W
W
8'' W
8'' W
8'' W
W
TEE
TEE
TEE
TEE
TEE
TEE
TEE
TEE
TEE
TEE
TEE
TEE
TEE
TEE
HYDRANT
HS-22-03
HYDRANT
HS-22-04
HYDRANT
HS-22-05
FM
FM
SS
SS
SS
8' ' W
8' ' W
8'' W
8'' W
8'' W
8'' W
8'' W
8'' W
8'' W
8'' W
8'' W
FM
FM
FM
S
S
S S
C O
C O
L
X
X
ELECTRICAL SUBSTATION PAD
81902
FUEL TANK PAD
81900-3
WALL
WALL
SERVICE
2 PVC
MAIN
8 PVC
MAIN
8 PVC
SERVICE
4 PVC
FIRE
8 PVC
TEE
TEE
TEE
TEE
BACKFLOW
BACKFLOW
C
C
C
C
C
E E
E E
X X
X
X
X
X
X
X
X
X
X
X
SERVICE
2 PVC
MAIN
8 PVC
MAIN
8 PVC
SERVICE
4 PVC
FIRE
8 PVC
W
W
8'' W
8'' W
TEE
TEE
TEE
TEE
8'' W
8'' W
8'' W
8'' W
W
100%
DESIGN REVIEW ONLY
NOT FOR CONSTRUCTION
1. AVERAGE MAKEUP WATER RATE 24 GPM.
2. TAKE ALL NECESSARY MEASURES TO PROTECT EXISTING TO REMAIN ITEMS DURING
DEMOLITION AND CONSTRUCTION.
3. LAWFULLY DISPOSE OF ALL MATERIALS, DRILL CUTTINGS, AND WATER USED TO AN
OFFSITE LOCATION.
4. PATCH ALL HOLES CREATED BY THE REMOVAL OF PIPING OR OTHER ITEMS. IN-FILL
UNUSED OPENINGS WITH SAME MATERIAL, UNLESS NOTED OTHERWISE.
5. REFER TO SHEET C-701 FOR PUMP SKID REQUIREMENTS FOR MOC LOCATION.
6. COORDINATE FINAL LOCATION OF WELL AND PUMP SYSTEM EQUIPMENT WITH
FACILITY OWNER PRIOR TO START OF CONSTRUCTION.
SPECIFIC NOTES:
0 25 50 100
1"=50'
SCALE IN FEET
GRAPHIC SCALE
SCALE:
MORRELL OPERATIONS CENTER (MOC) - SITE PLAN
1" = 50'
N
SCALE:
ENLARGED PLAN VIEW
1" = 30'
N
A
B
2 3
C
D
1 2 3
4 5 6
AS
B
U
IL
T D
AT
E:
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
R
EV
IE
W
ED
B
Y:
D
AT
E:
4 5
M
AR
K D
ES
C
R
IP
TI
O
N D
AT
E
AP
PR
SHEET
IDENTIFICATION
C
D
A
B
U
SA
F
TH
C
IV
IL
E N
G
IN
EE
R
S Q
U
AD
R O
N , P
AF
B, F L
C O
N
TR
AC
T
N O
FA
-1 8-
D -0
TR
AC
ES
TE
C H
N
IC
AL
R
AN
G
E
AR
C H
IT
EC
T
EN
G
IN
EE
R
IN
G
SE
R
VI
C
ES
D
EL
IV
ER
Y N
O
Ne lso nE ng in ee ri ng Co rh od es b rit
C-101
M O
R R
EL
L
O
PE
R
AT
IO
N
S C
EN
TE
R (M
O C
S
IT
E
PL
AN
100%
DESIGN REVIEW ONLY
NOT FOR CONSTRUCTION
N
EL
SO
N
EN
G
IN
EE
R
IN
G
-1
2-
M J
O H
N
SO
N
J
TY
SO
N
B H
AR
VE
Y
D
BE
H
8-
XX
XX
XX
-X
X-
XX
D
BE
H
8-
IN
ST
AL
L
EM
ER
G
EN
C Y
M
AK
EU
P
W
AT
ER
F
O R
C R
IT
IC
AL
F
AC
IL
IT
IE
S
0 15 30 60
1"=30'
SCALE IN FEET
GRAPHIC SCALE
1. EXCAVATE APPROXIMATELY 120 SF OF EXISTING GRAVEL.
2. INSTALL NEW 3-INCH DIAMETER DEEP WELL TO AN APPROXIMATE DEPTH OF 180
FEET BELOW GROUND SURFACE. REFERENCE SPECIFICATION 33 11 13 FOR WELL
INSTALLATION REQUIREMENTS.
3. INSTALL APPROXIMATELY 25 SQUARE FEET OF 3,000 PSI TYPE 1 PORTLAND CEMENT,
NORMAL WEIGHT, CONCRETE PAD WITH BROOM FINISH CENTERED ON THE NEW
GROUNDWATER WELL. SIZE CONCRETE PAD TO ENABLE MOUNTING OF PUMP SKID
ENCLOSURE. SEE XY AND MOC FACILITIES WELL PIPING INSTALLATION DETAIL ON
SHEET C-501 FOR ALL INSTALLATION DETAILS.
4. INSTALL PUMP SKID IN ACCORDANCE WITH VENDOR SUBMITTED SHOP DRAWINGS.
REFER TO SPECIFICATION SECTION 23 21 23 AND CIVIL SHEET C-701 FOR PUMP SKID
REQUIREMENTS. SEE ELECTRICAL SHEETS FOR ELECTRICAL SUPPLY INFORMATION.
