This document is the Agency Specific Requirements (ASR) for the lease of a 31,765 ABOA square feet / 42,882 rentable square feet (RSF) medical community-based outpatient clinic (CBOC) in Richmond, TX.

The ASR provides detailed requirements for the design and construction of the clinic space, including specifications for the lobby/reception area, procedure rooms, mental health area, audiology room, laboratory, team-work area, communication/special systems rooms, and police area. It also outlines requirements for the mechanical, plumbing, electrical, and security systems, as well as general site requirements, signage, commissioning, maintenance, and environmental management. The document references relevant industry standards and guidelines such as the Facility Guidelines Institute (FGI) and VA policies. The goal is to ensure the leased facility meets the VA's specific functional and operational requirements for a CBOC.

View the file

Other files

Show all 16

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

AGENCY SPECIFIC REQUIREMENTS

PAGE 1 LESSOR: ______ GOVERNMENT: ________

Richmond, TX CBOC

Agency Specific Requirements

VHA

Richmond Community Based Outpatient Clinic (CBOC)

This appendix contains Agency Specific Requirements that must be included in the construction and operation of the leased premises. These requirements supersede any conflicting requirements in the standard lease template.

The Joint Commission (TJC)

The Lessor’s project team must review the VAMC’s local TJC inspection reports to determine what if any facility requirements need to be included in the lease project. First consideration should be to modify the local plan if possible and reasonable to eliminate facility requirements. Example – we are not following VA Standards, but a local TJC plan may state that the environment of care is designed per VA standards; this local policy should be rewritten to state environment of care is designed per FGI standards. Lessor shall refer to all TJC standards to ensure they understand and apply all the requirements.

The Agency Specific Requirements (ASRs) do not reduce the minimum requirements contained within the Lease. These ASRs provides specific agency requirements, which may be complementary, more specific, or more stringent than those of the Lease minimum requirements.

GSA Public Buildings Service

[Type text]

PAGE 2 LESSOR: ______ GOVERNMENT: ________

SECTION 1 SPACE DETAILS

1.01 SPACE DETAILS

SECTION 2 MECHANICAL DESIGN

2.01 HVAC SYSTEMS

2.02 CONTROL SYSTEMS

2.03 PLUMBING DESIGN

2.04 AUTOMATIC SPRINKLER SYSTEM

2.05 ELECTRICAL

2.06 BACK-UP POWER SYSTEMS

SECTION 3 GENERAL REQUIREMENTS

3.01 GENERAL SITE REQUIREMENTS

3.02 SECURITY

3.03 INFORMATION TECHNOLOGY/ELECTRONICS AND TELECOMMUNICATIONS

3.04 SIGNAGE

3.05 COMMISSIONING REQUIREMENTS

3.06 MAINTENANCE REQUIREMENTS

3.07 ENVIRONMENTAL MANAGEMENT PLAN

SECTION 1 SPACE DETAILS

1.01 SPACE DETAILS

Please refer to the Lease document for the construction’s standards applicable to the interior tenant area build-out. These standards provide a general outline of the interior build-out requirements. For a complete list of requirements refer to the Lease document. The building architectural design is to include the following elements:

Lobby/Reception Area

• Flooring – To be LVT at circulation areas at seating/waiting areas and reception. Provide LVT at vestibule.

• Walls – At the Vestibule, provide wall, corner, and base protection panels (from wheelchair and cart impact), a one-way glazing panel between the vestibule and the adjacent Police operations room, and electrical power for a future metal detection system. Provide 2-inch x 2-inch x 60-inch high wall corner guards and wall protection panels at all public circulation, hallways, lobby, and waiting areas to protect walls from cart damage. Corner guards shall be thru body color to match wall paint or adjacent finish.

• Doors – Automatic sliding glass doors at the main vestibule.

• Ceiling – Ceiling heights in the lobby waiting areas and reception shall be a minimum of 12-foot. Provide 9-foot ceiling height in other clinic areas.

• Reception area – Information desk shall include both a working countertop, and a higher transaction countertop, and a low gate for security. Refer to OSHA 3148-01R-2004 for more Lobby desk design information. Include continuous curved soffits in the lobby area to help define the reception desks, kiosk check-in stations, information desk, patient education workstation, vending machine area, and waiting/seating areas. Soffits shall also be used as a backdrop for signage. Vertical face at information desk, check-in/reception desks, and lab reception/check-in desks to be impact resistant finish materials such as plastic laminate with 3-form design accent panels. Include partial height decorative glass partitions between reception countertops (patient side) to provide patient privacy.

