Atch_3_Drawings.pdf
PDF 7 MB Posted
- Attached to
- MORU-Renovate Main Restrooms Federal contract opportunity
- Solicitation number
- 140P6324B0009
About this file
This document appears to be a set of architectural and engineering drawings for a renovation project to renovate the main restrooms at the Mount Rushmore National Memorial in Keystone, South Dakota. The project involves demolishing and renovating the existing men's and women's restrooms, lobby, and mechanical rooms. Key details include:
The project requires new plumbing, HVAC, and fire protection systems, as well as architectural finishes and fixtures. The drawings show floor plans, interior elevations, mechanical/electrical plans, and construction details. The project is being solicited by the Department of the Interior National Park Service Midwest Region under Solicitation Number 140P6324B0009, with the project titled "MORU-Renovate Main Restrooms". The drawings provide comprehensive details on the scope of work required for this federal construction project.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Sol_140P6324B0009_Amd_0002.pdf | ||
| Questions_Answers_5_30_24_0002.pdf | ||
| Sol_140P6324B0009_Amd_0001.pdf | ||
| Atch_2_Questions_Answers_0001.pdf | ||
| Atch_1_Site_Visits_Sign_In_0001.pdf | ||
| Atch_1_Statement_of_Work_(SOW)_Division1.pdf | ||
| Atch_2_Statement_of_Work_(SOW).pdf | ||
| Atch_6_Limitations_on_Subcontracting_Report.xlsx | XLSX spreadsheet | |
| Atch_5_DOL_Wage_Determination_SD20240029.pdf | ||
| Atch_4_Submittal_List.pdf | ||
| Sol_140P6324B0009.pdf |
Show all 11
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
REGIONAL MAP PROJECT LOCATION
A/E FIRM
PRIME/ARCH:
KENNETH HAHN ARCHITECTS
OMAHA, NE
MECHANICAL ENGINEER:
ALVINE ENGINEERING
OMAHA, NE
PROJECT
LOCATION
PROJECT
LOCATION
ELECTRICAL ENGINEER:
ALVINE ENGINEERING
OMAHA, NE
SCHEDULE OF DRAWINGS
GENERAL
1. G1 COVER SHEET
2. G2 GENERAL NOTES, LEGEND AND ABBREVIATIONS
ARCHITECTURAL
3. A1 FLOOR PLAN - DEMOLITION
4. A2 FLOOR PLAN - CEILING DEMOLITION
5. A3 FLOOR PLAN
6. A4 INTERIOR ELEVATIONS AND WALL SECTION
7. A5 INTERIOR ELEVATIONS
8. A6 ELEVATIONS, INTERIOR ELEVATIONS AND SECTION
9. A7 ENLARGED FLOOR PLANS
10. A8 FLOOR PLAN - FLOORING
11. A9 ROOM FINISH AND DOOR SCHEDULE AND WALL TYPE
12. A10 REFLECTED CEILING PLAN
13. A11 ROOF PLAN
MECHANICAL
14. M0 MECHANICAL SYMBOLS AND ABBREVIATIONS
15. M0.1 MECHANICAL GENERAL NOTES
16. M1 FLOOR PLAN - PLUMBING DEMOLITION PLAN
17. M2 FLOOR PLAN - HVAC DEMOLITION PLAN
18. M3 FLOOR PLAN - HVAC PIPING DEMOLITION
19. M4 FLOOR PLAN - PLUMBING
20. M5 FLOOR PLAN - HVAC
21. M6 FLOOR PLAN - HVAC PIPING
22. M7 FLOOR PLAN - FIRE PROTECTION
23. M8 MECHANICAL DETAILS
24. M9 MECHANICAL SCHEDULES
25. M10 MECHANICAL SCHEDULES
ELECTRICAL
26. E0 ELECTRICAL NOTES, SYMBOLS AND ABBREVIATIONS
27. E1 FLOOR PLAN - ELECTRICAL DEMOLITION
28. E2 FLOOR PLAN - LIGHTING AND FIRE ALARM
29. E3 FLOOR PLAN - POWER
30. E4 ELECTRICAL DETAILS
31. E5 ELECTRICAL SCHEDULES
PLAN NORTH
REG
IS
TE
RE
D P
ROFESSIONA L A RCHITECT
SOUT H DA KOTA
14417
STEPHEN R. SMITH
REG. NO.
ABBREVIATIONS
TILE(LARGE SCALE)
CARPET
BRICK PAVERS
ACOUSTICAL TILE
TERRAZZO
OR BOARD
STRUCTURAL STEEL
METAL STUD WALL
OTHER
(LARGE SCALE)
(SMALL SCALE)
WOOD STUD WALL
PARTICLE BOARD
PLYWOOD
FINISH WOOD
DIMENSION LUMBER
ROOF OR RIGID
FLASHING, DAMPROOFING
CAULKING OR SEALANT
BATT OR LOOSE
INSULATION
INSULATION
GLASS
GLASS
OR PLASTER
(SMALL SCALE)
GYPSUM WALLBOARD
(LARGE SCALE)
OR WATERPROFING
LAMINATED WOOD
CERAMIC OR QUARRY
CEMENT GYPSUM
CONCRETE MASONRY
LIGHTWEIGHT
METALS
CUT STONE
STEEL
CONCRETE MASONRY
COMPRESSIBLE
OR E.J. FILLER
BRICK
MASONRY
PRECAST
REINFORCEMENT
FINISHES
GLAZING
MOISTURE
THERMAL AND
PROTECTION
MATERIALS
BITUMINOUS PAVEMENT
CONCRETE POURED
CRUSHED ROCK
GRAVEL OR
SAND
SITE EARTH WOOD
REFERENCES
XX
DETAIL NUMBER
DETAIL SHEET NUMBER
SECTION NUMBER
SECTION SHEET NUMBER
ELEVATION NUMBER
ELEVATION SHEET NUMBER
COLUMN LINE
ROOM NAME AND NUMBER
DOOR NUMBER
WINDOW NUMBER
WALL TYPE
KEYNOTE
ELEVATION NUMBER
ELEVATION SHEET NUMBER
ELEVATION SYMBOL
ABOVE FINISHED FLOOR AFF
ACOUSTIC TILE CEILING ATC
ADJACENT ADJ
AIR CONDITIONING AC
ALTERNATE ALT
ALUMINUM ALUM
ANCHOR BOLT AB
ANGLE L
APPROXIMATELY APPROX
ARCHITECT ARCH
ARCHITECT / ENGINEER A/E
AT @
BASEMENT BSMT
BEAM BM
BEARING BRG
BLOCKING BLKG
BOARD BD
BOTTOM BOT
BOTTOM OF B.O.
BUILDING BLDG
CARPET CPT
CAST IRON CI
CEILING CLG
CENTERLINE CL
CERAMIC TILE CT
CHANNEL CH
CIRCUIT CKT
CLEANOUT CO
CLEAR CLR
CLOSET CLO
COMPACTED COMP
COMPRESSIBLE COMPR
CONCRETE CONC
CONCRETE MASONRY UNIT CMU
CONSTRUCTION CONST
CONTINUOUS CONT
CONTRACTOR CONTR
CONTROL JOINT CJ
CORRIDOR CORR
COUNTERSUNK CTSK
CURB C
DEAD LOAD DL
DETAIL DET
DIAMETER DIA
DIMENSION DIM
DISPENSER DISP
DISHWASHER DW
DOOR DR
DOUBLE DBL
DOWN DN
DOWNSPOUT DS
DRAWING DWG
DRINKING FOUNTAIN DF
EACH EA
ELECTRICAL ELEC
ELECTRIC WATER COOLER EWC
ELEVATION EL
ELEVATOR ELEV
ENGINEER ENGR
EQUAL EQ
EQUIPMENT EQUIP
EXHAUST FAN EF
EXISTING EXIST
EXPANSION EXP
EXPANSION JOINT EJ
EXTERIOR EXT
EXTERIOR INSULATION FINISH SYSTEM EIFS
FIELD VERIFY F.V.
FINISH FIN
FIRE ALARM FA
FIRE EXTINGUISHER FE
FIRE EXTINGUISHER CABINET FEC
FLATHEAD FH
FLEXIBLE FLEX
FLOOR FL
FLOORING FLRG
FLOOR DRAIN FD
FLUORESCENT FLUOR
FOOTING FTG
FOUNDATION FNDN
FRAME FR
FURRING FUR
GALVANIZED GALV
GAUGE GA
GLASS GL
GLASS FIBER REINFORCED PANEL GFRP
GLAZING GLZ
GRANULAR GRAN
GUTTER G
GYPSUM WALLBOARD GWB
HANDICAP HC
HARDWARE HDWE
HARDWOOD HDWD
HEIGHT HT
HIGH POINT HP
HOLLOW CORE HC
HOLLOW METAL HM
HORIZONTAL HORIZ
INSIDE DIAMETER ID
INSULATION INSUL
INTERIOR INT
JOINT JT
JOIST JST
KNEE SPACE KS
LAVATORY LAV
LIGHT LT
LIGHTWEIGHT LTWT
LIVE LOAD LL
LOW POINT LP
LUXURY VINYL TILE LVT
MARKERBOARD MB.
MANHOLE MH
MANUFACTURER MFR
MATERIAL MATL, MAT
MECHANICAL MECH
MEDICINE CABINET MC
METAL MET
METAL BUILDING PANEL MBP
METAL WALL PANEL MWP
MINIMUM MIN
MISCELLANEOUS MISC
MOUNT MT
NOT IN CONTRACT NIC
NOT TO SCALE NTS
NUMBER NO.
ON CENTER O.C.
OPENING OPNG
OPPOSITE OPP
ORIENTED STRAND BOARD OSB
OUTSIDE AIR OA
OUTSIDE DIAMETER OD
PAINT PT
PANEL PNL
PARTITION PART
PLASTER PLAS
PLASTIC LAMINATE PLAM
PLATE PL
PLYWOOD PLYWD
POLISHED POL
POUND LB
PROPERTY PROP
QUARRY TILE QT
RADIUS R
RECESSED REC
REFERENCE REF
REFRIGERATOR REFRIG, REF
REGARDING RE:
REINFORCE REINF
REQUIRED REQ
RESILIENT BASE RB
RETURN AIR RA
REVERSE REV
RISER R
ROOF DRAIN RD
ROOM RM
ROUGH OPENING RO
ROUND RND
SCHEDULE SCHED
SECTION SET
SHEET SHT
SHEET METAL SM
SHEET VINYL SV
SHEET VINYL BASE SVB
SIMILAR SIM
SLAB-ON-GRADE SOG
SPECIFICATIONS SPEC
SQUARE SQ
SQUARE FOOT SF
STEEL STL
STORAGE STOR
STRUCTURAL STRUCT
SUPPLY AIR SA
SUSPENDED SUSP
TACKBOARD TB.
TELEPHONE TELE
TEMPERATURE TEMP
TERRAZZO TERR
TOILET TLT
TONGUE & GROOVE T&G
TOP OF T.O.
TOP OF STEEL TOS
TREAD T
TYPICAL TYP
UNDERGROUND UG
UNLESS NOTED OTHERWISE UNO
URINAL UR
VERTICAL VERT
VESTIBULE VEST
VINYL COMPOSITION TILE VCT
VINYL WALLCOVERING VWC
WATER CLOSET WC
WATER HEATER WH
WEIGHT WT
WELDED WIRE FABRIC WWF
WHERE OCCURRING W.O.
WOOD WD
X A-X01
X A-X01
XX.XX
X X
X
A-X01 X
ROOM
NAME
XXXX
XX
XX
ELEV. = 100'-0"
FINISH FLOOR
XX
GENERAL NOTES
XXX
1. IN THE EVENT OF DISCREPANCIES WITHIN THE DRAWINGS OR SPECIFICATIONS, THE GREATER QUALITY AND QUANTITY OF THE ITEMS IN QUESTION SHALL BE UTILIZED AT ALL LOCATIONS WHERE SUCH DISCREPANCIES OCCUR. IN THE EVENT DISCREPANCIES BETWEEN THE DRAWINGS
AND THE SPECIFICATIONS OCCURS, THE SPECIFICATIONS SHALL BE USED.
