Att 002 - Fire Alarm Inspection Reports - 2900 Block.pdf

PDF 2 MB Posted

Attached to
Fire Alarm Replacement Federal contract opportunity
Solicitation number
W9124823Q0011
Issued by
Department of the Army Materiel Command Mission and Installation Contracting Command

About this file

This document contains fire alarm inspection reports for four buildings at an Army installation. The reports detail inspection dates, teams, device locations and addresses, sensitivity test results, and notes on failures and deviations from standards. Numerous smoke detectors failed sensitivity testing on Siemens fire alarm panels. Backflow preventers also failed inspections or required repairs. Sprinkler systems required new heads and had missing or unpainted components. The reports identify building numbers, locations, and points of contact for the installation and the fire and security contractor that performed the inspections.

View the file

Other files for this federal contract opportunity

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

X

BATTERY VOLTAGE TYPE:

VDC VDC AH 12

VDC VDC AH 12

ELEVATOR SYSTEM(S)

SHUNT

BATTERY VOLTAGE TYPE:

VDC VDC AH

VDC VDC AH

KF KINGFISHER PS PULL STATION HS HORN / STROBE WA WATER ALARM AN ANNUNCIATOR

FA FIRE ALARM PANEL SD SMOKE DETECTOR S STROBE ONLLY DH DOOR HOLDER AN MASS CONSOLE

BPS POWER SUPPLY HD HEAT DETECTOR MS MASS STROBE TS TAMPER SWITCH CR CONTROL RELAY

VP VOICE / MASS PANEL DD DUCT DETECTOR SPK SPEAKER WF WATER FLOW CM CONTROL MOD

PASS

DOOR HOLDERS PASS

HVAC AUTO RESTART FROM FACP RESET PASS

PASS

PRIMARY RECALL

IS SYSTEM CONNECTED TO MONITORING AGENCY

RESPONSE TO SUPERVISORY TIME:N/A

1:19

ELEVATOR RESTART FROM FIRE SYSTEM RESET

KFRI COMBO

PASS

N/A

ANNUNCIATOR

SPECIAL CONSIDERATIONS - List any unique functions to be aware of before testing

KINGFISHER

MODEL TYPE LOCATION

PASS

TIME:

HVAC SHUTDOWN

PASS

FIRE ALARM

PANEL REPORT

VDC

BATTERY CHARGING VOLTAGE

PANEL MANUFACTURER

1:19

5/27/2021

RESPONSE TO TROUBLE

System DOES NOT provide the audible notification for the facility. The fire alarm system uses Horn/Strobes

NOTES, FAILURES AND SYSTEM DEVIATIONS FROM CONTRACT STANDARDS

Cooper Wheelock AMP for Mass Notification system is bad. No voice notification in the facility, Mass

20.3

TIME:

SIEMENS

13.51

DIGITAL ALARM RADIO TRANSMITTER (DART)

VDC 26.0

LAMPS / LED TEST

LOCATION

SECONDARY RECALL RECALL

13.47

CIRCUIT BREAKER LOCATION

LOCATION

ELECT ROOM

AMP

PASS @ 78%

PASS @ 78%

VDC

INSPECTION DATES:

27.5

BATTERY CHARGING VOLTAGE

POC CONTACT INFO

20.3

MXL-IQ

INSPECTION TEAM:

JENNIFER

MODEL

CENTERAL DISPATCH 270-798-1221

MONITORING AGENCY

Indiana AVE Fort Campbell KY 42223

FIRE ALARM CONTROL PANEL (FACP)

BUILDING POC NAME

PANEL MANUFACTURER

KS,BH,RR

NCS

11501 Plantside Drive Suite #4 Louisville, KY 40299

(502) 614-8646

Premier Fire & Security Inc.

1251 N 6th St

Paducah, KY 42002

(270) 443-7060

VDC

MONITORING AGENCY PERSONNEL NOTIFIED

PASS

SWAPPED BATTERY CHARGING LOCATIONLED TESTTRANSMITTER RECEIVES ALARMS FROM FACP

NAPASS

TRANSMITTER RECEIVES TROUBLES FROM FACP

MODELRESPONSE TO ALARM MANUFACTURER

AMP

AMP

1 YEAR -

INSPECTION TYPE

PASS

BUILDING NUMBER 2 YEAR -

5 YEAR -

OTHER -

26.0 AMP

BUILDING 2989-5YR-5-27-2021 PAGE 1 OF 9

VDC VDC AH 12

VDC VDC AH 12

BATTERY VOLTAGE TYPE:

VDC VDC AH 12

VDC VDC AH 12

BATTERY VOLTAGE TYPE:

VDC VDC AH 12

VDC VDC AH 12

BATTERY VOLTAGE TYPE:

VDC VDC AH

VDC VDC AH

BATTERY VOLTAGE TYPE:

VDC VDC AH

VDC VDC AH

PASS

FAIL

FAIL @ 0%

NCS

11501 Plantside Drive Suite #4 Louisville, KY 40299

(502) 614-8646

SP-80

BATTERY CHARGING VOLTAGE

27.2

PANEL MANUFACTURER

Premier Fire & Security Inc.

1251 N 6th St

Paducah, KY 42002

(270) 443-7060

AUXILIARY

PANEL REPORT

7.0

PASS @ 70%

PASS @ 77%

VDC

AMP

AMP

VDC AMP

AMP

VDC 7.0

VDC

VDC

POWER EXPANDER/AUDIO-VISUAL PANEL

MODEL

BATTERY CHARGING VOLTAGE

0.00

AMP

AMP

VDC 7.0

VDC

12.84 0.00

0.00 FAIL @ 0%

13.48 5.38

7.0

POWER EXPANDER/AUDIO-VISUAL PANEL

WHEELOCK

PANEL MANUFACTURER MODEL PURPOSE LOCATION

ELECT ROOM

0.00

FAIL @ 0%

PANEL MANUFACTURER

POWER EXPANDER/AUDIO-VISUAL PANEL

LOCATIONPURPOSEMODEL

AMP

SBP 4 MASS SYSTEM ELECT ROOM

VDC 7.0 AMP0.00 0.00

PANEL MANUFACTURER MODEL

BATTERY CHARGING VOLTAGE

POWER EXPANDER/AUDIO-VISUAL PANEL

ELECT ROOM

Cooper Wheelock AMP for Mass Notification system is bad.

LOCATIONPURPOSE

WHEELOCK

BATTERY CHARGING VOLTAGE

27.7 13.47 4.9

SIEMENS PAD-3 NAC POWER

MODELPANEL MANUFACTURER PURPOSE

MASS PANEL

11.4

PASS

LOCATION

0.00

PURPOSE

VDC 7.0 AMPFAIL @ 0%

POWER EXPANDER/AUDIO-VISUAL PANEL

LOCATION

VDC AMP

NOTES, FAILURES AND SYSTEM DEVIATIONS FROM CONTRACT STANDARDS

BATTERY CHARGING VOLTAGE

INSPECTION DATES: INSPECTION TEAM: INSPECTION TYPE

5/27/2021 KS,BH,RR 1 YEAR -

2 YEAR -

BUILDING POC NAME 5 YEAR -

POC CONTACT INFO OTHER -

BUILDING NUMBER 2989 Indiana AVE Fort Campbell KY 42223

BUILDING 2989-5YR-5-27-2021 PAGE 2 OF 9

NCS

11501 Plantside Drive Suite #4 Louisville, KY 40299

(502) 614-8646

Premier Fire & Security Inc.

1251 N 6th St

Paducah, KY 42002

(270) 443-7060

DATE

5/27/2021

DEVICE DEVICE LOCATION DEVICE

ADDRESS

OR

ZONE

P A

S S

F

A

IL

S en si ti vi ty

NOTES:

FA FACP ROOM P

KF FACP ROOM P

VP FACP ROOM P

BPS FACP ROOM - NAC BOOSTER P

BPS FACP ROOM - MASS AMP F

SD FACP ROOM P 3.82 Range .88 to 3.86

S FACP ROOM P

PS FACP ROOM P

PIV OUTSIDE P

FDC OUTSIDE P

WA OUTSIDE P

S OUTSIDE P

TS ON PIV P

TS BACKFLOW CONTROL VALVE#1 P

TS BACKFLOW CONTROL VALVE#2 P

TS FORWARD FLOW P

WF SPRINKLER RISER P

SD MECH ROOM P 3.85 Range .88 to 3.86

HS MECH ROOM P

PS MECH ROOM P

PS 1ST FLOOR IN STAIR #3 P

PS 1ST FLOOR BY STAIR #3 P

SD 1ST FLOOR BY STAIR #3 P 3.58 Range .88 to 3.86

HS 1ST FLOOR BY STAIR #3 P

SPK 1ST FLOOR BY STAIR #3 F

SD 1ST FLOOR BY 138 P 3.75 Range .88 to 3.86

HS 1ST FLOOR BY 137 P

SPK 1ST FLOOR BY 137 F

SD 1ST FLOOR BY ROOM 146 P 3.68 Range .88 to 3.86

SPK 1ST FLOOR BY 136 F

FA = FIRE ALARM - KF = KINGFISHER - BPS = BOOSTER POWER SUPPLY - VP=VOICE/MASS PANEL - AN=ANNUNCIATOR/MASS CONSOLE - PS=MANUAL PULL - SD=SMOKE DETECTOR - DD=DUCT DETECTOR - HD = HEAT DETECTOR - MM=MONITOR MODULE - CR=CONTROL RELAY - CM=CONTROL MODULE - HS = HORN/STROBE - S=STROBE ONLY - MS=MASS STROBE - SPK=SPEAKER - DH=DOOR HOLDER

BUILDING NUMBERINSPECTION TEAM

KS,BH,RR 2989

FIRE ALARM

DEVICE REPORT

BUILDING 2989-5YR-5-27-2021 PAGE 3 OF 9

Suite #4 Louisville, KY 40299

(502) 614-8646

Premier Fire & Security Inc.