5. ROUTE APPROXIMATELY 25 LF OF 1-1/2 INCH, SCH 40, PVC FOR THE NEW
EMERGENCY MAKE UP WATER SUPPLY.
6. CONNECT TO EXISTING COOLING TOWER MAKE UP WATER SUPPLY AND BLOW DOWN
DRAIN.
7. BACKFILL AND COMPACT APPROXIMATELY 104 SF OF GRAVEL.
8. INSTALL THREE (3) TYPICAL CONCRETE BOLLARDS. SEE SHEET C-502 FOR DETAIL.
FLAG NOTES:
W
X
X X
X X
X X
X X
X X
X
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
W W
W W
W W
W W
W W
W W
W W
W W
TEE
TEE
TEE
HYDRANT
HS-60-09
SS
SS
SS
SS
SS
SS
SS
SS
SS
S
S
C O
XXXXXXX
X
XXXXXXXX
X X
X X
X X
X X
X X
X
X
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SDSD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
D
D
D
D
D
D
D
D
D
D
D
D
D
D
SD
W
W W
W W
W W
W W
W W
W
W W
W W
W W
W
W W
W W
W
W W
W W
W
W
W
TEE
TEE
HYDRANT
HS-60-10
TEE
HYDRANT
HS-60-01
TEE
TEE
TEE
TEE
TEE
HYDRANT
HS-60-09
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
S
S
S
S
S
C O
C O
C O
C O
C O
100%
DESIGN REVIEW ONLY
NOT FOR CONSTRUCTION
1. SAWCUT APPROXIMATELY 75 LF AND REMOVE APPROXIMATELY 162 SF OF
ASPHALT PAVEMENT.
2. INSTALL NEW 3-INCH DIAMETER DEEP WELL TO AN APPROXIMATE DEPTH OF
180 FEET BELOW GROUND SURFACE. REFERENCE SPECIFICATION 33 11 13 FOR
WELL INSTALLATION REQUIREMENTS. INSTALL TRAFFIC RATED HAND HOLE
ENCLOSURE OVER THE GROUNDWATER WELL AND FLUSH WITH SURROUNDING
GRADE IN ACCORDANCE WITH THE TSF AND EPF FACILITIES WELL PIPING
INSTALLATION DETAIL ON SHEET C-501.
3. ROUTE APPROXIMATELY 26 LF OF 2-1/2 INCH, SCH 40, PVC FOR THE NEW
EMERGENCY MAKE UP WATER SUPPLY. REFER TO UTILITY TRENCH DETAIL ON
SHEET C-501.
4. INSTALL PUMP SKID IN ACCORDANCE WITH VENDOR SUBMITTED SHOP
DRAWINGS. REFER TO SPECIFICATION SECTION 23 21 23 AND CIVIL SHEET
C-701 FOR PUMP SKID REQUIREMENTS. SEE ELECTRICAL SHEETS FOR
ELECTRICAL SUPPLY INFORMATION.
5. CONNECT TO EXISTING COOLING TOWER MAKE UP WATER SUPPLY AND BLOW
DOWN DRAIN.
6. REPAIR APPROXIMATELY 162 SF OF ASPHALT PAVEMENT. REFER TO ASPHALT
PAVEMENT DETAIL ON SHEET C-501.
FLAG NOTES:
1. AVERAGE MAKEUP WATER RATE 71 GPM.
2. TAKE ALL NECESSARY MEASURES TO PROTECT EXISTING TO REMAIN ITEMS
DURING DEMOLITION AND CONSTRUCTION.
3. LAWFULLY DISPOSE OF ALL MATERIALS REMOVED.
4. PATCH ALL HOLES CREATED BY THE REMOVAL OF PIPING OR OTHER ITEMS.
IN-FILL UNUSED OPENINGS WITH SAME MATERIAL, UNLESS NOTED OTHERWISE.
5. REFER TO SHEET C-701 FOR PUMP SKID REQUIREMENTS FOR MOC LOCATION.
6. COORDINATE FINAL LOCATION OF WELL AND PUMP SYSTEM EQUIPMENT WITH
FACILITY OWNER PRIOR TO START OF CONSTRUCTION.
