Atch_3_Drawings.pdf

PDF 7 MB Posted

Attached to
MORU-Renovate Main Restrooms Federal contract opportunity
Solicitation number
140P6324B0009
Issued by
Department of the Interior National Park Service Midwest Region

About this file

This document appears to be a set of architectural and engineering drawings for a renovation project to renovate the main restrooms at the Mount Rushmore National Memorial in Keystone, South Dakota. The project involves demolishing and renovating the existing men's and women's restrooms, lobby, and mechanical rooms. Key details include:

The project requires new plumbing, HVAC, and fire protection systems, as well as architectural finishes and fixtures. The drawings show floor plans, interior elevations, mechanical/electrical plans, and construction details. The project is being solicited by the Department of the Interior National Park Service Midwest Region under Solicitation Number 140P6324B0009, with the project titled "MORU-Renovate Main Restrooms". The drawings provide comprehensive details on the scope of work required for this federal construction project.

View the file

Other files for this federal contract opportunity

Other files attached to MORU-Renovate Main Restrooms, newest first.
File Type Posted
Sol_140P6324B0009_Amd_0002.pdf PDF
Questions_Answers_5_30_24_0002.pdf PDF
Sol_140P6324B0009_Amd_0001.pdf PDF
Atch_2_Questions_Answers_0001.pdf PDF
Atch_1_Site_Visits_Sign_In_0001.pdf PDF
Atch_1_Statement_of_Work_(SOW)_Division1.pdf PDF
Atch_2_Statement_of_Work_(SOW).pdf PDF
Atch_6_Limitations_on_Subcontracting_Report.xlsx XLSX spreadsheet
Atch_5_DOL_Wage_Determination_SD20240029.pdf PDF
Atch_4_Submittal_List.pdf PDF
Sol_140P6324B0009.pdf PDF
Show all 11

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

REGIONAL MAP PROJECT LOCATION

A/E FIRM

PRIME/ARCH:

KENNETH HAHN ARCHITECTS

OMAHA, NE

MECHANICAL ENGINEER:

ALVINE ENGINEERING

OMAHA, NE

PROJECT

LOCATION

PROJECT

LOCATION

ELECTRICAL ENGINEER:

ALVINE ENGINEERING

OMAHA, NE

SCHEDULE OF DRAWINGS

GENERAL

1. G1 COVER SHEET

2. G2 GENERAL NOTES, LEGEND AND ABBREVIATIONS

ARCHITECTURAL

3. A1 FLOOR PLAN - DEMOLITION

4. A2 FLOOR PLAN - CEILING DEMOLITION

5. A3 FLOOR PLAN

6. A4 INTERIOR ELEVATIONS AND WALL SECTION

7. A5 INTERIOR ELEVATIONS

8. A6 ELEVATIONS, INTERIOR ELEVATIONS AND SECTION

9. A7 ENLARGED FLOOR PLANS

10. A8 FLOOR PLAN - FLOORING

11. A9 ROOM FINISH AND DOOR SCHEDULE AND WALL TYPE

12. A10 REFLECTED CEILING PLAN

13. A11 ROOF PLAN

MECHANICAL

14. M0 MECHANICAL SYMBOLS AND ABBREVIATIONS

15. M0.1 MECHANICAL GENERAL NOTES

16. M1 FLOOR PLAN - PLUMBING DEMOLITION PLAN

17. M2 FLOOR PLAN - HVAC DEMOLITION PLAN

18. M3 FLOOR PLAN - HVAC PIPING DEMOLITION

19. M4 FLOOR PLAN - PLUMBING

20. M5 FLOOR PLAN - HVAC

21. M6 FLOOR PLAN - HVAC PIPING

22. M7 FLOOR PLAN - FIRE PROTECTION

23. M8 MECHANICAL DETAILS

24. M9 MECHANICAL SCHEDULES

25. M10 MECHANICAL SCHEDULES

ELECTRICAL

26. E0 ELECTRICAL NOTES, SYMBOLS AND ABBREVIATIONS

27. E1 FLOOR PLAN - ELECTRICAL DEMOLITION

28. E2 FLOOR PLAN - LIGHTING AND FIRE ALARM

29. E3 FLOOR PLAN - POWER

30. E4 ELECTRICAL DETAILS

31. E5 ELECTRICAL SCHEDULES

PLAN NORTH

REG

IS

TE

RE

D P

ROFESSIONA L A RCHITECT

SOUT H DA KOTA

14417

STEPHEN R. SMITH

REG. NO.

ABBREVIATIONS

TILE(LARGE SCALE)

CARPET

BRICK PAVERS

ACOUSTICAL TILE

TERRAZZO

OR BOARD

STRUCTURAL STEEL

METAL STUD WALL

OTHER

(LARGE SCALE)

(SMALL SCALE)

WOOD STUD WALL

PARTICLE BOARD

PLYWOOD

FINISH WOOD

DIMENSION LUMBER

ROOF OR RIGID

FLASHING, DAMPROOFING

CAULKING OR SEALANT

BATT OR LOOSE

INSULATION

INSULATION

GLASS

GLASS

OR PLASTER

(SMALL SCALE)

GYPSUM WALLBOARD

(LARGE SCALE)

OR WATERPROFING

LAMINATED WOOD

CERAMIC OR QUARRY

CEMENT GYPSUM

CONCRETE MASONRY

LIGHTWEIGHT

METALS

CUT STONE

STEEL

CONCRETE MASONRY

COMPRESSIBLE

OR E.J. FILLER

BRICK

MASONRY

PRECAST

REINFORCEMENT

FINISHES

GLAZING

MOISTURE

THERMAL AND

PROTECTION

MATERIALS

BITUMINOUS PAVEMENT

CONCRETE POURED

CRUSHED ROCK

GRAVEL OR

SAND

SITE EARTH WOOD

REFERENCES

XX

DETAIL NUMBER

DETAIL SHEET NUMBER

SECTION NUMBER

SECTION SHEET NUMBER

ELEVATION NUMBER

ELEVATION SHEET NUMBER

COLUMN LINE

ROOM NAME AND NUMBER

DOOR NUMBER

WINDOW NUMBER

WALL TYPE

KEYNOTE

ELEVATION NUMBER

ELEVATION SHEET NUMBER

ELEVATION SYMBOL

ABOVE FINISHED FLOOR AFF

ACOUSTIC TILE CEILING ATC

ADJACENT ADJ

AIR CONDITIONING AC

ALTERNATE ALT

ALUMINUM ALUM

ANCHOR BOLT AB

ANGLE L

APPROXIMATELY APPROX

ARCHITECT ARCH

ARCHITECT / ENGINEER A/E

AT @

BASEMENT BSMT

BEAM BM

BEARING BRG

BLOCKING BLKG

BOARD BD

BOTTOM BOT

BOTTOM OF B.O.

BUILDING BLDG

CARPET CPT

CAST IRON CI

CEILING CLG

CENTERLINE CL

CERAMIC TILE CT

CHANNEL CH

CIRCUIT CKT

CLEANOUT CO

CLEAR CLR

CLOSET CLO

COMPACTED COMP

COMPRESSIBLE COMPR

CONCRETE CONC

CONCRETE MASONRY UNIT CMU

CONSTRUCTION CONST

CONTINUOUS CONT

CONTRACTOR CONTR

CONTROL JOINT CJ

CORRIDOR CORR

COUNTERSUNK CTSK

CURB C

DEAD LOAD DL

DETAIL DET

DIAMETER DIA

DIMENSION DIM

DISPENSER DISP

DISHWASHER DW

DOOR DR

DOUBLE DBL

DOWN DN

DOWNSPOUT DS

DRAWING DWG

DRINKING FOUNTAIN DF

EACH EA

ELECTRICAL ELEC

ELECTRIC WATER COOLER EWC

ELEVATION EL

ELEVATOR ELEV

ENGINEER ENGR

EQUAL EQ

EQUIPMENT EQUIP

EXHAUST FAN EF

EXISTING EXIST

EXPANSION EXP

EXPANSION JOINT EJ

EXTERIOR EXT

EXTERIOR INSULATION FINISH SYSTEM EIFS

FIELD VERIFY F.V.

FINISH FIN

FIRE ALARM FA

FIRE EXTINGUISHER FE

FIRE EXTINGUISHER CABINET FEC

FLATHEAD FH

FLEXIBLE FLEX

FLOOR FL

FLOORING FLRG

FLOOR DRAIN FD

FLUORESCENT FLUOR

FOOTING FTG

FOUNDATION FNDN

FRAME FR

FURRING FUR

GALVANIZED GALV

GAUGE GA

GLASS GL

GLASS FIBER REINFORCED PANEL GFRP

GLAZING GLZ

GRANULAR GRAN

GUTTER G

GYPSUM WALLBOARD GWB

HANDICAP HC

HARDWARE HDWE

HARDWOOD HDWD

HEIGHT HT

HIGH POINT HP

HOLLOW CORE HC

HOLLOW METAL HM

HORIZONTAL HORIZ

INSIDE DIAMETER ID

INSULATION INSUL

INTERIOR INT

JOINT JT

JOIST JST

KNEE SPACE KS

LAVATORY LAV

LIGHT LT

LIGHTWEIGHT LTWT

LIVE LOAD LL

LOW POINT LP

LUXURY VINYL TILE LVT

MARKERBOARD MB.

MANHOLE MH

MANUFACTURER MFR

MATERIAL MATL, MAT

MECHANICAL MECH

MEDICINE CABINET MC

METAL MET

METAL BUILDING PANEL MBP

METAL WALL PANEL MWP

MINIMUM MIN

MISCELLANEOUS MISC

MOUNT MT

NOT IN CONTRACT NIC

NOT TO SCALE NTS

NUMBER NO.

ON CENTER O.C.

OPENING OPNG

OPPOSITE OPP

ORIENTED STRAND BOARD OSB

OUTSIDE AIR OA

OUTSIDE DIAMETER OD

PAINT PT

PANEL PNL

PARTITION PART

PLASTER PLAS

PLASTIC LAMINATE PLAM

PLATE PL

PLYWOOD PLYWD

POLISHED POL

POUND LB

PROPERTY PROP

QUARRY TILE QT

RADIUS R

RECESSED REC

REFERENCE REF

REFRIGERATOR REFRIG, REF

REGARDING RE:

REINFORCE REINF

REQUIRED REQ

RESILIENT BASE RB

RETURN AIR RA

REVERSE REV

RISER R

ROOF DRAIN RD

ROOM RM

ROUGH OPENING RO

ROUND RND

SCHEDULE SCHED

SECTION SET

SHEET SHT

SHEET METAL SM

SHEET VINYL SV

SHEET VINYL BASE SVB

SIMILAR SIM

SLAB-ON-GRADE SOG

SPECIFICATIONS SPEC

SQUARE SQ

SQUARE FOOT SF

STEEL STL

STORAGE STOR

STRUCTURAL STRUCT

SUPPLY AIR SA

SUSPENDED SUSP

TACKBOARD TB.

TELEPHONE TELE

TEMPERATURE TEMP

TERRAZZO TERR

TOILET TLT

TONGUE & GROOVE T&G

TOP OF T.O.

TOP OF STEEL TOS

TREAD T

TYPICAL TYP

UNDERGROUND UG

UNLESS NOTED OTHERWISE UNO

URINAL UR

VERTICAL VERT

VESTIBULE VEST

VINYL COMPOSITION TILE VCT

VINYL WALLCOVERING VWC

WATER CLOSET WC

WATER HEATER WH

WEIGHT WT

WELDED WIRE FABRIC WWF

WHERE OCCURRING W.O.

WOOD WD

X A-X01

X A-X01

XX.XX

X X

X

A-X01 X

ROOM

NAME

XXXX

XX

XX

ELEV. = 100'-0"

FINISH FLOOR

XX

GENERAL NOTES

XXX

1. IN THE EVENT OF DISCREPANCIES WITHIN THE DRAWINGS OR SPECIFICATIONS, THE GREATER QUALITY AND QUANTITY OF THE ITEMS IN QUESTION SHALL BE UTILIZED AT ALL LOCATIONS WHERE SUCH DISCREPANCIES OCCUR. IN THE EVENT DISCREPANCIES BETWEEN THE DRAWINGS

AND THE SPECIFICATIONS OCCURS, THE SPECIFICATIONS SHALL BE USED.

