Atch 2 Salient Characteristics -Pad Mount Transformers.pdf

PDF 134 KB Posted

Attached to
CES Voltage Pad Mount Transformers
Solicitation number
FA4610Q0222
Issued by

About this file

This document contains the Salient Characteristics for the requested pad mount and pole mount transformers under the federal contract opportunity FA4610Q0222 issued by the Department of the Air Force Space Command.

The key details are:

  • All transformers are required to have copper windings, stainless steel tanks/construction, FR3 insulation, and be made in the USA.
  • Pad mount transformers must have dead front loop feed, tap changers, and bayonet fusing.
  • Specific technical requirements are provided for temperature rise, cooling class, insulating fluid, elevation, sound level, efficiency, harmonic factor, voltage class, taps, bushings, overcurrent protection, and other design elements.
  • The federal contract opportunity is for the purchase of five medium voltage pad-mounted transformers of varying kVA ratings (122.5 kVA, 150 kVA, 300 kVA, 500 kVA, 750 kVA) to replace aging equipment at Vandenberg Space Force Base, which has a corrosive environment requiring the unique stainless steel construction.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Salient Characteristics

SALIENT CHARACTERISTICS 0F REQUESTED TRANSFORMERS – Applies to all transformers.

ALL POLE MOUNT UNITS TO HAVE COPPER WINDINGS

STAINLESS STEEL TANKS

FR3 INSUALTION MADE IN THE USA

TAP CHANGER

ALL PADMOUNT UNIT TO HAVE COPPER WINDINGS

STAINLESS STEEL CONSTRUCTION

FR3 INSULATION MADE IN THE USA

DEAD FRONT LOOP FEED

TAP CHANGER, W/TAPS

BAYONET FUSING

LABOR SWITCHES

STANDARD GAUGES AND EQUIPMENT

PADMOUNT TRANSFORMERS

• Temperature Rise: 65-degree average winding rise

• Cooling Class: KNAN

• Frequency: 60 Hz

• Insulating Fluid: Envirotemp FR3

• Elevation: 3300 ft above sea level

• Sound Level: NEMA TR1 Standard

• Efficiency Standard: DOE 2016

• Harmonic "K" Factor: None

• kV Class: 15 kV

• High Voltage Configuration: Dead Front, Lopp Feed

• Taps: 2 - 2.5% taps above and 2 - 2.5% taps below normal

• Tap Changer: 100 Amp 5-position tap changer

• High Voltage Bushings: 200-amp Cooper bushing wells with removable studs

• Inserts: 15 kV, 95 kV BIL Copper load-break inserts

• Load-break Switching: 15-38 kV, 300A 2-Position

• Arresters: None

• Overcurrent Protection: Bayonet Fuses in series with Partial Range Current-Limit Fuses

• Expulsion fuses: Bayonet Fuses

• Bayonet Holder: Copper Bayonet Fuse Holder

• Spare Expulsion Fuses: Bayonet Fuses

• Low Voltage kV Class: 1.2 kV

• Low Voltage Bushings: 1" copper stud with 4-hole screw on spade bushings

• Cabinet: 20-inch-deep cabinet

• IEEE K-Dimension: Loop feed per IEEE C57.12.34-2015 Figure 11

• Coatings: Munsell Green topcoat

• Construction: 100% Stainless Steel

• Stainless Steel Type: 304L Stainless Steel

• Configuration: Standard Design

• Mounting Provisions: Hangar Brackets (One Set)

• Temperature Rise: 65

• Cooling Class: KNAN

• Insulating Fluid: Envirotemp FR3

• Frequency: 60 Hz

• Efficiency Standard: DOE 2016

• Taps: 2 - 2.5% taps above and 2 - 2.5% taps below normal

• Tap Changer: 100 amp 5-position tap changer

• Primary Bushings: 15kV Cover Mount

• Arrestors: None

• Overcurrent Protection: None

• Secondary Bushings: 5/8 Eyebolt with 3/8-16 stud Secondary Bushing

• Coatings: ANSI 70 Gray (Munsell 5BG7.0/0.4) topcoat

File details come from the government source that posted it. Updated .