chk
| Patrick Fire & Emergency Services Hood/Ducts Inspection Checklist | ||||||
| FACILITY NAME: | BLDG: | Date: | Start: | Finish: | ||
| CONTRACTOR # | RATING | YES | NO | |||
| TO BE ACCOMPLISHED BY THE CONTRACTOR | ||||||
| 1. Upon inspection, were there any evidence of deposits from grease-laden vapors on any parts of hood and duct system and/or components? | ||||||
| ref. NFPA 96 Chapter 11 Section 11.6.2 | ||||||
| 2. Does the frequency of cleaning adequately prevent the build up of heavy combustible contaminants on hood components, exhaust system and suppression components? | ||||||
| ref. NFPA 96 Chapter 11 Section 11.6.3. | ||||||
| 3. Before any cleaning processes took place, were all electrical switches and system components turned off and locked out? | ||||||
| ref. NFPA 96 Chapter 11 Section 11.6.3. | ||||||
| 4. Was any component of the Fire Suppression system rendered inoperable during the cleaning process? | ||||||
| ref. NFPA 96 Chapter 11 Section 11.6.4. | ||||||
| 5. Was the Fire-extinguishing system rendered inoperable during the cleaning process by proper trained and qualified personnel? | ||||||
| ref. NFPA 96 Chapter 11 Section 11.6.5. | ||||||
| 6. Were non-flammable solvent or cleaning aids used? | ||||||
| ref. NFPA 96 Chapter 11 Section 11.6.6. | ||||||
| 7. Were prevention measures taken to protect fusible links or other detection devices of the automatic extinguishing system from any type of cleaning chemicals? | ||||||
| ref. NFPA 96 Chapter 11 Section 11.6.7. | ||||||
| 8. Were prevention measures taken to protect equipment during inclement weather? | ||||||
| ref. former checklist | ||||||
| 9. Were prevention measures taken to protect and cover kitchen equipment during cleaning process? | ||||||
| ref. NFPA 96 Chapter 11 Section 11.6.7. | ||||||
| 10. Do exhaust fans open properly with a hinge or other approved method? | ||||||
| ref. NFPA 96 Chapter 7 Section 7.8.2.1. | ||||||
| TO BE ACCOMPLISHED BY FIRE DEPARTMENT REPRESENTATIVE | ||||||
| 11. Are all the following items identified and cleaned? | ||||||
| A) Air Flow Equipment (Exhaust Fans) | ||||||
| B) Entire Duct Section from Hood Canopy to Roof Discharge | ||||||
| C) Canopy or non-canopy Exhaust Hood face | ||||||
| D) Vertical type fume scrubber | ||||||
| E) Fan Discharge Stack | ||||||
| F) Impeller Shaft | ||||||
| G) Roof top Exhausts and Vents | ||||||
| H) Fire Dampers | ||||||
| I) Fan Blades or Blower Wheels | ||||||
| J) Filters | ||||||
| K) Duct and Exhaust equipment hangars and support components | ||||||
| L) Any other miscellaneous components associated with hood and duct system | ||||||
| 12. After completion of the rinse process; was there any evidence of cleaning product residue left on any exhaust system component? | YES | NO | ||||
| ref. NFPA 96 Chapter 11 Section 11.6.8. | ||||||
| 13. After completion of the cleaning process; were all access panels (doors) and cover plates restored to their normal operational condition? | ||||||
| ref. NFPA 96 Chapter 11 Section 11.6.9. | ||||||
| 14. Does removed access panels (doors) have a service company label with the name of the company and date of cleaning affixed near the affected access panels? | ||||||
| ref. NFPA 96 Chapter 11 Section 11.6.10. | ||||||
| 15. After completion of the cleaning process; were all Dampers and diffusers positions checked for proper airflow? | ||||||
| ref. NFPA 96 Chapter 11 Section 11.6.11. | ||||||
| 16. After completion of the cleaning process; were all electrical switches and system components returned to normal operable state? | ||||||
| ref. NFPA 96 Chapter 11 Section 11.6.12. | ||||||
| 17. Was a certificate showing the name of the servicing company, the persons performing the work, and the date of cleaning provided? | ||||||
| ref. NFPA 96 Chapter 11 Section 11.6.13. | ||||||
| 18. Was a report showing the name of the servicing company, the persons performing the work, the date of cleaning and areas not accessible for cleaning or cleaning was not accomplished provided for the Facility Manager and Fire Inspectors? | ||||||
| ref. NFPA 96 Chapter 11 Section 11.6.14. | ||||||
| *This checklist was developed from the guidelines listed in NFPA 96 Chapter11 Section 4 and Section 6 and Chapter 7 | ||||||
| INSPECTOR: | Signature | |||||
| A/C OF PREVENTION | Signature | |||||
| COMMENTS: | ||||||
| ITEM # |