Atch 4_B668 Electrical Equipment Wiring Schedule_MH_20160629.pdf

PDF 333 KB Posted

Attached to
129 RQW - VMF Crane Federal contract opportunity
Solicitation number
W50S8X21Q0015
Issued by
Department of the Army California Army National Guard

View the file

Other files for this federal contract opportunity

Other files attached to 129 RQW - VMF Crane, newest first.
File Type Posted
W50S8X21Q00150001.pdf PDF
Atch 1_SOW_VMF Crane_20210817.pdf PDF
Atch 2_Specification_VMF Crane_20210816.pdf PDF
Atch 3_B668 PEMB Drawings Set_DBKO_20181101.pdf PDF
W50S8X21Q0015.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Mead & Hunt, Inc.

2440 Deming Way

Middleton, WI 53562 phone: 608-273-6380 meadhunt.com

SHEET NO.:

SHEET CONTENTS

DO NOT SCALE DRAWINGS

M&H NO.:

DATE:

DESIGNED BY:

DRAWN BY:

CHECKED BY:

ISSUED

© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.

6/

/2

8:

:1

AM

C :\U se rs

\1

8m rf\

D oc um en ts \3

-1

0.

-E -C

EN

TR

AL

-2

6_ m rf.

rv t

C A

AN

G

M of fe tt

Fe de ra l A irf ie ld th

R es cu e

W in g

R ep la ce

V eh ic le

M ai nt en an ce

F ac ilit ie s C om pl ex

E-603

SCHEDULES

3142600-114900.01

MRF

SDL

06/30/2016

MAM

06/30/16 TYPE B3 FINAL

WR WELDING RECEPTACLE SEE PLANS 0.1 - 40 - - 220 1 2 6 10 1" - - - - - - - - 6

WC-2 WATER CLOSET (ADA) SEE PLANS 0.1 - - - - 120 1 2 12 12 3/4" - - - - - - - -

WC-1 WATER CLOSET 107 0.1 - - - - 120 1 2 12 12 3/4" - - - - - - - -

VL VEHICLE LIFT 110 - 5 16.7 - - 208 3 3 10 10 1/2" - - - F 30A/25A 1 EC/EC -

UR-2 URINAL (ADA) 107 0.1 - - - - 120 1 2 12 12 3/4" - - - - - - - -

UR-1 URINAL 107 0.1 - - - - 120 1 2 12 12 3/4" - - - - - - - -

UH-4M UNIT HEATER 110 - 1/8 - - - 120 1 2 12 12 3/4" - - MFR/MFR - - - MFR/MFR -

UH-3M UNIT HEATER 110 - 1/8 - - - 120 1 2 12 12 3/4" - - MFR/MFR - - - MFR/MFR -

UH-2M UNIT HEATER 110 - 1/8 - - - 120 1 2 12 12 3/4" - - MFR/MFR - - - MFR/MFR -

UH-1R UNIT HEATER 114 - 1/8 - - - 120 1 2 12 12 3/4" - - MFR/MFR - - - MFR/MFR -

UH-1M UNIT HEATER 110 - 1/8 - - - 120 1 2 12 12 3/4" - - MFR/MFR - - - MFR/MFR -

TP-1 TRAP PRIMING SYSTEM 110 0.1 - - - - 120 1 2 12 12 3/4" - - - - - - - -

SP SHOP PRESS 110 - 1 - - - 220 3 3 12 12 3/4" - - - NF 30A 1 EC/EC -

PWC PARTS WASHER CONTROL 113 - - 16 - - 120 1 2 12 12 3/4" - - - - - - - -

PW PARTS WASHER 113 - - 36 - - 220 3 3 6 10 3/4" - - - NF 30A 1 EC/EC -