1251 N 6th St

Paducah, KY 42002

(270) 443-7060

DATE

5/27/2021

DEVICE DEVICE LOCATION DEVICE

ADDRESS

OR

ZONE

P A

S S

F

A

IL

S en si ti vi ty

NOTES:

FA = FIRE ALARM - KF = KINGFISHER - BPS = BOOSTER POWER SUPPLY - VP=VOICE/MASS PANEL - AN=ANNUNCIATOR/MASS CONSOLE - PS=MANUAL PULL - SD=SMOKE DETECTOR - DD=DUCT DETECTOR - HD = HEAT DETECTOR - MM=MONITOR MODULE - CR=CONTROL RELAY - CM=CONTROL MODULE - HS = HORN/STROBE - S=STROBE ONLY - MS=MASS STROBE - SPK=SPEAKER - DH=DOOR HOLDER

BUILDING NUMBERINSPECTION TEAM

KS,BH,RR 2989

FIRE ALARM

DEVICE REPORT

SD 1ST FLOOR BY 136 P 3.63 Range .88 to 3.86

SD 1ST FLOOR LOBBY BY ELECT ROOM 134 P 3.71 Range .88 to 3.86

HS 1ST FLOOR LOBBY BY ELECT ROOM 134 P

MS 1ST FLOOR LOBBY BY ELECT ROOM 134 P

PS 1ST FLOOR LOBBY EXIT NEAR ROOM 103 P

SD 1ST FLOOR WAITING ROOM 103 P 3.73 Range .88 to 3.86

S MENS ROOM P

S WOMENS ROOM P

SD 1ST FLOOR VENDING ROOM 106 P 3.84 Range .88 to 3.86

HS 1ST FLOOR LOBBY ENTRANCE P

MS 1ST FLOOR LOBBY ENTRANCE P

PS 1ST FLOOR LOBBY ENTRANCE P

SD 1ST FLOOR LAUNDRY ROOM 132 P 3.66 Range .88 to 3.86

SPK 1ST FLOOR LOBBY F

SPK 1ST FLOOR LOBBY F

DH 1ST FLOOR BY BY 128 P 3.66 Range .88 to 3.86

DH 1ST FLOOR LOBBY P

DH 1ST FLOOR LOBBY P

DH 1ST FLOOR LOBBY P

SD 1ST FLOOR BY BY 128 P 3.66 Range .88 to 3.86

HS 1ST FLOOR BY BY 128 P

SPK 1ST FLOOR BY BY 128 F

HD 1ST FLOOR JANITOR ROOM 108 P

SPK 1ST FLOOR BY 127 F

SD 1ST FLOOR BY 126 P 3.71 Range .88 to 3.86

SPK 1ST FLOOR BY 125 F

HS 1ST FLOOR BY 125 P

SD COMM ROOM 133 F NO ACCESS

SD 1ST FLOOR BY 124 F 3.90 Range .88 to 3.86

SPK 1ST FLOOR BY 113 F

BUILDING 2989-5YR-5-27-2021 PAGE 4 OF 9

Suite #4 Louisville, KY 40299

(502) 614-8646

Premier Fire & Security Inc.

1251 N 6th St

Paducah, KY 42002

(270) 443-7060

DATE

5/27/2021

DEVICE DEVICE LOCATION DEVICE

ADDRESS

OR

ZONE

P A

S S

F

A

IL

S en si ti vi ty

NOTES:

FA = FIRE ALARM - KF = KINGFISHER - BPS = BOOSTER POWER SUPPLY - VP=VOICE/MASS PANEL - AN=ANNUNCIATOR/MASS CONSOLE - PS=MANUAL PULL - SD=SMOKE DETECTOR - DD=DUCT DETECTOR - HD = HEAT DETECTOR - MM=MONITOR MODULE - CR=CONTROL RELAY - CM=CONTROL MODULE - HS = HORN/STROBE - S=STROBE ONLY - MS=MASS STROBE - SPK=SPEAKER - DH=DOOR HOLDER

BUILDING NUMBERINSPECTION TEAM

KS,BH,RR 2989

FIRE ALARM

DEVICE REPORT

SD 1ST FLOOR BY 122 P 3.61 Range .88 to 3.86

HS 1ST FLOOR BY 122 P

SPK 1ST FLOOR BY 115 F

SD 1ST FLOOR BY 121 P 3.75 Range .88 to 3.86

SPK 1ST FLOOR BY 140 F

HS 1ST FLOOR BY 140 P

SD 1ST FLOOR BY 140 P 3.72 Range .88 to 3.86

PS 1ST FLOOR BY 140 P

PS 1ST FLOOR IN STAIR #2 P

PS 2ND FLOOR BY 212 P

HS 2ND FLOOR BY 212 P

SPK 2ND FLOOR BY 212 F

SD 2ND FLOOR BY 212 F 4.11 Range .88 to 3.86

SD 2ND FLOOR BY 210 F 4.35 Range .88 to 3.86

SPK 2ND FLOOR BY 210 F

HS 2ND FLOOR BY 209 P

SD 2ND FLOOR BY 208 P 3.64 Range .88 to 3.86

SPK 2ND FLOOR BY 208 F

SD 2ND FLOOR BY 206 F 4.15 Range .88 to 3.86

HS 2ND FLOOR BY 206 P

SPK 2ND FLOOR BY 206 F

SD 2ND FLOOR BY 205 P 3.25 Range .88 to 3.86

SPK 2ND FLOOR BY 204 F

SD 2ND FLOOR BY 203 P 3.69 Range .88 to 3.86

HS 2ND FLOOR BY 203 P

SD 2ND FLOOR LOBBY 203 SIDE F 3.97 Range .88 to 3.86

DH 2ND FLOOR LOBBY 203 SIDE P

SD 2ND FLOOR VENDING 223 F 4.03 Range .88 to 3.86

HD 2ND FLOOR JANITOR 224 P

HS 2ND FLOOR MECH ROOM 225 P

BUILDING 2989-5YR-5-27-2021 PAGE 5 OF 9

Suite #4 Louisville, KY 40299

(502) 614-8646

Premier Fire & Security Inc.

1251 N 6th St

Paducah, KY 42002

(270) 443-7060

DATE

5/27/2021

DEVICE DEVICE LOCATION DEVICE

ADDRESS

OR

ZONE

P A

S S

F

A

IL

S en si ti vi ty

NOTES:

FA = FIRE ALARM - KF = KINGFISHER - BPS = BOOSTER POWER SUPPLY - VP=VOICE/MASS PANEL - AN=ANNUNCIATOR/MASS CONSOLE - PS=MANUAL PULL - SD=SMOKE DETECTOR - DD=DUCT DETECTOR - HD = HEAT DETECTOR - MM=MONITOR MODULE - CR=CONTROL RELAY - CM=CONTROL MODULE - HS = HORN/STROBE - S=STROBE ONLY - MS=MASS STROBE - SPK=SPEAKER - DH=DOOR HOLDER

BUILDING NUMBERINSPECTION TEAM

KS,BH,RR 2989

FIRE ALARM

DEVICE REPORT

HD 2ND FLOOR MECH ROOM 225 P

PS 2ND FLOOR LOBBY P

HS 2ND FLOOR LOBBY P

SPK 2ND FLOOR LOBBY F

SPK 2ND FLOOR LOBBY F

SD 2ND FLOOR LAUNDRY 226 P 3.57 Range .88 to 3.86

SD 2ND FLOOR COMM ROOM 227 F NO ACCESS

SD 2ND FLOOR LOBBY BY ELECT ROOM 228 P 3.67 Range .88 to 3.86

SD 2ND IN ELECT ROOM 228 P 3.68 Range .88 to 3.86

DH 2ND FLOOR LOBBY BY ELECT ROOM 228 P

SD 2ND FLOOR BY 239 F 4.10 Range .88 to 3.86

HS 2ND FLOOR BY 239 P

SPK 2ND FLOOR BY 239 F

SD 2ND FLOOR BY 238 P 3.55 Range .88 to 3.86

SPK 2ND FLOOR BY 238 F

HS 2ND FLOOR BY 237

SD 2ND FLOOR BY 236 P 3.81 Range .88 to 3.86

SPK 2ND FLOOR BY STAIR #3 F

PS 2ND FLOOR BY STAIR #3 P

HS 2ND FLOOR BY 235 P

SD 2ND FLOOR BY 235 F 5.26 Range .88 to 3.86

PS ATTIC P

HD ATTIC

HD ATTIC

HD ATTIC

HD ATTIC

HD ATTIC

HD ATTIC

HD ATTIC

HD ATTIC

BUILDING 2989-5YR-5-27-2021 PAGE 6 OF 9

Suite #4 Louisville, KY 40299

(502) 614-8646

Premier Fire & Security Inc.

1251 N 6th St

Paducah, KY 42002

(270) 443-7060

DATE

5/27/2021

DEVICE DEVICE LOCATION DEVICE

ADDRESS

OR

ZONE

P A

S S

F

A

IL

S en si ti vi ty

NOTES:

FA = FIRE ALARM - KF = KINGFISHER - BPS = BOOSTER POWER SUPPLY - VP=VOICE/MASS PANEL - AN=ANNUNCIATOR/MASS CONSOLE - PS=MANUAL PULL - SD=SMOKE DETECTOR - DD=DUCT DETECTOR - HD = HEAT DETECTOR - MM=MONITOR MODULE - CR=CONTROL RELAY - CM=CONTROL MODULE - HS = HORN/STROBE - S=STROBE ONLY - MS=MASS STROBE - SPK=SPEAKER - DH=DOOR HOLDER

BUILDING NUMBERINSPECTION TEAM

KS,BH,RR 2989

FIRE ALARM

DEVICE REPORT

HD ATTIC

HD ATTIC

HS ATTIC

HS ATTIC

HS ATTIC

DD ATTIC F 4.06 Range .63 to 2.64

DD ATTIC P 2.07 Range .63 to 2.64

DD ATTIC F 4.17 Range .63 to 2.64

DD ATTIC F 4.37 Range .63 to 2.64

BUILDING 2989-5YR-5-27-2021 PAGE 7 OF 9

BACKFLOW INSPECTION REPORT

PSID PSID PSID

ON

PSID

PASS PASS PASS

CHECK VALVE #2 BACKPRESSURE TEST

CLOSED TIGHT

PASSED 5/27/2021

375A

TEST KIT (BRAND) TEST KIT (MODEL) TEST KIT (SERIAL NUMBER)

PASS

Yes

WILKINS 4"

INSPECTION DATES: INSPECTION TEAM:

5/27/2021 KS,BH,RR

BUILDING NUMBER 02989 Indiana AVE Fort Campbell KY 42223

SERVICE LOCATION

NCS

11501 Plantside Drive Suite #4 Louisville, KY 40299

(502) 614-8646

Premier Fire & Security Inc.

1251 N 6th St

Paducah, KY 42002

(270) 443-7060

SERIAL NUMBER

MECH ROOM

RP X-02748

TYPE OF ASSEMBLY MANUFACTURER MODEL SIZE

PASS

DEVICE PROTECTED FROM FREEZING AND FLOODING

No. 2 SHUT OFF CHECK VALVE #2

REDUCED PRESSURE PRINCIPLE ASSEMBLY

CLOSED TIGHT HELD AT

RELIEF VALVE OPENING

POINT

CHECK VALVE #2

BACKPRESSURE TEST

CHECK VALVE #1

OPENED AT 2 HELD ATCLOSED TIGHT Yes

HELD AT HELD ATCLOSED TIGHT

DOUBLE CHECK VALVE ASSEMBLY

CHECK VALVE #2

PSID

No. 2 SHUT OFF

NOTES, FAILURES AND PARTS USED IF REPAIRED

STATE AND CERTIFICATION NUMBER(S) WITH EXPIRATION DATE(S)

6850 - MAY 2024

COMPANY FINAL TEST BY (PRINT) (SIGNATURE)

PREMIER FIRE & SECURITY

(SIGNATURE) REPAIRED BY (PRINT) (SIGNATURE)

8 1.2

CHECK VALVE #1

K STACEY

THE ABOVE REPORT IS TRUE, ACCURATE, AND COMPLETE.