2. THE LOCATION OF ALL UNDERGROUND UTILITIES MAY NOT BE INDICATED ON THESE PLANS, AND SOME LOCATIONS MAY BE INACCURATE. NO EXCAVATION WILL BE PERMITTED IN THE AREA OF UNDERGROUND UTILITIES UNTIL SUCH UTILITIES HAVE BEEN LOCATED AND IDENTIFIED TO THE SATISFACTION OF ALL PARTIES, AND THEN ONLY WITH EXTREME CAUTION TO AVOID ANY POSSIBILITY OF DAMAGE TO THE UTILITY OR PERSONAL INJURY. HAND-DIGGING MAY BE REQUIRED WHEN THE EXCAVATION AND UTILITIES ARE EXTREMELY CLOSE. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL REPAIR AND REPLACEMENT COST OF ANY UNDERGROUND UTILITY DAMAGE.

3. THE CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS AND SHALL BE RESPONSIBLE FOR THE SAME. COORDINATE ALL WORK AND SHOP DRAWINGS WITH OTHER TRADES.

4. THE CONTRACTOR SHALL COORDINATE ALL TESTING AND INSPECTIONS AS SPECIFIED, OR AS NECESSARY TO DEMONSTRATE A COMPLETE AND SATISFACTORY INSTALLATION.

5. ALL WORK SHALL COMPLY WITH APPLICABLE CODES, REGULATIONS, AND ORDINANCES.

6. ALL MATERIALS AND EQUIPMENT OF THE SAME TYPE SHALL BE SUPPLIED BY THE SAME MANUFACTURER, AND SHALL BE NEW, OF THE BEST QUALITY AND DESIGN, AND FREE FROM DEFECTS.

7. ALL ITEMS ARE NEW UNLESS SPECIFICALLY IDENTIFIED AS EXISTING.

8. "PROVIDE" MEANS TO FURNISH AND INSTALL.

9. THE CONTRACTOR SHALL COORDINATE ON-SITE STORAGE OF BUILDING MATERIALS, EQUIPMENT, AND TRASH CONTAINERS WITH GOVERNMENT - SEE SPECIFICATIONS FOR INSTRUCTIONS.

10. THE GOVERNMENT RESERVES THE RIGHT TO REMOVE ANY ITEMS FROM THE CONSTRUCTION AREA PRIOR TO THE START OF DEMOLITION WORK BY THE CONTRACTOR AND TO RETAIN SUCH ITEMS AS THEIR PROPERTY.

11. IT IS THE INTENT OF THIS CONTRACT THAT ALL AREAS AFFECTED BY CONSTRUCTION BE A FINISHED AND COMPLETE PROJECT. CONTRACTOR SHALL PATCH, REPAIR, AND ADJUST AS REQUIRED TO ACHIEVE THIS FINISHED PROJECT.

12. EXISTING WALL VENT GRILLES IN TOILET AREAS TO REMAIN.

13. EXISTING TILE WALLS HAVE CEMENT BOARD BACKING, WHICH SHALL BE REMOVED ALONG WITH THE TILE. CEMENT BOARD SHALL BE RE-INSTALLED ( SEE SPEC.)

GENERAL NOTES, LEGEND

AND ABBREVIATIONS

DATE:

TECH. REVIEW:

SUB SHEET NO. TITLE OF SHEET

PMIS NO.

DRAWING NO.

SHEET

OF

DRAWN BY:

DESIGNED:

DJS

DJS

KJH

15 FEB 2024

80071

RENOVATE MAIN RESTROOMS FROM THE LINCOLN

AND WASHINGTON PARKING STRUCTURES

MOUNT RUSHMORE NATIONAL MEMORIAL

KEYSTONE, SOUTH DAKOTA

305644

F eb

9,

- 4

:3 4p m Y

:\1

\1

-0

M

OU

NT

R

US

HM

OR

E

RE

ST

RO

OM

S\

DR

AW

IN

GS

\ 1

-0

_G

2.

dw g

- U

SE

R da ria n

FINAL CONSTRUCTION DOCUMENTS

G2

A01

A01

A01 A01

A02 A02

A05

TYP.

A05

TYP.

A03 A03

TYP.

TYP.

A10

A10

A06

A07 A07

A08

A04

A04

A06

A09 A13

A13

A13

A13

A13

A13 A14A14

A13

A13

A13

A13

EXISTING UNDERGROUND PROPANE

LINE - APPROXIMATE LOCATION

EXISTING TREE

TO REMAIN

A12

A15

A15

A15

A15

A16 A16

A17 A17

A18

A18

TYP.

TYP.

A19

A20

A19

A20

A21A21

A22 A22

TYP.

TYP.TYP.

A01

A11A11

A22A22

A23

A23

A23

A23

SCALE: 1/4" = 1'-0" 4' 2' 0 4'

DEMOLITION FLOOR PLAN

N1

A1

FLOOR PLAN - DEMOLITION

DEMOLITION - KEYNOTES:

A01 REMOVE WALL SHOWN DASHED COMPLETE.

A02 REMOVE HAND DRYERS - SEE ELECTRICAL.

A03 REMOVE TOILETS AND URINAL FIXTURES COMPLETE - SEE MECHANICAL.

A04 REMOVE LAVATORIES COMPLETE - SEE MECHANICAL.

A05 REMOVE TOILET PARTITIONS COMPLETE.

A06 REMOVE DOOR, FRAME AND HARDWARE COMPLETE.

A07 SALVAGE TRASH CANS AND RETURN TO GOVERNMENT.

A08 REMOVE WINDOW GLAZING AND FRAME COMPLETE.

A09 REMOVE COUNTER COMPLETE.

A10 SALVAGE BENCH COMPLETE - RETURN TO GOVERNMENT.

A11 REMOVE DOOR OPERATOR AND PREPARE FOR NEW DOOR OPERATOR.

A12 SALVAGE DISPENSER- RETURN TO OWNER.

A13 REMOVE WALL TILE AND CEMENT BOARD COMPLETE AND PREP FOR NEW WORK-

SEE GENERAL NOTES RE: CEMENT BOARD REPLACEMENT.

A14 REMOVE MIRRORS COMPLETE

A15 REMOVE PORCELAIN TILE FLOORING COMPLETE AND PREP FOR NEW WORK

A16 COORDINATE WITH GOVERNMENT RE: TEMP. STORAGE OF VENDING MACHINE

A17 REMOVE PUSH BUTTON DOOR OPERATOR (RAILING TO REMAIN.)

A18 REMOVE ACCESS PANELS BENEATH SINKS

A19 SEE ELECTRICAL RE: SALVAGE CAMERA TO BE LOWERED DOWN ON WALL

A20 REMOVE DOOR OPERATOR BUTTON

A21 REMOVE WINDOW EXHAUST FAN AND INFILL DAMPER PANEL COMPLETE.

ALUMINUM FRAME TO REMAIN & BE REUSED - SEE ARCHITECTURAL DRAWINGS

A22 CUT DOWN EXISTING ALUMINUM METAL BASE PANEL AS REQUIRED FOR NEW

METAL DOOR FRAME.

A23 REMOVE LAYER OF GWB ON EXISTING WALL THIS SIDE AND INSTALL CEMENT

BOARD.

DATE:

TECH. REVIEW:

SUB SHEET NO. TITLE OF SHEET

PMIS NO.

DRAWING NO.

SHEET

OF

DRAWN BY:

DESIGNED:

DJS

DJS

KJH

15 FEB 2024

80071

RENOVATE MAIN RESTROOMS FROM THE LINCOLN

AND WASHINGTON PARKING STRUCTURES

MOUNT RUSHMORE NATIONAL MEMORIAL

KEYSTONE, SOUTH DAKOTA

305644

F eb

9,

- 4

:3 5p m Y

:\1

\1

-0

M

OU

NT

R

US

HM

OR

E

RE

ST

RO

OM

S\

DR

AW

IN

GS

\X

RE

F\

-0

_M

OR

U

BA

TH

RO

OM

_X

DE

M

O.

dw g

- U

SE

R da ria n

A01 A02

A01 A01

A02 A01

A01A01

A2

REFLECTED CEILING PLAN -

DEMOLITION

SCALE: 1/4" = 1'-0" 4' 2' 0 4'

CEILING PLAN - DEMOLITION

N1

DEMOLITION - KEYNOTES:

A01 REMOVE GWB CEILING AND FRAMING COMPLETE.

A02 REMOVE BULKHEAD SHOWN DASHED.

DATE:

TECH. REVIEW:

SUB SHEET NO. TITLE OF SHEET

PMIS NO.

DRAWING NO.

SHEET

OF

DRAWN BY:

DESIGNED:

DJS

DJS

KJH

15 FEB 2024

80071

RENOVATE MAIN RESTROOMS FROM THE LINCOLN

AND WASHINGTON PARKING STRUCTURES

MOUNT RUSHMORE NATIONAL MEMORIAL

KEYSTONE, SOUTH DAKOTA

305644

F eb

9,

- 5

:0 2p m Y

:\1

\1

-0

M

OU

NT

R

US

HM

OR

E

RE

ST

RO

OM

S\

DR

AW

IN

GS

\X

RE

F\

-0

_M

OR

U

BA

TH

RO

OM

XC

PL

AN

.d wg

US

ER

d ar ian

A03

TYP.A03

TYP.

107A

102 103

WOMEN'S

LOBBY

RESTROOM

RESTROOM

103 MEN'S

LOBBY

WOMEN'S

RESTROOM

MEN'S

RESTROOM

JANITOR

ROOM

MECHANICAL

ROOM

CLOSET

C1C1

A2

A05A05

A04 A04A4

A4

A5

A5

A4

A4

SIM.

WOMEN'S

TOILETS

MEN'S

TOILETS

5'-0" 5'-0"

A5

14 15

A6

EXISTING UNDERGROUND PROPANE

LINE - APPROXIMATE LOCATION

EXISTING TREE

TO REMAIN

107B

D1

B1

A6

5 4

1'-0" MIN. 1'-0" MIN.

A6

A01

A02

4'-3" 4'-3"

1'- 4 1

/4" A1 A1

A11 A09

A2 A2

A15

A08A08

A15

1'-6" 1'-6"

F3 F3

A7

A7

A12 A12

A12 A12

A13A13

A14 A14

17'-9 1/4" 17'-5 1/4"

3'- 3"

3'- 3"

F4 F4

DRAINAGE SWALE

4"4"

B1 B1

A7

A7

A4

A07 A07

ARCHITECTURE - KEYNOTES:

A01 NAPKIN DISPENSER - SEE SPECS

A02 BABY CHANGING STATION SEE SPECS

A03 TOILET PARTITIONS

A04 INFILL OPENINGS ABOVE THIS WALL WITH METAL STUDS - SEE WALL TYPES

A05 ELECTRIC WATER COOLER - SEE MECHANICAL

A06 PATCH WALL AS REQUIRED FOR NEW WORK

A07 DOOR OPERATOR CONTROL BUTTON - SEE ELECTRICAL

A08 OUTSIDE CORNER TRIM - SEE SPECS

A09 RE-GRADE AS REQUIRED AROUND CRAWLSPACE DOOR TO ALLOW

FULL FUNCTION OF CRAWL SPACE DOOR. FINISH GRADE SHALL

MITIGATE WATER TO FLOW AWAY FROM BUILDING.

A10 SEE MECHANICAL AND ELECTRICAL RE: RAISING EXISTING ELECTRIC

WATER COOLER.

A11 ROOF LADDER - SEE SPECS

A12 DIAPER DISPOSAL UNIT - SITTING ON FLOOR.

A13 RECESSED HOSE BIB BOX - SEE MECHANICAL

A14 REINSTALL LOWERED CAMERA AT THIS LOCATION - SEE ELECTRICAL

A15 S.S. FRAME - TYPE F2

FLOOR PLAN

A3

DATE:

TECH. REVIEW:

SUB SHEET NO. TITLE OF SHEET

PMIS NO.

DRAWING NO.

