Atch 4_Replace HVAC for Animal Rooms Drawings.pdf

PDF 4 MB Posted

Attached to
Replace HVAC System to Animal Rooms at Hawaii Field Station
Solicitation number
12639525R0013
Issued by

About this file

These are mechanical and electrical design drawings for replacing the HVAC system in two animal research rooms at the USDA Animal and Plant Health Inspection Service (APHIS) Hawaii Field Station in Hilo, Hawaii. The comprehensive set of technical drawings, prepared by Coffman Engineers, details the replacement of existing fan coil units, condensing units, exhaust fans, and associated ductwork and controls in Animal Rooms 6 and 7. The project involves installing new AAON and Johnson Controls equipment with specific design requirements, including 100% outside air ventilation, maintaining negative room pressure, and providing constant volume airflow between 10-15 air changes per hour. The new system will include advanced controls allowing manual airflow adjustment, temperature monitoring, and operational modes for different occupancy scenarios. The drawings include detailed mechanical schedules, electrical one-line diagrams, floor plans, roof plans, and installation details, with the contract number 12639521D0051 and a project date of March 28, 2024.

View the file

Other files

File Type Posted
12639525R0013-0001.pdf PDF
Atch 2_Federal Construction Wage Rates.pdf PDF
12639525R0013.pdf PDF
Atch 3_Replace HVAC for Animal Rooms Spec Manual.pdf PDF
Atch 1_SOW_Hilo Animal Rooms HVAC.doc DOC document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

REV DATE DESCRIPTION

PROJ. NO.

DRAWN

CHECKED

DATE

SHEET OF

COFFMAN ENGINEERS INC.C

APHIS - REPLACE

VENTILATION UNITS,

ANIMAL RESEARCH

BUILDING

210 AMAUULU RD.

HAWAII COUNTY

HILO, HI

232507

03/28/24

SHEET TITLE:

SHEET NO:

A

B

C

D

A

B

C

D

1 2 3 4 5

2 3 4 5

CONTRACT # 12639521D0051

A 12/8/23 35% DD

B 01/19/24 95% CD

www.coffman.com ph 509.328.2994

221 N. Wall Street

Spokane, WA 99201 Suite 500

C 03/28/24 100% CD

COVER SHEET

G-001

RKC

TAH

APHIS - REPLACE HVAC SYSTEM

TO ANIMAL ROOMS, HAWAII FIELD STATION

210 AMAUULU ROAD

HAWAII COUNTY

HILO, HI

HAWAII COUNTY

PROJECT LOCATION

HILO BAY

PROJECT LOCATION

SHEET INDEX

E-602 ALT-1 SCHEDULES

ABBR

STANDARD ABBREVIATIONS

DESCRIPTION ABBR DESCRIPTION

A/E ARCHITECT/ENGINEER

AAV AUTOMATIC AIR VENT

ACH AIR CHANGES PER HOUR

AD ACCESS DOOR

AFF ABOVE FINISHED FLOOR

AHU AIR HANDLING UNIT

AP ACCESS PANEL

APD AIR PRESSURE DROP

ARCH ARCHITECT/ARCHITECTURAL

ASME AMERICAN SOCIETY OF MECHANICAL

ENGINEERS

BAS BUILDING AUTOMATION SYSTEM

BD BACKDRAFT DAMPER

BFP BACK FLOW PREVENTER

BG BELOW GROUND

BHP BRAKE HORSEPOWER

BLDG BUILDING

BOD BOTTOM OF DUCT

BTU BRITISH THERMAL UNIT

BTUH BRITISH THERMAL UNITS PER HOUR

CAP CAPACITY

CC COOLING COIL

CFM CUBIC FEET PER MINUTE

CI CAST IRON

CLG CEILING

CMU CONCRETE MASONRY UNIT

CO CLEANOUT

CONC CONCRETE

COND CONDENSER

CONN CONNECT/CONNECTION

CONST CONSTRUCTION

CONT CONTINUATION

COP COEFFICIENT OF PERFORMANCE

CW COLD WATER

CWR CHILLED WATER RETURN

CWS CHILLED WATER SUPPLY

DB DECIBEL or DRY BULB

DDC DIRECT DIGITAL CONTROL

DEMO DEMOLISH

DIA/Ø DIAMETER

DIM DIMENSION

DN DOWN

DWG DRAWING

EA EXHAUST AIR

EAT ENTERING AIR TEMPERATURE

EC ELECTRICAL CONTRACTOR

EDB ENTERING DRY BULB

EER ENERGY EFFICIENCY RATIO

EF EXHAUST FAN

EFF EFFICIENCY

EG EXHAUST GRILLE

ELEC ELECTRIC/ELECTRIAL

ELEV ELEVATION

EMCS ENERGY MANAGEMENT CONTROL

SYSTEM

ENCL ENCLOSURE

EQUIP EQUIPMENT

ESP EXTERNAL STATIC PRESSURE

EWB ENTERING WET BULB

EWT ENTERING WATER TEMPERATURE

EXH EXHAUST

F FAHRENHEIT

FCO FLOOR CLEANOUT

FD FLOOR DRAIN or FIRE DAMPER

FDC FIRE DEPARTMENT CONNECTION

FF FINAL FILTER

FLA FULL LOAD AMPS

FLR FLOOR

FP FIRE PROTECTION

FPM FEET PER MINUTE

FPI FINS PER INCH

FPS FEET PER SECOND

FS FLOOR SINK

FSD FIRE-SMOKE DAMPER

FT FEET or FLASH TANK

FV FACE VELOCITY

GA GAGE or GAUGE

GAL GALLONS

GALV GALVANIZED STEEL

GC GENERAL CONTRACTOR

GPH GALLONS PER HOUR

GPM GALLONS PER MINUTE

HB HOSE BIBB

HC HEATING COIL

HEPA HIGH EFFICIENCY PARTICULATE AIR

HG HOT GAS

HP HORSEPOWER

HR HOUR

HTG HEATING

HVAC HEATING, VENTILATION, AND AIR

CONDITIONING

HW HOT WATER

HWC HOT WATER CIRCULATION

HX HEAT EXCHANGER

HZ HERTZ

(N) NEW

(E) EXISTING

(R) RELOCATE

(M) MODIFIED

IBC INTERNATIONAL BUILDING CODE

ID INSIDE DIAMETER

IE INVERT ELEVATION

IEEC INTERNATIONAL ENERGY

EFFICIENCY CODE

IFC INTERNATIONAL FIRE CODE

IMC INTERNATIONAL MECHANICAL CODE

IN INCHES

INSUL INSULATION

KW KILOWATT

KWH KILOWATT HOUR

LAT LEAVING AIR TEMPERATURE

LBS POUNDS

LDB LEAVING DRY BULB

LWB LEAVING WET BULB

LWT LEAVING WATER TEMPERATURE

MAV MANUAL AIR VENT

MAX MAXIMUM

MBH THOUSAND BTU PER HOUR

MCA MINIMUM CIRCUIT AMPS

MC MECHANICAL CONTRACTOR

MCC MOTOR CONTROL CENTER

MECH MECHANICAL

MFR MANUFACTURER

MIN MINIMUM or MINUTES

MISC MISCELLANEOUS

MOCP MAXIMUM OVER CURRENT

PROTECTION

NA NOT APPLICABLE

NC NORMALLY CLOSED or NOISE

CRITERIA

NIC NOT IN CONTRACT

NO NORMALLY OPEN

NPT NATIONAL PIPE THREAD

NTS NOT TO SCALE

OBD OPPOSED BLADE DAMPER

OC ON CENTER

OD OUTSIDE DIAMETER

ORD OVERFLOW ROOF DRAINAGE

OA or OSA OUTSIDE (SUPPLY) AIR

PD PRESSURE DROP

PG PROPYLENE GLYCOL

PH/Ø PHASE

PLBG PLUMBING

POC POINT OF CONNECTION

PRV PRESSURE REDUCING VALVE

PSI POUNDS PER SQUARE INCH

PSIG POUNDS PER SQUARE INCH GAGE

PT PRESSURE TEMPERATURE

RA RETURN AIR

REQD REQUIRED

REV REVISION(S)

RO REVERSE OSMOSIS

RPBP REDUCED PRESSURE BACKFLOW

PREVENTER

RPM REVOLUTIONS PER MINUTE

SA SUPPLY AIR

SD SMOKE DETECTOR or SMOKE

DAMPER

SEER SEASONAL ENERGY EFFICIENCY

RATIO

SENS SENSIBLE

SF SUPPLY FAN or SQUARE FEET

SIM SIMILAR

SM SHEET METAL

SMACNA SHEET METAL AND AIR

CONDITIONING CONTRACTORS

NATIONAL ASSOCIATION

SP STATIC PRESSURE

SPEC SPECIFICATION or SPECIFIED

SQ SQUARE

SQ FT SQUARE FEET

SS STAINLESS STEEL

STD STANDARD

TAB TEST, ADJUSTMENT & BALANCE

TC TEMPERATURE CONTROLS

TEMP TEMPERATURE

TP TRAP PRIMER or TEST PLUG

TSP TOTAL STATIC PRESSURE

TSTAT THERMOSTAT

TU TERMINAL UNIT

TYP TYPICAL

UNO UNLESS NOTED OTHERWISE

UPC UNIFORM PLUMBING CODE

V VENTS OR VOLTS

VAC VACUUM or VOLTAGE ALTERNATING

CURRENT

VAV VARIABLE AIR VOLUME

VD VOLUME DAMPER

VEL VELOCITY

VFD VARIABLE FREQUENCY DRIVE

VTR VENT THRU ROOF

WB WET BULB

WC WATER CLOSET

WCO WALL CLEANOUT

WH WATER HEATER

WHA WATER HAMMER ARRESTOR

W/ WITH

W/O WITHOUT

ZVB ZONE VALVE BOX

D

RL

RS REFRIGERANT SUCTION

REFRIGERANT LIQUID

DRAIN - INDIRECTD

RL

RS

TEE DOWN

PIPE TURNING UP OR TOWARD

PIPE TURNING DOWN OR AWAY

PIPE END CAP

TEE UP

SD

H

T

AHU-1

P1-1

GENERAL LEGEND

SYMBOL DESCRIPTION

THIN LINEWORK INDICATES EXISTING

MEDIUM LINEWORK INDICATES NEW

THERMOSTAT OR TEMPERATURE SENSOR (WALL MOUNTED)

HUMIDISTAT OR HUMIDITY SENSOR (WALL MOUNTED)

DETAIL SYMBOL: A = IDENTIFYING NUMBER

B = SHEET WHERE DETAIL IS SHOWN

SECTION SYMBOL: A = IDENTIFYING LETTER

B = SHEET WHERE SECTION IS SHOWN

SECTION CUT LINE INDICATOR

THICK DASHED LINEWORK WITH HATCH

INDICATES EXISTING TO BE DEMOLISHED

KEYED REFERENCE NOTE SPECIFIC TO LOCATION INDICATED

POINT OF CONNECTION (POC)

PLUMBING FIXTURE TAG (REFER TO SCHEDULE)

MECHANICAL EQUIPMENT TAG (REFER TO SCHEDULES)

REVISION CLOUD AND REVISION NUMBER

SMOKE DETECTOR

GENERAL NOTE APPLIES TO ENTIRE SHEETX.