TESTED BY (PRINT)

4" WILKINS 375A Backflow

BUILDING 2989-5YR-5-27-2021 PAGE 8 OF 9

Sprinkler System Inspection

X

Yes No N/A Yes No N/A P P P P

Yes No N/A

P P P P

Yes No N/A P

O Yes No N/A P P P

P Yes No N/A

P Yes No N/A P P

Air:Pilot:Pilot:

50 Static:System:

Air:

ANNUAL -

INSPECTION TYPE

5. Dry Pipe and Pre-action 5 Year

6. Pre-action Bi-Annual

SYSTEM TYPE

OTHER -

PRE-ACTION -

DRY PIPE -

WET PIPE -

Indiana AVE Fort Campbell KY 42223

5 YEAR -

2 YEAR -2989

Hydrostatic or Previous Gauge Readings

Is there a Backflow Device at the riser?

Current Gauge Readings

Street:

Internally inspected, cleaned and free from damage?

Is air compressor in service and in

Residule:

Static:

OTHER -

Residule: 45

System: 45

Anti-freeze loops have correct solution mixture.

Does low air supply works properly?

Premier Fire & Security Inc.

1251 N 6th St

Paducah, KY 42002

(270) 443-7060

NCS

11501 Plantside Drive Suite #4 Louisville, KY 40299

(502) 614-8646

SPECIAL CONSIDERATIONS - List any unique functions to be aware of prior to testing

Are fire department caps in good condition?

Alarm test in proper position.

Does water flow devices work properly?

Is fire department connection accessible?

3. 2 Year and 5 Year Inspections:

and filled with the correct sprinkler heads?

Is sprinkler head cabinet mounted close to the riser

Are all control valves and trim in good condition?

5. Dry Pipe Bi-Annual

Trip valve, drain and clean internally Does quick opening devices work properly?

All low points drained?

All low points drained?

Are OS&Y stems lubricated?

All strainers cleaned and in proper condition.Operated valve to verify proper function?

Verified water travels through inspectors test.

Street:

INSPECTION DATES:

5/27/2021

Adequate heating, and on if necessary.

KS,BH,RR

INSPECTION TEAM:

Is hydrolic nameplace present and visible?

Are control valves supervised, lock or Tamper?

VALVE LOCATION

POC CONTACT INFO

BUILDING POC NAME

VALVE SIZE AND TYPE

NOTES, FAILURES AND SYSTEM DEVIATIONS FROM CONTRACT STANDARDS

Does low air supply works properly?

1.All Inspections:

BUILDING NUMBER

Verify water supply "conduct main drain test"

Gauges appear to be in working order ?

2.Annual, 2 Year and 5 Year Inspections:

STAIRWELLS 2 AND 3 HAVE A TOTAL OF 2 PAINTED 155DG BRASS UPRIGHT 1/2" QUICK RESPONSE HEADS

STAIRWELL 3 MISSING SEMI RECESSED SLIP ON ESCT MISSING

4" OS&Y #2 ON BACKFLOW NEEDS PACKING REPLACED

PHONE ROOM 146 - 1 PAINTED 155DG CHROME PEND 1/2" QUICK RESPONSE HEAD

MAKE

31 SECONDS TO ALARM

Is air pressure on the system satisfactory?

satisfactory operating condition?

Did system trip by device to verify operation?

Does quick opening devices work properly?

Did system trip by manual actuator?

MODEL NUMBER

MECH ROOM 4" STRAIGHT NANA

4. Wet Systems 5 Year Wet:

P

Is System in operation?

BUILDING 2989-5YR-5-27-2021 PAGE 9 OF 9

VDC VDC AH 12

VDC VDC AH 12

ELEVATOR SYSTEM(S)

SHUNT

BATTERY VOLTAGE TYPE:

VDC VDC AH

VDC VDC AH

KF KINGFISHER PS PULL STATION HS HORN / STROBE WA WATER ALARM AN ANNUNCIATOR

FA FIRE ALARM PANEL SD SMOKE DETECTOR S STROBE ONLLY DH DOOR HOLDER AN MASS CONSOLE

BPS POWER SUPPLY HD HEAT DETECTOR MS MASS STROBE TS TAMPER SWITCH CR CONTROL RELAY

VP VOICE / MASS PANEL DD DUCT DETECTOR SPK SPEAKER WF WATER FLOW CM CONTROL MOD

1 YEAR -

INSPECTION TYPE

PASS

BUILDING NUMBER 2 YEAR -

5 YEAR -

OTHER -

35.0 AMP

MODELRESPONSE TO ALARM MANUFACTURER

AMP

AMP

PASS

SWAPPED BATTERY CHARGING LOCATIONLED TESTTRANSMITTER RECEIVES ALARMS FROM FACP

NAPASS

TRANSMITTER RECEIVES TROUBLES FROM FACP

NCS

11501 Plantside Drive Suite #4 Louisville, KY 40299

(502) 614-8646

Premier Fire & Security Inc.

1251 N 6th St

Paducah, KY 42002

(270) 443-7060

VDC

MONITORING AGENCY PERSONNEL NOTIFIED

CORTNEY

MODEL

CENTERAL DISPATCH 270-798-1221

MONITORING AGENCY

Indiana AVE Fort Campbell KY 42223

FIRE ALARM CONTROL PANEL (FACP)

BUILDING POC NAME

PANEL MANUFACTURER

KS-BH-RR

INSPECTION DATES:

27.3

BATTERY CHARGING VOLTAGE

POC CONTACT INFO

27.5

MXL-IQ

INSPECTION TEAM:

13.56

CIRCUIT BREAKER LOCATION

LOCATION

ELECT ROOM

AMP

PASS @ 79%

PASS @ 79%

VDC

27.5

TIME:

SIEMENS

13.62

DIGITAL ALARM RADIO TRANSMITTER (DART)

VDC 35.0

LAMPS / LED TEST

LOCATION

SECONDARY RECALL RECALL

NOTES, FAILURES AND SYSTEM DEVIATIONS FROM CONTRACT STANDARDS

21 OF 40 SMOKE DETECTOR HEADS FAILED THE SENSITIVITY TEST ON SIEMENS MXL-IQ PANEL

FIRE ALARM

PANEL REPORT

VDC

BATTERY CHARGING VOLTAGE

PANEL MANUFACTURER

2:00

5/27/2021

RESPONSE TO TROUBLE

ANNUNCIATOR

SPECIAL CONSIDERATIONS - List any unique functions to be aware of before testing

KINGFISHER

MODEL TYPE LOCATION

PASS

TIME:

HVAC SHUTDOWN

PASS

2:00

ELEVATOR RESTART FROM FIRE SYSTEM RESET

KFRI COMBO

PASS

N/A

RESPONSE TO SUPERVISORY TIME:N/A

PASS

DOOR HOLDERS PASS

HVAC AUTO RESTART FROM FACP RESET PASS

PASS

PRIMARY RECALL

IS SYSTEM CONNECTED TO MONITORING AGENCY

BUILDING 2990-5YR-5-27-2021 PAGE 1 OF 9

VDC VDC AH 12

VDC VDC AH 12

BATTERY VOLTAGE TYPE:

VDC VDC AH 12

VDC VDC AH 12

BATTERY VOLTAGE TYPE:

VDC VDC AH 12

VDC VDC AH 12

BATTERY VOLTAGE TYPE:

VDC VDC AH

VDC VDC AH

BATTERY VOLTAGE TYPE:

VDC VDC AH

VDC VDC AH

2 YEAR -

BUILDING POC NAME 5 YEAR -

POC CONTACT INFO OTHER -

BUILDING NUMBER 2990 Indiana AVE Fort Campbell KY 42223

INSPECTION DATES: INSPECTION TEAM: INSPECTION TYPE

5/27/2021 KS,BH,RR 1 YEAR -

NOTES, FAILURES AND SYSTEM DEVIATIONS FROM CONTRACT STANDARDS

BATTERY CHARGING VOLTAGE

LOCATION

VDC AMP

LOCATION

3.95

PURPOSE

VDC 7.0 AMPFAIL @ 56%

POWER EXPANDER/AUDIO-VISUAL PANEL

MODELPANEL MANUFACTURER PURPOSE

MASS PANEL

13.54

PASS

BATTERY CHARGING VOLTAGE

27.8 13.81 8.3

SIEMENS PAD-3 NAC POWER ELECT ROOM

LOCATIONPURPOSE

WHEELOCK

PANEL MANUFACTURER MODEL

BATTERY CHARGING VOLTAGE

POWER EXPANDER/AUDIO-VISUAL PANEL

SPB-80 MASS AMP ELECT ROOM

VDC 7.0 AMP13.06 0.92

13.06

FAIL @ 13%

PANEL MANUFACTURER

POWER EXPANDER/AUDIO-VISUAL PANEL

LOCATIONPURPOSEMODEL

AMP13.93 6.52

7.0

POWER EXPANDER/AUDIO-VISUAL PANEL

WHEELOCK

PANEL MANUFACTURER MODEL PURPOSE LOCATION

ELECT ROOM

AMP

AMP

VDC 7.0

VDC

13.51 3.73

3.56 FAIL @ 51%

VDC

VDC

POWER EXPANDER/AUDIO-VISUAL PANEL

MODEL

BATTERY CHARGING VOLTAGE

27.1

VDC

AMP

AMP

VDC AMP

AMP

VDC 7.0

NCS

11501 Plantside Drive Suite #4 Louisville, KY 40299

(502) 614-8646

SP-40

BATTERY CHARGING VOLTAGE

27.3

PANEL MANUFACTURER

Premier Fire & Security Inc.

1251 N 6th St

Paducah, KY 42002

(270) 443-7060

AUXILIARY

PANEL REPORT

7.0

PASS @ 119%

PASS @ 93%

PASS

PASS

FAIL @ 53%

BUILDING 2990-5YR-5-27-2021 PAGE 2 OF 9

Suite #4 Louisville, KY 40299

(502) 614-8646

Premier Fire & Security Inc.

1251 N 6th St

Paducah, KY 42002

(270) 443-7060

DATE

5/27/2021

DEVICE DEVICE LOCATION DEVICE

ADDRESS

OR

ZONE

P A

S S

F

A

IL

S en si ti vi ty

NOTES:

FA ELECTRICAL ROOM P

KF ELECTRICAL ROOM P

BPS ELECTRICAL ROOM P

BPS ELECTRICAL ROOM P

VP ELECTRICAL ROOM P

PS ELECTRICAL ROOM P

SD ELECTRICAL ROOM F 3.89 Range .88 to 3.86

HS ELECTRICAL ROOM P

PIV OUTSIDE P

WA OUTSIDE P

FDC OUTSIDE P

WPSR MECH ROOM P

BCKFLW MECH ROOM P

TS MECH ROOM OS&Y BACKFLOW #1 VALVE P

TS MECH ROOM OS&Y BACKFLOW #2 VALVE P

TS MECH ROOM FORWARD FLOW P

WF SPRINKLER RISER P

SD MECH ROOM F 4.98 Range .88 to 3.86

PS MECH ROOM P

HS MECH ROOM P

PS 1ST FLOOR EXIT BY STAIR # 3 P

SD 1ST FLOOR BY 144 F 3.96 Range .88 to 3.86

SPK 1ST FLOOR BY 144 P

HS 1ST FLOOR BY 144 P

SD 1ST FLOOR BY ROOM 146 P 3.84 Range .88 to 3.86

SPK 1ST FLOOR BY 136 P

SD 1ST FLOOR BY 136 P 3.18 Range .88 to 3.86

HS 1st FLOOR BY 136 P

SD 1ST FLOOR LAUNDRY ROOM F 3.99 Range .88 to 3.86

SD IN ELECT ROOM 134 P 3.28 Range .88 to 3.86

FA = FIRE ALARM - KF = KINGFISHER - BPS = BOOSTER POWER SUPPLY - VP=VOICE/MASS PANEL - AN=ANNUNCIATOR/MASS CONSOLE - PS=MANUAL PULL - SD=SMOKE DETECTOR - DD=DUCT DETECTOR - HD = HEAT DETECTOR - MM=MONITOR MODULE - CR=CONTROL RELAY - CM=CONTROL MODULE - HS = HORN/STROBE - S=STROBE ONLY - MS=MASS STROBE - SPK=SPEAKER - DH=DOOR HOLDER

BUILDING NUMBERINSPECTION TEAM

KS,BH,RR 2990

FIRE ALARM

BUILDING 2990-5YR-5-27-2021 PAGE 3 OF 9

Suite #4 Louisville, KY 40299

(502) 614-8646

Premier Fire & Security Inc.

