USArmyCorpsofEngineers
OmahaDistrict
API653In‐Service
InspectionReport
U.S.ArmyGarrisonKwajaleinAtoll
FacilityNumber962
TankNumber6
USArmyCorpsofEngineersCenterofExpertiseforPetroleum,Oils,andLubricants
(USACEPOL‐MCX)
September29,2017

API 653 In‐Service Inspection Report USAG Kwajalein‐Atoll

TableofContents
ACRONYMSANDABBREVIATIONS .............................................................................................................................................. 3

GENERAL SUMMARY

INSPECTION DATE

STATE REGULATIONS

PREVIOUS INSPECTION DATES

RECOMMENDED FUTURE INSPECTION DATES (CALCULATIONS SHALL BE PROVIDED)

GENERAL TANK INFORMATION

A. GENERAL PROJECT INFORMATION

1. API 653 Inspection

2. Site Information

B. TANK INSPECTION COMMENTS

1. Tank Construction

2. Tank Foundation

3. Tank Shell

4. Tank Appurtenances

5. Tank Coating

6. Tank Piping System

7. Fire Protection System

8. Secondary Containment

9. Cathodic Protection

C. FINDINGS AND RECOMMENDATIONS

1. MANDATORY REPAIRS per API 653, UFC 3‐460‐01, or AW 78‐24‐27 Standards

2. REQUIRED REPAIRS to Fully Comply with API 653 or Federal, State, and Local Codes…………………………………..11

3. RECOMMENDED REPAIRS as Part of Regular Maintenance………………………………………………………………………….23

APPENDIX A: ENGINEERING CALCULATIONS AND DRAWINGS…………………………………………………………………………...32

A.1 SHELL SERVICE LIFE EVALUATION

A.2 SHELL SETTLEMENT EVALUATION

A.3 ULTRASONIC UT DATA

A.4 CONTAINMENT LAYOUT DRAWING

A.5 SHELL LAYOUT DRAWING

A.6 OSHA ACCESS STRUCTURE REPORT

APPENDIX B: 3‐D DOCUMENTATION AND ANALYSIS

APPENDIX C: API 653 CHECKLISTS FOR TANK INSPECTIONS

APPENDIX D: PHOTOGRAPHS

API 653 In‐Service Inspection Report USAG Kwajalein‐Atoll

ACRONYMS AND ABBREVIATIONS

API American Petroleum Institute

ASME American Society of Mechanical Engineers

ASNT American Society of Non‐Destructive Testing

ARD Anti‐rotation device

ATG Automatic Tank Gauge

BBL Barrel

CFR Code of Federal Regulations

CP Cathodic Protection

DFT Dry Film Thickness

HLA High Level Alarm

HLCS High Level Control Shutoff

HHLA High‐High Level Alarm

LLA Low Level Alarm

LLLA Low‐Low Level Alarm

MFL Magnetic Flux Leakage

MT Magnetic Particle Testing

NACE National Association of Corrosion Engineers

NDT Non‐Destructive Testing

NFPA National Fire Protection Association

PSI Pounds per Square Inch

PT Penetrant Testing

P/V Pressure/Vacuum

RP Recommended Practice

PST Product Saver Tank

RT Radiography Testing

TML Thickness Measurement Location

TRV Thermal Relief Valve

UFC Unified Facilities Criteria

UFGS Unified Facilities Guide Specifications

ULS Ultra Low Sulfur

UT Ultrasonic Testing

VT Visual Testing

VPI Valve Position Indicator

API 653 In‐Service Inspection Report USAG Kwajalein‐Atoll

GENERALSUMMARY
SummaryofInspection
AnAPIStandard653In‐ServiceinspectionofTank6(Facility962)atUSAGKwajalein‐Atoll,Republicofthe
MarshallIslandswascompletedonSeptember29,2017toevaluatethetank’sintegrity,collectdata,andestablisha
databaseforfutureinspectionsandevaluations.Theshellservicelifeevaluationperformedashavinggreaterthan
30yearsofremainingshelllifeundercurrentconditions.InspectionResultsarelistedinSectionC.

API 653 In‐Service Inspection Report USAG Kwajalein‐Atoll

INSPECTIONDATE
APIIn‐Service(External)InspectionDate:29September2017

Equipment (s) Used:

UltrasonicThickness(A‐scan/B‐scan)Testing
Manufacturer:GeneralElectric
Model:DMSGo+
CalibrationMethodsUsed:ZeroingProcedure,CopperCoatingCalibrationProcedure,andTwoPoint

Calibration Procedure

TankSettlementSurveying
Manufacturer:NorthwestInstrument
Model:NRL802KRotatingwithNLD5GLaserReceiver
CalibrationMethodsUsed:Mainandtransversehorizontalaxeschecksat100ft.≤1/16inch
TankShellSurveying
Manufacturer:LeicaGeosystem
Model:3DDisto
CalibrationMethodsUsed:Tiltsensorcalibrationautomaticallyperformedwithunitsetat<3°and

crosshairs calibration using target at a distance > 25 m

Inspector(s): Benyam Berhane

STATEREGULATIONS
StateRegulationforAPIIn‐ServiceTankInspectionsN/A
StateRegulationforAPIOut‐of‐ServiceTankInspectionsN/A
NOTE:Iftherearenostateregulationsfortankinspections,thenN/Ashallresidein‐placeofthenumberofyears
betweeninspections.Ifstateregulationsreside,therecommendedfutureinspectiondatesshallbebasedon
whicheverismorestringentbetweentheAPIinspector’scalculationsandthestateregulations.
PREVIOUSINSPECTIONDATES
APIOut‐of‐Service(Internal)InspectionDate:21March2010
APIIn‐Service(External)InspectionDate:21March2010(Norecordof2015Inspection)
RECOMMENDEDFUTUREINSPECTIONDATES(CALCULATIONSSHALLBEPROVIDED)
APIOut‐of‐Service(Internal)InspectionDate:21March2037PerAPI653Section6.4.2‐Initial

service for refurbished AST (21 March 2020 IAW

UFC)

API In‐Service (External) Inspection Date: 29 September 2022

BenyamBerhane
MechanicalEngineer/Sr.Inspector
InterSpec,LLC
API653CertifiedInspectorNo.28492

API 653 In‐Service Inspection Report USAG Kwajalein‐Atoll

GENERAL TANK INFORMATION

ITEMDESCRIPTION
OwnerU.SArmy
LocationU.S.ArmyGarrisonKwajaleinAtoll;RMI
FacilityNumber962
TankNumber6
State/CountryKwajaleinAtoll/ RepublicofMarshallIslands
City‐
InspectionDate29September2017
TankManufacturerUnknown
DesignStandardUnknown(AssumedAPISTD12CEleventhEdition)
DateofConstruction1954
TankContentsJP‐5(F‐44)
TankSerialNumberNone
TankDiameter60Feet
ShellHeight54Feet
ProductHeight49.5Feet
TankCapacity27,500BBL(1,134,000gallons)
FoundationConcreteRingWall

