ASD26-SCMHS-BP2B_specs_Vol3.pdf

PDF 13 MB Posted

Attached to
Summit Campus MS HS PAC Bid Pack 2B
Solicitation number
ASD26-SCMHS-BP2B
Issued by
New Castle County, Delaware

About this file

This is a specification document for Bid Package 2B (Conformance Set, Volumes 3) for the Summit Campus Middle and High School construction project in Middletown, Delaware, issued by the Appoquinimink School District. The document provides detailed specifications for fire suppression systems, plumbing, HVAC, electrical, communications, electronic safety and security, exterior improvements, and conveying equipment. The specifications cover divisions 21 through 34 of the construction standards, including wet-pipe sprinkler systems, standpipe systems, an electric fire pump rated at 500 GPM at 60 PSIG, CPVC sprinkler piping for 3-inch and smaller applications, and associated valves, fittings, and equipment. The fire suppression contractor is responsible for obtaining all permits, conducting water flow testing and pressure tests, submitting working drawings and hydraulic calculations for approval by the local Fire Prevention Bureau and State Fire Marshal, and providing system acceptance and commissioning. The document dated May 22, 2026, requires contractors to design systems in compliance with NFPA standards 13 and 14, Delaware State Fire Prevention Regulations, and applicable local codes, with sprinkler occupancy hazard classifications ranging from Light Hazard (classrooms, offices, corridors) to Ordinary Hazard Group 1 (building service areas, storage areas).

The specifications establish performance requirements including a 10 psi cushion pressure margin in water flow calculations, maximum piping velocity of 20 feet per second, and minimum working pressure ratings of 175 psig for components and piping systems. The fire pump system shall be a vertical in-line Aurora model with associated electric motor driver, jockey pump, and Tornatech or Firetrol controller, with all equipment UL-listed and Factory Mutual approved. Acceptable manufacturers are specified for sprinklers, valves, fittings, fire department connections, and alarm devices from vendors including Tyco Fire Suppression, Reliable Automatic Sprinkler, Viking Corporation, and Victaulic Company. Contractors must submit comprehensive shop drawings, product data, hydraulic calculations prepared using Hazen-Williams formula with C-values per NFPA standards, field test reports, maintenance data, record drawings, and system diagrams for approval prior to installation. The contractor assumes responsibility for damage caused by leaks during installation and testing, must provide one year of maintenance service including 24-hour emergency repair availability, furnish spare sprinklers in wall-mounted cabinets, and conduct final system acceptance testing witnessed by the Delaware State Fire Marshal and Owner's representatives before placing systems in service.

View the file

Other files

File Type Posted
ASD26-SCMHS-BP2B_itb.pdf PDF
ASD26-SCMHS-BP2B_specs_Vol1_pt2.pdf PDF
ASD26-SCMHS-BP2B_specs_Vol2.pdf PDF
ASD26-SCMHS-BP2B_specs_Vol1_pt1.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SUMMIT CAMPUS

NEW MIDDLE SCHOOL

AND HIGH SCHOOL

Summit Bridge Road

Middletown, DE 19709

BID PAC 2

CONFORMANCE SET

Volume 3 [Divisions 21-34]