1251 N 6th St

Paducah, KY 42002

(270) 443-7060

DATE

5/27/2021

DEVICE DEVICE LOCATION DEVICE

ADDRESS

OR

ZONE

P A

S S

F

A

IL

S en si ti vi ty

NOTES:

FA = FIRE ALARM - KF = KINGFISHER - BPS = BOOSTER POWER SUPPLY - VP=VOICE/MASS PANEL - AN=ANNUNCIATOR/MASS CONSOLE - PS=MANUAL PULL - SD=SMOKE DETECTOR - DD=DUCT DETECTOR - HD = HEAT DETECTOR - MM=MONITOR MODULE - CR=CONTROL RELAY - CM=CONTROL MODULE - HS = HORN/STROBE - S=STROBE ONLY - MS=MASS STROBE - SPK=SPEAKER - DH=DOOR HOLDER

BUILDING NUMBERINSPECTION TEAM

KS,BH,RR 2990

FIRE ALARM

DEVICE REPORT

SPK 1ST FLOOR BY ROOM 134 P

DH 1ST FLOOR BY ROOM 134 P

SD 1ST FLOOR BY ROOM 134 P 3.40 Range .88 to 3.86

SD 1ST FLOOR CQ DESK P 3.80 Range .88 to 3.86

MS 1ST FLOOR CQ DESK P

HS 1ST FLOOR CQ DESK P

SD 1ST FLOOR MAIL ROOM F NO ACCESS

SD COMM ROOM 133 F 3.92 Range .88 to 3.86

PS LOBBY EXIT P

PS LOBBY ENTRANCE P

MS LOBBY ENTRANCE P

HS LOBBY ENTRANCE P

SD WAITING 103 P 3.84 Range .88 to 3.86

S MENS ROOM P

S WOMENS ROOM P

SD VENDIND 106 F 4.69 Range .88 to 3.86

SD LOBBY NEAR 106 P 3.83 Range .88 to 3.86

DH LOBBY NEAR 106 P

HS 1ST FLOOR BY JANITOR 108 P

SD 1ST FLOOR BY JANITOR 108 P

SPK 1ST FLOOR BY JANITOR 108 P

HD IN JANITOR 108 P

SPK 1ST FLOOR BY 109 P

SD 1ST FLOOR BY 126 P 3.72 Range .88 to 3.86

SPK 1ST FLOOR BY 125 P

SD 1ST FLOOR BY 125 P 3.83 Range .88 to 3.86

HS 1st FLOOR BY 125 P

SPK 1ST FLOOR BY 113 P

SD 1ST FLOOR BY 113 P 3.73 Range .88 to 3.86

HS 1ST FLOOR BY 118 P

BUILDING 2990-5YR-5-27-2021 PAGE 4 OF 9

Suite #4 Louisville, KY 40299

(502) 614-8646

Premier Fire & Security Inc.

1251 N 6th St

Paducah, KY 42002

(270) 443-7060

DATE

5/27/2021

DEVICE DEVICE LOCATION DEVICE

ADDRESS

OR

ZONE

P A

S S

F

A

IL

S en si ti vi ty

NOTES:

FA = FIRE ALARM - KF = KINGFISHER - BPS = BOOSTER POWER SUPPLY - VP=VOICE/MASS PANEL - AN=ANNUNCIATOR/MASS CONSOLE - PS=MANUAL PULL - SD=SMOKE DETECTOR - DD=DUCT DETECTOR - HD = HEAT DETECTOR - MM=MONITOR MODULE - CR=CONTROL RELAY - CM=CONTROL MODULE - HS = HORN/STROBE - S=STROBE ONLY - MS=MASS STROBE - SPK=SPEAKER - DH=DOOR HOLDER

BUILDING NUMBERINSPECTION TEAM

KS,BH,RR 2990

FIRE ALARM

DEVICE REPORT

SPK 1ST FLOOR BY 118 P

SD 1ST FLOOR BY 118 P 3.82 Range .88 to 3.86

PS 1ST FLOOR IN STAIR # 2 P

SD 1ST FLOOR BY STAIR # 2 P 3.78 Range .88 to 3.86

PS 1ST FLOOR BY STAIR # 2 P

HS 1ST FLOOR BY STAIR # 2 P

PS 2ND FLOOR BY STAIR # 2 P

SD 2ND FLOOR BY STAIR # 2 F 4.09 Range .88 to 3.86

SPK 2ND FLOOR BY STAIR # 2 P

SD 2ND FLOOR BY 210 F 4.27 Range .88 to 3.86

SPK 2ND FLOOR BY 210 P

HS 2ND FLOOR BY 209 P

SPK 2ND FLOOR BY 208 P

SD 2ND FLOOR BY 208 F 3.97 Range .88 to 3.86

SPK 2ND FLOOR BY 206 P

SD 2ND FLOOR BY 206 P 3.66 Range .88 to 3.86

SPK 2ND FLOOR BY 205 P

SD 2ND FLOOR BY 221 F 4.67 Range .88 to 3.86

HS 2ND FLOOR BY 203 P

SPK 2ND FLOOR BY 203 P

SD 2ND FLOOR BY 203 F 4.09 Range .88 to 3.86

SD 2ND FLOOR LOBBY NEAR 203 F 4.50 Range .88 to 3.86

DH 2ND FLOOR LOBBY NEAR 203 P

PS 2ND FLOOR LOBBY P

HS 2ND FLOOR LOBBY P

SD 2ND FLOOR VENDING 223 P 3.65 Range .88 to 3.86

HD 2ND FLOOR JANITOR 224 P

HS 2ND FLOOR MECH ROOM 225 P

S 2ND FLOOR MECH ROOM 225 P

SD 2ND FLOOR LOBBY F 4.30 Range .88 to 3.86

BUILDING 2990-5YR-5-27-2021 PAGE 5 OF 9

Suite #4 Louisville, KY 40299

(502) 614-8646

Premier Fire & Security Inc.

1251 N 6th St

Paducah, KY 42002

(270) 443-7060

DATE

5/27/2021

DEVICE DEVICE LOCATION DEVICE

ADDRESS

OR

ZONE

P A

S S

F

A

IL

S en si ti vi ty

NOTES:

FA = FIRE ALARM - KF = KINGFISHER - BPS = BOOSTER POWER SUPPLY - VP=VOICE/MASS PANEL - AN=ANNUNCIATOR/MASS CONSOLE - PS=MANUAL PULL - SD=SMOKE DETECTOR - DD=DUCT DETECTOR - HD = HEAT DETECTOR - MM=MONITOR MODULE - CR=CONTROL RELAY - CM=CONTROL MODULE - HS = HORN/STROBE - S=STROBE ONLY - MS=MASS STROBE - SPK=SPEAKER - DH=DOOR HOLDER

BUILDING NUMBERINSPECTION TEAM

KS,BH,RR 2990

FIRE ALARM

DEVICE REPORT

SD 2ND FLOOR ELECT ROOM 228 P 3.85 Range .88 to 3.86

SD 2ND FLOOR COMM ROOM F NO ACCESS

SD 2ND FLOOR LOBBY NEAR 230 P

DH 2ND FLOOR LOBBY NEAR 230 P 3.82 Range .88 to 3.86

SD 2ND FLOOR BY 230 P 3.84 Range .88 to 3.86

HS 2ND FLOOR BY 230 P

SPK 2ND FLOOR BY 230 P

SD 2ND FLOOR BY 231 P 3.72 Range .88 to 3.86

HS 2ND FLOOR BY 232 P

SPK 2ND FLOOR BY 232 P

SD 2ND FLOOR BY 233 F 4.15 Range .88 to 3.86

PS 2ND FLOOR BY 234 P

HS 2ND FLOOR BY 234 P

SD 2ND FLOOR BY 234 F 4.73 Range .88 to 3.86

PS ATTIC P

HS ATTIC P

HS ATTIC P

HS ATTIC P

HD ATTIC P

HD ATTIC P

HD ATTIC P

HD ATTIC P

HD ATTIC P

HD ATTIC P

HD ATTIC P

HD ATTIC P

HD ATTIC P

HD ATTIC P

DD ATTIC F 4.98 Range .63 to 2.64

DD ATTIC F 4.26 Range .63 to 2.64

BUILDING 2990-5YR-5-27-2021 PAGE 6 OF 9

Suite #4 Louisville, KY 40299

(502) 614-8646

Premier Fire & Security Inc.

1251 N 6th St

Paducah, KY 42002

(270) 443-7060

DATE

5/27/2021

DEVICE DEVICE LOCATION DEVICE

ADDRESS

OR

ZONE

P A

S S

F

A

IL

S en si ti vi ty

NOTES:

FA = FIRE ALARM - KF = KINGFISHER - BPS = BOOSTER POWER SUPPLY - VP=VOICE/MASS PANEL - AN=ANNUNCIATOR/MASS CONSOLE - PS=MANUAL PULL - SD=SMOKE DETECTOR - DD=DUCT DETECTOR - HD = HEAT DETECTOR - MM=MONITOR MODULE - CR=CONTROL RELAY - CM=CONTROL MODULE - HS = HORN/STROBE - S=STROBE ONLY - MS=MASS STROBE - SPK=SPEAKER - DH=DOOR HOLDER

BUILDING NUMBERINSPECTION TEAM

KS,BH,RR 2990

FIRE ALARM

DEVICE REPORT

DD ATTIC F 3.95 Range .63 to 2.64

DD ATTIC F 4.02 Range .63 to 2.64

BUILDING 2990-5YR-5-27-2021 PAGE 7 OF 9

ON

PSID

7.2 2

CHECK VALVE #1

K STACEY

THE ABOVE REPORT IS TRUE, ACCURATE, AND COMPLETE.