2. THE LOCATION OF ALL UNDERGROUND UTILITIES MAY NOT BE INDICATED ON THESE PLANS, AND SOME LOCATIONS MAY BE INACCURATE. NO EXCAVATION WILL BE PERMITTED IN THE AREA OF UNDERGROUND UTILITIES UNTIL SUCH UTILITIES HAVE BEEN LOCATED AND IDENTIFIED TO THE SATISFACTION OF ALL PARTIES, AND THEN ONLY WITH EXTREME CAUTION TO AVOID ANY POSSIBILITY OF DAMAGE TO THE UTILITY OR PERSONAL INJURY. HAND-DIGGING MAY BE REQUIRED WHEN THE EXCAVATION AND UTILITIES ARE EXTREMELY CLOSE. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL REPAIR AND REPLACEMENT COST OF ANY UNDERGROUND UTILITY DAMAGE.
3. THE CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS AND SHALL BE RESPONSIBLE FOR THE SAME. COORDINATE ALL WORK AND SHOP DRAWINGS WITH OTHER TRADES.
4. THE CONTRACTOR SHALL COORDINATE ALL TESTING AND INSPECTIONS AS SPECIFIED, OR AS NECESSARY TO DEMONSTRATE A COMPLETE AND SATISFACTORY INSTALLATION.
5. ALL WORK SHALL COMPLY WITH APPLICABLE CODES, REGULATIONS, AND ORDINANCES.
6. ALL MATERIALS AND EQUIPMENT OF THE SAME TYPE SHALL BE SUPPLIED BY THE SAME MANUFACTURER, AND SHALL BE NEW, OF THE BEST QUALITY AND DESIGN, AND FREE FROM DEFECTS.
7. ALL ITEMS ARE NEW UNLESS SPECIFICALLY IDENTIFIED AS EXISTING.
8. "PROVIDE" MEANS TO FURNISH AND INSTALL.
9. THE CONTRACTOR SHALL COORDINATE ON-SITE STORAGE OF BUILDING MATERIALS, EQUIPMENT, AND TRASH CONTAINERS WITH GOVERNMENT - SEE SPECIFICATIONS FOR INSTRUCTIONS.
10. THE GOVERNMENT RESERVES THE RIGHT TO REMOVE ANY ITEMS FROM THE CONSTRUCTION AREA PRIOR TO THE START OF DEMOLITION WORK BY THE CONTRACTOR AND TO RETAIN SUCH ITEMS AS THEIR PROPERTY.
11. IT IS THE INTENT OF THIS CONTRACT THAT ALL AREAS AFFECTED BY CONSTRUCTION BE A FINISHED AND COMPLETE PROJECT. CONTRACTOR SHALL PATCH, REPAIR, AND ADJUST AS REQUIRED TO ACHIEVE THIS FINISHED PROJECT.
12. EXISTING WALL VENT GRILLES IN TOILET AREAS TO REMAIN.
13. EXISTING TILE WALLS HAVE CEMENT BOARD BACKING, WHICH SHALL BE REMOVED ALONG WITH THE TILE. CEMENT BOARD SHALL BE RE-INSTALLED ( SEE SPEC.)
GENERAL NOTES, LEGEND
AND ABBREVIATIONS
DATE:
TECH. REVIEW:
SUB SHEET NO. TITLE OF SHEET
PMIS NO.
DRAWING NO.
SHEET
OF
DRAWN BY:
DESIGNED:
DJS
DJS
KJH
15 FEB 2024
80071
RENOVATE MAIN RESTROOMS FROM THE LINCOLN
AND WASHINGTON PARKING STRUCTURES
MOUNT RUSHMORE NATIONAL MEMORIAL
KEYSTONE, SOUTH DAKOTA
305644
F eb
9,
- 4
:3 4p m Y
:\1
\1
-0
M
OU
NT
R
US
HM
OR
E
RE
ST
RO
OM
S\
DR
AW
IN
GS
\ 1
-0
_G
2.
dw g
- U
SE
R da ria n
FINAL CONSTRUCTION DOCUMENTS
G2
A01
A01
A01 A01
A02 A02
A05
TYP.
A05
TYP.
A03 A03
TYP.
TYP.
A10
A10
A06
A07 A07
A08
A04
A04
A06
A09 A13
A13
A13
A13
A13
A13 A14A14
A13
A13
A13
A13
EXISTING UNDERGROUND PROPANE
LINE - APPROXIMATE LOCATION
EXISTING TREE
TO REMAIN
A12
A15
A15
A15
A15
A16 A16
A17 A17
A18
A18
TYP.
TYP.
A19
A20
A19
A20
A21A21
A22 A22
TYP.
TYP.TYP.
A01
A11A11
A22A22
A23
A23
A23
A23
SCALE: 1/4" = 1'-0" 4' 2' 0 4'
DEMOLITION FLOOR PLAN
N1
A1
FLOOR PLAN - DEMOLITION
DEMOLITION - KEYNOTES:
A01 REMOVE WALL SHOWN DASHED COMPLETE.
A02 REMOVE HAND DRYERS - SEE ELECTRICAL.
A03 REMOVE TOILETS AND URINAL FIXTURES COMPLETE - SEE MECHANICAL.
A04 REMOVE LAVATORIES COMPLETE - SEE MECHANICAL.
A05 REMOVE TOILET PARTITIONS COMPLETE.
A06 REMOVE DOOR, FRAME AND HARDWARE COMPLETE.
A07 SALVAGE TRASH CANS AND RETURN TO GOVERNMENT.
A08 REMOVE WINDOW GLAZING AND FRAME COMPLETE.
A09 REMOVE COUNTER COMPLETE.
A10 SALVAGE BENCH COMPLETE - RETURN TO GOVERNMENT.
A11 REMOVE DOOR OPERATOR AND PREPARE FOR NEW DOOR OPERATOR.
A12 SALVAGE DISPENSER- RETURN TO OWNER.
A13 REMOVE WALL TILE AND CEMENT BOARD COMPLETE AND PREP FOR NEW WORK-
SEE GENERAL NOTES RE: CEMENT BOARD REPLACEMENT.
A14 REMOVE MIRRORS COMPLETE
A15 REMOVE PORCELAIN TILE FLOORING COMPLETE AND PREP FOR NEW WORK
A16 COORDINATE WITH GOVERNMENT RE: TEMP. STORAGE OF VENDING MACHINE
A17 REMOVE PUSH BUTTON DOOR OPERATOR (RAILING TO REMAIN.)
A18 REMOVE ACCESS PANELS BENEATH SINKS
A19 SEE ELECTRICAL RE: SALVAGE CAMERA TO BE LOWERED DOWN ON WALL
A20 REMOVE DOOR OPERATOR BUTTON
A21 REMOVE WINDOW EXHAUST FAN AND INFILL DAMPER PANEL COMPLETE.
ALUMINUM FRAME TO REMAIN & BE REUSED - SEE ARCHITECTURAL DRAWINGS
A22 CUT DOWN EXISTING ALUMINUM METAL BASE PANEL AS REQUIRED FOR NEW
METAL DOOR FRAME.
A23 REMOVE LAYER OF GWB ON EXISTING WALL THIS SIDE AND INSTALL CEMENT
BOARD.
DATE:
TECH. REVIEW:
SUB SHEET NO. TITLE OF SHEET
PMIS NO.
DRAWING NO.
SHEET
OF
DRAWN BY:
DESIGNED:
DJS
DJS
KJH
15 FEB 2024
80071
RENOVATE MAIN RESTROOMS FROM THE LINCOLN
AND WASHINGTON PARKING STRUCTURES
MOUNT RUSHMORE NATIONAL MEMORIAL
KEYSTONE, SOUTH DAKOTA
305644
F eb
9,
- 4
:3 5p m Y
:\1
\1
-0
M
OU
NT
R
US
HM
OR
E
RE
ST
RO
OM
S\
DR
AW
IN
GS
\X
RE
F\
-0
_M
OR
U
BA
TH
RO
OM
_X
DE
M
O.
dw g
- U
SE
R da ria n
A01 A02
A01 A01
A02 A01
A01A01
A2
REFLECTED CEILING PLAN -
DEMOLITION
SCALE: 1/4" = 1'-0" 4' 2' 0 4'
CEILING PLAN - DEMOLITION
N1
DEMOLITION - KEYNOTES:
A01 REMOVE GWB CEILING AND FRAMING COMPLETE.
A02 REMOVE BULKHEAD SHOWN DASHED.
DATE:
TECH. REVIEW:
SUB SHEET NO. TITLE OF SHEET
PMIS NO.
DRAWING NO.
SHEET
OF
DRAWN BY:
DESIGNED:
DJS
DJS
KJH
15 FEB 2024
80071
RENOVATE MAIN RESTROOMS FROM THE LINCOLN
AND WASHINGTON PARKING STRUCTURES
MOUNT RUSHMORE NATIONAL MEMORIAL
KEYSTONE, SOUTH DAKOTA
305644
F eb
9,
- 5
:0 2p m Y
:\1
\1
-0
M
OU
NT
R
US
HM
OR
E
RE
ST
RO
OM
S\
DR
AW
IN
GS
\X
RE
F\
-0
_M
OR
U
BA
TH
RO
OM
XC
PL
AN
.d wg
US
ER
d ar ian
A03
TYP.A03
TYP.
107A
102 103
WOMEN'S
LOBBY
RESTROOM
RESTROOM
103 MEN'S
LOBBY
WOMEN'S
RESTROOM
MEN'S
RESTROOM
JANITOR
ROOM
MECHANICAL
ROOM
CLOSET
C1C1
A2
A05A05
A04 A04A4
A4
A5
A5
A4
A4
SIM.
WOMEN'S
TOILETS
MEN'S
TOILETS
5'-0" 5'-0"
A5
14 15
A6
EXISTING UNDERGROUND PROPANE
LINE - APPROXIMATE LOCATION
EXISTING TREE
TO REMAIN
107B
D1
B1
A6
5 4
1'-0" MIN. 1'-0" MIN.
A6
A01
A02
4'-3" 4'-3"
1'- 4 1
/4" A1 A1
A11 A09
A2 A2
A15
A08A08
A15
1'-6" 1'-6"
F3 F3
A7
A7
A12 A12
A12 A12
A13A13
A14 A14
17'-9 1/4" 17'-5 1/4"
3'- 3"
3'- 3"
F4 F4
DRAINAGE SWALE
4"4"
B1 B1
A7
A7
A4
A07 A07
ARCHITECTURE - KEYNOTES:
A01 NAPKIN DISPENSER - SEE SPECS
A02 BABY CHANGING STATION SEE SPECS
A03 TOILET PARTITIONS
A04 INFILL OPENINGS ABOVE THIS WALL WITH METAL STUDS - SEE WALL TYPES
A05 ELECTRIC WATER COOLER - SEE MECHANICAL
A06 PATCH WALL AS REQUIRED FOR NEW WORK
A07 DOOR OPERATOR CONTROL BUTTON - SEE ELECTRICAL
A08 OUTSIDE CORNER TRIM - SEE SPECS
A09 RE-GRADE AS REQUIRED AROUND CRAWLSPACE DOOR TO ALLOW
FULL FUNCTION OF CRAWL SPACE DOOR. FINISH GRADE SHALL
MITIGATE WATER TO FLOW AWAY FROM BUILDING.
A10 SEE MECHANICAL AND ELECTRICAL RE: RAISING EXISTING ELECTRIC
WATER COOLER.
A11 ROOF LADDER - SEE SPECS
A12 DIAPER DISPOSAL UNIT - SITTING ON FLOOR.
A13 RECESSED HOSE BIB BOX - SEE MECHANICAL
A14 REINSTALL LOWERED CAMERA AT THIS LOCATION - SEE ELECTRICAL
A15 S.S. FRAME - TYPE F2
FLOOR PLAN
A3
DATE:
TECH. REVIEW:
SUB SHEET NO. TITLE OF SHEET
PMIS NO.
DRAWING NO.