Date: May 22, 2026

1621 N. Lincoln Street / Wilmington, Delaware 19806 / 302.658.6426 p1 / 302.658.6426 p2 / 302.658.8431 f

Summit Campus Middle and

High School

TABLE OF CONTENTS

BP2 – Conformance Set

05/22/2026

TABLE OF CONTENTS

VOLUME 2

00 01 07 SEALS PAGE

DIVISION 02 - EXISTING CONDITIONS

DIVISION 03 - CONCRETE

03 05 06 UNDER-SLAB VAPOR BARRIER

03 30 00 CAST-IN-PLACE CONCRETE

03 30 05 CAST-IN-PLACE CONCRETE FOR LANDSCAPING

03 30 06 CRYSTALLINE WATERPROOFING ADMIXTURE FOR CAST-IN-

PLACE CONCRETE

03 49 00 GLASS-FIBER REINFORCED CONCRETE

DIVISION 04 - MASONRY

04 20 00 UNIT MASONRY

04 72 00 CAST STONE MASONRY

04 72 10 CAST STONE MASONRY FOR LANDSCAPING

04 73 13 CALCIUM SILICATE MANUFACTURED STONE

DIVISION 05 - METALS

05 12 00 STRUCTURAL STEEL

05 21 00 STEEL JOISTS

05 31 00 STEEL DECK

05 40 00 COLD-FORMED METAL FRAMING

05 44 00 COLD-FORMED METAL TRUSSES

05 50 00 METAL FABRICATIONS

05 51 00 METAL STAIRS

05 51 33 METAL LADDERS

05 52 13 PIPE AND TUBE RAILINGS

05 53 05 METAL GRATINGS AND FLOOR PLATES

05 58 00 ARCHITECTURAL METAL COLUMN COVERS

05 58 13 FORMED METAL FABRICATIONS- ROOF FINIAL

05 73 00 DECORATIVE METAL RAILINGS

DIVISION 06 - WOOD, PLASTICS, AND COMPOSITES

06 10 00 ROUGH CARPENTRY

06 20 00 FINISH CARPENTRY

DIVISION 07 - THERMAL AND MOISTURE PROTECTION

07 05 53 FIRE AND SMOKE ASSEMBLY IDENTIFICATION

07 11 13 BITUMINOUS DAMPPROOFING

07 14 00 FLUID-APPLIED WATERPROOFING

07 21 00 THERMAL INSULATION

07 21 29 SPRAYED ACOUSTICAL INSULATION

TABLE OF CONTENTS

BP2 – Conformance Set

05/22/2026

07 21 29.13 SPRAY APPLIED GLASS FIBER INSULATION

07 24 00 EXTERIOR INSULATION AND FINISH SYSTEMS

07 26 40 SPRAY POLYURETHANE FOAM INSULATING AIR BARRIER

07 41 00 METAL ROOF PANELS

07 42 13 METAL WALL PANELS

07 42 13.23 METAL COMPOSITE MATERIAL WALL PANELS

07 46 46 FIBER CEMENT WALL PANELS

07 53 00 ELASTOMERIC MEMBRANE ROOFING

07 62 00 SHEET METAL FLASHING AND TRIM

07 62 62 FLUID APPLIED MEMBRANE AIR BARRIERS

07 71 00 ROOF SPECIALTIES

07 72 00 ROOF ACCESSORIES

07 81 00 APPLIED FIRE PROTECTION

07 84 00 FIRESTOPPING

07 92 00 JOINT SEALANTS

07 95 13 EXPANSION JOINT COVER ASSEMBLIES

DIVISION 08 - OPENINGS

08 06 71 DOOR HARDWARE SCHEDULE

08 11 13 HOLLOW METAL DOORS AND FRAMES

08 14 16 FLUSH WOOD DOORS

08 16 13 FRP FLUSH DOORS

08 31 00 ACCESS DOORS AND PANELS

08 33 13 COILING COUNTER DOORS

08 33 23 OVERHEAD COILING DOORS

08 33 94 HORIZONTAL COILING FABRIC FIRE CURTAINS

08 35 13.23 ACCORDION FOLDING FIRE DOORS

08 41 13 ALUMINUM-FRAMED STOREFRONTS

08 41 23 FIRE RATED ALUMINUM-FRAMED STOREFRONTS

08 41 26 ALL-GLASS ENTRANCES

08 44 13 GLAZED ALUMINUM CURTAIN WALLS

08 51 13 ALUMINUM WINDOWS

08 56 74 CONTROL ROOM WINDOWS

08 63 00 METAL FRAMED SKYLIGHTS

08 71 00 DOOR HARDWARE

08 80 00 GLAZING

08 83 00 MIRRORS

08 87 23 SAFETY AND SECURITY FILMS

08 88 13 FIRE-RATED GLAZING

08 90 00 LOUVERS & VENTS

DIVISION 09 - FINISHES

09 05 61 COMMON WORK RESULTS FOR FLOORING PREPARATION

09 21 16 GYPSUM BOARD ASSEMBLIES

09 30 00 TILING

09 51 00 ACOUSTICAL CEILINGS

TABLE OF CONTENTS

BP2 – Conformance Set

05/22/2026

09 54 20 SPECIALTY CEILING SYSTEMS

09 64 29 WOOD STRIP FLOORING

09 65 00 RESILIENT FLOORING

09 65 66 RESILIENT ATHLETIC FLOORING

09 66 23 RESINOUS MATRIX TERRAZZO FLOORING

09 67 23 RESINOUS FLOORING

09 68 13 TILE CARPETING

09 68 16 SHEET CARPETING

09 72 00 WALL COVERINGS

09 84 00 ACOUSTIC ROOM COMPONENTS

09 91 13 EXTERIOR PAINTING

09 91 23 INTERIOR PAINTING

DIVISION 10 - SPECIALTIES

10 11 01 VISUAL DISPLAY BOARDS AND DISPLAY CASES

10 21 13 TOILET COMPARTMENTS

10 21 23 CUBICLE CURTAINS

10 22 13 WIRE MESH PARTITIONS

10 26 00 WALL PROTECTION

10 28 00 TOILET ACCESSORIES

10 44 00 FIRE PROTECTION SPECIALTIES

10 51 00 METAL LOCKERS

10 73 16 PREFABRICATED CANOPIES

10 75 00 FLAGPOLES

10 82 00 LOUVERED ROOFTOP EQUIPMENT SCREENS

DIVISION 11 - EQUIPMENT

11 23 00 COMMERCIAL LAUNDRY EQUIPMENT

11 40 00 FOODSERVICE EQUIPMENT

11 53 13 LABORATORY FUME HOODS

11 54 15 KILNS

11 61 13 ORCHESTRA SHELL

11 61 23 DEMOUNTABLE PLATFORMS

11 61 33 RIGGING SYSTEMS AND DRAPERIES

11 61 63 LOOSE PERFORMANCE LIGHTING FIXTURES

11 66 25 GYMNASIUM EQUIPMENT

DIVISION 12 - FURNISHINGS

12 24 13 WINDOW TREATMENT – ROLLER SHADES

12 34 00 LAMINATE CLAD CASEWORK

12 35 53.19 WOOD LABORATORY CASEWORK

12 35 83 SPECIALTY CASEWORK

12 36 00 COUNTERTOPS, BACKSPLASHES AND WINDOW STOOLS

12 48 13 ENTRANCE FLOOR MATS AND FRAMES

12 61 13 FIXED AUDIENCE SEATING

12 66 13 TELESCOPING BLEACHERS

12 66 23 TELESCOPING CHAIR PLATFORMS

TABLE OF CONTENTS

BP2 – Conformance Set

12 93 00 SITE FURNISHINGS

DIVISION 13 – SPECIAL CONSTRUCTION

13 34 13.13 FABRICATED GREENHOUSE

DIVISION 14 - CONVEYING EQUIPMENT

14 20 13 HYDRAULIC HOLELESS PASSENGER ELEVATOR

14 42 16 VERTICAL WHEELCHAIR LIFTS

TABLE OF CONTENTS

BP2 – Conformance Set

TABLE OF CONTENTS

VOLUME 3

00 01 07 SEALS PAGE

DIVISION 21 – FIRE SUPPRESSION

21 01 70 FIRE SUPPRESSION SPRINKLER AND STANDPIPE SYSTEMS

21 01 71 FIRE PUMP – ELECTRIC

21 01 72 CPVC SPRINKLER PIPING

DIVISION 22 - PLUMBING

22 00 00 GENERAL PROVISIONS – PLUMBING/FIRE PROTECTION

22 00 10 BASIC MATERIALS AND METHODS – PLUMBING

22 00 30 INSULATION & COVERING – PLUMBING

22 01 10 DRAINAGE SYSTEMS – PLUMBING

22 01 20 DOMESTIC WATER SYSTEMS – PLUMBING

22 01 21 (PP-R) DOMESTIC WATER PIPING

22 01 30 GAS PIPING SYSTEMS – PLUMBING

22 01 40 FIXTURES – PLUMBING

22 01 50 EQUIPMENT – PLUMBING

22 01 90 TESTING – PLUMBING

22 01 91 BALANCING – PLUMBING

DIVISION 23 - HVAC

23 02 00 GENERAL PROVISIONS – HVAC

23 02 05 POLYPROPYLENE WATER PIPING

23 02 10 BASIC MATERIALS AND METHODS – HVAC

23 02 15 VALVES

23 02 30 INSULATION & COVERING – HVAC

23 03 00 VIBRATION ISOLATION – HVAC

23 04 00 HEATING GENERATION EQUIPMENT

23 04 10 HEATING GENERATION AUXILIARY EQUIPMENT

23 04 50 REFRIGERATION EQUIPMENT – HVAC

23 05 00 PIPING SYSTEMS & ACCESSORIES – HVAC

23 05 10 WATER TREATMENT (HVAC)

