Atch 4_Replace HVAC for Animal Rooms Drawings.pdf
PDF 4 MB Posted
- Solicitation number
- 12639525R0013
About this file
These are mechanical and electrical design drawings for replacing the HVAC system in two animal research rooms at the USDA Animal and Plant Health Inspection Service (APHIS) Hawaii Field Station in Hilo, Hawaii. The comprehensive set of technical drawings, prepared by Coffman Engineers, details the replacement of existing fan coil units, condensing units, exhaust fans, and associated ductwork and controls in Animal Rooms 6 and 7. The project involves installing new AAON and Johnson Controls equipment with specific design requirements, including 100% outside air ventilation, maintaining negative room pressure, and providing constant volume airflow between 10-15 air changes per hour. The new system will include advanced controls allowing manual airflow adjustment, temperature monitoring, and operational modes for different occupancy scenarios. The drawings include detailed mechanical schedules, electrical one-line diagrams, floor plans, roof plans, and installation details, with the contract number 12639521D0051 and a project date of March 28, 2024.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 12639525R0013-0001.pdf | ||
| Atch 2_Federal Construction Wage Rates.pdf | ||
| 12639525R0013.pdf | ||
| Atch 3_Replace HVAC for Animal Rooms Spec Manual.pdf | ||
| Atch 1_SOW_Hilo Animal Rooms HVAC.doc | DOC document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
REV DATE DESCRIPTION
PROJ. NO.
DRAWN
CHECKED
DATE
SHEET OF
COFFMAN ENGINEERS INC.C
APHIS - REPLACE
VENTILATION UNITS,
ANIMAL RESEARCH
BUILDING
210 AMAUULU RD.
HAWAII COUNTY
HILO, HI
232507
03/28/24
SHEET TITLE:
SHEET NO:
A
B
C
D
A
B
C
D
1 2 3 4 5
2 3 4 5
CONTRACT # 12639521D0051
A 12/8/23 35% DD
B 01/19/24 95% CD
www.coffman.com ph 509.328.2994
221 N. Wall Street
Spokane, WA 99201 Suite 500
C 03/28/24 100% CD
COVER SHEET
G-001
RKC
TAH
APHIS - REPLACE HVAC SYSTEM
TO ANIMAL ROOMS, HAWAII FIELD STATION
210 AMAUULU ROAD
HAWAII COUNTY
HILO, HI
HAWAII COUNTY
PROJECT LOCATION
HILO BAY
PROJECT LOCATION
SHEET INDEX
E-602 ALT-1 SCHEDULES
ABBR
STANDARD ABBREVIATIONS
DESCRIPTION ABBR DESCRIPTION
A/E ARCHITECT/ENGINEER
AAV AUTOMATIC AIR VENT
ACH AIR CHANGES PER HOUR
AD ACCESS DOOR
AFF ABOVE FINISHED FLOOR
AHU AIR HANDLING UNIT
AP ACCESS PANEL
APD AIR PRESSURE DROP
ARCH ARCHITECT/ARCHITECTURAL
ASME AMERICAN SOCIETY OF MECHANICAL
ENGINEERS
BAS BUILDING AUTOMATION SYSTEM
BD BACKDRAFT DAMPER
BFP BACK FLOW PREVENTER
BG BELOW GROUND
BHP BRAKE HORSEPOWER
BLDG BUILDING
BOD BOTTOM OF DUCT
BTU BRITISH THERMAL UNIT
BTUH BRITISH THERMAL UNITS PER HOUR
CAP CAPACITY
CC COOLING COIL
CFM CUBIC FEET PER MINUTE
CI CAST IRON
CLG CEILING
CMU CONCRETE MASONRY UNIT
CO CLEANOUT
CONC CONCRETE
COND CONDENSER
CONN CONNECT/CONNECTION
CONST CONSTRUCTION
CONT CONTINUATION
COP COEFFICIENT OF PERFORMANCE
CW COLD WATER
CWR CHILLED WATER RETURN
CWS CHILLED WATER SUPPLY
DB DECIBEL or DRY BULB
DDC DIRECT DIGITAL CONTROL
DEMO DEMOLISH
DIA/Ø DIAMETER
DIM DIMENSION
DN DOWN
DWG DRAWING
EA EXHAUST AIR
EAT ENTERING AIR TEMPERATURE
EC ELECTRICAL CONTRACTOR
EDB ENTERING DRY BULB
EER ENERGY EFFICIENCY RATIO
EF EXHAUST FAN
EFF EFFICIENCY
EG EXHAUST GRILLE
ELEC ELECTRIC/ELECTRIAL
ELEV ELEVATION
EMCS ENERGY MANAGEMENT CONTROL
SYSTEM
ENCL ENCLOSURE
EQUIP EQUIPMENT
ESP EXTERNAL STATIC PRESSURE
EWB ENTERING WET BULB
EWT ENTERING WATER TEMPERATURE
EXH EXHAUST
F FAHRENHEIT
FCO FLOOR CLEANOUT
FD FLOOR DRAIN or FIRE DAMPER
FDC FIRE DEPARTMENT CONNECTION
FF FINAL FILTER
FLA FULL LOAD AMPS
FLR FLOOR
FP FIRE PROTECTION
FPM FEET PER MINUTE
FPI FINS PER INCH
FPS FEET PER SECOND
FS FLOOR SINK
FSD FIRE-SMOKE DAMPER
FT FEET or FLASH TANK
FV FACE VELOCITY
GA GAGE or GAUGE
GAL GALLONS
GALV GALVANIZED STEEL
GC GENERAL CONTRACTOR
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
HB HOSE BIBB
HC HEATING COIL
HEPA HIGH EFFICIENCY PARTICULATE AIR
HG HOT GAS
HP HORSEPOWER
HR HOUR
HTG HEATING
HVAC HEATING, VENTILATION, AND AIR
CONDITIONING
HW HOT WATER
HWC HOT WATER CIRCULATION
HX HEAT EXCHANGER
HZ HERTZ
(N) NEW
(E) EXISTING
(R) RELOCATE
(M) MODIFIED
IBC INTERNATIONAL BUILDING CODE
ID INSIDE DIAMETER
IE INVERT ELEVATION
IEEC INTERNATIONAL ENERGY
EFFICIENCY CODE
IFC INTERNATIONAL FIRE CODE
IMC INTERNATIONAL MECHANICAL CODE
IN INCHES
INSUL INSULATION
KW KILOWATT
KWH KILOWATT HOUR
LAT LEAVING AIR TEMPERATURE
LBS POUNDS
LDB LEAVING DRY BULB
LWB LEAVING WET BULB
LWT LEAVING WATER TEMPERATURE
MAV MANUAL AIR VENT
MAX MAXIMUM
MBH THOUSAND BTU PER HOUR
MCA MINIMUM CIRCUIT AMPS
MC MECHANICAL CONTRACTOR
MCC MOTOR CONTROL CENTER
MECH MECHANICAL
MFR MANUFACTURER
MIN MINIMUM or MINUTES
MISC MISCELLANEOUS
MOCP MAXIMUM OVER CURRENT
PROTECTION
NA NOT APPLICABLE
NC NORMALLY CLOSED or NOISE
CRITERIA
NIC NOT IN CONTRACT
NO NORMALLY OPEN
NPT NATIONAL PIPE THREAD
NTS NOT TO SCALE
OBD OPPOSED BLADE DAMPER
OC ON CENTER
OD OUTSIDE DIAMETER
ORD OVERFLOW ROOF DRAINAGE
OA or OSA OUTSIDE (SUPPLY) AIR
PD PRESSURE DROP
PG PROPYLENE GLYCOL
PH/Ø PHASE
PLBG PLUMBING
POC POINT OF CONNECTION
PRV PRESSURE REDUCING VALVE
PSI POUNDS PER SQUARE INCH
PSIG POUNDS PER SQUARE INCH GAGE
PT PRESSURE TEMPERATURE
RA RETURN AIR
REQD REQUIRED
REV REVISION(S)
RO REVERSE OSMOSIS
RPBP REDUCED PRESSURE BACKFLOW
PREVENTER
RPM REVOLUTIONS PER MINUTE
SA SUPPLY AIR
SD SMOKE DETECTOR or SMOKE
DAMPER
SEER SEASONAL ENERGY EFFICIENCY
RATIO
SENS SENSIBLE
SF SUPPLY FAN or SQUARE FEET
SIM SIMILAR
SM SHEET METAL
SMACNA SHEET METAL AND AIR
CONDITIONING CONTRACTORS
NATIONAL ASSOCIATION
SP STATIC PRESSURE
SPEC SPECIFICATION or SPECIFIED
SQ SQUARE
SQ FT SQUARE FEET
SS STAINLESS STEEL
STD STANDARD
TAB TEST, ADJUSTMENT & BALANCE
TC TEMPERATURE CONTROLS
TEMP TEMPERATURE
TP TRAP PRIMER or TEST PLUG
TSP TOTAL STATIC PRESSURE
TSTAT THERMOSTAT
TU TERMINAL UNIT
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
UPC UNIFORM PLUMBING CODE
V VENTS OR VOLTS
VAC VACUUM or VOLTAGE ALTERNATING
CURRENT
VAV VARIABLE AIR VOLUME
VD VOLUME DAMPER
VEL VELOCITY
VFD VARIABLE FREQUENCY DRIVE
VTR VENT THRU ROOF
WB WET BULB
WC WATER CLOSET
WCO WALL CLEANOUT
WH WATER HEATER
WHA WATER HAMMER ARRESTOR
W/ WITH
W/O WITHOUT
ZVB ZONE VALVE BOX
D
RL
RS REFRIGERANT SUCTION
REFRIGERANT LIQUID
DRAIN - INDIRECTD
RL
RS
TEE DOWN
PIPE TURNING UP OR TOWARD
PIPE TURNING DOWN OR AWAY
PIPE END CAP
TEE UP
SD
H
T
AHU-1
P1-1
GENERAL LEGEND
SYMBOL DESCRIPTION
THIN LINEWORK INDICATES EXISTING
MEDIUM LINEWORK INDICATES NEW
THERMOSTAT OR TEMPERATURE SENSOR (WALL MOUNTED)
HUMIDISTAT OR HUMIDITY SENSOR (WALL MOUNTED)
DETAIL SYMBOL: A = IDENTIFYING NUMBER
B = SHEET WHERE DETAIL IS SHOWN
SECTION SYMBOL: A = IDENTIFYING LETTER
B = SHEET WHERE SECTION IS SHOWN
SECTION CUT LINE INDICATOR
THICK DASHED LINEWORK WITH HATCH
INDICATES EXISTING TO BE DEMOLISHED
KEYED REFERENCE NOTE SPECIFIC TO LOCATION INDICATED
POINT OF CONNECTION (POC)
PLUMBING FIXTURE TAG (REFER TO SCHEDULE)
MECHANICAL EQUIPMENT TAG (REFER TO SCHEDULES)
REVISION CLOUD AND REVISION NUMBER
SMOKE DETECTOR
GENERAL NOTE APPLIES TO ENTIRE SHEETX.