TESTED BY (PRINT)

4" WILKINS 375A Backflow

(SIGNATURE) REPAIRED BY (PRINT) (SIGNATURE)

STATE AND CERTIFICATION NUMBER(S) WITH EXPIRATION DATE(S)

6850 - 11 MAY 2024

COMPANY FINAL TEST BY (PRINT) (SIGNATURE)

PREMIER FIRE & SECURITY

NOTES, FAILURES AND PARTS USED IF REPAIRED

DOUBLE CHECK VALVE ASSEMBLY

CHECK VALVE #2

PSID

No. 2 SHUT OFF

CLOSED TIGHT Yes

HELD AT HELD ATCLOSED TIGHT

REDUCED PRESSURE PRINCIPLE ASSEMBLY

CLOSED TIGHT HELD AT

RELIEF VALVE OPENING

POINT

CHECK VALVE #2

BACKPRESSURE TEST

CHECK VALVE #1

OPENED AT 2.1 HELD AT

X-03392

TYPE OF ASSEMBLY MANUFACTURER MODEL SIZE

PASS

DEVICE PROTECTED FROM FREEZING AND FLOODING

No. 2 SHUT OFF CHECK VALVE #2

SERVICE LOCATION

NCS

11501 Plantside Drive Suite #4 Louisville, KY 40299

(502) 614-8646

Premier Fire & Security Inc.

1251 N 6th St

Paducah, KY 42002

(270) 443-7060

SERIAL NUMBER

MECH ROOM

RP

INSPECTION DATES: INSPECTION TEAM:

5/27/2021 KS,BH,RR

BUILDING NUMBER 02990 Indiana AVE Fort Campbell KY 42223

375A

TEST KIT (BRAND) TEST KIT (MODEL) TEST KIT (SERIAL NUMBER)

PASS

Yes

WILKINS 4"

PASS PASS PASS

CHECK VALVE #2 BACKPRESSURE TEST

CLOSED TIGHT

PASSED 5/27/2021

BUILDING 2990-5YR-5-27-2021 PAGE 8 OF 9

X

Yes No N/A Yes No N/A P P P P

Yes No N/A

P P P P

Yes No N/A P P Yes No N/A P P P

P Yes No N/A

P Yes No N/A P P

MECH ROOM 4" STRAIGHT NANA

4. Wet Systems 5 Year Wet:

P

Is System in operation?

FDC CAPS MISSING

MAKE

Is air pressure on the system satisfactory?

satisfactory operating condition?

Did system trip by device to verify operation?

Does quick opening devices work properly?

Did system trip by manual actuator?

MODEL NUMBER

BUILDING NUMBER

Verify water supply "conduct main drain test"

Gauges appear to be in working order ?

2.Annual, 2 Year and 5 Year Inspections:

POC CONTACT INFO

BUILDING POC NAME

VALVE SIZE AND TYPE

NOTES, FAILURES AND SYSTEM DEVIATIONS FROM CONTRACT STANDARDS

Does low air supply works properly?

1.All Inspections:

INSPECTION DATES:

5/27/2021

Adequate heating, and on if necessary.

KS,BH,RR

INSPECTION TEAM:

Is hydrolic nameplace present and visible?

Are control valves supervised, lock or Tamper?

VALVE LOCATION

All low points drained?

All low points drained?

Are OS&Y stems lubricated?

All strainers cleaned and in proper condition.Operated valve to verify proper function?

Verified water travels through inspectors test.

Street:

and filled with the correct sprinkler heads?

Is sprinkler head cabinet mounted close to the riser

Are all control valves and trim in good condition?

5. Dry Pipe Bi-Annual

Trip valve, drain and clean internally Does quick opening devices work properly?

Anti-freeze loops have correct solution mixture.

Does low air supply works properly?

Premier Fire & Security Inc.

1251 N 6th St

Paducah, KY 42002

(270) 443-7060

NCS

11501 Plantside Drive Suite #4 Louisville, KY 40299

(502) 614-8646

SPECIAL CONSIDERATIONS - List any unique functions to be aware of prior to testing

Are fire department caps in good condition?

Alarm test in proper position.

Does water flow devices work properly?

Is fire department connection accessible?

3. 2 Year and 5 Year Inspections:

Internally inspected, cleaned and free from damage?

Is air compressor in service and in

Residule:

Static:

OTHER -

Residule: 40

System: 45

5 YEAR -

2 YEAR -2990

Hydrostatic or Previous Gauge Readings

Is there a Backflow Device at the riser?

Current Gauge Readings

Street: 45

ANNUAL -

INSPECTION TYPE

5. Dry Pipe and Pre-action 5 Year

6. Pre-action Bi-Annual

SYSTEM TYPE

OTHER -

PRE-ACTION -

DRY PIPE -

WET PIPE -

Indiana AVE Fort Campbell KY 42223

Static:System:

Air: Air:Pilot:Pilot:

BUILDING 2990-5YR-5-27-2021 PAGE 9 OF 9

VDC VDC AH 12

VDC VDC AH 12

ELEVATOR SYSTEM(S)

SHUNT

BATTERY VOLTAGE TYPE:

VDC VDC AH

VDC VDC AH

KF KINGFISHER PS PULL STATION HS HORN / STROBE WA WATER ALARM AN ANNUNCIATOR

FA FIRE ALARM PANEL SD SMOKE DETECTOR S STROBE ONLLY DH DOOR HOLDER AN MASS CONSOLE

BPS POWER SUPPLY HD HEAT DETECTOR MS MASS STROBE TS TAMPER SWITCH CR CONTROL RELAY

VP VOICE / MASS PANEL DD DUCT DETECTOR SPK SPEAKER WF WATER FLOW CM CONTROL MOD

1 YEAR -

INSPECTION TYPE

PASS

BUILDING NUMBER 2 YEAR -

5 YEAR -

OTHER -

35.0 AMP

MODELRESPONSE TO ALARM MANUFACTURER

AMP

AMP

PASS

MASS PANEL AUDIBLE NOT WORKING UPON ARRIVAL, CYCLED POWER AND STARTED WORKING.

SWAPPED BATTERY CHARGING LOCATIONLED TESTTRANSMITTER RECEIVES ALARMS FROM FACP

NAPASS

TRANSMITTER RECEIVES TROUBLES FROM FACP

NCS

11501 Plantside Drive Suite #4 Louisville, KY 40299

(502) 614-8646

Premier Fire & Security Inc.

1251 N 6th St

Paducah, KY 42002

(270) 443-7060

VDC

MONITORING AGENCY PERSONNEL NOTIFIED

JOSHUA

MODEL

CENTERAL DISPATCH 270-798-1221

MONITORING AGENCY

Indiana AVE Fort Campbell KY 42223

FIRE ALARM CONTROL PANEL (FACP)

BUILDING POC NAME

PANEL MANUFACTURER

KS,AS,RR

INSPECTION DATES:

26.79

BATTERY CHARGING VOLTAGE

POC CONTACT INFO

3.56

MXL-IQ

INSPECTION TEAM:

13.36

CIRCUIT BREAKER LOCATION

LOCATION

ELECT ROOM

AMP

FAIL @ 10%

FAIL @ 17%

VDC

5.83

TIME:

SIEMENS

13.47

DIGITAL ALARM RADIO TRANSMITTER (DART)

VDC 35.0

LAMPS / LED TEST

LOCATION

SECONDARY RECALL RECALL

22 TROUBLES UPON ARRIVAL, RESET AND CLEARED

2 TOTAL 12V-7AMP BATTERIES FAILED IN SIEMENS PAD-2 BOOSTER PANEL

NOTES, FAILURES AND SYSTEM DEVIATIONS FROM CONTRACT STANDARDS

SIEMENS PAD 2 HAS TROUBLES FOR OUT PUT 2 AND 4

FIRE ALARM

PANEL REPORT

VDC

BATTERY CHARGING VOLTAGE

PANEL MANUFACTURER

7:55

5/24/2021

RESPONSE TO TROUBLE

ANNUNCIATOR

SPECIAL CONSIDERATIONS - List any unique functions to be aware of before testing

KINGFISHER

MODEL TYPE LOCATION

PASS

TIME:

HVAC SHUTDOWN

PASS

7:55

ELEVATOR RESTART FROM FIRE SYSTEM RESET

KFRI COMBO

PASS

N/A

RESPONSE TO SUPERVISORY TIME:N/A

PASS

DOOR HOLDERS PASS

HVAC AUTO RESTART FROM FACP RESET PASS

PASS

PRIMARY RECALL

IS SYSTEM CONNECTED TO MONITORING AGENCY

BUILDING 2992-5YR-5-24-2021 PAGE 1 OF 10

VDC VDC AH 12

VDC VDC AH 12

BATTERY VOLTAGE TYPE:

VDC VDC AH 12

VDC VDC AH 12

BATTERY VOLTAGE TYPE:

VDC VDC AH 12

VDC VDC AH 12

BATTERY VOLTAGE TYPE:

VDC VDC AH

VDC VDC AH

BATTERY VOLTAGE TYPE:

VDC VDC AH

VDC VDC AH

2 YEAR -

BUILDING POC NAME 5 YEAR -

POC CONTACT INFO OTHER -

BUILDING NUMBER 2992 Indiana AVE Fort Campbell KY 42223

INSPECTION DATES: INSPECTION TEAM: INSPECTION TYPE

5/24/2021 KS,AS,RR 1 YEAR -

NOTES, FAILURES AND SYSTEM DEVIATIONS FROM CONTRACT STANDARDS

BATTERY CHARGING VOLTAGE

LOCATION

VDC AMP

LOCATION

4.47

PURPOSE

VDC 7.0 AMPPASS @ 64%

POWER EXPANDER/AUDIO-VISUAL PANEL

MODELPANEL MANUFACTURER PURPOSE

MASS PANEL

13.57

PASS

BATTERY CHARGING VOLTAGE

27.4 12 2.4

SIEMENS PAD-3 NAC POWER ELECT ROOM

LOCATIONPURPOSE

WHEELOCK

PANEL MANUFACTURER MODEL

BATTERY CHARGING VOLTAGE

POWER EXPANDER/AUDIO-VISUAL PANEL

SPB-80 MASS AMP ELECT ROOM

VDC 7.0 AMP13.62 4.65

13.57

PASS @ 66%

PANEL MANUFACTURER

POWER EXPANDER/AUDIO-VISUAL PANEL

LOCATIONPURPOSEMODEL

AMP12 2.4

7.0

POWER EXPANDER/AUDIO-VISUAL PANEL

WHEELOCK

PANEL MANUFACTURER MODEL PURPOSE LOCATION

ELECT ROOM

AMP

AMP

VDC 7.0

VDC

13.57 8.3

6.76 PASS @ 97%

VDC

VDC

POWER EXPANDER/AUDIO-VISUAL PANEL

MODEL

BATTERY CHARGING VOLTAGE

27.3

VDC

AMP

AMP

VDC AMP

AMP

VDC 7.0

NCS

11501 Plantside Drive Suite #4 Louisville, KY 40299

(502) 614-8646

SP-40

BATTERY CHARGING VOLTAGE

27.39

PANEL MANUFACTURER

Premier Fire & Security Inc.

1251 N 6th St

Paducah, KY 42002

(270) 443-7060

AUXILIARY

PANEL REPORT

7.0

FAIL @ 34%

FAIL @ 34%

PASS

PASS

PASS @ 119%

BUILDING 2992-5YR-5-24-2021 PAGE 2 OF 10

Suite #4 Louisville, KY 40299

(502) 614-8646

Premier Fire & Security Inc.

