This document outlines requirements for boilers and flue systems for two federal contract opportunities at Whiteman Air Force Base. The first opportunity requires one 500,000 btu/hr condensing boiler with a modulating 10:1 turndown ratio and associated ASME-certified heat exchanger, relief valve, and controls. Accessories and a 4" polypropylene venting system are also specified. The second larger opportunity requires two 725,000 btu/hr condensing boilers each with a modulating 7:1 turndown, ASME components, controls, and accessories. Two 6" polypropylene venting systems are specified along with additional venting components. The related solicitation is numbered FA462523Q1102 for boilers at Whiteman AFB from the Department of the Air Force Global Strike Command.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| ATCH 1 FA462523Q1102 Provisions and Clauses B1120 B3019 11Aug2023.pdf | ||
| FA462523Q1102 Boiler Combo 16Aug23.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Salient Characteristics
B1120 Requirements Item #1 Quantity of one (1) Boiler; complete as follows:
Fire Tube Condensing Boiler
- 500,000 btu/hr input, 489,000 btu/hr output
- Natural gas fired
- CSD-1 compliant
- Modulating 10:1 turndown
- ASME-certified "H" stamped stainless steel heat exchanger
- ASME pressure relief valve
- Adjustable automatic reset high limit
- Contacts on any failure
- Digital operating control featuring a built-in cascading sequencer
- Lead-lag or efficiency optimized cascade operation
- Multiple size boilers (up to 8 boilers)
- Front-end loading
- USB thumb drive port for easy programming
- Data Logging
- Programmable system efficiency optimizers
- Inlet & outlet temperature sensors
- Outdoor reset w/ wired sensor (shipped loose)
- Pump relay w/ freeze protection
- System sensor (shipped loose)
- Low water cutoff
- Adjustable high limit w/ manual reset
- Low NOx compliant ACCESSORIES (shipped loose for field installation)
- Condensate neutralization kit (1/boiler)
- Step down gas regulator 2 psi max inlet (1/boiler)
Item #2 Quantity of one (1) Flue Systems; complete as follows:
- Integrated Gasket Polypropylene Piping System
- Environmentally-friendly polypropylene (100% recyclable)
- Venting systems (sustained temperatures up to 230F)
- Zero clearance to combustibles
- 10 year limited warranty
- 4" diameter pipe
- Complete system to include:
- Boiler connection
- 11 linear feet of straight pipe
- Termination tee with bird screens
- (2) 45 degree elbows
- Bird screen and termination
Item #3 Quantity of one (1) Pump; complete as follows:
Tag:
Variable speed inline circulator pump
- 50 gpm @ 25' tdh
- 115/1/60
- Integrated variable speed drive
- 4-pole synchronous permanent-magnet motor (PM motor)
- Canned-rotor type pump
- Carbon-fiber reinforced composite rotor can
- Stainless steel bearing plate and rotor cladding
- Aluminum alloy stator housing
- Air-cooled power electronics
- Controller integrated in the control box
- Control panel with TFT display on control box
- Built-in differential pressure and temperature sensor
- (1) Flange Kit per pump
B3019 Requirements
Item #1 Quantity of two (2) Boiler(s); complete as follows:
Fire Tube Condensing Boiler
- 725,000 btu/hr input, 705,000 btu/hr output
- Natural gas fired
- CSD-1 compliant
- Modulating 7:1 turndown
- ASME-certified "H" stamped stainless steel heat exchanger
- ASME pressure relief valve
- Adjustable automatic reset high limit
- Contacts on any failure
- Digital operating control featuring a built-in cascading sequencer
- Lead-lag or efficiency optimized cascade operation
- Multiple size boilers (up to 8 boilers)
- Front-end loading
- USB thumb drive port for easy programming
- Data Logging
- Programmable system efficiency optimizers
- Inlet & outlet temperature sensors
- Outdoor reset w/ wired sensor (shipped loose)
- Pump relay w/ freeze protection
- System sensor (shipped loose)
- Low water cutoff
- Adjustable high limit w/ manual reset
- Low NOx compliant ACCESSORIES (shipped loose for field installation)
- Condensate neutralization kit (1/boiler)
- Step down gas regulator 2 psi max inlet (1/boiler)
- Cast iron circulator boiler pump
Item #2 Quantity of one (1) Flue Systems; complete as follows:
- Integrated Gasket Polypropylene Piping System
- Environmentally-friendly polypropylene (100% recyclable)
- Venting systems (sustained temperatures up to 230F)
- Zero clearance to combustibles
- 10 year limited warranty
- 6" diameter pipe
- Complete system to include:
- Boiler connection
- Approx 30 linear feet of straight pipe per boiler
- Termination tee with bird screens
- (2) 45 degree elbows per boiler