Att. A. NBWC Misc Notes and Special Provisions.pdf
PDF 772 KB Posted
- Solicitation number
- RFP - 591 - 230000002051
- Issued by
- Berrien County, Coldwater City, Michigan
About this file
This document is a Special Provision from the Michigan Department of Transportation (MDOT) related to the installation of a 3,450-gallon precast concrete septic tank at the New Buffalo Welcome Center in Berrien County, Michigan. The work includes furnishing and installing the septic tank, manhole frames and covers, grade rings, internal PVC pipe and fittings, an effluent filter, as well as all necessary excavation, bedding, backfilling, compaction, and dewatering. The project must be completed by June 23, 2023, with the Welcome Center potentially closed for up to 12 hours on Mondays, Tuesdays, or Wednesdays during the work. The septic tank must meet specific material and design requirements, including being anti-floatation and HS-20 load-rated.
The pay item for this work is "Conc Septic Tank, 3450 Gallon" paid per each. The document provides detailed measurement and payment information, as well as construction requirements such as shop drawing submittals, testing, and backfilling specifications. No other pricing terms, set-asides, or funding information is provided in the document.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| RFP.NBWC Septic Tank.PI.CT.VQ.docx | DOCX document | |
| NBWC.Standard Contract terms.docx | DOCX document | |
| Schedule B-Pricing-NBWC Septic Tank Installation.docx | DOCX document | |
| Schedule A-SOW-NBWC Septic Tank Installation.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
MISCELLANEOUS NOTES
The Engineer for this project is as follows:
Michael Bippley, P.E.
Michigan Department of Transportation 3880 Red Arrow Hwy Benton Harbor, MI 49022 269-207-2269 bippleym@michigan.gov
After award, start work on the date approved by the Engineer, which must be no earlier than April 1, 2023. In no case may any work be commenced prior to award by the Department.
The project must be completely open to traffic by June 14, 2023.
The entire project must be completed by June 23, 2023.
New Buffalo Welcome Center may be closed during work to place septic tank and for hook up to system. The maximum closure of Welcome Center is 12 hours.
The closure and maintenance of traffic must be coordinated with the local MDOT Garage and the New Buffalo Welcome Center staff.
Only days allowed for complete closure of Welcome Center are Monday, Tuesday, or Wednesday.
20MUXXX(AXXX)
MICHIGAN
DEPARTMENT OF TRANSPORTATION
SPECIAL PROVISION
FOR
PRECAST CONCRETE SEPTIC TANK
UTL:JBM 1 of 2 APPR:::XX-XX-XX
a. Description. This work consists of furnishing and installing a 3450-gallon precast concrete septic tank as shown on the plans, including the manhole frames and covers, grade rings, internal PVC pipe and fittings, effluent filter, and all excavation, bedding, backfill, compaction and dewatering as necessary to complete the installation.
Ensure the precast concrete septic tank complies with all state and local regulations which apply to construction, installation and use in a septic system.
b. Materials. Ensure the precast concrete septic tank is rated at a minimum of 3450- gallons and constructed of precast concrete segments free of interior lateral or other bracing, as manufactured by Advance Concrete Products Company, Kerkstra Precast, Inc., Norwalk Concrete Industries or Engineer approved equal. Provide a septic tank meeting ASTM C1227.
Ensure the septic tank is an anti-floatation design and certified to meet HS-20 loading by a Professional Engineer licensed in the State of Michigan.
Provide septic tank effluent filter with stem extension and stainless-steel stiffener, as shown on the plans. Use Orenco Systems Inc. Biotube Effluent Filter FT1554-36, Polylok PL-525 or Engineer approved equal. Place the effluent filter as shown on the plans or where easily accessible.
Provide Schedule 40 PVC pipe in accordance with ASTM D2665. Pipe connections to tanks must utilize cast-in connectors or boot connectors meeting ASTM C923.