EXISTING(E)

NEW(N)

RELOCATE(REL)

NEW LOCATION(NL)

CO2 CO2 SENSOR

GENERAL MECHANICAL NOTES

DESIGN CONDITIONS

LOCATION HILO, HAWAII

OUTDOORS

SUMMER: 86.3°F DB / 74.6°F WB

WINTER: 61.7°F DB / 55.6 WB

INDOOR

COOLING: 77°F DB

HEATING: NO HEATING

VENTILATION PER ARS 242.1: 10-15 AIR CHANGES PER HOUR

HUMIDITY 60% RH INDOORS MAX. / NO MINIMUM

ELEVATION 212 FT ABOVE SEA LEVEL

DUCT HANGER

MECHANICAL LEGEND

DUCT SIZE IN INCHES FIRST SIZE

LISTED IS SIDE SHOWN

DUCT OFFSET (UP) IN DIRECTION OF

ARROW (NOT TYPICALLY SHOWN)

DUCT OFFSET (DN) IN DIRECTION OF

ARROW (NOT TYPICALLY SHOWN)

CHANGE OF DUCT SIZE

(TRIANGLE NOT ALWAYS SHOWN)

RECTANGULAR SUPPLY DUCT

ELBOW TURNED DOWN OR AWAY

RECTANGULAR RETURN/EXHAUST DUCT

ELBOW TURNED UP

RECTANGULAR RETURN/EXHAUST DUCT

ELBOW TURNED DOWN OR AWAY

SMALL RECTANGULAR DUCT ELBOW

TURNED DOWN OR AWAY

END OF DUCT WITH CAP

(UNLESS INDICATED OTHERWISE)

RECTANGULAR ELBOW WITH TURNING

VANES (SINGLE LINE)

BRANCH DUCT TAKE-OFF (SINGLE LINE)

GRILLE, REGISTER OR OPEN DUCT

(SUPPLY SHOWN)

TAG FOR GRILLE, REGISTER OR DIFFUSER.

REFER TO GRD SCHEDULE.

LINEAR SLOT DIFFUSER. REFER TO DIFFUSER AND

GRILLE SCHEDULE FOR ADDITIONAL INFORMATION.

CEILING SUPPLY DIFFUSER. REFER TO GRD

SCHEDULE

HYDRONIC HEATING OR COOLING COIL. REFER TO

DRAWING NOTES AND/OR SCHEDULE FOR CAPACITY.

TERMINAL OR DUCT MOUNTED ELECTRIC HEATING

COIL. IF NOT INDICATED ON SCHEDULES, FIRST

NUMBER INDICATES COIL HEATING CAPACITY (KW),

SECOND NUMBER INDICATES SUPPLY VOLTAGE

(VOLTS), THIRD NUMBER INDICATES PHASE(S).

MODULATING OPPOSED BLADE DAMPER

BACKDRAFT DAMPER

FIRE/SMOKE DAMPER

FIRE DAMPER

VOLUME DAMPER

RADIUS ELBOW (SINGLE LINE)

DUCT ACCESS DOOR

FLEXIBLE DUCT

ROUND DUCT ELBOW TURNED DOWN

OR AWAY

ROUND DUCT ELBOW TURNED UP

RECTANGULAR SUPPLY DUCT ELBOW

TURNED UP

CHANGE OF DUCT SIZE

OVAL DUCT IN INCHES

ROUND DUCT IN INCHES

ACOUSTIC LINED DUCT

BDD

MD

FSD

FDPR

VD

INDICATES RETURN or EXHAUST AIR FLOW

DIRECTION

INDICATES SUPPLY AIR FLOW DIRECTION

DUCT SMOKE DETECTOR

LOW LIMIT THERMOSTATLLT

DSD

4.5 KW-460-3Ø

MTD MOTORIZED DAMPER

SD SMOKE DAMPER

CEILING GRILLE (RETURN OR TRANSFER)

REFER TO GRD SCHEDULE

CEILING EXHAUST GRILLE (RETURN OR TRANSER)

REFER TO GRD SCHEDULE

RECTANGULAR EXHAUST DUCT TURNED UP

RECTANGULAR EXHAUST DUCT TURNED DOWN

RECTANGULAR OUTSIDE AIR DUCT TURNED UP

RECTANGULAR OUTSIDE AIR DUCT TURNED DOWN

1. CONTRACTOR SHALL SECURE, MAINTAIN, AND PAY FOR ALL REQUIRED

PERMITS, LICENSES, AND INSPECTIONS FOR DURATION OF WORK UNLESS

DIRECTED OTHERWISE.

2. ALL WORK SHALL COMPLY WITH THE OWNER'S REQUIREMENTS, AND WITH ALL

APPLICABLE STATE AND LOCAL CODES, OR AUTHORITY HAVING JURISDICTION.

3. DRAWINGS ARE DIAGRAMMATIC IN NATURE AND DO NOT ATTEMPT TO SHOW

ALL REQUIRED OFFSETS. COORDINATE WITH OTHER TRADES AND PROVIDE

ALL NECESSARY OFFSETS.

4. MATERIALS OR EQUIPMENT SPECIFIED TO BE "FURNISHED BY OTHERS" SHALL

BE FURNISHED BY THE GENERAL CONTRACTOR AND/OR PROCURED FROM

SOURCES SPECIFIED BY THE CONTRACT DOCUMENTS.

5. ALL EQUIPMENT AND MATERIAL ON THE JOB SITE PRIOR TO INSTALLATION

SHALL BE COVERED AND PROTECTED FROM DIRT, DUST, AND DAMAGE.

6. PROVIDE ALL DEMOLITION WORK CALLED FOR OR REQUIRED BY THE

INSTALLATION. REMOVE ALL EXISTING EQUIPMENT AND MATERIALS NOT

REUSED UNLESS SPECIFIED OTHERWISE BY THE OWNER'S REP.

7. VERIFY PHYSICAL DIMENSIONS OF EQUIPMENT TO ENSURE THAT ACCESS

CLEARANCES CAN BE MET. COORDINATE FINAL EQUIPMENT LOCATIONS W/

GENERAL CONTRACTOR AND OTHER TRADES TO ALLOW FOR REQUIRED

MECHANICAL EQUIPMENT CLEARANCES.

8. PROVIDE NEC CODE MINIMUM HORIZONTAL AND VERTICAL WORKING

CLEARANCES FOR ALL ELECTRICAL PANELS AND EQUIPMENT. OFFSET

MECHANICAL WORK AS REQUIRED.

9. CONTRACTOR IS RESPONSIBLE FOR VERIFICATION OF INSTALLATION

STANDARDS AND CONSTRUCTION CONDITIONS. CONTRACTOR SHALL FIELD

VERIFY ALL DIMENSIONS AND EXISTING CONDITIONS PRIOR TO SHOP

FABRICATION AND/OR FIELD INSTALLATION. DISCREPANCIES BETWEEN

EXISTING CONDITIONS AND THE CONSTRUCTION DRAWINGS SHALL BE CALLED

TO THE ATTENTION OF THE ENGINEER. WORK DONE WITHOUT THE

ENGINEERS APPROVAL IS THE RESPONSIBILITY OF THE CONTRACTOR.

10. ALL MECHANICAL EQUIPMENT, MATERIALS, AND INSTALLATION SHALL BE

PROVIDED BY THE CONTRACTOR. ALL EQUIPMENT SHALL BE COMPLETE,

INSTALLED, AND FULLY FUNCTIONAL PRIOR TO FINAL ACCEPTANCE OF THE

WORK.

11. INSTALL ALL EQUIPMENT PER MANUFACTURERS RECOMMENDATIONS AND

REQUIREMENTS. ANY CONFLICTS BETWEEN THE MANUFACTURERS

DOCUMENTATION AND THE CONTRACT DOCUMENTS SHALL BE BROUGHT TO

THE ATTENTION OF THE ENGINEER.

12. PROVIDE SEISMIC RESTRAINT OF MECHANICAL SYSTEMS AND EQUIPMENT AS

REQUIRED BY ASCE-7 AND INTERNATIONAL BUILDING CODE AS ADOPTED BY

THE AUTHORITY HAVING JURISDICTION.

13. IN ALL PLACES WHERE A SPECIFIC MANUFACTURER IS LISTED, THE

MANUFACTURER LISTED WAS USED AS BASIS-OF-DESIGN. EQUIVALENT

PRODUCT BY ANOTHER MANUFACTURER WILL BE ACCEPTABLE. THE

CONTRACTOR IS RESPONSIBLE FOR NOTIFYING ENGINEER OF SUBSTITUTIONS

AND PROVIDING SUBMITTALS FOR APPROVAL. CONTRACTOR IS RESPONSIBLE

FOR ANY AND ALL ADDITIONAL DESIGN FEES OR ADDITIONAL ELECTRICAL,

STRUCTURAL, MECHANICAL, OR ARCHITECTURAL REQUIREMENTS AS

REQUIRED DUE TO SUBSTITUTIONS.

REV DATE DESCRIPTION

PROJ. NO.

DRAWN

CHECKED

DATE

SHEET OF

COFFMAN ENGINEERS INC.C

APHIS - REPLACE

VENTILATION UNITS,

ANIMAL RESEARCH

BUILDING

210 AMAUULU RD.

HAWAII COUNTY

HILO, HI

232507

03/28/24

SHEET TITLE:

SHEET NO:

A

B

C

D

A

B

C

D

1 2 3 4 5

2 3 4 5

CONTRACT # 12639521D0051

A 12/8/23 35% DD

B 01/19/24 95% CD

www.coffman.com ph 509.328.2994

221 N. Wall Street

Spokane, WA 99201 Suite 500

C 03/28/24 100% CD

MECHANICAL

LEGENDS AND

ABBREVIATIONS

M-001

RKC

TAH

MECHANICAL DESIGN BASIS

PROJECT SUMMARY

THIS PROJECT WILL REPLACE THE EXISTING HVAC SYSTEMS SERVING ANIMAL ROOMS 6 AND 7. THESE ROOMS ARE CLASSIFIED AS BSL-2 OR LOWER. SYSTEM REPLACEMENT IS NECESSITATED BY THE POOR CONDITION OF THE EXISTING FAN COIL UNITS AND OUTSIDE AIR DUCTING. SYSTEM CONDITION PROBLEMS INCLUDE CORROSION AND UNRELIABLE OPERATION. THE PROJECT WILL ALSO PROVIDE NEW HVAC SYSTEM CONTROLS THAT WILL IMPROVE THE OPERATOR-TO-SYSTEM INTERFACE AND SYSTEM CONTROLLABILITY. THE NEW SYSTEM CONTROLS WILL MAINTAIN THE ANIMAL ROOMS AT A NEGATIVE PRESSURE RELATIVE TO THE REST OF THE BUILDING.

APPLICABLE CODES AND STANDARDS

2018 INTERNATIONAL MECHANICAL CODE

2020 NATIONAL ELECTRIC CODE (NFPA 70)

MANUAL 242.1 ARS FACILITIES DESIGN STANDARDS

DESIGN CRITERIA

1. INSIDE DESIGN CONDITIONS: SEE DESIGN CONDITION SCHEDULE.

2. OUTSIDE DESIGN CONDITIONS: SEE DESIGN CONDITION SCHEDULE.

3. DESIGN COOLING LOAD

· ANIMAL ROOM 6: 15,000 BTU/HR (SENSIBLE). THIS SENSIBLE LOAD INCLUDES ~4,000 BTU/HR OF LAB EQUIPMENT HEAT REJECTION BASED ON THE FOLLOWING

ANALYSIS AND ASSUMPTIONS:

· AIR SCIENCE DOWNFLOW HOOD, MODEL DWS 36, 120V/10A. HEAT REJECTION INTO ROOM ASSUMES 75% OF RATED POWER, WITH A USE FACTOR OF 25%. TOTAL

HEAT REJECTION = 768 BTU/HR.

· THERMOSCIENTIFIC BIOSAFETY CABINET, 1300 SERIES A2, 120V/8A. HEAT REJECTION INTO ROOM ASSUMES 75% OF RATED POWER, WITH A USE FACTOR OF 25%.

TOTAL HEAT REJECTION = 614 BTU/HR.

· THERMOSCIENTIFIC LOW TEMPERATURE FREEZER, MODEL UXF30086A, 115V/16. HEAT REJECTION INTO ROOM IS BASED ON THE RATED POWER INPUT, WITH A USAGE FACTOR OF 0.41 PER ASHRAE FUNDAMENTALS CHAPTER 18 TABLE 5A. TOTAL HEAT REJECTION = 2,575 BTU/HR.