SHEET
OF
DRAWN BY:
DESIGNED:
DJS
DJS
KJH
15 FEB 2024
80071
RENOVATE MAIN RESTROOMS FROM THE LINCOLN
AND WASHINGTON PARKING STRUCTURES
MOUNT RUSHMORE NATIONAL MEMORIAL
KEYSTONE, SOUTH DAKOTA
305644
F eb
9,
- 4
:3 5p m Y
:\1
\1
-0
M
OU
NT
R
US
HM
OR
E
RE
ST
RO
OM
S\
DR
AW
IN
GS
\X
RE
F\
-0
_M
OR
U
BA
TH
RO
OM
A-
FP
LA
N.
dw g
- U
SE
R da ria n
FINAL CONSTRUCTION DOCUMENTS
SCALE: 1/4" = 1'-0" 4' 2' 0 4'
FLOOR PLAN
N1
ARCHITECTURE - KEYNOTES:
A01 NAPKIN DISPENSER - SEE SPECS
A02 BABY CHANGING STATION SEE SPECS
A03 TOILET PARTITIONS
A04 INFILL OPENINGS ABOVE THIS WALL WITH METAL STUDS - SEE WALL TYPES
A05 ELECTRIC WATER COOLER - SEE MECHANICAL
A06 PATCH WALL AS REQUIRED FOR NEW WORK
A07 DOOR OPERATOR CONTROL BUTTON - SEE ELECTRICAL
A08 OUTSIDE CORNER TRIM - SEE SPECS
A09 RE-GRADE AS REQUIRED AROUND CRAWLSPACE DOOR TO ALLOW
FULL FUNCTION OF CRAWL SPACE DOOR. FINISH GRADE SHALL
MITIGATE WATER TO FLOW AWAY FROM BUILDING.
A10 SEE MECHANICAL AND ELECTRICAL RE: RAISING EXISTING ELECTRIC
WATER COOLER.
A11 ROOF LADDER - SEE SPECS
A12 DIAPER DISPOSAL UNIT - SITTING ON FLOOR.
A13 RECESSED HOSE BIB BOX - SEE MECHANICAL
A14 REINSTALL LOWERED CAMERA AT THIS LOCATION - SEE ELECTRICAL
A15 S.S. FRAME - TYPE F2
GENERAL NOTES:
1. WALL FRAMING BEHIND TILE SURFACES SHALL RECEIVE CEMENT BOARD.
2. WHERE TILE IS SCHEDULED ON WALLS, IT SHALL EXTEND FULL HEIGHT.
3. SEE ROOF PLAN FOR ROOF CURB DETAILS.
4. PATCH UNUSED OPENINGS IN GWB TO MATCH EXISTING.
SCALE: 1/2" = 1'-0" 2' 1' 0 2'
RESTROOM 102 - NORTH
LEVEL 01
ELEV. = 100'-0"
LEVEL 01
ELEV. = 100'-0"
LEVEL 01
ELEV. = 100'-0"
LEVEL 01
ELEV. = 100'-0"
GB-1
SCALE: 1/2" = 1'-0" 2' 1' 0 2'
RESTROOM 102 - WEST
SCALE: 1/2" = 1'-0" 2' 1' 0 2'
RESTROOM 102 - SOUTH
SCALE: 1/2" = 1'-0" 2' 1' 0 2'
RESTROOM 102 - EAST
BCT-1GB-1BCT-1
3'- 3"
MIRROR
PT-2(TYP.)
PT-3 (TYP.)
PT-2 (TYP.)
PT-3 (TYP.)
PT-2 (TYP.)
PT-3 (TYP.)
PT-2 (TYP.)
PT-3 (TYP.)
A4
INFILL OPENINGS (SEE PLANS)
RECESSED
A4
2'- 9 3
/4"
5' MINIMUM CLEARANCE
HAND WASH, SOAP
AND HAND DRYER
COMBO (TYP.)
2'-
2'-
ND-1
PH-1 (OWNER
PROVIDED,
CONTRACTOR
INSTALLED)
SCALE: 3/4" = 1'-0" 6" 0 18"6"
WALL SECTION DETAIL
2 1/2" RIGID INSULATION
5/8" EXTERIOR SHEATHING
3 5/8" METAL STUD
PORCELAIN TILE ON
CEMENT BOARD
SPRAY FOAM INSULATION
3 5/8" METAL STUD
PORCELAIN TILE ON
CEMENT BOARD
WALL VENT
EIFS SYSTEM
CHAMFER EDGE
EXISTING CONCRETE SLAB
EXISTING SUPPORT
WALLS TO REMAIN
EXISTING CONCRETE PANEL
TILE OVER EXISTING CONCRETE SLAB
TOP AND EDGE FLUSH TO WALL
PRE-FINISHED SHEET
METAL SILL FLASHING
WINDOW AS SCHEDULED
EXISTING STONE FACE
BACKER ROD AND SEALANT - BOTH
SIDES
PRE-FINISHED SHEET METAL
FLASHING WITH WEEP
LEVEL 01
ELEV. = 100'-0"
A4
ELEV. = 107'-0"
B.O. WINDOW
SCALE: 1-1/2" = 1'-0" 0"4"8" 8"
PLAN DETAIL
PT-3
EXISTING GRANITE
CEMENT BOARD
EXTERIOR
EIFS INFILL PANEL
EIFS SYSTEM
PORCELAIN TILE ON
CEMENT BOARD
3-5/8" METAL STUD
PORCELAIN TILE ON
CEMENT BOARD
5" +/-
3-5/8" METAL STUDS
1'-1 1/4"
DIAPER DISPOSAL UNIT
SCALE: 1-1/2" = 1'-0" 0"4"8" 8"
RECESSED WALL SECTION DETAIL
PORCELAIN TILE WRAPPING
TOP AND EDGE OF EXISTING
CONCRETE LEDGE
EXTERIOR
EXISTING GRANITE BEYOND
EXTERIOR SHEATHING
TREATED 2X BLOCKING
PRE-FINISHED SHEET METAL
FLASHING & WEEP
SPRAY FOAM INSULATION
EXISTING CONCRETE PANEL
STONE WALL FACE BEYOND
1"
SCALE: 1/2" = 1'-0" 2' 1' 0 2'
RESTROOM 103 - WEST
SCALE: 1/2" = 1'-0" 2' 1' 0 2'
RESTROOM 103 - NORTH
SCALE: 1/2" = 1'-0" 2' 1' 0 2'
RESTROOM 103 - EAST
SCALE: 1/2" = 1'-0" 2' 1' 0 2'
RESTROOM 103 - SOUTH
LEVEL 01
ELEV. = 100'-0"
GB-1
LEVEL 01
ELEV. = 100'-0"
LEVEL 01
ELEV. = 100'-0"
LEVEL 01
ELEV. = 100'-0"
BCT-1
GB-1
PH-1 (OWNER
PROVIDED
CONTRACTOR
INSTALLED)
BCT-1
MIRROR
ND-1
2'- 9 3
/4"
3'- 3"
PT-2 (TYP.)
PT-3 (TYP.)
PT-2 (TYP.)
PT-3 (TYP.)
PT-2 (TYP.)
PT-3 (TYP.)
PT-2 (TYP.)
PT-3 (TYP.)
A4
1 SIM.
INFILL OPENINGS (SEE PLANS)
RECESSED
A4
5' MINIMUM CLEARANCE
HAND WASH, SOAP
AND HAND DRYER
COMBO (TYP.)
2'-
2'-
A4
INTERIOR ELEVATIONS AND
WALL SECTION
DATE:
TECH. REVIEW:
SUB SHEET NO. TITLE OF SHEET
PMIS NO.
DRAWING NO.
SHEET
OF
DRAWN BY:
DESIGNED:
DJS
DJS
KJH
15 FEB 2024
80071
RENOVATE MAIN RESTROOMS FROM THE LINCOLN
AND WASHINGTON PARKING STRUCTURES
MOUNT RUSHMORE NATIONAL MEMORIAL
KEYSTONE, SOUTH DAKOTA
305644
F eb
9,
- 4
:3 3p m Y
:\1
\1
-0
M
OU
NT
R
US
HM
OR
E
RE
ST
RO
OM
S\
DR
AW
IN
GS
\X
RE
F\
-0
_M
OR
U
BA
TH
RO
OM
- A
-5
IN
TE
RI
OR
E
LE
VA
TI
ON
S.
dw g
- U
SE
R da ria n
LEVEL 01
ELEV. = 100'-0"
LEVEL 01
ELEV. = 100'-0"
SCALE: 1/2" = 1'-0" 2' 1' 0 2'
WOMEN'S RESTROOM
SCALE: 1/2" = 1'-0" 2' 1' 0 2'
WOMEN'S RESTROOM
MIRROR (TYP)
HAND WASH, SOAP
AND HAND DRYER
COMBO (TYP.)
S.S. FRAMED
OPENING
2'-
3'- 3"
PT-2 (TYP.)
PT-3 (TYP.)
PT-2 (TYP.)
PT-3 (TYP.)
A6
A6
3 SIM.
REV.
LEVEL 01
ELEV. = 100'-0"
LEVEL 01
ELEV. = 100'-0"
SCALE: 1/2" = 1'-0" 2' 1' 0 2'
MEN'S RESTROOM
SCALE: 1/2" = 1'-0" 2' 1' 0 2'
MEN'S RESTROOM
2'-
3'- 3"
PT-2 (TYP.)
PT-3 (TYP.)
A6
A6
3 SIM.
REV.
S.S. FRAMED
OPENING
MIRROR (TYP)
PT-3 (TYP.)
HAND WASH, SOAP AND
HAND DRYER COMBO (TYP.)
PT-2 (TYP.)
SCALE: 1/2" = 1'-0" 2' 1' 0 2'
MEN'S TOILETS
5'- 0"
URINAL SCREEN
(TYP.)
PT-2 (TYP.)
PT-3 (TYP.)
1'- 0"1'-
4" 2'- 0"
EXISTING GRILLES
TO REMAIN
EXISTING GRILLES
TO REMAIN
LEVEL 01
ELEV. = 100'-0"
SCALE: 1/2" = 1'-0" 2' 1' 0 2'
MENS STALLS
PT-2 (TYP.)
PT-3 (TYP.)
TOILET PARTITIONS
(TYP.)
EXISTING GRILLES
TO REMAIN
EXISTING GRILLES
TO REMAIN
SCALE: 1/2" = 1'-0" 2' 1' 0 2'
MEN'S RESTROOM
S.S. FRAMED
OPENING PT-2 (TYP.)
PT-3 (TYP.)
S.S. ACCESS
PANEL -SEE
MECHANICAL
URINAL SCREEN
TOILET PARTITION
A5
INTERIOR ELEVATIONS
DATE:
TECH. REVIEW:
SUB SHEET NO. TITLE OF SHEET
PMIS NO.
DRAWING NO.
SHEET
OF
DRAWN BY:
DESIGNED:
DJS
DJS
KJH
15 FEB 2024
80071
RENOVATE MAIN RESTROOMS FROM THE LINCOLN
AND WASHINGTON PARKING STRUCTURES
MOUNT RUSHMORE NATIONAL MEMORIAL
KEYSTONE, SOUTH DAKOTA
305644
F eb
9,
- 4
:3 3p m Y
:\1
\1
-0
M
OU
NT
R
US
HM
OR
E
RE
ST
RO
OM
S\
DR
AW
IN
GS
\X
RE
F\
-0
_M
OR
U
BA
TH
RO
OM
- A
-5
IN
TE
RI
OR
E
LE
VA
TI
ON
S.
dw g
- U
SE
R da ria n
LEVEL 01
ELEV. = 100'-0"
ROOF
ELEV. = 115'-0"
A4
EIFS INFILL
SCALE: 1/4" = 1'-0" 4' 2' 0 4'
FRONT ELEVATION
EXISTING GRANITE
3'- 3"
MIRROR (TYP.)
PT-2 (TYP.)
PT-3 (TYP.)
1/2" SOLID SURFACE SHELF
10"
EXISTING WALL
SCALE: 3/4" = 1'-0" 6" 0 18"6"
RESTROOM DETAIL AT SINKS
1'-6"
4'- 9"
CEILING AS SCHEDULED
ELEV. = 108'-0"
B.O. SOFFIT
LIGHT FIXTURE-
SEE ELECTRICAL
8"
5/8" GWB ON 3-5/8" METAL STUD
VERTICAL FRAMING AND 2-1/2" METAL
STUD HORIZONTAL FRAMING
PORCELAIN TILE ON
CEMENT BOARD AT FACE
CORNER GUARD - SEE SPECS
6"
A6
LEVEL 01
ELEV. = 100'-0"
PT-2 (TYP.)