SPECIFIC NOTES:
0 25 50 100
1"=50'
SCALE IN FEET
GRAPHIC SCALE
SCALE:
EASTERN PROCESSING FACILITY (EPF) - SITE PLAN
1" = 50'
N
SCALE:
ENLARGED PLAN VIEW
1" = 20'
N
A
B
2 3
C
D
1 2 3
4 5 6
AS
B
U
IL
T D
AT
E:
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
R
EV
IE
W
ED
B
Y:
D
AT
E:
4 5
M
AR
K D
ES
C
R
IP
TI
O
N D
AT
E
AP
PR
SHEET
IDENTIFICATION
C
D
A
B
U
SA
F
TH
C
IV
IL
E N
G
IN
EE
R
S Q
U
AD
R O
N , P
AF
B, F L
C O
N
TR
AC
T
N O
FA
-1 8-
D -0
TR
AC
ES
TE
C H
N
IC
AL
R
AN
G
E
AR
C H
IT
EC
T
EN
G
IN
EE
R
IN
G
SE
R
VI
C
ES
D
EL
IV
ER
Y N
O
Ne lso nE ng in ee ri ng Co rh od es b rit
C-102
EA
ST
ER
N
P R
O C
ES
SI
N G
F
AC
IL
IT
Y (E
PF
S
IT
E
PL
AN
100%
DESIGN REVIEW ONLY
NOT FOR CONSTRUCTION
N
EL
SO
N
EN
G
IN
EE
R
IN
G
-1
2-
M J
O H
N
SO
N
J
TY
SO
N
B H
AR
VE
Y
D
BE
H
8-
XX
XX
XX
-X
X-
XX
D
BE
H
8-
IN
ST
AL
L
EM
ER
G
EN
C Y
M
AK
EU
P
W
AT
ER
F
O R
C R
IT
IC
AL
F
AC
IL
IT
IE
S
0 10 20 40
1"=20'
SCALE IN FEET
GRAPHIC SCALE
C C
C C
C
W
MAIN
6 PVC
MAIN
6 PVC
MAIN
6 PVC
BACKFLOW
TEE HYDRANT
HI-11-04
VALVE
TEE HYDRANT
HI-11-05
VALVE
TEE
VALVE
VALVE
BACKFLOW
BACKFLOW
TEE
HYDRANT
HI-11-02
VALVE
VALVE
REDUCER
VALVE
VALVE
2x5x4x1x4x6
MH-263
8x8x6
MH-261B
8x8x6
MH-261A
2x5x4x2x3x5
MH-261
8x8x6
MH-261C
C C C C
C C
C C
C
C C
C C
C
C C
C
E
E
E
E
E
E
E
CC
C
C
C
C
8" W
P
VC
FW
FW
8' ' F
8' ' F
2' ' W
2' ' W
2'' W
FW
2'' W
MAIN
6 PVC
MAIN
6 PVC
MAIN
6 PVC
W
W
W
W
W W
W
TEE HYDRANT
HI-11-04
TEE HYDRANT
HI-11-05
TEE
TEE
HYDRANT
HI-11-02
REDUCER
SS
SS
SS
C O
C O
C O C
O
L
100%
DESIGN REVIEW ONLY
NOT FOR CONSTRUCTION
1. SAWCUT APPROXIMATELY 68 LF AND REMOVE APPROXIMATELY 94 SF OF ASPHALT
PAVEMENT. DO NOT DISTURB EXISTING CHILLER FOUNDATIONS.
2. INSTALL NEW 3-INCH DIAMETER DEEP WELL TO AN APPROXIMATE DEPTH OF 180 FEET
BELOW GROUND SURFACE. REFERENCE SPECIFICATION 33 11 13 FOR WELL
INSTALLATION REQUIREMENTS. INSTALL TRAFFIC RATED HAND HOLE ENCLOSURE
OVER THE GROUNDWATER WELL, FLUSH WITH SURROUNDING GRADE IN
ACCORDANCE WITH THE TSF AND EPF FACILITIES WELL PIPING INSTALLATION DETAIL
ON SHEET C-501.
3. ROUTE 1-1/2 INCH, SCH 40, PVC FOR THE NEW EMERGENCY MAKE UP SUPPLY AND
ELECTRICAL SERVICE IN COMMON TRENCH, APPROXIMATELY 28 LF. REFER TO
UTILITY TRENCH DETAIL ON SHEET C-501.
4. CONNECT TO EXISTING COOLING TOWER MAKE UP WATER SUPPLY AND BLOW DOWN
DRAIN.
5. INSTALL APPROXIMATELY 25 SQUARE FEET OF 3,000 PSI TYPE 1 PORTLAND CEMENT,
NORMAL WEIGHT, CONCRETE PAD WITH BROOM FINISH. SIZE CONCRETE PAD TO
ENABLE MOUNTING OF PUMP SKID ENCLOSURE. SEE PUMP SKID CONCRETE PAD
DETAIL ON SHEET C-502 FOR INSTALLATION DETAILS.
6. INSTALL PUMP SKID IN ACCORDANCE WITH VENDOR SUBMITTED SHOP DRAWINGS.
REFER TO SPECIFICATION SECTION 23 21 23 AND CIVIL SHEET C-701 FOR PUMP SKID
REQUIREMENTS. SEE ELECTRICAL SHEETS FOR ELECTRICAL SUPPLY INFORMATION.
7. REPAIR APPROXIMATELY 94 LF OF ASPHALT PAVEMENT. REFER TO ASPHALT
PAVEMENT REPAIR DETAIL ON SHEET C-501.
8. MINIMIZE CLEARANCE BETWEEN WELL AND EXISTING WALL BASED ON VENDOR'S
INSTALLATION REQUIREMENTS.
9. INSTALL FIVE (5) TYPICAL CONCRETE BOLLARDS. SEE SHEET C-502 FOR DETAIL.
10. WELL PUMP AND EQUIPMENT FINAL LOCATION TO BE CHOSEN FROM PRIMARY OR
SECONDARY LOCATIONS DEPENDING ON TIME OF INSTALLATION. CONTRACTOR TO
COORDINATE LOCATION WITH USER PRIOR TO CONSTRUCTION.
FLAG NOTES:
1. AVERAGE MAKEUP WATER RATE 19 GPM.
2. TAKE ALL NECESSARY MEASURES TO PROTECT EXISTING TO REMAIN ITEMS DURING
DEMOLITION AND CONSTRUCTION.
3. LAWFULLY DISPOSE OF ALL MATERIALS, DRILL CUTTINGS, AND WATER USED TO AN
OFFSITE LOCATION.
4. PATCH ALL HOLES CREATED BY THE REMOVAL OF PIPING OR OTHER ITEMS. IN-FILL
UNUSED OPENINGS WITH SAME MATERIAL, UNLESS NOTED OTHERWISE.
5. REFER TO SHEET C-701 FOR PUMP SKID REQUIREMENTS FOR MOC LOCATION.
6. COORDINATE FINAL LOCATION OF WELL AND PUMP SYSTEM EQUIPMENT WITH
FACILITY OWNER PRIOR TO START OF CONSTRUCTION.