EXISTING(E)
NEW(N)
RELOCATE(REL)
NEW LOCATION(NL)
CO2 CO2 SENSOR
GENERAL MECHANICAL NOTES
DESIGN CONDITIONS
LOCATION HILO, HAWAII
OUTDOORS
SUMMER: 86.3°F DB / 74.6°F WB
WINTER: 61.7°F DB / 55.6 WB
INDOOR
COOLING: 77°F DB
HEATING: NO HEATING
VENTILATION PER ARS 242.1: 10-15 AIR CHANGES PER HOUR
HUMIDITY 60% RH INDOORS MAX. / NO MINIMUM
ELEVATION 212 FT ABOVE SEA LEVEL
DUCT HANGER
MECHANICAL LEGEND
DUCT SIZE IN INCHES FIRST SIZE
LISTED IS SIDE SHOWN
DUCT OFFSET (UP) IN DIRECTION OF
ARROW (NOT TYPICALLY SHOWN)
DUCT OFFSET (DN) IN DIRECTION OF
ARROW (NOT TYPICALLY SHOWN)
CHANGE OF DUCT SIZE
(TRIANGLE NOT ALWAYS SHOWN)
RECTANGULAR SUPPLY DUCT
ELBOW TURNED DOWN OR AWAY
RECTANGULAR RETURN/EXHAUST DUCT
ELBOW TURNED UP
RECTANGULAR RETURN/EXHAUST DUCT
ELBOW TURNED DOWN OR AWAY
SMALL RECTANGULAR DUCT ELBOW
TURNED DOWN OR AWAY
END OF DUCT WITH CAP
(UNLESS INDICATED OTHERWISE)
RECTANGULAR ELBOW WITH TURNING
VANES (SINGLE LINE)
BRANCH DUCT TAKE-OFF (SINGLE LINE)
GRILLE, REGISTER OR OPEN DUCT
(SUPPLY SHOWN)
TAG FOR GRILLE, REGISTER OR DIFFUSER.
REFER TO GRD SCHEDULE.
LINEAR SLOT DIFFUSER. REFER TO DIFFUSER AND
GRILLE SCHEDULE FOR ADDITIONAL INFORMATION.
CEILING SUPPLY DIFFUSER. REFER TO GRD
SCHEDULE
HYDRONIC HEATING OR COOLING COIL. REFER TO
DRAWING NOTES AND/OR SCHEDULE FOR CAPACITY.
TERMINAL OR DUCT MOUNTED ELECTRIC HEATING
COIL. IF NOT INDICATED ON SCHEDULES, FIRST
NUMBER INDICATES COIL HEATING CAPACITY (KW),
SECOND NUMBER INDICATES SUPPLY VOLTAGE
(VOLTS), THIRD NUMBER INDICATES PHASE(S).
MODULATING OPPOSED BLADE DAMPER
BACKDRAFT DAMPER
FIRE/SMOKE DAMPER
FIRE DAMPER
VOLUME DAMPER
RADIUS ELBOW (SINGLE LINE)
DUCT ACCESS DOOR
FLEXIBLE DUCT
ROUND DUCT ELBOW TURNED DOWN
OR AWAY
ROUND DUCT ELBOW TURNED UP
RECTANGULAR SUPPLY DUCT ELBOW
TURNED UP
CHANGE OF DUCT SIZE
OVAL DUCT IN INCHES
ROUND DUCT IN INCHES
ACOUSTIC LINED DUCT
BDD
MD
FSD
FDPR
VD
INDICATES RETURN or EXHAUST AIR FLOW
DIRECTION
INDICATES SUPPLY AIR FLOW DIRECTION
DUCT SMOKE DETECTOR
LOW LIMIT THERMOSTATLLT
DSD
4.5 KW-460-3Ø
MTD MOTORIZED DAMPER
SD SMOKE DAMPER
CEILING GRILLE (RETURN OR TRANSFER)
REFER TO GRD SCHEDULE
CEILING EXHAUST GRILLE (RETURN OR TRANSER)
REFER TO GRD SCHEDULE
RECTANGULAR EXHAUST DUCT TURNED UP
RECTANGULAR EXHAUST DUCT TURNED DOWN
RECTANGULAR OUTSIDE AIR DUCT TURNED UP
RECTANGULAR OUTSIDE AIR DUCT TURNED DOWN
1. CONTRACTOR SHALL SECURE, MAINTAIN, AND PAY FOR ALL REQUIRED
PERMITS, LICENSES, AND INSPECTIONS FOR DURATION OF WORK UNLESS
DIRECTED OTHERWISE.
2. ALL WORK SHALL COMPLY WITH THE OWNER'S REQUIREMENTS, AND WITH ALL
APPLICABLE STATE AND LOCAL CODES, OR AUTHORITY HAVING JURISDICTION.
3. DRAWINGS ARE DIAGRAMMATIC IN NATURE AND DO NOT ATTEMPT TO SHOW
ALL REQUIRED OFFSETS. COORDINATE WITH OTHER TRADES AND PROVIDE
ALL NECESSARY OFFSETS.
4. MATERIALS OR EQUIPMENT SPECIFIED TO BE "FURNISHED BY OTHERS" SHALL
BE FURNISHED BY THE GENERAL CONTRACTOR AND/OR PROCURED FROM
SOURCES SPECIFIED BY THE CONTRACT DOCUMENTS.
5. ALL EQUIPMENT AND MATERIAL ON THE JOB SITE PRIOR TO INSTALLATION
SHALL BE COVERED AND PROTECTED FROM DIRT, DUST, AND DAMAGE.
6. PROVIDE ALL DEMOLITION WORK CALLED FOR OR REQUIRED BY THE
INSTALLATION. REMOVE ALL EXISTING EQUIPMENT AND MATERIALS NOT
REUSED UNLESS SPECIFIED OTHERWISE BY THE OWNER'S REP.
7. VERIFY PHYSICAL DIMENSIONS OF EQUIPMENT TO ENSURE THAT ACCESS
CLEARANCES CAN BE MET. COORDINATE FINAL EQUIPMENT LOCATIONS W/
GENERAL CONTRACTOR AND OTHER TRADES TO ALLOW FOR REQUIRED
MECHANICAL EQUIPMENT CLEARANCES.
8. PROVIDE NEC CODE MINIMUM HORIZONTAL AND VERTICAL WORKING
CLEARANCES FOR ALL ELECTRICAL PANELS AND EQUIPMENT. OFFSET
MECHANICAL WORK AS REQUIRED.
9. CONTRACTOR IS RESPONSIBLE FOR VERIFICATION OF INSTALLATION
STANDARDS AND CONSTRUCTION CONDITIONS. CONTRACTOR SHALL FIELD
VERIFY ALL DIMENSIONS AND EXISTING CONDITIONS PRIOR TO SHOP
FABRICATION AND/OR FIELD INSTALLATION. DISCREPANCIES BETWEEN
EXISTING CONDITIONS AND THE CONSTRUCTION DRAWINGS SHALL BE CALLED
TO THE ATTENTION OF THE ENGINEER. WORK DONE WITHOUT THE
ENGINEERS APPROVAL IS THE RESPONSIBILITY OF THE CONTRACTOR.
10. ALL MECHANICAL EQUIPMENT, MATERIALS, AND INSTALLATION SHALL BE
PROVIDED BY THE CONTRACTOR. ALL EQUIPMENT SHALL BE COMPLETE,
INSTALLED, AND FULLY FUNCTIONAL PRIOR TO FINAL ACCEPTANCE OF THE
WORK.
11. INSTALL ALL EQUIPMENT PER MANUFACTURERS RECOMMENDATIONS AND
REQUIREMENTS. ANY CONFLICTS BETWEEN THE MANUFACTURERS
DOCUMENTATION AND THE CONTRACT DOCUMENTS SHALL BE BROUGHT TO
THE ATTENTION OF THE ENGINEER.
12. PROVIDE SEISMIC RESTRAINT OF MECHANICAL SYSTEMS AND EQUIPMENT AS
REQUIRED BY ASCE-7 AND INTERNATIONAL BUILDING CODE AS ADOPTED BY
THE AUTHORITY HAVING JURISDICTION.
13. IN ALL PLACES WHERE A SPECIFIC MANUFACTURER IS LISTED, THE
MANUFACTURER LISTED WAS USED AS BASIS-OF-DESIGN. EQUIVALENT
PRODUCT BY ANOTHER MANUFACTURER WILL BE ACCEPTABLE. THE
CONTRACTOR IS RESPONSIBLE FOR NOTIFYING ENGINEER OF SUBSTITUTIONS
AND PROVIDING SUBMITTALS FOR APPROVAL. CONTRACTOR IS RESPONSIBLE
FOR ANY AND ALL ADDITIONAL DESIGN FEES OR ADDITIONAL ELECTRICAL,
STRUCTURAL, MECHANICAL, OR ARCHITECTURAL REQUIREMENTS AS
REQUIRED DUE TO SUBSTITUTIONS.
REV DATE DESCRIPTION
PROJ. NO.
DRAWN
CHECKED
DATE
SHEET OF
COFFMAN ENGINEERS INC.C
APHIS - REPLACE
VENTILATION UNITS,
ANIMAL RESEARCH
BUILDING
210 AMAUULU RD.
HAWAII COUNTY
HILO, HI
232507
03/28/24
SHEET TITLE:
SHEET NO:
A
B
C
D
A
B
C
D
1 2 3 4 5
2 3 4 5
CONTRACT # 12639521D0051
A 12/8/23 35% DD
B 01/19/24 95% CD
www.coffman.com ph 509.328.2994
221 N. Wall Street
Spokane, WA 99201 Suite 500
C 03/28/24 100% CD
MECHANICAL
LEGENDS AND
ABBREVIATIONS
M-001
RKC
TAH
MECHANICAL DESIGN BASIS
PROJECT SUMMARY
THIS PROJECT WILL REPLACE THE EXISTING HVAC SYSTEMS SERVING ANIMAL ROOMS 6 AND 7. THESE ROOMS ARE CLASSIFIED AS BSL-2 OR LOWER. SYSTEM REPLACEMENT IS NECESSITATED BY THE POOR CONDITION OF THE EXISTING FAN COIL UNITS AND OUTSIDE AIR DUCTING. SYSTEM CONDITION PROBLEMS INCLUDE CORROSION AND UNRELIABLE OPERATION. THE PROJECT WILL ALSO PROVIDE NEW HVAC SYSTEM CONTROLS THAT WILL IMPROVE THE OPERATOR-TO-SYSTEM INTERFACE AND SYSTEM CONTROLLABILITY. THE NEW SYSTEM CONTROLS WILL MAINTAIN THE ANIMAL ROOMS AT A NEGATIVE PRESSURE RELATIVE TO THE REST OF THE BUILDING.
APPLICABLE CODES AND STANDARDS
2018 INTERNATIONAL MECHANICAL CODE
2020 NATIONAL ELECTRIC CODE (NFPA 70)
MANUAL 242.1 ARS FACILITIES DESIGN STANDARDS
DESIGN CRITERIA
1. INSIDE DESIGN CONDITIONS: SEE DESIGN CONDITION SCHEDULE.
2. OUTSIDE DESIGN CONDITIONS: SEE DESIGN CONDITION SCHEDULE.
3. DESIGN COOLING LOAD
· ANIMAL ROOM 6: 15,000 BTU/HR (SENSIBLE). THIS SENSIBLE LOAD INCLUDES ~4,000 BTU/HR OF LAB EQUIPMENT HEAT REJECTION BASED ON THE FOLLOWING
ANALYSIS AND ASSUMPTIONS:
· AIR SCIENCE DOWNFLOW HOOD, MODEL DWS 36, 120V/10A. HEAT REJECTION INTO ROOM ASSUMES 75% OF RATED POWER, WITH A USE FACTOR OF 25%. TOTAL
HEAT REJECTION = 768 BTU/HR.
· THERMOSCIENTIFIC BIOSAFETY CABINET, 1300 SERIES A2, 120V/8A. HEAT REJECTION INTO ROOM ASSUMES 75% OF RATED POWER, WITH A USE FACTOR OF 25%.
TOTAL HEAT REJECTION = 614 BTU/HR.
· THERMOSCIENTIFIC LOW TEMPERATURE FREEZER, MODEL UXF30086A, 115V/16. HEAT REJECTION INTO ROOM IS BASED ON THE RATED POWER INPUT, WITH A USAGE FACTOR OF 0.41 PER ASHRAE FUNDAMENTALS CHAPTER 18 TABLE 5A. TOTAL HEAT REJECTION = 2,575 BTU/HR.