PT-3 (TYP.)
TOILET PARTITIONS
(TYP.)
SCALE: 1/2" = 1'-0" 2' 1' 0 2'
WOMENS STALLS
7'- 0"
EXISTING GRILLES
TO REMAIN
EXISTING GRILLES
TO REMAIN
1'- 2"
4'- 8"
LEVEL 01
ELEV. = 100'-0"
PT-2 (TYP.)
PT-3 (TYP.)
SCALE: 1/2" = 1'-0" 2' 1' 0 2'
WOMENS STALLS
TOILET PARTITIONS
(TYP.)
EXISTING GRILLES
TO REMAIN
EXISTING GRILLES
TO REMAIN
SCALE: 1/4" = 1'-0" 4' 2' 0 4'
REAR ELEVATION
LEVEL 01
ELEV. = 100'-0"
ROOF
ELEV. = 115'-0"
ROOF LADDER
CENTERED BETWEEN
WINDOWS - SEE SPECS
RAILING TO EXTEND 4' BEYOND
END OF ROOFTOP MECHANICAL
ON BOTH SIDES - SEE ROOF PLAN
SCALE: 1/2" = 1'-0" 2' 1' 0 2'
WOMEN'S RESTROOM
S.S. FRAMED
OPENING
PT-2 (TYP.)
PT-3 (TYP.)
S.S. ACCESS
PANEL - SEE
MECHANICAL
TOILET PARTITION TOILET PARTITION
1 1 /4"
PLYWOOD
SOLID SURFACE
PT-3 ON CEMENT BOARD
4"SCALE: 3" = 1'-0" 2"0 8"
SOLID SURFACE COUNTER DETAIL
A6
ELEVATIONS, INTERIOR
ELEVATION AND SECTION
DATE:
TECH. REVIEW:
SUB SHEET NO. TITLE OF SHEET
PMIS NO.
DRAWING NO.
SHEET
OF
DRAWN BY:
DESIGNED:
DJS
DJS
KJH
15 FEB 2024
80071
RENOVATE MAIN RESTROOMS FROM THE LINCOLN
AND WASHINGTON PARKING STRUCTURES
MOUNT RUSHMORE NATIONAL MEMORIAL
KEYSTONE, SOUTH DAKOTA
305644
F eb
9,
- 4
:3 3p m Y
:\1
\1
-0
M
OU
NT
R
US
HM
OR
E
RE
ST
RO
OM
S\
DR
AW
IN
GS
\X
RE
F\
-0
_M
OR
U
BA
TH
RO
OM
- A
-5
IN
TE
RI
OR
E
LE
VA
TI
ON
S.
dw g
- U
SE
R da ria n
5'-0" CLR.
3'- 0"
C
LR
A7
SCALE: 3/4" = 1'-0" 6" 0 18"6"
WOMEN'S RESTROOM - ENLARGED PLAN
5'- 0"
C
LR
2'-
7 1 /2"
C
LR
2'-
7 1 /2"
C
LR
2'-
7 1 /2"
C
LR
2'-
7 1 /2"
C
LR
2'- 6"
C
LR
2'-
6" C
LR
2'- 6"
C
LR
2'-
6" C
LR
2'- 6 3
/8" C
LR
5'-0" CLR.
ND-1
PH-1 (OWNER PROVIDED,
CONTRACTOR INSTALLED) (TYP.)
ND-2
ND-2
ND-2
ND-2
ND-2
5'- 0 1
/4" C
LR
5'-0" CLR.
SCALE: 3/4" = 1'-0" 6" 0 18"6"
MEN'S RESTROOM - ENLARGED PLAN
A7
2'- 7 1
/2" C
LR
2'- 7 1
/2" C
LR
2'- 7 1
/2" C
LR
2'- 7 1
/4" C
LR
PH-1 (OWNER PROVIDED,
CONTRACTOR INSTALLED (TYP.)
PH-1 (OWNER PROVIDED,
CONTRACTOR INSTALLED)
ND-1
SC-1
PT-2(TYP.)
PT-3 (TYP.)
TOILET
PARTITION
GB-1
2'-
1'-0" 3'-6"
PT-2 (TYP.)
PT-3 (TYP.)
5' MINIMUM CLEARANCE
TOILET
PARTITION
1'-6"
3'-0" 6"
1'-0"2'-0"
SCALE: 1/2" = 1'-0" 2' 1' 0 2'
WOMEN'S RESTROOM - ELEVATION
SCALE: 1/2" = 1'-0" 2' 1' 0 2'
WOMEN'S RESTROOM - ELEVATION
GB-1
PH-1 (OWNER PROVIDED,
CONTRACTOR INSTALLED)
PT-2 (TYP.)
PT-3 (TYP.)
TOILET
PARTITION
GB-1
2'-
1'-0"3'-6"
GB-1
PT-2 (TYP.)
PT-3 (TYP.)
5' MINIMUM CLEARANCE
TOILET
PARTITION
1'-6"
3'-0"6"
1'-0" 2'-0"
SCALE: 1/2" = 1'-0" 2' 1' 0 2'
MEN'S RESTROOM - ELEVATION
SCALE: 1/2" = 1'-0" 2' 1' 0 2'
MEN'S RESTROOM - ELEVATION
ND-1
LEVEL 01
ELEV. = 100'-0"
SCALE: 1/2" = 1'-0" 2' 1' 0 2'
WOMEN'S LOBBY
SCALE: 1/2" = 1'-0" 2' 1' 0 2'
MEN'S LOBBY
RELOCATED CAMERA - SEE ELECTRICAL RELOCATED CAMERA - SEE ELECTRICAL
A7
ENLARGED FLOOR PLANS
DATE:
TECH. REVIEW:
SUB SHEET NO. TITLE OF SHEET
PMIS NO.
DRAWING NO.
SHEET
OF
DRAWN BY:
DESIGNED:
DJS
DJS
KJH
15 FEB 2024
80071
RENOVATE MAIN RESTROOMS FROM THE LINCOLN
AND WASHINGTON PARKING STRUCTURES
MOUNT RUSHMORE NATIONAL MEMORIAL
KEYSTONE, SOUTH DAKOTA
305644
F eb
9,
- 4
:3 3p m Y
:\1
\1
-0
M
OU
NT
R
US
HM
OR
E
RE
ST
RO
OM
S\
DR
AW
IN
GS
\X
RE
F\
-0
_M
OR
U
BA
TH
RO
OM
- A
-5
IN
TE
RI
OR
E
LE
VA
TI
ON
S.
dw g
- U
SE
R da ria n
WOMEN'S
LOBBY
RESTROOM
RESTROOM
103 MEN'S
LOBBY
WOMEN'S
RESTROOM
MEN'S
RESTROOM
JANITOR
ROOM
MECHANICAL
ROOM
CLOSET
WOMEN'S
TOILETS
MEN'S
TOILETS
A01 A01
A01A01
DATE:
TECH. REVIEW:
SUB SHEET NO. TITLE OF SHEET
PMIS NO.
DRAWING NO.
SHEET
OF
DRAWN BY:
DESIGNED:
DJS
DJS
KJH
15 FEB 2024
80071
RENOVATE MAIN RESTROOMS FROM THE LINCOLN
AND WASHINGTON PARKING STRUCTURES
MOUNT RUSHMORE NATIONAL MEMORIAL
KEYSTONE, SOUTH DAKOTA
305644
F eb
9,
- 5
:0 4p m Y
:\1
\1
-0
M
OU
NT
R
US
HM
OR
E
RE
ST
RO
OM
S\
DR
AW
IN
GS
\X
RE
F\
F
LO
OR
IN
G
PL
AN
.d wg
US
ER
d ar ian
FINAL CONSTRUCTION DOCUMENTS
A8
FLOOR PLAN - FLOORING
SCALE: 1/4" = 1'-0" 4' 2' 0 4'
FLOORING - FLOOR PLAN
N1
ARCHITECTURE - KEYNOTES:
A01 FLOORING TRANSITION STRIP - SEE SPECS
NOTES
DOOR AND FRAME SCHEDULE
NO. SIZE TYPE MAT.
FRAME
TYPE MAT. DEPTH DETAILS SHEET
DOOR
GLASS
KEY
TYPE
HDWR
SET
FIRE
RATING
DOOR
WD WOOD
HM HOLLOW METAL
AL ALUMINUM
SS STAINLESS STEEL
WG WIRE GLASS
CTG CLEAR TEMPERED GLASS
CTIG CLEAR TEMPERED INSULATED GLASS
LDG 9/16" LAMINATED DOOR GLASS
FRG 60-MINUTE FIRE-RATED GLASS
LEGEND
101 PR 3'-0" x 7'-0" x 1-3/4" EXIST. -- EXIST. -- -- -- -- -- -- 1 102 3'-0" x 7'-0" x 1-3/4" D01 SS F1 HM 5-7/8" -- -- HW # 1 -- 103 3'-0" x 7'-0" x 1-3/4" D01 SS F1 HM 5-7/8" -- -- HW # 1 -- 104 PR 3'-0" x 7'-0" x 1-3/4" EXIST. -- -- -- -- -- -- -- -- 1 105 4'-0" x 7'-0" x 1-3/4" D01 SS F1 HM 8-1/4" -- -- HW # 2 -- 106 4'-0" x 7'-0" x 1-3/4" D01 SS F1 HM 8-1/4" -- -- HW # 2 -- 107A 3'-0" x 7'-0" x 1-3/4" D01 SS F1 HM 8-1/4" -- -- HW # 3 -- 107B 3'-0" x 7'-0" x 1-3/4" D01 SS F1 HM 8-1/4" -- -- HW # 3 -- 108 3'-0" x 7'-0" x 1-3/4" EXIST. -- EXIST. -- -- -- -- -- -- 109 3'-0" x 7'-0" x 1-3/4" EXIST. -- EXIST. -- -- -- -- -- --
NOTES
ROOM FINISH SCHEDULE
NO. DESCRIPTION FLOOR BASE
NORTH WALL EAST WALL SOUTH WALL WEST WALL CEILING
MAT. FIN. MAT. FIN. HEIGHTMAT. FIN. MAT. FIN. MAT. FIN.
ATC ACOUSTICAL TILE CEILING
CONC CONCRETE
CPT CARPET
CT CERAMIC TILE
CTG CLEAR TEMPERED GLASS
EXIST. EXISTING
EXP EXPOSED
GWB GYPSUM WALLBOARD
P PAINT
RB RUBBER BASE
SC SPECIAL COATING
SS STAINLESS STEEL
PT PORCELAIN TILE
VB VINYL BASE
VT VINYL TILE
WP WALL PANEL
ROOM FINISH SCHEDULE LEGEND
NOTE: REFER TO COLOR SCHEDULE FOR ALL INTERIOR FINISHES.
101 WOMEN'S LOBBY EXIST. EXIST./RB-1 GWB P-1 GWB P-1 GWB P-1 GWB P-1 GWB P-2 10'-0" 4
102 RESTROOM PT-1 PT-2 PT-3 -- PT-3 -- PT-3 -- PT-3 -- GWB P-2 10'-0" 3
103 RESTROOM PT-1 PT-2 PT-3 -- PT-3 -- PT-3 -- PT-3 -- GWB P-2 10'-0" 3
104 MEN'S LOBBY EXIST. EXIST./ RB-1 GWB P-1 GWB P-1 GWB P-1 GWB P-1 GWB P-2 10'-0" 5
105 MEN'S RESTROOM PT-1 PT-2 PT-3 -- PT-3 -- PT-3 -- PT-3 -- GWB P-2 9'-6" 2, 3
106 WOMEN'S RESTROOM PT-1 PT-2 PT-3 -- PT-3 -- PT-3 -- PT-3 -- GWB P-2 9'-6" 2, 3 107 JANITOR ROOM EXIST. RB-1 EXIS/GWB P-1 EXIST. -- EXIS/GWB P-1 EXIST. -- EXP. -- --
108 CLOSET EXIST. EXIST. EXIST. -- EXIST. -- EXIST. -- EXIST. -- EXIST. -- --
109 MECHANICAL ROOM EXIST. EXIST. EXIST. EXIST. EXIST. EXIST. EXIST. EXIST. EXIST. EXIST. EXP. -- -- 110 WOMEN'S TOILET ROOM PT-1 PT-2 PT-3 -- PT-3 -- PT-3 -- PT-3 -- GWB P-2 9'-6" 1, 3 111 MEN'S TOILET ROOM PT-1 PT-2 PT-3 -- PT-3 -- PT-3 -- PT-3 -- GWB P-2 9'-6" 1, 3
ROOM FINISH SCHEDULE NOTES:
DOOR AND FRAME SCHEDULE NOTES:
1. ADD NEW DOOR OPERATOR AND PUSH BUTTON
2. SEE ARCH PLANS FOR S.S. FRAME F2 AT OPENING
INTO MENS AND WOMENS TOILET STALL AREAS.