· CONCLUSION: THE 15,000 BTU/HR SENSIBLE COOLING LOAD IN ANIMAL ROOM 6 IS CONSISTENT WITH THE ESTIMATED COOLING CAPACITY OF A 3-TON COOLING SYSTEM. THE EXISTING COOLING SYSTEM HAS A 3-TON NOMINAL CAPACITY AND HAS A HISTORY OF SUCCESSFULLY MEETING THE COOLING NEEDS OF THE

ROOM (ASIDE FROM UNRELIABILITY DUE TO AGE).

· ANIMAL ROOM 7: 10,770 BTU/HR (SENSIBLE): THIS ROOM DOES NOT CURRENTLY HAVE LAB EQUIPMENT.

4. PARTICULATE FILTRATION: NEW EQUIPMENT WILL BE PROVIDED WITH NOMINAL 30% / MERV 8 FILTERS FOR PARTICULATE FILTRATION. A SECOND RACK WILL BE

SPECIFIED FOR A MERV 13 FINAL FILTER DOWNSTREAM OF THE MERV 8 FILTER THAT CAN BE ADDED IF DESIRED BY THE FIELD STATION MANAGER.

5. VENTILATION: 100% OUTSIDE AIR WILL BE PROVIDED TO ANIMAL ROOMS 6 AND 7. PER MANUAL 242.1 PARAGRAPH 9.5.3.A, THE DESIGN AIR FLOW RATE IS 15 AIR

CHANGES PER HOUR, WITH TURNDOWN TO 10-12 AIR CHANGES PER HOUR PERMISSIBLE DURING NORMAL OPERATION WHEN ROOMS ARE OCCUPIED BY ANIMALS. AIR FLOW RATES CAN BE REDUCED TO 50% OF THE DESIGN AIR FLOW RATE WHEN NO ANIMALS ARE PRESENT, BY MANUALLY CHANGING THE AIR FLOW RATE AT THE

TOUCHSCREEN IN EACH ROOM.

6. ROOM PRESSURE REQUIREMENTS: PER MANUAL 242.1 PARAGRAPH 9.5.3.A, ANIMAL ROOMS SHOULD BE MAINTAINED AT A NEGATIVE PRESSURE OF ~0.05” W.G.

RELATIVE TO ADJACENT CONNECTED SPACES. IT SHOULD BE NOTED THAT THIS LEVEL OF NEGATIVE PRESSURE MAY BE IMPOSSIBLE TO ACHIEVE GIVEN THE EXISTING BUILDING ENVELOPE AND INTERIOR WALL CONSTRUCTION. A NEGATIVE PRESSURE OF ~0.01”-0.02” W.G. MAY BE MORE REALISTIC. ROOM NEGATIVE PRESSURE WILL BE CONTROLLED BY MEASURING SUPPLY AND EXHAUST AIR FLOW RATES AND CONTROLLING THE SUPPLY FAN TO ALWAYS MAINTAIN A LOWER CFM THAN THE EXHAUST

FAN.

EXISTING SYSTEM DESCRIPTION

THE EXISTING HVAC SYSTEM SERVING ANIMAL ROOM 7 INCLUDES FAN COIL FC-1, EXHAUST FAN EF-1, AND CONDENSING UNIT CU-1. FC-1 IS DESIGNED TO PROVIDE 900 CFM OF 100% OUTSIDE AIR. EF-1 IS DESIGNED TO EXHAUST 910 CFM. FC-1 IS CONTROLLED BY A WALL MOUNT THERMOSTAT. THE FAN SPEED OF EF-1 CAN BE MANUALLY

ADJUSTED BY A WALL MOUNTED CONTROL.

THE EXISTING HVAC SYSTEM SERVING ANIMAL ROOM 6 INCLUDES FAN COIL FC-2, EXHAUST FAN EF-2, AND CONDENSING UNIT CU-2. FC-2 IS DESIGNED TO PROVIDE 900 CFM OF 100% OUTSIDE AIR. EF-2 IS DESIGNED TO EXHAUST 910 CFM. FC-2 IS CONTROLLED BY A WALL MOUNT THERMOSTAT. THE FAN SPEED OF EF-2 CAN BE MANUALLY

ADJUSTED BY A WALL MOUNTED CONTROL.

NEW/MODIFIED HVAC SYSTEM AND CONTROLS DESCRIPTION

EXISTING EQUIPMENT FC-1, FC-2, EF-1, EF-2, CU-1, AND CU-2 WILL BE DEMOLISHED AND REPLACED WITH NEW COMMERCIAL QUALITY EQUIPMENT OF THE SAME APPROXIMATE CAPACITY AND CONFIGURATION. EXISTING SUPPLY DUCTING WILL BE DEMOLISHED. EXISTING EXHAUST DUCTING WILL BE CLEANED AND REMAIN IN PLACE.

NEW CONTROLS WILL INCLUDE TEMPERATURE AND PRESSURE CONTROL FOR EACH ANIMAL ROOM. A NEGATIVE PRESSURE WILL BE AUTOMATICALLY MAINTAINED BY MEASURING THE SUPPLY AND EXHAUST FLOW RATES FOR EACH ROOM AND APPLYING A CONSTANT NEGATIVE ~150 CFM (ADJ) SUPPLY OFFSET FROM THE EXHAUST CFM FLOW RATE. THE FLOW RATE IN EACH ANIMAL ROOM WILL BE CONSTANT VOLUME, BUT MANUALLY ADJUSTABLE FROM 10-15 AIR CHANGES PER HOUR, VIA A WALL MOUNTED CONTROLLER. THE OCCUPIED AIR FLOW RATE FOR ROOM 6 CAN BE ADJUSTED FROM 10 AC/HR (655 CFM) TO 16 AC/HR (1,050 CFM). THE UNOCCUPIED (NO ANIMALS) AIR FLOW

RATE FOR ROOM 6 CAN BE ADJUSTED AS LOW AS 8 ACH/HR (525 CFM).

THE OCCUPIED AIR FLOW RATE FOR ROOM 7 CAN BE ADJUSTED FROM 10 AC/HR (705 CFM) TO 15 AC/HR (1,050 CFM). THE UNOCCUPIED (NO ANIMALS) AIR FLOW RATE FOR

ROOM 7 CAN BE ADJUSTED AS LOW AS 8 ACH/HR (525 CFM).

FAN COIL UNIT SCHEDULE

TAG MANUFACTURER/ MODEL

FAN COOLING COIL UNIT POWER REQUIREMENTS UNIT

WT.

(LBS)

REMARKSCFM ESP

(IN WC)

TSP

(IN WC)

RPM MOTOR BHP FLA MOTOR

HP

TOTAL

MBH

SENSIBLE

MBH

EAT DB

(˚F)

EAT WB

(˚F)

LAT DB

(˚F)

LAT WB

(˚F)

ROWS/

FPI CONN. (IN) VOLTS Ø MCA MOCP

FCU-1 AAON/H3-BRB-2-A-141D-000 900 0.3 0.8 1,208 0.21 2.30 1.00 56.6 20.6 80.0 76.5 58.9 58.3 4/14 1-1/8 / 5/8 208 3 3.0 15.0 530 1,2,3,4,5,6,7

FCU-2 AAON/H3-BRB-2-A-141D-000 900 0.3 0.8 1,208 0.21 2.30 1.00 56.6 20.6 80.0 76.5 58.9 58.3 4/14 1-1/8 / 5/8 208 3 3.0 15.0 530 1,2,3,4,5,6,7

FCU-1 ALT-1 JOHNSON

CONTROLS/AHD08 900 0.5 1.2 1,360 BY VENDOR 5.00 0.50 57.6 21.4 80.0 76.5 59.4 59.0 4/12 5/8 / 5/8 208 1 6.3 15.0 209 1,2,3,6,7,8

FCU-2 ALT-1 JOHNSON

CONTROLS/AHD08 900 0.5 1.2 1,360 BY VENDOR 5.00 0.50 57.6 21.4 80.0 76.5 59.4 59.0 4/12 5/8 / 5/8 208 1 6.3 15.0 209 1,2,3,6,7,8

REMARKS:

1. THIS APPLICATION IS COOLING ONLY. UNITS ARE PAIRED WITH A REMOTE CONDENSER.

2. PROVIDE WITH CLASS 1 MOTORIZED AUTOMATIC DAMPER INTEGRAL TO UNIT.

3. PROVIDE VFD WITH TEFC MOTOR.

4. UNIT TO BE DOUBLE WALL.

5. PROVIDE INTERIOR CORROSION PROTECTION AND POLYMER E-COATED COIL AND STAINLESS STEEL COIL CASING.

6. PROVIDE WITH MERV 8 PRE FILTER AND OPTION TO ADD ADDITIONAL MERV 13 FILTER UNIT FILTER.

7. PROVIDE WITH MAGNEHELIC GAUGE AND CLOGGED FILTER SWITCH.

8. PROVIDE THIRD PARTY CONTROLS.

FAN SCHEDULE

TAG SERVES MANUFACTURER/ MODEL

DESCRIPTION FAN PERFORMANCE UNIT POWER REQMTS UNIT

WT.

(LBS)

REMARKSTYPE DRIVE FLOW

(CFM)

ESP

(IN WC)

SPEED

(RPM)

NOISE

(SONES)

BHP HP VOLTS Ø FLA LOCATION

EF-1 ANIMAL ROOM

EXHAUST GREENHECK / CUE-120-A UPBLAST DIRECT 1050 1 1441 12.9 1.01 1/2 208 3 2.4 89 ROOF 1,2,3,4,5

EF-2 ANIMAL ROOM

EXHAUST GREENHECK / CUE-120-A UPBLAST DIRECT 1050 1 1441 12.9 1.01 1/2 208 3 2.4 89 ROOF 1,2,3,4,5

REMARKS:

1. PROVIDE FAN WITH CORROSION RESISTANT MATERIAL AND FASTENERS OR COATED MATERIAL SUITABLE FOR A MARINE ENVIRONMENT.

2. PROVIDE WITH BIRD SCREEN.

3. PROVIDE UNIT WITH VFD CONFIGURATION.

4. PROVIDE AUTOMATIC CLASS 1 MOTORIZED DAMPER AT ROOF CURB. DAMPER MANUFACTURER AND MODEL: GREENHECK VCD-23-PB.

5. PROVIDE 115VAC DAMPER ACTUATOR INTERLOCKED WITH FAN. ACTUATOR MANUFACTURER AND MODEL: GREENHEACK MS4103F1025.

ROOM AIR BALANCE SCHEDULE

ROOM NO ROOM NAME

AIR

HANDLING

UNIT NO.

INDIVIDUAL ROOM

TEMP CONTROL

SUPPLY EXHAUST

ROOM AIR FLOW ROOM AIR

BALANCE

NET

INFILTRATION

NET

EXFILTRATION REMARKSROOM

AIR FLOW REQUIRED

ACH

DESIGN

ACH EXHAUST

ROOM

AIR FLOW

CFM CFM CV VAV CFM CFM

6 ANIMAL ROOM FC-2 YES 900 8-15 15 E 1050 CV - NEGATIVE 150 - 1

7 ANIMAL ROOM FC-1 YES 900 8-15 15 E 1050 CV - NEGATIVE 150 - 1

- CORRIDOR / BUILDING - YES - - - - - CV - NEGATIVE 300 300

REMARKS:

1. ANIMAL ROOM AIR FLOW RATES ARE CONSTANT VOLUME WITH MANUAL ADJUSTEMENT.

GRILLES, REGISTERS, DIFFUSERS SCHEDULE

GRILLE NECK PANEL THROW DAMPER FRAME

TAG TYPE MFR MODEL SIZE SIZE SIZE PATTERN TYPE MATERIAL STYLE FINISH REMARKS

1S SUPPLY PRICE 620/N/L/A 26x10 26x10 - - VCS3AL ALUM. SURFACE B12 1,2,3,4

1E EXHAUST PRICE 630FF/L/HL 24x24 24x24 24x24 - - ALUM. SURFACE B12 5

REMARKS:

1. PROVIDE TRANSITION AT GRILLE IF REQUIRED; SEE PLANS FOR DUCT SIZES.

2. GRILLES SHALL HAVE A 1-1/4" BORDER ON ALL SIDES WITH COUNTERSUNK SCREWS AND HAVE A MINIMUM THICKNESS OF 20-GUAGE. CORNERS SHALL BE WELDED WITH A REINFORICNG PATCH.