• Electrical, Data, Voice – One duplex electrical receptacle and one combination data/voice jack per 80 ABOA SF on walls per Lease paragraph Electrical: Distribution and Telecommunications; Distribution and Equipment.

Procedure Room

• Provide 48-inch wide door at toilet room and hallway.

Mental Health Area

PAGE 3 LESSOR: ______ GOVERNMENT: ________

• Include integrated sound masking system with individual room controls in all patient rooms and group therapy areas.

• Provide a minimum sound isolation of 50 STC between all consultation/exam/toilet/group therapy/teamwork/tele-mental rooms and public spaces/hallways.

Audiology Room

• Provide power and data for two (2) Audiology Booths room.

Laboratory Area

• Lab toilet room to have water shut-off valve outside the toilet room door.

• Provide rolling grills (between countertop and soffit) used to close off and secure the Lab at the check-in desk.

• Provide impact resistant vertical panels at the Lab reception/check-in desk such as plastic laminate with 3-form accent design panels.

• Eye wash station inside the lab.

Team-Work Area

• The teamwork areas are to be centrally located within the building with access to natural daylight, either directly or thru an adjacent space that has full height wall glazing on both the interior and exterior wall.

• Provide daylight and views into this area.

• Provide impact wall protection, such as vinyl wall coverings at all walls in the team area.

• Provide 2-inch x 2-inch x 60-inch high wall corner guards at public circulation and hallways to protect walls from cart damage. Corner guards to be thru body color to match wall paint or adjacent finish.

Communication Room and Special Systems Room

• Provide fire rated wood wall board finish (no paint) at three entire walls.

• All perimeter walls to be full height (to deck) for security.

• Provide security camera inside this room.

• Dedicated AC system at Special Systems Room and Communications Room.

• Meet VA PG-18-14-Room finish requirements (i.e. No dropped ceilings in these rooms).

• No interior or exterior windows allowed in these rooms.

• Provide electric strike door hardware.

Police Area

• At Police Armory the design is to meet all VA design codes and be constructed as follows: Construct wall for holding room with 5/8-inch abuse-resistant GWB over security mesh on metal studs as specified for plaster finish. Walls shall meet Level 3 Ballistic standards in the armory. Metal lath or plaster base is unacceptable as security mesh. Security mesh shall be flattened, expanded metal manufactured from high strength, low alloy steel and shall conform to ASTM F 1267, Type 11, Class 1, Mill finish.

Mesh designation: 3/4 #13F Mesh Design Size: 0.923 x 2.10 inch Mesh Opening Size: 0.688 x 1.781 inch 13 meshes per foot: 74% open area Mesh Strand Width: 0.106 inch Mesh Strand Thickness: 0.078 inch Weight: 0.75 pounds per square foot Provide manufacturer’s attachment clips and use recommended fasteners to secure mesh to wall framing.

• The (front lobby) Operations room shall have exterior safety windows with one-way glass and operable window blinds for viewing into the parking lot and main entry.

• Provide two interior one-way safety windows at the front Operations room for viewing into the Lobby and into the Vestibule.

• All entrance doors into Police operations rooms shall open into the room, and include card readers, pin pad, and an independent intrusion detection security system with 90 Db (verify) alarm.

• Include signage at front lobby Police Operation room.

• LVT flooring in all police areas. Tile for restroom areas.

• Provide USB outlets and desk grommet holes at Operations rooms.

• Security cameras to connect to Michael E. DeBakey VAMC security system (no fisheye lens cameras allowed).

• All perimeter walls at Police department to be full height to deck.

• Refer to VA Handbook 0730-4 for additional Police Department requirements.

General

• All wall mounted items require fire rated wood blocking inside walls.

• Emergency pull cords in all restrooms.

• Cypher locks are to be provided on casework in all clinical areas.

PAGE 4 LESSOR: ______ GOVERNMENT: ________

• All plumbing fixtures to be sensor (hands free) and hard wired.

• Cable trays to be located above accessible ceiling (all rooms).

• Add wall protection panel with wood backer board around all mop sinks.

• Include generator for emergency lighting, all refrigeration/freezers in clinic/lab areas, communication equipment, special system equipment, security cameras, door locks, PAC system, and parking gate arms/camera/voice.