· CONCLUSION: THE 15,000 BTU/HR SENSIBLE COOLING LOAD IN ANIMAL ROOM 6 IS CONSISTENT WITH THE ESTIMATED COOLING CAPACITY OF A 3-TON COOLING SYSTEM. THE EXISTING COOLING SYSTEM HAS A 3-TON NOMINAL CAPACITY AND HAS A HISTORY OF SUCCESSFULLY MEETING THE COOLING NEEDS OF THE
ROOM (ASIDE FROM UNRELIABILITY DUE TO AGE).
· ANIMAL ROOM 7: 10,770 BTU/HR (SENSIBLE): THIS ROOM DOES NOT CURRENTLY HAVE LAB EQUIPMENT.
4. PARTICULATE FILTRATION: NEW EQUIPMENT WILL BE PROVIDED WITH NOMINAL 30% / MERV 8 FILTERS FOR PARTICULATE FILTRATION. A SECOND RACK WILL BE
SPECIFIED FOR A MERV 13 FINAL FILTER DOWNSTREAM OF THE MERV 8 FILTER THAT CAN BE ADDED IF DESIRED BY THE FIELD STATION MANAGER.
5. VENTILATION: 100% OUTSIDE AIR WILL BE PROVIDED TO ANIMAL ROOMS 6 AND 7. PER MANUAL 242.1 PARAGRAPH 9.5.3.A, THE DESIGN AIR FLOW RATE IS 15 AIR
CHANGES PER HOUR, WITH TURNDOWN TO 10-12 AIR CHANGES PER HOUR PERMISSIBLE DURING NORMAL OPERATION WHEN ROOMS ARE OCCUPIED BY ANIMALS. AIR FLOW RATES CAN BE REDUCED TO 50% OF THE DESIGN AIR FLOW RATE WHEN NO ANIMALS ARE PRESENT, BY MANUALLY CHANGING THE AIR FLOW RATE AT THE
TOUCHSCREEN IN EACH ROOM.
6. ROOM PRESSURE REQUIREMENTS: PER MANUAL 242.1 PARAGRAPH 9.5.3.A, ANIMAL ROOMS SHOULD BE MAINTAINED AT A NEGATIVE PRESSURE OF ~0.05” W.G.
RELATIVE TO ADJACENT CONNECTED SPACES. IT SHOULD BE NOTED THAT THIS LEVEL OF NEGATIVE PRESSURE MAY BE IMPOSSIBLE TO ACHIEVE GIVEN THE EXISTING BUILDING ENVELOPE AND INTERIOR WALL CONSTRUCTION. A NEGATIVE PRESSURE OF ~0.01”-0.02” W.G. MAY BE MORE REALISTIC. ROOM NEGATIVE PRESSURE WILL BE CONTROLLED BY MEASURING SUPPLY AND EXHAUST AIR FLOW RATES AND CONTROLLING THE SUPPLY FAN TO ALWAYS MAINTAIN A LOWER CFM THAN THE EXHAUST
FAN.
EXISTING SYSTEM DESCRIPTION
THE EXISTING HVAC SYSTEM SERVING ANIMAL ROOM 7 INCLUDES FAN COIL FC-1, EXHAUST FAN EF-1, AND CONDENSING UNIT CU-1. FC-1 IS DESIGNED TO PROVIDE 900 CFM OF 100% OUTSIDE AIR. EF-1 IS DESIGNED TO EXHAUST 910 CFM. FC-1 IS CONTROLLED BY A WALL MOUNT THERMOSTAT. THE FAN SPEED OF EF-1 CAN BE MANUALLY
ADJUSTED BY A WALL MOUNTED CONTROL.
THE EXISTING HVAC SYSTEM SERVING ANIMAL ROOM 6 INCLUDES FAN COIL FC-2, EXHAUST FAN EF-2, AND CONDENSING UNIT CU-2. FC-2 IS DESIGNED TO PROVIDE 900 CFM OF 100% OUTSIDE AIR. EF-2 IS DESIGNED TO EXHAUST 910 CFM. FC-2 IS CONTROLLED BY A WALL MOUNT THERMOSTAT. THE FAN SPEED OF EF-2 CAN BE MANUALLY
ADJUSTED BY A WALL MOUNTED CONTROL.
NEW/MODIFIED HVAC SYSTEM AND CONTROLS DESCRIPTION
EXISTING EQUIPMENT FC-1, FC-2, EF-1, EF-2, CU-1, AND CU-2 WILL BE DEMOLISHED AND REPLACED WITH NEW COMMERCIAL QUALITY EQUIPMENT OF THE SAME APPROXIMATE CAPACITY AND CONFIGURATION. EXISTING SUPPLY DUCTING WILL BE DEMOLISHED. EXISTING EXHAUST DUCTING WILL BE CLEANED AND REMAIN IN PLACE.
NEW CONTROLS WILL INCLUDE TEMPERATURE AND PRESSURE CONTROL FOR EACH ANIMAL ROOM. A NEGATIVE PRESSURE WILL BE AUTOMATICALLY MAINTAINED BY MEASURING THE SUPPLY AND EXHAUST FLOW RATES FOR EACH ROOM AND APPLYING A CONSTANT NEGATIVE ~150 CFM (ADJ) SUPPLY OFFSET FROM THE EXHAUST CFM FLOW RATE. THE FLOW RATE IN EACH ANIMAL ROOM WILL BE CONSTANT VOLUME, BUT MANUALLY ADJUSTABLE FROM 10-15 AIR CHANGES PER HOUR, VIA A WALL MOUNTED CONTROLLER. THE OCCUPIED AIR FLOW RATE FOR ROOM 6 CAN BE ADJUSTED FROM 10 AC/HR (655 CFM) TO 16 AC/HR (1,050 CFM). THE UNOCCUPIED (NO ANIMALS) AIR FLOW
RATE FOR ROOM 6 CAN BE ADJUSTED AS LOW AS 8 ACH/HR (525 CFM).
THE OCCUPIED AIR FLOW RATE FOR ROOM 7 CAN BE ADJUSTED FROM 10 AC/HR (705 CFM) TO 15 AC/HR (1,050 CFM). THE UNOCCUPIED (NO ANIMALS) AIR FLOW RATE FOR
ROOM 7 CAN BE ADJUSTED AS LOW AS 8 ACH/HR (525 CFM).
FAN COIL UNIT SCHEDULE
TAG MANUFACTURER/ MODEL
FAN COOLING COIL UNIT POWER REQUIREMENTS UNIT
WT.
(LBS)
REMARKSCFM ESP
(IN WC)
TSP
(IN WC)
RPM MOTOR BHP FLA MOTOR
HP
TOTAL
MBH
SENSIBLE
MBH
EAT DB
(˚F)
EAT WB
(˚F)
LAT DB
(˚F)
LAT WB
(˚F)
ROWS/
FPI CONN. (IN) VOLTS Ø MCA MOCP
FCU-1 AAON/H3-BRB-2-A-141D-000 900 0.3 0.8 1,208 0.21 2.30 1.00 56.6 20.6 80.0 76.5 58.9 58.3 4/14 1-1/8 / 5/8 208 3 3.0 15.0 530 1,2,3,4,5,6,7
FCU-2 AAON/H3-BRB-2-A-141D-000 900 0.3 0.8 1,208 0.21 2.30 1.00 56.6 20.6 80.0 76.5 58.9 58.3 4/14 1-1/8 / 5/8 208 3 3.0 15.0 530 1,2,3,4,5,6,7
FCU-1 ALT-1 JOHNSON
CONTROLS/AHD08 900 0.5 1.2 1,360 BY VENDOR 5.00 0.50 57.6 21.4 80.0 76.5 59.4 59.0 4/12 5/8 / 5/8 208 1 6.3 15.0 209 1,2,3,6,7,8
FCU-2 ALT-1 JOHNSON
CONTROLS/AHD08 900 0.5 1.2 1,360 BY VENDOR 5.00 0.50 57.6 21.4 80.0 76.5 59.4 59.0 4/12 5/8 / 5/8 208 1 6.3 15.0 209 1,2,3,6,7,8
REMARKS:
1. THIS APPLICATION IS COOLING ONLY. UNITS ARE PAIRED WITH A REMOTE CONDENSER.
2. PROVIDE WITH CLASS 1 MOTORIZED AUTOMATIC DAMPER INTEGRAL TO UNIT.
3. PROVIDE VFD WITH TEFC MOTOR.
4. UNIT TO BE DOUBLE WALL.
5. PROVIDE INTERIOR CORROSION PROTECTION AND POLYMER E-COATED COIL AND STAINLESS STEEL COIL CASING.
6. PROVIDE WITH MERV 8 PRE FILTER AND OPTION TO ADD ADDITIONAL MERV 13 FILTER UNIT FILTER.
7. PROVIDE WITH MAGNEHELIC GAUGE AND CLOGGED FILTER SWITCH.
8. PROVIDE THIRD PARTY CONTROLS.
FAN SCHEDULE
TAG SERVES MANUFACTURER/ MODEL
DESCRIPTION FAN PERFORMANCE UNIT POWER REQMTS UNIT
WT.
(LBS)
REMARKSTYPE DRIVE FLOW
(CFM)
ESP
(IN WC)
SPEED
(RPM)
NOISE
(SONES)
BHP HP VOLTS Ø FLA LOCATION
EF-1 ANIMAL ROOM
EXHAUST GREENHECK / CUE-120-A UPBLAST DIRECT 1050 1 1441 12.9 1.01 1/2 208 3 2.4 89 ROOF 1,2,3,4,5
EF-2 ANIMAL ROOM
EXHAUST GREENHECK / CUE-120-A UPBLAST DIRECT 1050 1 1441 12.9 1.01 1/2 208 3 2.4 89 ROOF 1,2,3,4,5
REMARKS:
1. PROVIDE FAN WITH CORROSION RESISTANT MATERIAL AND FASTENERS OR COATED MATERIAL SUITABLE FOR A MARINE ENVIRONMENT.
2. PROVIDE WITH BIRD SCREEN.
3. PROVIDE UNIT WITH VFD CONFIGURATION.
4. PROVIDE AUTOMATIC CLASS 1 MOTORIZED DAMPER AT ROOF CURB. DAMPER MANUFACTURER AND MODEL: GREENHECK VCD-23-PB.
5. PROVIDE 115VAC DAMPER ACTUATOR INTERLOCKED WITH FAN. ACTUATOR MANUFACTURER AND MODEL: GREENHEACK MS4103F1025.
ROOM AIR BALANCE SCHEDULE
ROOM NO ROOM NAME
AIR
HANDLING
UNIT NO.
INDIVIDUAL ROOM
TEMP CONTROL
SUPPLY EXHAUST
ROOM AIR FLOW ROOM AIR
BALANCE
NET
INFILTRATION
NET
EXFILTRATION REMARKSROOM
AIR FLOW REQUIRED
ACH
DESIGN
ACH EXHAUST
ROOM
AIR FLOW
CFM CFM CV VAV CFM CFM
6 ANIMAL ROOM FC-2 YES 900 8-15 15 E 1050 CV - NEGATIVE 150 - 1
7 ANIMAL ROOM FC-1 YES 900 8-15 15 E 1050 CV - NEGATIVE 150 - 1
- CORRIDOR / BUILDING - YES - - - - - CV - NEGATIVE 300 300
REMARKS:
1. ANIMAL ROOM AIR FLOW RATES ARE CONSTANT VOLUME WITH MANUAL ADJUSTEMENT.
GRILLES, REGISTERS, DIFFUSERS SCHEDULE
GRILLE NECK PANEL THROW DAMPER FRAME
TAG TYPE MFR MODEL SIZE SIZE SIZE PATTERN TYPE MATERIAL STYLE FINISH REMARKS
1S SUPPLY PRICE 620/N/L/A 26x10 26x10 - - VCS3AL ALUM. SURFACE B12 1,2,3,4
1E EXHAUST PRICE 630FF/L/HL 24x24 24x24 24x24 - - ALUM. SURFACE B12 5
REMARKS:
1. PROVIDE TRANSITION AT GRILLE IF REQUIRED; SEE PLANS FOR DUCT SIZES.
2. GRILLES SHALL HAVE A 1-1/4" BORDER ON ALL SIDES WITH COUNTERSUNK SCREWS AND HAVE A MINIMUM THICKNESS OF 20-GUAGE. CORNERS SHALL BE WELDED WITH A REINFORICNG PATCH.