Provide manhole frames and covers in accordance with the Standard Plan R-18 Series, Cover Q.
Provide granular material Class IIIA for bedding in accordance with section 902 of the Standard Specifications for Construction. Ensure the bedding material is from a natural source. The use of fine material generated from crushing recycled concrete is prohibited.
c. Construction. Minimize disturbance to the existing ground and avoid damage to existing vegetation. Place the tank on a six-inch bedding layer comprised of compacted, level, granular material Class IIIA in accordance with section 902 of the Standard Specifications for Construction.
Ensure excavation and backfill is in accordance with sections 206 and 402 of the Standard Specifications for Construction, respectively. The tanks must be designed to withstand buoyant forces when completely submerged. Furnish buoyancy calculations to the Engineer prior to installation. Prior to backfilling, septic tanks must be tested as prescribed in section 9.2.2 of ASTM C1227: 9.2.2 Water-Pressure Testing-Seal the tank, fill with water, and let stand for 24 hours.
Refill the tank. The tank is approved if water level is held for 1 hour. Repair leaks and retest until zero leakage requirement is met. Submit shop drawings in portable document format (PDF) for all appurtenances associated with the concrete septic tank. Ensure shop drawings are reviewed and approved prior to beginning work on the concrete septic tank.
20MUXXX(AXXX)
UTL:JBM 2 of 2 XX-XX-XX
d. Measurement and Payment. The completed work, as described, will be measured, and paid for at the contact unit price using the following pay item:
Pay Item Pay Unit
Conc Septic Tank, 3450 Gallon ................................................................................. Each
© 2023 Microsoft Corporation © 2023 Maxar ©CNES (2023) Distribution Airbus DS Earthstar Geographics SIO
SEPTIC TANK
PROP ANTI-FLOTATION
EX STEEL ENCASEMENT PIPE
APPROXIMATE END POINT OF
(269) 926-0600
BENTON HARBOR, MI 49022
2425 MEADOWBROOK RD.
INDIANA MICHIGAN POWER
EX LIFT STATION
CS:
JN:
TSC:
DATE:
DESIGN UNIT:
DRAWING SHEET
11014
03/22/2023
0 1
VERT. (FT)
HORZ. (FT)
MILLER
COLOMA
SEWER SYSTEM IMPROVEMENTS
NEW BUFFALO WELCOME CENTER
SANITARY SEWER SHEET
Michigan Department of Transportation
SECT
DESCRIPTIONAUTH
DATENO.
FINAL ROW PLAN REVISIONS SUBMITTAL DATE:
FILE:New Buffalo Welcome Center_Site Layout.dgn
OR WEDNESDAY.
ONLY DAYS ALLOWED FOR CLOSURE ARE MONDAY, TUESDAY,
MAXIMUM CLOSURE OF WELCOME CENTER IS 12 HOURS.
SEPTIC TANK AND FOR HOOK UP TO SYSTEM.
WELCOME CENTER MAY BE CLOSED DURING WORK TO PLACE
NOTE TO CONTRACTOR:
© 2023 Microsoft Corporation © 2023 Maxar ©CNES (2023) Distribution Airbus DS Earthstar Geographics SIO
CRITICAL UTILITY
CAUTION -
QUANTITIES THIS SHEET
Mobilization, Max1 LSUM
Mulch Blanket167 Syd
Seeding, Mixture TUF8 Lb
Topsoil Surface, Salv, LM14 Cyd
Conc Septic Tank, 3450 Gallon1 Ea
Sanitary Sewer, PVC, 8 inch, Tr Det B210 Ft
CS:
JN:
TSC:
DATE:
02/17/2023
MILLER
COLOMA
SEWER SYSTEM IMPROVEMENTS
NEW BUFFALO WELCOME CENTER
SANITARY SEWER DETAIL SHEET
NO SCALE
Michigan Department of Transportation
FILE:
NEW BUFFALO WELCOME CENTER SEPTIC TANK_DETAIL
STRUCTURES AS APPROVED BY THE ENGINEER.