Construction

Bottom Lap‐Welded (Cone‐Down)

Shell Butt‐Welded (Cylindrical)

Floating Roof None

Fixed Roof Aluminum Geodesic Dome

Material

Bottom Carbon Steel (Unknown Specification)

Shell Carbon Steel (Unknown Specification)

Floating Roof NA

FixedRoofAluminum(UnknownSpecification)
CathodicProtectionImpressedCurrent
InteriorCoatingSystemThinFilmEpoxy(CompletedApril2012)
ExteriorCoatingSystemThinFilmEpoxy/Polyurethane (CompletedMay2012)
LevelGaugingENRAFAutomaticTankGaugewithShand&Jurs92021MechanicalTape
OverfillProtection
HydraulicallyOperatedHighLevelShut‐OffValvewithDedicatedFloat(Setat
48.375Feet)
PipingReceipt8"CarbonSteel
Issue6"CarbonSteel
LowSuction6”CarbonSteel
WaterDraw‐Off1"CarbonSteel

Level Alarms

Low‐LevelAlarm:7.20 Feet
Low‐LowLevelAlarm:2.40Feet
High‐LevelAlarm:47.875Feet
High‐HighLevelAlarm:48.875Feet
High‐LevelControlShutoff:48.375Feet

Type of Internal Floating Roof

NA

API 653 In‐Service Inspection Report USAG Kwajalein‐Atoll

A. GENERAL PROJECT INFORMATION

1. API653Inspection
ThisprojectwillperformAPI653inspectionsofvarioustanksatfacilitiesthroughouttheUnited
States/OCONUS.Additionalconsiderationisgiventofederal,state,andlocalregulations,aswellas
applicablemilitarycriteriaandgeneralindustrystandards.

An API Standard 653 In‐Service (External) inspection was performed on Tank 6 (FAC 962).

2. SiteInformation
OnSeptember29,2017Burns&McDonnellandoursub‐consultant(InterSpec)performedanAPI653
In‐Service(External)inspectionofTank6(Facility962)locatedatU.S.ArmyGarrisonKwajaleinAtoll,
RMI.USAGKwajaleinAtoll(USAG‐KA)ishometotheRonaldReaganBallisticMissileDefenseTestSite.
TheReaganTestSiteisaMajorRangeandTestFacilityBaseundertheDoDwiththeprimarymissionof
researching,developingtests,anddevelopingmissiledefenseandspaceprograms.

Tank 6 is used as an aboveground JP‐5 fuel storage tank supporting the installation fueling needs.

B. TANK INSPECTION COMMENTS

1. TankConstruction
Tank6(FAC962)isanominal27,500BBL,60‐footdiameterby54‐foottall,F‐44(JP‐5),aboveground
verticalstoragetank.Thetankwasconstructedin1954presumablytoAPISTD12CEleventhEdition.
Therearenodataornameplatesaffixedonthetank.Thetankhasundergoneseveralmodifications,
includingtheadditionofanewtankbottomin2012.Additionally,modificationsincludinglevelalarms,
ahighliquidlevelshut‐offsystem,additionalaluminumstillingwells,shellpatchrepairs/removal,and
internalpipesupportmodificationwerenotedassomeofthealterations.
2. TankFoundation
Thetanksitsonaconcreteringwallfoundationthatisapproximately10"abovethecontainmentfloor.
Thefoundationisdesignedwithaleakdetection(tell‐tale)systemthatpresumablyextendstothe
centerofthetank(designdrawingswerenotavailableatthetimeoftheinspection).Itisreportedas
havingaflexiblemembraneliner(FML)forthesecondarycontainmentattachedtothefoundationwith
battenstrips.Accessiblesectionsofthefoundationwerevisuallyevaluatedduringtheinspectionfor
brokenconcrete,spalling,cracks,andvegetationagainstthebottomofthetank.Nospallingand
vegetationwerepresent.Thereisminorvegetationfromtheearthensecondarycontainment
encroachingtowardsthefoundation‐to‐bottominterface.Thefoundationtochimeinterfaceissealed,
andnocaulkingdeteriorationwasidentified.Shellsettlementsurveyswereperformedduringthe
inspectioninaccordancewithAnnexBofAPIStandard653.SettlementresultsarelistedinAppendixA.
Thereisnoindicationofsignificantsettlement.Overall,thefoundationappearstobeisinsatisfactory
condition(Asmallsectionofthefoundationisaccessibleforinspection).
3. TankShell
Thetankshellisconstructedfromcarbonsteelmaterialofanunknownspecification.Theshellisof
cylindricaldesign,butt‐weldedtogether,andconsistingofeight(8)courseswithoneanglestiffening‐
ringapproximately15"fromthetopoftheshell.Evaluatedtheshellforplumbness,roundness,peaking,
andbanding;allofwhichwerefoundtobewithintheallowabletolerancesoftheAPIStandard653.

API 653 In‐Service Inspection Report USAG Kwajalein‐Atoll

Visuallyinspectedtheexterioroftheshell.Inspectedthecoatingfordis‐bonding,adhesion,
deterioration,anddiscoloration.Thetankshellisequippedwithtwo36"manholes(180°apart)andan
additional30"manhole.Thetankisequippedwithashellmountedlowlevelalarmandhigh‐highlevel
alarms,aswellasahigh‐levelshut‐off.Theshellwasevaluatedforremainingmetalthicknessutilizing
ultrasonictechnology.Theultrasonicthicknessmeasurementsandthicknessmeasurementlocations
(TML)arelistedintheShellPlateThicknessMeasurementstableinAppendixA.Threeareasof
laminationswerelocatedontankshellonplatenumber1‐2(SeeShellLayoutDrawinginAppendixA
forlocation).Laminationisformedwithinthemetalsheetwhenadiscontinuitypresentinthemetal,
suchasporosityorinclusionstrappedintheslab,areelongatedinthedirectionofrollingduringthe
steelmanufacturingprocess.Thelaminationsarealllessthan0.75"basedontheB‐Scanultrasonicdata
andarewithinacceptablelimitsofthecurrentAPISTD650section6.2.4.Evaluateifanyhotworkis
performedattheselocationinthefuture;otherwise,monitoratthenextAPISTD653UTinspection
interval.Aservicelifeevaluationperformedshowstheshellwithgreaterthan30yearsofremaining
lifeundercurrentconditions.Theengineeringcalculations,asperAPIStandard653,fortheservicelife
evaluationareshowninAppendixAunder“ServiceLifeEvaluation.”Thetankshellisinsatisfactory
mechanicalcondition.
4. TankAppurtenances
a. GeodesicDomeRoof
Thistankisretrofittedwithaclear‐spanaluminumdomecovermanufacturedby
ConservatekIndustries.Itisanaluminumgeodesicdomeroofthatwasretrofittedtothis
tanksometimein1994.Thedomeisjoinedwithstainlesssteelfastenerswithan
interlockingpanelthathasanenclosedgasketincompressionforamechanicalseal.The
battenbarsandgussetcoveraresealedwithcaulking(externaljointseals).Thereisminor
tomoderatecaulkingdeteriorationandsignsofstandingwateronthegeodesicroofpanels.
Inspectionofthedomeroofislimitedtowhatisaccessiblefromtheplatform.