ODO OVERHEAD DOOR OPERATOR SEE PLANS - 3/4 - - - 208 3 3 12 12 3/4" MAG - MFR/MFR F 30A/4.5A 1 EC/EC - 4

MRS MEGAMAT RS 110 - - 16 - - 208 3 3 12 12 3/4" - - - - - - - -

MPS MOTORIZED PROJECT SCREEN 105 0.25 - - - - 120 1 2 12 12 3/4" - - - NF 20A 1 EC/EC -

HP-2A HEAT PUMP EXTERIOR - - - 15 25 208 1 2 12 12 3/4" - - - F 30A/25A 3R EC/EC - HP-1A HEAT PUMP EXTERIOR - - - 15 25 208 1 2 12 12 3/4" - - - F 30A/25A 3R EC/EC - GWH-1 GAS WATER HEATER MECH. MEZZ. - - 1.5 - - 120 1 2 12 12 3/4" - - - - - - - -

GO GATE OPERATOR EXTERIOR - 1 - - - 208 3 3 12 12 3/4" - - MFR/MFR NF 30A 3R EC/EC -

GD-1 SINK DISPOSER 105 - - 8.1 - - 120 1 2 12 12 3/4" - - - NF 20A 1 EC/EC -

FER-4M FUME EXTRACTOR REEL 110 - 1/3 - - - 120 1 2 12 12 3/4" - - - NF 20A 1 EC/EC FER-3M FUME EXTRACTOR REEL 110 - 1/3 - - - 120 1 2 12 12 3/4" - - - NF 20A 1 EC/EC FER-2M FUME EXTRACTOR REEL 110 - 1/3 - - - 120 1 2 12 12 3/4" - - - NF 20A 1 EC/EC FER-1R FUME EXTRACTOR REEL 114 - 1/3 - - - 120 1 2 12 12 3/4" - - - NF 20A 1 EC/EC FER-1M FUME EXTRACTOR REEL 110 - 1/3 - - - 120 1 2 12 12 3/4" - - - NF 20A 1 EC/EC FE-4M FUME EXTRACTOR 110 - 1.5 - - - 208 3 3 12 12 3/4" - - MFR/EC NF 30A 1 EC/EC - FE-3M FUME EXTRACTOR 110 - 2 - - - 208 3 3 12 12 3/4" - - MFR/EC NF 30A 1 EC/EC - FE-2M FUME EXTRACTOR 110 - 3 - - - 208 3 3 12 12 3/4" - - MFR/EC NF 30A 1 EC/EC - FE-1R FUME EXTRACTOR 114 - 3 - - - 208 3 3 12 12 3/4" - - MFR/EC NF 30A 3R EC/EC - FE-1M FUME EXTRACTOR 110 - 3 - - - 208 3 3 12 12 3/4" - - MFR/EC NF 30A 1 EC/EC - FC-1A AIR HANDLING UNIT 108 - FRAC. - - - 120 1 2 12 12 3/4" - - MFR/MFR - - - - - 2 FMCP FIRE ALARM/MASS NOTIFICATION CONTROL... 111 0.5 - - - - 120 1 2 12 12 3/4" - - - - - - - -

EWH-2A ELECTRIC WALL HEATER 101 1.5 - - - - 120 1 2 12 12 3/4" - - - - - - MFR/MFR - EWH-1A ELECTRIC WALL HEATER 101 1.5 - - - - 120 1 2 12 12 3/4" - - - - - - MFR/MFR - ESEW-1 ENERGY SHOWER AND EYE WASH SEE PLANS 0.1 - - - - 120 1 2 12 12 3/4" - - - - - - - - EF-2R EXHAUST FAN 114 - 3/4 - - - 120 1 2 10 10 3/4" - - MFR/MFR NF - - MFR/MFR - EF-2M EXHAUST FAN 110 - 3/4 - - - 208 3 3 12 12 3/4" - - MFR/MFR NF 30A 1 EC/EC - EF-1R EXHAUST FAN 114 - 1/2 - - - 208 3 3 12 12 3/4" - - MFR/MFR NF 30A 3R EC/EC - EF-1M EXHAUST FAN 112 - 3/4 - - - 208 3 3 12 12 3/4" - - MFR/MFR NF 30A 1 EC/EC - EF-1E EXHAUST FAN 111 - 1/6 - - - 120 1 2 12 12 3/4" - - MFR/MFR NF - - MFR/MFR - EF-1A EXHAUST FAN 105 - 1/6 - - - 120 1 2 12 12 3/4" - - MFR/MFR NF - - MFR/MFR -