3. DIFLECTION BLADES SHALL BE MADE OF HEAVY-DUTY ALUMIUM AND SHALL EXTEND COMPLETELY THROUGH THE SIDE FRAME. BLADES SHALL BE INDIVIDUALLY ADJUSTABLE AND HELD IN PLACE WITH TENSION WIRE.

4. INSTALL GRILLE LEVEL AND PLUMB IN ACCORDANCE TO MANUFACTURER INSTRUCTIONS. GRILLE SHALL BE INSTALLED WITH AIRTIGHT CONNECTIONS TO DUCT.

5. GRILLES SHALL ACCEPT 2" FILTER AND SHALL HAVE HINGES AT BOTTOM OF GRILLE, SAME AS EXISTING.

EXHAUST FAN VARIABLE FREQUENCY DRIVE SCHEDULE

TAG LOCATION SERVES MFR MODEL MOTOR

QTY

MOTOR

HP VOLTS PHASE BYPASS DISCONNECT

AND FUSES

NEMA

ENCLOSURE

INPUT LINE

REACTOR OUTPUT LC FILTER EP/UPS REMARKS

VFD-1 ANIMAL ROOM 7 EF-1 ABB ACH580 1 1/2 208 3 YES YES NEMA 1 YES IF MOTOR LEAD LENGTH EXCEED 25 FT. Y/N VFD-3 ANIMAL ROOM 6 EF-2 ABB ACH580 1 1/2 208 3 YES YES NEMA 1 YES IF MOTOR LEAD LENGTH EXCEED 25 FT. Y/N

REMARKS:

SEISMIC AND VIBRATION CONTROL

ITEM/TAG ISOLATOR AND BRACING REQUIREMENTS CONNECTIONS

FCU-1 BRACE PER DETAIL NOTES, USE SPRING HANGER, 1.5" DEFLECTION FLEXIBLE DUCT CONNECTIONS FCU-2 BRACE PER DETAIL NOTES, USE SPRING HANGER, 1.5" DEFLECTION FLEXIBLE DUCT CONNECTIONS

EF-1 BRACE PER DETAIL NOTES FASTENED TO CURB

EF-2 BRACE PER DETAIL NOTES FASTENED TO CURB

SEISMIC RESTRAINT PROVISIONS

SEISMIC RESTRAINT CALCULATIONS MUST BE PROVIDED BY THE PRODUCT MANUFACTURER FOR ALL CONNECTIONS OF EQUIPMENT TO THE STRUCTURE. ALL RESTRAINING DEVICES SHALL HAVE TESTING DATA TO VALIDATE MAXIMUM RESTRAINT RATINGS. CALCULATIONS (INCLUDING THE COMBINING OF TENSILE AND SHEAR LOADING) TO SUPPORT SEISMIC RESTRAINT DESIGNS MUST BE STAMPED BY A REGISTERED PROFESSIONAL ENGINEER LICENSED IN WASHINGTON. THE ENGINEERING ANALYSIS MUST INDICATE CALCULATED DEAD LOADS, STATIC SEISMIC LOADS, AND CAPACITY OF MATERIALS UTILIZED FOR CONNECTIONS TO EQUIPMENT STRUCTURE.

ANALYSIS MUST DETAIL ANCHORING METHODS, BOLT DIAMETER, EMBEDMENT, AND/OR WELDED LENGTH.

ALL SEISMIC RESTRAINT DEVICES SHALL BE DESIGNED TO ACCEPT, WITHOUT FAILURE, THE FORCES PRESCRIBED PER THE ASCE 7-16 ACTING THROUGH THE EQUIPMENT CENTER OF GRAVITY. OVERTURNING MOMENTS MAY EXCEED FORCES AT GROUND LEVEL AND MAY BE RESISTED BY SEISMIC RESTRAINTS, SUPPORT, OR ANCHORAGE.

ANCHORAGE TO CONCRETE MUST HAVE AN ICC TESTING REPORT THAT ADHERES TO THE REQUIREMENTS OF THE 2018 IBC AND MUST BE RATED FOR SEISMIC RESTRAINT IN CRACKED CONCRETE USING THE APPROPRIATE REDUCTION FACTORS PER ACI 318 APPENDIX D. ACCEPTABLE ANCHORS INCLUDE THE HILTI KWIK BOLT TZ AND SIMPSON STRONG BOLT WEDGE ANCHORS OR HILTI HIT-RE 500-SD AND SIMPSON SET XP EPOXY ANCHORS. EPOXIES ARE NOT ACCEPTABLE FOR USE IN OVERHEAD

APPLICATIONS.

SEISMIC DESIGN CRITERIA

SEISMIC DESIGN CATEGORY = D

SITE CLASS = D

RISK CATEGORY = II

BUILDING SEISMIC IMPORTANCE FACTOR: I = 1.0

DESIGN SPECTRAL RESPONSE ACCELERATION AT SHORT PERIODS (0.2 SECOND), Sds = 1.0 G DESIGN SPECTRAL RESPONSE ACCELERATION AT 1-SECOND PERIOD, Sd1 = 0.6 G

NOTES

COMPONENT RESPONSE MODIFICATION AND AMPLIFICATION FACTORS SHALL BE DETERMINED IN ACCORDANCE WITH ASCE 7-16, TABLE 13.6-1.

NR = NOT REQUIRED

N/A = NOT APPLICABLE

ALL MECHANICAL AND PLUMBING DISCRETE COMPONENTS AND DISTRIBUTED SYSTEMS SHALL BE POSITIVELY ATTACHED TO STRUCTURE.

HORIZONTALY DUCTING TO BE BRACED LATERALLY AND LONGITUDINALLY A MINIMUM OF EVERY 40', REGARDLESS OF SEISMIC REQUIREMENTS.

VERTICAL DUCTING AND PIPING TO BE BRACED LATERALLY A MINIMUM OF EVERY 15', REGARDLESS OF SEISMIC REQUIREMENTS.

DESIGN WIND SPEED IS 110 MPH AT 3 SECOND GUSTS.

HVAC CONDENSING UNIT SCHEDULE

TAG LOCATION SERVES MANUFACTURER/ MODEL

COND FAN(S) COMPRESS. NOM.

CAPACITY

(TONS)

COOLING CAPACITY

REFRIG.

LIQUID

CONN.

(IN)

SUCTION

CONN.

(IN)

UNIT POWER

REQUIREMENTS

UNIT

WT.

(LBS)

REMARKS# HP FLA TOTAL

MBh

AAT

(°F)

EER/

SEER# RLA VOLTS Ø MCA MOCP

CU-1 GRADE FCU-1 AAON/CFA-004-A-A-2-DA0EH 1 1/3 2.8 1 16.1 4 43.5 80 12.2/

14.0 R-410A 5/8 1 1/8 208 3 3 15 527 1,2,3,4,5,6

CU-2 GRADE FCU-2 AAON/CFA-004-A-A-2-DA0EH 1 1/3 2.8 1 16.1 4 43.5 80 12.2/

14.0 R-410A 5/8 1 1/8 208 3 3 15 527 1,2,3,4,5,6

CU-1 ALT-1 GRADE CU-1 ALT-1 FRASER-JOHNSTON/AL19B6021S 1 1/3 2.8 1 22.9 5 58.3 80 -/19 R-410A 3/8 1 1/8 208 1 31.4 50 295 1,2,3,4,7,8

CU-2 ALT-1 GRADE CU-2 ALT-1 FRASER-JOHNSTON/AL19B6021S 1 1/3 2.8 1 22.9 5 58.3 80 -/19 R-410A 3/8 1 1/8 208 1 31.4 50 295 1,2,3,4,7,8

REMARKS:

1. UNIT IS PAIRED WITH A REMOTE FAN COIL UNIT.

2. UNIT TO HAVE A SINGLE POINT POWER NON-FUSED DISCONNECT OF 100 AMPS.

3. PROVIDE WITH SUCTION PRESSURE TRANSDUCER ON EACH REFRIGERATION SYSTEM

4. PROVIDE WITH 115VAC CONVENIENCE OUTLET.

5. PROVIDE WITH POLYMER E-COATED CONDENSER COIL.

6.PROVIDE WITH VARIABLE CAPACITY SCROLL COMPRESSOR CAPABLE OF 10-100% MODULATING CAPACITY.

7.UNIT TO HAVE 2-STAGE COMPRESSOR.

8. ADAPTER FITTING MUST BE FIELD INSTALLED FOR SUCTION CONNECTION.

REV DATE DESCRIPTION

PROJ. NO.

DRAWN

CHECKED

DATE

SHEET OF

COFFMAN ENGINEERS INC.C

APHIS - REPLACE

VENTILATION UNITS,

ANIMAL RESEARCH

BUILDING

210 AMAUULU RD.

HAWAII COUNTY

HILO, HI

232507

03/28/24

SHEET TITLE:

SHEET NO:

A

B

C

D

A

B

C

D

1 2 3 4 5

2 3 4 5

CONTRACT # 12639521D0051

A 12/8/23 35% DD

B 01/19/24 95% CD

www.coffman.com ph 509.328.2994

221 N. Wall Street

Spokane, WA 99201 Suite 500

C 03/28/24 100% CD

MECHANICAL

SCHEDULES AND

DIAGRAMS

M-002

RKC

TAH

DI

DI

AIPIPTAI

AI

DI

DO

CONDENSATE

ALARM

UNIT ALARM

SPEED

START/STOP

OUTSIDE AIR

TEMP

ANALOG DP

INDICATOR

OUTSIDE AIR

900 CFM

SUPPLY AIR

SCALE:1 AIRFLOW AND CONTROL DIAGRAM - ANIMAL ROOMS 6 & 7

NTS

FT

AIOUTSIDE

AIRFLOW

FCU-1

VFD-2

DI ALARM

BACNET

DI

DI

AIPIPT

AI

DI

DO

CONDENSATE

ALARM

UNIT ALARM

RL RS

SPEED

START/STOP

ANALOG DP

INDICATOR

SUPPLY AIR

FCU-2

VFD-4

DI ALARM

BACNET

PT

PT

150 CFM

150 CFM

+0.0"-0.02"

+0.0"-0.02"

CORRIDOR

ROOM

DIFFERENTIAL

PRESSURE

ROOM

DIFFERENTIAL

PRESSURE

EF-1

AO

DI

SPEED

START/STOPDO

ALARM

VFD-3

BACNET

EF-2

AO

DI

SPEED

START/STOPDO

ALARM

VFD-1

BACNET

ROOF

ROOF

FT AI

ROOM

TEMP

ROOM AIRFLOW

ADJUSTMENT

CFM

CFM

1,050

CFM

CFM

CFM

1,050

CFM

ROOM

TEMP

ROOM AIRFLOW

ADJUSTMENT

WALL MOUNTED

TOUCH SCREEN

WALL MOUNTED

TOUCH SCREEN

RM 7

RM 6

M

AO

OUTSIDE AIR

DAMPER

M AO

EXHAUST AIR

DAMPER

EXHAUST

AIRFLOW

FT AI

M AO EXHAUST AIR

DAMPER

NOTES:

1. AIRFLOW SENSOR TO BE EBTRON GTX116E-P+.

2. EXHAUST GRILLS, EXHAUST FILTERS, AND EXHAUST

DUCT ARE EXISTING TO REMAIN. ALL OTHER

EQUIPMENT, DUCT, AND CONTROLS ARE NEW.