1251 N 6th St

Paducah, KY 42002

(270) 443-7060

DATE

5/24/2021

DEVICE DEVICE LOCATION DEVICE

ADDRESS

OR

ZONE

P A

S S

F

A

IL

S en si ti vi ty

NOTES:

FA ELECT ROOM

KF ELECT ROOM

VP ELECT ROOM

BPS ELECT ROOM MASS

BPS ELECT ROOM FIRE ALARM

PS ELECT ROOM WITH FACP P

SD ELECT ROOM WITH FACP P 3.85 Range .88 to 3.86

HS ELECT ROOM WITH FACP P

PS 1ST FLOOR EXIT BY STAIR # 3 P

HS 1ST FLOOR EXIT BY STAIR # 3 P

SD 1ST FLOOR BY STAIR # 3 P 3.64 Range .88 to 3.86

HS 1ST FLOOR BY STAIR # 3 P

PS 1ST FLOOR IN STAIR # 3 P

SPK 1ST FLOOR BY 140 P

SD 1ST FLOOR BY 135 P 3.60 Range .88 to 3.86

HS 1ST FLOOR BY 135 P

SD 1ST FLOOR BY 134 F 3.88 Range .88 to 3.86

SD 1ST FLOOR BY 134 P 3.62 Range .88 to 3.86

SPK 1ST FLOOR BY 141 P

DH 1ST FLOOR BY 131 P

SD 1ST FLOOR BY 131 F 3.99 Range .88 to 3.86

SPK 1ST FLOOR BY 143 P

SPK 1ST FLOOR BY 131 P

SD CQ DESK 144 P 3.84 Range .88 to 3.86

HS CQ DESK 144 P

MS CQ DESK 144 P

SD MAIL ROOM 148 F 5.02 Range .88 to 3.86

SD WAITING 103 BY REST ROOMS P 3.75 Range .88 to 3.86

SD VENDING 106 P 3.50 Range .88 to 3.86

SD LOBBY NEAR 106 VENDING F 5.00 Range .88 to 3.86

FA = FIRE ALARM - KF = KINGFISHER - BPS = BOOSTER POWER SUPPLY - VP=VOICE/MASS PANEL - AN=ANNUNCIATOR/MASS CONSOLE - PS=MANUAL PULL - SD=SMOKE DETECTOR - DD=DUCT DETECTOR - HD = HEAT DETECTOR - MM=MONITOR MODULE - CR=CONTROL RELAY - CM=CONTROL MODULE - HS = HORN/STROBE - S=STROBE ONLY - MS=MASS STROBE - SPK=SPEAKER - DH=DOOR HOLDER

BUILDING NUMBERINSPECTION TEAM

KS,AS,RR 2992

FIRE ALARM

BUILDING 2992-5YR-5-24-2021 PAGE 3 OF 10

Suite #4 Louisville, KY 40299

(502) 614-8646

Premier Fire & Security Inc.

1251 N 6th St

Paducah, KY 42002

(270) 443-7060

DATE

5/24/2021

DEVICE DEVICE LOCATION DEVICE

ADDRESS

OR

ZONE

P A

S S

F

A

IL

S en si ti vi ty

NOTES:

FA = FIRE ALARM - KF = KINGFISHER - BPS = BOOSTER POWER SUPPLY - VP=VOICE/MASS PANEL - AN=ANNUNCIATOR/MASS CONSOLE - PS=MANUAL PULL - SD=SMOKE DETECTOR - DD=DUCT DETECTOR - HD = HEAT DETECTOR - MM=MONITOR MODULE - CR=CONTROL RELAY - CM=CONTROL MODULE - HS = HORN/STROBE - S=STROBE ONLY - MS=MASS STROBE - SPK=SPEAKER - DH=DOOR HOLDER

BUILDING NUMBERINSPECTION TEAM

KS,AS,RR 2992

FIRE ALARM

DEVICE REPORT

DH LOBBY NEAR 106 VENDING P

HS MAIN ENTRANCE P

MS MAIN ENTRANCE P

PS MAIN ENTRANCE P

PS LOBBY EXIT P

SD 1ST FLOOR LAUNDRY P 3.26 Range .88 to 3.86

HS 1ST FLOOR BY 125 P

SD 1ST FLOOR BY 125 P 3.61 Range .88 to 3.86

SPK 1ST FLOOR BY JANITOR 108 P

HD IN 1ST FLOOR JANITOR 108 P

SD 1ST FLOOR BY 123 P 3.54 Range .88 to 3.86

SPK 1ST FLOOR BY 123 P

SPK 1ST FLOOR BY 122 P

HS 1ST FLOOR BY 122 P

SD 1ST FLOOR BY 121 F 4.11 Range .88 to 3.86

SPK 1ST FLOOR BY 121 P

HS 1ST FLOOR BY 113 P

SD 1ST FLOOR BY 120 P 3.64 Range .88 to 3.86

SPK 1ST FLOOR BY 114 P

SD 1ST FLOOR BY 118 F 4.11 Range .88 to 3.86

HS 1ST FLOOR BY 118 P

PS 1ST FLOOR EXIT BY STAIR # 2 P

PS 1ST FLOOR IN STAIR # 2 P

PS 2ND FLOOR BY STAIR #2 P

SD 2ND FLOOR BY STAIR #2 P 3.26 Range .88 to 3.86

HS 2ND FLOOR BY 212 P

SD 2ND FLOOR BY 212 F 3.91 Range .88 to 3.86

SPK 2ND FLOOR BY 212 P

HS 2ND FLOOR BY 209 P

SPK 2ND FLOOR BY 209 P

BUILDING 2992-5YR-5-24-2021 PAGE 4 OF 10

Suite #4 Louisville, KY 40299

(502) 614-8646

Premier Fire & Security Inc.

1251 N 6th St

Paducah, KY 42002

(270) 443-7060

DATE

5/24/2021

DEVICE DEVICE LOCATION DEVICE

ADDRESS

OR

ZONE

P A

S S

F

A

IL

S en si ti vi ty

NOTES:

FA = FIRE ALARM - KF = KINGFISHER - BPS = BOOSTER POWER SUPPLY - VP=VOICE/MASS PANEL - AN=ANNUNCIATOR/MASS CONSOLE - PS=MANUAL PULL - SD=SMOKE DETECTOR - DD=DUCT DETECTOR - HD = HEAT DETECTOR - MM=MONITOR MODULE - CR=CONTROL RELAY - CM=CONTROL MODULE - HS = HORN/STROBE - S=STROBE ONLY - MS=MASS STROBE - SPK=SPEAKER - DH=DOOR HOLDER

BUILDING NUMBERINSPECTION TEAM

KS,AS,RR 2992

FIRE ALARM

DEVICE REPORT

SD 2ND FLOOR BY 214 P 3.75 Range .88 to 3.86

SPK 2ND FLOOR BY 207 P

SD 2ND FLOOR BY 216 P 3.68 Range .88 to 3.86

SPK 2ND FLOOR BY 216 P

HS 2ND FLOOR BY 216 P

SPK 2ND FLOOR BY 205 P

SD 2ND FLOOR BY 217 P 3.72 Range .88 to 3.86

SPK 2ND FLOOR BY 218 P

SD 2ND FLOOR BY 219 F 4.31 Range .88 to 3.86

HS 2ND FLOOR BY 203 P

DH 2ND FLOOR BY 203 P

DH 2ND FLOOR NEAR 236 P

SD 2ND FLOOR LOBBY NEAR 203 P 3.79 Range .88 to 3.86

PS 2ND FLOOR LOBBY P

SD 2ND FLOOR VENDING 220 P 3.70 Range .88 to 3.86

HD 2ND FLOOR JANITOR P

HD 2ND FLOOR MECH ROOM 222 P

HS 2ND FLOOR MECH ROOM 222 P

SD 2ND FLOOR LAUNDRY 223 F 3.97 Range .88 to 3.86

SD 2ND FLOOR ELECT ROOM 225 P 3.41 Range .88 to 3.86

SD 2ND FLOOR LOBBY NEAR 225 P 3.85 Range .88 to 3.86

SPK 2ND FLOOR LOBBY P

SPK 2ND FLOOR LOBBY P

SD 2ND FLOOR BY 227 P 3.76 Range .88 to 3.86

HS 2ND FLOOR BY 236 P

SPK 2ND FLOOR BY 236 P

SD 2ND FLOOR BY 228 P 3.72 Range .88 to 3.86

HS 2ND FLOOR BY 229 P

SPK 2ND FLOOR BY 229 P

SD 2ND FLOOR BY 230 P 3.61 Range .88 to 3.86

BUILDING 2992-5YR-5-24-2021 PAGE 5 OF 10

Suite #4 Louisville, KY 40299

(502) 614-8646

Premier Fire & Security Inc.

1251 N 6th St

Paducah, KY 42002

(270) 443-7060

DATE

5/24/2021

DEVICE DEVICE LOCATION DEVICE

ADDRESS

OR

ZONE

P A

S S

F

A

IL

S en si ti vi ty

NOTES:

FA = FIRE ALARM - KF = KINGFISHER - BPS = BOOSTER POWER SUPPLY - VP=VOICE/MASS PANEL - AN=ANNUNCIATOR/MASS CONSOLE - PS=MANUAL PULL - SD=SMOKE DETECTOR - DD=DUCT DETECTOR - HD = HEAT DETECTOR - MM=MONITOR MODULE - CR=CONTROL RELAY - CM=CONTROL MODULE - HS = HORN/STROBE - S=STROBE ONLY - MS=MASS STROBE - SPK=SPEAKER - DH=DOOR HOLDER

BUILDING NUMBERINSPECTION TEAM

KS,AS,RR 2992

FIRE ALARM

DEVICE REPORT

PS 2ND FLOOR BY STAIR # 3 P

SD 2ND FLOOR BY STAIR # 3 P 3.76 Range .88 to 3.86

HS 2ND FLOOR BY STAIR # 3 P

SPK 2ND FLOOR BY STAIR # 3 P

PS 3RD FLOOR BY STAIR # 3 P

SD 3RD FLOOR BY 331 F 4.34 Range .88 to 3.86

HS 3RD FLOOR BY 331 P

SPK 3RD FLOOR BY 332 P

SD 3RD FLOOR BY 328 P 3.22 Range .88 to 3.86

HS 3RD FLOOR BY 328 P

SPK 3RD FLOOR BY 328 P

SD 3RD FLOOR BY 327 F 4.00 Range .88 to 3.86

SD 3RD FLOOR BY 326 P 3.70 Range .88 to 3.86

HS 3RD FLOOR BY 326 P

SD 3RD FLOOR LOBBY BY 324 P 3.65 Range .88 to 3.86

DH 3RD FLOOR LOBBY BY 324

SD 3RD FLOOR ELECT ROOM 324 F 4.79 Range .88 to 3.86

SD 3RD FLOOR LAUNDRY 322 P 3.75 Range .88 to 3.86

SPK 3RD FLOOR BY 324 P

SD 3RD FLOOR IN 319 F 3.89 Range .88 to 3.86

HD 3RD FLOOR JANITOR P

HD 3RD FLOOR MECH ROOM 321 P

HS 3RD FLOOR MECH ROOM 321 P

SD 3RD FLOOR LOBBY NEAR 318 P 3.69 Range .88 to 3.86

DH 3RD FLOOR LOBBY NEAR 318 P

SD 3RD FLOOR BY 318 P 3.71 Range .88 to 3.86

HS 3RD FLOOR BY 318 P

SPK 3RD FLOOR BY 304 P

SD 3RD FLOOR BY 316 F 3.99 Range .88 to 3.86

SPK 3RD FLOOR BY 316 P

BUILDING 2992-5YR-5-24-2021 PAGE 6 OF 10

Suite #4 Louisville, KY 40299

(502) 614-8646

Premier Fire & Security Inc.