23 06 00 AIR DISTRIBUTION AND ACCESSORIES – HVAC

23 06 05 FANS

23 07 25 TERMINAL HEATING UNITS

23 07 60 AIR HANDLING EQUIPMENT

23 08 61 AIR PURIFICATION SYSTEM

23 09 00 AUTOMATIC TEMPERATURE CONTROLS (DDC)

23 09 50 TESTING & BALANCING OF MECHANICAL SYSTEMS

TABLE OF CONTENTS

BP2 – Conformance Set

DIVISION 26 - ELECTRICAL

26 00 00 GENERAL PROVISIONS – ELECTRICAL

26 00 55 ELECTRICAL IDENTIFICATION

26 01 10 RACEWAYS

26 01 20 WIRES AND CABLES

26 01 30 MANHOLES

26 01 35 ELECTRICAL BOXES & FITTINGS

26 01 40 WIRING DEVICES

26 01 55 MOTOR STARTERS

26 01 56 ADJUSTABLE FREQUENCY DRIVES

26 01 60 PANELBOARDS

26 01 65 SWITCHBOARDS

26 01 70 MOTOR AND CIRCUIT DISCONNECTS

26 01 80 OVERCURRENT PROTECTIVE DEVICES

26 01 90 SUPPORTING DEVICES

26 01 95 POWER SYSTEM STUDIES

26 04 30 METERING EQUIPMENT

26 04 44 PAD-MOUNTED PRIMARY LOAD INTERRUPTER

26 04 52 GROUNDING

26 04 60 TRANSFORMERS

26 04 70 DISTRIBUTION CIRCUITS

26 04 71 FEEDER CIRCUITS

26 04 72 BRANCH CIRCUITS

26 04 75 ELEVATOR ELECTRICAL SYSTEMS

26 05 10 BUILDING LIGHTING

26 05 20 ROADWAY & PARKING AREA LIGHTING

26 06 01 LIGHTNING PROTECTION SYSTEMS

26 06 06 AUTOMATIC TRANSFER SWITCHES

26 06 12 EMERGENCY GENERATOR SYSTEMS

26 06 60 SURGE PROTECTIVE DEVICES

26 07 31 WIRELESS CLOCK SYSTEM

26 07 40 NETWORK CABLING SYSTEMS

26 07 71 INTERCOM/TELEPHONE COMMUNICATION SYSTEMS

26 07 73 CLASSROOM AUDIO, SAFETY, INTERCOMMUNICATION

SYSTEM

26 08 51 HEATING TERMINALS

26 09 61 PERFORMANCE LIGHTING SYSTEMS

26 09 63 PERFORMANCE LIGHTING SYSTEMS INSTALLATION

26 09 73 AUDIO VIDEO SYSTEMS INSTALLATION

26 60 10 RIGGING SYSTEMS ELECTRICAL WORK

DIVISION 27 - COMMUNICATIONS

27 41 17 AUDIO VIDEO SYSTEMS

TABLE OF CONTENTS

BP2 – Conformance Set

05/22/2026

DIVISION 28 – ELECTRONIC SAFETY AND SECURITY

28 07 21 FIRE ALARM AND DETECTION SYSTEMS

28 07 24 AREA RESCUE SYSTEM

28 07 25 INTRUSION SYSTEM

28 07 27 INTEGRATED ACCESS CONTROL & SECURITY MANAGEMENT

SYTEM

28 07 28 CCTV-NETWORK DIGITAL VIDEO MANAGEMENT SYSTEM

DIVISION 32 - EXTERIOR IMPROVEMENTS

32 12 43 POROUS FLEXIBLE PAVING

32 13 13 CONCRETE PAVING

32 13 73 CONCRETE PAVING JOINT SEALANTS

32 17 23 DECORATIVE INTERCONNECTED PAVEMENT MARKINGS

32 18 13 SYNTHETIC TURF

32 18 16.13 PLAYGROUND PROTECTIVE SURFACING

32 31 19.1 DECORATIVE METAL FENCES & GATES FOR LANDSCAPING

32 91 13 PLANTING PREPARATION

32 92 00 TURF AND GRASSES

32 93 00 PLANTS

32 94 00 SEEDING AND GROUNDCOVERS

Appoquinimink School District Summit Campus Middle and High School

Seals Page BP2 - Conformance Set - 05/22/2026 00 01 07 - 1

SECTION 00 01 07

SEALS PAGE

ARCHITECT

ABHA|BSA+A

1621 N. LINCOLN STREET

WILMINGTON, DELAWARE 19806

(302) 658-6426

DE License No. 5701

CIVIL ENGINEER

LANDMARK SCIENCE & ENGINEERING

200 CONTINENTAL DRIVE, SUITE 400

NEWARK, DELAWARE 19713

(302) 323-9377

DE License No. 20916

LANDSCAPE ARCHITECT - FIELDS

ACTIVITAS

70 MILTON STREET

DEDHAM, MA 02026

(781) 326-2600

LANDSCAPE ARCHITECT

SIKORA WELLS APPEL

8 KINGS HIGHWAY WEST, SUITE A

HADDONFIELD, NEW JERSEY 08033

(856) 433-6380

STRUCTURAL ENGINEER

DCI ENGINEERS

2 MILL ROAD, SUITE 100

WILMINGTON, DELAWARE 19806

(302) 252-9200

MEP ENGINEER

FURLOW ASSOCIATES, INC.

650 NAAMANS ROAD, SUITE 211

CLAYMONT, DELAWARE 19703

(302) 798-3515

DE License No.