• Survey the building during construction (after walls are framed) to locate all WIFI locations for the VA's internal network and the Public/VA WIFI system per VA Requirements.

• Lighting throughout clinic to be LED (in lieu of florescent)

• Provide ligature resistant nurse call devices in all patient and staff toilet rooms. Call devices report to the Teamwork

Area.

• Provide ligature resistant nurse call devices in public toilet rooms. These two call devices report to the front reception desk.

• Wall mounted AEDs shall be located as follows: in Lobby, front clinic hallway (back side of MSA office) and in back staff hallway (at exam room wall across from Clinic supply storage).

• Include grommet hole and device for wire management at all workstation countertops throughout clinic.

• Baby changing stations in public toilets, Women's exam toilets, and lactation room.

• Include water cooled drinking fountains (two sets) back-to-back at lobby/Hallway and elsewhere as required per code.

• Provide window treatments at all perimeter windows including black-out window shades at all meeting rooms and lounge. Windows must be covered with vertical window blinds that utilize traverse rods provided by the Lessor. Blinds that utilize pull cords are not acceptable. Traverse rods shall draw from the center, right or left side. Horizontal blinds are acceptable only for enclosed integrated blinds. Draperies are not acceptable.

• Include cable service at all TV's areas: Lobby and Breakroom.

• Except for the procedure room door listed above, all doors accessed by patients to be 42 inches. Staff-only doors may be 36 inches. Exterior entrance door shall be a minimum of 48 inches. Automatic door openers are required at the main entrance of the clinic and waiting room bathrooms for handicap accessibility. Doors to the clinic area shall be push pad operated on the clinic side and numerical combination operated on the waiting room side. Exterior doors with removable hinge pins will be retained with set pins or spot welded. A locked door will be required from the main waiting room to access the clinic areas.

All doors shall have corresponding doorstops (wall or floor mounted) and silencers. All public use doors and toilet room doors shall be equipped with kick plates. Exterior doors and all common area doors shall have automatic door closers. Hands-free, handicap access on all doors in the pathway from the exterior into the lobby, i.e., the main VA Clinic public entrance.

Door for Telecommunication closet(s), Medication room, Police Office and Suite entry door and all other doors connecting the government space with the rest of the building, shall be equipped with 7-pin Interchangeable Cores and strike plates to be operated by card readers.

• Door Locks. All doors must be equipped with cylinder lock locking hardware and master keyed to match existing VA “Best” brand, 7 pin locking system. Egress doors must be equipped with panic hardware and meet NFPA requirements for exit. Toilets to be equipped with privacy locks that can be unlocked in emergency with coin from outside. The Lessor will be responsible for providing and installing an automatic locking system with a buzzer to be used on the door from the waiting room to access the clinic area. The Lessor/Owner shall provide all hardware to include the interchangeable cores. The Lessor shall be responsible for the cost of the cores. The Lessor/Owner shall provide a door schedule submittal for VA approval. The key numbering convention will be agreed upon.

Three master keys will be provided to the government. An exception to the building entrance will be made when the VA is not sole building tenant. The entire space will be keyed the same except for the following spaces: Electrical Closet, OI&T Closet, Janitorial Closet, Storage/Supply Closets, Mechanical Space.

• Provide door locks at Copy/Supply rooms, bulk storage, hazardous storage, utility, clinic supplies and all sliding doors.

Keypad access required at all medication rooms, electrical, and HAC closets.

• Building designed to meet LEED standards and requirements.

• Provide 2-inch x 2-inch x 60-inch corner guards at public circulation (lobby, vestibule, etc.) and hallways to protect walls from cart damage. Corner guards to be thru body color to match wall paint or adjacent finish.

• Provide 2-inch x 2-inch x 60-inch stainless steel corner guards at staff hallways to protect walls from cart damage.

• Refer to The Facility Guidelines Institute Guidelines for Design and Construction of Outpatient Facilities 2018 edition for additional requirements including acoustic requirements to protect patient privacy.

• Bathroom sinks shall be equipped with soap dispenser and paper towel dispenser provided by the lessor. A shelf and mirror provided by the lessor shall be installed above each sink. Each commode shall have a toilet paper dispenser provided by the lessor installed within easy reach. A coat hook shall be installed on inside face of door. All toilets shall meet handicap accessibility codes and will include grab bars at commode. Metal partitions required at urinals and metal partitions with doors at commodes unless otherwise noted.

