This document is a detailed specification for a Technology Storage Building construction project. The facility is a 30' x 92' x 16' metal building with a 3/12 degree roof pitch designed to fit on an existing concrete foundation. The structure requires 32-gauge metal for the roof and inner/outer sidewalls in an R-Panel style, with 12' sheet iron liner panels around the interior perimeter. Insulation specifications include minimum 3-inch closed cell spray foam on interior walls and minimum 4-inch thickness on the roof, with light grey paint applied above the 12' liner panels.

The building includes multiple access points: a 14' x 14' insulated steel panel garage door on the south end, a 10' x 10' canister roll-up door on the east side, a single steel exterior door on the southwest corner, and a double door in the breezeway. An enclosed breezeway measuring 9' x 5' 4" connects the building to an existing structure. The mechanical and electrical systems include a central HVAC system (estimated at $30,000) with heat pumps, air handlers, heat strip kits, thermostats, plenums, and duct fittings, along with electrical infrastructure providing 110v access throughout the building, one 220v plug in the southeast corner, and lighting consisting of dimmable highbay UFO LED lights (minimum 150W) arranged in a minimum of two rows down the building length with maximum 15-foot spacing between fixtures.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Technology Storage Building Details 30’ x 92’ x 16’

3/12 ° Roof Pitch

30’ x 92’ x 16’ Metal Building package (fit on existing concrete foundation) o 32 ft wide x 92 ft long x 16 ft high sidewalls

Painted Roof, Walls/Trim, Gutters, & Downs (match existing buildings) Minimum 26-gauge metal for Roof & Inner/Outer Sidewalls

Style: “R-Panel” o 12’ Sheet Iron Liner Panels around interior perimeter (color match building)

Closed Cell Spray Foam Insulation o Interior Walls - Minimum 3-inch thickness o Roof – Minimum 4- inch thickness o Painted above 12’ liner panels (light grey)

One 14’ x 14’ Insulated Steel Panel garage door on the South End o Cut out existing concrete and patch to create slope notch for door.

One 10’ x 10’ Cannister (Roll Up) Door on the East side o Cut out existing concrete and patch to create slope notch for door.

One single steel exterior door on the Southwest corner One double door in the breezeway Enclosed Breezeway that connects the building to an existing building o Existing foundation is 9’ x 5’ 4” (includes sheet notch) Central HVAC system (est. $30,000.00):

o Large duct system with air directing duct fittings.

o Including Heat pumps, air handlers, heat strip kits, thermostats, plenums and duct fittings, labor, installation, and materials Electrical – (similar layout to diagram) o Adequate 110v access throughout entire building o One 220v plug in Southeast Corner o Lighting:

Highbay UFO LED lights (Dimmable; Minimum 150 W) Minimum of 2 rows down length of building Maximum spacing of 15 ft apart between lights