Atch 2 Salient Characteristics -Pad Mount Transformers.pdf
PDF 134 KB Posted
- Attached to
- CES Voltage Pad Mount Transformers
- Solicitation number
- FA4610Q0222
About this file
This document contains the Salient Characteristics for the requested pad mount and pole mount transformers under the federal contract opportunity FA4610Q0222 issued by the Department of the Air Force Space Command.
The key details are:
- All transformers are required to have copper windings, stainless steel tanks/construction, FR3 insulation, and be made in the USA.
- Pad mount transformers must have dead front loop feed, tap changers, and bayonet fusing.
- Specific technical requirements are provided for temperature rise, cooling class, insulating fluid, elevation, sound level, efficiency, harmonic factor, voltage class, taps, bushings, overcurrent protection, and other design elements.
- The federal contract opportunity is for the purchase of five medium voltage pad-mounted transformers of varying kVA ratings (122.5 kVA, 150 kVA, 300 kVA, 500 kVA, 750 kVA) to replace aging equipment at Vandenberg Space Force Base, which has a corrosive environment requiring the unique stainless steel construction.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Atch 1 SOW Pad Mount Transformers.pdf | ||
| Atch 2 RFQ Voltage Pad Mount Transformers.xlsx | XLSX spreadsheet | |
| Atch 3 RFQ Combo Voltage Pad Mount Transformers.pdf | ||
| Atch 1 SOW Transformers.pdf | ||
| RFQ Combo Voltage Pad Mount Transformers.pdf | ||
| Atch 3 RFQ Voltage Pad Mount Transformers.xlsx | XLSX spreadsheet |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Salient Characteristics
SALIENT CHARACTERISTICS 0F REQUESTED TRANSFORMERS – Applies to all transformers.
ALL POLE MOUNT UNITS TO HAVE COPPER WINDINGS
STAINLESS STEEL TANKS
FR3 INSUALTION MADE IN THE USA
TAP CHANGER
ALL PADMOUNT UNIT TO HAVE COPPER WINDINGS
STAINLESS STEEL CONSTRUCTION
FR3 INSULATION MADE IN THE USA
DEAD FRONT LOOP FEED
TAP CHANGER, W/TAPS
BAYONET FUSING
LABOR SWITCHES
STANDARD GAUGES AND EQUIPMENT
PADMOUNT TRANSFORMERS
• Temperature Rise: 65-degree average winding rise
• Cooling Class: KNAN
• Frequency: 60 Hz
• Insulating Fluid: Envirotemp FR3
• Elevation: 3300 ft above sea level
• Sound Level: NEMA TR1 Standard
• Efficiency Standard: DOE 2016
• Harmonic "K" Factor: None
• kV Class: 15 kV
• High Voltage Configuration: Dead Front, Lopp Feed
• Taps: 2 - 2.5% taps above and 2 - 2.5% taps below normal
• Tap Changer: 100 Amp 5-position tap changer
• High Voltage Bushings: 200-amp Cooper bushing wells with removable studs
• Inserts: 15 kV, 95 kV BIL Copper load-break inserts
• Load-break Switching: 15-38 kV, 300A 2-Position
• Arresters: None
• Overcurrent Protection: Bayonet Fuses in series with Partial Range Current-Limit Fuses
• Expulsion fuses: Bayonet Fuses
• Bayonet Holder: Copper Bayonet Fuse Holder
• Spare Expulsion Fuses: Bayonet Fuses
• Low Voltage kV Class: 1.2 kV
• Low Voltage Bushings: 1" copper stud with 4-hole screw on spade bushings
• Cabinet: 20-inch-deep cabinet
• IEEE K-Dimension: Loop feed per IEEE C57.12.34-2015 Figure 11
• Coatings: Munsell Green topcoat
• Construction: 100% Stainless Steel
• Stainless Steel Type: 304L Stainless Steel
• Configuration: Standard Design
• Mounting Provisions: Hangar Brackets (One Set)
• Temperature Rise: 65
• Cooling Class: KNAN
• Insulating Fluid: Envirotemp FR3
• Frequency: 60 Hz
• Efficiency Standard: DOE 2016
• Taps: 2 - 2.5% taps above and 2 - 2.5% taps below normal
• Tap Changer: 100 amp 5-position tap changer
• Primary Bushings: 15kV Cover Mount
• Arrestors: None
• Overcurrent Protection: None
• Secondary Bushings: 5/8 Eyebolt with 3/8-16 stud Secondary Bushing
• Coatings: ANSI 70 Gray (Munsell 5BG7.0/0.4) topcoat