END OF SECTION

This page intentionally left blank

FIRE SUPPRESSION SPRINKLER AND STANDPIPE SYSTEMS 21 01 70-1

BP2 – Conformance Set - 05/22/2026

SECTION 21 01 70

FIRE SUPPRESSION SPRINKLER AND STANDPIPE SYSTEMS

PART 1 – GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary

Conditions and Division 1 Specification Sections, apply to this Section.

B. Codes and Standards listed below, apply to work indicated on the drawings and in the specifications.

1. National Fire Protection Association (NFPA)

2. Delaware State Fire Prevention Regulations (DSFPR)

3. American National Standards Institute (ANSI)

4. American Society for Testing Materials (ASTM)

5. National Electrical Manufacturer’s Association (NEMA)

6. Underwriters’ Laboratories (UL)

1.2 SUMMARY

A. This Section includes fire-suppression sprinklers, piping, and equipment for the following building systems:

1. Wet-pipe, fire-suppression sprinkler systems, including piping, valves, specialties and automatic sprinklers.

2. Wet pipe, fire suppression standpipe system, including piping, hose valves, valves, and specialties.

3. Contractor shall provide schedule and location of all fire hose valve cabinets on sprinkler drawings regardless of which trade procures or installs them.

B. Additional work includes, but is not limited to the following:

1. Obtain and pay for all permits, licenses, approvals, reviews, utility shutdowns, water flow testing, pressure tests and acceptance inspections.

2. Pipe sleeves through floors, walls and structural elements of the building, set in coordinated locations. Penetrations created in fire rated walls and floors, shall have their smoke stopping and fire rating integrity restored with the use of fire tested, U.L. listed details, that have prior approval of the local Fire Prevention Bureau.

3. All cutting, coring and patching of general construction as necessary for installation of the work specified.

4. Coordinated working drawings and hydraulic calculations from water flow test data less than one year old; submit and obtain approval by the local Fire Prevention Bureau and Owner’s

Insurance Underwriter, and State Fire Marshal.

5. Clean-up, on a daily basis, of all debris associated with the installation of this work, as necessary to maintain the premises in a broom swept condition.

6. Testing, adjusting, retesting, re-adjusting as may be required to obtain system acceptance by the local Fire Prevention Bureau, Owner’s Insurance Underwriter, State Fire Marshal and

Owner’s Representative. Fire Protection Contractor shall remain responsible for the fire protection systems until all approvals are obtained.

7. Provide equipment manuals, record drawings, valve tag schedules and personnel instruction, prior to system turnover to the Owner.

Summit Campus Appoquinimink School District

21 01 70-2 FIRE SUPPRESSION SPRINKLER AND STANDPIPE SYSTEMS

8. Provide fire protection on all floors during construction, utilizing temporary standpipes or fire extinguishers, according to the requirements of the authority having jurisdiction.

9. Performance of all work specified in this Section shall be in compliance with the requirements of the Occupational Safety and Health Act and Construction Safety Standards.

C. The work in this Section includes providing all labor, materials, specialty products testing and services for, and reasonably incidental to, the satisfactory completion of the Fire Protection systems, as indicated on the Contract Drawings, in the Specification Sections, and as required by the applicable Codes and Standards.

D. The following related work is specified in other Divisions and Sections of the specification.

1. Electrical power supply to water flow switches, tamper switches.

2. Fire extinguishers and cabinets.

E. Related Sections include the following:

1. Division 26 Section "Fire Alarm Systems" for alarm devices not in this Section.

2. Division 22 Section “General Provisions – Plumbing/Fire Protection

3. Division 10 Section “Fire Protection Specialties” for cabinets and fire extinguishers.

4. Division 7 Section “Fire Stopping”

1.3 DEFINITIONS AND INTERPERTATIONS

A. Specific terminology used in the Design Drawings and Specifications shall have the following meanings;

1. “Piping” includes pipe, fittings, flanges, valves, controls, hangers, supports, vents, drains and other customarily required items required in connection with the transfer of gases and fluids.

2. “Install” includes unloading at the delivery point for the project and performing all tasks necessary to establish a secure mounting and correct operation, for items and assemblies furnished by other trades or the Owner.

3. “Furnish” includes purchase and delivery to the project site, of items and assemblies, complete with every necessary appurtenance.

4. “Provide” shall mean “Furnish and Install”

5. “Concealed” when used in connection with the installation of piping, shall mean hidden from view behind chases, furred spaces, pipe shafts, or above suspended ceilings.

6. “Concealed Spaces of Combustible Construction shall be as defined in NFPA#13, Section

8.15.1.

7. “Contractor” shall mean the Fire Protection contractor and his vendors, fabricators or subcontractors.

8. “Design Drawings” shall mean documents, including drawings and written specifications, prepared by the Architects and Engineers, to obtain building permits and competitive bid proposals from contractors, for construction of the specified fire protection systems.

9. “Working Plans” shall mean documents, including calculations, drawings and material specifications prepared by the fire protection contractor, according to NFPA#13, for obtaining approval from the authority having jurisdiction, Owner’s insurance underwriter, Architect/Engineer and the State Fire Marshal.

10. “NPS” shall mean nominal pipe size, in inches.

11. “CPVC” shall mean Chlorinated polyvinyl chloride plastic.

12. “Owner” shall mean Appoquinimink School District.

FIRE SUPPRESSION SPRINKLER AND STANDPIPE SYSTEMS 21 01 70-3

13. “Architect” shall mean the Architect of Record as denoted in this package.

14. “Engineer” shall mean the Engineer of Record as denoted in this package.

15. “UL” means Underwriter’s Laboratories

16. “FM” means Factory Mutual.

17. “Sprinkler System” shall mean piping and sprinklers under the individual control of a supervised control valve, with provisions for alarm annunciation, alarm testing and system drainage.

18. “Standpipe” shall mean piping, valves, hose connections, and allied equipment with the hose connections located such that water can be discharged through attached hose and nozzles, for the purpose of extinguishing a fire, thereby protecting a building, structure, its contents, and the occupants.

19. Reference applicable NFPA Standards for additional definitions that shall apply to work under this Section.

B. The use of the Design Drawings and Specifications by the contractor, for Bid Proposal and

Working Drawing preparation, shall include the following understandings:

1. The information included in the drawings and specifications is given as a guide only, to indicate general design feasibility and to show an acceptable arrangement of system zones, system types, sprinkler positions, main piping location and equipment layout.