1. SEE RCP FOR BULKHEAD AND HIGHER CEILING AT WINDOWS.
2. SEE RCP FOR BULKHEAD AT LIGHT COVE.
3. SEE SPECS FOR ALUMINUM COVE AT BASE AND FLOORING TRANSITION.
4. INSTALL VINYL BASE ON NORTH WALL. EXISTING BASE TO REMAIN IN REST OF ROOM.
5. INSTALL VINYL BASE ON SOUTH WALL. EXISTING BASE TO REMAIN IN REST OF ROOM.
SCALE: 1/4" = 1'-0" 4' 2' 0 4'
DOOR TYPES
SCALE: 1/4" = 1'-0" 4' 2' 0 4'
FRAME TYPES
CONTROL JOINT
ON EACH SIDE
OF FRAME TO
CEILING
SCALE: 1/4" = 1'-0" 4' 2' 0 4'
TYPICAL CONTROL JOINT DETAILS AT GWB
SEE SCHED.
SE
E
SC
HE
DU
LE
FLOOR
LINE
D01
STAINLESS STEELF1
A
A
S.S. FRAME
2'- 8"
VE
RI
FY
6'-4 3/4"
F2
F.
V.
B
B
SIM.
F3
3'- 4"
2'-8"
SEE SCHED.
SE
E
SC
HE
DU
LE
C
C
S.S. FRAME
F4
CTIG
EXISTING
ALUMINUM
FRAMING
RE-GLAZE
WITH CTIG
A4
A1
1'SCALE: 1" = 1'-0" 0 1' 2'
WALL TYPES
SE
E
SC
HE
DU
LE
EXISTING 3-5/8" METAL
STUD
B1
GWB CEILING
SE
E
SC
HE
DU
LE
3-5/8" METAL STUD
WALL TILE AS SCHEDULED
C1
6" METAL STUD
6"
5/8 GWB
CEMENT BOARDSE
E
SC
HE
DU
LE
GWB CEILING
WALL TILE AS SCHEDULED
BASE AS SCHEDULED
EXISTING 5/8" GWB
CEMENT BOARD
WALL TILE AS
SCHEDULED
6"
GWB CEILING
SE
E
SC
HE
DU
LE
3-5/8" METAL STUD
CEMENT BOARD -
BOTH SIDES
WALL TILE AS
SCHEDULED - BOTH
SIDES
6"
GWB CEILING
A2
6"
D1
6" METAL STUD
6"
CEMENT BOARD - BOTH SIDES
SE
E
SC
HE
DU
LE
GWB CEILING
WALL TILE AS SCHEDULED -
BOTH SIDES
BASE AS SCHEDULED
CEMENT BOARD
BATT INSULATION
BATT INSULATION
BATT INSULATION
BATT INSULATION
BATT INSULATION
LOBBY SIDERESTROOM SIDE
METAL STUDS
SCALE: 1-1/2" = 1'-0" 8"4"0 16"
HEAD/JAMB DETAIL
A
5/8
2"
SPOT GROUT
HOLLOW METAL FRAME
DOOR AS SCHEDULED
SCALE: 1-1/2" = 1'-0" 8"4"0 16"
HEAD/JAMB DETAIL
B
ALUMINUM FRAME
2"
"J" MOLD EA SIDE
GLAZING
SEE FLOOR PLAN
FOR WALL TYPE
SEE FLOOR PLAN
FOR WALL TYPE
6" METAL STUD FRAMING
SCALE: 1-1/2" = 1'-0" 8"4"0 16"
HEAD/JAMB DETAIL
C
2"
SPOT GROUT
STAINLESS STEEL FRAME
PORCELAIN TILE ON
CEMENT BOARD
DATE:
TECH. REVIEW:
SUB SHEET NO. TITLE OF SHEET
PMIS NO.
DRAWING NO.
SHEET
OF
DRAWN BY:
DESIGNED:
DJS
DJS
KJH
15 FEB 2024
80071
RENOVATE MAIN RESTROOMS FROM THE LINCOLN
AND WASHINGTON PARKING STRUCTURES
MOUNT RUSHMORE NATIONAL MEMORIAL
KEYSTONE, SOUTH DAKOTA
305644
F eb
9,
- 5
:0 4p m Y
:\1
\1
-0
M
OU
NT
R
US
HM
OR
E
RE
ST
RO
OM
S\
DR
AW
IN
GS
\ 1
-0
_A
6.
dw g
- U
SE
R da ria n
FINAL CONSTRUCTION DOCUMENTS
SCHEDULES, DOORS,
FRAMES AND WALL TYPESA9
LOBBY
RESTROOM
RESTROOM
103 MEN'S
LOBBY
WOMEN'S
RESTROOM
MEN'S
RESTROOM
JANITOR
ROOM
MECHANICAL
ROOM
CLOSET
WOMEN'S
TOILETS
MEN'S
TOILETS
A01
A01A01
A01 A01
A01A01
A02A02
A01A01
A01A01A02 A02
A10
A6
A10
A6
A01
A03 A03
SIM.
ELEV. = 109'-6"
FINISH FLOOR
ELEV. = 110'-0"
FINISH FLOOR
MOISTURE RESISTANT GWB
ON 3-5/8" METAL STUDS
3'- 6"
GALVANIZED STEEL 1-1/2" STANDARD PIPE RAIL -
ANCHOR TO SIDE OF GRANITE W/ 3/8" EPOXY
ANCHOR BOLTS - SEE ROOF PLAN FOR LENGTH.
UPRIGHTS AT 6' O.C. MAX. +/
- 8
2'-0"
EXISTING WINDOW
A10
REFLECTED CEILING PLAN
SCALE: 1/4" = 1'-0" 4' 2' 0 4'
CEILING PLAN
N1
DATE:
TECH. REVIEW:
SUB SHEET NO. TITLE OF SHEET
PMIS NO.
DRAWING NO.
SHEET
OF
DRAWN BY:
DESIGNED:
DJS
DJS
KJH
15 FEB 2024
80071
RENOVATE MAIN RESTROOMS FROM THE LINCOLN
AND WASHINGTON PARKING STRUCTURES
MOUNT RUSHMORE NATIONAL MEMORIAL
KEYSTONE, SOUTH DAKOTA
305644
F eb
9,
- 5
:0 5p m Y
:\1
\1
-0
M
OU
NT
R
US
HM
OR
E
RE
ST
RO
OM
S\
DR
AW
IN
GS
\X
RE
F\
-0
_M
OR
U
BA
TH
RO
OM
A-
CP
LA
N.
dw g
- U
SE
R da ria n
FINAL CONSTRUCTION DOCUMENTS
ARCHITECTURE - KEYNOTES:
A01 GWB CEILING SHOWN HATCHED
A02 GWB BULKHEAD
A03 12" X 12"ACCESS PANEL - COORDINATE LOCATION WITH VALVE - SEE MECHANICAL
SCALE: 3/4" = 1'-0" 6" 0 18"6"
CEILING PLAN SECTION
ROOF TOP MECHANICAL
UNIT - SEE MECHANICAL
RAILING TO EXTEND 4' BEYOND
END OF ROOFTOP MECHANICAL
ON BOTH SIDES
+/- 18'-2 3/4"
EXHAUST VENT - SEE
MECHANICAL
CONDENSING UNITS - SEE
MECHANICAL
A10
A11
4'-0"4'-0"
A11
(TYP.)
PROPANE GAS PIPING ROOF
PENETRATION - SEE MECHANICAL
HIGH DOMED, CAPPED GASKETED
FASTENERS AS REQUIRED
WOOD BLOCKING AS
REQUIRED
METAL CURB
COUNTER FLASHING
EXISTING
RIGID INSULATION
EXISTING BALLAST
EXISTING ROOF
MEMBRANE
EXISTING
ROOF STRUCTURE
SCALE: 1-1/2" = 1'-0" 8"4"0 16"
ROOF CURB DETAIL
" M
IN
8"
CANT STRIP FILLER
SELF-ADHERED MEMBRANE FLASHING
1'-1 3/4" (VERIFY)
MAX OPENING SIZE
SAWCUT AND REMOVE CONCRETE SLAB
BETWEEN CONCRETE JOISTS - VERIFY
LOCATION BY PILOT HOLE PRIOR TO CUTTING
EXISTING CONCRETE ROOF JOISTS - DO NOT
CUT OR DAMAGE.
A11
ROOF PLAN
DATE:
TECH. REVIEW:
SUB SHEET NO. TITLE OF SHEET
PMIS NO.
DRAWING NO.
SHEET
OF
DRAWN BY:
DESIGNED:
DJS
DJS
KJH
15 FEB 2024
80071
RENOVATE MAIN RESTROOMS FROM THE LINCOLN
AND WASHINGTON PARKING STRUCTURES
MOUNT RUSHMORE NATIONAL MEMORIAL
KEYSTONE, SOUTH DAKOTA
305644
F eb
9,
- 4
:5 6p m Y
:\1
\1
-0
M
OU
NT
R
US
HM
OR
E
RE
ST
RO
OM
S\
SU
BM
IT
TA
LS
\0 3_
0%
F
IN
AL
S
UB
M
IT
TA
L\
DR
AW
IN
GS
\D
W G' s\ A1
1.
dw g
- U
SE
R da ria n
FINAL CONSTRUCTION DOCUMENTS
SCALE: 1/4" = 1'-0" 4' 2' 0 4'
ROOF PLAN
N1
DEMOLITION NOTES:
1. CONTRACTOR IS URGED TO VISIT SITE AND FIELD VERIFY ALL EXISTING CONDITIONS
PRIOR TO BIDDING PROJECT.
2. THE OWNER SHALL HAVE THE FIRST RIGHT OF SALVAGE FOR ALL MECHANICAL,
ELECTRICAL, AND PLUMBING ITEMS BEING REMOVED. IF OWNER DECLINES, THE
CONTRACTOR SHALL REMOVE FROM THE PREMISES AND DISPOSE OF PROPERLY.
VERIFY OWNER'S INTENT PRIOR TO REMOVAL OR DEMOLITION.
3. INFORMATION PERTAINING TO THE EXISTING BUILDING HAS BEEN OBTAINED THROUGH
THE BUILDINGS ORIGINAL DRAWINGS WHERE AVAILABLE. REPORT DISCREPANCIES TO
THE ARCHITECT/ENGINEER PRIOR TO ANY DEMOLITION. CONTRACTOR SHALL FIELD
VERIFY ALL EXISTING CONDITIONS PRIOR TO COMMENCING WORK.
4. COORDINATE SHUT DOWN OF ALL UTILITIES FOR DEMOLITION WORK WITH THE OWNER.
5. DISCONNECT AND REMOVE MECHANICAL SYSTEMS, EQUIPMENT, AND COMPONENTS AS
INDICATED TO BE REMOVED.
PIPING TO BE REMOVED: REMOVE PORTION OF PIPING INDICATED TO BE REMOVED AND
CAP REMAINING PIPING WITH THE SAME OR COMPATIBLE PIPING MATERIAL.
PIPING TO BE ABANDONED IN PLACE: DRAIN PIPING AND CAP WITH THE SAME OR
COMPATIBLE PIPING MATERIAL.
DUCTS TO BE REMOVED: REMOVE PORTIONS OF DUCT AND CAP REMAINING DUCTS
WITH THE SAME OR COMPATIBLE DUCTWORK MATERIAL.