SHEET

OF

DRAWN BY:

DESIGNED:

DJS

DJS

KJH

15 FEB 2024

80071

RENOVATE MAIN RESTROOMS FROM THE LINCOLN

AND WASHINGTON PARKING STRUCTURES

MOUNT RUSHMORE NATIONAL MEMORIAL

KEYSTONE, SOUTH DAKOTA

305644

F eb

9,

- 4

:3 5p m Y

:\1

\1

-0

M

OU

NT

R

US

HM

OR

E

RE

ST

RO

OM

S\

DR

AW

IN

GS

\X

RE

F\

-0

_M

OR

U

BA

TH

RO

OM

A-

FP

LA

N.

dw g

- U

SE

R da ria n

FINAL CONSTRUCTION DOCUMENTS

SCALE: 1/4" = 1'-0" 4' 2' 0 4'

FLOOR PLAN

N1

ARCHITECTURE - KEYNOTES:

A01 NAPKIN DISPENSER - SEE SPECS

A02 BABY CHANGING STATION SEE SPECS

A03 TOILET PARTITIONS

A04 INFILL OPENINGS ABOVE THIS WALL WITH METAL STUDS - SEE WALL TYPES

A05 ELECTRIC WATER COOLER - SEE MECHANICAL

A06 PATCH WALL AS REQUIRED FOR NEW WORK

A07 DOOR OPERATOR CONTROL BUTTON - SEE ELECTRICAL

A08 OUTSIDE CORNER TRIM - SEE SPECS

A09 RE-GRADE AS REQUIRED AROUND CRAWLSPACE DOOR TO ALLOW

FULL FUNCTION OF CRAWL SPACE DOOR. FINISH GRADE SHALL

MITIGATE WATER TO FLOW AWAY FROM BUILDING.

A10 SEE MECHANICAL AND ELECTRICAL RE: RAISING EXISTING ELECTRIC

WATER COOLER.

A11 ROOF LADDER - SEE SPECS

A12 DIAPER DISPOSAL UNIT - SITTING ON FLOOR.

A13 RECESSED HOSE BIB BOX - SEE MECHANICAL

A14 REINSTALL LOWERED CAMERA AT THIS LOCATION - SEE ELECTRICAL

A15 S.S. FRAME - TYPE F2

GENERAL NOTES:

1. WALL FRAMING BEHIND TILE SURFACES SHALL RECEIVE CEMENT BOARD.

2. WHERE TILE IS SCHEDULED ON WALLS, IT SHALL EXTEND FULL HEIGHT.

3. SEE ROOF PLAN FOR ROOF CURB DETAILS.

4. PATCH UNUSED OPENINGS IN GWB TO MATCH EXISTING.

SCALE: 1/2" = 1'-0" 2' 1' 0 2'

RESTROOM 102 - NORTH

LEVEL 01

ELEV. = 100'-0"

LEVEL 01

ELEV. = 100'-0"

LEVEL 01

ELEV. = 100'-0"

LEVEL 01

ELEV. = 100'-0"

GB-1

SCALE: 1/2" = 1'-0" 2' 1' 0 2'

RESTROOM 102 - WEST

SCALE: 1/2" = 1'-0" 2' 1' 0 2'

RESTROOM 102 - SOUTH

SCALE: 1/2" = 1'-0" 2' 1' 0 2'

RESTROOM 102 - EAST

BCT-1GB-1BCT-1

3'- 3"

MIRROR

PT-2(TYP.)

PT-3 (TYP.)

PT-2 (TYP.)

PT-3 (TYP.)

PT-2 (TYP.)

PT-3 (TYP.)

PT-2 (TYP.)

PT-3 (TYP.)

A4

INFILL OPENINGS (SEE PLANS)

RECESSED

A4

2'- 9 3

/4"

5' MINIMUM CLEARANCE

HAND WASH, SOAP

AND HAND DRYER

COMBO (TYP.)

2'-

2'-

ND-1

PH-1 (OWNER

PROVIDED,

CONTRACTOR

INSTALLED)

SCALE: 3/4" = 1'-0" 6" 0 18"6"

WALL SECTION DETAIL

2 1/2" RIGID INSULATION

5/8" EXTERIOR SHEATHING

3 5/8" METAL STUD

PORCELAIN TILE ON

CEMENT BOARD

SPRAY FOAM INSULATION

3 5/8" METAL STUD

PORCELAIN TILE ON

CEMENT BOARD

WALL VENT

EIFS SYSTEM

CHAMFER EDGE

EXISTING CONCRETE SLAB

EXISTING SUPPORT

WALLS TO REMAIN

EXISTING CONCRETE PANEL

TILE OVER EXISTING CONCRETE SLAB

TOP AND EDGE FLUSH TO WALL

PRE-FINISHED SHEET

METAL SILL FLASHING

WINDOW AS SCHEDULED

EXISTING STONE FACE

BACKER ROD AND SEALANT - BOTH

SIDES

PRE-FINISHED SHEET METAL

FLASHING WITH WEEP

LEVEL 01

ELEV. = 100'-0"

A4

ELEV. = 107'-0"

B.O. WINDOW

SCALE: 1-1/2" = 1'-0" 0"4"8" 8"

PLAN DETAIL

PT-3

EXISTING GRANITE

CEMENT BOARD

EXTERIOR

EIFS INFILL PANEL

EIFS SYSTEM

PORCELAIN TILE ON

CEMENT BOARD

3-5/8" METAL STUD

PORCELAIN TILE ON

CEMENT BOARD

5" +/-

3-5/8" METAL STUDS

1'-1 1/4"

DIAPER DISPOSAL UNIT

SCALE: 1-1/2" = 1'-0" 0"4"8" 8"

RECESSED WALL SECTION DETAIL

PORCELAIN TILE WRAPPING

TOP AND EDGE OF EXISTING

CONCRETE LEDGE

EXTERIOR

EXISTING GRANITE BEYOND

EXTERIOR SHEATHING

TREATED 2X BLOCKING

PRE-FINISHED SHEET METAL

FLASHING & WEEP

SPRAY FOAM INSULATION

EXISTING CONCRETE PANEL

STONE WALL FACE BEYOND

1"

SCALE: 1/2" = 1'-0" 2' 1' 0 2'

RESTROOM 103 - WEST

SCALE: 1/2" = 1'-0" 2' 1' 0 2'

RESTROOM 103 - NORTH

SCALE: 1/2" = 1'-0" 2' 1' 0 2'

RESTROOM 103 - EAST

SCALE: 1/2" = 1'-0" 2' 1' 0 2'

RESTROOM 103 - SOUTH

LEVEL 01

ELEV. = 100'-0"

GB-1

LEVEL 01

ELEV. = 100'-0"

LEVEL 01

ELEV. = 100'-0"

LEVEL 01

ELEV. = 100'-0"

BCT-1

GB-1

PH-1 (OWNER

PROVIDED

CONTRACTOR

INSTALLED)

BCT-1

MIRROR

ND-1

2'- 9 3

/4"

3'- 3"

PT-2 (TYP.)

PT-3 (TYP.)

PT-2 (TYP.)

PT-3 (TYP.)

PT-2 (TYP.)

PT-3 (TYP.)

PT-2 (TYP.)

PT-3 (TYP.)

A4

1 SIM.

INFILL OPENINGS (SEE PLANS)

RECESSED

A4

5' MINIMUM CLEARANCE

HAND WASH, SOAP

AND HAND DRYER

COMBO (TYP.)

2'-

2'-

A4

INTERIOR ELEVATIONS AND

WALL SECTION

DATE:

TECH. REVIEW:

SUB SHEET NO. TITLE OF SHEET

PMIS NO.

DRAWING NO.

SHEET

OF

DRAWN BY:

DESIGNED:

DJS

DJS

KJH

15 FEB 2024

80071

RENOVATE MAIN RESTROOMS FROM THE LINCOLN

AND WASHINGTON PARKING STRUCTURES

MOUNT RUSHMORE NATIONAL MEMORIAL

KEYSTONE, SOUTH DAKOTA

305644

F eb

9,

- 4

:3 3p m Y

:\1

\1

-0

M

OU

NT

R

US

HM

OR

E

RE

ST

RO

OM

S\

DR

AW

IN

GS

\X

RE

F\

-0

_M

OR

U

BA

TH

RO

OM

- A

-5

IN

TE

RI

OR

E

LE

VA

TI

ON

S.

dw g

- U

SE

R da ria n

LEVEL 01

ELEV. = 100'-0"

LEVEL 01

ELEV. = 100'-0"

SCALE: 1/2" = 1'-0" 2' 1' 0 2'

WOMEN'S RESTROOM

SCALE: 1/2" = 1'-0" 2' 1' 0 2'

WOMEN'S RESTROOM

MIRROR (TYP)

HAND WASH, SOAP

AND HAND DRYER

COMBO (TYP.)

S.S. FRAMED

OPENING

2'-

3'- 3"

PT-2 (TYP.)

PT-3 (TYP.)

PT-2 (TYP.)

PT-3 (TYP.)

A6

A6

3 SIM.

REV.

LEVEL 01

ELEV. = 100'-0"

LEVEL 01

ELEV. = 100'-0"

SCALE: 1/2" = 1'-0" 2' 1' 0 2'

MEN'S RESTROOM

SCALE: 1/2" = 1'-0" 2' 1' 0 2'

MEN'S RESTROOM

2'-

3'- 3"

PT-2 (TYP.)

PT-3 (TYP.)

A6

A6

3 SIM.

REV.

S.S. FRAMED

OPENING

MIRROR (TYP)

PT-3 (TYP.)

HAND WASH, SOAP AND

HAND DRYER COMBO (TYP.)

PT-2 (TYP.)

SCALE: 1/2" = 1'-0" 2' 1' 0 2'

MEN'S TOILETS

5'- 0"

URINAL SCREEN

(TYP.)

PT-2 (TYP.)

PT-3 (TYP.)

1'- 0"1'-

4" 2'- 0"

EXISTING GRILLES

TO REMAIN

EXISTING GRILLES

TO REMAIN

LEVEL 01

ELEV. = 100'-0"

SCALE: 1/2" = 1'-0" 2' 1' 0 2'

MENS STALLS

PT-2 (TYP.)

PT-3 (TYP.)

TOILET PARTITIONS

(TYP.)

EXISTING GRILLES

TO REMAIN

EXISTING GRILLES

TO REMAIN

SCALE: 1/2" = 1'-0" 2' 1' 0 2'

MEN'S RESTROOM

S.S. FRAMED

OPENING PT-2 (TYP.)

PT-3 (TYP.)

S.S. ACCESS

PANEL -SEE

MECHANICAL

URINAL SCREEN

TOILET PARTITION

A5

INTERIOR ELEVATIONS

DATE:

TECH. REVIEW:

SUB SHEET NO. TITLE OF SHEET

PMIS NO.

DRAWING NO.

SHEET

OF

DRAWN BY:

DESIGNED:

DJS

DJS

KJH

15 FEB 2024

80071

RENOVATE MAIN RESTROOMS FROM THE LINCOLN

AND WASHINGTON PARKING STRUCTURES

MOUNT RUSHMORE NATIONAL MEMORIAL

KEYSTONE, SOUTH DAKOTA

305644

F eb

9,

- 4

:3 3p m Y

:\1

\1

-0

M

OU

NT

R

US

HM

OR

E

RE

ST

RO

OM

S\

DR

AW

IN

GS

\X

RE

F\

-0

_M

OR

U

BA

TH

RO

OM

- A

-5

IN

TE

RI

OR

E

LE

VA

TI

ON

S.

dw g

- U

SE

R da ria n

LEVEL 01

ELEV. = 100'-0"

ROOF

ELEV. = 115'-0"

A4

EIFS INFILL

SCALE: 1/4" = 1'-0" 4' 2' 0 4'

FRONT ELEVATION

EXISTING GRANITE

3'- 3"

MIRROR (TYP.)

PT-2 (TYP.)

PT-3 (TYP.)

1/2" SOLID SURFACE SHELF

10"

EXISTING WALL

SCALE: 3/4" = 1'-0" 6" 0 18"6"

RESTROOM DETAIL AT SINKS

1'-6"

4'- 9"

CEILING AS SCHEDULED

ELEV. = 108'-0"

B.O. SOFFIT

LIGHT FIXTURE-

SEE ELECTRICAL

8"

5/8" GWB ON 3-5/8" METAL STUD

VERTICAL FRAMING AND 2-1/2" METAL

STUD HORIZONTAL FRAMING

PORCELAIN TILE ON

CEMENT BOARD AT FACE

CORNER GUARD - SEE SPECS

6"

A6

LEVEL 01

ELEV. = 100'-0"

PT-2 (TYP.)