• Lessor must provide, approved by the LCO, an internally lighted sign with VA logo and words that designate the name of the clinic on sign a minimum of 4 ft by 8ft legible from main serving road. Sign shall be a minimum of 24 inches above finished grade. Lessor shall develop and provide a complete exterior signage plan to include identification, directional, informational, and regulatory signage. Signage must comply with local municipality’s codes and specifications. Careful consideration of the location of monument signs shall be taken to avoid sight triangle

PAGE 5 LESSOR: ______ GOVERNMENT: ________

encroachment. Lessor shall provide signage on the building/ door. Signage outside building provided by the Lessor, according to VA specifications and meets City Ordinances.

• Telecommunications room(s) must include:

-All perimeter walls shall extend from floor slab to structural system (deck) to prevent up and over access.

-Four (4) electrical 20 amp duplex outlets -No windows or other openings -Door hinges inside the room door -Metal frame and door with dead lock pin, automatic locking upon entry and exit for a secure room.

-Doors shall be 1-3/4 in hardwood or hollow steel with welded pins. All doors shall be outfitted with 2 locksets. Doors with metal frames shall have a mortise lock with a deadlock pin feature and automatically latch on closure. If the door is not in a steel frame, one of the two locks must be a jimmy-proof rim dead lock.

• Facilities shall be non-smoking, and Lessor must provide signage prohibiting smoking and directing visitors and staff to the designated smoking areas, if applicable.

SECTION 2 MECHANICAL DESIGN

2.01 HVAC SYSTEMS

The HVAC systems shall be provided to meet the requirements of the current FGI Guidelines. Comply with all current building codes with all local amendments.

HVAC Design Calculations are to use the outdoor design temperatures listed in the current local codes and FGI Guidelines.

Systems to maintain temperatures, pressure relationships, and humidity requirements listed the FGI Guidelines. Verify occupancy and heat loads from all equipment prior to commencing HVAC system design.

The HVAC systems shall be zoned to provide individual control as specified in the current FGI Guidelines.

Provide stand-alone conditioning for telecom and server rooms in accordance with ASHRAE, the current VA HVAC Design Manual, and Appendix E. These rooms shall maintain the temperature and humidity requirements within the VA HVAC Design Manual.

Storage rooms shall be controlled separate from other spaces with their own thermostat and humidistat in order to maintain space and humidity requirements per the FGI Guidelines.

2.02 CONTROL SYSTEMS

A complete automatic temperature control system shall be provided. The direct digital control (DDC) system shall be a complete system suitable for the heating, ventilating, and air conditioning (HVAC) systems provided. The system shall also be accessible by VA. The system shall have a GUI interface that includes a floor plan that shows the location and status of the controlled equipment. It shall be expandable and capable of accepting additional points.

Storage rooms, Communications Room and Special Systems Room shall be controlled separate from other spaces with their own thermostat and humidistat in order to maintain space and humidity requirements per the FGI Guidelines.

Toilet rooms will use inline or ceiling-mounted exhaust fans interlocked with outside air controls. Janitor's closets will have continuous exhaust.

2.03 PLUMBING DESIGN

Provide plumbing systems in accordance with all local building codes with all local amendments.

Provide all plumbing fixtures required for this project. Provide sanitary and vent piping to all fixtures. Provide domestic cold and hot water systems to all fixtures.

Specific plumbing requirements include:

- Lab requires one eye wash station with the required emergency mixing valve as required by ANSI/ISEA Z358.1

- Lab toilet room with wall switched water shut off

- All sensor faucets to be hardwired.

PAGE 6 LESSOR: ______ GOVERNMENT: ________

- Thermostatic mixing valves provided on plumbing fixtures per VHA Directive 1061 and the VA Plumbing Design Guide.

- Provide separate irrigation water meter.

2.04 AUTOMATIC SPRINKLER SYSTEM

Provide an automatic sprinkler system in accordance with the current VA Fire Protection Design Manual.

Comply with all local building codes, including current amendments.

The server rooms shall be protected with a wet pipe sprinkler system overhead and standard response fusible link sprinkler heads. Quick response glass bulb heads are not acceptable.

The secure areas (Holding Room) in the Police Operations area require an institutional style anti-ligature sprinkler head for use in detention facilities.