3. DIFLECTION BLADES SHALL BE MADE OF HEAVY-DUTY ALUMIUM AND SHALL EXTEND COMPLETELY THROUGH THE SIDE FRAME. BLADES SHALL BE INDIVIDUALLY ADJUSTABLE AND HELD IN PLACE WITH TENSION WIRE.
4. INSTALL GRILLE LEVEL AND PLUMB IN ACCORDANCE TO MANUFACTURER INSTRUCTIONS. GRILLE SHALL BE INSTALLED WITH AIRTIGHT CONNECTIONS TO DUCT.
5. GRILLES SHALL ACCEPT 2" FILTER AND SHALL HAVE HINGES AT BOTTOM OF GRILLE, SAME AS EXISTING.
EXHAUST FAN VARIABLE FREQUENCY DRIVE SCHEDULE
TAG LOCATION SERVES MFR MODEL MOTOR
QTY
MOTOR
HP VOLTS PHASE BYPASS DISCONNECT
AND FUSES
NEMA
ENCLOSURE
INPUT LINE
REACTOR OUTPUT LC FILTER EP/UPS REMARKS
VFD-1 ANIMAL ROOM 7 EF-1 ABB ACH580 1 1/2 208 3 YES YES NEMA 1 YES IF MOTOR LEAD LENGTH EXCEED 25 FT. Y/N VFD-3 ANIMAL ROOM 6 EF-2 ABB ACH580 1 1/2 208 3 YES YES NEMA 1 YES IF MOTOR LEAD LENGTH EXCEED 25 FT. Y/N
REMARKS:
SEISMIC AND VIBRATION CONTROL
ITEM/TAG ISOLATOR AND BRACING REQUIREMENTS CONNECTIONS
FCU-1 BRACE PER DETAIL NOTES, USE SPRING HANGER, 1.5" DEFLECTION FLEXIBLE DUCT CONNECTIONS FCU-2 BRACE PER DETAIL NOTES, USE SPRING HANGER, 1.5" DEFLECTION FLEXIBLE DUCT CONNECTIONS
EF-1 BRACE PER DETAIL NOTES FASTENED TO CURB
EF-2 BRACE PER DETAIL NOTES FASTENED TO CURB
SEISMIC RESTRAINT PROVISIONS
SEISMIC RESTRAINT CALCULATIONS MUST BE PROVIDED BY THE PRODUCT MANUFACTURER FOR ALL CONNECTIONS OF EQUIPMENT TO THE STRUCTURE. ALL RESTRAINING DEVICES SHALL HAVE TESTING DATA TO VALIDATE MAXIMUM RESTRAINT RATINGS. CALCULATIONS (INCLUDING THE COMBINING OF TENSILE AND SHEAR LOADING) TO SUPPORT SEISMIC RESTRAINT DESIGNS MUST BE STAMPED BY A REGISTERED PROFESSIONAL ENGINEER LICENSED IN WASHINGTON. THE ENGINEERING ANALYSIS MUST INDICATE CALCULATED DEAD LOADS, STATIC SEISMIC LOADS, AND CAPACITY OF MATERIALS UTILIZED FOR CONNECTIONS TO EQUIPMENT STRUCTURE.
ANALYSIS MUST DETAIL ANCHORING METHODS, BOLT DIAMETER, EMBEDMENT, AND/OR WELDED LENGTH.
ALL SEISMIC RESTRAINT DEVICES SHALL BE DESIGNED TO ACCEPT, WITHOUT FAILURE, THE FORCES PRESCRIBED PER THE ASCE 7-16 ACTING THROUGH THE EQUIPMENT CENTER OF GRAVITY. OVERTURNING MOMENTS MAY EXCEED FORCES AT GROUND LEVEL AND MAY BE RESISTED BY SEISMIC RESTRAINTS, SUPPORT, OR ANCHORAGE.
ANCHORAGE TO CONCRETE MUST HAVE AN ICC TESTING REPORT THAT ADHERES TO THE REQUIREMENTS OF THE 2018 IBC AND MUST BE RATED FOR SEISMIC RESTRAINT IN CRACKED CONCRETE USING THE APPROPRIATE REDUCTION FACTORS PER ACI 318 APPENDIX D. ACCEPTABLE ANCHORS INCLUDE THE HILTI KWIK BOLT TZ AND SIMPSON STRONG BOLT WEDGE ANCHORS OR HILTI HIT-RE 500-SD AND SIMPSON SET XP EPOXY ANCHORS. EPOXIES ARE NOT ACCEPTABLE FOR USE IN OVERHEAD
APPLICATIONS.
SEISMIC DESIGN CRITERIA
SEISMIC DESIGN CATEGORY = D
SITE CLASS = D
RISK CATEGORY = II
BUILDING SEISMIC IMPORTANCE FACTOR: I = 1.0
DESIGN SPECTRAL RESPONSE ACCELERATION AT SHORT PERIODS (0.2 SECOND), Sds = 1.0 G DESIGN SPECTRAL RESPONSE ACCELERATION AT 1-SECOND PERIOD, Sd1 = 0.6 G
NOTES
COMPONENT RESPONSE MODIFICATION AND AMPLIFICATION FACTORS SHALL BE DETERMINED IN ACCORDANCE WITH ASCE 7-16, TABLE 13.6-1.
NR = NOT REQUIRED
N/A = NOT APPLICABLE
ALL MECHANICAL AND PLUMBING DISCRETE COMPONENTS AND DISTRIBUTED SYSTEMS SHALL BE POSITIVELY ATTACHED TO STRUCTURE.
HORIZONTALY DUCTING TO BE BRACED LATERALLY AND LONGITUDINALLY A MINIMUM OF EVERY 40', REGARDLESS OF SEISMIC REQUIREMENTS.
VERTICAL DUCTING AND PIPING TO BE BRACED LATERALLY A MINIMUM OF EVERY 15', REGARDLESS OF SEISMIC REQUIREMENTS.
DESIGN WIND SPEED IS 110 MPH AT 3 SECOND GUSTS.
HVAC CONDENSING UNIT SCHEDULE
TAG LOCATION SERVES MANUFACTURER/ MODEL
COND FAN(S) COMPRESS. NOM.
CAPACITY
(TONS)
COOLING CAPACITY
REFRIG.
LIQUID
CONN.
(IN)
SUCTION
CONN.
(IN)
UNIT POWER
REQUIREMENTS
UNIT
WT.
(LBS)
REMARKS# HP FLA TOTAL
MBh
AAT
(°F)
EER/
SEER# RLA VOLTS Ø MCA MOCP
CU-1 GRADE FCU-1 AAON/CFA-004-A-A-2-DA0EH 1 1/3 2.8 1 16.1 4 43.5 80 12.2/
14.0 R-410A 5/8 1 1/8 208 3 3 15 527 1,2,3,4,5,6
CU-2 GRADE FCU-2 AAON/CFA-004-A-A-2-DA0EH 1 1/3 2.8 1 16.1 4 43.5 80 12.2/
14.0 R-410A 5/8 1 1/8 208 3 3 15 527 1,2,3,4,5,6
CU-1 ALT-1 GRADE CU-1 ALT-1 FRASER-JOHNSTON/AL19B6021S 1 1/3 2.8 1 22.9 5 58.3 80 -/19 R-410A 3/8 1 1/8 208 1 31.4 50 295 1,2,3,4,7,8
CU-2 ALT-1 GRADE CU-2 ALT-1 FRASER-JOHNSTON/AL19B6021S 1 1/3 2.8 1 22.9 5 58.3 80 -/19 R-410A 3/8 1 1/8 208 1 31.4 50 295 1,2,3,4,7,8
REMARKS:
1. UNIT IS PAIRED WITH A REMOTE FAN COIL UNIT.
2. UNIT TO HAVE A SINGLE POINT POWER NON-FUSED DISCONNECT OF 100 AMPS.
3. PROVIDE WITH SUCTION PRESSURE TRANSDUCER ON EACH REFRIGERATION SYSTEM
4. PROVIDE WITH 115VAC CONVENIENCE OUTLET.
5. PROVIDE WITH POLYMER E-COATED CONDENSER COIL.
6.PROVIDE WITH VARIABLE CAPACITY SCROLL COMPRESSOR CAPABLE OF 10-100% MODULATING CAPACITY.
7.UNIT TO HAVE 2-STAGE COMPRESSOR.
8. ADAPTER FITTING MUST BE FIELD INSTALLED FOR SUCTION CONNECTION.
REV DATE DESCRIPTION
PROJ. NO.
DRAWN
CHECKED
DATE
SHEET OF
COFFMAN ENGINEERS INC.C
APHIS - REPLACE
VENTILATION UNITS,
ANIMAL RESEARCH
BUILDING
210 AMAUULU RD.
HAWAII COUNTY
HILO, HI
232507
03/28/24
SHEET TITLE:
SHEET NO:
A
B
C
D
A
B
C
D
1 2 3 4 5
2 3 4 5
CONTRACT # 12639521D0051
A 12/8/23 35% DD
B 01/19/24 95% CD
www.coffman.com ph 509.328.2994
221 N. Wall Street
Spokane, WA 99201 Suite 500
C 03/28/24 100% CD
MECHANICAL
SCHEDULES AND
DIAGRAMS
M-002
RKC
TAH
DI
DI
AIPIPTAI
AI
DI
DO
CONDENSATE
ALARM
UNIT ALARM
SPEED
START/STOP
OUTSIDE AIR
TEMP
ANALOG DP
INDICATOR
OUTSIDE AIR
900 CFM
SUPPLY AIR
SCALE:1 AIRFLOW AND CONTROL DIAGRAM - ANIMAL ROOMS 6 & 7
NTS
FT
AIOUTSIDE
AIRFLOW
FCU-1
VFD-2
DI ALARM
BACNET
DI
DI
AIPIPT
AI
DI
DO
CONDENSATE
ALARM
UNIT ALARM
RL RS
SPEED
START/STOP
ANALOG DP
INDICATOR
SUPPLY AIR
FCU-2
VFD-4
DI ALARM
BACNET
PT
PT
150 CFM
150 CFM
+0.0"-0.02"
+0.0"-0.02"
CORRIDOR
ROOM
DIFFERENTIAL
PRESSURE
ROOM
DIFFERENTIAL
PRESSURE
EF-1
AO
DI
SPEED
START/STOPDO
ALARM
VFD-3
BACNET
EF-2
AO
DI
SPEED
START/STOPDO
ALARM
VFD-1
BACNET
ROOF
ROOF
FT AI
ROOM
TEMP
ROOM AIRFLOW
ADJUSTMENT
CFM
CFM
1,050
CFM
CFM
CFM
1,050
CFM
ROOM
TEMP
ROOM AIRFLOW
ADJUSTMENT
WALL MOUNTED
TOUCH SCREEN
WALL MOUNTED
TOUCH SCREEN
RM 7
RM 6
M
AO
OUTSIDE AIR
DAMPER
M AO
EXHAUST AIR
DAMPER
EXHAUST
AIRFLOW
FT AI
M AO EXHAUST AIR
DAMPER
NOTES:
1. AIRFLOW SENSOR TO BE EBTRON GTX116E-P+.
2. EXHAUST GRILLS, EXHAUST FILTERS, AND EXHAUST
DUCT ARE EXISTING TO REMAIN. ALL OTHER
EQUIPMENT, DUCT, AND CONTROLS ARE NEW.