SPECIFIC NOTES:
0 15 30 60
1"=30'
SCALE IN FEET
GRAPHIC SCALE
SCALE:
TECH SUPPORT FACILITY (TSF) - SITE PLAN
1" = 30'
N
SCALE:
ENLARGED PLAN VIEW
1" = 10'
N
A
B
2 3
C
D
1 2 3
4 5 6
AS
B
U
IL
T D
AT
E:
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
R
EV
IE
W
ED
B
Y:
D
AT
E:
4 5
M
AR
K D
ES
C
R
IP
TI
O
N D
AT
E
AP
PR
SHEET
IDENTIFICATION
C
D
A
B
U
SA
F
TH
C
IV
IL
E N
G
IN
EE
R
S Q
U
AD
R O
N , P
AF
B, F L
C O
N
TR
AC
T
N O
FA
-1 8-
D -0
TR
AC
ES
TE
C H
N
IC
AL
R
AN
G
E
AR
C H
IT
EC
T
EN
G
IN
EE
R
IN
G
SE
R
VI
C
ES
D
EL
IV
ER
Y N
O
Ne lso nE ng in ee ri ng Co rh od es b rit
C-103
TE
C
H S
U
PP
O R
T
FA
C
IL
IT
Y
(T
SF
S
IT
E
PL
AN
100%
DESIGN REVIEW ONLY
NOT FOR CONSTRUCTION
N
EL
SO
N
EN
G
IN
EE
R
IN
G
-1
2-
M J
O H
N
SO
N
J
TY
SO
N
B H
AR
VE
Y
D
BE
H
8-
XX
XX
XX
-X
X-
XX
D
BE
H
8-
IN
ST
AL
L
EM
ER
G
EN
C Y
M
AK
EU
P
W
AT
ER
F
O R
C R
IT
IC
AL
F
AC
IL
IT
IE
S
W
0 5 10 20
1"=10'
X
X
X
MAIN
6 TBD
SERVICE
TBD TBD
SERVICE
TBD TBD
HYDRANT
HI-22-03
VALVE
NG
C
C
C
C
C
C
C
C
C
C
E
E
E
E
E
E
E
E
E
E
E
E E
E E
E
E
E
E
E
E E
E
E
E
E
E
E
E
E
ABANDONED
TBD TBD
MAIN
6 TBD
SERVICE
TBD TBD
SERVICE
TBD TBD
W
W
W
W
W
W
W
W
W
W
HYDRANT
HI-22-03
SSSS
SS
W
X
X
X
X
X X
X
X
X
X
X
X
X
X X
X
X
X
X
MAIN
6 DI
MAIN
TBD TBD
MAIN
8 TBD
MAIN
6 TBD
SERVICE
TBD TBD
SERVICE
TBD TBD
SERVICE
TBD TBD
SERVICE
TBD TBD
SERVICE
TBD TBD
SERVICE
TBD TBD
TEE
TEE
TEE
TEE
HYDRANT
HI-22-03
HYDRANT
HI-22-02
REDUCER
VALVE
VALVE
VALVE
VALVE
VALVE
VALVE
VALVE
VALVE
VALVE
VALVE
NG
NG
NG
NG
C
C
C
C
C
C
C
C
C
C
CC
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C C C
C
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E E
E
E
E
E
E
E
C
E
E
E
E
E
E
E
E
E
E
E
E
E
E
12"AC
12"AC
8"
8"
ABANDONED
TBD TBD
MAIN
6 DI
MAIN
TBD TBD
MAIN
8 TBD
MAIN
6 TBD
SERVICE
TBD TBD
SERVICE
TBD TBD
SERVICE
TBD TBD
SERVICE
TBD TBD
SERVICE
TBD TBD
SERVICE
TBD TBD
AIP
AIP
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
AI
P
AI
P
W
W
W
W
W
W
W W
W
TEE
TEE
TEE
TEE
HYDRANT
HI-22-03
HYDRANT
HI-22-02
REDUCER
W
W
AI
P
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
AIP
AIP
AIP
S
S
S
S
S
L
FM
FM
L
100%
DESIGN REVIEW ONLY
NOT FOR CONSTRUCTION
1. INSTALL AND MAINTAIN 65 LF OF SILT FENCE (APPROXIMATE LOCATION);
REMOVE UPON COMPLETION. REFER TO TYPICAL SILT FENCE DETAIL ON
SHEET C-501.
2. EXCAVATE APPROXIMATELY 102 SF OF SOD.
3. SAWCUT APPROXIMATELY 60 LF AND REMOVE APPROXIMATELY 100 SF OF
ASPHALT PAVEMENT. DO NOT DISTURB ANY EXISTING UTILITY LINES.
4. INSTALL NEW 3-INCH DIAMETER DEEP WELL TO AN APPROXIMATE DEPTH OF
180 FEET BELOW GROUND SURFACE. REFERENCE SPECIFICATION 33 11 13 FOR
WELL INSTALLATION REQUIREMENTS.
5. INSTALL APPROXIMATELY 25 SQUARE FEET OF 3,000 PSI TYPE 1 PORTLAND
CEMENT, NORMAL WEIGHT, CONCRETE PAD WITH BROOM FINISH CENTERED
ON THE NEW GROUNDWATER WELL. SIZE CONCRETE PAD TO ENABLE
MOUNTING OF PUMP SKID ENCLOSURE. SEE XY AND MOC FACILITIES WELL
PIPING INSTALLATION DETAIL ON SHEET C-501 FOR INSTALLATION DETAILS.