3. VFD PROVIDED INTEGRAL TO UNIT BY

MANUFACTURER.

MERV 13 FILTER

SUPPLY AIR

TEMPERATURE

AI

OUTSIDE AIR

TEMP

OUTSIDE AIR

900 CFM

FT

AIOUTSIDE

AIRFLOW

M

AO

OUTSIDE AIR

DAMPER

SUPPLY AIR

TEMPERATURE

MERV 13 FILTER

ROOM

HUMIDITY

ROOM

HUMIDITY MERV 8 FILTER

EXHAUST

AIRFLOW

MERV 8 FILTER

MODES OF OPERATION:

FULL FLOW: MANUALLY SELECTED ON WALL MOUNTED TOUCH SCREEN DEVICE.

OCCUPIED (ANIMALS):WHEN ANIMALS ARE PRESENT IN THE ROOM. MANUALLY SELECTED ON WALL MOUNTED

TOUCH SCREEN DEVICE.

OCCUPIED (PEOPLE ONLY): WHEN ONLY PEOPLE ARE PRESENT IN THE ROOM. SET FOR MONDAY THROUGH

FRIDAY 7:00 AM TO 5:00 PM (ADJ).

OCCUPIED (ANIMALS & PEOPLE): WHEN ANIMALS AND PEOPLE ARE PRESENT IN THE ROOM. SET FOR 24/7

CONDITIONING.

UNOCUPIED: ALL OTHER TIMES.

AIRFLOW SETPOINTS FOR ANIMAL ROOM 6:

FULL FLOW - FCU-1=900 CFM, EF-1=1050CFM

OCCUPIED (ANIMALS) - FCU-1=600 CFM, EF-1=750 CFM

OCCUPIED (PEOPLE ONLY) - FCU-1=480 CFM, EF-1=630 CFM

UNOCCUPIED - FCU-1= 400 CFM, EF-1= 550 CFM

AIRFLOW SETPOINTS FOR ANIMAL ROOM 7:

FULL FLOW - FCU-2=900 CFM, EF-2=1050CFM

OCCUPIED (ANIMALS & PEOPLE) - FCU-2=600 CFM, EF-2=750 CFM

UNOCCUPIED - FCU-2= 400 CFM, EF-2= 550 CFM

ALARMS REPORTED:

1. DIRTY FAN COIL UNIT FILTER WHEN DIFFERENTIAL PRESSURE EXCEEDS 1" WC.

2. SUPPLY FAN FAILURE.

3. CONDENSATE BUILDUP.

DO

TXV

REFRIGERANT

PIPING

AI

10-100%

COOLING

CU-1

DO

TXV

REFRIGERANT

PIPING

AI

10-100%

COOLING

CU-2

RL RS

SEQUENCE OF OPERATIONS

ANIMAL ROOMS SYSTEM DESCRIPTION:

EACH ANIMAL ROOMS HVAC SYSTEM INCLUDES A FAN COIL UNIT WITH A CONDENSING UNIT AND AN EXHAUST FAN. THE FAN COIL UNIT PROVIDES FILTERED AND TEMPERED AIR FOR COOLING AND VENTILATION. COOLING IS SUPPLIED BY THE DX COIL AND ASSOCIATED CONDENSING UNIT. THE FAN COIL UNIT PROVIDES 100% OUTSIDE AIR AND WILL BE ON AT ALL OCCUPIED HOURS. THE EXHAUST FAN FOR EACH ANIMAL ROOM WILL EXHAUST 150 MORE CFM THAN WHAT IS SUPPLIED BY THE FAN COIL UNIT TO KEEP THE ROOM NEGATIVE TO THE ADJACENT

CORRIDOR.

ANIMAL ROOMS - HVAC SYSTEM CONTROL:

1. EACH FAN COIL UNIT AND EXHAUST FAN WILL OPERATE TO PROVIDE COOLING AND VENTILATION AT ALL

OCCUPIED HOURS.

2. EACH FAN COIL UNIT IS A CONSTANT VOLUME SYSTEM AND WILL PROVIDE THE AIRFLOW REQUIRED

BASED ON THE MODE OF OCCUPATION AS SENSED BY THE RESPECTIVE EBTRON AIRFLOW

MEASUREMENT DEVICE THE CFM WILL BE AUTOMATICALLY ADJUSTED BASED ON THE EXHAUST FANS CFM AND EACH FAN COIL UNIT WILL PROVIDE 150 CFM LESS THAN THE EXHAUST FAN IS EXHAUSTING.

3. EACH ANIMAL ROOM COOLING TEMPERATURE SETPOINT IS 75°F (ADJ) AS SENSED BY THE THERMOSTAT IN THE ROOM AND IS PROVIDED AS AN INPUT TO THE ASSOCIATED WALL MOUNT TOUCH SCREEN DEVICE.

EACH FAN COIL UNIT SUPPLY AIR TEMPERATURE (SAT) SETPOINT IS 60°F (ADJ). EACH CONDENSING UNITS COMPRESSOR WILL MODULATE BETWEEN 10% AND 100% CAPACITY TO ACHIEVE THE SAT SETPOINT.

4. EACH EXHAUST FAN IS A CONSTANT VOLUME SYSTEM AND WILL EXHAUST 150 CFM MORE THAN THE ASSOCIATED FAN COIL UNIT IS SUPPLYING AS SENSED BY THE EBTRON AIRFLOW MEASUREMENT DEVICE UPSTREAM OF THE EXHAUST FAN. EACH EXHAUST FAN ALSO HAS AN EXHAUST AIR DAMPER THAT WILL BE INTERLOCKED WITH THE EXHAUST FAN. WHEN THE EXHAUST FAN IS ON THE DAMPER WILL BE OPEN AND

WHEN THE EXHAUST FAN IS OFF THE DAMPER WILL BE CLOSED.

T T

STORAGE

ANIMAL ROOM

ANIMAL ROOM

BAIT FORMULATION

LABORATORY

OFFICE/

RECEPTION

SECURITY

CLOSET--

FREEZERS

MEN

WOMEN

1 1

6 6

7 7

REV DATE DESCRIPTION

PROJ. NO.

DRAWN

CHECKED

DATE

SHEET OF

COFFMAN ENGINEERS INC.C

APHIS - REPLACE

VENTILATION UNITS,

ANIMAL RESEARCH

BUILDING

210 AMAUULU RD.

HAWAII COUNTY

HILO, HI

232507

03/28/24

SHEET TITLE:

SHEET NO:

A

B

C

D

A

B

C

D

1 2 3 4 5

2 3 4 5

CONTRACT # 12639521D0051

A 12/8/23 35% DD

B 01/19/24 95% CD

www.coffman.com ph 509.328.2994

221 N. Wall Street

Spokane, WA 99201 Suite 500

C 03/28/24 100% CD

MECHANICAL FLOOR

PLAN DEMOLITION

MD-201

RKC

TAH

GENERAL NOTES

KEY NOTES

1. DEMO EXISTING FAN COIL UNIT AND EXISTING REFRIGERANT PIPING.

2. DEMO EXISTING CONDENSING UNIT.

3. DEMO EXISTING EXHAUST FANS .

4. CLEAN EXISTING EXHAUST DUCT.

5. EXISTING OUTDOOR SINK TO REMAIN.

6. DEMO EXISTING OUTSIDE AIR INTAKE HOOD AND DUCTWORK.

7. DEMO EXISTING THERMOSTAT AND FAN SPEED CONTROL DIAL.

8. DEMO EXISTING FILTER-BACK EXHAUST GRILLE AND PREPARE FOR

DIRECT REPLACEMENT.

A. THESE DRAWINGS HAVE BEEN PREPARED USING OWNER PROVIDED

DRAWINGS DATED 8/23/82 AND THROUGH FIELD OBSERVATIONS. VERIFY

EXISTING CONDITIONS AS THEY APPLY TO THIS PROJECT AND INCLUDE

IN BID A SUFFICIENT ALLOWANCE TO COVER ANY DISCREPANCY

BETWEEN THE DRAWINGS AND THE ACTUAL CONDITIONS AS THEY

CURRENTLY EXIST.

B. EXISTING WORK IS SHOWN WITH LIGHT LINES AND DEMO WORK IS

SHOWN WITH BOLD BROKEN LINES, TYP.

C. CONTRACTOR SHALL BE RESPONSIBLE FOR DISPOSAL OF ALL

EQUIPMENT THE OWNER DOES NOT WISH TO RETAIN FOR FUTURE USE.

D. CONTRACTOR SHALL COORDINATE ANY SHUT DOWN OF SYSTEMS WITH

OWNER.

X

SCALE:

PROJECT

NORTH

3/16"=1'-0"

MECHANICAL FLOOR PLAN - DEMOLITION

SCALE:

PROJECT

NORTH

3/16"=1'-0"

MECHANICAL ROOF PLAN - DEMOLITION

STORAGE

ANIMAL ROOM

ANIMAL ROOM

BAIT FORMULATION

LABORATORY

OFFICE/

RECEPTION

SECURITY

CLOSET--

FREEZERS

MEN

WOMEN

(N ) C

U-

(N ) C

U-

(N) FCU-2 (N) FCU-1

(N) EF-1

(N) EF-2

(E) HOUSEKEEPING PAD

1 1

22x14

(E) OUTDOOR SINK

22x14

3/4" D

1S

1S

1S

1S

12x14

26x10

OUTSIDE AIR INTAKE HOOD

SEE DETAIL 2/M-501

OUTSIDE AIR INTAKE HOOD

SEE DETAIL 2/M-501

INSTALLATION OF FCU-2 WILL

REQUIRE TO BE MOVED THROUGH

DOOR

T T

RL/RS

RL/RS

VFD-1

VFD-3

UNIT ACCESS TYP

12x14

26x10

1E

1E

(E) HOOD

(E) BCS

(E) FREEZER

REV DATE DESCRIPTION

PROJ. NO.

DRAWN

CHECKED

DATE

SHEET OF

COFFMAN ENGINEERS INC.C

APHIS - REPLACE

VENTILATION UNITS,

ANIMAL RESEARCH

BUILDING

210 AMAUULU RD.

HAWAII COUNTY

HILO, HI

232507

03/28/24

SHEET TITLE:

SHEET NO:

A

B

C

D

A

B

C

D

1 2 3 4 5

2 3 4 5

CONTRACT # 12639521D0051

A 12/8/23 35% DD

B 01/19/24 95% CD

www.coffman.com ph 509.328.2994

221 N. Wall Street

Spokane, WA 99201 Suite 500

C 03/28/24 100% CD

MECHANICAL FLOOR

PLAN

M-201

RKC

TAH

GENERAL NOTES

KEY NOTES

1. ROUTE CONDENSATE LINES FROM FCU-1 AND FCU-2 TO OUTDOOR SINK

TAILPIECE. SEE DETAIL 4/M-502

2. EXISTING EXHAUST DUCT TO BE CLEANED. REPLACE GRILLE MOUNTED

FILTER WITH NEW MERV-8 FILTER.

3. SLOPE OUTSIDE AIR DUCT AT 1/8" PER 1'-0" DOWN TOWARDS INTAKE

HOOD.

4. NOT USED.

5. AIRFLOW MEASUREMENT DEVICE.

6. EBTRON AIRFLOW SENSOR TO BE INSTALLED IN ATTIC SPACE IN EXISTING

DUCTWORK, SEE DETAIL C/M-202.

7. NEW TOUCH SCREEN CONTROLLER LOCATED AT LOCATION SHOWN.

8. SEE DETAIL C/M-202.

9. ALTERNATE FAN COIL UNITS AND CONDENSING UNITS ARE NOT SHOWN

ON PLAN FOR CLARITY.