2. The design drawings utilize symbols and diagrams to indicate required work, representing only the sequence of items to be installed, which have no dimensional significance and do not indicate every required item to be provided. The work shall be installed in accordance with the diagrammatic intent expressed on the drawings, in conformity with the dimensions indicated on the final architectural and structural working drawings, and final equipment shop drawings. Information regarding general construction shall be derived only from the

Architectural and Structural Design Drawings and Specifications.

3. The drawings and specifications are complementary and are to be utilized together for a complete interpretation of the work intended. The higher capacity or standard shall be provided, where conflicts between the drawings and specifications, or conflicts within themselves, occur.

4. The limitations of the language used on the drawings and specifications shall not be interpreted as meaning that accessories and appurtenances, required for completion of work, are to be excluded. The description of any item, on the drawings or in the specifications or both, requires the installation of all it’s necessary components for approved, satisfactory operation. These drawings do not indicate sprinkler head locations. The Contractor shall reference the architectural reflected ceiling plans. The intent is to establish an architecturally acceptable arrangement of sprinklers with other ceiling elements including lights, diffusers, speakers etc., to be repeated in similar areas. Provide sprinklers according to the NFPA#13 occupancy hazard classification and spacing rules, for unfinished ceiling area.

5. Submission of a bid proposal requires the contractor to review all project documents and visit the construction site, to be thoroughly familiar with all requirements for the project, and identify in his bid, conditions that may affect the efficient and satisfactory performance of the work. Claims for additional compensation shall be denied if the above procedures are not followed and the disputed conditions may have been identified by the completion of these required tasks.

6. The information shown on the design drawings and written in the specifications shall not be interpreted as to instruct the contractor to not follow the applicable codes or local amendments. Where the information provided is believed not to be in conformance with the

21 01 70-4 FIRE SUPPRESSION SPRINKLER AND STANDPIPE SYSTEMS

code requirements, the contractor shall notify the Architect and Engineer for clarification prior to the submission of his bid proposal.

7. References to providing sprinklers per the NFPA#13 Standard mandates that all building areas shall be provided with complete, full sprinkler protection, unless specific notation is made to the contrary on the drawings or in the specification.

8. References in this Specification to NFPA Standards as design and installation guidance of fire protection systems, invoke all of the Sections, Subsections, Exceptions and Advisory

Provisions of the Standard that are applicable to the Project's requirements; they are hereby included in this Specification as if repeated in their entirety, and are referenced to convey the minimum acceptable performance and installation requirements acceptable.

9. All the referenced information and guidance for design noted prior shall also be used and adhered to in the design of the fire suppression standpipe systems. Fire suppression standpipe systems shall be designed and installed in accordance with NFPA 14 and the Delaware State

Fire Prevention Regulations.

1.4 SPRINKLER SYSTEM PERFORMANCE REQUIREMENTS

A. Design sprinkler system piping according to the following requirements and obtain approval from authorities having jurisdiction, Owner’s insurance underwriter, Architect, Engineer and Fire

Marshal. Refer to Section 1.7 QUALITY ASSURANCE, paragraph I., Working Plans and

Hydraulic Calculations, and Section 3.1 PREPARATION WORKING OF PLANS, for additional system performance related design requirements.

B. Design sprinkler system piping according to the following:

1. Include 10 psi cushion pressure as a margin of safety in available water flow and pressure calculations.

2. Include losses from point of connection to city water main, through water-service entrance, backflow preventer, sprinkler system piping, including all valves, fittings and devices.

3. Maximum piping velocity shall be limited to 20 fps.

4. Sprinkler Occupancy Hazard Classifications shall be as follows:

a. Classrooms, Art Rooms, Music Rooms, Multi-Purpose Room: Light Hazard

b. Offices, Corridors, Toilet rooms, Locker rooms, Public Areas, Cafeteria Seating Areas:

Light Hazard

c. Building Service Areas, Kitchen, Janitor's Closets, Electrical and Telephone Equipment

Rooms and Closets, Mechanical Equipment Rooms: Ordinary Hazard, Gp. 1.

d. General Storage Areas, Stage Loading Docks: Ordinary Hazard, Gp. 1.

e. Combustible construction and Combustible concealed spaces: Light Hazard.

f. All other occupancies and hazards not noted, shall be in accordance with NFPA.

5. Minimum Density for Automatic-Sprinkler Piping Design shall be as follows:

a. Light Hazard Occupancy: 0.10 gpm over 1500-sq. ft. area unless otherwise indicated on drawing data schedule.

b. Ordinary Hazard, Group 1 Occupancy: 0.15 gpm over 1500-sq. ft. area unless otherwise indicated on drawing data schedule.

c. Ordinary Hazard, Group 2 Occupancy: 0.20 over 1,500 sq. ft. area unless otherwise indicated on drawing data schedule.

d. Combustible construction and Combustible concealed spaces: 0.10 gpm over 1500-sq. ft.

area unless otherwise indicated on drawing data schedule.

FIRE SUPPRESSION SPRINKLER AND STANDPIPE SYSTEMS 21 01 70-5

e. Special Occupancy Hazard: As determined by authorities having jurisdiction.

f. For light and ordinary hazard occupancies, where the requirements of NFPA 13 are met, design are reduction for quick response sprinklers may be used.

C. Components and Installation shall be capable of producing piping systems with 175-psig minimum working-pressure rating, unless otherwise indicated.

1.5 STANDPIPE SYSTEM PERFORMANCE REQUIREMENTS

A. Design Class I horizontal fire standpipe system piping according to the following requirements and obtain approval from authorities having jurisdiction, Owner’s insurance underwriter, Architect, Engineer, and Fire Marshal. Refer to Section 1.8 QUALITY ASSURANCE, Paragraph

I, Working Plans and Hydraulic Calculations, and Section 3.1 PREPARATION WORKING OF

PLANS, for additional system requirements related design requirements.

B. Design fire standpipe system piping according to the following:

1. Design shall be in accordance with NFPA 14 and the Delaware State Fire Protection

Regulations/International Building Code.

2. Include losses from the fire department connection, including all valves including hose valves, fittings, and devices.

3. Maximum piping velocity shall be limited to 20 fps.

4. Classification: Class I Horizontal Wet Standpipe supplied by the fire department at the system fire department connection.