1251 N 6th St

Paducah, KY 42002

(270) 443-7060

DATE

5/24/2021

DEVICE DEVICE LOCATION DEVICE

ADDRESS

OR

ZONE

P A

S S

F

A

IL

S en si ti vi ty

NOTES:

FA = FIRE ALARM - KF = KINGFISHER - BPS = BOOSTER POWER SUPPLY - VP=VOICE/MASS PANEL - AN=ANNUNCIATOR/MASS CONSOLE - PS=MANUAL PULL - SD=SMOKE DETECTOR - DD=DUCT DETECTOR - HD = HEAT DETECTOR - MM=MONITOR MODULE - CR=CONTROL RELAY - CM=CONTROL MODULE - HS = HORN/STROBE - S=STROBE ONLY - MS=MASS STROBE - SPK=SPEAKER - DH=DOOR HOLDER

BUILDING NUMBERINSPECTION TEAM

KS,AS,RR 2992

FIRE ALARM

DEVICE REPORT

HS 3RD FLOOR BY 315 P

SPK 3RD FLOOR BY 315 P

SD 3RD FLOOR BY 315 P 3.72 Range .88 to 3.86

SPK 3RD FLOOR BY 307 P

SD 3RD FLOOR BY 313 F 4.05 Range .88 to 3.86

SPK 3RD FLOOR BY 313 P

HS 3RD FLOOR BY 309 P

SPK 3RD FLOOR BY 311 P

SD 3RD FLOOR BY 311 F 4.13 Range .88 to 3.86

PS 3RD FLOOR BY STAIR # 2 P

SD 3RD FLOOR BY STAIR # 2 P 3.69 Range .88 to 3.86

DD ATTIC F 4.45 Range .63 to 2.64

DD ATTIC F 3.69 Range .63 to 2.64

DD ATTIC F 4.45 Range .63 to 2.64

DD ATTIC F 4.20 Range .63 to 2.64

HD ATTIC P

HD ATTIC P

HD ATTIC P

HD ATTIC P

HD ATTIC P

HD ATTIC P

HD ATTIC P

HD ATTIC P

HD ATTIC P

PS ATTIC P

HS ATTIC P

HS ATTIC P

HS ATTIC P

SD 1ST FLOOR MECH ROOM P 3.74 Range .88 to 3.86

TS MECH ROOM BACKFLOW VALVE # 1 P

BUILDING 2992-5YR-5-24-2021 PAGE 7 OF 10

Suite #4 Louisville, KY 40299

(502) 614-8646

Premier Fire & Security Inc.

1251 N 6th St

Paducah, KY 42002

(270) 443-7060

DATE

5/24/2021

DEVICE DEVICE LOCATION DEVICE

ADDRESS

OR

ZONE

P A

S S

F

A

IL

S en si ti vi ty

NOTES:

FA = FIRE ALARM - KF = KINGFISHER - BPS = BOOSTER POWER SUPPLY - VP=VOICE/MASS PANEL - AN=ANNUNCIATOR/MASS CONSOLE - PS=MANUAL PULL - SD=SMOKE DETECTOR - DD=DUCT DETECTOR - HD = HEAT DETECTOR - MM=MONITOR MODULE - CR=CONTROL RELAY - CM=CONTROL MODULE - HS = HORN/STROBE - S=STROBE ONLY - MS=MASS STROBE - SPK=SPEAKER - DH=DOOR HOLDER

BUILDING NUMBERINSPECTION TEAM

KS,AS,RR 2992

FIRE ALARM

DEVICE REPORT

TS MECH ROOM BACKFLOW VALVE # 2 P

TS MECH ROOM FORWARD FLOW P

WF MECH ROOM SPRINKLER RISER P

WPSR

BCKFLW

FDC

PIV

INSPTEST

INSPTEST

INSPTEST

WA

BUILDING 2992-5YR-5-24-2021 PAGE 8 OF 10

ON

PSID

CHECK VALVE #1

THE ABOVE REPORT IS TRUE, ACCURATE, AND COMPLETE.

TESTED BY (PRINT)

4" WILKINS 375A Backflow

(SIGNATURE) REPAIRED BY (PRINT) (SIGNATURE)

4" WILKINS 375A BACKFLOW FAILED DUE TO LEAKING #1 CHECK

STATE AND CERTIFICATION NUMBER(S) WITH EXPIRATION DATE(S)

COMPANY FINAL TEST BY (PRINT) (SIGNATURE)

NOTES, FAILURES AND PARTS USED IF REPAIRED

DOUBLE CHECK VALVE ASSEMBLY

CHECK VALVE #2

PSID

No. 2 SHUT OFF

CLOSED TIGHT No

HELD AT HELD ATCLOSED TIGHT

REDUCED PRESSURE PRINCIPLE ASSEMBLY

CLOSED TIGHT HELD AT

RELIEF VALVE OPENING

POINT

CHECK VALVE #2

BACKPRESSURE TEST

CHECK VALVE #1

OPENED AT 3 HELD AT

04891

TYPE OF ASSEMBLY MANUFACTURER MODEL SIZE

DEVICE PROTECTED FROM FREEZING AND FLOODING

No. 2 SHUT OFF CHECK VALVE #2

SERVICE LOCATION

NCS

11501 Plantside Drive Suite #4 Louisville, KY 40299

(502) 614-8646

Premier Fire & Security Inc.

1251 N 6th St

Paducah, KY 42002

(270) 443-7060

SERIAL NUMBER

MECH ROOM

RP

INSPECTION DATES: INSPECTION TEAM:

5/24/2021 KS,AS,RR

BUILDING NUMBER 02992 Indiana AVE Fort Campbell KY 42223

375A

TEST KIT (BRAND) TEST KIT (MODEL) TEST KIT (SERIAL NUMBER)

WILKINS 4"

PASS FAIL FAILED

CHECK VALVE #2 BACKPRESSURE TEST

CLOSED TIGHT

FAILED 5/24/2021

BUILDING 2992-5YR-5-24-2021 PAGE 9 OF 10

Yes No N/A Yes No N/A P P P P

Yes No N/A

P P P P

Yes No N/A P P Yes No N/A P P P

P Yes No N/A

P Yes No N/A P P

MECH ROOM 4" STRAIGHT NANA

4. Wet Systems 5 Year Wet:

P

Is System in operation?

PAINTED QR 1/2" CHROME 155DG PEND HEAD BY 307, AND ONE BETWEEN 304 AND 305.

A TOTAL OF 4 HEADS PAINTED IN STAIRS, 1/2" QR UPRIGHT 155DG HEADS.

MAKE

29 SECONDS TO ALARM

Is air pressure on the system satisfactory?

satisfactory operating condition?

Did system trip by device to verify operation?

Does quick opening devices work properly?

Did system trip by manual actuator?

MODEL NUMBER

BUILDING NUMBER

Verify water supply "conduct main drain test"

Gauges appear to be in working order ?

2.Annual, 2 Year and 5 Year Inspections:

POC CONTACT INFO

BUILDING POC NAME

VALVE SIZE AND TYPE

NOTES, FAILURES AND SYSTEM DEVIATIONS FROM CONTRACT STANDARDS

Does low air supply works properly?

1.All Inspections:

INSPECTION DATES:

5/24/2021

Adequate heating, and on if necessary.

KS,AS,RR

INSPECTION TEAM:

Is hydrolic nameplace present and visible?

Are control valves supervised, lock or Tamper?

VALVE LOCATION

All low points drained?

All low points drained?

Are OS&Y stems lubricated?

All strainers cleaned and in proper condition.Operated valve to verify proper function?

Verified water travels through inspectors test.

Street: 45 and filled with the correct sprinkler heads?

Is sprinkler head cabinet mounted close to the riser

Are all control valves and trim in good condition?

5. Dry Pipe Bi-Annual

Trip valve, drain and clean internally Does quick opening devices work properly?

Anti-freeze loops have correct solution mixture.

Does low air supply works properly?

Premier Fire & Security Inc.

1251 N 6th St

Paducah, KY 42002

(270) 443-7060

NCS

11501 Plantside Drive Suite #4 Louisville, KY 40299

(502) 614-8646

SPECIAL CONSIDERATIONS - List any unique functions to be aware of prior to testing

Are fire department caps in good condition?

Alarm test in proper position.

Does water flow devices work properly?

Is fire department connection accessible?

3. 2 Year and 5 Year Inspections:

Internally inspected, cleaned and free from damage?

Is air compressor in service and in

Residule:

Static:

OTHER -

Residule: 43

System: 43

5 YEAR -

2 YEAR -2992

Hydrostatic or Previous Gauge Readings

Is there a Backflow Device at the riser?

Current Gauge Readings

Street: 45

ANNUAL -

INSPECTION TYPE

5. Dry Pipe and Pre-action 5 Year

6. Pre-action Bi-Annual

SYSTEM TYPE

OTHER -

PRE-ACTION -

DRY PIPE -

WET PIPE -

Indiana AVE Fort Campbell KY 42223

Static:System:

Air: Air:Pilot:Pilot:

BUILDING 2992-5YR-5-24-2021 PAGE 10 OF 10

VDC VDC AH

VDC VDC AH

ELEVATOR SYSTEM(S)

SHUNT

BATTERY VOLTAGE TYPE:

VDC VDC AH

VDC VDC AH

KF KINGFISHER PS PULL STATION HS HORN / STROBE WA WATER ALARM AN ANNUNCIATOR

FA FIRE ALARM PANEL SD SMOKE DETECTOR S STROBE ONLLY DH DOOR HOLDER AN MASS CONSOLE

BPS POWER SUPPLY HD HEAT DETECTOR MS MASS STROBE TS TAMPER SWITCH CR CONTROL RELAY

VP VOICE / MASS PANEL DD DUCT DETECTOR SPK SPEAKER WF WATER FLOW CM CONTROL MOD

PASS

DOOR HOLDERS PASS

HVAC AUTO RESTART FROM FACP RESET PASS

PASS

PRIMARY RECALL

IS SYSTEM CONNECTED TO MONITORING AGENCY

RESPONSE TO SUPERVISORY TIME:N/A

9:11

ELEVATOR RESTART FROM FIRE SYSTEM RESET

KFRI COMBO

PASS

N/A

ANNUNCIATOR

SPECIAL CONSIDERATIONS - List any unique functions to be aware of before testing

KINGFISHER

MODEL TYPE LOCATION

PASS

TIME:

HVAC SHUTDOWN

PASS

FIRE ALARM

PANEL REPORT

VDC

BATTERY CHARGING VOLTAGE

PANEL MANUFACTURER

9:11

5/20/2021

RESPONSE TO TROUBLE

MASS IN TROUBLE FOR AMP FAIL, VOICE NOT WORKING. CYCLED POWER AND GOT WORKING

NOTES, FAILURES AND SYSTEM DEVIATIONS FROM CONTRACT STANDARDS

10 OF 52 SMOKES (FP-11) FAILED SENSITIVITY TEST ON SIEMENS MXL-IQ PANEL.

3.04

TIME:

SIEMENS

13.53

DIGITAL ALARM RADIO TRANSMITTER (DART)

VDC 35.0

LAMPS / LED TEST

LOCATION

SECONDARY RECALL RECALL

13.41

CIRCUIT BREAKER LOCATION

LOCATION

ELECT ROOM

AMP

FAIL @ 9%

FAIL @ 9%

VDC

INSPECTION DATES:

26.89

BATTERY CHARGING VOLTAGE

POC CONTACT INFO

3.08

MXL-IQ

INSPECTION TEAM:

REAGEN

MODEL

CENTERAL DISPATCH 270-798-1221

MONITORING AGENCY

Indiana AVE Fort Campbell KY 42223

FIRE ALARM CONTROL PANEL (FACP)

BUILDING POC NAME

PANEL MANUFACTURER

KS,AS,RR

NCS

11501 Plantside Drive Suite #4 Louisville, KY 40299

(502) 614-8646

Premier Fire & Security Inc.