10. ALTERNATE FAN COIL UNITS ARE NOT TO EXCEED 58" IN LENGTH.

11. ALTERNATE FAN COIL UNITS ARE NOT TO EXCEED 530 LBS. IN WEIGHT.

A. THESE DRAWINGS HAVE BEEN PREPARED USING OWNER PROVIDED

DRAWINGS DATED 8/23/82 AND THROUGH FIELD OBSERVATIONS. VERIFY

EXISTING CONDITIONS AS THEY APPLY TO THIS PROJECT AND INCLUDE

IN BID A SUFFICIENT ALLOWANCE TO COVER ANY DISCREPANCY

BETWEEN THE DRAWINGS AND THE ACTUAL CONDITIONS AS THEY

CURRENTLY EXIST.

B. EXISTING WORK IS SHOWN WITH LIGHT LINES AND NEW WORK IS SHOWN

WITH BOLD LINES, TYP.

C. CONTRACTOR SHALL COORDINATE ROUTING AND SPACE

REQUIREMENTS OF PIPING WITH STRUCTURAL MEMBERS AND ALL

OTHER TRADES INCLUDING HVAC, FIRE PROTECTION, ELECTRICAL, AND

COMMUNICATIONS/DATA. OFFSET PIPING AROUND DUCTWORK AND

OTHER OBSTACLES WHERE REQUIRED.

D. ALL PIPING SHALL BE SLEEVED AND SEALED THROUGH ANY STRUCTURE

OR CONCRETE.

E. CONDENSATE DRAIN PIPING SHALL BE TYPE 'L' OR 'M' COPPER. SLOPE

ALL CONDENSATE DRAIN PIPING AT 1/8" PER FOOT, MIN.

X

SCALE:

PROJECT

NORTH

3/16"=1'-0"

MECHANICAL FLOOR PLAN

SCALE:

PROJECT

NORTH

MECHANICAL ROOF PLAN

3/4" D

RL/RS

RL/RS

12"x10"12"x10" 12"x10" 12"x10"

EBTRON AIRFLOW

SENSOR 14"x22"

SEE DETAIL 2/M-501

BIRDSCREEN

3/4" D

1S

0"

16"x16"

(E) 15"x5"

16"x16"

(E) 15"x5"

EBTRON AIRFLOW

SENSOR

EBTRON AIRFLOW

SENSOR

44 77

(N) CU-1 BEHIND

(E) CEILING

(E) CEILING

REV DATE DESCRIPTION

PROJ. NO.

DRAWN

CHECKED

DATE

SHEET OF

COFFMAN ENGINEERS INC.C

APHIS - REPLACE

VENTILATION UNITS,

ANIMAL RESEARCH

BUILDING

210 AMAUULU RD.

HAWAII COUNTY

HILO, HI

232507

03/28/24

SHEET TITLE:

SHEET NO:

A

B

C

D

A

B

C

D

1 2 3 4 5

2 3 4 5

CONTRACT # 12639521D0051

A 12/8/23 35% DD

B 01/19/24 95% CD

www.coffman.com ph 509.328.2994

221 N. Wall Street

Spokane, WA 99201 Suite 500

C 03/28/24 100% CD

MECHANICAL

SECTIONS

M-202

RKC

TAH

GENERAL NOTES

KEY NOTES

1. SLOPE OUTSIDE AIR DUCT AT 1/8" PER 1'-0" DOWN TOWARDS INTAKE

HOOD.

2. CONNECT INTO TAILPIECE OF EXISTING OUTDOOR SINK. SEE DETAIL

4/M-502.

3. NOT USED.

4. EBTRON FLOW SENSOR TO BE MOUNTED 6" BEFORE TRANSITION,

MINIMUM. SEE DETAIL 7/M-502 FOR INSTALLATION.

5. EBTRON FLOW SENSOR TO BE MOUNTED 21" AFTER ELBOW AND 6"

BEFORE FILTER, MINIMUM. SEE DETAIL 7/M-502 FOR INSTALLATION.

6. VOLUME DAMPER IS INTEGRAL WITH SUPPLY DIFFUSER.

7. ACCESS TO EBTRON FLOW SENSOR IS THROUGH ATTIC.

8. FAN COIL UNITS ARE LOCATED UNDER ROOFING WITH NO CEILING

OBSTRUCTION AND ARE DIRECTLY ACCESSIBLE BY LADDER.

9. REUSE EXISTING DUCT PENETRATIONS.

A. THESE DRAWINGS HAVE BEEN PREPARED USING OWNER PROVIDED

DRAWINGS DATED 8/23/82 AND THROUGH FIELD OBSERVATIONS. VERIFY

EXISTING CONDITIONS AS THEY APPLY TO THIS PROJECT AND INCLUDE

IN BID A SUFFICIENT ALLOWANCE TO COVER ANY DISCREPANCY

BETWEEN THE DRAWINGS AND THE ACTUAL CONDITIONS AS THEY

CURRENTLY EXIST.

B. EXISTING WORK IS SHOWN WITH LIGHT LINES AND NEW WORK IS SHOWN

WITH BOLD LINES, TYP.

C. CONTRACTOR SHALL COORDINATE ROUTING AND SPACE

REQUIREMENTS OF PIPING WITH STRUCTURAL MEMBERS AND ALL

OTHER TRADES INCLUDING HVAC, FIRE PROTECTION, ELECTRICAL, AND

COMMUNICATIONS/DATA. OFFSET PIPING AROUND DUCTWORK AND

OTHER OBSTACLES WHERE REQUIRED.

D. ALL PIPING SHALL BE SLEEVED AND SEALED THROUGH ANY STRUCTURE

OR CONCRETE.

E. CONDENSATE DRAIN PIPING SHALL BE TYPE 'L' OR 'M' COPPER. SLOPE

ALL CONDENSATE DRAIN PIPING AT 1/8" PER FOOT, MIN.

X

SCALE:A SECTION

1/4" = 1'-0" SCALE:B SECTION

1/4" = 1'-0"

SCALE:C SECTION

1/4" = 1'-0"

SCALE:1 LOW PRESSURE DUCT FITTING REQUIREMENTS

NTS

HVAC UNIT

DRAIN PAN

OPEN VENT

2"

2"

MIN.

SIZE SAME AS OUTLET OR 3/4",

WHICHEVER IS LARGER

UNION

ROUTE TO DRAIN AT

1/4" PER FOOT SLOPE,

SEE PLANS FOR

ROUTING

DRAW-THROUGH

(FAN DOWNSTREAM OF COILS)

FORM FLANGE AT END

OF SHEET METAL DUCT.

SET TIGHT AGAINST WALL.

SUPPLY, RETURN, OR

EXHAUST GRILLE

OR

STUD FRAME OPENING

NOT BY MECHANICAL

SHEET METAL DUCT

18 GAUGE SHEET METAL

COLLAR FLANGE TIGHT AGAINST

WALL SURFACE. ATTACH TO

DUCT WITH SHEET METAL

SCREWS OR POP RIVETS

WALLBOARD

PARTITION WALL

SQUARE TO ROUND TRANSITION

SHEET METAL AS SPECIFIED

FOR DUCTWORK.

1"X1/8" BAND IRON

BOLT ON 4" CENTERS

1" FLANGE & HEM

WASHER

SHEET METAL AS SPECIFIED

FOR DUCTWORK.

FLANGED CONNECTION

ON FAN SIDE.

ALTERNATE POSITION OF BOLT

1-1/2" MIN. TO 3" MAX. INSTALLED. 6"

NOMINAL WITH MATERIAL TAUT.

FLEXIBLE MATERIAL AS SPECIFIED DUCT

1-1/2" POCKET

SLIP

END VIEW

NOTES

MA

X

UNISTRUT P1000

LATERAL BRACE

UNISTRUT P1843

HINGE CONNECTOR

TYPICAL EA. END

HANGER RODS WITH STIFFENERS OR HOT DIPPED

GALVANIZED ANGLE IRON SUPPORTS.

HOT DIPPED GALVANIZED ANGLE

IRON CROSS MEMBER.

RIGID BRACE (SHOWN) OR MULTIPLE CABLE

BRACES.

UNISTRUT P1000

UNISTRUT P1000

3"

1'- 0"

AS

IN

DI

CA

TE

D

ON

P

LA

N

AS INDICATED ON PLAN

7/16" Ø HOLES @ 8"CC MAX. FOR

3/8"x3-1/2" LG. BOLTS, NUTS & WASHERS

3"x3"x1/4" ANGLE FRAME

16 GAGE GALV. SHEET METAL

NOTES

1. DUCT JOINTS SHALL BE COATED WITH SEALANT

TYPE S-2 AS MANUFACTURED BY DURO-DYNNE CORP. OR

APPROVED EQUAL

2. DUCTWORK ATTACHED TO ANGLE FRAME SHALL

BE WELDED

3. ALL BOLTS SHALL BE ASTM-307 & HOT DIPPED

GALVANIZED

4. ANGLE IRON FRAMEWORK FOR INTAKE & EXHAUST HOODS

SHALL BE ASTM-A36 & HOT DIPPED GALV.

1" SQ.x 0.148

GALV. SCREEN

BIRD SCREEN

1" INTERMEDIATE WELD

STAGGERED ON ALTERNATE

SIDES OF ANGLE

6" ON CENTER (TYPICAL)

1-1/2"x1-1/2"x1/4"

ANGLE IRON

DUCT

1-1/2"x 1/4" FLAT BAR

BIRD SCREEN

1/4" DIA. SELF

TAPPING SCREWS

CHANGE OF DUCT SIZE

TRANSITION

BRANCH DUCT TAKEOFFS

END TAP

RECTANGULAR

DUCT

DUCT ELBOWS

NOTE: OFFSETS (TO AVOID OBSTRUCTIONS) ARE REQUIRED BUT ARE

NOT NECESSARILY SHOWN ON THE PLANS.

OFFSETS

R=1/2W FOR DUCTS W/ AIR

VELOCITY UNDER 1,500 FPM

R=W FOR DUCTS W/ AIR VELOCITY

OVER 1,500 FPM AND ALL DUCTS

UPSTREAM OF TERMINAL UNITS

.0

.0

D

W

D=1/2W, BUT NOT MORE THAN

12" (1/3W PERMITTED IF AIR

VELOCITY UNDER 3,000 FPM)

A

CONICAL SPIN-IN OR TRANSITION

TO AT LEAST 70% GREATER THAN

AREA OF SMALLER DUCT. SEE MAX

TRANSITION ANGLE.

THE DUCT FITTINGS ABOVE ARE CONSIDERED ACCEPTABLE. THE CONTRACTOR SHALL OBTAIN ENGINEER'S APPROVAL FOR ALTERNATIVE FITTINGS PRIOR TO

FABRICATION. ONLY FITTINGS WITH EQUAL OR LOWER PRESSURE DROP WILL BE CONSIDERED.

A

W

(ONLY PERMITTED FOR AIR

VELOCITY UNDER 1,500 FPM)

A ≤ 15° FOR DUCTS W/ AIR

VELOCITY OVER 1,500 FPM.

R

A

W

R

R=1/2W FOR DUCTS W/ AIR

VELOCITY UNDER 1,500 FPM

R=W FOR DUCTS W/ AIR

VELOCITY OVER 1,500 FPM

AND ALL DUCTS UPSTREAM

OF TERMINAL UNITS

ROUND DUCT RUNOUT

TO SINGLE DIFFUSER

OR GRILLE ONLY

CONICAL SPIN-IN

ROUND OR

RECTANGULAR

12"x12" ACCESS PANEL ON

BOTTOM OF DUCT UPSTREAM OF

TURNING VANES, REQUIRED FOR

RETURN AND EXHAUST DUCTS

TURNING VANES

A ≤ 30° FOR DUCTS W/ AIR

VELOCITY UNDER 1,500 FPM.

45° OR 90° RADIUS

ELBOWS

A ≤ 15° FOR DUCTS W/ AIR

VELOCITY OVER 1,500 FPM.