2.05 ELECTRICAL

Specific Design Requirements

A single utility source is required to the facility. New electrical service shall be 480/277V, three-phase, four-wire switchgear with feeder breakers. The electrical distribution system shall be designed such that additional building modules can be added without having to route conduit through production areas.

Lighting

Lighting controls shall comply with ASHRAE 90.1, including occupancy and daylight harvesting where applicable. In areas with multiple entrances, three-way switching will be required at each entrance location. Low voltage control system shall be used throughout the building. Occupancy sensors shall be dual technology. At a minimum, dimming controls are required in conference rooms, tele-mental health, mental health group therapy, group meeting rooms, tele-health, shared appointment rooms and tele- retinal areas.

LED exit signs and egress lighting NFPA 101-compliant, with integral battery.

Interior and exterior light fixtures shall be LED. Interior fixtures in Conference room, tele-health, tele- retinal, tele-mental health, Shared appointment rooms, and Mental Health Group Therapy Rooms shall include dimming drivers. Exterior fixtures, including parking areas, shall meet local adopted design standards. Meet the power density requirements of ASHRAE 90.1.

Power Distribution

The electrical distribution shall comply with, NFPA 70 (NEC, current edition), and any local amendments.

K-rated transformers with 200% neutrals shall be utilized to serve non-linear loads. Panelboards serving nonlinear loads shall have 200% neutral buses. Computers shall have dedicated circuits/neutrals. Circuit breakers SCCR or AIC shall be fully rated.

Convenience receptacle circuits shall be limited to six receptacles per circuit. Provide a minimum of 25% excess load capacity throughout distribution after demand factors have been applied to the electrical calculations. Distribution panelboards shall have 25% excess prepared space. Distribution equipment shall be in rooms or closets dedicated solely for this purpose.

Provide surge protection at main switchgear and panels serving computers/critical equipment. Power monitoring and metering shall be installed.

Dedicated receptacles shall be provided for the electrical equipment charging area.

Provide a minimum of one general-purpose duplex receptacle outlet per wall in each room. On walls exceeding ten feet, provide an additional duplex outlet per eight feet of wall or fraction thereof.

Receptacle spacing shall not exceed eight feet. Where possible, systems furniture shall be fed by wall mounted outlets.

Otherwise, above ceiling junction boxes shall be provided for connection/routing of circuits via power poles.

Perform arc-flash study/labels on power distribution equipment in compliant with NFPA 70E. Provide lockout/tag-out procedures /labeling for distribution equipment.

PAGE 7 LESSOR: ______ GOVERNMENT: ________

Provide USB outlets at counter height for each workspace in the Police Operations Area. USB outlets shall be located adjacent to each power outlet in the Lobby Waiting areas, Lounge/Break rooms, and conference rooms.

All devices shall be hospital grade. Provide red face plates and devices for emergency power.

2.06 BACK-UP POWER SYSTEMS

The facility shall have a standby emergency generator to support the loads listed below. Provide automatic transfer switches (ATS) and associated branch distribution in accordance with NEC, NFPA 99 and NFPA 101.:

Life Safety, lighting, clinical refrigerators and freezers, lab refrigerators and freezers, communication equipment, special system equipment, security cameras and systems, intrusion detection systems, card readers, PACS system, parking gate arms/voice, Pyxis and UPS. Confirm other loads as required in the Equipment List. Pyxis shall also be protected by a UPS system.

Provide critical-grade enclosures, stainless steel exhaust and belly tank with integral fuel polishing system. Provide fuel capacity and routine generator testing/maintenance in accordance with NFPA 110, current edition, and VA requirements. Provide an automatic digital continuous fuel monitoring system compliant with VA CFM Specification 23 10 10.

SECTION 3 GENERAL REQUIREMENTS

3.01 GENERAL SITE REQUIREMENTS

• Provide passive barriers for protection from vehicles at site utilities, and other areas requiring protection. Passive vehicle barriers shall be selected on the appropriateness of the architecture of the facility and specifics of the site and natural environment, or man-made barriers may be used.

• Negative pressure in dirty utility rooms.

• Provide an access drive for patients and staff and a separate access drive for service vehicles. The patient drive to include a parking lot by-pass lane within the site (so patient vehicles can circle back around and park after dropping off at the main entrance) per VA (Site development section of) Design Manual and Appendices.

• Provide a separate patient parking lot near the front main entrance designed for pedestrian and vehicular traffic to safely co-exist. Include a variety of parking space types including ADA accessible auto and van spaces, motorcycle spaces, etc. The parking stall number shall be determined using local zoning codes AND this RLP.