1251 N 6th St

Paducah, KY 42002

(270) 443-7060

VDC

MONITORING AGENCY PERSONNEL NOTIFIED

PASS

UPON ARRIVAL FACP IN TROUBLE FOR TAMPER ON SPRINKLER, ADJUSTED AND CLEARED.

SWAPPED BATTERY CHARGING LOCATIONLED TESTTRANSMITTER RECEIVES ALARMS FROM FACP

NAPASS

TRANSMITTER RECEIVES TROUBLES FROM FACP

MODELRESPONSE TO ALARM MANUFACTURER

AMP

AMP

1 YEAR -

INSPECTION TYPE

PASS

BUILDING NUMBER 2 YEAR -

5 YEAR -

OTHER -

35.0 AMP

BUILDING 2993-5YR-5-20-2021 PAGE 1 OF 9

VDC VDC AH 12

VDC VDC AH 12

BATTERY VOLTAGE TYPE:

VDC VDC AH 12

VDC VDC AH 12

BATTERY VOLTAGE TYPE:

VDC VDC AH 12

VDC VDC AH 12

BATTERY VOLTAGE TYPE:

VDC VDC AH

VDC VDC AH

BATTERY VOLTAGE TYPE:

VDC VDC AH

VDC VDC AH

PASS

PASS

PASS @ 80%

NCS

11501 Plantside Drive Suite #4 Louisville, KY 40299

(502) 614-8646

SP-40

BATTERY CHARGING VOLTAGE

27.35

PANEL MANUFACTURER

Premier Fire & Security Inc.

1251 N 6th St

Paducah, KY 42002

(270) 443-7060

AUXILIARY

PANEL REPORT

7.0

PASS @ 90%

FAIL @ 13%

VDC

AMP

AMP

VDC AMP

AMP

VDC 7.0

VDC

VDC

POWER EXPANDER/AUDIO-VISUAL PANEL

MODEL

BATTERY CHARGING VOLTAGE

27.34

AMP

AMP

VDC 7.0

VDC

13.62 5.59

7.00 PASS @ 100%

13.57 0.90

7.0

POWER EXPANDER/AUDIO-VISUAL PANEL

WHEELOCK

PANEL MANUFACTURER MODEL PURPOSE LOCATION

ELECT ROOM

13.59

PASS @ 108%

PANEL MANUFACTURER

POWER EXPANDER/AUDIO-VISUAL PANEL

LOCATIONPURPOSEMODEL

AMP

SPB-80 MASS AMP ELECT ROOM

VDC 7.0 AMP13.6 7.56

PANEL MANUFACTURER MODEL

BATTERY CHARGING VOLTAGE

POWER EXPANDER/AUDIO-VISUAL PANEL

ELECT ROOM

LOCATIONPURPOSE

WHEELOCK

BATTERY CHARGING VOLTAGE

27.94 13.77 6.28

SIEMENS PAD-3 NAC POWER

MODELPANEL MANUFACTURER PURPOSE

MASS PANEL

13.62

PASS

LOCATION

4.69

PURPOSE

VDC 7.0 AMPPASS @ 67%

POWER EXPANDER/AUDIO-VISUAL PANEL

LOCATION

VDC AMP

NOTES, FAILURES AND SYSTEM DEVIATIONS FROM CONTRACT STANDARDS

BATTERY CHARGING VOLTAGE

INSPECTION DATES: INSPECTION TEAM: INSPECTION TYPE

5/20/2021 KS,AS,RR 1 YEAR -

2 YEAR -

BUILDING POC NAME 5 YEAR -

POC CONTACT INFO OTHER -

BUILDING NUMBER 2993 Indiana AVE Fort Campbell KY 42223

BUILDING 2993-5YR-5-20-2021 PAGE 2 OF 9

Suite #4 Louisville, KY 40299

(502) 614-8646

Premier Fire & Security Inc.

1251 N 6th St

Paducah, KY 42002

(270) 443-7060

DATE

5/20/2021

DEVICE DEVICE LOCATION DEVICE

ADDRESS

OR

ZONE

P A

S S

F

A

IL

S en si ti vi ty

NOTES:

FA ELECT ROOM P

KF ELECT ROOM P

BPS ELECT ROOM P

BPS ELECT ROOM P

VP ELECT ROOM P

PS EXIT BY 139 P

HS BY 139 P

PS IN STAIR 137 P

SD BY 139 P 3.33 Range .88 to 3.86

SPK BY 139 P

SD BY 141 P 3.11 Range .88 to 3.86

HS BY 141 P

SD BY 143 P 3.23 Range .88 to 3.86

SPK BY 143 P

SD BY 133 P 3.39 Range .88 to 3.86

HS BY 133 P

SD CQ DESK 144 P 3.46 Range .88 to 3.86

HS CQ DESK 144 P

MS CQ DESK 144 P

SD 1ST FLOOR LOBBY BY 131 P 3.70 Range .88 to 3.86

DH 1ST FLOOR LOBBY BY 131 P

SPK 1ST FLOOR LOBBY P

SPK 1ST FLOOR LOBBY P

PS 1ST FLOOR LOBBY P

PS 1ST FLOOR LOBBY P

SD ABOVE FACP IN ELECT ROOM 131 P 3.82 Range .88 to 3.86

HS IN ELECT ROOM 131 P

PS IN ELECT ROOM 131 P

SD MAIL ROOM 148 P 3.71 Range .88 to 3.86

SD 1ST FLOOR LAUNDRY 129 P 3.34 Range .88 to 3.86

FA = FIRE ALARM - KF = KINGFISHER - BPS = BOOSTER POWER SUPPLY - VP=VOICE/MASS PANEL - AN=ANNUNCIATOR/MASS CONSOLE - PS=MANUAL PULL - SD=SMOKE DETECTOR - DD=DUCT DETECTOR - HD = HEAT DETECTOR - MM=MONITOR MODULE - CR=CONTROL RELAY - CM=CONTROL MODULE - HS = HORN/STROBE - S=STROBE ONLY - MS=MASS STROBE - SPK=SPEAKER - DH=DOOR HOLDER

BUILDING NUMBERINSPECTION TEAM

KS,AS,RR 2993

FIRE ALARM

BUILDING 2993-5YR-5-20-2021 PAGE 3 OF 9

Suite #4 Louisville, KY 40299

(502) 614-8646

Premier Fire & Security Inc.

1251 N 6th St

Paducah, KY 42002

(270) 443-7060

DATE

5/20/2021

DEVICE DEVICE LOCATION DEVICE

ADDRESS

OR

ZONE

P A

S S

F

A

IL

S en si ti vi ty

NOTES:

FA = FIRE ALARM - KF = KINGFISHER - BPS = BOOSTER POWER SUPPLY - VP=VOICE/MASS PANEL - AN=ANNUNCIATOR/MASS CONSOLE - PS=MANUAL PULL - SD=SMOKE DETECTOR - DD=DUCT DETECTOR - HD = HEAT DETECTOR - MM=MONITOR MODULE - CR=CONTROL RELAY - CM=CONTROL MODULE - HS = HORN/STROBE - S=STROBE ONLY - MS=MASS STROBE - SPK=SPEAKER - DH=DOOR HOLDER

BUILDING NUMBERINSPECTION TEAM

KS,AS,RR 2993

FIRE ALARM

DEVICE REPORT

HS 1ST FLOOR LAUNDRY 129 P

SD IN WAITING 103 P 3.25 Range .88 to 3.86

S MENS ROOM P

S WOMENS ROOM P

SD IN VENDING 106 F 4.02 Range .88 to 3.86

SD LOBBY NEAR 106 P

DH LOBBY NEAR 106 P

HS BY 125 P

HD IN JAINTOR 108 P

SD BY 108 P

HS BY 108 P

SPK BY 108 P

SD BY 123 P 3.69 Range .88 to 3.86

HS BY 122 P

SPK BY 122 P

SD BY 121 P 3.68 Range .88 to 3.86

HS BY 113 P

SD BY 119 P 3.77 Range .88 to 3.86

SPK BY 119 P

HS BY 118 P

SD BY 118 P 3.52 Range .88 to 3.86

SPK BY 118 P

PS BY ROOM 118 P

PS IN STAIR 117 P

SD 2ND FLOOR BY STAIR #2 P 3.67 Range .88 to 3.86

PS 2ND FLOOR BY STAIR #2 P

SD 2ND FLOOR BY 212 F 4.08 Range .88 to 3.86

HS 2ND FLOOR BY 209 P

SPK 2ND FLOOR BY 209 P

SD 2ND FLOOR BY 214 P 3.71 Range .88 to 3.86

BUILDING 2993-5YR-5-20-2021 PAGE 4 OF 9

Suite #4 Louisville, KY 40299

(502) 614-8646

Premier Fire & Security Inc.

1251 N 6th St

Paducah, KY 42002

(270) 443-7060

DATE

5/20/2021

DEVICE DEVICE LOCATION DEVICE

ADDRESS

OR

ZONE

P A

S S

F

A

IL

S en si ti vi ty

NOTES:

FA = FIRE ALARM - KF = KINGFISHER - BPS = BOOSTER POWER SUPPLY - VP=VOICE/MASS PANEL - AN=ANNUNCIATOR/MASS CONSOLE - PS=MANUAL PULL - SD=SMOKE DETECTOR - DD=DUCT DETECTOR - HD = HEAT DETECTOR - MM=MONITOR MODULE - CR=CONTROL RELAY - CM=CONTROL MODULE - HS = HORN/STROBE - S=STROBE ONLY - MS=MASS STROBE - SPK=SPEAKER - DH=DOOR HOLDER

BUILDING NUMBERINSPECTION TEAM

KS,AS,RR 2993

FIRE ALARM