6. INSTALL PUMP SKID IN ACCORDANCE WITH VENDOR SUBMITTED SHOP
DRAWINGS. REFER TO SPECIFICAITON SECTION 23 21 23 AND CIVIL SHEET
C-701 FOR PUMP SKID REQUIREMENTS. SEE ELECTRICAL SHEETS FOR
ELECTIRCAL SUPPLY INFORMATION.
7. ROUTE APPROXIMATELY 13 LF OF 1-1/2 INCH, SCH 40, PVC FOR THE NEW
EMERGENCY MAKE UP WATER SUPPLY.
8. CONNECT TO EXISTING COOLING TOWER MAKE UP WATER SUPPLY AND BLOW
DOWN DRAIN.
9. REPAIR APPROXIMATELY 100 SF OF ASPHALT PAVEMENT. REFER TO ASPHALT
PAVEMENT DETAIL ON SHEET C-501.
10. BACKFILL AND COMPACT APPROXIMATELY 86 SF OF SOD.
FLAG NOTES:
1. AVERAGE MAKEUP WATER RATE 30 GPM.
2. TAKE ALL NECESSARY MEASURES TO PROTECT EXISTING TO REMAIN ITEMS
DURING DEMOLITION AND CONSTRUCTION.
3. LAWFULLY DISPOSE OF ALL MATERIALS, DRILL CUTTINGS, AND WATER USED
TO AN OFFSITE LOCATION.
4. PATCH ALL HOLES CREATED BY THE REMOVAL OF PIPING OR OTHER ITEMS.
IN-FILL UNUSED OPENINGS WITH SAME MATERIAL, UNLESS NOTED OTHERWISE.
5. REFER TO SHEET C-701 FOR PUMP SKID REQUIREMENTS FOR MOC LOCATION.
6. COORDINATE FINAL LOCATION OF WELL AND PUMP SYSTEM EQUIPMENT WITH
FACILITY OWNER PRIOR TO START OF CONSTRUCTION.
SPECIFIC NOTES:
0 15 30 60
1"=30'
SCALE IN FEET
GRAPHIC SCALE
SCALE:
XY COMM BUILDING (XY) - SITE PLAN
1" = 30'
N
SCALE:
ENLARGED PLAN VIEW
1" = 10'
N
A
B
2 3
C
D
1 2 3
4 5 6
AS
B
U
IL
T D
AT
E:
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
R
EV
IE
W
ED
B
Y:
D
AT
E:
4 5
M
AR
K D
ES
C
R
IP
TI
O
N D
AT
E
AP
PR
SHEET
IDENTIFICATION
C
D
A
B
U
SA
F
TH
C
IV
IL
E N
G
IN
EE
R
S Q
U
AD
R O
N , P
AF
B, F L
C O
N
TR
AC
T
N O
FA
-1 8-
D -0
TR
AC
ES
TE
C H
N
IC
AL
R
AN
G
E
AR
C H
IT
EC
T
EN
G
IN
EE
R
IN
G
SE
R
VI
C
ES
D
EL
IV
ER
Y N
O
Ne lso nE ng in ee ri ng Co rh od es b rit
C-104
XY
C
O M
M B
U
IL
D
IN
G (X
Y)
SI
TE
P
LA
N
100%
DESIGN REVIEW ONLY
NOT FOR CONSTRUCTION
N
EL
SO
N
EN
G
IN
EE
R
IN
G
-1
2-
M J
O H
N
SO
N
J
TY
SO
N
B H
AR
VE
Y
D
BE
H
8-
XX
XX
XX
-X
X-
XX
D
BE
H
8-
IN
ST
AL
L
EM
ER
G
EN
C Y
M
AK
EU
P
W
AT
ER
F
O R
C R
IT
IC
AL
F
AC
IL
IT
IE
S
0 5 10 20
1"=10'
1. SUBMIT A DIG PERMIT TO THE CONTRACTING OFFICER AT LEAST FOURTEEN
(14) DAYS PRIOR TO EXCAVATION.
2. FIELD LOCATE AND PERFORM EXCAVATION BY HAND WITHIN FIVE (5) FEET OF
ALL EXISTING UTILITIES AS TO LOCATION AND ELEVATION. NOTIFY THE
CONTRACTING OFFICER OF ANY AND ALL CONFLICTS PRIOR TO BEGINNING
CONSTRUCTION.
3. BACKFILLING NOT TO BEGIN UNTIL CONSTRUCTION BELOW FINISH GRADE AND
ALL. UNDERGROUND UTILITIES SYSTEMS HAVE BEEN INSPECTED, TESTED AND
APPROVED BY THE CONTRACTING OFFICER, FORMS REMOVED, AND THE
EXCAVATION CLEANED OF TRASH AND DEBRIS.
4. BACKFILL AND COMPACT TRENCH WITH NATIVE SOIL TO 95% OF THE SOIL
MATERIAL MODIFIED PROCTOR DRY UNIT DENSITY.
5. PROVIDE FINISH GRADES OVER TRENCHES THAT ARE BUILT-UP OR CROWNED
A MINIMUM OF THREE (3) INCHES ABOVE THE EXISTING GRADE.
6. REFER TO SHEET C-701 FOR PUMP CONTROL SEQUENCE OF OPERATIONS AND
PUMP CONTROLLER REQUIREMENTS.
7. INSTALL NEW 1-1/4 INCH PITLESS ADAPTER INTO EACH WELL HEAD AT A
MINIMUM OF FOUR (4) INCHES ABOVE CONCRETE PAD.
8. INSTALL 120 GALLON PRESSURE TANK FOR ALL FACILITIES.
9. NEW WELLS ARE NOT PERMITTED TO BE CONSTRUCTED IN BASEMENTS, WELL
PITS, OR IN A BUILDING OTHER THAN A WELL HOUSE.