PT-3 (TYP.)

TOILET PARTITIONS

(TYP.)

SCALE: 1/2" = 1'-0" 2' 1' 0 2'

WOMENS STALLS

7'- 0"

EXISTING GRILLES

TO REMAIN

EXISTING GRILLES

TO REMAIN

1'- 2"

4'- 8"

LEVEL 01

ELEV. = 100'-0"

PT-2 (TYP.)

PT-3 (TYP.)

SCALE: 1/2" = 1'-0" 2' 1' 0 2'

WOMENS STALLS

TOILET PARTITIONS

(TYP.)

EXISTING GRILLES

TO REMAIN

EXISTING GRILLES

TO REMAIN

SCALE: 1/4" = 1'-0" 4' 2' 0 4'

REAR ELEVATION

LEVEL 01

ELEV. = 100'-0"

ROOF

ELEV. = 115'-0"

ROOF LADDER

CENTERED BETWEEN

WINDOWS - SEE SPECS

RAILING TO EXTEND 4' BEYOND

END OF ROOFTOP MECHANICAL

ON BOTH SIDES - SEE ROOF PLAN

SCALE: 1/2" = 1'-0" 2' 1' 0 2'

WOMEN'S RESTROOM

S.S. FRAMED

OPENING

PT-2 (TYP.)

PT-3 (TYP.)

S.S. ACCESS

PANEL - SEE

MECHANICAL

TOILET PARTITION TOILET PARTITION

1 1 /4"

PLYWOOD

SOLID SURFACE

PT-3 ON CEMENT BOARD

4"SCALE: 3" = 1'-0" 2"0 8"

SOLID SURFACE COUNTER DETAIL

A6

ELEVATIONS, INTERIOR

ELEVATION AND SECTION

DATE:

TECH. REVIEW:

SUB SHEET NO. TITLE OF SHEET

PMIS NO.

DRAWING NO.

SHEET

OF

DRAWN BY:

DESIGNED:

DJS

DJS

KJH

15 FEB 2024

80071

RENOVATE MAIN RESTROOMS FROM THE LINCOLN

AND WASHINGTON PARKING STRUCTURES

MOUNT RUSHMORE NATIONAL MEMORIAL

KEYSTONE, SOUTH DAKOTA

305644

F eb

9,

- 4

:3 3p m Y

:\1

\1

-0

M

OU

NT

R

US

HM

OR

E

RE

ST

RO

OM

S\

DR

AW

IN

GS

\X

RE

F\

-0

_M

OR

U

BA

TH

RO

OM

- A

-5

IN

TE

RI

OR

E

LE

VA

TI

ON

S.

dw g

- U

SE

R da ria n

5'-0" CLR.

3'- 0"

C

LR

A7

SCALE: 3/4" = 1'-0" 6" 0 18"6"

WOMEN'S RESTROOM - ENLARGED PLAN

5'- 0"

C

LR

2'-

7 1 /2"

C

LR

2'-

7 1 /2"

C

LR

2'-

7 1 /2"

C

LR

2'-

7 1 /2"

C

LR

2'- 6"

C

LR

2'-

6" C

LR

2'- 6"

C

LR

2'-

6" C

LR

2'- 6 3

/8" C

LR

5'-0" CLR.

ND-1

PH-1 (OWNER PROVIDED,

CONTRACTOR INSTALLED) (TYP.)

ND-2

ND-2

ND-2

ND-2

ND-2

5'- 0 1

/4" C

LR

5'-0" CLR.

SCALE: 3/4" = 1'-0" 6" 0 18"6"

MEN'S RESTROOM - ENLARGED PLAN

A7

2'- 7 1

/2" C

LR

2'- 7 1

/2" C

LR

2'- 7 1

/2" C

LR

2'- 7 1

/4" C

LR

PH-1 (OWNER PROVIDED,

CONTRACTOR INSTALLED (TYP.)

PH-1 (OWNER PROVIDED,

CONTRACTOR INSTALLED)

ND-1

SC-1

PT-2(TYP.)

PT-3 (TYP.)

TOILET

PARTITION

GB-1

2'-

1'-0" 3'-6"

PT-2 (TYP.)

PT-3 (TYP.)

5' MINIMUM CLEARANCE

TOILET

PARTITION

1'-6"

3'-0" 6"

1'-0"2'-0"

SCALE: 1/2" = 1'-0" 2' 1' 0 2'

WOMEN'S RESTROOM - ELEVATION

SCALE: 1/2" = 1'-0" 2' 1' 0 2'

WOMEN'S RESTROOM - ELEVATION

GB-1

PH-1 (OWNER PROVIDED,

CONTRACTOR INSTALLED)

PT-2 (TYP.)

PT-3 (TYP.)

TOILET

PARTITION

GB-1

2'-

1'-0"3'-6"

GB-1

PT-2 (TYP.)

PT-3 (TYP.)

5' MINIMUM CLEARANCE

TOILET

PARTITION

1'-6"

3'-0"6"

1'-0" 2'-0"

SCALE: 1/2" = 1'-0" 2' 1' 0 2'

MEN'S RESTROOM - ELEVATION

SCALE: 1/2" = 1'-0" 2' 1' 0 2'

MEN'S RESTROOM - ELEVATION

ND-1

LEVEL 01

ELEV. = 100'-0"

SCALE: 1/2" = 1'-0" 2' 1' 0 2'

WOMEN'S LOBBY

SCALE: 1/2" = 1'-0" 2' 1' 0 2'

MEN'S LOBBY

RELOCATED CAMERA - SEE ELECTRICAL RELOCATED CAMERA - SEE ELECTRICAL

A7

ENLARGED FLOOR PLANS

DATE:

TECH. REVIEW:

SUB SHEET NO. TITLE OF SHEET

PMIS NO.

DRAWING NO.

SHEET

OF

DRAWN BY:

DESIGNED:

DJS

DJS

KJH

15 FEB 2024

80071

RENOVATE MAIN RESTROOMS FROM THE LINCOLN

AND WASHINGTON PARKING STRUCTURES

MOUNT RUSHMORE NATIONAL MEMORIAL

KEYSTONE, SOUTH DAKOTA

305644

F eb

9,

- 4

:3 3p m Y

:\1

\1

-0

M

OU

NT

R

US

HM

OR

E

RE

ST

RO

OM

S\

DR

AW

IN

GS

\X

RE

F\

-0

_M

OR

U

BA

TH

RO

OM

- A

-5

IN

TE

RI

OR

E

LE

VA

TI

ON

S.

dw g

- U

SE

R da ria n

WOMEN'S

LOBBY

RESTROOM

RESTROOM

103 MEN'S

LOBBY

WOMEN'S

RESTROOM

MEN'S

RESTROOM

JANITOR

ROOM

MECHANICAL

ROOM

CLOSET

WOMEN'S

TOILETS

MEN'S

TOILETS

A01 A01

A01A01

DATE:

TECH. REVIEW:

SUB SHEET NO. TITLE OF SHEET

PMIS NO.

DRAWING NO.

SHEET

OF

DRAWN BY:

DESIGNED:

DJS

DJS

KJH

15 FEB 2024

80071

RENOVATE MAIN RESTROOMS FROM THE LINCOLN

AND WASHINGTON PARKING STRUCTURES

MOUNT RUSHMORE NATIONAL MEMORIAL

KEYSTONE, SOUTH DAKOTA

305644

F eb

9,

- 5

:0 4p m Y

:\1

\1

-0

M

OU

NT

R

US

HM

OR

E

RE

ST

RO

OM

S\

DR

AW

IN

GS

\X

RE

F\

F

LO

OR

IN

G

PL

AN

.d wg

US

ER

d ar ian

FINAL CONSTRUCTION DOCUMENTS

A8

FLOOR PLAN - FLOORING

SCALE: 1/4" = 1'-0" 4' 2' 0 4'

FLOORING - FLOOR PLAN

N1

ARCHITECTURE - KEYNOTES:

A01 FLOORING TRANSITION STRIP - SEE SPECS

NOTES

DOOR AND FRAME SCHEDULE

NO. SIZE TYPE MAT.

FRAME

TYPE MAT. DEPTH DETAILS SHEET

DOOR

GLASS

KEY

TYPE

HDWR

SET

FIRE

RATING

DOOR

WD WOOD

HM HOLLOW METAL

AL ALUMINUM

SS STAINLESS STEEL

WG WIRE GLASS

CTG CLEAR TEMPERED GLASS

CTIG CLEAR TEMPERED INSULATED GLASS

LDG 9/16" LAMINATED DOOR GLASS

FRG 60-MINUTE FIRE-RATED GLASS

LEGEND

101 PR 3'-0" x 7'-0" x 1-3/4" EXIST. -- EXIST. -- -- -- -- -- -- 1 102 3'-0" x 7'-0" x 1-3/4" D01 SS F1 HM 5-7/8" -- -- HW # 1 -- 103 3'-0" x 7'-0" x 1-3/4" D01 SS F1 HM 5-7/8" -- -- HW # 1 -- 104 PR 3'-0" x 7'-0" x 1-3/4" EXIST. -- -- -- -- -- -- -- -- 1 105 4'-0" x 7'-0" x 1-3/4" D01 SS F1 HM 8-1/4" -- -- HW # 2 -- 106 4'-0" x 7'-0" x 1-3/4" D01 SS F1 HM 8-1/4" -- -- HW # 2 -- 107A 3'-0" x 7'-0" x 1-3/4" D01 SS F1 HM 8-1/4" -- -- HW # 3 -- 107B 3'-0" x 7'-0" x 1-3/4" D01 SS F1 HM 8-1/4" -- -- HW # 3 -- 108 3'-0" x 7'-0" x 1-3/4" EXIST. -- EXIST. -- -- -- -- -- -- 109 3'-0" x 7'-0" x 1-3/4" EXIST. -- EXIST. -- -- -- -- -- --

NOTES

ROOM FINISH SCHEDULE

NO. DESCRIPTION FLOOR BASE

NORTH WALL EAST WALL SOUTH WALL WEST WALL CEILING

MAT. FIN. MAT. FIN. HEIGHTMAT. FIN. MAT. FIN. MAT. FIN.

ATC ACOUSTICAL TILE CEILING

CONC CONCRETE

CPT CARPET

CT CERAMIC TILE

CTG CLEAR TEMPERED GLASS

EXIST. EXISTING

EXP EXPOSED

GWB GYPSUM WALLBOARD

P PAINT

RB RUBBER BASE

SC SPECIAL COATING

SS STAINLESS STEEL

PT PORCELAIN TILE

VB VINYL BASE

VT VINYL TILE

WP WALL PANEL

ROOM FINISH SCHEDULE LEGEND

NOTE: REFER TO COLOR SCHEDULE FOR ALL INTERIOR FINISHES.

101 WOMEN'S LOBBY EXIST. EXIST./RB-1 GWB P-1 GWB P-1 GWB P-1 GWB P-1 GWB P-2 10'-0" 4

102 RESTROOM PT-1 PT-2 PT-3 -- PT-3 -- PT-3 -- PT-3 -- GWB P-2 10'-0" 3

103 RESTROOM PT-1 PT-2 PT-3 -- PT-3 -- PT-3 -- PT-3 -- GWB P-2 10'-0" 3

104 MEN'S LOBBY EXIST. EXIST./ RB-1 GWB P-1 GWB P-1 GWB P-1 GWB P-1 GWB P-2 10'-0" 5

105 MEN'S RESTROOM PT-1 PT-2 PT-3 -- PT-3 -- PT-3 -- PT-3 -- GWB P-2 9'-6" 2, 3

106 WOMEN'S RESTROOM PT-1 PT-2 PT-3 -- PT-3 -- PT-3 -- PT-3 -- GWB P-2 9'-6" 2, 3 107 JANITOR ROOM EXIST. RB-1 EXIS/GWB P-1 EXIST. -- EXIS/GWB P-1 EXIST. -- EXP. -- --

108 CLOSET EXIST. EXIST. EXIST. -- EXIST. -- EXIST. -- EXIST. -- EXIST. -- --

109 MECHANICAL ROOM EXIST. EXIST. EXIST. EXIST. EXIST. EXIST. EXIST. EXIST. EXIST. EXIST. EXP. -- -- 110 WOMEN'S TOILET ROOM PT-1 PT-2 PT-3 -- PT-3 -- PT-3 -- PT-3 -- GWB P-2 9'-6" 1, 3 111 MEN'S TOILET ROOM PT-1 PT-2 PT-3 -- PT-3 -- PT-3 -- PT-3 -- GWB P-2 9'-6" 1, 3

ROOM FINISH SCHEDULE NOTES:

DOOR AND FRAME SCHEDULE NOTES:

1. ADD NEW DOOR OPERATOR AND PUSH BUTTON

2. SEE ARCH PLANS FOR S.S. FRAME F2 AT OPENING

INTO MENS AND WOMENS TOILET STALL AREAS.

