Mead & Hunt, Inc.
2440 Deming Way
Middleton, WI 53562 phone: 608-273-6380 meadhunt.com
SHEET NO.:
SHEET CONTENTS
DO NOT SCALE DRAWINGS
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
ISSUED
© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
6/
/2
8:
:1
AM
C :\U se rs
\1
8m rf\
D oc um en ts \3
-1
0.
-E -C
EN
TR
AL
-2
6_ m rf.
rv t
C A
AN
G
M of fe tt
Fe de ra l A irf ie ld th
R es cu e
W in g
R ep la ce
V eh ic le
M ai nt en an ce
F ac ilit ie s C om pl ex
E-603
SCHEDULES
3142600-114900.01
MRF
SDL
06/30/2016
MAM
06/30/16 TYPE B3 FINAL
WR WELDING RECEPTACLE SEE PLANS 0.1 - 40 - - 220 1 2 6 10 1" - - - - - - - - 6
WC-2 WATER CLOSET (ADA) SEE PLANS 0.1 - - - - 120 1 2 12 12 3/4" - - - - - - - -
WC-1 WATER CLOSET 107 0.1 - - - - 120 1 2 12 12 3/4" - - - - - - - -
VL VEHICLE LIFT 110 - 5 16.7 - - 208 3 3 10 10 1/2" - - - F 30A/25A 1 EC/EC -
UR-2 URINAL (ADA) 107 0.1 - - - - 120 1 2 12 12 3/4" - - - - - - - -
UR-1 URINAL 107 0.1 - - - - 120 1 2 12 12 3/4" - - - - - - - -
UH-4M UNIT HEATER 110 - 1/8 - - - 120 1 2 12 12 3/4" - - MFR/MFR - - - MFR/MFR -
UH-3M UNIT HEATER 110 - 1/8 - - - 120 1 2 12 12 3/4" - - MFR/MFR - - - MFR/MFR -
UH-2M UNIT HEATER 110 - 1/8 - - - 120 1 2 12 12 3/4" - - MFR/MFR - - - MFR/MFR -
UH-1R UNIT HEATER 114 - 1/8 - - - 120 1 2 12 12 3/4" - - MFR/MFR - - - MFR/MFR -
UH-1M UNIT HEATER 110 - 1/8 - - - 120 1 2 12 12 3/4" - - MFR/MFR - - - MFR/MFR -
TP-1 TRAP PRIMING SYSTEM 110 0.1 - - - - 120 1 2 12 12 3/4" - - - - - - - -
SP SHOP PRESS 110 - 1 - - - 220 3 3 12 12 3/4" - - - NF 30A 1 EC/EC -
PWC PARTS WASHER CONTROL 113 - - 16 - - 120 1 2 12 12 3/4" - - - - - - - -
PW PARTS WASHER 113 - - 36 - - 220 3 3 6 10 3/4" - - - NF 30A 1 EC/EC -
ODO OVERHEAD DOOR OPERATOR SEE PLANS - 3/4 - - - 208 3 3 12 12 3/4" MAG - MFR/MFR F 30A/4.5A 1 EC/EC - 4
MRS MEGAMAT RS 110 - - 16 - - 208 3 3 12 12 3/4" - - - - - - - -
MPS MOTORIZED PROJECT SCREEN 105 0.25 - - - - 120 1 2 12 12 3/4" - - - NF 20A 1 EC/EC -
HP-2A HEAT PUMP EXTERIOR - - - 15 25 208 1 2 12 12 3/4" - - - F 30A/25A 3R EC/EC - HP-1A HEAT PUMP EXTERIOR - - - 15 25 208 1 2 12 12 3/4" - - - F 30A/25A 3R EC/EC - GWH-1 GAS WATER HEATER MECH. MEZZ. - - 1.5 - - 120 1 2 12 12 3/4" - - - - - - - -
GO GATE OPERATOR EXTERIOR - 1 - - - 208 3 3 12 12 3/4" - - MFR/MFR NF 30A 3R EC/EC -
GD-1 SINK DISPOSER 105 - - 8.1 - - 120 1 2 12 12 3/4" - - - NF 20A 1 EC/EC -