10. PROVIDE PUMP SKID ENCLOSURE FOR ALL OUTDOOR EQUIPMENT. REFERENCE
SPECIFICATION SECTION 23 21 23 FOR ENCLOSURE.
11. EXISTING COOLING TOWER MAKE UP WATER SYSTEM HAS A BACK FLOW
PREVENTER TO POTABLE WATER SYSTEM.
12. AT THE XY AND MOC FACILITIES, INSTALL A CONCRETE PAD CENTERED ON THE
GROUNDWATER WELL PIPE. INSTALL GROUNDWATER WELL CEMENT GROUT
SEAL FLUSH WITH GROUNDWATER WELL CONCRETE PAD. EXTEND OUTER
CASTING A MINIMUM OF 12 INCHES ABOVE GRADE AND INSTALL A WELL CAP.
SPECIFIC NOTES:
A
B
2 3
C
D
1 2 3
4 5 6
AS
B
U
IL
T D
AT
E:
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
R
EV
IE
W
ED
B
Y:
D
AT
E:
4 5
M
AR
K D
ES
C
R
IP
TI
O
N D
AT
E
AP
PR
SHEET
IDENTIFICATION
C
D
A
B
U
SA
F
TH
C
IV
IL
E N
G
IN
EE
R
S Q
U
AD
R O
N , P
AF
B, F L
C O
N
TR
AC
T
N O
FA
-1 8-
D -0
TR
AC
ES
TE
C H
N
IC
AL
R
AN
G
E
AR
C H
IT
EC
T
EN
G
IN
EE
R
IN
G
SE
R
VI
C
ES
D
EL
IV
ER
Y N
O
Ne lso nE ng in ee ri ng Co rh od es b rit
C-501
C
IV
IL
D
ET
AI
LS
I
100%
DESIGN REVIEW ONLY
NOT FOR CONSTRUCTION
N
EL
SO
N
EN
G
IN
EE
R
IN
G
-1
2-
M J
O H
N
SO
N
J
TY
SO
N
B H
AR
VE
Y
D
BE
H
8-
XX
XX
XX
-X
X-
XX
D
BE
H
8-
IN
ST
AL
L
EM
ER
G
EN
C Y
M
AK
EU
P
W
AT
ER
F
O R
C R
IT
IC
AL
F
AC
IL
IT
IE
S
FINISHED GRADEEXCAVATED TRENCH
24"
BACKCUT OR SLOPE
TRENCH WALL TO TOP
OF PIPE AS NEEDED
FLAT TAMP
PIPE ZONE
(SIDE TAMP)
16" BACKFILL
MAGNETIC WARNING TAPE
12 " BELOW GRADE
8" COVER MATERIAL
2" HAUNCHING
6" BEDDING SAND EXISTING SUBGRADE
3" MAKEUP WATER
SUPPLY
BOTTOM OF TRENCH
SCALE:
RAW WATER TRENCH SECTION
N.T.S.
18" MIN
SILT FLOW
FILTER FABRIC
WOOD POST @ 10' O.C.
MIN 1" x 2" x 3'
GEOTEXTILE SILT SCREEN
STAPLE TO POST
TRENCH MIN 4" x 4"
BURY MIN 8" OF FABRIC IN TRENCH
SECTION ELEVATION
NOTES:
1. AFTER EACH STORM EVENT, INSPECT THE SILT FENCE. REMOVE SEDIMENT
DEPOSITS AND REPAIR WASHOUTS/STRUCTURAL FAILURES.
2. ATTACH TWO SILT FENCES BY PLACING THE END POST OF THE SECOND FENCE
INSIDE THE END POST OF THE FIRST FENCE. ROTATE BOTH POSTS AT LEAST 180
DEGREES IN A CLOCKWISE DIRECTION TO CREATE A TIGHT SEAL WITH THE FABRIC
MATERIAL. DRIVE BOTH POSTS 18 INCH INTO THE GROUND AND BURY FLAP.
3. REMOVE SILT FENCE ONLY AFTER DISTURBED AREAS HAVE BEEN STABILIZED.
SCALE:
EROSION CONTROL - SILT FENCE
N.T.S.
INSTALL GROUNDWATER WELL
CEMENT GROUT SEAL FLUSH WITH
GROUNDWATER WELL CONCRETE PAD
EDGE OF DRILL HOLE
EIGHT (8) INCH DIA PVC
OUTER CASING
THREE (3) INCH DIA PVC
INNER CASING
GEOLOGIC HAWTHORN FORMATION
8"
GROUNDWATER WELL
CONCRETE PAD
#5 REBAR 12" OC EW
#57 STONE
SUBGRADE
4"
10 MIL VAPOR BARRIER
SCALE:
XY AND MOC FACILITIES WELL PIPING INSTALLATION DETAIL
N.T.S.
1. AT THE TSF AND EPF FACILITIES, TERMINATE OUTER WELL CASING 24 INCHES
BELOW GRADE AND INSTALL A WELL SEAL. INSTALL BALL VALVE AND PVC CAP
18 INCHES BELOW GRADE AND COVER WITH A CONCAST HEAVY TRAFFIC
HANDHOLE PART NUMBER FHR-24-30-30 OR APPROVED EQUAL. INSTALL IN
ACCORDANCE WITH MANUFACTURERS INSTRUCTIONS.
FLAG NOTES:
EXTEND OUTER
CASING A MIN 12
INCHES ABOVE GRADE
SCALE:
TSF AND EPF FACILITIES WELL PIPING INSTALLATION DETAIL
N.T.S.