1. SEE RCP FOR BULKHEAD AND HIGHER CEILING AT WINDOWS.

2. SEE RCP FOR BULKHEAD AT LIGHT COVE.

3. SEE SPECS FOR ALUMINUM COVE AT BASE AND FLOORING TRANSITION.

4. INSTALL VINYL BASE ON NORTH WALL. EXISTING BASE TO REMAIN IN REST OF ROOM.

5. INSTALL VINYL BASE ON SOUTH WALL. EXISTING BASE TO REMAIN IN REST OF ROOM.

SCALE: 1/4" = 1'-0" 4' 2' 0 4'

DOOR TYPES

SCALE: 1/4" = 1'-0" 4' 2' 0 4'

FRAME TYPES

CONTROL JOINT

ON EACH SIDE

OF FRAME TO

CEILING

SCALE: 1/4" = 1'-0" 4' 2' 0 4'

TYPICAL CONTROL JOINT DETAILS AT GWB

SEE SCHED.

SE

E

SC

HE

DU

LE

FLOOR

LINE

D01

STAINLESS STEELF1

A

A

S.S. FRAME

2'- 8"

VE

RI

FY

6'-4 3/4"

F2

F.

V.

B

B

SIM.

F3

3'- 4"

2'-8"

SEE SCHED.

SE

E

SC

HE

DU

LE

C

C

S.S. FRAME

F4

CTIG

EXISTING

ALUMINUM

FRAMING

RE-GLAZE

WITH CTIG

A4

A1

1'SCALE: 1" = 1'-0" 0 1' 2'

WALL TYPES

SE

E

SC

HE

DU

LE

EXISTING 3-5/8" METAL

STUD

B1

GWB CEILING

SE

E

SC

HE

DU

LE

3-5/8" METAL STUD

WALL TILE AS SCHEDULED

C1

6" METAL STUD

6"

5/8 GWB

CEMENT BOARDSE

E

SC

HE

DU

LE

GWB CEILING

WALL TILE AS SCHEDULED

BASE AS SCHEDULED

EXISTING 5/8" GWB

CEMENT BOARD

WALL TILE AS

SCHEDULED

6"

GWB CEILING

SE

E

SC

HE

DU

LE

3-5/8" METAL STUD

CEMENT BOARD -

BOTH SIDES

WALL TILE AS

SCHEDULED - BOTH

SIDES

6"

GWB CEILING

A2

6"

D1

6" METAL STUD

6"

CEMENT BOARD - BOTH SIDES

SE

E

SC

HE

DU

LE

GWB CEILING

WALL TILE AS SCHEDULED -

BOTH SIDES

BASE AS SCHEDULED

CEMENT BOARD

BATT INSULATION

BATT INSULATION

BATT INSULATION

BATT INSULATION

BATT INSULATION

LOBBY SIDERESTROOM SIDE

METAL STUDS

SCALE: 1-1/2" = 1'-0" 8"4"0 16"

HEAD/JAMB DETAIL

A

5/8

2"

SPOT GROUT

HOLLOW METAL FRAME

DOOR AS SCHEDULED

SCALE: 1-1/2" = 1'-0" 8"4"0 16"

HEAD/JAMB DETAIL

B

ALUMINUM FRAME

2"

"J" MOLD EA SIDE

GLAZING

SEE FLOOR PLAN

FOR WALL TYPE

SEE FLOOR PLAN

FOR WALL TYPE

6" METAL STUD FRAMING

SCALE: 1-1/2" = 1'-0" 8"4"0 16"

HEAD/JAMB DETAIL

C

2"

SPOT GROUT

STAINLESS STEEL FRAME

PORCELAIN TILE ON

CEMENT BOARD

DATE:

TECH. REVIEW:

SUB SHEET NO. TITLE OF SHEET

PMIS NO.

DRAWING NO.

SHEET

OF

DRAWN BY:

DESIGNED:

DJS

DJS

KJH

15 FEB 2024

80071

RENOVATE MAIN RESTROOMS FROM THE LINCOLN

AND WASHINGTON PARKING STRUCTURES

MOUNT RUSHMORE NATIONAL MEMORIAL

KEYSTONE, SOUTH DAKOTA

305644

F eb

9,

- 5

:0 4p m Y

:\1

\1

-0

M

OU

NT

R

US

HM

OR

E

RE

ST

RO

OM

S\

DR

AW

IN

GS

\ 1

-0

_A

6.

dw g

- U

SE

R da ria n

FINAL CONSTRUCTION DOCUMENTS

SCHEDULES, DOORS,

FRAMES AND WALL TYPESA9

LOBBY

RESTROOM

RESTROOM

103 MEN'S

LOBBY

WOMEN'S

RESTROOM

MEN'S

RESTROOM

JANITOR

ROOM

MECHANICAL

ROOM

CLOSET

WOMEN'S

TOILETS

MEN'S

TOILETS

A01

A01A01

A01 A01

A01A01

A02A02

A01A01

A01A01A02 A02

A10

A6

A10

A6

A01

A03 A03

SIM.

ELEV. = 109'-6"

FINISH FLOOR

ELEV. = 110'-0"

FINISH FLOOR

MOISTURE RESISTANT GWB

ON 3-5/8" METAL STUDS

3'- 6"

GALVANIZED STEEL 1-1/2" STANDARD PIPE RAIL -

ANCHOR TO SIDE OF GRANITE W/ 3/8" EPOXY

ANCHOR BOLTS - SEE ROOF PLAN FOR LENGTH.

UPRIGHTS AT 6' O.C. MAX. +/

- 8

2'-0"

EXISTING WINDOW

A10

REFLECTED CEILING PLAN

SCALE: 1/4" = 1'-0" 4' 2' 0 4'

CEILING PLAN

N1

DATE:

TECH. REVIEW:

SUB SHEET NO. TITLE OF SHEET

PMIS NO.

DRAWING NO.

SHEET

OF

DRAWN BY:

DESIGNED:

DJS

DJS

KJH

15 FEB 2024

80071

RENOVATE MAIN RESTROOMS FROM THE LINCOLN

AND WASHINGTON PARKING STRUCTURES

MOUNT RUSHMORE NATIONAL MEMORIAL

KEYSTONE, SOUTH DAKOTA

305644

F eb

9,

- 5

:0 5p m Y

:\1

\1

-0

M

OU

NT

R

US

HM

OR

E

RE

ST

RO

OM

S\

DR

AW

IN

GS

\X

RE

F\

-0

_M

OR

U

BA

TH

RO

OM

A-

CP

LA

N.

dw g

- U

SE

R da ria n

FINAL CONSTRUCTION DOCUMENTS

ARCHITECTURE - KEYNOTES:

A01 GWB CEILING SHOWN HATCHED

A02 GWB BULKHEAD

A03 12" X 12"ACCESS PANEL - COORDINATE LOCATION WITH VALVE - SEE MECHANICAL

SCALE: 3/4" = 1'-0" 6" 0 18"6"

CEILING PLAN SECTION

ROOF TOP MECHANICAL

UNIT - SEE MECHANICAL

RAILING TO EXTEND 4' BEYOND

END OF ROOFTOP MECHANICAL

ON BOTH SIDES

+/- 18'-2 3/4"

EXHAUST VENT - SEE

MECHANICAL

CONDENSING UNITS - SEE

MECHANICAL

A10

A11

4'-0"4'-0"

A11

(TYP.)

PROPANE GAS PIPING ROOF

PENETRATION - SEE MECHANICAL

HIGH DOMED, CAPPED GASKETED

FASTENERS AS REQUIRED

WOOD BLOCKING AS

REQUIRED

METAL CURB

COUNTER FLASHING

EXISTING

RIGID INSULATION

EXISTING BALLAST

EXISTING ROOF

MEMBRANE

EXISTING

ROOF STRUCTURE

SCALE: 1-1/2" = 1'-0" 8"4"0 16"

ROOF CURB DETAIL

" M

IN

8"

CANT STRIP FILLER

SELF-ADHERED MEMBRANE FLASHING

1'-1 3/4" (VERIFY)

MAX OPENING SIZE

SAWCUT AND REMOVE CONCRETE SLAB

BETWEEN CONCRETE JOISTS - VERIFY

LOCATION BY PILOT HOLE PRIOR TO CUTTING

EXISTING CONCRETE ROOF JOISTS - DO NOT

CUT OR DAMAGE.

A11

ROOF PLAN

DATE:

TECH. REVIEW:

SUB SHEET NO. TITLE OF SHEET

PMIS NO.

DRAWING NO.

SHEET

OF

DRAWN BY:

DESIGNED:

DJS

DJS

KJH

15 FEB 2024

80071

RENOVATE MAIN RESTROOMS FROM THE LINCOLN

AND WASHINGTON PARKING STRUCTURES

MOUNT RUSHMORE NATIONAL MEMORIAL

KEYSTONE, SOUTH DAKOTA

305644

F eb

9,

- 4

:5 6p m Y

:\1

\1

-0

M

OU

NT

R

US

HM

OR

E

RE

ST

RO

OM

S\

SU

BM

IT

TA

LS

\0 3_

0%

F

IN

AL

S

UB

M

IT

TA

L\

DR

AW

IN

GS

\D

W G' s\ A1

1.

dw g

- U

SE

R da ria n

FINAL CONSTRUCTION DOCUMENTS

SCALE: 1/4" = 1'-0" 4' 2' 0 4'

ROOF PLAN

N1

DEMOLITION NOTES:

1. CONTRACTOR IS URGED TO VISIT SITE AND FIELD VERIFY ALL EXISTING CONDITIONS

PRIOR TO BIDDING PROJECT.

2. THE OWNER SHALL HAVE THE FIRST RIGHT OF SALVAGE FOR ALL MECHANICAL,

ELECTRICAL, AND PLUMBING ITEMS BEING REMOVED. IF OWNER DECLINES, THE

CONTRACTOR SHALL REMOVE FROM THE PREMISES AND DISPOSE OF PROPERLY.

VERIFY OWNER'S INTENT PRIOR TO REMOVAL OR DEMOLITION.

3. INFORMATION PERTAINING TO THE EXISTING BUILDING HAS BEEN OBTAINED THROUGH

THE BUILDINGS ORIGINAL DRAWINGS WHERE AVAILABLE. REPORT DISCREPANCIES TO

THE ARCHITECT/ENGINEER PRIOR TO ANY DEMOLITION. CONTRACTOR SHALL FIELD

VERIFY ALL EXISTING CONDITIONS PRIOR TO COMMENCING WORK.

4. COORDINATE SHUT DOWN OF ALL UTILITIES FOR DEMOLITION WORK WITH THE OWNER.

5. DISCONNECT AND REMOVE MECHANICAL SYSTEMS, EQUIPMENT, AND COMPONENTS AS

INDICATED TO BE REMOVED.

PIPING TO BE REMOVED: REMOVE PORTION OF PIPING INDICATED TO BE REMOVED AND

CAP REMAINING PIPING WITH THE SAME OR COMPATIBLE PIPING MATERIAL.

PIPING TO BE ABANDONED IN PLACE: DRAIN PIPING AND CAP WITH THE SAME OR

COMPATIBLE PIPING MATERIAL.