b. Gauging

Thetank’sEnraf(Model#854)ATGisinstalledthroughan8‐inchaluminumstillingwell.
Thestillingwellisslotted.TheEnrafsystemwasnotinworkingorderatthetimeofthe
inspection.Thereisnomanualgaugingandsamplingwell,butitappearsthisactionis
performedviathegeodesicroofaccesshatch.Aseparateslotted8‐inchcarbonsteelwellis
usedfortheATGwaterprobe.Thetankisequippedwithafloatandtapetypemechanical
tapegaugemanufacturedbyShand&Jurs(Model92021).Thesystemisnotingood
workingcondition.
c. LevelAlarms
Thehighlevelalarm,theHLVfloatchamber,andthehigh‐highlevelalarmaremountedon
theshellandareaccessibleviathecircumferentialstairway.Thetankisequippedwitha
low‐levelalarm,butnoindependentlow‐lowlevelalarmsystemwasinstalled,asrequired
bymilitarycriteria.
d. StairsandPlatforms
Thetank’sfixedroofisaccessiblebyacircumferentialstairwaymountedontheshellofthe
tankwithatopplatform.Thestairsandplatformwereinspectedforcorrosionand
structuralsoundness.Thestairwayhandrailisconstructedwith1½"angleironhandrails
andcoatedsteelplatetreadswithnon‐slipprofile.Thetopplatformisagalvanizedgrating

API 653 In‐Service Inspection Report USAG Kwajalein‐Atoll

type,andseveralstairwaytreadswerereplacedinthepastwithcarbonsteelgrating.The
overallgeneralconditionofthestairsandplatformaremostlysatisfactory(withsome
exception–SeeSectionC).
e. GroundingandBonding
Thereisonegroundingcablemechanicallyconnectedtolugonthetank’sshell.The
groundingrodpenetratesthroughthesecondarycontainmentfloorlinerandisattachedto
agroundingcable.Thetankisnotequippedwithacoppergroundingbarforpersonnel
staticelectricdischarge(typicallyrequiredbymilitarycriteria).
5. TankCoating
Thetankshell,stairway,handrails,piping,andappurtenancesarecoated.Theexteriorcoatingisan
epoxywithapolyurethanetopcompletedinMay2012.Theexteriorshellcoatingismostlysatisfactory
withisolatedcoatingfailuresneartheappurtenances.Isolatedcoatingfailurewasnotedonthe
appurtenances,productpiping,andvalveswithinthesecondarycontainment.
6. TankPipingSystem
Thefuelisreceivedthrough8‐inchcarbonsteelpiping,andproductisissuedfromthetankthrougha
6‐inchcarbonsteelpipe.Thetankisalsoequippedwithotherauxiliarypipingforthewaterdraw(NPS
1) attachedtoaproductsavertank(PST)anda6‐inchlowsuctionpipingthatterminatestoaCamlock
fittingadjacenttothePST.InspectedandevaluatedeachtanknozzleinaccordancewithAPIStandards
650and653.Identifiedthetypeanduseofeachshellnozzleandmeasuredthenozzleneckthickness
onallaccessibleshellnozzles.Evaluatedallnozzlesandreinforcementplatesforleaksandcorrosion.
7. FireProtectionSystem
Thestoragetankisequippedwithasurfaceapplicationfixedfoamfiresuppressionsystemthatusesa
mobilefoamsupply.OneNPS8foamchamberismountedapproximately24inchesdownfromthetop
ofthetankonshellcourseeight.AllVictauliccouplingsforthefiresuppressionsystempipinghave
deterioratedfasteners.Servallocationshavecompletelyfailedcouplings.Nofirehydrantswerenoted
nearthetankduringtheinspection.
8. SecondaryContainment
Thetanksitsinsideanearthensecondarycontainmentbasinwithageotextilelinerpositioned
approximatelyeighttoteninchesbelowthesoilandconcretedikewalls.Theoveralldimensionofthe
secondarycontainmentis189.67feetx129.33feet,withaverticalheightof72.125"(totopsoil).The
secondarycontainmentisequippedwitha6"draininletandadrainvalvethattietotheunderground
PVCpipingsystemtotheOWS.Thesecondarycontainmentreleasevalveishousedinsideavalvepit
adjacenttothedraininletwithinthedike.ThePVCpipingsystemismanifoldedtogetherandcannotbe
individuallyisolatedoutsideofthevalvepit.Thedrainline,thedraininlet,andvalvepitwerevisually
evaluatedtodetermineifthedrainagesystemisliquid‐tight.Thevalvepithasraincovers,butstanding
waterwasnotedinthevalvepit.Additionaltestingandevaluationmayberequiredtodetermineifthe
valvepitisliquid‐tight.Theliquidinthevalvepitwaslowerthantheliquidintheadjacentdraininlet
andthussuggeststhatthedraininletissatisfactory.Howeverthesourceofthestandingwaterinthe
valvepitshouldbedetermined.
Thesecondarycontainmentwasvisuallyevaluatedduringtheinspectionforbrokenconcrete,spalling,
cracks,andvegetationgrowth.Minorhairlinecracks(temperaturecracks)andsomemoderatecracks
werenotedinthesecondarycontainmentwall.Anapproximatetotalof183linearfeetofcracksinthe