3" PVC TEE
BALL VALVE
SCALE:
PUMP SKID CONFIGURATION DETAIL
N.T.S.
RELIEF VALVE
CHECK VALVE
TEMPORARY
CONNECTION POINT
WATER METER
PUMP
SCHEDULE 80 PVC PIPE
CEMENT GROUT
PIPE ROUTED TO
FACILITY MAKEUP
WATER PIPE
BACKFLOW
PREVENTER
PRESSURE
TANK
PRESSURE
TRANSDUCER
INTERIOR SIDE
OF BUILDING
EXTERIOR SIDE OF
BUILDING
3" PVC TEE
WATERTIGHT PVC CAPBALL VALVE
BALL VALVE
ROUTE PIPE TO EXISTING
BLOWDOWN PIPE
EDGE OF DRILL HOLE
EIGHT (8) INCH DIA PVC
OUTER CASING
THREE (3) INCH DIA PVC
INNER CASING
GEOLOGIC HAWTHORN FORMATION
EXISTING
ASPHALT
H20 RATED TRAFFIC
HANDHOLE
PUMP SKID EQUIPMENT
WELL SEAL
SCALE:
TSF AND EPF FACILITIES WELL PIPING INSTALLATION DETAIL
N.T.S.
STRAINER
CARTRIDGE FILTER
HOUSING (2)
SCALE:
FILTER HOUSING CONFIGURATION DETAIL
N.T.S.
TO PUMP SKID
MAKE BOTH ENDS OF
STRAINER FLANGE TO
FLANGE CONNECTIONS
BALL VALVE FILTER HOUSING
2" PIPE
WELL CAP WITH INTEGRAL
OUTLET CONNECTION
B
2 3
C
D
1 2 3
4 5 6
AS
B
U
IL
T D
AT
E:
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
R
EV
IE
W
ED
B
Y:
D
AT
E:
4 5
M
AR
K D
ES
C
R
IP
TI
O
N D
AT
E
AP
PR
SHEET
IDENTIFICATION
C
D
A
B
U
SA
F
TH
C
IV
IL
E N
G
IN
EE
R
S Q
U
AD
R O
N , P
AF
B, F L
C O
N
TR
AC
T
N O
FA
-1 8-
D -0
TR
AC
ES
TE
C H
N
IC
AL
R
AN
G
E
AR
C H
IT
EC
T
EN
G
IN
EE
R
IN
G
SE
R
VI
C
ES
D
EL
IV
ER
Y N
O
Ne lso nE ng in ee ri ng Co rh od es b rit
C-502
C
IV
IL
D
ET
AI
LS
II
100%
DESIGN REVIEW ONLY
NOT FOR CONSTRUCTION
N
EL
SO
N
EN
G
IN
EE
R
IN
G
-1
2-
M J
O H
N
SO
N
J
TY
SO
N
B H
AR
VE
Y
D
BE
H
8-
XX
XX
XX
-X
X-
XX
D
BE
H
8-
IN
ST
AL
L
EM
ER
G
EN
C Y
M
AK
EU
P
W
AT
ER
F
O R
C R
IT
IC
AL
F
AC
IL
IT
IE
S
4'-0"
SIX (6) INCH DIAMETER HOT DIP GALVANIZED
STEEL PIPE BOLLARD
EXISTING GRADE
QUANTITY 2, 1/2" DIA X 3"
LONG HEAD STUDS (GALV)
WELDED TO BOLLARD
3,000 PSI CAST IN PLACE
CONCRETE FOUNDATION 2'-6"
SCALE:
TYPICAL BOLLARD DETAIL
N.T.S.
1'-6"
#57 STONE
BURIED WATER PIPE
NATIVE BACKFILL
UTILITY BEDDING
SAND AND COVER
COMPACTED SUBGRADE
PAVEMENT RESTORATION
PARAMETERS
TRENCH WIDTH1'-0"
24" MIN
EXISTING ASPHALT
PAVEMENT TO REMAIN EXISTING BASE COURSE
SAWCUT
P-603 BITUMINOUS TACK COAT
1'-0"
4" BITUMINOUS SURFACE
COURSE
(2 - 2" LIFTS) (P-401)
BITUMINOUS PRIME COAT
SUBGRADE STABILIZATION
(P-601)
DETECTABLE TAPE
6"
6"
UNDISTURBED EARTH (TYP)
SCALE:
ASPHALT RESTORATION DETAIL
N.T.S. SCALE:
PUMP SKID CONCRETE PAD DETAIL
N.T.S.
8"
EXISTING GRADE
3,000 PSI CONCRETE SLAB
EXISTING GRADE#5 REBAR 12" OC EW
4"
4"
4" #57 STONE
SUBGRADE
1'-0"
1. INSTALL ASPHALT PAVEMENT MATERIALS IN ACCORDANCE WITH THE
FOLLOWING STANDARDS LISTED IN THE FEDERAL AVIATION ADMINISTRATION
DOCUMENT150/5370-10H, STANDARD SPECIFICATIONS FOR CONSTRUCTION OF
AIRPORTS:
· ITEM P-401 ASPHALT MIX PAVEMENT;
· ITEM P-602 EMULSIFIED ASPHALT PRIME COAT;
· ITEM P-603 EMULSIFIED ASPHALT TACK COAT.