FER-4M FUME EXTRACTOR REEL 110 - 1/3 - - - 120 1 2 12 12 3/4" - - - NF 20A 1 EC/EC FER-3M FUME EXTRACTOR REEL 110 - 1/3 - - - 120 1 2 12 12 3/4" - - - NF 20A 1 EC/EC FER-2M FUME EXTRACTOR REEL 110 - 1/3 - - - 120 1 2 12 12 3/4" - - - NF 20A 1 EC/EC FER-1R FUME EXTRACTOR REEL 114 - 1/3 - - - 120 1 2 12 12 3/4" - - - NF 20A 1 EC/EC FER-1M FUME EXTRACTOR REEL 110 - 1/3 - - - 120 1 2 12 12 3/4" - - - NF 20A 1 EC/EC FE-4M FUME EXTRACTOR 110 - 1.5 - - - 208 3 3 12 12 3/4" - - MFR/EC NF 30A 1 EC/EC - FE-3M FUME EXTRACTOR 110 - 2 - - - 208 3 3 12 12 3/4" - - MFR/EC NF 30A 1 EC/EC - FE-2M FUME EXTRACTOR 110 - 3 - - - 208 3 3 12 12 3/4" - - MFR/EC NF 30A 1 EC/EC - FE-1R FUME EXTRACTOR 114 - 3 - - - 208 3 3 12 12 3/4" - - MFR/EC NF 30A 3R EC/EC - FE-1M FUME EXTRACTOR 110 - 3 - - - 208 3 3 12 12 3/4" - - MFR/EC NF 30A 1 EC/EC - FC-1A AIR HANDLING UNIT 108 - FRAC. - - - 120 1 2 12 12 3/4" - - MFR/MFR - - - - - 2 FMCP FIRE ALARM/MASS NOTIFICATION CONTROL... 111 0.5 - - - - 120 1 2 12 12 3/4" - - - - - - - -
EWH-2A ELECTRIC WALL HEATER 101 1.5 - - - - 120 1 2 12 12 3/4" - - - - - - MFR/MFR - EWH-1A ELECTRIC WALL HEATER 101 1.5 - - - - 120 1 2 12 12 3/4" - - - - - - MFR/MFR - ESEW-1 ENERGY SHOWER AND EYE WASH SEE PLANS 0.1 - - - - 120 1 2 12 12 3/4" - - - - - - - - EF-2R EXHAUST FAN 114 - 3/4 - - - 120 1 2 10 10 3/4" - - MFR/MFR NF - - MFR/MFR - EF-2M EXHAUST FAN 110 - 3/4 - - - 208 3 3 12 12 3/4" - - MFR/MFR NF 30A 1 EC/EC - EF-1R EXHAUST FAN 114 - 1/2 - - - 208 3 3 12 12 3/4" - - MFR/MFR NF 30A 3R EC/EC - EF-1M EXHAUST FAN 112 - 3/4 - - - 208 3 3 12 12 3/4" - - MFR/MFR NF 30A 1 EC/EC - EF-1E EXHAUST FAN 111 - 1/6 - - - 120 1 2 12 12 3/4" - - MFR/MFR NF - - MFR/MFR - EF-1A EXHAUST FAN 105 - 1/6 - - - 120 1 2 12 12 3/4" - - MFR/MFR NF - - MFR/MFR -
DW DISHWASHER 105 0.5 - - - - 120 1 2 12 12 3/4" - - - - - - - -
DRYER AIR DRYER EXTERIOR - 1/4 - - - 120 1 2 12 12 3/4" - - MFR/MFR NF 20A 3R EC/EC -
DMC DYNAMOMETER CONTROLS 110 - - 16 - - 120 1 2 12 12 3/4" - - - - - - - -
DM DYNAMOMETER 110 - - 24 - - 220 1 3 10 10 3/4" - - MFR/MFR - - - - - 5
DDC DIRECT DIGITAL CONTROLLER 108 0.5 - - - - 120 1 2 12 12 3/4" - - - - - - - -
CU-1A CONDENSING UNIT EXTERIOR - - - - 15 120 1 2 12 12 3/4" - - - F 20A/15A 3R EC/EC -
CF-1 CEILING FAN 110 - 1 - - - 208 3 3 12 12 3/4" VFD - MC/MC F - - MC/EC -
BC BRIDGE CRANE 110 - 15 - - - 208 3 4 3 8 1-1/2" - - MFR F 200A/MFR 12 EC/EC Y 3
AHU-2A AIR HANDLING UNIT 101 - - 2.8 - - 208 1 2 12 12 3/4" - - - NF 30A 1 EC/EC - AHU-1A AIR HANDLING UNIT 101 - - 2.8 - - 208 1 2 12 12 3/4" - - - NF 30A 1 EC/EC -
AC-1 AIR COMPRESSOR EXTERIOR - (2) 7.5 (2) 24.2 55 - 208 3 3 6 8 1" - - MFR/MFR - - - MFR/MFR Y 1
KW HP FLA
(AMPS)
MCA
(AMPS)
MOCP
(AMPS) VOLTS PHASE NO. SIZE GND. C TYPE NEMA
SIZE
FURNISHED/
INSTALLED BY TYPE SIZE /
FUSE
NEMA
ENCLOSURE
FURNISHED/
INSTALLED BY
EQUIPMENT EQUIPMENT DESCRIPTION LOCATION
LOAD EQUIPMENT BRANCH WIRING STARTER DISCONNECT TYPE AND RATING SEE
ONE-LINE
DIAG.