3. VFD PROVIDED INTEGRAL TO UNIT BY
MANUFACTURER.
MERV 13 FILTER
SUPPLY AIR
TEMPERATURE
AI
OUTSIDE AIR
TEMP
OUTSIDE AIR
900 CFM
FT
AIOUTSIDE
AIRFLOW
M
AO
OUTSIDE AIR
DAMPER
SUPPLY AIR
TEMPERATURE
MERV 13 FILTER
ROOM
HUMIDITY
ROOM
HUMIDITY MERV 8 FILTER
EXHAUST
AIRFLOW
MERV 8 FILTER
MODES OF OPERATION:
FULL FLOW: MANUALLY SELECTED ON WALL MOUNTED TOUCH SCREEN DEVICE.
OCCUPIED (ANIMALS):WHEN ANIMALS ARE PRESENT IN THE ROOM. MANUALLY SELECTED ON WALL MOUNTED
TOUCH SCREEN DEVICE.
OCCUPIED (PEOPLE ONLY): WHEN ONLY PEOPLE ARE PRESENT IN THE ROOM. SET FOR MONDAY THROUGH
FRIDAY 7:00 AM TO 5:00 PM (ADJ).
OCCUPIED (ANIMALS & PEOPLE): WHEN ANIMALS AND PEOPLE ARE PRESENT IN THE ROOM. SET FOR 24/7
CONDITIONING.
UNOCUPIED: ALL OTHER TIMES.
AIRFLOW SETPOINTS FOR ANIMAL ROOM 6:
FULL FLOW - FCU-1=900 CFM, EF-1=1050CFM
OCCUPIED (ANIMALS) - FCU-1=600 CFM, EF-1=750 CFM
OCCUPIED (PEOPLE ONLY) - FCU-1=480 CFM, EF-1=630 CFM
UNOCCUPIED - FCU-1= 400 CFM, EF-1= 550 CFM
AIRFLOW SETPOINTS FOR ANIMAL ROOM 7:
FULL FLOW - FCU-2=900 CFM, EF-2=1050CFM
OCCUPIED (ANIMALS & PEOPLE) - FCU-2=600 CFM, EF-2=750 CFM
UNOCCUPIED - FCU-2= 400 CFM, EF-2= 550 CFM
ALARMS REPORTED:
1. DIRTY FAN COIL UNIT FILTER WHEN DIFFERENTIAL PRESSURE EXCEEDS 1" WC.
2. SUPPLY FAN FAILURE.
3. CONDENSATE BUILDUP.
DO
TXV
REFRIGERANT
PIPING
AI
10-100%
COOLING
CU-1
DO
TXV
REFRIGERANT
PIPING
AI
10-100%
COOLING
CU-2
RL RS
SEQUENCE OF OPERATIONS
ANIMAL ROOMS SYSTEM DESCRIPTION:
EACH ANIMAL ROOMS HVAC SYSTEM INCLUDES A FAN COIL UNIT WITH A CONDENSING UNIT AND AN EXHAUST FAN. THE FAN COIL UNIT PROVIDES FILTERED AND TEMPERED AIR FOR COOLING AND VENTILATION. COOLING IS SUPPLIED BY THE DX COIL AND ASSOCIATED CONDENSING UNIT. THE FAN COIL UNIT PROVIDES 100% OUTSIDE AIR AND WILL BE ON AT ALL OCCUPIED HOURS. THE EXHAUST FAN FOR EACH ANIMAL ROOM WILL EXHAUST 150 MORE CFM THAN WHAT IS SUPPLIED BY THE FAN COIL UNIT TO KEEP THE ROOM NEGATIVE TO THE ADJACENT
CORRIDOR.
ANIMAL ROOMS - HVAC SYSTEM CONTROL:
1. EACH FAN COIL UNIT AND EXHAUST FAN WILL OPERATE TO PROVIDE COOLING AND VENTILATION AT ALL
OCCUPIED HOURS.
2. EACH FAN COIL UNIT IS A CONSTANT VOLUME SYSTEM AND WILL PROVIDE THE AIRFLOW REQUIRED
BASED ON THE MODE OF OCCUPATION AS SENSED BY THE RESPECTIVE EBTRON AIRFLOW
MEASUREMENT DEVICE THE CFM WILL BE AUTOMATICALLY ADJUSTED BASED ON THE EXHAUST FANS CFM AND EACH FAN COIL UNIT WILL PROVIDE 150 CFM LESS THAN THE EXHAUST FAN IS EXHAUSTING.
3. EACH ANIMAL ROOM COOLING TEMPERATURE SETPOINT IS 75°F (ADJ) AS SENSED BY THE THERMOSTAT IN THE ROOM AND IS PROVIDED AS AN INPUT TO THE ASSOCIATED WALL MOUNT TOUCH SCREEN DEVICE.
EACH FAN COIL UNIT SUPPLY AIR TEMPERATURE (SAT) SETPOINT IS 60°F (ADJ). EACH CONDENSING UNITS COMPRESSOR WILL MODULATE BETWEEN 10% AND 100% CAPACITY TO ACHIEVE THE SAT SETPOINT.
4. EACH EXHAUST FAN IS A CONSTANT VOLUME SYSTEM AND WILL EXHAUST 150 CFM MORE THAN THE ASSOCIATED FAN COIL UNIT IS SUPPLYING AS SENSED BY THE EBTRON AIRFLOW MEASUREMENT DEVICE UPSTREAM OF THE EXHAUST FAN. EACH EXHAUST FAN ALSO HAS AN EXHAUST AIR DAMPER THAT WILL BE INTERLOCKED WITH THE EXHAUST FAN. WHEN THE EXHAUST FAN IS ON THE DAMPER WILL BE OPEN AND
WHEN THE EXHAUST FAN IS OFF THE DAMPER WILL BE CLOSED.
T T
STORAGE
ANIMAL ROOM
ANIMAL ROOM
BAIT FORMULATION
LABORATORY
OFFICE/
RECEPTION
SECURITY
CLOSET--
FREEZERS
MEN
WOMEN
1 1
6 6
7 7
REV DATE DESCRIPTION
PROJ. NO.
DRAWN
CHECKED
DATE
SHEET OF
COFFMAN ENGINEERS INC.C
APHIS - REPLACE
VENTILATION UNITS,
ANIMAL RESEARCH
BUILDING
210 AMAUULU RD.
HAWAII COUNTY
HILO, HI
232507
03/28/24
SHEET TITLE:
SHEET NO:
A
B
C
D
A
B
C
D
1 2 3 4 5
2 3 4 5
CONTRACT # 12639521D0051
A 12/8/23 35% DD
B 01/19/24 95% CD
www.coffman.com ph 509.328.2994
221 N. Wall Street
Spokane, WA 99201 Suite 500
C 03/28/24 100% CD
MECHANICAL FLOOR
PLAN DEMOLITION
MD-201
RKC
TAH
GENERAL NOTES
KEY NOTES
1. DEMO EXISTING FAN COIL UNIT AND EXISTING REFRIGERANT PIPING.
2. DEMO EXISTING CONDENSING UNIT.
3. DEMO EXISTING EXHAUST FANS .
4. CLEAN EXISTING EXHAUST DUCT.
5. EXISTING OUTDOOR SINK TO REMAIN.
6. DEMO EXISTING OUTSIDE AIR INTAKE HOOD AND DUCTWORK.
7. DEMO EXISTING THERMOSTAT AND FAN SPEED CONTROL DIAL.
8. DEMO EXISTING FILTER-BACK EXHAUST GRILLE AND PREPARE FOR
DIRECT REPLACEMENT.
A. THESE DRAWINGS HAVE BEEN PREPARED USING OWNER PROVIDED
DRAWINGS DATED 8/23/82 AND THROUGH FIELD OBSERVATIONS. VERIFY
EXISTING CONDITIONS AS THEY APPLY TO THIS PROJECT AND INCLUDE
IN BID A SUFFICIENT ALLOWANCE TO COVER ANY DISCREPANCY
BETWEEN THE DRAWINGS AND THE ACTUAL CONDITIONS AS THEY
CURRENTLY EXIST.
B. EXISTING WORK IS SHOWN WITH LIGHT LINES AND DEMO WORK IS
SHOWN WITH BOLD BROKEN LINES, TYP.
C. CONTRACTOR SHALL BE RESPONSIBLE FOR DISPOSAL OF ALL
EQUIPMENT THE OWNER DOES NOT WISH TO RETAIN FOR FUTURE USE.
D. CONTRACTOR SHALL COORDINATE ANY SHUT DOWN OF SYSTEMS WITH
OWNER.
X
SCALE:
PROJECT
NORTH
3/16"=1'-0"
MECHANICAL FLOOR PLAN - DEMOLITION
SCALE:
PROJECT
NORTH
3/16"=1'-0"
MECHANICAL ROOF PLAN - DEMOLITION
STORAGE
ANIMAL ROOM
ANIMAL ROOM
BAIT FORMULATION
LABORATORY
OFFICE/
RECEPTION
SECURITY
CLOSET--
FREEZERS
MEN
WOMEN
(N ) C
U-
(N ) C
U-
(N) FCU-2 (N) FCU-1
(N) EF-1
(N) EF-2
(E) HOUSEKEEPING PAD
1 1
22x14
(E) OUTDOOR SINK
22x14
3/4" D
1S
1S
1S
1S
12x14
26x10
OUTSIDE AIR INTAKE HOOD
SEE DETAIL 2/M-501
OUTSIDE AIR INTAKE HOOD
SEE DETAIL 2/M-501
INSTALLATION OF FCU-2 WILL
REQUIRE TO BE MOVED THROUGH
DOOR
T T
RL/RS
RL/RS
VFD-1
VFD-3
UNIT ACCESS TYP
12x14
26x10
1E
1E
(E) HOOD
(E) BCS
(E) FREEZER
REV DATE DESCRIPTION
PROJ. NO.
DRAWN
CHECKED
DATE
SHEET OF
COFFMAN ENGINEERS INC.C
APHIS - REPLACE
VENTILATION UNITS,
ANIMAL RESEARCH
BUILDING
210 AMAUULU RD.
HAWAII COUNTY
HILO, HI
232507
03/28/24
SHEET TITLE:
SHEET NO:
A
B
C
D
A
B
C
D
1 2 3 4 5
2 3 4 5
CONTRACT # 12639521D0051
A 12/8/23 35% DD
B 01/19/24 95% CD
www.coffman.com ph 509.328.2994
221 N. Wall Street
Spokane, WA 99201 Suite 500
C 03/28/24 100% CD
MECHANICAL FLOOR
PLAN
M-201
RKC
TAH
GENERAL NOTES
KEY NOTES
1. ROUTE CONDENSATE LINES FROM FCU-1 AND FCU-2 TO OUTDOOR SINK
TAILPIECE. SEE DETAIL 4/M-502
2. EXISTING EXHAUST DUCT TO BE CLEANED. REPLACE GRILLE MOUNTED
FILTER WITH NEW MERV-8 FILTER.
3. SLOPE OUTSIDE AIR DUCT AT 1/8" PER 1'-0" DOWN TOWARDS INTAKE
HOOD.
4. NOT USED.
5. AIRFLOW MEASUREMENT DEVICE.
6. EBTRON AIRFLOW SENSOR TO BE INSTALLED IN ATTIC SPACE IN EXISTING
DUCTWORK, SEE DETAIL C/M-202.
7. NEW TOUCH SCREEN CONTROLLER LOCATED AT LOCATION SHOWN.
8. SEE DETAIL C/M-202.
9. ALTERNATE FAN COIL UNITS AND CONDENSING UNITS ARE NOT SHOWN
ON PLAN FOR CLARITY.