5. Minimum standpipe flow and pressure to be as follows:

a. A flow of 250 gpm at the three most hydraulically remote hose connections of the hydraulically most remote horizontal standpipe.

b. A minimum of 100 psi at the most remote hose valve while flowing system demand.

c. The system shall be hydraulically designed so that the required system pressure does not exceed 175 psi at any point in the system.

C. Components and installation shall be capable of producing piping systems with 175-psig minimum working-pressure rating, unless otherwise indicated.

1.6 SUBMITTALS

A. The contractor shall provide Submittals according to Section 220010, with all required drawings, calculations and product data for complete review of the proposed system installation submitted at the same time. Incomplete submittals shall be returned unreviewed. When resubmittals are required, all changes from the original submittal shall be clearly identified with revision triangles and clouds.

B. Product Data shall be provided for the following:

1. Pipe and fitting materials and methods of joining for sprinkler piping.

2. Pipe hangers and supports.

3. Valves, including specialty valves, accessories, and devices.

4. Alarm devices. Include electrical data.

5. Air compressors. Include electrical data.

6. Fire department connections. Include type; number, size, and arrangement of inlets; caps and chains; size and direction of outlet; escutcheon and marking; and finish.

7. Sprinklers, escutcheons, and guards. Include sprinkler flow characteristics, mounting, finish, and other pertinent data.

21 01 70-6 FIRE SUPPRESSION SPRINKLER AND STANDPIPE SYSTEMS

8. Fire stopping product materials and U.L. listed installation details for penetrations of fire-rated walls and floors.

9. Fire hose station equipment including hose valves, hose adapters and hose cabinets.

C. Fire-Hydrant Flow Test has been executed for the project on 1/16/19 and data is recorded on the drawing.

D. Sprinkler and Standpipe Piping Drawings: Working plans and hydraulic calculations, shall be prepared according to NFPA #13 and NFPA #14, and submitted to the authorities having jurisdiction, Owner’s insurance agent, Architect, Engineer, and State Fire Marshal for approval.

E. Field Test Reports and Certificates: Indicate and interpret test results for compliance with performance requirements and as described in NFPA #13 and NFPA #14, including the

"Contractor's Material and Test Certificate for Aboveground Piping" for each system.

F. Maintenance Data: shall be submitted for each type of sprinkler component and specialty, and included in the maintenance manuals, specified in Division 1.

G. Record Drawings: Refer to Division 1 for requirements. An up to date set of working drawings shall be kept at the site to record minor change in the intended system installation, as as-built conditions. Provide the required copies of final working drawings, corrected to show all as-built conditions, to the Owner, and the Owner’s insurance agent upon completion of the project.

H. System Diagram and Operating Instructions: Provide at the completion of work, a color coded, neatly drawn small scale plan, mounted in a substantial glass enclosed frame, showing the locations of all sprinkler system control valves, auxiliary low point drains and inspector’s test connections. Provide a minimum of two (2) copies of the current edition of NFPA#25, “Standard for the Inspection, Testing, and Maintenance of Water Based Fire Protection Systems”.

I. Guarantee: The contractor shall submit a written guarantee of all materials and workmanship for a period of one (1) year, beginning at the date of final acceptance or beneficial use to the Owner, which includes emergency repair service for sprinkler systems, within four (4) hours, on a twenty-four (24) hour, seven (7) day a week basis, upon request for repair service by the Owner.

1.7 QUALITY ASSURANCE

A. All materials, specialty products, equipment, methods of installation, and the application of materials and products in specific situations, shall be in strict accordance with the applicable requirements of NFPA #13 and NFPA #14, and have the prior approval of the authority having jurisdiction. All materials and equipment shall be U.L. labeled and/or F.M. approved, and installed in accordance with their listings.

B. Installer Qualifications: An experienced installer who has designed and installed fire-suppression systems similar to that indicated for this Project and obtained design approval and inspection approval from authorities having jurisdiction.

C. Manufacturer Qualifications: Firms whose equipment, specialties, and accessories are listed by product name and manufacturer in UL's and/or Fire Marshal’s "Fire Protection Equipment

Directory" and that comply with other requirements indicated.

D. Sprinkler Components: Listing/approval stamp, label, or other marking by a testing agency acceptable to authorities having jurisdiction.

E. Working Plans and Hydraulic Calculations

1. Design the specified sprinkler systems and standpipe systems utilizing hydraulic calculations and indicate the intended installation of systems accurately on minimum 1/8”scale plans, with

¼” scale details which include the following:

a. Building section/elevation details, with all necessary elevation data shown.

FIRE SUPPRESSION SPRINKLER AND STANDPIPE SYSTEMS 21 01 70-7

b. Riser diagram of system water supply and backflow prevention.

c. All pipe lengths, diameters, fittings, hangers locations and details, earthquake bracing and restraints, valves and devices with piping details.

d. A site plan indicating project location, site elevations, north arrow, street intersections, Fire Department access lane(s), location of Fire Department connection(s), and size, material and location of public, and private fire water service mains and their appurtenances. The site plan shall be scaled or indicate dimensions and distances (of mains) and show location of water flow test(s).

e. Hydraulically most remote design area(s) with hydraulic nodes on plans corresponding to hydraulic calculations.

2. Provide hydraulic calculations utilizing Hazen-Williams formula for determining piping friction losses, to prove the intended design, according to the requirements NFPA#13 and

NFPA #14, using “C” values therein, which include the following:

a. Each type of pipe and joining method to be used, including weight, schedule, wall thickness, exact internal diameters, wall thicknesses and corrosion resistance ratio (CRR), for pipes other than Sch. 40.

b. The K-factor, orifice diameter, and minimum operating pressure required, for each flowing sprinkler in the hydraulically most remote area(s), according to the worst case requirements of either NFPA#13, NFPA #14, the local Fire Dept., or the appropriate approval/U.L. listing pressure required, to deliver the required minimum water distribution. Flows shall be calculated to the nearest 1/10 gallon.

c. Piping friction losses calculated to the nearest foot for all pipe lengths over (1) foot; all vertical lengths shall be included to show loss or gain of elevation pressures. Pressures shall be calculated to the nearest 1/100 psi.

d. Pressure losses for dry valves, deluge valves, backflow preventers etc., shall be clearly indicated as a device, and expressed as additional feet of pipe.

e. Velocity in all piping to be 20 feet per second or less. Velocity pressure may be ignored in hydraulic calculations.

f. Provide hydraulic calculations in an "easily reviewable" format, similar to the traditional

NFPA#13 presentation, including the name of the hydraulic calculation program used, if applicable. The order of entry shall follow the flow of water from the most remote design sprinkler back to the riser, with flows added and subtracted at the cross main; order entry based upon only a sequential ordering of the node numbers, which could result in jumps from one pipe segment to a disjunct segment, is not "easily reviewable", and therefore is not an acceptable submittal format.

g. All notes in the hydraulic calculations corresponding to the calculated results shall be clearly identified on the plans, including the site plan.