GRADES AS NECESSARY TO ALLOW DRAINAGE AWAY FROM
APPROXIMATIONS ONLY. CONTRACTOR MUST FIELD ADJUST
PROPOSED GROUND AND SANITARY ELEVATIONS ARE
SATISFIED.
LINES TO ASSURE MINIMUM SEWAGE FLOW REQUIREMENTS ARE
PIPING PRIOR TO CONSTRUCTION OF THE BUILDING WASTE
VERIFY FLOW ELEVATIONS OF THE EXISTING SYSTEM AND
EXISTING SANITARY SEWER SYSTEM. THE CONTRACTOR MUST FIELD
EXISTING ELEVATIONS ARE FROM AS-BUILT PLANS OF THE
NOTES:
9'-6"
8'-8"
PROP COVER "Q" (TYP)
EXISTING LIFT STATION PLAN
NOT TO SCALE
1'-6"
1'-6"
TYP
5"
8'6"±
PROP 8" PVC
TYP
5"
SEPTIC TANK PLAN
PROPOSED 3450 GALLON
NOT TO SCALE
10'-6"
TYP
6"
PROP BOLTED DOWN COVER (TYP)
EX CONTROL PANEL
PROP 8" PVC SAN SEWER @ 1.11%
NOT TO SCALE
EXISTING LIFT STATION ELEVATION
NOT TO SCALE
AS NECESSARY (TYP)
OR GRADE RINGS
PROP 3" DIA MANHOLE RISER
5"
TYP
PROP 11.25° BENDS
TYP
6"
"7
FILTER
PROP EFFLUENT
1'-6"
FROM COVERS (TYP)
PROP GRADE TO DRAIN AWAY
1'-6"
PROP EL = 684.67
EX 8" PVC SAN SEWER @ 2.00%
PROP FL EL 683.00
PROP FL EL 682.75
EL 682.65
RPOP INLET INVERT
SEPTIC TANK ELEVATION
WATER DEPTH (APPROX 3')
AT THE MIDPOINT OF THE
LOCATE BOTTOM OF TEE
& DROP PIPE
PROP 6"X6' TEE
8"
TYP
TYP
WATERSTOP
© 2023 Microsoft Corporation © 2023 Maxar ©CNES (2023) Distribution Airbus DS Earthstar Geographics SIO
EX LIFT STATION
CS:
JN:
TSC:
DATE:
03/22/2023
0 1
VERT. (FT)
HORZ. (FT)
MILLER
COLOMA
SEWER SYSTEM IMPROVEMENTS
NEW BUFFALO WELCOME CENTER
SANITARY SEWER SHEET
Michigan Department of Transportation
FILE:New Buffalo Welcome Center_MOT.dgn
HIGH LEVEL ALARM
SEPTIC TANK WITH
PROP ANTI-FLOTATION
© 2023 Microsoft Corporation © 2023 Maxar ©CNES (2023) Distribution Airbus DS Earthstar Geographics SIO
QUANTITIES THIS SHEET
FLUORESCENT PLASTIC DRUM OR 42" GRABBER CONES50 EA
PORTABLE CHANGEABLE MESSAGE SIGN1 EA
BLOCK OFF WORK AREA
TO EACH OTHER TO
PLACE DRUMS NEXT
IN WEAVE/MERGE LANE
TO CREATE 840' MERGE
USE 17 GRABBER CONES (DOUBLE BASES)
WHEN CLOSING WELCOME CENTER,
MDOT WILL BE PROVIDING MOT
FOR CONTRACTOR INFORMATION ONLY
NOTE:
AS WELL AS WHEN IT IS CLOSED
TO WARN OF UPCOMING WELCOME CENTER CLOSURE
PCMS TO BE PLACED ON EB I-94 IN INDIANA
File details come from the government source that posted it. Updated .