This report provides the results of an asbestos and lead inspection conducted at the 1800 Cabrillo Memorial Drive Visitor's Center View Building in San Diego, California. The inspection tested interior and exterior suspect tile surfaces in preparation for an upcoming renovation project under National Park Service Solicitation 140P8523R0015 to rehabilitate the visitor center view building. No asbestos was detected in any samples tested. All surfaces tested were found to contain lead concentrations less than 0.5 mg/cm2. The report recommends dust containment and worker protection practices for all surfaces during renovation work involving aggressive disturbance due to the potential to create lead-contaminated dust even from surfaces with lower detected lead levels.

View the file

Other files

Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

10601 Tierrasanta Blvd. #G120 858-688-2868 San Diego, CA 92124 info@sandiegotesting.com

Limited Asbestos and Lead Report

1800 Cabrillo Memorial Drive Visitor’s Center View Building

San Diego, CA 92106

July 12, 2023

Prepared by:

Mike Anderson CDPH Lead Certification # LRC-00002576, 2577 California Certified Asbestos Consultant # 06-3922

Asbestos and Lead Report 1800 Cabrillo Memorial Drive San Diego, CA

1. Overview

Mike Anderson, an EPA AHERA-accredited building inspector representing San Diego Testing, performed limited asbestos and lead testing at 1800 Cabrillo Memorial Drive – Visitor’s Center View Building, San Diego, CA 92106 on 07/11/2023. The property owner is Cabrillo National Monument, which can be reached at (619) 523-4285. The site is a national park facility. The asbestos and lead testing included interior and exterior suspect tile surfaces expected to be impacted by an upcoming renovation.

The lead inspection was performed in accordance with the protocols in Title 17 of the California Code of Regulations (17CCR 35000 et seq.) effective April 30, 2008, and the procedures described in Chapter 5: Risk Assessment, section II (A), (B), (C), and (D), “Guidelines for the Evaluation and Control of Lead-Based Paint Hazards in Housing,” U.S. Department of Housing and Urban Development, June 1995.

Test methods used for asbestos testing included bulk sample collection and analysis at Eurofins EMLab P&K, an accredited laboratory in San Diego, CA.

Test methods used for lead testing included a portable X-ray Fluorescence (XRF) analyzer, Heuresis Model Pb200i, serial number 1557.

2. Regulatory Background

Title 17 of the California Code of Regulations (CCR) contains provisions dictated by California Department of Public Health (CDPH) and applies when "lead activities" are performed in residential or public buildings. It requires testing companies to submit CDPH form 8552 to CDPH after conducting lead investigations. Form 8552 contains test results and property owner information. Title 17 includes lead-safe work practice requirements when "lead activities" are performed in any type of structure with any construction date. "Lead activities" includes work that can create lead-contaminated dust. Lead-contaminated dust is defined as (a) forty micrograms per square foot (40 μg/ft2) for interior floor surfaces; or (b) two hundred and fifty micrograms per square foot (250 μg/ft2) for interior horizontal surfaces; or (c) four hundred micrograms per square foot (400 μg/ft2) for exterior floor and exterior horizontal surfaces.

The Environmental Protection Agency (EPA) Renovation, Repair, and Painting (RRP) Rule requires training and certification for anyone working for compensation in pre-1978 residential structures, day care centers, and schools where known or assumed lead-based paint is impacted.

Lead-based paint is any surface coating containing 1.0 mg/cm2 lead or greater or 5000 ppm lead or greater.

The Cal/OSHA Lead in Construction Standard, CCR Title 8 Section 1532.1 contains safety provisions that protect employees in construction that may be occupationally exposed to lead. It includes worker air monitoring, blood lead level monitoring, training, notifications, and specific work practices.

The Cal/OSHA Asbestos in Construction Standard, CCR Title 8 Section 1529 applies when asbestos containing material is removed or disturbed in any quantity during construction related activities (except when a home-owner is doing work inside his own home). Materials found to contain asbestos with concentrations at 0.1% or greater must be handled by an asbestos abatement contractor.

The San Diego County Air Pollution Control District (APCD), Rule 1206, applies to institutional, commercial, public, or industrial facilities, as well as residential buildings, condominiums, or apartments that contain more than four dwelling units. Additionally, a group of residential buildings located on the same property, managed by a common entity, falls under the Rule, such as a single-family home with a granny flat. The Rule requires that a facility survey be conducted prior to renovation or demolition of 100 square feet or more in 365 days or one calendar year, and prior to submitting a "Notice of Intention Form" to the APCD. A complete copy of the facility survey must be maintained onsite for the duration of any renovation and/or demolition operation, and be made available to APCD upon request. There are no exclusions related to construction date(s) of the structure(s).

The EPA's National Emission Standards for Hazardous Air Pollutants (NESHAP) standard requires an owner or operator of a renovation or demolition activity occurring in an institutional, commercial, public, or industrial structure, installation, or building to thoroughly inspect the affected facility or part of the facility where the demolition or renovation operation will occur for the presence of asbestos. There are no exclusions related to construction date(s) of the structure(s).