10. ALTERNATE FAN COIL UNITS ARE NOT TO EXCEED 58" IN LENGTH.
11. ALTERNATE FAN COIL UNITS ARE NOT TO EXCEED 530 LBS. IN WEIGHT.
A. THESE DRAWINGS HAVE BEEN PREPARED USING OWNER PROVIDED
DRAWINGS DATED 8/23/82 AND THROUGH FIELD OBSERVATIONS. VERIFY
EXISTING CONDITIONS AS THEY APPLY TO THIS PROJECT AND INCLUDE
IN BID A SUFFICIENT ALLOWANCE TO COVER ANY DISCREPANCY
BETWEEN THE DRAWINGS AND THE ACTUAL CONDITIONS AS THEY
CURRENTLY EXIST.
B. EXISTING WORK IS SHOWN WITH LIGHT LINES AND NEW WORK IS SHOWN
WITH BOLD LINES, TYP.
C. CONTRACTOR SHALL COORDINATE ROUTING AND SPACE
REQUIREMENTS OF PIPING WITH STRUCTURAL MEMBERS AND ALL
OTHER TRADES INCLUDING HVAC, FIRE PROTECTION, ELECTRICAL, AND
COMMUNICATIONS/DATA. OFFSET PIPING AROUND DUCTWORK AND
OTHER OBSTACLES WHERE REQUIRED.
D. ALL PIPING SHALL BE SLEEVED AND SEALED THROUGH ANY STRUCTURE
OR CONCRETE.
E. CONDENSATE DRAIN PIPING SHALL BE TYPE 'L' OR 'M' COPPER. SLOPE
ALL CONDENSATE DRAIN PIPING AT 1/8" PER FOOT, MIN.
X
SCALE:
PROJECT
NORTH
3/16"=1'-0"
MECHANICAL FLOOR PLAN
SCALE:
PROJECT
NORTH
MECHANICAL ROOF PLAN
3/4" D
RL/RS
RL/RS
12"x10"12"x10" 12"x10" 12"x10"
EBTRON AIRFLOW
SENSOR 14"x22"
SEE DETAIL 2/M-501
BIRDSCREEN
3/4" D
1S
0"
16"x16"
(E) 15"x5"
16"x16"
(E) 15"x5"
EBTRON AIRFLOW
SENSOR
EBTRON AIRFLOW
SENSOR
44 77
(N) CU-1 BEHIND
(E) CEILING
(E) CEILING
REV DATE DESCRIPTION
PROJ. NO.
DRAWN
CHECKED
DATE
SHEET OF
COFFMAN ENGINEERS INC.C
APHIS - REPLACE
VENTILATION UNITS,
ANIMAL RESEARCH
BUILDING
210 AMAUULU RD.
HAWAII COUNTY
HILO, HI
232507
03/28/24
SHEET TITLE:
SHEET NO:
A
B
C
D
A
B
C
D
1 2 3 4 5
2 3 4 5
CONTRACT # 12639521D0051
A 12/8/23 35% DD
B 01/19/24 95% CD
www.coffman.com ph 509.328.2994
221 N. Wall Street
Spokane, WA 99201 Suite 500
C 03/28/24 100% CD
MECHANICAL
SECTIONS
M-202
RKC
TAH
GENERAL NOTES
KEY NOTES
1. SLOPE OUTSIDE AIR DUCT AT 1/8" PER 1'-0" DOWN TOWARDS INTAKE
HOOD.
2. CONNECT INTO TAILPIECE OF EXISTING OUTDOOR SINK. SEE DETAIL
4/M-502.
3. NOT USED.
4. EBTRON FLOW SENSOR TO BE MOUNTED 6" BEFORE TRANSITION,
MINIMUM. SEE DETAIL 7/M-502 FOR INSTALLATION.
5. EBTRON FLOW SENSOR TO BE MOUNTED 21" AFTER ELBOW AND 6"
BEFORE FILTER, MINIMUM. SEE DETAIL 7/M-502 FOR INSTALLATION.
6. VOLUME DAMPER IS INTEGRAL WITH SUPPLY DIFFUSER.
7. ACCESS TO EBTRON FLOW SENSOR IS THROUGH ATTIC.
8. FAN COIL UNITS ARE LOCATED UNDER ROOFING WITH NO CEILING
OBSTRUCTION AND ARE DIRECTLY ACCESSIBLE BY LADDER.
9. REUSE EXISTING DUCT PENETRATIONS.
A. THESE DRAWINGS HAVE BEEN PREPARED USING OWNER PROVIDED
DRAWINGS DATED 8/23/82 AND THROUGH FIELD OBSERVATIONS. VERIFY
EXISTING CONDITIONS AS THEY APPLY TO THIS PROJECT AND INCLUDE
IN BID A SUFFICIENT ALLOWANCE TO COVER ANY DISCREPANCY
BETWEEN THE DRAWINGS AND THE ACTUAL CONDITIONS AS THEY
CURRENTLY EXIST.
B. EXISTING WORK IS SHOWN WITH LIGHT LINES AND NEW WORK IS SHOWN
WITH BOLD LINES, TYP.
C. CONTRACTOR SHALL COORDINATE ROUTING AND SPACE
REQUIREMENTS OF PIPING WITH STRUCTURAL MEMBERS AND ALL
OTHER TRADES INCLUDING HVAC, FIRE PROTECTION, ELECTRICAL, AND
COMMUNICATIONS/DATA. OFFSET PIPING AROUND DUCTWORK AND
OTHER OBSTACLES WHERE REQUIRED.
D. ALL PIPING SHALL BE SLEEVED AND SEALED THROUGH ANY STRUCTURE
OR CONCRETE.
E. CONDENSATE DRAIN PIPING SHALL BE TYPE 'L' OR 'M' COPPER. SLOPE
ALL CONDENSATE DRAIN PIPING AT 1/8" PER FOOT, MIN.
X
SCALE:A SECTION
1/4" = 1'-0" SCALE:B SECTION
1/4" = 1'-0"
SCALE:C SECTION
1/4" = 1'-0"
SCALE:1 LOW PRESSURE DUCT FITTING REQUIREMENTS
NTS
HVAC UNIT
DRAIN PAN
OPEN VENT
2"
2"
MIN.
SIZE SAME AS OUTLET OR 3/4",
WHICHEVER IS LARGER
UNION
ROUTE TO DRAIN AT
1/4" PER FOOT SLOPE,
SEE PLANS FOR
ROUTING
DRAW-THROUGH
(FAN DOWNSTREAM OF COILS)
FORM FLANGE AT END
OF SHEET METAL DUCT.
SET TIGHT AGAINST WALL.
SUPPLY, RETURN, OR
EXHAUST GRILLE
OR
STUD FRAME OPENING
NOT BY MECHANICAL
SHEET METAL DUCT
18 GAUGE SHEET METAL
COLLAR FLANGE TIGHT AGAINST
WALL SURFACE. ATTACH TO
DUCT WITH SHEET METAL
SCREWS OR POP RIVETS
WALLBOARD
PARTITION WALL
SQUARE TO ROUND TRANSITION
SHEET METAL AS SPECIFIED
FOR DUCTWORK.
1"X1/8" BAND IRON
BOLT ON 4" CENTERS
1" FLANGE & HEM
WASHER
SHEET METAL AS SPECIFIED
FOR DUCTWORK.
FLANGED CONNECTION
ON FAN SIDE.
ALTERNATE POSITION OF BOLT
1-1/2" MIN. TO 3" MAX. INSTALLED. 6"
NOMINAL WITH MATERIAL TAUT.
FLEXIBLE MATERIAL AS SPECIFIED DUCT
1-1/2" POCKET
SLIP
END VIEW
NOTES
MA
X
UNISTRUT P1000
LATERAL BRACE
UNISTRUT P1843
HINGE CONNECTOR
TYPICAL EA. END
HANGER RODS WITH STIFFENERS OR HOT DIPPED
GALVANIZED ANGLE IRON SUPPORTS.
HOT DIPPED GALVANIZED ANGLE
IRON CROSS MEMBER.
RIGID BRACE (SHOWN) OR MULTIPLE CABLE
BRACES.
UNISTRUT P1000
UNISTRUT P1000
3"
1'- 0"
AS
IN
DI
CA
TE
D
ON
P
LA
N
AS INDICATED ON PLAN
7/16" Ø HOLES @ 8"CC MAX. FOR
3/8"x3-1/2" LG. BOLTS, NUTS & WASHERS
3"x3"x1/4" ANGLE FRAME
16 GAGE GALV. SHEET METAL
NOTES
1. DUCT JOINTS SHALL BE COATED WITH SEALANT
TYPE S-2 AS MANUFACTURED BY DURO-DYNNE CORP. OR
APPROVED EQUAL
2. DUCTWORK ATTACHED TO ANGLE FRAME SHALL
BE WELDED
3. ALL BOLTS SHALL BE ASTM-307 & HOT DIPPED
GALVANIZED
4. ANGLE IRON FRAMEWORK FOR INTAKE & EXHAUST HOODS
SHALL BE ASTM-A36 & HOT DIPPED GALV.
1" SQ.x 0.148
GALV. SCREEN
BIRD SCREEN
1" INTERMEDIATE WELD
STAGGERED ON ALTERNATE
SIDES OF ANGLE
6" ON CENTER (TYPICAL)
1-1/2"x1-1/2"x1/4"
ANGLE IRON
DUCT
1-1/2"x 1/4" FLAT BAR
BIRD SCREEN
1/4" DIA. SELF
TAPPING SCREWS
CHANGE OF DUCT SIZE
TRANSITION
BRANCH DUCT TAKEOFFS
END TAP
RECTANGULAR
DUCT
DUCT ELBOWS
NOTE: OFFSETS (TO AVOID OBSTRUCTIONS) ARE REQUIRED BUT ARE
NOT NECESSARILY SHOWN ON THE PLANS.
OFFSETS
R=1/2W FOR DUCTS W/ AIR
VELOCITY UNDER 1,500 FPM
R=W FOR DUCTS W/ AIR VELOCITY
OVER 1,500 FPM AND ALL DUCTS
UPSTREAM OF TERMINAL UNITS
.0
.0
D
W
D=1/2W, BUT NOT MORE THAN
12" (1/3W PERMITTED IF AIR
VELOCITY UNDER 3,000 FPM)
A
CONICAL SPIN-IN OR TRANSITION
TO AT LEAST 70% GREATER THAN
AREA OF SMALLER DUCT. SEE MAX
TRANSITION ANGLE.
THE DUCT FITTINGS ABOVE ARE CONSIDERED ACCEPTABLE. THE CONTRACTOR SHALL OBTAIN ENGINEER'S APPROVAL FOR ALTERNATIVE FITTINGS PRIOR TO
FABRICATION. ONLY FITTINGS WITH EQUAL OR LOWER PRESSURE DROP WILL BE CONSIDERED.
A
W
(ONLY PERMITTED FOR AIR
VELOCITY UNDER 1,500 FPM)
A ≤ 15° FOR DUCTS W/ AIR
VELOCITY OVER 1,500 FPM.
R
A
W
R
R=1/2W FOR DUCTS W/ AIR
VELOCITY UNDER 1,500 FPM
R=W FOR DUCTS W/ AIR
VELOCITY OVER 1,500 FPM
AND ALL DUCTS UPSTREAM
OF TERMINAL UNITS
ROUND DUCT RUNOUT
TO SINGLE DIFFUSER
OR GRILLE ONLY
CONICAL SPIN-IN
ROUND OR
RECTANGULAR
12"x12" ACCESS PANEL ON
BOTTOM OF DUCT UPSTREAM OF
TURNING VANES, REQUIRED FOR
RETURN AND EXHAUST DUCTS
TURNING VANES
A ≤ 30° FOR DUCTS W/ AIR
VELOCITY UNDER 1,500 FPM.
45° OR 90° RADIUS
ELBOWS
A ≤ 15° FOR DUCTS W/ AIR
VELOCITY OVER 1,500 FPM.