DW DISHWASHER 105 0.5 - - - - 120 1 2 12 12 3/4" - - - - - - - -

DRYER AIR DRYER EXTERIOR - 1/4 - - - 120 1 2 12 12 3/4" - - MFR/MFR NF 20A 3R EC/EC -

DMC DYNAMOMETER CONTROLS 110 - - 16 - - 120 1 2 12 12 3/4" - - - - - - - -

DM DYNAMOMETER 110 - - 24 - - 220 1 3 10 10 3/4" - - MFR/MFR - - - - - 5

DDC DIRECT DIGITAL CONTROLLER 108 0.5 - - - - 120 1 2 12 12 3/4" - - - - - - - -

CU-1A CONDENSING UNIT EXTERIOR - - - - 15 120 1 2 12 12 3/4" - - - F 20A/15A 3R EC/EC -

CF-1 CEILING FAN 110 - 1 - - - 208 3 3 12 12 3/4" VFD - MC/MC F - - MC/EC -

BC BRIDGE CRANE 110 - 15 - - - 208 3 4 3 8 1-1/2" - - MFR F 200A/MFR 12 EC/EC Y 3

AHU-2A AIR HANDLING UNIT 101 - - 2.8 - - 208 1 2 12 12 3/4" - - - NF 30A 1 EC/EC - AHU-1A AIR HANDLING UNIT 101 - - 2.8 - - 208 1 2 12 12 3/4" - - - NF 30A 1 EC/EC -

AC-1 AIR COMPRESSOR EXTERIOR - (2) 7.5 (2) 24.2 55 - 208 3 3 6 8 1" - - MFR/MFR - - - MFR/MFR Y 1

KW HP FLA

(AMPS)

MCA

(AMPS)

MOCP

(AMPS) VOLTS PHASE NO. SIZE GND. C TYPE NEMA

SIZE

FURNISHED/

INSTALLED BY TYPE SIZE /

FUSE

NEMA

ENCLOSURE

FURNISHED/

INSTALLED BY

EQUIPMENT EQUIPMENT DESCRIPTION LOCATION

LOAD EQUIPMENT BRANCH WIRING STARTER DISCONNECT TYPE AND RATING SEE

ONE-LINE

DIAG.

KEYED

NOTE

RE - REVERSING RVS - REDUCED VOLTAGE (MAGNETIC) PC - PLUMBING CONTRACTOR

SS - REDUCED VOLTAGE, SOLID STATE VFD - VARIABLE FREQUENCY DRIVE MC - MECHANICAL CONTRACTOR

FV - FULL VOLTAGE FS - FUSED SWITCH EC - ELECTRICAL CONTRACTOR

YD - WYE- DELTA CS - COMBINATION MAGNETIC CONTROLLER NF - NON-FUSED

MS - MANUAL MOTOR STARTER (W/OVERLOADS) SW - 2 SPEED, 1 WINDING F- FUSED

MX - MANUAL MOTOR SWITCH 2SP - 2 SPEED, 2 WINDING ECB - ENCLOSED CIRCUIT BREAKER MFR - MANUFACTURER

STARTER/DISCONNECT TYPE: KEY:

ELECTRICAL EQUIPMENT WIRING SCHEDULE

6. PROVIDE NEMA 6-50R RECEPTACLE MOUNTED AT 48" AFF.

5. EQUIPMENT SUPPLIED WITH (1) 220V, 2 POLE, 30A, NEMA L14-30 RECEPTACLE.

4. OVERHEAD DOOR IS FURNISHED WITH CONTROL PANEL. CONTROL PANEL SHALL BE MOUNTED BY DIVISION 8, WIRED BY EC. EC SHALL PROVIDE ALL RACEWAYS AND WIRING REQUIRED FOR INTERCONNECTION OF DOOR EDGE SENSOR, PHOTOELECTIC SENSOR, CONTROL PANEL AND MOTOR.