3. Asbestos Results

No asbestos was detected in any of the samples collected. The following table lists all samples collected. For additional details please see the laboratory report and asbestos sample locations attached to this report.

Sample Numbers

Homogeneous Material

Sample Location(s)

Represented Location(s)

Approximate Quantity

Asbestos

ACM

Category

1 Grout / Mortar Interior East

Throughout Interior & Exterior Tile Floor Areas

ND

- 2 Grout / Mortar Exterior

Northeast

ND

3 Grout / Mortar Exterior

Southwest

ND

ND = no asbestos detected

4. Lead Results

All surfaces tested were found to contain lead in concentrations less than 0.5 mg/cm2. For additional details please see the XRF report attached.

5. Conclusions and Recommendations

No asbestos was detected in any of the samples collected. No recommendations are warranted.

The purpose of the lead inspection was to identify surfaces with lead concentrations greater than

0.5 mg/cm2 and surfaces with lead concentrations greater than 1.0 mg/cm2. All of the lead regulations cited above make it a violation to create lead-contaminated dust in areas accessible to unprotected humans. It's important to understand that disturbance of surfaces with XRF measurements below 0.5 mg/cm2 and 1.0 mg/cm2 potentially could create lead-contaminated dust if work practices are aggressive and especially if power tools are used. XRF readings cannot identify specific levels of lead but rather provide results with a range of error. Therefore it is recommended to use dust containment practices and worker protection for all surfaces when aggressive disturbance of the surface occurs.

6. Limitations

This assessment was limited to specific areas/materials to be impacted by an upcoming project at the direction of the property owner representative. Additional asbestos and lead materials may be present at the property and this report should not be used for the purposes of a different renovation or demolition project in place of a comprehensive asbestos/lead survey for regulatory compliance.

In the event untested suspect asbestos or lead materials are discovered during the course of demolition they should be sampled or assumed to be above regulatory thresholds.

7. Attachments

Asbestos Sample Locations and Room Designations Asbestos Laboratory Report Lead XRF Report CDPH Form 8552 Inspector’s Credentials

Cabrillo Memorial Drive Visitor’s Center View Building

Asbestos Sample Locations and Room Designations

N

Drawing Scale: not to scale

Open Area

Approved by:

Approved Signatory Ahmed Fageer

Report for:

Mr. Mike Anderson San Diego Testing 1859 Amie Ct San Marcos, CA 92069

Regarding:

Eurofins EPK Built Environment Testing, LLC Project: 1800 Cabrillo Memorial Dr.; Visitors View Bldg

EML ID: 3316162

All samples were received in acceptable condition unless noted in the Report Comments portion in the body of the report. The results relate only to the samples as received and tested. The results include an inherent uncertainty of measurement associated with estimating percentages by polarized light microscopy. Measurement uncertainty data for sample results with >1% asbestos concentration can be provided when requested.

Eurofins EPK Built Environment Testing, LLC ("the Company"), a member of the Eurofins Built Environment Testing group of companies, shall have no liability to the client or the client's customer with respect to decisions or recommendations made, actions taken or courses of conduct implemented by either the client or the client's customer as a result of or based upon the Test Results. In no event shall the Company be liable to the client with respect to the Test Results except for the Company's own willful misconduct or gross negligence nor shall the Company be liable for incidental or consequential damages or lost profits or revenues to the fullest extent such liability may be disclaimed by law, even if the Company has been advised of the possibility of such damages, lost profits or lost revenues. In no event shall the Company's liability with respect to the Test Results exceed the amount paid to the Company by the client therefor.

Dates of Analysis:

Asbestos PLM: 07-12-2023

Service SOPs: Asbestos PLM (EPA 40CFR App E to Sub E of Part 763 & EPA METHOD 600/R-93-116, SOP EM-AS-S-1267) NVLAP Lab Code 500034-0

EMLab ID: 3316162, Page 1 of 2Eurofins EPK Built Environment Testing, LLC

Eurofins EPK Built Environment Testing, LLC 8304 Clairemont Mesa Blvd, Suite 103, San Diego, CA 92111

(800) 651-4802 www.eurofinsus.com/Built Client: San Diego Testing C/O: Mr. Mike Anderson Re: 1800 Cabrillo Memorial Dr.; Visitors View Bldg

Date of Sampling: 07-11-2023 Date of Receipt: 07-11-2023 Date of Report: 07-12-2023

ASBESTOS PLM REPORT

Total Samples Submitted: 3 Total Samples Analyzed: 3

Total Samples with Layer Asbestos Content > 1%: 0

Location: 1, Grout/Mortar - Interior E Lab ID-Version‡: 16107406-1

Sample Layers Asbestos Content Dark Gray Grout ND

Gray Mortar ND Composite Non-Asbestos Content: < 1% Cellulose Sample Composite Homogeneity: Good

Location: 2, Grout/Mortar - Ext. NE Lab ID-Version‡: 16107407-1

Sample Layers Asbestos Content Dark Gray Grout ND

Gray Mortar ND Composite Non-Asbestos Content: 2% Cellulose Sample Composite Homogeneity: Good

Location: 3, Grout/Mortar - Ext. SW Lab ID-Version‡: 16107408-1

Sample Layers Asbestos Content Dark Gray Grout ND

Gray Mortar ND Composite Non-Asbestos Content: 2% Cellulose Sample Composite Homogeneity: Good

EMLab ID: 3316162, Page 2 of 2Eurofins EPK Built Environment Testing, LLC

The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by any agency of the federal government. The Company reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.

Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.

‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is reflected by the value of "x".

San Diego Testing

10601 Tierrasanta Blvd. #G120

San Diego, CA 92124

XRF Report

Project: 1800 Cabrillo Memorial Drive

Test Date: July 12, 2023

Reading

Number Date Time Type Duration Room Side Component Substrate Condition PbC

PbC

Error Units

0.5 to 1.0 mg/cm2

> 1.0 mg/cm2

14 7/11/2023 12:51:40 Paint 5 Calibration 1 0.1 mg/cm2

15 7/11/2023 12:51:50 Paint 5 Calibration 1 0.1 mg/cm2

16 7/11/2023 12:52:01 Paint 5 Calibration 1 0.1 mg/cm2

17 7/11/2023 12:57:21 Paint 1 Open Area North Floor Ceramic Intact 0 0.3 mg/cm2

18 7/11/2023 12:57:53 Paint 1 Open Area East Floor Ceramic Intact 0 0.3 mg/cm2

19 7/11/2023 13:07:16 Paint 1 Exterior East Floor Ceramic Intact 0 0.3 mg/cm2

20 7/11/2023 13:12:06 Paint 1 Exterior North Floor Ceramic Intact 0.1 0.3 mg/cm2

21 7/11/2023 13:12:22 Paint 1 Exterior West Floor Ceramic Intact 0.4 0.3 mg/cm2

22 7/11/2023 13:12:43 Paint 1 Exterior South Floor Ceramic Intact 0.1 0.3 mg/cm2

23 7/11/2023 13:20:46 Paint 5 Calibration 1 0.1 mg/cm2

24 7/11/2023 13:20:57 Paint 5 Calibration 1 0.1 mg/cm2

25 7/11/2023 13:21:13 Paint 5 Calibration 1 0.1 mg/cm2

XRF Report Page 1 of 1

State of California—Health and Human Services Agency California Department of Public Health

LEAD HAZARD EVALUATION REPORT

Section 1 — Date of Lead Hazard Evaluation 07/05/2023

Section 2 — Type of Lead Hazard Evaluation (Check one box only)

☐ Lead Inspection ☐ Risk assessment ☐ Clearance Inspection ☒ Other (specify) Tile Testing

Section 3 — Structure Where Lead Hazard Evaluation Was Conducted

Address [number, street, apartment (if applicable)]

1800 Cabrillo Memorial Drive City

San Diego County

San Diego Zip Code

92106

Construction date (year) of structure

Type of structure

☐Multi-unit building ☐School or daycare

☒Single family dwelling ☐ Other_________

Children living in structure?

☐ Yes ☐No

☒Don’t Know

Section 4 — Owner of Structure (if business/agency, list contact person)

Name

Jed Sauer (National Parks Service) Telephone number

(619) 523-4285

Address [number, street, apartment (if applicable)]

1800 Cabrillo Memorial Drive City

San Diego State

CA

Zip Code

92106

Section 5 — Results of Lead Hazard Evaluation (check all that apply)

☒ No lead-based paint detected ☐Intact lead-based paint detected ☐Deteriorated lead-based paint detected

☐No lead hazards detected ☐Lead-contaminated dust found ☐Lead-contaminated soil found ☐Other

Section 6 — Individual Conducting Lead Hazard Evaluation

Name

Michael Anderson Telephone number

(858) 688-2868

Address [number, street, apartment (if applicable)]

10601 Tierrasanta Blvd. #G210 City

San Diego State

CA

Zip Code

92124

CDPH certification number

LRC-00002576, 2577

Signature

Date

7/11/2023

Name and CDPH certification number of any other individuals conducting sampling or testing (if applicable)

Section 7 — Attachments

A. A foundation diagram or sketch of the structure indicating the specific locations of each lead hazard or presence of lead-based paint;

B. Each testing method, device, and sampling procedure used;

C. All data collected, including quality control data, laboratory results, including laboratory name, address, and phone number.

First copy and attachments retained by inspector

Second copy and attachments retained by owner

Third copy only (no attachments) mailed or faxed to:

California Department of Public Health

Childhood Lead Poisoning Prevention Branch Reports 850 Marina Bay Parkway, Building P, Third Floor

Richmond, CA 94804-6403

Fax: (510) 620-5656

CDPH 8552 (6/07)