A ≤ 30° FOR DUCTS W/ AIR
VELOCITY UNDER 1,500 FPM.
3/16" 3/16"
3/16"
3/16" STAGGERED
EACH END
SCALE:2 HOOD DETAIL
NTS
SCALE:3 GRILLE IN WALL INSTALLATION
NTS
SCALE:4 OUTDOOR DUCT DETAIL
NTS
SCALE:5 SUSPENDED DUCTWORK
NTS SCALE:7 RECTANGULAR FLEXIBLE CONNECTION
NTSSCALE:6 COND. TRAP AND DRAIN - FAN COILS
NTS
COPE ANGLE LEG
EACH END
12" 12"
DUCT PER PLAN
PITCH TOP OF JACKETING
TO SHED WATER
FLASH AND SEAL JOINTS,
SEAMS, AND EDGES
WATER TIGHT
2" RIGID INSULATION,
TAPE ALL SEAMS
ALUMINUM JACKET
STAGGERED12"
12"
NOTE:
ARRANGEMENT SHOWN IS SCHEMATIC AND NOT SPECIFIC TO ANY
MANUFACTURER. CONTRACTOR REQUIRED TO ADAPT TO EQUIPMENT
SPECIFIC CONNECTION.
REV DATE DESCRIPTION
PROJ. NO.
DRAWN
CHECKED
DATE
SHEET OF
COFFMAN ENGINEERS INC.C
APHIS - REPLACE
VENTILATION UNITS,
ANIMAL RESEARCH
BUILDING
210 AMAUULU RD.
HAWAII COUNTY
HILO, HI
232507
03/28/24
SHEET TITLE:
SHEET NO:
A
B
C
D
A
B
C
D
1 2 3 4 5
2 3 4 5
CONTRACT # 12639521D0051
A 12/8/23 35% DD
B 01/19/24 95% CD
www.coffman.com ph 509.328.2994
221 N. Wall Street
Spokane, WA 99201 Suite 500
C 03/28/24 100% CD
MECHANICAL
DETAILS
M-501
RKC
TAH
1 1 /2"
V
(E) STUDOR VENT
FLEXIBLE DUCT
CONNECTOR, TYP.
DUCT
SUPPLY FAN COIL
LIQUID
SUCTION
SEE FLOOR
PLANS FOR
ROUTING
DOUBLE DEFLECTION SPRING
NEOPRENE HANGER, MASON MODEL
30N, OR APPROVED EQUAL
FAN BASE
EXHAUST FAN
3/4" CONDENSATE
FROM FAN COIL
CO
P-TRAP
2" W
CO
3/4" D
1/8" / 1'-0"
SI
ZE
A S
IN
DI
CA
TE
D
ON
P
LA
NS
EXISTING GIRT
SLOPE OUTSIDE AIR DUCT AT
1/8" PER 1'-0" DOWN TOWARDS
INTAKE HOOD
NOTES:
CONTRACTOR TO SUBMIT
HOOD/DUCT SUPPORT STRUCTURE
FOR REVIEW.
NEW HOOD SUPPORT FRAMING TO
CONNECT TO EXISTING WIND GIRTS AND
ROOF FRAMING.
FLASHING
FLASHING
CORRUGATED METAL SIDING
CAULK ALL AROUND
SCALE:3 EXHAUST FAN DETAIL - UPBLAST
NTS
SCALE:4 COND. DRAIN CONNECTION
NTS SCALE:5 HORIZONTAL FAN COIL INSTALLATION
NTS
SCALE:2 TYPICAL EXTERIOR WALL DUCT CONNECTION DETAIL
NTSSCALE:1 NOT USED
NTS
SCALE:6 CONDENSING UNIT HOUSEKEEPING PAD
NTS
#4 AT 12" ON CENTER EACH
WAY, CENTERED IN SLAB
GRADE
1" CHAMFER
6" 6" a b c
(x 4)
(x 4)
Alignment Notches
Alignment Notches
A
SCALE:7 EBTRON FLOW SENSOR INSTALLATION
NTS
B
SCALE:8 EXHAUST DUCT IN ATTIC
NTS
DEMO EXHAUST DUCT FROM
TRANSITION UP THROUGH THE
EXHAUST FAN AS SHOWN.
SECURE UNIT TO
FIELD PROVIDED
BEAMS
OUTSIDE
AIR DUCT
NOTES:
· CONTRACTOR TO CONFIRM OUTDOOR PURLINS
ARE SAME DEPTH AS INTERIOR PURLINS.
· REPLACE ANGLE IRON SPANNING BETWEEN
PURLINS WHERE REQUIRED FOR FAN COIL UNIT
HANGERS WITH 3x3x1/4" ANGLE IRON.
DUCT TRANSITION AS
REQUIRED
ANCHOR FAN TO CURB WITH (3)
#12d EACH SIDE, TYPICAL, AND
SEAL ALL AROUND
NOTES:
· CONTRACTOR TO FIELD VERIFY CONSTRUCTION OF
EXISTING ROOF AND CURB TO DETERMINE SUITABILITY
FOR INSTALLATION OF NEW EXHAUST FAN. SUBMIT A
DRAWING WITH DETAILS SHOWING PROPOSED METHOD
FOR ATTACHING NEW EXHAUST FAN TO EXISTING CURB.
· CONTRACTOR TO CONFIRM NEW EXHAUST FANS ARE
WITHIN 5% WEIGHT OF EXISTING EXHAUST FANS AND
NOTIFY ENGINEER IF THAT IS NOT THE CASE.
REV DATE DESCRIPTION
PROJ. NO.
DRAWN
CHECKED
DATE
SHEET OF
COFFMAN ENGINEERS INC.C
APHIS - REPLACE
VENTILATION UNITS,
ANIMAL RESEARCH
BUILDING
210 AMAUULU RD.
HAWAII COUNTY
HILO, HI
232507
03/28/24
SHEET TITLE:
SHEET NO:
A
B
C
D
A
B
C
D
1 2 3 4 5
2 3 4 5
CONTRACT # 12639521D0051
A 12/8/23 35% DD
B 01/19/24 95% CD
www.coffman.com ph 509.328.2994
221 N. Wall Street
Spokane, WA 99201 Suite 500
C 03/28/24 100% CD
MECHANICAL
DETAILS
M-502
RKC
TAH
X:#
SHEET NOTE
CONDUIT, VERTICAL TRANSITION
CONDUIT CAPPED
HOME RUN
X = PANELBOARD
# = BRANCH CIRCUIT NUMBER(S)
JUNCTION BOX
SURFACE RACEWAY (DEVICES SHOWN)
FLUSH FLOOR BOX (DEVICES SHOWN)
POWER POLE
VAULT
TRANSFORMER
CURRENT TRANSFORMER
NORMALLY OPEN CONTACTOR
NORMALLY CLOSED CONTACTOR
CIRCUIT BREAKER
NUMBER INDICATES TRIP AND POLES
DISCONNECT SWITCH
FUSE WITH RATING
FUSED DISCONNECT WITH RATING
MOTOR THERMAL OVERLOADS
GROUND CONNECTION
AUTOMATIC TRANSFER SWITCH
POWER METER
RELAY
VARIABLE FREQUENCY DRIVE
FEEDER CALLOUT
LUMINAIRE:
ID = FIXTURE TYPE
x = SWITCH ASSOCIATION
2'x4' RECESSED LUMINAIRE
2'x4' RECESSED LUMINAIRE
1'x4' RECESSED LUMINAIRE
1'X4' SURFACE MTD LUMINAIRE
PENDANT-MTD/SUSPENDED LUMINAIRE
WALL-MTD LUMINAIRE
STRIP FLUORESCENT LUMINAIRE
CEILING-MTD DIRECTIONAL LUMINAIRE
CEILING-MTD LUMINAIRE
TRACK LIGHT WITH NUMBER OF HEADS SHOWN
WALL-MTD LUMINAIRE
EXIT SIGN WITH ARROW INDICATING DIRECTION OF EGRESS
WALL-MTD EXIT SIGN
CEILING-MTD EXIT SIGN
BATTERY POWERED EMERGENCY LIGHT
SINGLE-POLE WALL SWITCH
PHOTOCELL CONTROL
OCCUPANCY SENSOR
LIGHTING CONTROL PANEL
WALL SWITCH:
X = AS FOLLOWS:
3 - THREE-WAY
4 - FOUR-WAY
D - DIMMER
K - KEY-OPERATED
LV/2B - LOW-VOLTAGE 2 BUTTON
LV/4B - LOW-VOLTAGE 4 BUTTON
LV/D - LOW-VOLTAGE DIMMER
LV/2D - LOW-VOLTAGE OCCUPANCY DIMMING
LV-O/D - LOW VOLTAGE OCCUPANCY DIMMING
LV-OS - LOW-VOLTAGE OCCUPANCY SENSING
VS - VACANCY SENSING
M - MOTOR STARTER WITH OVERLOADS
MC - MOMENTARY CONTACT
O - OCCUPANCY SENSOR
P - PILOT LIGHT
WP- WEATHERPROOF
a - LOWER-CASE INDICATES SWITCHING CNTRL
MOTION DETECTOR
RECEPTACLE OUTLET:
X = AS FOLLOWS:
A - ABOVE COUNTER, REFER TO ARCHITECTURAL
C - CLOCK HANGER
EP - EXPLOSION PROOF
G - GROUND FAULT CIRCUIT INTERRUPT
S - SAFETY TYPE
T - TIMER CONTROLLED
WP- WEATHERPROOF
MW- MICROWAVE, REFER TO ARCHITECTURAL
DUPLEX RECEPTACLE, 125V, 20A
DOUBLE-DUPLEX RECEPT, 125V, 20A
SWITCHED DUPLEX RECEPTACLE, 125V, 20A
SWITCHED DOUBLE-DUPLEX RECEPT, 125V, 20A
CEILING-MTD DUPLEX RECEPTACLE, 125V, 20A
CEILING-MTD DOUBLE-DUPLEX RECEPTACLE, 125V, 20A
SPECIAL PURPOSE RECEPTACLE
X = TYPE
MOTOR CONNECTION
EQUIPMENT CONNECTION
DISCONNECT SWITCH
FLUSH MOUNTED PANELBOARD
SURFACE MOUNTED PANELBOARD
480V PANELBOARD
208V OR 240V PANELBOARD
TRANSFORMER
RELAY
MECHANICAL EQUIPMENT CALLOUT
DATA/TEL OUTLET, 2-PORTS
WIRELESS ACCESS POINT
DOOR CONTACT
CARD READER
KEYPAD
CCTV SECURITY VIDEO CAMERA
SPEAKER
VR- VANDAL RESISTANT
WALL-MOUNTED SPEAKER
INTERCOM AUDIO MUSIC SOURCE
CLOCK
PUSH BUTTON
SMOKE DETECTOR
HEAT DETECTOR
FIRE ALARM MANUAL PULL STATION
FIRE ALARM HORN STROBE - WALL MOUNTED
FIRE ALARM HORN STROBE - CEILING MOUNTED
FIRE ALARM ANNUNCIATOR PANEL
FIRE ALARM CONTROL PANEL
J
V
VFD
30A/3P
30A/3P
30A
30A
PC
ID x
SYMBOLS LEGEND
SYMBOL DESCRIPTION
SYMBOLS LEGEND
SYMBOL DESCRIPTION
MD
X
M
X
T
X
R
S
S
CR
C
K
I
OR
CAM
X
F
SHEET INDEX
GENERAL NOTES
1. MOUNTING HEIGHTS OF DUPLEX RECEPTACLES AND OTHER OUTLETS SHALL BE 16" TO BOTTOM OF
BOX, UNLESS OTHERWISE NOTED.
2. CATALOG NUMBERS USED SHALL BE AS NOTED OR APPROVED EQUALS.
3. CONTRACTOR SHALL COORDINATE WORK WITH OTHER TRADES.
4. CONTRACTOR SHALL PROVIDE ALL WORK AND MATERIAL FOR COMPLETE WIRING SYSTEMS AS SHOWN
OR SPECIFIED.
