Atch 1- B731 Dry Cooler Salient Characteristics.pdf
PDF 179 KB Posted
- Attached to
- FY26 Fluid Cooler and Heat Pumps
- Solicitation number
- FA441826Q0094
About this file
This is an Equipment Salient Characteristics document for a federal procurement by the Department of the Air Force, Headquarters 628th Air Base Wing (AMC), located at Joint Base Charleston, South Carolina.
The procurement concerns equipment replacement under project designation DKFX 2026 – B731 and requires three primary pieces of equipment for Government installation. The Fluid Cooler specification calls for an adiabatic cooler (basis of design: Nimbus model VRGA022.0-EC-4) operating at 3-phase/60Hz/460V with a BacNet/MSTP unit controller compatible with the Trane Ensemble Base Energy Management Control System. The cooler must feature variable speed fans, air debris inlet screens, a NEMA 4X control panel, and achieve a minimum capacity of 1000 MBH/80 tons at listed conditions (95°F entering fluid temperature, 85°F exiting, with 20% propylene glycol fluid, 95°F dry bulb, and 80°F wet bulb). The maximum dimensions are 9 feet wide by 14 feet long by 10 feet high, with a minimum water flow rate of 200 GPM. The 6-ton Water Source Heat Pump (basis of design: Trane Axiom model GEVK0724) requires 460 volt/3-phase/60Hz power, copper heating and cooling refrigerant circuit with hot gas reheat, 2-speed fan assembly, top supply/back return air configuration, and Symbio 500 integrated controls. The 1.5-ton Water Source Heat Pump (basis of design: Trane Axiom model GECK0181) requires 208 volt/1-phase/60Hz power, cupro-nickel heating and cooling refrigerant circuit with hot gas reheat, wall-mount right-hand piping configuration, and Symbio 400B integrated controls.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Atch 2- BRAND NAME Justification- Fluid Cooler and Heat Pumps-Signed.pdf | ||
| Solicitation - FA441826Q0094.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CUI
DEPARTMENT OF THE AIR FORCE
HEADQUARTERS 628TH AIR BASE WING (AMC)
JOINT BASE CHARLESTON SC
CUI
Equipment Salient Characteristics DKFX 2026 – B731 Fluid Cooler / WSHP Replacement
Joint Base Charleston Air Base
Salient characteristics: The equipment purchase consists of providing equipment for Government installation.
Fluid Cooler Requirements: (Basis of design: Nimbus model VRGA022.0-EC-4)
• Cooler Type: Adiabatic Cooler
• Voltage: 3ph/60hz/460V
• BacNet/MSTP Unit Controller o Compatible with Trane Ensemble (Base Energy Management Control System)
• Variable Speed fans
• Air Debris inlet screens for coil protection
• Nema 4X Control Panel / Electrical connection Env Rating
• Listed Conditions:
o Fluid Temperature entering cooler: 95°F o Fluid Temperature exiting cooler: 85°F o Fluid Type: 20% Propylene Glycol o Dry Bulb Temp: 95.00°F; Wet Bulb Temp: 80.00°F
• Min Capacity at Listed Conditions: 1000 MBH / 80 Tons
• Minimum Water Flow Rate: 200 GPM
• Maximum dimensions: 9 feet wide x 14 feet long x 10 feet high
6-ton Water Source Heat Pump Requirements: (Basis of design: Trane Axiom model GEVK0724)
• 460 volt/60 hertz/3 phase power supply
• Copper Heating and cooling refrigerant circuit with hot gas reheat
• 2 Speed fan assembly
• Top supply / Back return air arrangement
• Symbio 500 Integrated controls
1.5-ton Water Source Heat Pump Requirements: (Basis of design: Trane Axiom model GECK0181)
• 208 volt/60 hertz/1 phase power supply
• Cupro-nickel Heating and cooling refrigerant circuit with hot gas reheat
• Wall mount, Right hand piping configuration
• Symbio 400B Integrated controls