DUCTS TO BE ABANDONED IN PLACE: CAP DUCTS WITH THE SAME OR COMPATIBLE
DUCTWORK MATERIAL.
EQUIPMENT TO BE REMOVED: DISCONNECT AND CAP SERVICES AND REMOVE
EQUIPMENT.
EQUIPMENT TO BE REMOVED AND REINSTALLED: DISCONNECT AND CAP SERVICES AND
REMOVE, CLEAN, AND STORE EQUIPMENT. WHEN APPROPRIATE, REINSTALL,
RECONNECT, AND MAKE EQUIPMENT FULLY OPERATIONAL.
EQUIPMENT TO BE REMOVED AND SALVAGED: DISCONNECT AND CAP SERVICES AND
REMOVE EQUIPMENT AND DELIVER TO OWNER.
6. IF PIPE OR EQUIPMENT INSULATION TO REMAIN IS DAMAGED DURING THE
PERFORMANCE OF THIS PROJECT, THE CONTRACTOR SHALL REMOVE DAMAGED OR
UNSERVICEABLE PORTIONS AND REPLACE WITH NEW PRODUCTS OF EQUAL CAPACITY
AND QUALITY.
7. COORDINATE DEMOLITION WITH THE WORK OF OTHER TRADES. PROVIDE TEMPORARY
UTILITIES AS REQUIRED TO ALLOW THE WORK OF OTHER TRADES TO PROCEED.
8. DUCTWORK, PIPING, PLUMBING, AND EQUIPMENT SHOWN BOLD SHALL BE REMOVED TO
THE EXTENTS INDICATED.
HVAC GENERAL NOTES:
1. DO NOT RUN DUCTWORK , PIPING, AND PLUMBING ABOVE ELECTRICAL
PANELS OR IN CODE REQUIRED CLEARANCE SPACES. COORDINATE ALL
ROUTING WORK WITH ALL OTHER TRADES.
2. DO NOT RUN DUCTWORK, PIPING, AND PLUMBING ABOVE OR THROUGH
INFORMATION TECHNOLOGY AND DATA CLOSETS, IDF, AND MDF ROOMS.
COORDINATE ALL ROUTING WITH ALL OTHER TRADES.
3. DRAWINGS, PLANS, SCHEMATICS, AND DIAGRAMS INDICATE THE GENERAL
LOCATIONS AND THE ARRANGEMENT OF SYSTEMS. WHEREVER PRACTICAL,
INSTALL SYSTEMS AS INDICATED. PROVIDE OFFSETS AND ELEVATION
CHANGES TO DUCTWORK, PIPING, AND PLUMBING AS REQUIRED TO
COMPLETE THE LAYOUT AND COORDINATION PROCESS AS WELL AS MEET
ALL REQUIREMENTS OF THE CONTRACT DOCUMENTS.
4. SEE ARCHITECTURAL REFLECTED CEILING PLANS FOR DIFFUSER,
REGISTER, GRILLE, AND CEILING MOUNTED DEVICE LOCATIONS.
5. CONTRACTOR SHALL COORDINATE LOCATION OF DUCTWORK IN CEILING
SPACE WITH ALL TRADES PRIOR TO FABRICATION AND INSTALLATION OF
DUCTWORK.
6. FOR GENERAL DUCTWORK CONSTRUCTION, SEE DUCT FITTING DETAILS.
7. DUCTWORK AND EQUIPMENT SHOWN WITH THIN LINES INDICATES EXISTING
TO REMAIN. DUCTWORK AND EQUIPMENT SHOWN WITH BOLD LINES
INDICATES NEW.
8. PROVIDE VOLUME DAMPER IN ALL BRANCH TAKEOFFS CONNECTING TO
DIFFUSERS, REGISTERS, OR GRILLES AND IN LOCATIONS INDICATED.
9. PROVIDE REMOTE VOLUME DAMPER BALANCING POSITION CONTROL FOR
ALL VOLUME DAMPERS MOUNTED ABOVE NON-ACCESSIBLE CEILINGS.
10. PROVIDE CLEARANCES TO ALL EQUIPMENT AS REQUIRED BY
MANUFACTURERS' INSTALLATION AND OPERATION REQUIREMENTS AND/OR
BY CODE.
11. INSTALL ALL DUCT AND PIPING IN MECHANICAL ROOMS AS HIGH AS
POSSIBLE. PROVIDE 7'-6" MINIMUM HIGH ACCESS PATHWAYS TO ALL
EQUIPMENT.
12. COORDINATE LOCATIONS OF ALL EQUIPMENT HOUSEKEEPING PADS WITH
GENERAL CONTRACTOR. MECHANICAL CONTRACTOR IS RESPONSIBLE FOR
INSTALLATION OF EQUIPMENT HOUSEKEEPING PADS.
13. CAP ENDS OF ALL INSTALLED DUCTWORK DURING CONSTRUCTION TO
MINIMIZE DIRT, DEBRIS, AND FOREIGN OBJECTS FROM ENTERING THE DUCT
SYSTEM.
14. COORDINATE SCHEDULE OF SHUTDOWN FOR EXISTING HVAC SYSTEMS,
FOR INSTALLATION OF NEW HVAC SYSTEMS, WITH THE OWNER'S
REPRESENTATIVE PRIOR TO SHUTDOWN.
15. ALL INSULATION SHALL MEET THE ENERGY CODE'S INSTALLED R VALUE
REQUIREMENTS.
FIRE PROTECTION GENERAL NOTES:
1. COORDINATE LOCATION OF FIRE SPRINKLER PIPING AND HEADS WITH
ALL TRADES PRIOR TO FINALIZATION OF SHOP DRAWINGS AND
HYDRAULIC CALCULATIONS.
2. SEE ARCHITECTURAL REFLECTED CEILING PLANS FOR LOCATIONS OF
ALL CEILING MOUNTED DEVICES.
3. COORDINATE SHUT DOWN OF EXISTING FIRE SERVICE WITH OWNERS
REPRESENTATIVE.
4. ALL WORK SHALL COMPLY WITH NFPA AND THE LOCAL AUTHORITIES
HAVING JURISDICTION, AND OWNERS INSURANCE CARRIER.
5. DIELECTRIC NIPPLES OR FLANGE INSULATION KITS SHALL BE UTILIZED
FOR ALL DISSIMILAR PIPE CONNECTIONS. DIELECTRIC UNIONS WILL
NOT BE ACCEPTED.
PIPING GENERAL NOTES:
1. DO NOT RUN PIPING, PLUMBING, AND DUCTWORK ABOVE ELECTRICAL
PANELS OR IN CODE REQUIRED CLEARANCE SPACES. COORDINATE ALL
ROUTING WORK WITH ALL OTHER TRADES.
2. DRAWINGS, PLANS, SCHEMATICS, AND DIAGRAMS INDICATE THE GENERAL
LOCATIONS AND THE ARRANGEMENT OF SYSTEMS. WHEREVER PRACTICAL,
INSTALL SYSTEMS AS INDICATED. PROVIDE OFFSETS AND ELEVATION
CHANGES TO PIPING, PLUMBING, AND DUCTWORK AS REQUIRED TO
COMPLETE THE LAYOUT AND COORDINATION PROCESS AS WELL AS MEET
ALL REQUIREMENTS OF THE CONTRACT DOCUMENTS.
3. SIZE AND ROUTE REFRIGERANT PIPING PER MANUFACTURERS'
RECOMMENDATIONS.
4. ROUTE ALL HORIZONTAL HVAC PIPING IN MECHANICAL ROOMS AT A
MINIMUM OF 7'-6" ABOVE FINISHED FLOOR.
5. PIPING AND EQUIPMENT SHOWN WITH THIN LINES INDICATES EXISTING TO
REMAIN. PIPING AND EQUIPMENT SHOWN WITH BOLD LINES INDICATES NEW.
6. ALL PIPING INSULATION SHALL MEET THE ENERGY CODE'S INSTALLED R
VALUE REQUIREMENTS.
7. DIELECTRIC NIPPLES OR FLANGE INSULATION KITS SHALL BE UTILIZED FOR
ALL DISSIMILAR PIPE CONNECTIONS. DIELECTRIC UNIONS WILL NOT BE
ACCEPTED.
PLUMBING GENERAL NOTES:
1. DO NOT RUN PLUMBING, PIPING, AND DUCTWORK ABOVE ELECTRICAL
PANELS OR IN CODE REQUIRED CLEARANCE SPACES. COORDINATE ALL
ROUTING WORK WITH ALL OTHER TRADES.
2. DO NOT RUN PLUMBING, PIPING, AND DUCTWORK ABOVE OR THROUGH
INFORMATION TECHNOLOGY AND DATA CLOSETS, IDF, AND MDF ROOMS.
COORDINATE ALL ROUTING WITH ALL OTHER TRADES.
3. DRAWINGS, PLANS, SCHEMATICS, AND DIAGRAMS INDICATE THE GENERAL
LOCATIONS AND THE ARRANGEMENT OF SYSTEMS. WHEREVER PRACTICAL,
INSTALL SYSTEMS AS INDICATED. PROVIDE OFFSETS AND ELEVATION
CHANGES TO PLUMBING, PIPING, AND DUCTWORK AS REQUIRED TO
COMPLETE THE LAYOUT AND COORDINATION PROCESS AS WELL AS MEET
ALL REQUIREMENTS OF THE CONTRACT DOCUMENTS.
4. CLEAN EXISTING UNDERGROUND SANITARY PIPING TO MANHOLE
CONNECTION AND ALL EXISTING ABOVEGROUND SANITARY PIPING IN
CRAWLSPACE WITH CABLE AND BLADE PRIOR TO INSTALLATION AND
CONNECTION OF NEW PIPING. VISUALLY INSPECT PIPING AFTER CLEANING
TO CHECK FOR DAMAGE. REPAIR ANY PIPING FAILURE DUE TO CLEANING.
5. SEE SPECIFICATIONS OR PLUMBING FIXTURE SCHEDULE FOR ALL PLUMBING
CONNECTION SIZES TO ALL PLUMBING FIXTURES.
6. LOCATE PLUMBING VENTS THROUGH THE ROOF AT A MINIMUM OF 10'-0"
AWAY FROM ALL OUTDOOR AIR INTAKES ON HVAC EQUIPMENT OR
OPERABLE WINDOWS.
7. PROVIDE WALL AND FLOOR MOUNTED SEWER CLEANOUTS AS REQUIRED BY
CODE AND AS INDICATED. COORDINATE LOCATION IN FIELD.
8. INSTALL AND ROUTE ALL FUEL GAS PIPING AS REQUIRED BY CODE.
9. TERMINATE ALL GAS FLUE VENTS A MINIMUM OF 2'-0" HIGHER THAN ANY
SURFACE OR EQUIPMENT WITHIN 10'-0" OR AS REQUIRED BY CODE.
10. PROVIDE GAS PRESSURE REGULATORS ON ALL GAS FIRED EQUIPMENT,
INCLUDING REGULATOR VENT PIPING, SHUTOFF VALVE, DIRT LEG, AND
UNION. REGULATE GAS PRESSURE AS REQUIRED FOR EACH SPECIFIC PIECE
OF GAS FIRED EQUIPMENT AND PER MANUFACTURER'S RECOMMENDATIONS.
11. DO NOT ROUTE PLUMBING BRANCHES OR MAINS WITHIN SPACE REQUIRED
TO SERVICE ALL HVAC EQUIPMENT ABOVE CEILINGS.
12. PIPING AND FIXTURES SHOWN WITH THIN LINES INDICATES EXISTING TO
REMAIN. PIPING AND FIXTURES SHOWN WITH BOLD LINES INDICATES NEW.
13. COORDINATE SHUT DOWN OF EXISTING WATER SERVICE WITH OWNERS
REPRESENTATIVE.
14. FURNISH AND INSTALL SHUT-OFF VALVES FOR WATER SUPPLY AT ALL
EQUIPMENT ITEMS.
15. COORDINATE FINISH FLOOR ELEVATIONS TO SET FLOOR DRAINS AND FLOOR
SINKS.