5. INSTALLATION SHALL COMPLY WITH NEC 2020 AND LOCAL CODES.
6. CONTRACTOR TO REFER TO MANUFACTURES DOCUMENTS FOR ADDITIONAL DATA PRIOR TO STARTING
ROUGH-IN.
7. CONTRACTOR TO PROVIDE ALL RECEPTACLES, CORDS, CORD CAPS, SWITCHES AND WIRING UNLESS
OTHERWISE NOTED.
XXXX
FAAP
FACP
OS
REV DATE DESCRIPTION
PROJ. NO.
DRAWN
CHECKED
DATE
SHEET OF
COFFMAN ENGINEERS INC.C
APHIS - REPLACE
VENTILATION UNITS,
ANIMAL RESEARCH
BUILDING
210 AMAUULU RD.
HAWAII COUNTY
HILO, HI
232507
12/08/23
SHEET TITLE:
SHEET NO:
A
B
C
D
A
B
C
D
1 2 3 4 5
2 3 4 5
CONTRACT # ______________
A 12/8/23 35% DD
B 01/19/24 95% CD
www.coffman.com ph 509.328.2994
221 N. Wall Street
Spokane, WA 99201 Suite 500
C 02/23/24 100% CD
LEGENDS,
ABBREVIATIONS &
SHEET INDEX
E-001
RGS
CLM
STORAGE
ANIMAL ROOM
ANIMAL ROOM
BAIT FORMULATION
LABORATORY
OFFICE/
RECEPTION
SECURITY
CLOSET--
FREEZERS
MEN
WOMEN
PANEL 1 (ON
ATS/GENERATOR)
ATS COMM BOX
PANEL 2
(E) GENERATOR
LOCATED ON ROOF
LOCATED ON ROOF
METERS
REV DATE DESCRIPTION
PROJ. NO.
DRAWN
CHECKED
DATE
SHEET OF
COFFMAN ENGINEERS INC.C
APHIS - REPLACE
VENTILATION UNITS,
ANIMAL RESEARCH
BUILDING
210 AMAUULU RD.
HAWAII COUNTY
HILO, HI
232507
03/28/24
SHEET TITLE:
SHEET NO:
A
B
C
D
A
B
C
D
1 2 3 4 5
2 3 4 5
CONTRACT # 12639521D0051
A 12/8/23 35% DD
B 01/19/24 95% CD
www.coffman.com ph 509.328.2994
221 N. Wall Street
Spokane, WA 99201 Suite 500
C 03/28/24 100% CD
ELECTRICAL FLOOR
PLAN
E-101
RGS
CLM
GENERAL NOTES
KEY NOTES
1. DISCONNECT CIRCUIT AND RE-CONNECT TO NEW UNIT.
2. DISCONNECT CIRCUIT AND REMOVE BACK TO PANEL.
A. NOT USED
X
SCALE:
PROJECT
NORTH
ELECTRICAL FLOOR PLAN
PANEL 2
100A 208V
4W
PANEL 1
250A 208V
4W
GENERATOR
UTILITY
TRANSFORMER
ATS
208/120V 3PH
ONE-LINE DIAGRAM
M
REV DATE DESCRIPTION
PROJ. NO.
DRAWN
CHECKED
DATE
SHEET OF
COFFMAN ENGINEERS INC.C
APHIS - REPLACE
VENTILATION UNITS,
ANIMAL RESEARCH
BUILDING
210 AMAUULU RD.
HAWAII COUNTY
HILO, HI
232507
03/28/24
SHEET TITLE:
SHEET NO:
A
B
C
D
A
B
C
D
1 2 3 4 5
2 3 4 5
CONTRACT # 12639521D0051
A 12/8/23 35% DD
B 01/19/24 95% CD
www.coffman.com ph 509.328.2994
221 N. Wall Street
Spokane, WA 99201 Suite 500
C 03/28/24 100% CD
ONE-LINE AND
SCHEDULES
E-601
RGS
CLM
GENERAL NOTES
KEY NOTES
1. NOT USED
A. NOT USED
X
PROJECT: 232507 APHIS REPLACE HVAC FOR ANIMAL ROOMS PANEL: PANEL 1
Location: Feed-Thru to: Date: 3/29/2024
Ckt Description Phase Amp Poles Notes Ckt Totals Specifications
1 EF-1, EF-2 AND DAMPERS (ROOF) A 20 3 1 Voltage (L-L): 208 3 - B - - Phase/Wire: 3PH / 4W 5 - C - - Bus Current Rating (Amps): 250 7 AC/ROOM NO.7 A 20 1 Bus Material: Cu/Al 9 RECEPTACLE/AC/ROOM NO.1 B 20 2 Short Circuit Current Rating (Amps) 11 - C - - Main Type: BRKR 13 RECEPTACLE/AC/ROOM NO.2 A 20 2 Main Rating: 250 15 - B - - Neutral Type: FULL 17 RECEPTACLE/AC/ROOM NO.3 C 20 2 Mounting/Encl.: SURFACE NEMA1 19 - A - - 2020 NEC Sections Used in Demand Calculations 21 RECEPTACLE/ROOM 6 B 20 2 Factor # NEC Reference Notes
23 - C - - 1 TBL 220.44
Receptacles ND 1st 10k @100%, Remainder @50%25 RECEPTACLE/ROOM 6 A 20 1
27 RECEPTACLE/ROOM 6 B 20 1 2 TBL 220.42
Apartments General Lighting
1st 20k@50%, 20-100k @40%, >100k @30%29 SPARE C 20 2
31 - A - -
33 FREEZER 9/14 B 20 1 3 430.24
Motors Largest @125% Remainder @100%35 SPACE C
37 EF RM-7, EF RM-6 A 20 1 4 210.19(A)1 Cont Loads 125% 39 GEN BATTER CHARGER B 20 1 5 Non-Cont Loads 100% 41 SPACE C 6 220.51 Heating 100%
Feeder Load Breakdown Conn(KVA) Dmd Fact 2 WATER A 30 2 Non-Dwelling Receptacles 0.00 0.00 4 HEATER B - - Dwelling General Illumination 0.00 0.00 6 SPACE (HIGH LEG) C SPACE - Non-Continuous Lighting 0.00 1.00 8 RECEPTACLE/AC/ROOM 5 A 20 1 Continuous Lighting 0.00 1.25
10 CU-1, CU-2 (GRADE) B 30 3 Exterior Lighting 0.00 1.25 12 - C - - Kitchen Appliances 0.00 1.00 14 - A - - Motors 0.00 1.00 16 WORKSHOP B 20 1 Largest Motor (per phase) 0.00 0.25 18 FCU-1, FCU-2 (STORAGE) C 20 3 Fixed Heating 0.00 1.00 20 - A - - Fixed Cooling 0.00 1.00 22 - B - - Non-Diversity Loads 0.00 1.00 24 SPACE C Other 0.00 1.00
26 RECEPTACLE/ROOM 3 A 20 2
28 RECEPTACLE/ROOM 3 B - -
30 INTAKE FAN C 20 2 Connected Feeder Load Summary
32 - A - -
CONN KVA CONN AMPS NEC
KVA
NEC
AMPS34 EXHAUST FAN B 20 2
36 - C - - PHASE A:
38 SPARE A 20 1 PHASE B:
40 SPARE B 20 1 PHASE C:
42 SPACE C TOTAL:
Notes: 1. PROVIDE NEUTRAL WIRE IN CONDUIT FOR DAMPER POWER
Panel Loading: ACCEPTABLE
PROJECT: 232507 APHIS REPLACE HVAC FOR ANIMAL ROOMS PANEL: PANEL 2
Location: Feed-Thru to: Date: 3/29/2024
Ckt Description Phase Amp Poles Notes Ckt Totals Specifications
1 EF (FUME HOOD) A 20 1 Voltage (L-L): 208 3 RECEPTACLE/ROOM #3 B 20 1 Phase/Wire: 3PH / 4W 5 SPARE C 20 1 Bus Current Rating (Amps): 100 7 RECEPTACLE/ROOM #3 (HALF ROOM) A 20 1 Bus Material: Cu/Al 9 RECEPTACLE/ROOM #3 B 20 1 Short Circuit Current Rating (Amps) 11 RECEPTACLE/ROOM #7 C 20 1 Main Type: BRKR 13 RECEPTACLE/ROOM #7 A 20 1 Main Rating: 100 15 RECEPTACLE ROOM 4 (ANIMAL CONTROL) B 20 1 Neutral Type: FULL 17 RECEPTACLE/ROOM #4 C 20 1 Mounting/Encl.: SURFACE NEMA1 19 RECEPTACLE ROOM 4 (ANIMAL CONTROL) A 20 1 2020 NEC Sections Used in Demand Calculations 21 RECEPTACLE ROOM 4 (ANIMAL CONTROL) B 20 1 Factor # NEC Reference Notes
23 RECEPTACLE/ROOM #4 C 20 1 1 TBL 220.44
Receptacles ND 1st 10k @100%, Remainder @50%25 RECEPTACLE/COMPUTER (RM#1) A 20 1
27 RECEPTACLE/COMPUTER (RM#1) B 20 1 2 TBL 220.42
Apartments General Lighting
1st 20k@50%, 20-100k @40%, >100k @30%29 RECEPTACLE/COMPUTER (RM#2) C 20 1
31 RECEPTACLE/ROOM #6 A 20 1
33 SPARE B 20 1 3 430.24
Motors Largest @125% Remainder @100%35 PUMP HOUSE, REFRIGERATOR C 20 1
37 RM #4 HOT PLATE A 20 2 4 210.19(A)1 Cont Loads 125% 39 RM #4 HOT PLATE B - - 5 Non-Cont Loads 100% 41 SPACE C 6 220.51 Heating 100%
Feeder Load Breakdown Conn(KVA) Dmd Fact 2 LIGHTING/ROOM #1 (SECURITY CLOSET) A 20 1 Non-Dwelling Receptacles 0.00 0.00 4 LIGHTS/ROOM #2 (ENTRY/RECEPTION) B 20 1 Dwelling General Illumination 0.00 0.00 6 LIGHTS/ROOM #3 , RESTROOM C 20 1 Non-Continuous Lighting 0.00 1.00 8 LIGHTS/HALLWAY A 20 1 Continuous Lighting 0.00 1.25
10 LIGHTS/ROOM #3 B 20 1 Exterior Lighting 0.00 1.25 12 LIGHTS/ROOM #4 (TCI) C 20 2 Kitchen Appliances 0.00 1.00 14 LIGHTS/ROOM #7 (TCI) A - - Motors 0.00 1.00 16 LIGHTS/ROOM #5, WORKSHOP B 20 1 Largest Motor (per phase) 0.00 0.25 18 LIGHTS/EXTERIOR C 20 1 Fixed Heating 0.00 1.00 20 MOTION SENSOR LIGHT A 20 1 Fixed Cooling 0.00 1.00 22 SPARE B 20 1 Non-Diversity Loads 0.00 1.00 24 WORKSHOP,ROOM #8 C 20 1 Other 0.00 1.00
26 WORKSHOP A 20 1
28 ? B 20 2 30 ? C - - Connected Feeder Load Summary
32 SPARE A 20 1
CONN KVA CONN AMPS NEC
KVA
NEC
AMPS34 COMPRESS PLUG B 20 1
36 WORKSHOP PLUG C 20 1 PHASE A:
38 CARPORT/LOAD CENTER A 60 2 PHASE B:
40 - B - - PHASE C:
42 SPACE C TOTAL:
Notes:
Panel Loading: ACCEPTABLE
PANEL 1 AND GENERATOR LOAD SUMMARY
CALCULATED LOAD
PANEL 1 (PEAK MAY '21) 16.01 KW
16.01…