3. PROVIDE FIELD WIRING FROM FUSIBLE DISCONNECT SWITCH UP TO BRIDGE TROLLEY BUS BARS. SIZE FUSE WITHIN FUSIBLE DISCONNECT IN ACCORDANCE

WITH MANUFACTURER RECOMMENDATIONS.

2. FC-1A IS POWERED THROUGH CU-1A. EC IS RESPONSIBLE FOR ALL INTERCONNECTING WIRING BETWEEN EQUIPMENT.

1. PROVIDE SINGLE POINT CONNECTION AT THE EQUIPMENT CONTROL PANEL.

EQUIPMENT SCHEDULE KEYED NOTES:

7. ALL INTERLOCKING REQUIRED BY THE DRIVE MANUFACTURER BETWEEN THE VARIABLE FREQUENCY DRIVE AND THE DISCONNECT SWITCHES SHALL BE THE

RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR.

6. THIS CONTRACTOR SHALL VERIFY WITH MECHANICAL CONTRACTOR, ELECTRICAL REQUIREMENTS INCLUDING VOLTAGES, HORSE POWER, DISCONNECTING MEANS, STARTERS FOR MOTORS AND EQUIPMENT PRIOR TO ORDERING CIRCUIT BREAKERS, FUSIBLE SWITCHES AND STARTERS.

5. MOTORS CONNECTED TO EMERGENCY SYSTEMS CIRCUITRY SHALL HAVE CIRCUITRY INSTALLED IN SEPARATE RACEWAY PER NEC ARTICLE 700.

4. PROVIDE ALL POWER WIRING INCLUDING ALL CIRCUITRY CARRYING ELECTRICAL ENERGY FROM PANELBOARD OR OTHER SOURCE THROUGH STARTERS AND DISCONNECTS TO MOTORS, PACKAGED EQUIPMENT OR PACKAGED CONTROL PANELS. PROVIDE ALL WIRING BETWEEN CONTROL PANELS AND MOTORS.

INCLUDE STARTERS, DISCONNECTS AND OVERLOAD PROTECTION IF NOT INCLUDED HVAC SPECIFICATION. COORDINATE WITH HVAC SPECIFICATIONS.

3. THIS CONTRACTOR SHALL BE RESPONSIBLE FOR INSTALLING A COMPLETE ELECTRICAL SYSTEM PER CONTRACT DRAWINGS AND ENSURING THAT THE

SYSTEM IS OPERATIONAL UPON JOB COMPLETION.

2. THIS CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATION WITH OTHER TRADES TO AVOID CONFLICTS AND TO VERIFY ALL EQUIPMENT CONNECTIONS

AND FOR COMPLETE INSTALLATION.

1. ALL WORK BY THIS CONTRACTOR TO COMPLY WITH ALL LOCAL, STATE AND NATIONAL ELECTRICAL CODES.

EQUIPMENT SCHEDULE GENERAL NOTES:

1188005965N Highlight

1188005965N Highlight

1188005965N Highlight

1188005965N Highlight

1188005965N Highlight

1188005965N Highlight

1188005965N Highlight

1188005965N Highlight

1188005965N Highlight

1188005965N Highlight

1188005965N Highlight

1188005965N Highlight

1188005965N Highlight

1188005965N Highlight

1188005965N Highlight

1188005965N Highlight

1188005965N Highlight

Sheets
E-131 - FIRST FLOOR AND MEZZANINE PLANS - POWER & FIRE ALARM
E-603 - SCHEDULES
2016-06-29T08:37:44-0700
Scott Lind

File details come from the government source that posted it. Updated .