1.8 EXTRA MATERIALS

A. Furnish extra materials described below that match products installed and that are packaged with protective covering for storage and identified with labels describing contents.

1. Sprinkler Cabinets: Finished, wall-mounting steel cabinet and hinged cover, with space spare sprinklers plus sprinkler wrench. Include the minimum number of each type of sprinkler in the project, as required by NFPA #13.

1.9 LEAK DAMAGE

A. The fire protection contractor shall be responsible during the installation and testing of the sprinkler and standpipe system(s), for damage to building, it’s contents, the work of

21 01 70-8 FIRE SUPPRESSION SPRINKLER AND STANDPIPE SYSTEMS

other trades etc., caused by leaks or overflow from equipment, defective valves, disconnected or unplugged pipes, fittings etc., and shall pay for the repair or replacement of work or facilities damaged by such leaks.

PART 2 – PRODUCTS

2.1 MANUFACTURERS

A. Available Manufacturers: Subject to compliance with requirements, manufacturers offering products that may be incorporated into the work include, but are not limited to, the following:

B. Manufacturers: Subject to compliance with requirements, provide products by one of the following:

1. Specialty Valves and Devices:

Vicatulic Company

Tyco Fire Suppression & Building Products

Reliable Automatic Sprinkler Co., Inc.

Viking Corp.

2. Water-Flow Indicators and Supervisory Switches/and Electrical Bells:

Tyco Fire Suppression & Building Products

Potter Electric Signal Co.

Reliable Automatic Sprinkler Co., Inc.

Viking Corp.

3. Sprinkler, Drain and Alarm Test Fittings:

Tyco Fire Suppression & Building Products

Fire-End and Croker Corp.

Victaulic Company

AFG Manufacturing

4. Sprinkler, Branch-Line Test Fittings:

Elkhart Brass Mfg. Co., Inc.

Fire-End and Croker Corp.

Smith Industries, Inc.; Potter-Roemer Div.

AFG Manufacturing

5. Sprinkler, Inspector's Test Fittings:

Fire-End and Croker Corp.

G/J Innovations, Inc.

Triple R Specialty of Ajax, Inc.

AFG Manufacturing

6. Fire Department Connections:

Potter-Roemer

Elkhart Brass Mfg. Co., Inc.

Fire-End and Croker Corp.

Tyco Fire Suppression & Building Products

Guardian Fire Equipment, Inc.

FIRE SUPPRESSION SPRINKLER AND STANDPIPE SYSTEMS 21 01 70-9

Reliable Automatic Sprinkler Co., Inc.

7. Sprinklers:

Tyco Fire Suppression & Building Products

Reliable Automatic Sprinkler Co., Inc.

Viking Corp.

Victaulic Company

8. Fire Dept. Hose Valves:

Potter-Roemer

Elkhart

Fire-End and Croker Corp.

Guardian Fire Equipment, Inc.

Fire Hose Valve Cabinets:

Potter-Roemer

Larsen

Guardian Fire Equipment, Inc.

Fire-End and Croker Corp.

9. Fire-Protection-Service Valves:

Tyco Fire Suppression & Building Products

Central Sprinkler Corp.

Nibco, Inc.

Stockham Valves & Fittings, Inc.

Victaulic Company

10. Keyed Couplings for Steel Piping: (Grooved Fittings)

Tyco Fire Suppression & Building Products

Victaulic Company

Viking Corp.

Anvil International Grulok

11. Fire Protection Backflow Prevention Valve Assemblies.

Ames Fire & Waterworks

Watts Regulator Company

Apollo Valves (Conbraco)

2.2 PIPING MATERIALS

A. Refer to Part 3 "Piping Applications" Article for applications of pipe, tube, fitting, and joining materials in specific fire protection services. All piping shall be permanently marked continuously along its length by the manufacturer, properly identifying the type of pipe. All fittings shall be stamped or embossed by the manufacturer, indicating the size, pressure rating, and U.L. listing or F.M. approval.

21 01 70-10 FIRE SUPPRESSION SPRINKLER AND STANDPIPE SYSTEMS

2.3 PIPES AND TUBES

A. Standard-Weight Steel Pipe: ANSI/ASTM A 53, ASTM A 135, or ASTM A 795; Schedule 40 in

NPS 6” and smaller, and Schedule 30 in NPS 8” and larger, may be joined with threads or cut-groove couplings and fittings, for pressures up to 300 psi.

B. Schedule 30 Steel Pipe: ASTM A 135 or ASTM A 795, with wall thickness less than Schedule

40 and equal to or greater than Schedule 30, or ASTM A 795 and ASME B36, 10M, Schedule 30 wrought-steel pipe, may be joined by welding or roll-groove couplings and fittings, for pressures up to 300 psi.

C. Schedule 10 Steel Pipe: ASTM A 135 Schedule 10 in NPS 5” and smaller and NFPA #13 specified wall thickness in NPS 6” to NPS 10”, may be joined by welding or roll-groove couplings and fittings, for pressures up to 300 psi.

D. UL Listed CPVC fire sprinkler pipe and fittings for fire sprinkler system piping 3” and smaller

(not including standpipe systems). See specification Section 21 01 72 CPVC Sprinkler Piping

(Basis of Design).