KEYED
NOTE
RE - REVERSING RVS - REDUCED VOLTAGE (MAGNETIC) PC - PLUMBING CONTRACTOR
SS - REDUCED VOLTAGE, SOLID STATE VFD - VARIABLE FREQUENCY DRIVE MC - MECHANICAL CONTRACTOR
FV - FULL VOLTAGE FS - FUSED SWITCH EC - ELECTRICAL CONTRACTOR
YD - WYE- DELTA CS - COMBINATION MAGNETIC CONTROLLER NF - NON-FUSED
MS - MANUAL MOTOR STARTER (W/OVERLOADS) SW - 2 SPEED, 1 WINDING F- FUSED
MX - MANUAL MOTOR SWITCH 2SP - 2 SPEED, 2 WINDING ECB - ENCLOSED CIRCUIT BREAKER MFR - MANUFACTURER
STARTER/DISCONNECT TYPE: KEY:
ELECTRICAL EQUIPMENT WIRING SCHEDULE
6. PROVIDE NEMA 6-50R RECEPTACLE MOUNTED AT 48" AFF.
5. EQUIPMENT SUPPLIED WITH (1) 220V, 2 POLE, 30A, NEMA L14-30 RECEPTACLE.
4. OVERHEAD DOOR IS FURNISHED WITH CONTROL PANEL. CONTROL PANEL SHALL BE MOUNTED BY DIVISION 8, WIRED BY EC. EC SHALL PROVIDE ALL RACEWAYS AND WIRING REQUIRED FOR INTERCONNECTION OF DOOR EDGE SENSOR, PHOTOELECTIC SENSOR, CONTROL PANEL AND MOTOR.
3. PROVIDE FIELD WIRING FROM FUSIBLE DISCONNECT SWITCH UP TO BRIDGE TROLLEY BUS BARS. SIZE FUSE WITHIN FUSIBLE DISCONNECT IN ACCORDANCE
WITH MANUFACTURER RECOMMENDATIONS.
2. FC-1A IS POWERED THROUGH CU-1A. EC IS RESPONSIBLE FOR ALL INTERCONNECTING WIRING BETWEEN EQUIPMENT.
1. PROVIDE SINGLE POINT CONNECTION AT THE EQUIPMENT CONTROL PANEL.
EQUIPMENT SCHEDULE KEYED NOTES:
7. ALL INTERLOCKING REQUIRED BY THE DRIVE MANUFACTURER BETWEEN THE VARIABLE FREQUENCY DRIVE AND THE DISCONNECT SWITCHES SHALL BE THE
RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR.
6. THIS CONTRACTOR SHALL VERIFY WITH MECHANICAL CONTRACTOR, ELECTRICAL REQUIREMENTS INCLUDING VOLTAGES, HORSE POWER, DISCONNECTING MEANS, STARTERS FOR MOTORS AND EQUIPMENT PRIOR TO ORDERING CIRCUIT BREAKERS, FUSIBLE SWITCHES AND STARTERS.
5. MOTORS CONNECTED TO EMERGENCY SYSTEMS CIRCUITRY SHALL HAVE CIRCUITRY INSTALLED IN SEPARATE RACEWAY PER NEC ARTICLE 700.
4. PROVIDE ALL POWER WIRING INCLUDING ALL CIRCUITRY CARRYING ELECTRICAL ENERGY FROM PANELBOARD OR OTHER SOURCE THROUGH STARTERS AND DISCONNECTS TO MOTORS, PACKAGED EQUIPMENT OR PACKAGED CONTROL PANELS. PROVIDE ALL WIRING BETWEEN CONTROL PANELS AND MOTORS.
INCLUDE STARTERS, DISCONNECTS AND OVERLOAD PROTECTION IF NOT INCLUDED HVAC SPECIFICATION. COORDINATE WITH HVAC SPECIFICATIONS.
3. THIS CONTRACTOR SHALL BE RESPONSIBLE FOR INSTALLING A COMPLETE ELECTRICAL SYSTEM PER CONTRACT DRAWINGS AND ENSURING THAT THE
SYSTEM IS OPERATIONAL UPON JOB COMPLETION.
2. THIS CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATION WITH OTHER TRADES TO AVOID CONFLICTS AND TO VERIFY ALL EQUIPMENT CONNECTIONS
AND FOR COMPLETE INSTALLATION.
1. ALL WORK BY THIS CONTRACTOR TO COMPLY WITH ALL LOCAL, STATE AND NATIONAL ELECTRICAL CODES.
EQUIPMENT SCHEDULE GENERAL NOTES:
1188005965N Highlight
1188005965N Highlight
1188005965N Highlight
1188005965N Highlight
1188005965N Highlight
1188005965N Highlight
1188005965N Highlight
1188005965N Highlight
1188005965N Highlight
1188005965N Highlight
1188005965N Highlight
1188005965N Highlight
1188005965N Highlight
1188005965N Highlight
1188005965N Highlight
1188005965N Highlight
1188005965N Highlight
| Sheets |
| E-131 - FIRST FLOOR AND MEZZANINE PLANS - POWER & FIRE ALARM |
| E-603 - SCHEDULES |
| 2016-06-29T08:37:44-0700 | |
| Scott Lind |
File details come from the government source that posted it. Updated .