API 653 In‐Service Inspection Report USAG Kwajalein‐Atoll

secondarycontainmentwallwereidentified.Hairlinecracksdonotseriouslyaffectthestrengthofthe
concretestructures;however,thesecrackscanbepotentialaccesspointsformoistureorwater
seepagethatcouldcorrodethereinforcingsteel(rebar).ThereareseveralCPtestport/anodeaccess
PVCopeningsaroundtheperimeterofthetankthatpenetratetheFML.SomeofthesePVCopenings
havedeterioratedcaulking.Thesecondarycontainmentisinmostlysatisfactorymechanicalcondition,
withtheexceptionofthediscrepanciesidentifiedinSectionCbelow.Fieldassessmentindicatesthat
thesecondarycontainmentisofsufficientsizetocontainatotaltankloss.Thesecondarycontainment
ispartiallyslopedtoallowfordrainageawayfromthetank.
Aformalsecondarycontainmentevaluation,inaccordancewith40CFR112,mayberequiredinorder
tosatisfyfederal,state,andlocalrequirements.
9. CathodicProtection
AnewimpressedcurrentCathodicProtection(CP)systemwasinstalledonthistankduringthetank
bottomrepairprojectin2012.TheCPsystemismanufacturedbyUniversalRectifiers,Inc.(ModelOSOI
Serial#114453).Thisunitisa50volt6ampereoil‐cooledrectifierunit(numberedCP4)andis
mountedontheoutsideofthepumphouseonthenortheastendofthesecondarycontainment.TheCP
testboxismountedonthesecondarycontainmentwalladjacenttotherectifier.Thetankappearsto
haveamixedmetaloxideanode(totalof9)laidunderthetankbottomthatleadtoanexplosionproof
junctionboxmountedonthesideofthetank.Thetankisalsoequippedwiththreepermanently
installedreferencecellsburiedbeneaththenewbottom.
Atthetimeoftheinspection,therectifierwaspoweredonandinserviceableoperationcondition.Base
personnelperformedtherequiredtestinganddatalogging.TheJanuary2017reportprovided
indicatedthatTank#6isreceivingcathodicprotectionbasedonNACEcriterion.Therectifier,anode
junctionbox,andtankjunctionboxareallinsatisfactorycondition.

C. FINDINGS AND RECOMMENDATIONS

Thetankisgenerallynotinaccordancewithcurrentmilitarycriteriaforsomeofthetankdesign,
appurtenancesandpipingconfiguration.Therefore,therecommendationsarenotmeanttobringthetankinto
fullcompliancewithUFC3‐460‐01orAW78‐24‐27standardsbutrathertoidentifytheseitemsforthe
owner/user’splannedupgrades,rehabilitation,andpriorityrepairs.Mandatoryrepairsshouldbecompleted
toassurecompliancewithindustrystandards,aswellasfederalorstatejurisdictionalrequirements.
Duringthisevaluation,thetankwasfoundtobeinagenerallyserviceablecondition,withnoimminentriskto
operationandoverallintegrity.However,therewereseveraldeficienciesthatwerenoted.Thesenoted
deficienciesarelistedbelowinnoparticularorder,withrepairrecommendations.
AllrepairsandmodificationsshouldbeperformedinaccordancewithAPIStandard653,UFC3‐460‐01,DoD
StandardDesign78‐24‐27,andapplicableUFGSspecifications.
1. MANDATORYREPAIRSperAPI653,UFC3‐460‐01,orAW78‐24‐27Standards
Mandatoryrepairsrepresentitemsthatrequireimmediateattention,inordertopreventimminentrisk
tosystemoperators,equipmentintegrity,ortheadjacentenvironment.Thetankshouldremainoutof
serviceuntiltheserepairsarecompleted.

No mandatory repairs were identified for this tank.

API 653 In‐Service Inspection Report USAG Kwajalein‐Atoll

2. REQUIRED REPAIRS to Fully Comply with API 653 or Federal, State, and Local Codes

Requiredrepairsrepresentitemsthatshouldbeaddressedinatimelymanner,inordertoprevent
futurepotentialriskstosystemoperators,equipmentintegrity,ortheadjacentenvironment.These
itemsareberequiredbyAPI‐653orfederal,state,andlocalcodes.
a. SecondaryContainmentCracks
OBSERVATION:Unsealedcrackswereidentifiedinthesecondarycontainmentwall(thisincludes
areasthatwerepreviouslysealed).
CodeREFERENCE:40CFRSection112.7(c)statesthattheentiresecondarycontainmentsystem,
“includingwallsandfloor,mustbecapableofcontainingoilandmustbeconstructedsothatany
dischargefromaprimarycontainmentsystem...willnotescapecontainmentbeforecleanupoccurs.”
§§112.8(c)(2)and112.12(c)(2)statethatdikedareasmustbe“sufficientlyimpervioustocontainoil.”
RECOMMENDATION:RepairallexposedcracksinthecontainmentwallsbygrindinginaV‐shape
pattern,withatleast¼‐inchwidthatthesurfaceandadepthofatleast¼‐inchandsealingwith
flexibleurethane(e.g.Sikaflex1c)orasimilarapprovedsealant(Quantity:183linearfeet).
b. SecondaryContainmentExpansionJointSealant
OBSERVATION:Thereareareasofweatheredanddeterioratedsealantattheexpansionjointsforthe
secondarycontainmentwall.
CodeREFERENCE:40CFRSection112.7(c)(Seereferencefromabove)
RECOMMENDATION:Removethedamagedjointsealantandinstallnewbackerrodsandsealantwithin
thecontainment.Thesealantshallbeadequatetoaccommodateajointcompressionequalto50
percentofthewidthofthejoint.Thebackerrodshallbecompressiblerodstockofpolyethylene
foam,polyurethanefoam,butylrubberfoam,orotherflexible,non‐absorptivematerial,as
recommendedbythesealantmanufacturer.ThesealantshallconformtoUFGS079200JointSealant
(Quantity:28linearfeet–fourlocations).

API 653 In‐Service Inspection Report USAG Kwajalein‐Atoll

c. SecondaryContainmentDrain
OBSERVATION:The valvepithasraincovers,butstandingwaterwasnotedinthevalvepit.Theliquid
inthevalvepitwaslowerthantheliquidintheadjacentdraininletandthussuggeststhatthedrain
inletissatisfactory.However,thesourceofthestandingwaterinthevalvepitshouldbedetermined.
CodeREFERENCE:40CFRSection112.7(c)(Seereferencefromabove)
RECOMMENDATION:UpgradetheconcretedraininletasdetailedinAW78‐24‐27DrawingCD.09
Detail3orsimilar.UseductileironpipinginlieuofthePVCdikedrainlines.Ataminimum,
investigateandrepairthesourceofwaterinsidethevalvepit.Slopedikebasinsurfacesaminimum
of1%fordrainage.Drainageswalesshouldbeslopednoflatterthan0.5%todrainageinlet(seeAW