A ≤ 30° FOR DUCTS W/ AIR

VELOCITY UNDER 1,500 FPM.

3/16" 3/16"

3/16"

3/16" STAGGERED

EACH END

SCALE:2 HOOD DETAIL

NTS

SCALE:3 GRILLE IN WALL INSTALLATION

NTS

SCALE:4 OUTDOOR DUCT DETAIL

NTS

SCALE:5 SUSPENDED DUCTWORK

NTS SCALE:7 RECTANGULAR FLEXIBLE CONNECTION

NTSSCALE:6 COND. TRAP AND DRAIN - FAN COILS

NTS

COPE ANGLE LEG

EACH END

12" 12"

DUCT PER PLAN

PITCH TOP OF JACKETING

TO SHED WATER

FLASH AND SEAL JOINTS,

SEAMS, AND EDGES

WATER TIGHT

2" RIGID INSULATION,

TAPE ALL SEAMS

ALUMINUM JACKET

STAGGERED12"

12"

NOTE:

ARRANGEMENT SHOWN IS SCHEMATIC AND NOT SPECIFIC TO ANY

MANUFACTURER. CONTRACTOR REQUIRED TO ADAPT TO EQUIPMENT

SPECIFIC CONNECTION.

REV DATE DESCRIPTION

PROJ. NO.

DRAWN

CHECKED

DATE

SHEET OF

COFFMAN ENGINEERS INC.C

APHIS - REPLACE

VENTILATION UNITS,

ANIMAL RESEARCH

BUILDING

210 AMAUULU RD.

HAWAII COUNTY

HILO, HI

232507

03/28/24

SHEET TITLE:

SHEET NO:

A

B

C

D

A

B

C

D

1 2 3 4 5

2 3 4 5

CONTRACT # 12639521D0051

A 12/8/23 35% DD

B 01/19/24 95% CD

www.coffman.com ph 509.328.2994

221 N. Wall Street

Spokane, WA 99201 Suite 500

C 03/28/24 100% CD

MECHANICAL

DETAILS

M-501

RKC

TAH

1 1 /2"

V

(E) STUDOR VENT

FLEXIBLE DUCT

CONNECTOR, TYP.

DUCT

SUPPLY FAN COIL

LIQUID

SUCTION

SEE FLOOR

PLANS FOR

ROUTING

DOUBLE DEFLECTION SPRING

NEOPRENE HANGER, MASON MODEL

30N, OR APPROVED EQUAL

FAN BASE

EXHAUST FAN

3/4" CONDENSATE

FROM FAN COIL

CO

P-TRAP

2" W

CO

3/4" D

1/8" / 1'-0"

SI

ZE

A S

IN

DI

CA

TE

D

ON

P

LA

NS

EXISTING GIRT

SLOPE OUTSIDE AIR DUCT AT

1/8" PER 1'-0" DOWN TOWARDS

INTAKE HOOD

NOTES:

CONTRACTOR TO SUBMIT

HOOD/DUCT SUPPORT STRUCTURE

FOR REVIEW.

NEW HOOD SUPPORT FRAMING TO

CONNECT TO EXISTING WIND GIRTS AND

ROOF FRAMING.

FLASHING

FLASHING

CORRUGATED METAL SIDING

CAULK ALL AROUND

SCALE:3 EXHAUST FAN DETAIL - UPBLAST

NTS

SCALE:4 COND. DRAIN CONNECTION

NTS SCALE:5 HORIZONTAL FAN COIL INSTALLATION

NTS

SCALE:2 TYPICAL EXTERIOR WALL DUCT CONNECTION DETAIL

NTSSCALE:1 NOT USED

NTS

SCALE:6 CONDENSING UNIT HOUSEKEEPING PAD

NTS

#4 AT 12" ON CENTER EACH

WAY, CENTERED IN SLAB

GRADE

1" CHAMFER

6" 6" a b c

(x 4)

(x 4)

Alignment Notches

Alignment Notches

A

SCALE:7 EBTRON FLOW SENSOR INSTALLATION

NTS

B

SCALE:8 EXHAUST DUCT IN ATTIC

NTS

DEMO EXHAUST DUCT FROM

TRANSITION UP THROUGH THE

EXHAUST FAN AS SHOWN.

SECURE UNIT TO

FIELD PROVIDED

BEAMS

OUTSIDE

AIR DUCT

NOTES:

· CONTRACTOR TO CONFIRM OUTDOOR PURLINS

ARE SAME DEPTH AS INTERIOR PURLINS.

· REPLACE ANGLE IRON SPANNING BETWEEN

PURLINS WHERE REQUIRED FOR FAN COIL UNIT

HANGERS WITH 3x3x1/4" ANGLE IRON.

DUCT TRANSITION AS

REQUIRED

ANCHOR FAN TO CURB WITH (3)

#12d EACH SIDE, TYPICAL, AND

SEAL ALL AROUND

NOTES:

· CONTRACTOR TO FIELD VERIFY CONSTRUCTION OF

EXISTING ROOF AND CURB TO DETERMINE SUITABILITY

FOR INSTALLATION OF NEW EXHAUST FAN. SUBMIT A

DRAWING WITH DETAILS SHOWING PROPOSED METHOD

FOR ATTACHING NEW EXHAUST FAN TO EXISTING CURB.

· CONTRACTOR TO CONFIRM NEW EXHAUST FANS ARE

WITHIN 5% WEIGHT OF EXISTING EXHAUST FANS AND

NOTIFY ENGINEER IF THAT IS NOT THE CASE.

REV DATE DESCRIPTION

PROJ. NO.

DRAWN

CHECKED

DATE

SHEET OF

COFFMAN ENGINEERS INC.C

APHIS - REPLACE

VENTILATION UNITS,

ANIMAL RESEARCH

BUILDING

210 AMAUULU RD.

HAWAII COUNTY

HILO, HI

232507

03/28/24

SHEET TITLE:

SHEET NO:

A

B

C

D

A

B

C

D

1 2 3 4 5

2 3 4 5

CONTRACT # 12639521D0051

A 12/8/23 35% DD

B 01/19/24 95% CD

www.coffman.com ph 509.328.2994

221 N. Wall Street

Spokane, WA 99201 Suite 500

C 03/28/24 100% CD

MECHANICAL

DETAILS

M-502

RKC

TAH

X:#

SHEET NOTE

CONDUIT, VERTICAL TRANSITION

CONDUIT CAPPED

HOME RUN

X = PANELBOARD

# = BRANCH CIRCUIT NUMBER(S)

JUNCTION BOX

SURFACE RACEWAY (DEVICES SHOWN)

FLUSH FLOOR BOX (DEVICES SHOWN)

POWER POLE

VAULT

TRANSFORMER

CURRENT TRANSFORMER

NORMALLY OPEN CONTACTOR

NORMALLY CLOSED CONTACTOR

CIRCUIT BREAKER

NUMBER INDICATES TRIP AND POLES

DISCONNECT SWITCH

FUSE WITH RATING

FUSED DISCONNECT WITH RATING

MOTOR THERMAL OVERLOADS

GROUND CONNECTION

AUTOMATIC TRANSFER SWITCH

POWER METER

RELAY

VARIABLE FREQUENCY DRIVE

FEEDER CALLOUT

LUMINAIRE:

ID = FIXTURE TYPE

x = SWITCH ASSOCIATION

2'x4' RECESSED LUMINAIRE

2'x4' RECESSED LUMINAIRE

1'x4' RECESSED LUMINAIRE

1'X4' SURFACE MTD LUMINAIRE

PENDANT-MTD/SUSPENDED LUMINAIRE

WALL-MTD LUMINAIRE

STRIP FLUORESCENT LUMINAIRE

CEILING-MTD DIRECTIONAL LUMINAIRE

CEILING-MTD LUMINAIRE

TRACK LIGHT WITH NUMBER OF HEADS SHOWN

WALL-MTD LUMINAIRE

EXIT SIGN WITH ARROW INDICATING DIRECTION OF EGRESS

WALL-MTD EXIT SIGN

CEILING-MTD EXIT SIGN

BATTERY POWERED EMERGENCY LIGHT

SINGLE-POLE WALL SWITCH

PHOTOCELL CONTROL

OCCUPANCY SENSOR

LIGHTING CONTROL PANEL

WALL SWITCH:

X = AS FOLLOWS:

3 - THREE-WAY

4 - FOUR-WAY

D - DIMMER

K - KEY-OPERATED

LV/2B - LOW-VOLTAGE 2 BUTTON

LV/4B - LOW-VOLTAGE 4 BUTTON

LV/D - LOW-VOLTAGE DIMMER

LV/2D - LOW-VOLTAGE OCCUPANCY DIMMING

LV-O/D - LOW VOLTAGE OCCUPANCY DIMMING

LV-OS - LOW-VOLTAGE OCCUPANCY SENSING

VS - VACANCY SENSING

M - MOTOR STARTER WITH OVERLOADS

MC - MOMENTARY CONTACT

O - OCCUPANCY SENSOR

P - PILOT LIGHT

WP- WEATHERPROOF

a - LOWER-CASE INDICATES SWITCHING CNTRL

MOTION DETECTOR

RECEPTACLE OUTLET:

X = AS FOLLOWS:

A - ABOVE COUNTER, REFER TO ARCHITECTURAL

C - CLOCK HANGER

EP - EXPLOSION PROOF

G - GROUND FAULT CIRCUIT INTERRUPT

S - SAFETY TYPE

T - TIMER CONTROLLED

WP- WEATHERPROOF

MW- MICROWAVE, REFER TO ARCHITECTURAL

DUPLEX RECEPTACLE, 125V, 20A

DOUBLE-DUPLEX RECEPT, 125V, 20A

SWITCHED DUPLEX RECEPTACLE, 125V, 20A

SWITCHED DOUBLE-DUPLEX RECEPT, 125V, 20A

CEILING-MTD DUPLEX RECEPTACLE, 125V, 20A

CEILING-MTD DOUBLE-DUPLEX RECEPTACLE, 125V, 20A

SPECIAL PURPOSE RECEPTACLE

X = TYPE

MOTOR CONNECTION

EQUIPMENT CONNECTION

DISCONNECT SWITCH

FLUSH MOUNTED PANELBOARD

SURFACE MOUNTED PANELBOARD

480V PANELBOARD

208V OR 240V PANELBOARD

TRANSFORMER

RELAY

MECHANICAL EQUIPMENT CALLOUT

DATA/TEL OUTLET, 2-PORTS

WIRELESS ACCESS POINT

DOOR CONTACT

CARD READER

KEYPAD

CCTV SECURITY VIDEO CAMERA

SPEAKER

VR- VANDAL RESISTANT

WALL-MOUNTED SPEAKER

INTERCOM AUDIO MUSIC SOURCE

CLOCK

PUSH BUTTON

SMOKE DETECTOR

HEAT DETECTOR

FIRE ALARM MANUAL PULL STATION

FIRE ALARM HORN STROBE - WALL MOUNTED

FIRE ALARM HORN STROBE - CEILING MOUNTED

FIRE ALARM ANNUNCIATOR PANEL

FIRE ALARM CONTROL PANEL

J

V

VFD

30A/3P

30A/3P

30A

30A

PC

ID x

SYMBOLS LEGEND

SYMBOL DESCRIPTION

SYMBOLS LEGEND

SYMBOL DESCRIPTION

MD

X

M

X

T

X

R

S

S

CR

C

K

I

OR

CAM

X

F

SHEET INDEX

GENERAL NOTES

1. MOUNTING HEIGHTS OF DUPLEX RECEPTACLES AND OTHER OUTLETS SHALL BE 16" TO BOTTOM OF

BOX, UNLESS OTHERWISE NOTED.

2. CATALOG NUMBERS USED SHALL BE AS NOTED OR APPROVED EQUALS.

3. CONTRACTOR SHALL COORDINATE WORK WITH OTHER TRADES.

4. CONTRACTOR SHALL PROVIDE ALL WORK AND MATERIAL FOR COMPLETE WIRING SYSTEMS AS SHOWN

OR SPECIFIED.

