Text version

140P5423Q0024 Attachment 1

Page 1 of 5 Pages

National Park Service Cumberland Island National Seashore

Statement of Work (SOW) Automatic Fire Alarm/Security Systems Replacement and Upgrades

Cumberland Island Museum, Visitor’s Center, and Headquarters

I Project Description

The National Park Service (NPS) is seeking an Automatic Fire Alarm System Contractor as well as a Security System Contractor to install comparable/compatible/equal to the Silent Knight Addressable Fire Alarm Control Panels (FACP) and accompanying notification and initiation devices in 3 buildings with existing older FACP’s and equipment, as well as install Vista commercial partitioned burglary systems and accompanying equipment in the same 3 buildings which also have existing older burglary systems.

The goal is to upgrade the existing video surveillance system in the visitor’s center and both the existing security systems and the existing fire alarm notification systems to serviceable condition, considering the historic significance of the sites with minimally invasive work.

Page 2 of 5 Pages

II Scope of Work

• Headquarters-Bachlott House (101 Wheeler Street, St. Marys, GA 31558)

• Fire System

• Install, Program and Checkout a direct upgrade from existing Fire system with:

• 1-100 Point Addressable Fire Alarm

• 1-LCD Remote Annunciator

• 5-Analog Addressable Pull Station

• 2-12v, 8AH Battery

• 2-Addressable Module

• 11-Addressable Photo Smoke Det

• 5-Horn/strobe, 12/24 volt, multi-candela 15, 30, 75, 95, 110, 135, 185,red

• 4-Strobe, 12/24 volt, multi-candela 15, 30, 75, 95, 110, 135, 185, red wall

• Security/Burglary System

• Install, Program and Checkout for direct upgrade from existing security system with:

• 1-Commercial Partitioned Burglary, Supports Touch Screen Keypads

• 1-Security Keypad

• 1-Commercial Security Wireless Receiver

• 12-Wireless Door and Window Contact

• 5-Wireless Dual TEC Motion Sensor

• Visitors Center (113 st Mary’s Street, St. Marys, GA 31558)

• Fire System

• Install, Program and Checkout a direct upgrade from existing Fire system with:

• 1-200 Point Addressable FACP

• 1-LCD Remote Annunciator

• 4-Analog Addressable Pull Station

• 2-12v, 8AH Battery

• 4-Dual Monitor Module

• 12-Addressable Photo Smoke Det

• 8-Horn/strobe, 12/24 volt, multi-candela 15, 30, 75, 95, 110, 135, 185, red

• 2-Strobe, 12/24 volt, multi-candela 15, 30, 75, 95, 110, 135, 185, red wall

• In addition, or in conjunction with the above fire system replacements:

• Install, Program and Checkout a direct upgrade from existing Fire system

Page 3 of 5 Pages with

• 1-50w, voice evax panel.

• 12-Speaker/Strobe, Multicandela

• 12-Back Box Wall Mount Red

• 1-Cable, 18awg, 2 pair, twisted, shielded (1000ft)

• Scope: Provide and install new Voice Evacuation System with prerecorded messages for Fire Alarm and a select switch option for Weather alert message. Includes a microphone for live use. Replace all horn strobes with speaker strobes and add additional wiring as needed.

system with:

• 1-Commercial Partitioned Burglary, Supports Touch Screen Keypads

• 2-Security Keypad

• 1-Commercial Security Wireless Receiver

• 15-Wireless Door and Window Contact

• 5-Wireless Dual TEC Motion Sensor

• CCTV Upgrade

• Install, Program and Checkout for direct upgrade from existing CCTV system with:

• 1-4K 8-CH NVR 4TB

• 1-27" Full HD Pro Grade Monitor

• 8-3MP IP Dome 2.7-13.5mm Lens

• 16-CAT 6 UTP MODULAR CONNECTOR, BLUE

• 1-RACK, WALL MOUNT FIXED FRAME, 8 RMS

• 8-RJ45 Jack

• 8-3-FT CAT6 PATCH CABLE BLUE

• 3-1000' Cat6 CMP Blue

• Museum

• Fire System (129 Osborne St, St. Marys, GA 31558)

• Install, Program and Checkout a direct upgrade from existing Fire system with:

• 1-100 Point Addressable Fire Alarm

• 2-Addressable Photo Smoke Det

• 8-Analog Addressable Pull Station

• 2-Heat Detector, Addressable

• 2-12v, 8AH Battery

• 2-Addressable Module

• 8-Horn/strobe, 12/24 volt, multi-candela 75

• 1-Strobe, 12/24 volt, multi-candela 75

• 2-Addressable Module, Sprinkler Monitoring

Page 4 of 5 Pages

• In addition, or in conjunction with the above fire system replacements:

• Install, Program and Checkout a direct upgrade from existing Fire system with:

• 10-Addressable Photo Smoke Det

• 12-Addressable Photo Smoke Det

• 4-Horn/strobe, 12/24 volt, multi-candela 15, 30, 75, 95, 115, 150, 177, red

• 20-4 in Sq Box

• 2-16-2 FPLP Cable 1k

• 1-14-2 FPLP Cable 1k

• Scope: Add the above equipment to the following locations.

• 1st floor, Exhibit Rm. 116, Exhibit 117, Vestibule 100, Hall 112,Hall

101A, Hall 102 A.

Loading Dock 115, Quarantine 114, MECH 113.

2ND Floor, Add Addressable smoke detectors using exposed electrical conduit Storage 200, Storage 203, Room 201.

2nd Floor Add four additional Horn / Strobes.

system with:

• 1-Commercial Partitioned Burglary, Supports Touch Screen Keypads

• 1-Security Keypad

• 1-Commercial Security Wireless Receiver

• 10-Wireless Door and Window Contact

• 3-Wireless Dual TEC Motion Sensor

• The contractor shall program the FACP’s with all the detection and notification devices. The work shall be supervised by a fire protection engineer or certified

NICET Level II or higher in the area of specialty.

• All work will be performed to the 2019 NFPA 72 National Fire Alarm and

Signaling Code for fire systems and to the 2023 NFPA 731, Stand for the

Installation of Premises Security Systems for the security/CCTV systems.

• Cameras must meet the requirements of the 2019 National Defense

Authorization Act.

• Conduct an acceptance test in the presence of the regional structural fire manager or his designee.

• Provide FACP user manual and staff training upon completion of the work.

Page 5 of 5 Pages

• Provide Security panel and CCTV user manuals and training upon completion of the work.

• Provide cost estimates for equipment and installation that would be needed to carry out the final plan.

Field Verification: The contractor shall field verify all proposed dimensions and materials to be utilized and provide submittals to the Contracting Officer’s Representative for approval prior to purchasing materials.