• Provide one bike rack near the front patient entrance and one near the staff entrance. Each rack to accommodate 10 bikes minimum.

• Provide a separate employee parking lot with electronic gates at the vehicle entrance and at the vehicle exit each with intercom and card reader control. Connect Intercom to Police Operations front and back offices. Parking lot to be located adjacent to staff entrance.

• The main patient entrance design shall include an architectural canopy structure that covers two driving lanes and one drop-off lane while maintaining a 14-foot height clearance.

• Exterior bollards, planters, or other VA approved barriers shall be installed at the main patient drop off entrance.

• VACM will locate a Mobile Unit (for diagnostics or treatment) located within close proximity to the Clinic access door. No additional parking provisions are required for this unit. See MRI requirements below.

• Provide exterior and interior doors at the mechanical room.

• Provide a transformer pad and generator pad with a fence and landscape screening.

• Provide dumpster pad and adequate area for garbage truck pick up.

• Provide staff entry with covered canopy extending from doors to parking lot curb.

• Locate site water retention pond a safe distance from building and pedestrians and provide a perimeter fence with landscape screen at any water retention ponds.

• Provide a concrete stoop and a canopy at all doors.

• All fencing on site, if any, to match and to be decorative metal (in lieu of chain link).

• Lessor to properly maintain plants and lawns, replace light bulbs, fluorescent tubes, ballasts, and starters, provide and empty exterior trash cans and clean area of any discarded cigarette butts.

• Lessor to control pests as needed, using Integrated Pest Management techniques, as specified in the VA

Environmental Management Integrated Pest Management Technique Guide (E402- 1001).

• Provide an at grade loading 'dock' area near the employee entrance. Design adequate space for truck maneuverability and parking. Provide wheel path diagram to support turning movements of facility equipment, delivery and waste removal vehicles. Loading area should accommodate at least one standard sized box truck.

Provide a canopy over the full width of the loading area. Provide a hard-wired pit-mounted scissor lift, for truck delivery unloading. Provide proper drainage of lift pit.

PAGE 8 LESSOR: ______ GOVERNMENT: ________

• Provide an ambulance parking space near the employee entry, separate from the loading area with a canopy covering from the parking space to the employee entry.

• MRI and pad: shall be Portland cement concrete at least 43 feet long by 10 feet wide. If reinforcement of concrete is required, use only non-ferrous reinforcement materials. Variations in pad levelness shall not exceed 1/8-inch in 10'- 0". Location should be near side exit door at Grid intersection E/9. Provide an accessible concrete sidewalk from the door stoop to the parking pad.

• Additional MRI requirements:

o Lessor shall furnish a dedicated five-wire 480V, 3-phase wye connection with neutral and ground, 150

Amp circuit to supply power to mobile MRI/CT scanner trucks at the MRI pad. The safety disconnect switch shall have lock-on provisions, which will allow the switch to be locked in the "ON" position. The disconnect switch shall also have lock- off provisions. Provide safety disconnect in electrical circuit, per code, on exterior of building for MRI/CT. Electrical feed shall terminate on exterior of building at Russell stoll connector rated for service receptacle, in a weatherproof box. The bottom of the receptacle shall be a minimum of 3 feet above grade. The disconnect switch, receptacle, and telecommunications jacks shall be mounted on concrete posts with strut framing adjacent to the MRI concrete pad.

o Lessor shall furnish a weatherproof box for telecommunications located adjacent to power receptacle.

Conduit shall extend to interior distribution system in the building. Install three (3) exterior telecommunications jacks.

o Provide the following plumbing provisions in two in-ground boxes adjacent to the truck pad. One in-ground box shall be for water supply connections and one in-ground box shall be for sanitary wastewater connection:

Provide a hose bib and backflow preventer, connected to a cold water supply line, for connection of a ¾-inch hose.

Provide ¾-inch female connector and backflow preventer, connected to a cold water supply line, for connection of a ¾-inch I.P.S. male threaded hose connector. Size line to provide 5 gallons per minute at 45-60 PSI. Provide an adjustable pressure regulator with gauge to ensure that pressure does not exceed 60 PSI. Water intake equipment will be protected with physical hardware equipment to provide preclusion of entry or introduction of foreign materials and also provide indication of tampering. Intake facilities above ground will provide physical barriers to preclude entry and tampering of equipment.