16. SAW CUT AND REMOVE FLOOR AS REQUIRED FOR INSTALLATION OF NEW
PIPING.
17. PIPING IN EXTERIOR BUILDING WALLS SHALL BE LOCATED ON THE WARM
SIDE OF BUILDING INSULATION AND VAPOR BARRIER. BUILDING INSULATION
SHALL RUN CONTINUOUS BETWEEN PIPING AND EXTERIOR OF BUILDING.
18. PVC PIPING SHALL NOT BE INSTALLED IN RETURN AIR PLENUMS.
19. SEE WATER HAMMER ARRESTOR DETAIL FOR WATER HAMMER ARRESTOR
REQUIREMENTS ON DOMESTIC WATER PIPING.
1. THIN LINE ITEMS INDICATE EXISTING TO REMAIN. BOLD LINE ITEMS INDICATE
NEW WORK.
2. CONTRACTOR IS RESPONSIBLE FOR ANY CUTTING AND PATCHING NEEDED
FOR MECHANICAL INSTALLATION. PATCHING MUST MATCH EXISTING.
GENERAL NOTES:
Fe br ua ry
, 2
2:0 1p m
_M
0.1 .dw g mg re go ry
NOTE:
DO NOT SCALE DRAWINGS. VERIFY ALL DIMENSIONS
and clearances from ARCHITECTURAL, STRUCTURAL, shop and other appropriate drawing or at site. lay out and coordinate all work prior to installation to provide clearances required for operation, maintenance, and codes and verify non-interference with other work. DO NOT FABRICATE
PRIOR TO VERIFICATION OF CLEARANCE FOR ALL
TRADES. READ SPECIFICATIONS.
COPYRIGHT 2024
Permission to reproduce all or part of this drawing is hereby granted solely for the limited purpose of construction of this project or archiving. Unauthorized copying, disclosure or construction use without written permission of Alvine Engineering is prohibited by copyright law.
AE# 20239894
DATE:
TECH. REVIEW:
SUB SHEET NO. TITLE OF SHEET
PMIS NO.
DRAWING NO.
SHEET
OF
DRAWN BY:
DESIGNED:
15 FEB 2024
80071
RENOVATE MAIN RESTROOMS FROM THE LINCOLN
AND WASHINGTON PARKING STRUCTURES
MOUNT RUSHMORE NATIONAL MEMORIAL
KEYSTONE, SOUTH DAKOTA
305644
FINAL CONSTRUCTION DOCUMENTS
MRG
MRG
BAH
MECHANICAL GENERAL NOTES
M0.1
AutoCAD SHX Text C
F
SM
FHC
FVC
PIV
FS
DESCRIPTIONSYMBOLSYMBOL DESCRIPTION SYMBOL DESCRIPTION
FIRE PROTECTION
FIRE LINE
CEILING CLEAN AGENT NOZZLE FLUSH FIRE PUMP TEST HEADERSPRINKLER MAIN
SUB-FLOOR CLEAN AGENT NOZZLE FREE-STANDING FIRE PUMP TEST HEADERCLEAN AGENT
CEILING DETECTOR FREE-STANDING FIRE DEPARTMENT CONNECTIONSPRINKLER BRANCH AND HEADS
SUB-FLOOR DETECTOR FLUSH FIRE DEPARTMENT CONNECTIONRECESSED PENDANT SPRINKLER
CLEAN AGENT ALARM BELL FIRE DEPARTMENT CONNECTIONCONCEALED PENDANT SPRINKLER
CLEAN AGENT HORN WITH STROBE FIRE HOSE CABINETUPRIGHT SPRINKLER
ELECTRIC PULL STATION FIRE HOSE VALVE CABINETDRY PENDANT SPRINKLER
ABORT PULL STATION POST INDICATOR VALVEHORIZONTAL SIDEWALL SPRINKLER
CLEAN AGENT PRESSURE SWITCH ISOLATION VALVE WITH TAMPER SWITCHDRY HORIZONTAL SIDEWALL SPRINKLER
WARNING LIGHT ALARM CHECK VALVEPRE-ACTION HEAT DETECTOR
CLEAN AGENT PANEL DRY PIPE VALVEPRE-ACTION PULL STATION
FIRE HYDRANT FLOW SWITCHPRE-ACTION ALARM BELL
ALARM BELL WATER FLOW SWITCHPRE-ACTION TROUBLE STROBE
ALARM STROBEDELUGE VALVE FOR PRE-ACTION SYSTEM
PRE-ACTION RELEASING PANEL FIRE DEPARTMENT HOSE VALVE
CA
PA
CAP
MECHANICAL SYMBOLS MECHANICAL SYMBOLS
SYMBOLS INDICATED HERE AND NOT USED IN THE
CONTRACT DOCUMENTS DO NOT APPLY TO THIS
PROJECT. ADDITIONAL SYMBOLS AND ABBREVIATIONS
MAY BE INDICATED IN THE CONTRACT DOCUMENTS.
FINTUBE-TYPE (SHADED AREA INDICATES
CAPACITY MBH ELEMENT LOCATION)
VOLUME DAMPER
DESCRIPTIONSYMBOLSYMBOL DESCRIPTION SYMBOL DESCRIPTION
HEATING - VENTILATING - AIR-CONDITIONING
T RS
T
H
A
S
P T
FS
AD
L"
D"
FT-1
MBH
XØ
X/X
SD
M
CFM
SIZE TYPE
CFM
SIZE TYPE
FRD
FSD
M
MCO2
CHILLED WATER SUPPLY
CHILLED WATER RETURN
CONDENSATE OR BOILER FEED PUMP DISCHARGE
CONDENSER WATER SUPPLY FROM TOWER
CONDENSER WATER RETURN TO TOWER
COIL OR EQUIPMENT DRAIN
GLYCOL SUPPLY
GLYCOL RETURN
FUEL OIL SUPPLY
FUEL OIL RETURN
FUEL OIL VENT
HEAT PUMP WATER SUPPLY
HEAT PUMP WATER RETURN
HIGH PRESSURE CONDENSATE RETURN
HIGH PRESSURE STEAM
HOT WATER SUPPLY
HOT WATER RETURN
LOW PRESSURE CONDENSATE RETURN
LOW PRESSURE STEAM
MEDIUM PRESSURE CONDENSATE RETURN
MEDIUM PRESSURE STEAM
REFRIGERANT LIQUID
REFRIGERANT SUCTION
REFRIGERANT HOT GAS DISCHARGE
BACK-DRAFT DAMPER (COUNTER BALANCED)B.D.D.
LPS
MPS
HPS
LPR
MPR
HPR
HWS
HWR
GS
GR
CWS
CWR
PC
FOS
FOR
FOV
PG
RL
RS
RD
CS
CR
CD
#/HR
HPWS
HPWR
PIPE IN SLEEVE
VALVE IN VERTICAL PIPE
F AND T TRAP CAP LBS/HR
BUCKET TRAP CAP LBS/HR
AIR QUALITY SENSOR
C02 SENSOR
HUMIDISTAT
REMOTE SENSOR
THERMOSTAT
THERMOSTAT WITH REMOTE SENSOR
AQUASTAT
SOLENOID VALVE (REFRIGERANT)
THERMOSTATIC EXPANSION VALVE (REFRIGERANT)
SIGHT GLASS
MANUAL AIR VENT
PRESSURE OR TEMPERATURE MEASURING POINTS
FLOW SWITCH
HEATING RISER
ACCESS DOOR - SIZE AS SHOWN OR PER SPEC.
EXPANSION LOOP, LENGTH AND DEPTH
NEW TO EXISTING CONNECTION
#/HR
AQ
RECTANGULAR DUCTWORK
(FIRST NUMBER IS SIDE SHOWN)X/X
ROUND DUCT
FLAT OVAL (FIRST NUMBER IS THE SIDE SHOWN)
MOTORIZED DAMPER
FIRE DAMPER WITH ACCESS DOOR
COMBINATION FIRE AND SMOKE DAMPER
WITH ACCESS DOOR
SMOKE DAMPER WITH ACCESS DOOR
SOUND ATTENUATOR
FLEX CONNECTION
SUPPLY REGISTER OR GRILLE
RETURN REGISTER OR GRILLE
SA
TYP DIFFUSER NECK SIZE, MARK
CFM
X X X
X X X
SUPPLY, OUTDOOR, OR MIXED AIR DUCT
END OR RISER (SA) (OA) (MA)
RETURN EXHAUST OR RELIEF AIR DUCT
END OR RISER (RA) (EA) (RLFA)
TYP EXHAUST/RETURN GRILLE NECK SIZE, MARK
CFM
TURNING VANES
MECHANICAL/ELECTRICAL COORDINATION SCHEDULE
MECHANICAL EQUIPMENT WITH ELEC CONNECTION SEE
AUTOMATIC CONTROL VALVE, 2-WAY
AUTOMATIC CONTROL VALVE, 3-WAY
PRESSURE REGULATING VALVE (PRV)
X X
POINT OF DISCONNECT BREAK / CONTINUATION
T
OR
DESCRIPTIONSYMBOLSYMBOL DESCRIPTION SYMBOL DESCRIPTION
PIPING
R
PTT
TEE
ELBOW
UNION
STRAINER WITH DRAIN VALVE AND HOSE END
BALANCING VALVE
ISOLATION VALVE (BALL OR BUTTERFLY)
PRESSURE RELIEF VALVE
ELBOW UP
ELBOW DOWN
GLOBE VALVE
PRESS / TEMP TEST PORT
GATE VALVE
CHECK VALVE (ARROW INDICATES FLOW)
FLEXIBLE PIPING
AUTOMATIC AIR VENT
MANUAL AIR VENT WITH ISOLATION VALVE
CONCENTRIC REDUCER
ECCENTRIC REDUCER
PRESSURE GAUGE WITH GAUGE COCK
THERMOMETER, SIDE FEED
THERMOMETER, BOTTOM FEED
ARROW INDICATES FLOW DIRECTION
ARROW INDICATES DOWNWARD PIPE PITCH
WATER METERM
S
S
SS
AW
AW
S
S
OF
OF
SS
AW
AW
AV
V
140°
140°
SS
W
S
S
S
A
V
GCO
HB
WH
Y.H.