DUCTS TO BE REMOVED: REMOVE PORTIONS OF DUCT AND CAP REMAINING DUCTS

WITH THE SAME OR COMPATIBLE DUCTWORK MATERIAL.

DUCTS TO BE ABANDONED IN PLACE: CAP DUCTS WITH THE SAME OR COMPATIBLE

DUCTWORK MATERIAL.

EQUIPMENT TO BE REMOVED: DISCONNECT AND CAP SERVICES AND REMOVE

EQUIPMENT.

EQUIPMENT TO BE REMOVED AND REINSTALLED: DISCONNECT AND CAP SERVICES AND

REMOVE, CLEAN, AND STORE EQUIPMENT. WHEN APPROPRIATE, REINSTALL,

RECONNECT, AND MAKE EQUIPMENT FULLY OPERATIONAL.

EQUIPMENT TO BE REMOVED AND SALVAGED: DISCONNECT AND CAP SERVICES AND

REMOVE EQUIPMENT AND DELIVER TO OWNER.

6. IF PIPE OR EQUIPMENT INSULATION TO REMAIN IS DAMAGED DURING THE

PERFORMANCE OF THIS PROJECT, THE CONTRACTOR SHALL REMOVE DAMAGED OR

UNSERVICEABLE PORTIONS AND REPLACE WITH NEW PRODUCTS OF EQUAL CAPACITY

AND QUALITY.

7. COORDINATE DEMOLITION WITH THE WORK OF OTHER TRADES. PROVIDE TEMPORARY

UTILITIES AS REQUIRED TO ALLOW THE WORK OF OTHER TRADES TO PROCEED.

8. DUCTWORK, PIPING, PLUMBING, AND EQUIPMENT SHOWN BOLD SHALL BE REMOVED TO

THE EXTENTS INDICATED.

HVAC GENERAL NOTES:

1. DO NOT RUN DUCTWORK , PIPING, AND PLUMBING ABOVE ELECTRICAL

PANELS OR IN CODE REQUIRED CLEARANCE SPACES. COORDINATE ALL

ROUTING WORK WITH ALL OTHER TRADES.

2. DO NOT RUN DUCTWORK, PIPING, AND PLUMBING ABOVE OR THROUGH

INFORMATION TECHNOLOGY AND DATA CLOSETS, IDF, AND MDF ROOMS.

COORDINATE ALL ROUTING WITH ALL OTHER TRADES.

3. DRAWINGS, PLANS, SCHEMATICS, AND DIAGRAMS INDICATE THE GENERAL

LOCATIONS AND THE ARRANGEMENT OF SYSTEMS. WHEREVER PRACTICAL,

INSTALL SYSTEMS AS INDICATED. PROVIDE OFFSETS AND ELEVATION

CHANGES TO DUCTWORK, PIPING, AND PLUMBING AS REQUIRED TO

COMPLETE THE LAYOUT AND COORDINATION PROCESS AS WELL AS MEET

ALL REQUIREMENTS OF THE CONTRACT DOCUMENTS.

4. SEE ARCHITECTURAL REFLECTED CEILING PLANS FOR DIFFUSER,

REGISTER, GRILLE, AND CEILING MOUNTED DEVICE LOCATIONS.

5. CONTRACTOR SHALL COORDINATE LOCATION OF DUCTWORK IN CEILING

SPACE WITH ALL TRADES PRIOR TO FABRICATION AND INSTALLATION OF

DUCTWORK.

6. FOR GENERAL DUCTWORK CONSTRUCTION, SEE DUCT FITTING DETAILS.

7. DUCTWORK AND EQUIPMENT SHOWN WITH THIN LINES INDICATES EXISTING

TO REMAIN. DUCTWORK AND EQUIPMENT SHOWN WITH BOLD LINES

INDICATES NEW.

8. PROVIDE VOLUME DAMPER IN ALL BRANCH TAKEOFFS CONNECTING TO

DIFFUSERS, REGISTERS, OR GRILLES AND IN LOCATIONS INDICATED.

9. PROVIDE REMOTE VOLUME DAMPER BALANCING POSITION CONTROL FOR

ALL VOLUME DAMPERS MOUNTED ABOVE NON-ACCESSIBLE CEILINGS.

10. PROVIDE CLEARANCES TO ALL EQUIPMENT AS REQUIRED BY

MANUFACTURERS' INSTALLATION AND OPERATION REQUIREMENTS AND/OR

BY CODE.

11. INSTALL ALL DUCT AND PIPING IN MECHANICAL ROOMS AS HIGH AS

POSSIBLE. PROVIDE 7'-6" MINIMUM HIGH ACCESS PATHWAYS TO ALL

EQUIPMENT.

12. COORDINATE LOCATIONS OF ALL EQUIPMENT HOUSEKEEPING PADS WITH

GENERAL CONTRACTOR. MECHANICAL CONTRACTOR IS RESPONSIBLE FOR

INSTALLATION OF EQUIPMENT HOUSEKEEPING PADS.

13. CAP ENDS OF ALL INSTALLED DUCTWORK DURING CONSTRUCTION TO

MINIMIZE DIRT, DEBRIS, AND FOREIGN OBJECTS FROM ENTERING THE DUCT

SYSTEM.

14. COORDINATE SCHEDULE OF SHUTDOWN FOR EXISTING HVAC SYSTEMS,

FOR INSTALLATION OF NEW HVAC SYSTEMS, WITH THE OWNER'S

REPRESENTATIVE PRIOR TO SHUTDOWN.

15. ALL INSULATION SHALL MEET THE ENERGY CODE'S INSTALLED R VALUE

REQUIREMENTS.

FIRE PROTECTION GENERAL NOTES:

1. COORDINATE LOCATION OF FIRE SPRINKLER PIPING AND HEADS WITH

ALL TRADES PRIOR TO FINALIZATION OF SHOP DRAWINGS AND

HYDRAULIC CALCULATIONS.

2. SEE ARCHITECTURAL REFLECTED CEILING PLANS FOR LOCATIONS OF

ALL CEILING MOUNTED DEVICES.

3. COORDINATE SHUT DOWN OF EXISTING FIRE SERVICE WITH OWNERS

REPRESENTATIVE.

4. ALL WORK SHALL COMPLY WITH NFPA AND THE LOCAL AUTHORITIES

HAVING JURISDICTION, AND OWNERS INSURANCE CARRIER.

5. DIELECTRIC NIPPLES OR FLANGE INSULATION KITS SHALL BE UTILIZED

FOR ALL DISSIMILAR PIPE CONNECTIONS. DIELECTRIC UNIONS WILL

NOT BE ACCEPTED.

PIPING GENERAL NOTES:

1. DO NOT RUN PIPING, PLUMBING, AND DUCTWORK ABOVE ELECTRICAL

PANELS OR IN CODE REQUIRED CLEARANCE SPACES. COORDINATE ALL

ROUTING WORK WITH ALL OTHER TRADES.

2. DRAWINGS, PLANS, SCHEMATICS, AND DIAGRAMS INDICATE THE GENERAL

LOCATIONS AND THE ARRANGEMENT OF SYSTEMS. WHEREVER PRACTICAL,

INSTALL SYSTEMS AS INDICATED. PROVIDE OFFSETS AND ELEVATION

CHANGES TO PIPING, PLUMBING, AND DUCTWORK AS REQUIRED TO

COMPLETE THE LAYOUT AND COORDINATION PROCESS AS WELL AS MEET

ALL REQUIREMENTS OF THE CONTRACT DOCUMENTS.

3. SIZE AND ROUTE REFRIGERANT PIPING PER MANUFACTURERS'

RECOMMENDATIONS.

4. ROUTE ALL HORIZONTAL HVAC PIPING IN MECHANICAL ROOMS AT A

MINIMUM OF 7'-6" ABOVE FINISHED FLOOR.

5. PIPING AND EQUIPMENT SHOWN WITH THIN LINES INDICATES EXISTING TO

REMAIN. PIPING AND EQUIPMENT SHOWN WITH BOLD LINES INDICATES NEW.

6. ALL PIPING INSULATION SHALL MEET THE ENERGY CODE'S INSTALLED R

VALUE REQUIREMENTS.

7. DIELECTRIC NIPPLES OR FLANGE INSULATION KITS SHALL BE UTILIZED FOR

ALL DISSIMILAR PIPE CONNECTIONS. DIELECTRIC UNIONS WILL NOT BE

ACCEPTED.

PLUMBING GENERAL NOTES:

1. DO NOT RUN PLUMBING, PIPING, AND DUCTWORK ABOVE ELECTRICAL

PANELS OR IN CODE REQUIRED CLEARANCE SPACES. COORDINATE ALL

ROUTING WORK WITH ALL OTHER TRADES.

2. DO NOT RUN PLUMBING, PIPING, AND DUCTWORK ABOVE OR THROUGH

INFORMATION TECHNOLOGY AND DATA CLOSETS, IDF, AND MDF ROOMS.

COORDINATE ALL ROUTING WITH ALL OTHER TRADES.

3. DRAWINGS, PLANS, SCHEMATICS, AND DIAGRAMS INDICATE THE GENERAL

LOCATIONS AND THE ARRANGEMENT OF SYSTEMS. WHEREVER PRACTICAL,

INSTALL SYSTEMS AS INDICATED. PROVIDE OFFSETS AND ELEVATION

CHANGES TO PLUMBING, PIPING, AND DUCTWORK AS REQUIRED TO

COMPLETE THE LAYOUT AND COORDINATION PROCESS AS WELL AS MEET

ALL REQUIREMENTS OF THE CONTRACT DOCUMENTS.

4. CLEAN EXISTING UNDERGROUND SANITARY PIPING TO MANHOLE

CONNECTION AND ALL EXISTING ABOVEGROUND SANITARY PIPING IN

CRAWLSPACE WITH CABLE AND BLADE PRIOR TO INSTALLATION AND

CONNECTION OF NEW PIPING. VISUALLY INSPECT PIPING AFTER CLEANING

TO CHECK FOR DAMAGE. REPAIR ANY PIPING FAILURE DUE TO CLEANING.

5. SEE SPECIFICATIONS OR PLUMBING FIXTURE SCHEDULE FOR ALL PLUMBING

CONNECTION SIZES TO ALL PLUMBING FIXTURES.

6. LOCATE PLUMBING VENTS THROUGH THE ROOF AT A MINIMUM OF 10'-0"

AWAY FROM ALL OUTDOOR AIR INTAKES ON HVAC EQUIPMENT OR

OPERABLE WINDOWS.

7. PROVIDE WALL AND FLOOR MOUNTED SEWER CLEANOUTS AS REQUIRED BY

CODE AND AS INDICATED. COORDINATE LOCATION IN FIELD.

8. INSTALL AND ROUTE ALL FUEL GAS PIPING AS REQUIRED BY CODE.

9. TERMINATE ALL GAS FLUE VENTS A MINIMUM OF 2'-0" HIGHER THAN ANY

SURFACE OR EQUIPMENT WITHIN 10'-0" OR AS REQUIRED BY CODE.

10. PROVIDE GAS PRESSURE REGULATORS ON ALL GAS FIRED EQUIPMENT,

INCLUDING REGULATOR VENT PIPING, SHUTOFF VALVE, DIRT LEG, AND

UNION. REGULATE GAS PRESSURE AS REQUIRED FOR EACH SPECIFIC PIECE

OF GAS FIRED EQUIPMENT AND PER MANUFACTURER'S RECOMMENDATIONS.

11. DO NOT ROUTE PLUMBING BRANCHES OR MAINS WITHIN SPACE REQUIRED

TO SERVICE ALL HVAC EQUIPMENT ABOVE CEILINGS.

12. PIPING AND FIXTURES SHOWN WITH THIN LINES INDICATES EXISTING TO

REMAIN. PIPING AND FIXTURES SHOWN WITH BOLD LINES INDICATES NEW.

13. COORDINATE SHUT DOWN OF EXISTING WATER SERVICE WITH OWNERS

REPRESENTATIVE.

14. FURNISH AND INSTALL SHUT-OFF VALVES FOR WATER SUPPLY AT ALL

EQUIPMENT ITEMS.

15. COORDINATE FINISH FLOOR ELEVATIONS TO SET FLOOR DRAINS AND FLOOR

SINKS.

16. SAW CUT AND REMOVE FLOOR AS REQUIRED FOR INSTALLATION OF NEW

PIPING.