Provide 1½-inch female threaded connector, connected to the sanitary wastewater drainage system, for connection of a 1½-inch male threaded hose connection.

3.02 SECURITY

Lessor shall comply with the security requirements shown in the Facility Security Level (FSL) II document Appendix C2. The document includes requirements for the site and building including concentric levels of protection, building systems, closed circuit television system, intrusion detection system, physical access control system security phones, and intercoms. The items below are supplemental to the information included in Appendix C2.

The following rooms require "up and over" protection to prevent unauthorized access: Record Files Storage, Communications, Holding and Police Armory.

3.03 INFORMATION TECHNOLOGY/ELECTRONICS AND TELECOMMUNICATIONS

PUBLIC ADDRESS (PA)

Provide public address and mass notification (PA) system(s) as required. System(s) shall be most current technology or manufacturer. System shall be capable of being zoned by area as requested by the VA. At a minimum provide a system with the capacity of 12 zones plus an all call. Exterior speakers shall be a separate zone. This system is required to be tied into the PBX with contractor provided interface.

STRUCTURED CABLING SYSTEM

Provide Category 6A structured cabling system throughout clinic. VA network and Non-VA networks shall terminate in separate rooms. Provide wireless access point cabling outlets throughout clinic for VA provided and installed WAP units.

NON-VA NETWORKS

The facility will contain Non-VA networks for CMOP contractors and the lessor. Non-VA modems and routers shall be located in the Demarc (Special Systems) room, not the VA IT rooms. The Non-VA networks shall not utilize wireless connectivity, only hard-wired, to prevent interference with VA wireless antennas. Additionally, provide outlets and conduit for timeclocks. Provide standalone Public WIFI system. Non-VA network infrastructure, including outlets, cabling, pathways, patch panels, wire management, racks and other components of the Non-VA network system shall be provided with the facility construction.

PAGE 9 LESSOR: ______ GOVERNMENT: ________

All Non-VA active equipment such as servers, switches, wireless access points, PC's, etc. will not be included in the building construction scope but will be furnished using other sources.

3.04 SIGNAGE

Lessor shall develop and provide a complete exterior and interior signage program to include identification, directional, informational, and regulatory signage. Signage must comply with local municipality's codes and specifications. Careful consideration of the location of monument signs shall be taken to avoid sight triangle encroachment.

Lessor shall provide ground mounted, illuminated horizontal monument sign to identify the Outpatient Clinic. VA will furnish message layout, content, and colors for the monument sign.

All signage to comply with the VA Signage Design Manual.

3.05 COMMISSIONING REQUIREMENTS

Lessor shall perform commissioning in accordance with the VA Whole Building Commissioning Process Manual, specifically the following systems:

- Building Exterior Closure

- Fire Suppression

- Plumbing

- HVAC

- Electrical

- Communications

- Electronic Safety and Security

- Interior Sound Rated walls

In addition to system commissioning requirements called out in the Facility Guidelines Institute (FGI), the developer shall also test and commission all sound rated walls required by FGI. FGI can be found on the following link:

HTTPS://WWW.FGIGUIDELINES.ORG/

The final HVAC test and balance report shall be completed by an independent third-party.

3.06 MAINTENANCE REQUIREMENTS

Lessor will maintain utilities and equipment as prescribed by local codes and references listed in Appendix D. Lessor will provide records of the maintenance in the format and frequency required by the VAMC to ensure compliance with TJC.

3.07 ENVIRONMENTAL MANAGEMENT PLAN

The lessor shall be responsible for providing services relating to environmental management.

End of Document https://www.fgiguidelines.org/

SPACE DETAILS
1.01 space details
SECTION 2 MECHANICAL DESIGN
2.01 HVAC SYSTEMS
2.02 CONTROL SYSTEMS
2.03 PLUMBING DESIGN
2.04 AUTOMATIC SPRINKLER SYSTEM
2.05 ELECTRICAL
2.06 BACK-UP POWER SYSTEMS
SECTION 3 GENERAL REQUIREMENTS
3.01 GENERAL SITE REQUIREMENTS
3.02 security
3.03 information technology/ELECTRONICS AND TELECOMMUNICATIONS
3.04 SIGNAGE
3.05 COMMISSIONING REQUIREMENTS
3.06 MAINTENANCE REQUIREMENTS
3.07 ENVIRONMENTAL MANAGEMENT PLAN