This document is a Salient Characteristics specification sheet for a 2000 KVA transformer required by 628 CES Electrical Systems shop to replace a leaking unit currently in service.

The transformer must meet the following core specifications: 2000 KVA capacity, liquid filled with non-PCB insulating fluid, pad mounted type, three phase loop feed configuration, and 60 Hz frequency. The primary voltage requirements specify 13,800 GRDY/7970 volts with primary voltage overcurrent protection via bayonet fuse and a standoff well bushing 200-amp load break elbow insert dead front configuration. The secondary voltage output must be 480/277V with live front threaded stud terminal paddles providing three secondary connection points (X1, X2, X3). The transformer shall include a 5-position voltage tap changer (2 above and 2 below system voltage) and a 4-position load break switch capable of loop feed only, loop feed with transformer, A primary with transformer, and B primary with transformer configurations. The enclosure must be tamper resistant, pad lockable, and finished in green color.

View the file

Other files for this federal contract opportunity

Other files attached to ELECTRIC (WS) B3147 2000 KVA TRANSFORMER, newest first.
File Type Posted
Atch 2- Solicitation - FA441826Q0005.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SALIENT CHARACTERISTICS

NIWIC 2000 KVA Transformer

I. GENERAL OVERVIEW.

628 CES Electrical Systems shop requires the purchase of the following transformer to replaced the unit in service, which is leaking oil.

II. SPECIFICATIONS.

At a minimum the equipment and accessories shall possess the following specifications:

- Specifications:

- 2000 KVA Capacity

- Liquid filled (Non-PCB Insulating fluid)

- Pad mounted type

- Three phase, loop feed

- Frequency: 60 Hz

- 5 Position voltage tap changer (2 above, 2 below system voltage)

- 4 Position load break switch (Loop feed only, Loop feed with transformer, A primary with transformer, B primary with transformer)

- Primary Voltage Requirements:

- Primary voltage over current protection with bayonet fuse

- Primary voltage: 13,800 GRDY/7970

- Primary configuration: Standoff well bushing 200-amp load break elbow inserts dead front

- Secondary Voltage Requirements:

- Secondary voltage: 480/277V

- Secondary configuration: live front with threaded stud terminal paddles with three secondary connection points (X1, X2, X3)

- Enclosure Specifications

- Tamper resistant pad lockable

- Green finished enclosure color

III. APPLICATION.

This transformers will replace the existing unit that is leaking insulation oil.