17. PIPING IN EXTERIOR BUILDING WALLS SHALL BE LOCATED ON THE WARM

SIDE OF BUILDING INSULATION AND VAPOR BARRIER. BUILDING INSULATION

SHALL RUN CONTINUOUS BETWEEN PIPING AND EXTERIOR OF BUILDING.

18. PVC PIPING SHALL NOT BE INSTALLED IN RETURN AIR PLENUMS.

19. SEE WATER HAMMER ARRESTOR DETAIL FOR WATER HAMMER ARRESTOR

REQUIREMENTS ON DOMESTIC WATER PIPING.

1. THIN LINE ITEMS INDICATE EXISTING TO REMAIN. BOLD LINE ITEMS INDICATE

NEW WORK.

2. CONTRACTOR IS RESPONSIBLE FOR ANY CUTTING AND PATCHING NEEDED

FOR MECHANICAL INSTALLATION. PATCHING MUST MATCH EXISTING.

GENERAL NOTES:

Fe br ua ry

, 2

2:0 1p m

_M

0.1 .dw g mg re go ry

NOTE:

DO NOT SCALE DRAWINGS. VERIFY ALL DIMENSIONS

and clearances from ARCHITECTURAL, STRUCTURAL, shop and other appropriate drawing or at site. lay out and coordinate all work prior to installation to provide clearances required for operation, maintenance, and codes and verify non-interference with other work. DO NOT FABRICATE

PRIOR TO VERIFICATION OF CLEARANCE FOR ALL

TRADES. READ SPECIFICATIONS.

COPYRIGHT 2024

Permission to reproduce all or part of this drawing is hereby granted solely for the limited purpose of construction of this project or archiving. Unauthorized copying, disclosure or construction use without written permission of Alvine Engineering is prohibited by copyright law.

AE# 20239894

DATE:

TECH. REVIEW:

SUB SHEET NO. TITLE OF SHEET

PMIS NO.

DRAWING NO.

SHEET

OF

DRAWN BY:

DESIGNED:

15 FEB 2024

80071

RENOVATE MAIN RESTROOMS FROM THE LINCOLN

AND WASHINGTON PARKING STRUCTURES

MOUNT RUSHMORE NATIONAL MEMORIAL

KEYSTONE, SOUTH DAKOTA

305644

FINAL CONSTRUCTION DOCUMENTS

MRG

MRG

BAH

MECHANICAL GENERAL NOTES

M0.1

AutoCAD SHX Text C

F

SM

FHC

FVC

PIV

FS

DESCRIPTIONSYMBOLSYMBOL DESCRIPTION SYMBOL DESCRIPTION

FIRE PROTECTION

FIRE LINE

CEILING CLEAN AGENT NOZZLE FLUSH FIRE PUMP TEST HEADERSPRINKLER MAIN

SUB-FLOOR CLEAN AGENT NOZZLE FREE-STANDING FIRE PUMP TEST HEADERCLEAN AGENT

CEILING DETECTOR FREE-STANDING FIRE DEPARTMENT CONNECTIONSPRINKLER BRANCH AND HEADS

SUB-FLOOR DETECTOR FLUSH FIRE DEPARTMENT CONNECTIONRECESSED PENDANT SPRINKLER

CLEAN AGENT ALARM BELL FIRE DEPARTMENT CONNECTIONCONCEALED PENDANT SPRINKLER

CLEAN AGENT HORN WITH STROBE FIRE HOSE CABINETUPRIGHT SPRINKLER

ELECTRIC PULL STATION FIRE HOSE VALVE CABINETDRY PENDANT SPRINKLER

ABORT PULL STATION POST INDICATOR VALVEHORIZONTAL SIDEWALL SPRINKLER

CLEAN AGENT PRESSURE SWITCH ISOLATION VALVE WITH TAMPER SWITCHDRY HORIZONTAL SIDEWALL SPRINKLER

WARNING LIGHT ALARM CHECK VALVEPRE-ACTION HEAT DETECTOR

CLEAN AGENT PANEL DRY PIPE VALVEPRE-ACTION PULL STATION

FIRE HYDRANT FLOW SWITCHPRE-ACTION ALARM BELL

ALARM BELL WATER FLOW SWITCHPRE-ACTION TROUBLE STROBE

ALARM STROBEDELUGE VALVE FOR PRE-ACTION SYSTEM

PRE-ACTION RELEASING PANEL FIRE DEPARTMENT HOSE VALVE

CA

PA

CAP

MECHANICAL SYMBOLS MECHANICAL SYMBOLS

SYMBOLS INDICATED HERE AND NOT USED IN THE

CONTRACT DOCUMENTS DO NOT APPLY TO THIS

PROJECT. ADDITIONAL SYMBOLS AND ABBREVIATIONS

MAY BE INDICATED IN THE CONTRACT DOCUMENTS.

FINTUBE-TYPE (SHADED AREA INDICATES

CAPACITY MBH ELEMENT LOCATION)

VOLUME DAMPER

DESCRIPTIONSYMBOLSYMBOL DESCRIPTION SYMBOL DESCRIPTION

HEATING - VENTILATING - AIR-CONDITIONING

T RS

T

H

A

S

P T

FS

AD

L"

D"

FT-1

MBH

XØ

X/X

SD

M

CFM

SIZE TYPE

CFM

SIZE TYPE

FRD

FSD

M

MCO2

CHILLED WATER SUPPLY

CHILLED WATER RETURN

CONDENSATE OR BOILER FEED PUMP DISCHARGE

CONDENSER WATER SUPPLY FROM TOWER

CONDENSER WATER RETURN TO TOWER

COIL OR EQUIPMENT DRAIN

GLYCOL SUPPLY

GLYCOL RETURN

FUEL OIL SUPPLY

FUEL OIL RETURN

FUEL OIL VENT

HEAT PUMP WATER SUPPLY

HEAT PUMP WATER RETURN

HIGH PRESSURE CONDENSATE RETURN

HIGH PRESSURE STEAM

HOT WATER SUPPLY

HOT WATER RETURN

LOW PRESSURE CONDENSATE RETURN

LOW PRESSURE STEAM

MEDIUM PRESSURE CONDENSATE RETURN

MEDIUM PRESSURE STEAM

REFRIGERANT LIQUID

REFRIGERANT SUCTION

REFRIGERANT HOT GAS DISCHARGE

BACK-DRAFT DAMPER (COUNTER BALANCED)B.D.D.

LPS

MPS

HPS

LPR

MPR

HPR

HWS

HWR

GS

GR

CWS

CWR

PC

FOS

FOR

FOV

PG

RL

RS

RD

CS

CR

CD

#/HR

HPWS

HPWR

PIPE IN SLEEVE

VALVE IN VERTICAL PIPE

F AND T TRAP CAP LBS/HR

BUCKET TRAP CAP LBS/HR

AIR QUALITY SENSOR

C02 SENSOR

HUMIDISTAT

REMOTE SENSOR

THERMOSTAT

THERMOSTAT WITH REMOTE SENSOR

AQUASTAT

SOLENOID VALVE (REFRIGERANT)

THERMOSTATIC EXPANSION VALVE (REFRIGERANT)

SIGHT GLASS

MANUAL AIR VENT

PRESSURE OR TEMPERATURE MEASURING POINTS

FLOW SWITCH

HEATING RISER

ACCESS DOOR - SIZE AS SHOWN OR PER SPEC.

EXPANSION LOOP, LENGTH AND DEPTH

NEW TO EXISTING CONNECTION

#/HR

AQ

RECTANGULAR DUCTWORK

(FIRST NUMBER IS SIDE SHOWN)X/X

ROUND DUCT

FLAT OVAL (FIRST NUMBER IS THE SIDE SHOWN)

MOTORIZED DAMPER

FIRE DAMPER WITH ACCESS DOOR

COMBINATION FIRE AND SMOKE DAMPER

WITH ACCESS DOOR

SMOKE DAMPER WITH ACCESS DOOR

SOUND ATTENUATOR

FLEX CONNECTION

SUPPLY REGISTER OR GRILLE

RETURN REGISTER OR GRILLE

SA

TYP DIFFUSER NECK SIZE, MARK

CFM

X X X

X X X

SUPPLY, OUTDOOR, OR MIXED AIR DUCT

END OR RISER (SA) (OA) (MA)

RETURN EXHAUST OR RELIEF AIR DUCT

END OR RISER (RA) (EA) (RLFA)

TYP EXHAUST/RETURN GRILLE NECK SIZE, MARK

CFM

TURNING VANES

MECHANICAL/ELECTRICAL COORDINATION SCHEDULE

MECHANICAL EQUIPMENT WITH ELEC CONNECTION SEE

AUTOMATIC CONTROL VALVE, 2-WAY

AUTOMATIC CONTROL VALVE, 3-WAY

PRESSURE REGULATING VALVE (PRV)

X X

POINT OF DISCONNECT BREAK / CONTINUATION

T

OR

DESCRIPTIONSYMBOLSYMBOL DESCRIPTION SYMBOL DESCRIPTION

PIPING

R

PTT

TEE

ELBOW

UNION

STRAINER WITH DRAIN VALVE AND HOSE END

BALANCING VALVE

ISOLATION VALVE (BALL OR BUTTERFLY)

PRESSURE RELIEF VALVE

ELBOW UP

ELBOW DOWN

GLOBE VALVE

PRESS / TEMP TEST PORT

GATE VALVE

CHECK VALVE (ARROW INDICATES FLOW)

FLEXIBLE PIPING

AUTOMATIC AIR VENT

MANUAL AIR VENT WITH ISOLATION VALVE

CONCENTRIC REDUCER

ECCENTRIC REDUCER

PRESSURE GAUGE WITH GAUGE COCK

THERMOMETER, SIDE FEED

THERMOMETER, BOTTOM FEED

ARROW INDICATES FLOW DIRECTION

ARROW INDICATES DOWNWARD PIPE PITCH

WATER METERM

S

S

SS

AW

AW

S

S

OF

OF

SS

AW

AW

AV

V

140°

140°

SS

W

S

S

S

A

V

GCO

HB

WH

Y.H.

BFP

_ FD-X

_ FS-X

_ RD-X

DS

MH

VTR

SH

EXISTING SANITARY DRAIN (ABOVE FLOOR)

VENT

DESCRIPTIONSYMBOLSYMBOL DESCRIPTION SYMBOL DESCRIPTION

PLUMBING

EXISTING SANITARY SEWER (BELOW FLOOR)

HOT WATER CIRCULATING 140°

GRADE CLEAN OUT

EXISTING STORM DRAIN (ABOVE FLOOR)

OVERFLOW STORM DRAIN (ABOVE FLOOR)

DOUBLE GRADE CLEAN-OUT

EXISTING STORM DRAIN (BELOW FLOOR)

OVERFLOW STORM DRAIN (BELOW FLOOR)

HOSE BIBB

EXISTING SUB SOIL DRAIN

SANITARY DRAIN (ABOVE FLOOR)

WALL HYDRANT (NON-FREEZE TYPE)

EXISTING ACID WASTE (ABOVE FLOOR)

SANITARY SEWER (BELOW FLOOR)

YARD HYDRANT

EXISTING ACID WASTE (BELOW FLOOR)

BACK FLOW PREVENTER

SITE STORM SEWER

FLOOR DRAIN SIZE-TYPE

SITE WATER PIPING

FLOOR SINK SIZE-TYPE

STORM DRAIN (BELOW FLOOR)

ROOF DRAIN SIZE-TYPE

SUB SOIL DRAIN

DOWN SPOUT

MANHOLE

ACID WASTE (ABOVE FLOOR)

VACUUM BREAKER

ACID WASTE (BELOW FLOOR)

GAS COCK

ACID VENT

RUNNING TRAP

VENT THROUGH ROOF ON RISER

PLUMBING RISER NUMBER

SHOWER

COLD WATER (CW)

COLD SOFT WATER

COMPRESSED AIR

HOT WATER (HW)

HOT WATER CIRCULATING (HWC)

HOT SOFT WATER

HOT SOFT WATER RECIRCULATING

STORM DRAIN (ABOVE FLOOR)