78‐24‐27

Drain Valve

Secondary Containment Drain

Valve Pit Rain Cover

Drain Inlet

API 653 In‐Service Inspection Report USAG Kwajalein‐Atoll

d. SecondaryContainmentLinerandPenetration
OBSERVATION:Thesecondarycontainmenthasalinerwithanearthencover.Theconditionofthe
linerisunknown,butsomepenetration,includingthePVCcathodicprotectionanodeaccesscapsand
thetankgroundingrodsleeve,havedeterioratedcaulkingandloosehoseclamps.Themajorityofthe
battenstripsontheperimeterofthefoundation,theperimeterofthedikewall,andthepipesupport
piersarenotaccessibleforinspection.Ahigherrateofraindisplacementwasnotedforthis
secondarycontainmentcomparedtotheotherASTdikesystems(ParticularlyTank8and9without
earthencover).Someofthewaterdisplacementislikelyduetothewaterabsorptionrateofthe
soil/vegetation.However,theevaporationoftheexcesswaterabovegradeisexpectedtobeconstant
foralldikesunlessthereisadeterioratedliner.
CodeREFERENCE:40CFRSection112.7(c)(Seereferencefromabove)
RECOMMENDATION:ResealallPVCFMLpenetrationsandsecurethehoseclamps.Seesimilar
applicationoverconcreteinAW78‐24‐27DrawingCD.02Detail2.
e. SecondaryContainmentLinerandPenetration
OBSERVATION:Thereisanopensix‐inchPVCpipeinthedikethatpenetratesthesecondary
containmentfloor.Thisisapotentialbreachinthesecondarycontainmentifthispipeextends
outsideofthedike,withnomeansofisolation.
CodeREFERENCE:40CFRSection112.7(c)(Seereferencefromabove)
RECOMMENDATION:InvestigatetheuseandroutingofthePVCpipe.Eithercaporremovethepipe.

API 653 In‐Service Inspection Report USAG Kwajalein‐Atoll

f. SecondaryContainmentWallPenetration
OBSERVATION:Thefiresuppressionpipingpenetratesthroughthesecondarycontainmentwall
withouttheuseofanadequatepipesleeve/seal(Quantity:3).
CodeREFERENCE:40CFRSection112.7(c)(Seereferencefromabove)
RECOMMENDATION:Resealallsecondarycontainmentwallpenetrations.Considerupgradingall
secondarycontainmentwallpenetrationsperAW78‐24‐27DrawingCD.08DetailNA(CONCRETE
WALLPENETRATIONDETAIL).
g. FoundationCracking/Spalling
OBSERVATION:Therearespallingandbreaksinthefoundation(approximately4”x18”section).
CodeREFERENCE:API653section4.5.2.2,“Concretepads,ringwalls,andpiers,showingevidenceof
spalling,structuralcracks,orgeneraldeterioration,shallberepairedtopreventwaterfromentering
theconcretestructureandcorrodingthereinforcingsteel.”
RECOMMENDATION:Repairthespallingarea(Quantity:1).

API 653 In‐Service Inspection Report USAG Kwajalein‐Atoll

h. FoamChamber“FixedFoamDischargeOutlets”
OBSERVATION:Thefoamchamberairinletscreenonthefiresuppressionsystemiscoated.Thefoam
chambermaynotproducetherequiredfoamwhentheairinletisblockedduetothecoating.
CodeREFERENCE:NFPA11Section5.2.5.1.2.2,“Eachoutletshallbesizedtodeliverfoamatthe
minimumapplicationrateorhigher.”
RECOMMENDATION:Replacewithanewstainlesssteelscreen.
i. DeterioratedVictaulicCoupling(AssociatedwiththeFireSuppressionSystem)
OBSERVATION:AllVictauliccouplingsforthefiresuppressionpipinghavedeterioratedbolts.Several
locationshavecompletelyfailedVictauliccouplings.Thiscouldresultinabreachinthesecondary
containmentbecausethispipeextendsoutsideofthesecondarycontainment,andasimilartypeof
corrosionwasnotedonthecouplingfastenersoutsideofthedike.Asectionofthefiresuppression
pipingisalsoroutedundergroundoutsideofthedike,andthetightnessofthepipingisunknown.
Thefiresuppressionsystemwillnotfunctionwiththesedeterioratedcouplingfasteners.
CodeREFERENCE:40CFRSection112.7(c)(Seereferencefromabove).AlsoNFPA11Section4.7.1.4,
“Whereexposedtocorrosiveinfluences,thepipingshallbecorrosionresistantorprotectedagainst
corrosion”InterSpecconcludestheintegrityofthepipingisdependentonthefasteners,thus
incorporatingthecodereferenceforthecouplingfasteners.
RECOMMENDATION:Replacealldeterioratedbolts,couplings,andpipe.Repairthepipetomeetthe
requirementsofNFPA11Section4.7.1.4byinstallingstainlesssteelfasteners.

API 653 In‐Service Inspection Report USAG Kwajalein‐Atoll

j. CorrosiononPipingandPipeSupports
OBSERVATION:Thepipingandpipesupportswithinthetank’ssecondarycontainmenthavemoderate
tomajorcorrosion.Themajorityofthepipesupportshavecompletelydeteriorated.
CodeREFERENCE:APIRP574Section7.4.14(ContactPointCorrosion)APIRP574Section8.2
(Properpositionandfunctionofsupports,hangers,andanchors).InaccordancewithAPI570Section
7.5,“Pipingshallbesupportedandguidedsothat(a)itsweightiscarriedsafely,(b)ithassufficient
flexibilityforthermalexpansionorcontraction,and(c)itdoesnotvibrateexcessively.”
RECOMMENDATION:Repairthecoatingfailureonthepiping.Replacethedeterioratedpipingsupports
perAW78‐24‐27DrawingCD.13Detail1and2.
k. CorrosionandPittingonContainmentPiping
OBSERVATION:Therewereareasofpittingnotedon NPS8receiptpiping.
CodeREFERENCE:APIRP574Section7.4.14(CreviceCorrosion).APIRP574Section10.1.6.3(Loss
inthickness)
RECOMMENDATION:Replacethespoolsofpipingthathavesignificantpittingandcorrosion.Itmaybe
practicaltoconductadetailedAPISTD570inspectionofthecontainmentpipingtogetanoverall
conditionassessment.NDTtoolssuchasguidedwaveexaminationcanalsobeemployedtogetthe
conditionofinaccessibleareasbetweenthepipesupports,sleevedpiping,wrappedpiping,orthe
throughdikewallpenetration.Guidedwaveexaminationisascreeningtoolusedtoinspectlarge
sectionsofpipingfromasingletestlocation.

API 653 In‐Service Inspection Report USAG Kwajalein‐Atoll

l. CorrodedFastenersonHLV
OBSERVATION:ThereissignificantcorrosiononthebodycoverfastenerontheHighLiquidLevel
shut‐offvalve(HLV).Thefastenersdonotappeartohavesufficientthreadengagementduetothe

corrosion.

CodeREFERENCE:API570Section5.15,“Flangefastenersshouldbeexaminedvisuallyforcorrosion
andthreadengagement.Fastenersshouldbefullyengaged.Anyfastenerfailingtodosoisconsidered
acceptablyengagedifthelackofcompleteengagementisnotmorethanonethread.”
RECOMMENDATION:Replacethecorrodedstudsandbolts.