2. INSTALL 7" X 60" HDPE YELLOW BOLLARD COVER AT ALL BOLLARD LOCATIONS.
SPECIFIC NOTES:
10 MIL VAPOR
BARRIER
B
2 3
C
D
1 2 3
4 5 6
AS
B
U
IL
T D
AT
E:
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
R
EV
IE
W
ED
B
Y:
D
AT
E:
4 5
M
AR
K D
ES
C
R
IP
TI
O
N D
AT
E
AP
PR
SHEET
IDENTIFICATION
C
D
A
B
U
SA
F
TH
C
IV
IL
E N
G
IN
EE
R
S Q
U
AD
R O
N , P
AF
B, F L
C O
N
TR
AC
T
N O
FA
-1 8-
D -0
TR
AC
ES
TE
C H
N
IC
AL
R
AN
G
E
AR
C H
IT
EC
T
EN
G
IN
EE
R
IN
G
SE
R
VI
C
ES
D
EL
IV
ER
Y N
O
Ne lso nE ng in ee ri ng Co rh od es b rit
C-701
PU
M
P
SK
ID
S
YS
TE
M R
EQ
U
IR
EM
EN
TS
100%
DESIGN REVIEW ONLY
NOT FOR CONSTRUCTION
N
EL
SO
N
EN
G
IN
EE
R
IN
G
-1
2-
M J
O H
N
SO
N
J
TY
SO
N
B H
AR
VE
Y
D
BE
H
8-
XX
XX
XX
-X
X-
XX
D
BE
H
8-
IN
ST
AL
L
EM
ER
G
EN
C Y
M
AK
EU
P
W
AT
ER
F
O R
C R
IT
IC
AL
F
AC
IL
IT
IE
S
PRESSURE TANK SCHEDULE
LOCATION MANUFACTURER MODEL NO.
TANK VOLUME
(GAL.)
CONNECTION
SIZE
MAX PRESSURE
(PSI) HEIGHT DIAMETER
WEIGHT
(LBS)
EPF, XY,
MOC,
TSF AMTROL WX-350 119 1-1/4" 150 61-7/8" 26" 146
EQUIPMENT
TAG
EPF-MTK1
XY-MTK1
MOC-MTK1
TSF-MTK1
CARTRIDGE FILTER SCHEDULE
LOCATION MANUFACTURER
HOUSING
PART NO.
MAXIMUM
FLOW
(GPM)
AVERAGE
FLOW
(GPM)
MAXIMUM
WORKING
PRESSURE
MICRON
RATING
FILTER
TYPE
MAXIMUM
PRESSURE
DROP PIPE SIZE
XY/TSF/
MOC BIG BUBBA BBH-150 150 73.7 125 150 PLEATED 30 2"
EPF BIG BUBBA BBH-150 150 106.1 125 150 PLEATED 30 2"
EQUIPMENT
TAG
XY-MFIL1
MOC-MFIL1
TSF-MFIL1
EPF-MFIL1
PUMP SCHEDULE
PUMP MOTOR BASIS OF DESIGN
EQUIPMENT TAG LOCATION TYPE GPM SERIES MANUFACTURER MODEL
EPF-MP1 EPF
CLOSE
COUPLED WATER@60F 110 E-1531 1.25AD
TSF-MP1, XY-MP1,
MOC-MP1
CLOSE
COUPLED 65 1.25ADTSF, XY, MOC WATER@60F
FLUID FT. HD.
EFFICIENCY (%)
68%
58%
NPSH (FT)
HP
7.5
7.5
RPM
VOLT/PH/HZ
460/3/60
460/3/60
BELL AND GOSSET
BELL AND GOSSET
PUMP SYSTEM DESIGN INTENT:
1. PUMP SKID SYSTEM WILL BE USED AS AN AUTOMATED EMERGENCY
BACKUP TO COOLING TOWER MAKEUP WATER DURING LOSS OF SITE
WATER UTILITY PRESSURE. SYSTEM WILL MONITOR LOCAL TOWER
MAKEUP WATER SUPPLY PRESSURE AND ACTIVATE WHEN PRESSURE
FALLS BELOW DESIGN SETPOINT FOR A USER SPECIFIED AMOUNT OF TIME.
FILTRATION SYSTEM IS INTENDED TO MINIMIZE SUSPENDED SOLIDS AND
PARTICULATES INTRODUCED TO THE COOLING TOWER SYSTEM FROM THE
WELL WATER SUPPLY. WHEN NORMAL MAKEUP WATER OPERATION IS
RESUMED, MAINTENANCE PERSONNEL WILL NEED TO FLUSH THE COOLING
TOWER SYSTEM AND TEST WATER QUALITY WITHIN THE HVAC SYSTEM TO
ENSURE CHLORIDE, SALINITY AND TOTAL DISSOLVED SOLIDS ARE WITHIN
ACCEPTABLE LIMITS.
1. ENSURE THAT PUMP SKID IS PROVIDED WITH SINGLE POINT ELECTRICAL
INTERFACE CONNECTION AND INTEGRAL MEANS OF DISCONNECT COMPLIANT
WITH NFPA 70.
2. EQUIPMENT MANUFACTURER AND MODEL NUMBERS IN SCHEDULES ARE
LISTED AS BASIS OF DESIGN OR APPROVED EQUAL.
SPECIFIC NOTES:
E-1531
PUMP SKID SEQUENCE OF OPERATIONS:
1. PUMP SYSTEM MUST HAVE AUTOMATIC AND MANUAL OPERATING MODES
WITH CAPABILITY TO BE REMOVED FROM SERVICE (TURNED OFF) AT THE
PUMP LOCATION.
2. SWITCHING BETWEEN MODES MUST BE SELECTABLE LOCALLY THROUGH
USE OF A HAND-OFF-AUTOMATIC (H-O-A) SWITCH.
3. PROVIDE ADDITIONAL FEATURES AND CAPABILITIES AS NOTED BELOW FOR
FUTURE CONNECTION OF REMOTE SHUTDOWN FUNCTIONALITY…