HOT WATER 140°

CLEAN OUT

NATURAL GASG

ORCO CO

BLDG BUILDING

BTUH BRITISH THERMAL UNIT PER HOUR

CFM CUBIC FEET PER MINUTE

CL CENTER LINE

CLG CEILING

CLR CLEAR

CRAC

CV CONSTANT VOLUME

DIAMETER

DISC DISCONNECT

DIST DISTRIBUTION

DN DOWN

DWG DRAWING

EA EXHAUST AIR

EL ELEVATION

EHC ELECTRIC HEATING COIL

EQUIP EQUIPMENT

EXH EXHAUST

EXIST EXISTING

FA FIRE ALARM

FL FLOOR

FT FEET

PWR POWER

PVC POLYVINYL CHLORIDE

PSI POUNDS PER SQUARE INCH

PSF POUNDS PER SQUARE FOOT

PNL PANEL

PLBG PLUMBING

PIV POST INDICATOR VALVE

RM ROOM

RH RELATIVE HUMIDITY

REQD REQUIRED

RLFA RELIEF AIR

RA RETURN AIR

UNO UNLESS NOTED OTHERWISE

UPS UNINTERRUPTIBLE POWER SUPPLY

UL UNDERWRITERS LABORATORY

UG UNDERGROUND

TYP TYPICAL

TEMP TEMPERATURE

STD STANDARD

SS STAINLESS STEEL

SPECS SPECIFICATIONS

SIM SIMILAR

SCHD SCHEDULE

SAN SANITARY

SA SUPPLY AIR

NC NORMALLY CLOSED

MTD MOUNTED

MISC MISCELLANEOUS

MIN MINIMUM

MECH MECHANICAL

MAX MAXIMUM

LBS POUNDS

KW KILOWATT

OC ON CENTER

OA OUTDOOR AIR

NTS NOT TO SCALE

NOM NOMINAL

NO NORMALLY OPEN

NIC NOT IN CONTRACT

GA GAUGE

HVAC HEATING, VENTILATING

HTG HEATING

HP HORSEPOWER

HGT HEIGHT

GPM GALLONS PER MINUTE

GEN GENERATOR

GALV GALVANIZED

AND AIR CONDITIONING

ELEC ELECTRICAL

DIA

CPVC

DX DIRECT EXPANSION

EPO EMERGENCY POWER OFF

F FIRE WATER

FCO FLOOR CLEAN OUT

FDC FIRE DEPARTMENT CONNECTION

FHC FIRE HOSE CABINET

FW FILTERED WATER

GC GENERAL CONTRACTOR

MBH 1000 BTU/HOUR

NPW NON-POTABLE WATER

PS PLASTER SINK

RO REVERSE OSMOSIS WATER

SCW SOFT COLD WATER

SM SPRINKLER MAIN

SMACNA SHEET METAL AND AIR

CONDITIONING CONTRACTORS'

BTU BRITISH THERMAL UNIT

PERP PERPENDICULAR

RGS RIGID GALVANIZED STEEL

HZ HERTZ, HIGH ZONE WET STANDPIPE

CFH CUBIC FEET PER HOUR

SHW SOFT HOT WATER

MERV MINIMUM EFFICIENCY REPORTING

VALUE

MOA MINIMUM OUTDOOR AIR

EOA ECONOMIZER OUTDOOR AIR

IE INVERT ELEVATION

NATIONAL ASSOCIATION

AHJ

ASHRAE

AUX

AV

AW

AWG

BFP

AUTHORITY HAVING JURISDICTION

AMERICAN SOCIETY OF HEATING,

REFRIGERATING AND

AIR-CONDITIONING ENGINEERS

AUXILIARY

ACID VENT

ACID WASTE

AMERICAN WIRE GAUGE

DOUBLE CHECK BACKFLOW

VOLT-AMPS

VERTICAL

VARIABLE FREQUENCY CONTROL

VENT THROUGH ROOF

WATT

WEATHERPROOF

TRANSFORMER

VA

VERT

VFC

VTR

W

WP

XFMR

AFF ABOVE FINISHED FLOOR

AMERICAN SOCIETY OF

MECHANICAL ENGINEERS

STANDARD SPECIFICATIONS OF

THE AMERICAN SOCIETY FOR

ASME

ASTM

TESTING MATERIALS

AVG AVERAGE

BMCS BUILDING MANAGEMENT

EMS ENERGY MANAGEMENT SYSTEM

IP INTERNET PROTOCOL

NATIONAL FIRE PROTECTION

ASSOCIATION

NFPA

WATER GAUGEWG

CHLORINATED POLYVINYL CHLORIDE

COMPUTER ROOM AIR CONDITIONER

MA MIXED AIR

CONTROL SYSTEM

ABBREVIATIONS

OFCI OWNER FURNISHED

CONTRACTOR INSTALLED

PREVENTER RPZ REDUCED PRESSURE ZONE

BACKFLOW PREVENTER

LZ LOW ZONE WET STANDPIPE

GW GARAGE WASTE

FHV FIRE HOSE VALVE

DDCV DOUBLE DETECTOR CHECK VALVE

ASSEMBLY BACKFLOW PREVENTER

DPAC DRY PIPE AIR COMPRESSOR

DPV DRY PIPE VALVE

PROPANE GAS

Fe br ua ry

, 2

2:0 1p m

_M

0.d wg m gr eg or y

NOTE:

DO NOT SCALE DRAWINGS. VERIFY ALL DIMENSIONS

and clearances from ARCHITECTURAL, STRUCTURAL, shop and other appropriate drawing or at site. lay out and coordinate all work prior to installation to provide clearances required for operation, maintenance, and codes and verify non-interference with other work. DO NOT FABRICATE

PRIOR TO VERIFICATION OF CLEARANCE FOR ALL

TRADES. READ SPECIFICATIONS.

COPYRIGHT 2024

Permission to reproduce all or part of this drawing is hereby granted solely for the limited purpose of construction of this project or archiving. Unauthorized copying, disclosure or construction use without written permission of Alvine Engineering is prohibited by copyright law.

AE# 20239894

DATE:

TECH. REVIEW:

SUB SHEET NO. TITLE OF SHEET

PMIS NO.

DRAWING NO.

SHEET

OF

DRAWN BY:

DESIGNED:

15 FEB 2024

80071

RENOVATE MAIN RESTROOMS FROM THE LINCOLN

AND WASHINGTON PARKING STRUCTURES

MOUNT RUSHMORE NATIONAL MEMORIAL

KEYSTONE, SOUTH DAKOTA

305644

FINAL CONSTRUCTION DOCUMENTS

MRG

MRG

BAH

MECHANICAL SYMBOLS AND

ABBREVIATIONSM0

AutoCAD SHX Text M-Lg Mechanical

AutoCAD SHX Text 2020-07-23

3 222

EXISTING COMBINATION

FIRE/DOMESTIC WATER

ENTRANCE

EXISTING

4" VTR

PG

EXISTING PROPANE GAS METER

(TYP-5) (TYP-5)

(TYP-6)

(TYP-5)

(TYP-6)(TYP-6)

Fe br ua ry

, 2

3:1 9p m M

1.d wg m gr eg or y

NOTE:

DO NOT SCALE DRAWINGS. VERIFY ALL DIMENSIONS

and clearances from ARCHITECTURAL, STRUCTURAL, shop and other appropriate drawing or at site. lay out and coordinate all work prior to installation to provide clearances required for operation, maintenance, and codes and verify non-interference with other work. DO NOT FABRICATE

PRIOR TO VERIFICATION OF CLEARANCE FOR ALL

TRADES. READ SPECIFICATIONS.

COPYRIGHT 2024

Permission to reproduce all or part of this drawing is hereby granted solely for the limited purpose of construction of this project or archiving. Unauthorized copying, disclosure or construction use without written permission of Alvine Engineering is prohibited by copyright law.

AE# 20239894

DATE:

TECH. REVIEW:

SUB SHEET NO. TITLE OF SHEET

PMIS NO.

DRAWING NO.

SHEET

OF

DRAWN BY:

DESIGNED:

15 FEB 2024

80071

RENOVATE MAIN RESTROOMS FROM THE LINCOLN

AND WASHINGTON PARKING STRUCTURES

MOUNT RUSHMORE NATIONAL MEMORIAL

KEYSTONE, SOUTH DAKOTA

305644

FINAL CONSTRUCTION DOCUMENTS

FLAG NOTES

REMOVE EXISTING GAS-FIRED WATER HEATER SHOWN BOLD. EXISTING 3"

COMBUSTION AIR AND FLUE EXHAUST VENT SHALL REMAIN AND BE REUSED UNDER

NEW WORK.

REMOVE EXISTING FLUSH VALVE WATER CLOSET SHOWN BOLD COMPLETE.

SANITARY PIPING UTILITIES SHALL REMAIN AND BE REUSED UNDER NEW WORK.

CLEAN EXISTING TO REMAIN.

REMOVE EXISTING FLUSH-VALVE URINAL SHOWN BOLD COMPLETE. PIPING

UTILITIES IN WALL SHALL REMAIN AND BE REUSED UNDER NEW WORK. CLEAN

EXISTING TO REMAIN.

REMOVE EXISTING WALL MOUNTED LAVATORY AND ASSOCIATED FAUCETS SHOWN

BOLD COMPLETE. REMOVE EXISTING ACCESS PANELS, THERMOSTATIC MIXING

VALVE ASSEMBLIES, TEMPERED AND COLD WATER PIPING SERVING LAVATORIES

COMPLETE. REMOVE WATER PIPING IN WALL TO BELOW FLOOR. REMOVE EXISTING

SANITARY WASTE PIPING BACK TO SANITARY MAIN WHERE PIPING EXITS

CRAWLSPACE ABOVE FLOOR. EXISTING SANITARY WASTE PIPING BACK DOWN INTO

CRAWLSPACE SHALL BE REUSED FOR NEW NEW WORK.

REMOVE EXISTING WALL MOUNTED WATER COOLER / BOTTLE FILLER AND SAVE

FOR RE-INSTALLATION.

REMOVE EXISTING COLD AND HOT WATER PIPING SHOWN DARK ROUTING WITHIN

CRAWLSPACE BELOW FLOOR.

REMOVE EXISTING COLD WATER SHOWN BOLD IN CHASE SERVING WATER

CLOSETS.

EXISTING COLD WATER SERVING EXISTING WALL HYDRANT TO REMAIN AND BE

REUSED.

REMOVE EXISTING HOT WATER PIPING IN WALL FROM BELOW FLOOR SERVING MOP

SINK. REMOVE TO ELEVATION IN WALL BELOW EXISTING MOP SINK FAUCET.

REMAINING HOT WATER AND HOT WATER CIRCULATING PIPING IN WALL SHALL

REMAIN AND BE REUSED UNDER NEW WORK.

REMOVE EXISTING HOT WATER CIRCULATING PIPING BELOW FLOOR IN

CRAWLSPACE SHOWN DASHED AND BOLD. VERIFY EXISTING CONDITIONS IN FIELD.

REMOVE EXISTING HOT WATER CIRCULATING PIPING SHOWN BOLD FROM WHERE

PIPING COMES UP FROM BELOW FLOOR AND ROUTES OVERHEAD TO ABOVE THE

EXISTING CIRCULATING PUMP.

REMOVE EXISTING HOT WATER CIRCULATING PUMP. EXISTING PUMP SHALL BE

REPLACED WITH A NEW PUMP UNDER NEW WORK (SEE SHEET M4).

REMOVE PORTION OF EXISTING 1" PROPANE GAS PIPING SHOWN BOLD FROM

EXISTING PROPANE METER LOCATED OUTSIDE TO A POINT INSIDE MECHANICAL

ROOM WHERE PIPING OFFSETS UP IN MECHANCIALROOM. COORDINATE HOW MUCH

PIPING NEEDS TO BE REMOVED ON VERTICAL PORTION OF PIPING INSIDE OF

MECHANICAL ROOM WHERE CONNECTION OF NEW PIPING WILL BE MADE. SEE

SHEET M-4 AND DETAIL #6 ON SHEET M-8 FOR ADDITIONAL INFORMATION.

MRG

MRG

BAH

FLOOR PLAN - PLUMBING

DEMOLITIONM1

SCALE…

This is the start of the file's text. The full file is on GovTribe.