API 653 In‐Service Inspection Report USAG Kwajalein‐Atoll

m. TankGroundingLug
OBSERVATION:Thetankgroundingstrapsareboltedtothetankshell(mechanicaljointonacoated
interface)andhavenoreinforcementplatesorgroundinglugsIAWAW78‐24‐27DrawingED.02
Detail2.
CodeREFERENCE:AW78‐24‐27DrawingED.02Detail2.(SeealsoAPI650Section5.8.11.3)
RECOMMENDATION:Exothermicallyweldthegroundingcablestothelugandinstallreinforcementat
theshell,inaccordancewithAW78‐24‐27DrawingED.02Detail2.Note:ifrepairsareelectednotto
bedone,thepaintshouldberemovedwherethecableboltstothelug,toprovideabetterconnection
toground(Quantity:1groundconnections).NotethecurrenteditionofAPISTD650suggestsa
maximumlugspacingof100ft.withaminimumoffourlugs.
n. ProductSaverTank(PST)Grounding
OBSERVATION:TheProductSaverTankisnotgroundedattheleganddoesnothaveaventinstalled
inaccordancewithAW78‐24‐27DrawingD.13DetailA1.ThePSTisastainlesssteeltankwithatop
lid.ThePSTtankhasnomeansofgrounding.
CodeREFERENCE:AW78‐24‐27DrawingD.13DetailA1.InaccordancewithNFPA30,paragraph
6.5.4,“Allequipmentsuchastanks,machinery,andpipingshallbedesignedandoperatedtoprevent
electrostaticignitions.Allmetallicequipmentwhereanignitablemixturecouldbepresentshallbe
bondedorgrounded.Thebondorgroundorbothshallbephysicallyappliedorshallbeinherently
presentbythenatureoftheinstallation.”
RECOMMENDATION:InstallagroundcableandventpipingtotheProductSaverTankinaccordance
withAW78‐24‐27DrawingD.13Detail5(Quantity:1ground,1ventpipe(1¼NPS,2‐feethigh).

API 653 In‐Service Inspection Report USAG Kwajalein‐Atoll

o. ShellManholeCoverwithnoHingeorDavitArm
OBSERVATION:Theshellmanholecoversarenotequippedwithahingeordavitarmtofacilitatethe
handlingofthemanholecoverplates.
CodeREFERENCE:APISTD650Section5.8.3.5states,“Shellmanholecoversshallhavetwohandles.
Thosecoversweighingmorethan34kg(75lb)shallbeequippedwitheitherahingeordavitto
facilitatethehandlingofthemanholecoverplate.Thedavitsupportarmshallnotbeweldeddirectly
totheshellwithoutareinforcingplate.”AlsoAW78‐24‐27drawingD.10detail3
RECOMMENDATION:InstallashellmanholedavitarmIAWwithAPISTD650andAW78‐24‐27
drawingD.10detail3(Quantity:2)
p. TopPlatformGratingNotSecuredDown
OBSERVATION:Thestairwaytopplatformdoesnothaveanchor/saddleclips.Tackweldswerenoted,
butsomearecracked.
CodeREFERENCE:OSHAandAW78‐24‐27DrawingD.11Detail1,“Gratingshallbeanchoredwith
saddleclips.”
RECOMMENDATION:Installgratinganchors.
q. CrackedGasket
OBSERVATION:TheTRVtestTeeblindflangefortheproductissuenozzlehasacrackedgasket.
CodeREFERENCE:APIRP574Section10.3.5.1,“Sitesshouldhaveaprogramtoassurethatflangesare
madeupproperly.Propermake‐upofeveryflangeinapipingsystemisimportantforreliability.
Propermake‐upincludestheuseofthepropergasketandfastenermaterial,typeandsize,proper

API 653 In‐Service Inspection Report USAG Kwajalein‐Atoll

positioningofthegasketandpropertorquingofthefasteners.Theassuranceprogramshouldinclude
proceduresforgasketandfastenerselectionandforfastenertorquing.”
RECOMMENDATION:Replacethegasket(3/4”flange).
r. CircumferentialStairwayPathRestricted
OBSERVATION:Thereisalimitedorrestrictedpathonthecircumferentialstairwayduetothe
geodesicdomeroofflashingprojectiontowardsthecircumferentialstairway.Thereisno
intermediateplatform.Thereisanapproximatelysixteen(16)inchclearancebetweenthehandrail
andthegeodesicdomeroof.Thisreducestheexistingtreadwidth.
REFERENCE:UFC3‐460‐01SectionTable8‐1itemj.OSHAminimumrequiredtreadwidthis22inches
(1920.25(C)(3)).SeealsoAPI650Table5.18item3.
RECOMMENDATION:Installanintermediateplatformorreworkthecircumferentialstairwayto
provideasufficientpathpastthegeodesicdomeroof.
s. NoorFadedConfinedSpaceMarkingsatManholes
OBSERVATION:Thetankisnotequippedwithaconfinedspacemarking.
CodeREFERENCE:InaccordancewithOSHARegulation29CFR1910.146(c)(2),“Iftheworkplace
containspermitspaces,theemployershallinformexposedemployees,bypostingdangersignsorby
anyotherequallyeffectivemeans,oftheexistenceandlocationofandthedangerposedbythepermit
spaces.NOTE:AsignreadingDANGER‐‐PERMIT‐REQUIREDCONFINEDSPACE,DONOTENTERor
usingothersimilarlanguagewouldsatisfytherequirementforasign.”
RECOMMENDATION:Installconfinedspacemarkingsonalltankentrypoints.

API 653 In‐Service Inspection Report USAG Kwajalein‐Atoll

t. TankMarking(NFPADiamond)
OBSERVATION:ThetankisnotequippedwithanNFPAmarking
CodeREFERENCE:MarkthetankinaccordancewithNFPA704.AW78‐24‐27DrawingD.13Detail3
Note4) “ProvidehazardidentificationsystemlabelinginaccordancewithNFPA704.”
RECOMMENDATION:InstallanNFPA704marking.

API 653 In‐Service Inspection Report USAG Kwajalein‐Atoll

u. Conduit,JunctionBoxes,Fittings,andMountingHardware
OBSERVATION:Theconduits,junctionboxes,fittings,andmountinghardwarewithinthesecondary
containmenthavedeteriorated.ThiswillnotmeettheClass1,Division1ratingrequirementsfor
hazardouslocations.
CodeREFERENCE:AllwiringandfittingsinaClassIlocationthatisabulkplantorterminalmust
complywiththeapplicableprovisionsofNECArticle501orArticle505[515.7].
RECOMMENDATION:Replaceallcorroded/deterioratedconduits,junctionboxes,fittings,and
mountinghardware.