5. INSTALLATION SHALL COMPLY WITH NEC 2020 AND LOCAL CODES.

6. CONTRACTOR TO REFER TO MANUFACTURES DOCUMENTS FOR ADDITIONAL DATA PRIOR TO STARTING

ROUGH-IN.

7. CONTRACTOR TO PROVIDE ALL RECEPTACLES, CORDS, CORD CAPS, SWITCHES AND WIRING UNLESS

OTHERWISE NOTED.

XXXX

FAAP

FACP

OS

REV DATE DESCRIPTION

PROJ. NO.

DRAWN

CHECKED

DATE

SHEET OF

COFFMAN ENGINEERS INC.C

APHIS - REPLACE

VENTILATION UNITS,

ANIMAL RESEARCH

BUILDING

210 AMAUULU RD.

HAWAII COUNTY

HILO, HI

232507

12/08/23

SHEET TITLE:

SHEET NO:

A

B

C

D

A

B

C

D

1 2 3 4 5

2 3 4 5

CONTRACT # ______________

A 12/8/23 35% DD

B 01/19/24 95% CD

www.coffman.com ph 509.328.2994

221 N. Wall Street

Spokane, WA 99201 Suite 500

C 02/23/24 100% CD

LEGENDS,

ABBREVIATIONS &

SHEET INDEX

E-001

RGS

CLM

STORAGE

ANIMAL ROOM

ANIMAL ROOM

BAIT FORMULATION

LABORATORY

OFFICE/

RECEPTION

SECURITY

CLOSET--

FREEZERS

MEN

WOMEN

PANEL 1 (ON

ATS/GENERATOR)

ATS COMM BOX

PANEL 2

(E) GENERATOR

LOCATED ON ROOF

LOCATED ON ROOF

METERS

REV DATE DESCRIPTION

PROJ. NO.

DRAWN

CHECKED

DATE

SHEET OF

COFFMAN ENGINEERS INC.C

APHIS - REPLACE

VENTILATION UNITS,

ANIMAL RESEARCH

BUILDING

210 AMAUULU RD.

HAWAII COUNTY

HILO, HI

232507

03/28/24

SHEET TITLE:

SHEET NO:

A

B

C

D

A

B

C

D

1 2 3 4 5

2 3 4 5

CONTRACT # 12639521D0051

A 12/8/23 35% DD

B 01/19/24 95% CD

www.coffman.com ph 509.328.2994

221 N. Wall Street

Spokane, WA 99201 Suite 500

C 03/28/24 100% CD

ELECTRICAL FLOOR

PLAN

E-101

RGS

CLM

GENERAL NOTES

KEY NOTES

1. DISCONNECT CIRCUIT AND RE-CONNECT TO NEW UNIT.

2. DISCONNECT CIRCUIT AND REMOVE BACK TO PANEL.

A. NOT USED

X

SCALE:

PROJECT

NORTH

ELECTRICAL FLOOR PLAN

PANEL 2

100A 208V

4W

PANEL 1

250A 208V

4W

GENERATOR

UTILITY

TRANSFORMER

ATS

208/120V 3PH

ONE-LINE DIAGRAM

M

REV DATE DESCRIPTION

PROJ. NO.

DRAWN

CHECKED

DATE

SHEET OF

COFFMAN ENGINEERS INC.C

APHIS - REPLACE

VENTILATION UNITS,

ANIMAL RESEARCH

BUILDING

210 AMAUULU RD.

HAWAII COUNTY

HILO, HI

232507

03/28/24

SHEET TITLE:

SHEET NO:

A

B

C

D

A

B

C

D

1 2 3 4 5

2 3 4 5

CONTRACT # 12639521D0051

A 12/8/23 35% DD

B 01/19/24 95% CD

www.coffman.com ph 509.328.2994

221 N. Wall Street

Spokane, WA 99201 Suite 500

C 03/28/24 100% CD

ONE-LINE AND

SCHEDULES

E-601

RGS

CLM

GENERAL NOTES

KEY NOTES

1. NOT USED

A. NOT USED

X

PROJECT: 232507 APHIS REPLACE HVAC FOR ANIMAL ROOMS PANEL: PANEL 1

Location: Feed-Thru to: Date: 3/29/2024

Ckt Description Phase Amp Poles Notes Ckt Totals Specifications

1 EF-1, EF-2 AND DAMPERS (ROOF) A 20 3 1 Voltage (L-L): 208 3 - B - - Phase/Wire: 3PH / 4W 5 - C - - Bus Current Rating (Amps): 250 7 AC/ROOM NO.7 A 20 1 Bus Material: Cu/Al 9 RECEPTACLE/AC/ROOM NO.1 B 20 2 Short Circuit Current Rating (Amps) 11 - C - - Main Type: BRKR 13 RECEPTACLE/AC/ROOM NO.2 A 20 2 Main Rating: 250 15 - B - - Neutral Type: FULL 17 RECEPTACLE/AC/ROOM NO.3 C 20 2 Mounting/Encl.: SURFACE NEMA1 19 - A - - 2020 NEC Sections Used in Demand Calculations 21 RECEPTACLE/ROOM 6 B 20 2 Factor # NEC Reference Notes

23 - C - - 1 TBL 220.44

Receptacles ND 1st 10k @100%, Remainder @50%25 RECEPTACLE/ROOM 6 A 20 1

27 RECEPTACLE/ROOM 6 B 20 1 2 TBL 220.42

Apartments General Lighting

1st 20k@50%, 20-100k @40%, >100k @30%29 SPARE C 20 2

31 - A - -

33 FREEZER 9/14 B 20 1 3 430.24

Motors Largest @125% Remainder @100%35 SPACE C

37 EF RM-7, EF RM-6 A 20 1 4 210.19(A)1 Cont Loads 125% 39 GEN BATTER CHARGER B 20 1 5 Non-Cont Loads 100% 41 SPACE C 6 220.51 Heating 100%

Feeder Load Breakdown Conn(KVA) Dmd Fact 2 WATER A 30 2 Non-Dwelling Receptacles 0.00 0.00 4 HEATER B - - Dwelling General Illumination 0.00 0.00 6 SPACE (HIGH LEG) C SPACE - Non-Continuous Lighting 0.00 1.00 8 RECEPTACLE/AC/ROOM 5 A 20 1 Continuous Lighting 0.00 1.25

10 CU-1, CU-2 (GRADE) B 30 3 Exterior Lighting 0.00 1.25 12 - C - - Kitchen Appliances 0.00 1.00 14 - A - - Motors 0.00 1.00 16 WORKSHOP B 20 1 Largest Motor (per phase) 0.00 0.25 18 FCU-1, FCU-2 (STORAGE) C 20 3 Fixed Heating 0.00 1.00 20 - A - - Fixed Cooling 0.00 1.00 22 - B - - Non-Diversity Loads 0.00 1.00 24 SPACE C Other 0.00 1.00

26 RECEPTACLE/ROOM 3 A 20 2

28 RECEPTACLE/ROOM 3 B - -

30 INTAKE FAN C 20 2 Connected Feeder Load Summary

32 - A - -

CONN KVA CONN AMPS NEC

KVA

NEC

AMPS34 EXHAUST FAN B 20 2

36 - C - - PHASE A:

38 SPARE A 20 1 PHASE B:

40 SPARE B 20 1 PHASE C:

42 SPACE C TOTAL:

Notes: 1. PROVIDE NEUTRAL WIRE IN CONDUIT FOR DAMPER POWER

Panel Loading: ACCEPTABLE

PROJECT: 232507 APHIS REPLACE HVAC FOR ANIMAL ROOMS PANEL: PANEL 2

Location: Feed-Thru to: Date: 3/29/2024

Ckt Description Phase Amp Poles Notes Ckt Totals Specifications

1 EF (FUME HOOD) A 20 1 Voltage (L-L): 208 3 RECEPTACLE/ROOM #3 B 20 1 Phase/Wire: 3PH / 4W 5 SPARE C 20 1 Bus Current Rating (Amps): 100 7 RECEPTACLE/ROOM #3 (HALF ROOM) A 20 1 Bus Material: Cu/Al 9 RECEPTACLE/ROOM #3 B 20 1 Short Circuit Current Rating (Amps) 11 RECEPTACLE/ROOM #7 C 20 1 Main Type: BRKR 13 RECEPTACLE/ROOM #7 A 20 1 Main Rating: 100 15 RECEPTACLE ROOM 4 (ANIMAL CONTROL) B 20 1 Neutral Type: FULL 17 RECEPTACLE/ROOM #4 C 20 1 Mounting/Encl.: SURFACE NEMA1 19 RECEPTACLE ROOM 4 (ANIMAL CONTROL) A 20 1 2020 NEC Sections Used in Demand Calculations 21 RECEPTACLE ROOM 4 (ANIMAL CONTROL) B 20 1 Factor # NEC Reference Notes

23 RECEPTACLE/ROOM #4 C 20 1 1 TBL 220.44

Receptacles ND 1st 10k @100%, Remainder @50%25 RECEPTACLE/COMPUTER (RM#1) A 20 1

27 RECEPTACLE/COMPUTER (RM#1) B 20 1 2 TBL 220.42

Apartments General Lighting

1st 20k@50%, 20-100k @40%, >100k @30%29 RECEPTACLE/COMPUTER (RM#2) C 20 1

31 RECEPTACLE/ROOM #6 A 20 1

33 SPARE B 20 1 3 430.24

Motors Largest @125% Remainder @100%35 PUMP HOUSE, REFRIGERATOR C 20 1

37 RM #4 HOT PLATE A 20 2 4 210.19(A)1 Cont Loads 125% 39 RM #4 HOT PLATE B - - 5 Non-Cont Loads 100% 41 SPACE C 6 220.51 Heating 100%

Feeder Load Breakdown Conn(KVA) Dmd Fact 2 LIGHTING/ROOM #1 (SECURITY CLOSET) A 20 1 Non-Dwelling Receptacles 0.00 0.00 4 LIGHTS/ROOM #2 (ENTRY/RECEPTION) B 20 1 Dwelling General Illumination 0.00 0.00 6 LIGHTS/ROOM #3 , RESTROOM C 20 1 Non-Continuous Lighting 0.00 1.00 8 LIGHTS/HALLWAY A 20 1 Continuous Lighting 0.00 1.25

10 LIGHTS/ROOM #3 B 20 1 Exterior Lighting 0.00 1.25 12 LIGHTS/ROOM #4 (TCI) C 20 2 Kitchen Appliances 0.00 1.00 14 LIGHTS/ROOM #7 (TCI) A - - Motors 0.00 1.00 16 LIGHTS/ROOM #5, WORKSHOP B 20 1 Largest Motor (per phase) 0.00 0.25 18 LIGHTS/EXTERIOR C 20 1 Fixed Heating 0.00 1.00 20 MOTION SENSOR LIGHT A 20 1 Fixed Cooling 0.00 1.00 22 SPARE B 20 1 Non-Diversity Loads 0.00 1.00 24 WORKSHOP,ROOM #8 C 20 1 Other 0.00 1.00

26 WORKSHOP A 20 1

28 ? B 20 2 30 ? C - - Connected Feeder Load Summary

32 SPARE A 20 1

CONN KVA CONN AMPS NEC

KVA

NEC

AMPS34 COMPRESS PLUG B 20 1

36 WORKSHOP PLUG C 20 1 PHASE A:

38 CARPORT/LOAD CENTER A 60 2 PHASE B:

40 - B - - PHASE C:

42 SPACE C TOTAL:

Notes:

Panel Loading: ACCEPTABLE

PANEL 1 AND GENERATOR LOAD SUMMARY

CALCULATED LOAD

PANEL 1 (PEAK MAY '21) 16.01 KW

16.01…

This is the start of the file's text. The full file is on GovTribe.