BFP
_ FD-X
_ FS-X
_ RD-X
DS
MH
VTR
SH
EXISTING SANITARY DRAIN (ABOVE FLOOR)
VENT
DESCRIPTIONSYMBOLSYMBOL DESCRIPTION SYMBOL DESCRIPTION
PLUMBING
EXISTING SANITARY SEWER (BELOW FLOOR)
HOT WATER CIRCULATING 140°
GRADE CLEAN OUT
EXISTING STORM DRAIN (ABOVE FLOOR)
OVERFLOW STORM DRAIN (ABOVE FLOOR)
DOUBLE GRADE CLEAN-OUT
EXISTING STORM DRAIN (BELOW FLOOR)
OVERFLOW STORM DRAIN (BELOW FLOOR)
HOSE BIBB
EXISTING SUB SOIL DRAIN
SANITARY DRAIN (ABOVE FLOOR)
WALL HYDRANT (NON-FREEZE TYPE)
EXISTING ACID WASTE (ABOVE FLOOR)
SANITARY SEWER (BELOW FLOOR)
YARD HYDRANT
EXISTING ACID WASTE (BELOW FLOOR)
BACK FLOW PREVENTER
SITE STORM SEWER
FLOOR DRAIN SIZE-TYPE
SITE WATER PIPING
FLOOR SINK SIZE-TYPE
STORM DRAIN (BELOW FLOOR)
ROOF DRAIN SIZE-TYPE
SUB SOIL DRAIN
DOWN SPOUT
MANHOLE
ACID WASTE (ABOVE FLOOR)
VACUUM BREAKER
ACID WASTE (BELOW FLOOR)
GAS COCK
ACID VENT
RUNNING TRAP
VENT THROUGH ROOF ON RISER
PLUMBING RISER NUMBER
SHOWER
COLD WATER (CW)
COLD SOFT WATER
COMPRESSED AIR
HOT WATER (HW)
HOT WATER CIRCULATING (HWC)
HOT SOFT WATER
HOT SOFT WATER RECIRCULATING
STORM DRAIN (ABOVE FLOOR)
HOT WATER 140°
CLEAN OUT
NATURAL GASG
ORCO CO
BLDG BUILDING
BTUH BRITISH THERMAL UNIT PER HOUR
CFM CUBIC FEET PER MINUTE
CL CENTER LINE
CLG CEILING
CLR CLEAR
CRAC
CV CONSTANT VOLUME
DIAMETER
DISC DISCONNECT
DIST DISTRIBUTION
DN DOWN
DWG DRAWING
EA EXHAUST AIR
EL ELEVATION
EHC ELECTRIC HEATING COIL
EQUIP EQUIPMENT
EXH EXHAUST
EXIST EXISTING
FA FIRE ALARM
FL FLOOR
FT FEET
PWR POWER
PVC POLYVINYL CHLORIDE
PSI POUNDS PER SQUARE INCH
PSF POUNDS PER SQUARE FOOT
PNL PANEL
PLBG PLUMBING
PIV POST INDICATOR VALVE
RM ROOM
RH RELATIVE HUMIDITY
REQD REQUIRED
RLFA RELIEF AIR
RA RETURN AIR
UNO UNLESS NOTED OTHERWISE
UPS UNINTERRUPTIBLE POWER SUPPLY
UL UNDERWRITERS LABORATORY
UG UNDERGROUND
TYP TYPICAL
TEMP TEMPERATURE
STD STANDARD
SS STAINLESS STEEL
SPECS SPECIFICATIONS
SIM SIMILAR
SCHD SCHEDULE
SAN SANITARY
SA SUPPLY AIR
NC NORMALLY CLOSED
MTD MOUNTED
MISC MISCELLANEOUS
MIN MINIMUM
MECH MECHANICAL
MAX MAXIMUM
LBS POUNDS
KW KILOWATT
OC ON CENTER
OA OUTDOOR AIR
NTS NOT TO SCALE
NOM NOMINAL
NO NORMALLY OPEN
NIC NOT IN CONTRACT
GA GAUGE
HVAC HEATING, VENTILATING
HTG HEATING
HP HORSEPOWER
HGT HEIGHT
GPM GALLONS PER MINUTE
GEN GENERATOR
GALV GALVANIZED
AND AIR CONDITIONING
ELEC ELECTRICAL
DIA
CPVC
DX DIRECT EXPANSION
EPO EMERGENCY POWER OFF
F FIRE WATER
FCO FLOOR CLEAN OUT
FDC FIRE DEPARTMENT CONNECTION
FHC FIRE HOSE CABINET
FW FILTERED WATER
GC GENERAL CONTRACTOR
MBH 1000 BTU/HOUR
NPW NON-POTABLE WATER
PS PLASTER SINK
RO REVERSE OSMOSIS WATER
SCW SOFT COLD WATER
SM SPRINKLER MAIN
SMACNA SHEET METAL AND AIR
CONDITIONING CONTRACTORS'
BTU BRITISH THERMAL UNIT
PERP PERPENDICULAR
RGS RIGID GALVANIZED STEEL
HZ HERTZ, HIGH ZONE WET STANDPIPE
CFH CUBIC FEET PER HOUR
SHW SOFT HOT WATER
MERV MINIMUM EFFICIENCY REPORTING
VALUE
MOA MINIMUM OUTDOOR AIR
EOA ECONOMIZER OUTDOOR AIR
IE INVERT ELEVATION
NATIONAL ASSOCIATION
AHJ
ASHRAE
AUX
AV
AW
AWG
BFP
AUTHORITY HAVING JURISDICTION
AMERICAN SOCIETY OF HEATING,
REFRIGERATING AND
AIR-CONDITIONING ENGINEERS
AUXILIARY
ACID VENT
ACID WASTE
AMERICAN WIRE GAUGE
DOUBLE CHECK BACKFLOW
VOLT-AMPS
VERTICAL
VARIABLE FREQUENCY CONTROL
VENT THROUGH ROOF
WATT
WEATHERPROOF
TRANSFORMER
VA
VERT
VFC
VTR
W
WP
XFMR
AFF ABOVE FINISHED FLOOR
AMERICAN SOCIETY OF
MECHANICAL ENGINEERS
STANDARD SPECIFICATIONS OF
THE AMERICAN SOCIETY FOR
ASME
ASTM
TESTING MATERIALS
AVG AVERAGE
BMCS BUILDING MANAGEMENT
EMS ENERGY MANAGEMENT SYSTEM
IP INTERNET PROTOCOL
NATIONAL FIRE PROTECTION
ASSOCIATION
NFPA
WATER GAUGEWG
CHLORINATED POLYVINYL CHLORIDE
COMPUTER ROOM AIR CONDITIONER
MA MIXED AIR
CONTROL SYSTEM
ABBREVIATIONS
OFCI OWNER FURNISHED
CONTRACTOR INSTALLED
PREVENTER RPZ REDUCED PRESSURE ZONE
BACKFLOW PREVENTER
LZ LOW ZONE WET STANDPIPE
GW GARAGE WASTE
FHV FIRE HOSE VALVE
DDCV DOUBLE DETECTOR CHECK VALVE
ASSEMBLY BACKFLOW PREVENTER
DPAC DRY PIPE AIR COMPRESSOR
DPV DRY PIPE VALVE
PROPANE GAS
Fe br ua ry
, 2
2:0 1p m
_M
0.d wg m gr eg or y
NOTE:
DO NOT SCALE DRAWINGS. VERIFY ALL DIMENSIONS
and clearances from ARCHITECTURAL, STRUCTURAL, shop and other appropriate drawing or at site. lay out and coordinate all work prior to installation to provide clearances required for operation, maintenance, and codes and verify non-interference with other work. DO NOT FABRICATE
PRIOR TO VERIFICATION OF CLEARANCE FOR ALL
TRADES. READ SPECIFICATIONS.
COPYRIGHT 2024
Permission to reproduce all or part of this drawing is hereby granted solely for the limited purpose of construction of this project or archiving. Unauthorized copying, disclosure or construction use without written permission of Alvine Engineering is prohibited by copyright law.
AE# 20239894
DATE:
TECH. REVIEW:
SUB SHEET NO. TITLE OF SHEET
PMIS NO.
DRAWING NO.
SHEET
OF
DRAWN BY:
DESIGNED:
15 FEB 2024
80071
RENOVATE MAIN RESTROOMS FROM THE LINCOLN
AND WASHINGTON PARKING STRUCTURES
MOUNT RUSHMORE NATIONAL MEMORIAL
KEYSTONE, SOUTH DAKOTA
305644
FINAL CONSTRUCTION DOCUMENTS
MRG
MRG
BAH
MECHANICAL SYMBOLS AND
ABBREVIATIONSM0
AutoCAD SHX Text M-Lg Mechanical
AutoCAD SHX Text 2020-07-23
3 222
EXISTING COMBINATION
FIRE/DOMESTIC WATER
ENTRANCE
EXISTING
4" VTR
PG
EXISTING PROPANE GAS METER
(TYP-5) (TYP-5)
(TYP-6)
(TYP-5)
(TYP-6)(TYP-6)
Fe br ua ry
, 2
3:1 9p m M
1.d wg m gr eg or y
NOTE:
DO NOT SCALE DRAWINGS. VERIFY ALL DIMENSIONS
and clearances from ARCHITECTURAL, STRUCTURAL, shop and other appropriate drawing or at site. lay out and coordinate all work prior to installation to provide clearances required for operation, maintenance, and codes and verify non-interference with other work. DO NOT FABRICATE
PRIOR TO VERIFICATION OF CLEARANCE FOR ALL
TRADES. READ SPECIFICATIONS.
COPYRIGHT 2024
Permission to reproduce all or part of this drawing is hereby granted solely for the limited purpose of construction of this project or archiving. Unauthorized copying, disclosure or construction use without written permission of Alvine Engineering is prohibited by copyright law.
AE# 20239894
DATE:
TECH. REVIEW:
SUB SHEET NO. TITLE OF SHEET
PMIS NO.
DRAWING NO.
SHEET
OF
DRAWN BY:
DESIGNED:
15 FEB 2024
80071
RENOVATE MAIN RESTROOMS FROM THE LINCOLN
AND WASHINGTON PARKING STRUCTURES
MOUNT RUSHMORE NATIONAL MEMORIAL
KEYSTONE, SOUTH DAKOTA
305644
FINAL CONSTRUCTION DOCUMENTS
FLAG NOTES
REMOVE EXISTING GAS-FIRED WATER HEATER SHOWN BOLD. EXISTING 3"
COMBUSTION AIR AND FLUE EXHAUST VENT SHALL REMAIN AND BE REUSED UNDER
NEW WORK.
REMOVE EXISTING FLUSH VALVE WATER CLOSET SHOWN BOLD COMPLETE.
SANITARY PIPING UTILITIES SHALL REMAIN AND BE REUSED UNDER NEW WORK.
CLEAN EXISTING TO REMAIN.
REMOVE EXISTING FLUSH-VALVE URINAL SHOWN BOLD COMPLETE. PIPING
UTILITIES IN WALL SHALL REMAIN AND BE REUSED UNDER NEW WORK. CLEAN
EXISTING TO REMAIN.
REMOVE EXISTING WALL MOUNTED LAVATORY AND ASSOCIATED FAUCETS SHOWN
BOLD COMPLETE. REMOVE EXISTING ACCESS PANELS, THERMOSTATIC MIXING
VALVE ASSEMBLIES, TEMPERED AND COLD WATER PIPING SERVING LAVATORIES
COMPLETE. REMOVE WATER PIPING IN WALL TO BELOW FLOOR. REMOVE EXISTING
SANITARY WASTE PIPING BACK TO SANITARY MAIN WHERE PIPING EXITS
CRAWLSPACE ABOVE FLOOR. EXISTING SANITARY WASTE PIPING BACK DOWN INTO
CRAWLSPACE SHALL BE REUSED FOR NEW NEW WORK.
REMOVE EXISTING WALL MOUNTED WATER COOLER / BOTTLE FILLER AND SAVE
FOR RE-INSTALLATION.
REMOVE EXISTING COLD AND HOT WATER PIPING SHOWN DARK ROUTING WITHIN
CRAWLSPACE BELOW FLOOR.
REMOVE EXISTING COLD WATER SHOWN BOLD IN CHASE SERVING WATER
CLOSETS.
EXISTING COLD WATER SERVING EXISTING WALL HYDRANT TO REMAIN AND BE
REUSED.
REMOVE EXISTING HOT WATER PIPING IN WALL FROM BELOW FLOOR SERVING MOP
SINK. REMOVE TO ELEVATION IN WALL BELOW EXISTING MOP SINK FAUCET.
REMAINING HOT WATER AND HOT WATER CIRCULATING PIPING IN WALL SHALL
REMAIN AND BE REUSED UNDER NEW WORK.
REMOVE EXISTING HOT WATER CIRCULATING PIPING BELOW FLOOR IN
CRAWLSPACE SHOWN DASHED AND BOLD. VERIFY EXISTING CONDITIONS IN FIELD.
REMOVE EXISTING HOT WATER CIRCULATING PIPING SHOWN BOLD FROM WHERE
PIPING COMES UP FROM BELOW FLOOR AND ROUTES OVERHEAD TO ABOVE THE
EXISTING CIRCULATING PUMP.
REMOVE EXISTING HOT WATER CIRCULATING PUMP. EXISTING PUMP SHALL BE
REPLACED WITH A NEW PUMP UNDER NEW WORK (SEE SHEET M4).
REMOVE PORTION OF EXISTING 1" PROPANE GAS PIPING SHOWN BOLD FROM
EXISTING PROPANE METER LOCATED OUTSIDE TO A POINT INSIDE MECHANICAL
ROOM WHERE PIPING OFFSETS UP IN MECHANCIALROOM. COORDINATE HOW MUCH
PIPING NEEDS TO BE REMOVED ON VERTICAL PORTION OF PIPING INSIDE OF
MECHANICAL ROOM WHERE CONNECTION OF NEW PIPING WILL BE MADE. SEE
SHEET M-4 AND DETAIL #6 ON SHEET M-8 FOR ADDITIONAL INFORMATION.
MRG
MRG
BAH
FLOOR PLAN - PLUMBING
DEMOLITIONM1
SCALE…