API 653 In‐Service Inspection Report USAG Kwajalein‐Atoll

3. RECOMMENDEDREPAIRSasPartofRegularMaintenance
Recommendedrepairsrepresentitemsthatshouldbeaddressedinatimelymanner,inorderto
preventfuturepotentialriskstosystemoperators,equipmentintegrity,ortheadjacentenvironment.
a. ExteriorCoatingFailuresonTankandAppurtenances
OBSERVATION:Thereisisolatedcoatingfailureontheexteriorshellmostlyaroundthestiffeningring,
topplatform,circumferentialstairwaywindgirder,andshellmanholes.Similarisolatedcoating
failureisnotedonthePSTpump,HLVtubingsupportmountingbrace,andlowlevelandhighlevel
sensorchambers.ThereismoderatecoatingfailureandcorrosionnotedontheLLA,HLA,HHLA,and
HLVonthepipenipplesandflanges.
CodeREFERENCE:UFC3‐460‐01,Section8‐3.10andSection9‐10
RECOMMENDATION:Mechanicallycleanandrecoattheareasofcoatingfailureonthetankshell,
circumferentialstairway,landing,piping,andappurtenances.Repairsshouldbeaccomplishedusing
anepoxybasedcoatingsystemorequivalent.

API 653 In‐Service Inspection Report USAG Kwajalein‐Atoll

b. MissingLeakDetectionPlugs
OBSERVATION:Theleakdetectionplugsaremissingonthefittingmountedbetweentheoldandnew
bottom.Waterintrusionislikelyduringaheavyraineventorifthecontainmentfillswithrainwater
uptothenewtankbottomfittings.
CodeREFERENCE:API650sectionI.5.5“Ifspecifiedbytheowner,theundertankdrainsshallbefitted
withavalveorpipedtoleakdetectionwellasshowninFigureI.10.”Thefiguredetailstheleak
detectionwithraincoverorpositionedabovethemaximumhighwaterlevelwithinthedike.AW
78‐24‐27DrawingD.03Detail2showstheleakdetectionwithapipecap).
RECOMMENDATION:Installplugs(Quantity:2).
c. WaterinLeakDetectionWell
OBSERVATION:AsmallamountofwaterwasnotedintheNPS4stainlesssteelleakdetectionwell.
CodeREFERENCE:Generalmaintenance
RECOMMENDATION:Removethewaterandmonitor.Comparewiththerainwateraccumulation
withinthediketoensurethesourceofwater.Somewaterduetocondensationisnormalandmaybe

disregarded.

API 653 In‐Service Inspection Report USAG Kwajalein‐Atoll

d. TankElectronicATGandWaterProbe
OBSERVATION:Thetank’sEnraf(Model#854)ATGisinstalledthroughan8‐inchaluminumsteel
well.Thestillingwellisslotted.TheEnrafsystemwasreportedtobeinnon‐workingorderatthe
timeoftheinspection.Thewaterprobeisnotmountedoverthesumpandisinstalledviaaneight
inchcarbonsteelwell.Thewaterprobeisnotinstalledoverthetankbottomsumpthroughawater
probewell(separatewell).
CodeREFERENCE:UFC3‐460‐01Table8‐1(itempands)andAW78‐24‐27DrawingD.07Detail3,4
and5)
RECOMMENDATION:ReplaceorrepairtheATG.ModifythestillingwellsIAWwithAW78‐24‐27.
MountingplateweldingperAPISTD653Section9.10.3
e. IndependentLow‐LowLevelAlarm
OBSERVATION:Thetankisnotequippedwithanindependentlow‐lowlevelalarm.Thereisalow
levelalarmsensorinstalledonthesideofthetankshell(seephotobelow).
CodeREFERENCE:UFC4603‐460‐01Table8‐1(k)andAW78‐24‐27DrawingD.12Detail1
RECOMMENDATION:Installanindependentlow‐lowlevelalarm.

API 653 In‐Service Inspection Report USAG Kwajalein‐Atoll

f. ProductSaverTank(PST)PumpandLevelAlarm
OBSERVATION:TheProductSaverTank(PST)isnotequippedwithanelectricalpumpanddoesnot
havehighlevelalarms.Theexistingdiaphragmoperatedpumphasmoderatecorrosionwith
deterioratedappurtenances(brokenregulator,corrodedairfilterhousing,andcorrodedvalve

handle)

CodeREFERENCE:AW78‐24‐27DrawingD.13Detail5.IAWUFC3‐460‐01Section3‐6.6.7,“Mount
permanentlyinstalledpumpsonsubstantialfoundationsofreinforcedconcretedesignedin
accordancewithHydraulicInstituteStandards.”
RECOMMENDATION:ConsiderreplacementoftheexistingsysteminaccordancewithAW78‐24‐27.
g. MechanicalTapeGauge(MTG)
OBSERVATION:Thetankisequippedwithafloatandtapetypemechanicaltapegaugemanufactured
byShand&Jurs(Model92021).Thesystemisnotingoodworkingcondition.Thecheckerknobdid
notrespondwhenactuated.
CodeREFERENCE:Generalmaintenance/manufacturer’sinstructionandUFC3‐460‐01Table8‐1
(itemo)
RECOMMENDATION:ConsiderreplacementofexistingsystemwithnewMTG.Considerincreasingthe
elevationofthegaugehead,sotheproductlevelreadingwindowisat“convenienteyelevel”from
grade.UFC3‐460‐01Section8‐8.3(itemo)listsaliquidlevelgaugemountedat60”abovethe
walkingsurface.

API 653 In‐Service Inspection Report USAG Kwajalein‐Atoll

h. Internalladder
OBSERVATION:Thereisnointernalladder(noteroofisnotequippedwithfloatingroof,andthis
recommendationmaybedeferredtountilIFRisinstalled).
CodeREFERENCE:UFC4603‐460‐01Table8‐1(h)andAW78‐24‐27DrawingD.08Detail2
RECOMMENDATION:Installtheinternalladder(inaccordancewithOSHAcriteria)fortanksof5,000
gallons(19000L)orlargerperUFC4603‐460‐01Table8‐1(h)andAW78‐24‐27DrawingD.08
Detail2
i. NoSampleGaugeWell
OBSERVATION:Thereisnomanualsampling/gaugingwell.
CodeREFERENCE:UFC4603‐460‐01Table8‐1(s)andAW78‐24‐27DrawingD.07Detail2
RECOMMENDATION:Installa10‐inchroofnozzleandanaluminum,slottedstillingwellthatextendsto
within3inchesofthebottomofthetankforgaugingandsamplingwithadatumplatetoestablisha
gaugingzeropoint.
j. DoubleBlockandBleedValveMissingTube
OBSERVATION:Theproductreceiptdoubleblockandbleedvalveismissingthemanualbleedvalve
goosenecktube.Coating,water,andsomecorrosionwerenotedinsidethedifferentialthermalrelief
(DTR)valves,andlongtermexposuretotheinternalsectionofDTRvalvecouldcausethesystemto
notperformasdesigned.
CodeREFERENCE:Generalmaintenance/manufacturerdrawing.

API 653 In‐Service Inspection Report USAG Kwajalein‐Atoll

RECOMMENDATION:Reinstallthegoosenecktubetopreventdrainageofbodyliquidandtoprevent
wateranddebrisfromenteringtheDTRvalve.Thetubeshouldbeabovethehighestpointofthe
bodycavity.Asteelplugcanalsobeusedtopreventwaterintrusion.
k. BrokenValveHandleonDoubleBlockandBleedValveDTR
OBSERVATION:Theproductreceiptdoubleblockandbleedvalvehasabrokendifferentialthermal
relief(DTR)valveandcorrosionontheDTRtubingcompressionfitting.
CodeREFERENCE:Generalmaintenance/manufacturerdrawing.
RECOMMENDATION:ReplacetheDTRvalveandcorrodedtubefitting.
l. ProductPipingLabelMarking
OBSERVATION:Themajorityofthesecondarycontainmentpipinghasproductpipemarking.Fadedor
missingmarkingwasnoted.
CodeREFERENCE:AW78‐24‐27DrawingCD.13Detailx.(refertoMIL‐STD‐161Gforcorrectfueltype)
RECOMMENDATION:Reapplyproductpipingmarking.

API 653 In‐Service Inspection Report USAG Kwajalein‐Atoll

m. FixedRoofDeterioratedCaulking
OBSERVATION:Thereisminortomoderatecaulkingdeteriorationonthegeodesicdomeroofpanels.
Inspectionofthedomeroofislimitedtowhatisaccessiblefromtheplatform.
CodeREFERENCE:Generalmaintenance/manufacturerinstruction
RECOMMENDATION:Sealthetopsideofthegeodesicdomeroofasneededtoeliminatewater

intrusion.

n. RoofHatchDoor
OBSERVATION:Thegeodesicdoomroofhatchlidwasintheopenposition.
CodeREFERENCE:Generalmaintenance/manufacturerinstruction
RECOMMENDATION:Secureroofhatch.

API 653 In‐Service Inspection Report USAG Kwajalein‐Atoll

o. ShellLamination(NoRepairRecommendation)
OBSERVATION:Threeareasoflaminationswerelocatedontankshellonplatenumber1‐2(SeeShell
LayoutDrawinginAppendixAforlocation).Laminationisformedwithinthemetalsheetwhena
discontinuitypresentinthemetal,suchasporosityorinclusionstrappedintheslab,areelongatedin
thedirectionofrollingduringthesteelmanufacturingprocess.Thelaminationsarealllessthan0.75"
basedontheB‐ScanultrasonicdataandarethewithinacceptablelimitsofthecurrentAPISTD650
section6.2.4.
CodeREFERENCE:API653Section4.3.6,“Flawssuchascracksorlaminationsshallbethoroughly
examinedandevaluatedtodeterminetheirnatureandextentandneedforrepair.”
RECOMMENDATION:Norepairsrecommend.Evaluateifanyhotworkisperformedattheselocationin
thefuture;otherwise,monitoratthenextAPISTD653UTinspectioninterval.
p. PersonnelStaticElectricDischarge
OBSERVATION:Thetankisnotequippedwithacoppergroundingbarforpersonnelstaticelectric
discharge(typicallyrequiredbymilitarycriteria).
CodeREFERENCE:UFC3‐460‐03Section2‐3.21andAW78‐24‐27DrawingD.11Detail4
RECOMMENDATION:Installacoppergroundingbarforpersonnelstaticelectricdischargeatthebase
ofthecircumferentialstairway.
q. AST ExteriorFireProtectionWaterSystems
OBSERVATION:ThetankdoesnotappeartomeetequipmentrequirementforASTexteriorfire
protectionsystem.Thestandpostmountedwaterjetmonitorwasnotedalongthefacilityfenceline
northeastcornerofthedike.

API 653 In‐Service Inspection Report USAG Kwajalein‐Atoll

CodeREFERENCE:UFC3‐460‐03Section2‐15.2.1
RECOMMENDATION:InstalladditionalservicesfortankexteriorfireprotectionwatersystemsIAW
UFC3‐460‐01Section2‐15.2.1(fireprotectionwatermains,hydrants,valves,pumps,andapplication
devicesoutsideofdike)tocontrolofbrushandgrassfiresandcoolingofstoragetanksintheeventof
afireexposure.

API 653 In-Service Inspection Report USAG Kwajalein-Atoll

APPENDIX A: ENGINEERING CALCULATIONS AND DRAWINGS

A.1 SHELL SERVICE LIFE EVALUATION

A.2 SHELL SETTLEMENT EVALUATION

A.3 ULTRASONIC UT DATA

A.4 CONTAINMENT LAYOUT DRAWING

A.5 SHELL LAYOUT DRAWING

A.6 ROOF LAYOUT DRAWING

A.7 OSHA ACCESS STRUCTURE REPORT

Shannon T Gray Typewritten Text

Shannon T Gray Typewritten Text

Shannon T Gray Typewritten Text

Shannon T Gray Typewritten Text

Shannon T Gray Typewritten Text

Shannon T Gray Typewritten Text

Shannon T Gray Typewritten Text

Where:

t min = minimum acceptable shell thickness for each course, in inches; however, t min shall not be less than 0.1 inch for any tank course.

t nom = nominal shell thickness, in inches.

t act = current measured shell thickness, excluding pits and corrosion, in inches.

t prev = previous measured shell thickness, excluding pits and corrosion or t nom , in inches.

D = nominal diameter of the tank, in feet.

H = height from the bottom of the shell course under considerations to the established maximum liquid level, in feet.

H c = calculated safe fill height, in feet, for the current product.

G = specific gravity of the contents.

Y = specified minimum yield strength of the plate; use 30,000 pounds per square inch if not known (N/A for riveted tanks).

T = smaller of the specified minimum tensile strength of the plate or 80,000 pounds per square inch; use 55,000 psi if not known (N/A for riveted tanks).

S = The maximum allowable stress, in pounds per square inch. For welded tanks, use the smaller of 0.80Y or 0.429T for the bottom and the second course or the smaller of 0.88Y or 0.472T for all other courses. For riveted tanks, use S =21,000 psi. For elevated temperatures above

200OF, the maximum allowable stress shall be the smaller of 2/3 the minimum yield strength multiplied by the M-factor (M) of API Standard 650 Appendix M or the product design stress value listed in Table M-1a or M-1b of API Standard 650.

E = original joint efficiency for the tank. Use Table 4-2 from API Standard 653 if original E is unknown; E =1.0 when evaluating the retirement thickness in a corroded plate, when away from welds or joints by at least the greater of one inch or twice the plate thickness.