E. “THINWALL,” “XL” piping shall not be permitted on this project.

2.4 PIPE AND TUBE FITTINGS

A. Cast-Iron Threaded Flanges: ASME B16.1.

B. Cast-Iron Threaded Fittings: ASME B16.4.

C. Malleable-Iron Threaded Fittings: ASME B16.3.

D. Steel, Threaded Couplings: ASTM A 865.

E. Steel Welding Fittings: ASTM A 234/A 234M, ASME B16.9, or ASME B16.11.

F. Steel, Grooved-End Fittings: UL-listed and approved, ASTM A 47, malleable iron or

ASTM A 536, ductile iron; with dimensions matching steel pipe and ends factory grooved according to AWWA C606.

2.5 JOINING MATERIALS

A. Refer to Division 22 Section "Basic Mechanical Materials and Methods" for pipe-flange gasket materials and welding filler metals.

B. Steel, Keyed Couplings: UL 213 and AWWA C606, for steel-pipe dimensions. Include

ASTM A 536, ductile-iron housing, rubber gaskets, and steel bolts and nuts. Include listing for dry-pipe service for couplings for dry piping.

2.6 FIRE-PROTECTION-SERVICE VALVES

A. General: UL listed and approved, with minimum 175-psig nonshock working-pressure rating.

Valves for grooved-end piping may be furnished with grooved ends instead of type of ends specified.

B. Gate Valves, NPS 6” and Smaller: UL 262; cast-bronze, threaded ends; solid wedge; OS&Y; and rising stem.

C. Indicating Valves, NPS 3” and Smaller: UL 1091; butterfly or ball-type, bronze body with threaded ends; and integral indicating device.

Indicator: Visual.

Indicator: Electrical 115-V ac, prewired, two-circuit, supervisory switch.

D. (Optional Section) Gate Valves, NPS 4” and Larger: UL 262, iron body, bronze mounted, taper wedge, OS&Y, and rising stem. Include replaceable, bronze, wedge facing rings and flanged ends.

FIRE SUPPRESSION SPRINKLER AND STANDPIPE SYSTEMS 21 01 70-11

E. Swing Check Valves, NPS 2” and Smaller: UL 312 or MSS SP-80, Class 150; bronze body with bronze disc and threaded ends.

F. Swing Check Valves, NPS 2-1/2” and Larger: UL 312, cast-iron body and bolted cap, with bronze disc or cast-iron disc with bronze-disc ring and flanged ends.

G. Split-Clapper Check Valves, NPS 4” and Larger: UL 312, cast-iron body with rubber seal, bronze-alloy discs, and stainless-steel spring and hinge pin.

2.7 SPRINKLERS

A. Utilize quick-response sprinklers throughout Light and Ordinary Hazard occupancies

B. Automatic Sprinklers: shall have heat-responsive element complying with the following:

UL 199, for applications except residential.

UL 1767, for early suppression, fast-response applications.

C. Sprinkler Types and Categories: Nominal 1/2-inch standard orifice, unless otherwise indicated or required by application.

D. Sprinkler types, features, and options include the following:

Dry upright sprinklers

Dry pendent sprinklers

Horizontal Dry/Sidewall sprinklers

Pendent sprinklers (Recessed)

Quick-response sprinklers

Sidewall sprinklers

Upright sprinklers

E. Sprinkler Finishes: Upright bronze, and “white” painted pendents and sidewalls.

F. Sprinkler Escutcheons: Materials, types, and finishes for the following sprinkler mounting applications. Escutcheons for concealed, flush, and recessed-type sprinklers are specified with sprinklers.

Ceiling Mounting: White-plated steel, two piece, flat.

Ceiling Mounting: Metal, white finish, two piece, flat.

Sidewall Mounting: White-plated steel, two piece, flat.

Sidewall Mounting: Metal, white finish, two piece, flat.

G. Sprinkler Guards: Wire-cage type, including fastening device for attaching to sprinkler.

H. Sprinkler Water Shields: Shield for protecting sprinkler, heat-sensing operating element from other sprinkler water discharge (pendent and/or upright sprinkler water shield.

2.8 SPECIALTY SPRINKLER FITTINGS

A. Specialty Fittings: UL listed and approved; made of steel, ductile iron, or other materials compatible with piping.

B. Locking-Lug Fittings: UL 213, ductile-iron body with locking-lug ends.

C. Mechanical-T Fittings: UL 213, ductile-iron housing with pressure-responsive gasket, bolts, and threaded or locking-lug outlet.

D. Mechanical-Cross Fittings: UL 213, ductile-iron housing with pressure-responsive gaskets, bolts, and threaded or locking-lug outlets.

E. Drop-Nipple Fittings: UL 1474, with threaded inlet, threaded outlet, and seals; adjustable.

21 01 70-12 FIRE SUPPRESSION SPRINKLER AND STANDPIPE SYSTEMS

F. Sprinkler, Drain and Alarm Test Fittings: UL-listed, cast- or ductile-iron body; with threaded inlet and outlet, test valve, and orifice and sight glass.

G. Sprinkler, Branch-Line Test Fittings: UL-listed, brass body; with threaded inlet and capped drain outlet and threaded outlet for sprinkler.

H. Sprinkler, Inspector's Test Fittings: UL-listed, cast- or ductile-iron housing; with threaded inlet and drain outlet and sight glass.

2.9 FIRE DEPARTMENT CONNECTIONS

A. Confirm with the local Fire Department for type of connection requirement: Storz or Siamese.

B. Wall, Fire Department Connections: UL 405; cast-brass body with brass, wall, escutcheon plate;

brass, lugged caps with gaskets and brass chains; and brass, lugged swivel connections. Include inlets with threads according to NFPA 1963 and matching local fire department sizes and threads, outlet with pipe threads, extension pipe nipples, check devices or clappers for inlets, and escutcheon plate with marking "AUTO SPKR”/“STANDPIPE AND AUTO SPKR”.

Type: Flush mounting.

Escutcheon Plate: Rectangular.

Finish: Polished chrome-plated.

2.10 ALARM DEVICES

A. General: All alarm devices shall be U.L. listed and F.M. approved as sprinkler system attachments. Types utilized shall match piping and equipment connections.

B. Electric-Operated Alarms: Provide 10” outside waterproof vibrating type bell and 6” inside bell, in locations shown on drawings or required by the local Fire Dept.

C. Water-Flow Indicators: UL 346; electrical-supervision, vane-type water-flow detector; with 250-psig pressure rating; and designed for horizontal or vertical installation. Include two single-pole, double-throw, circuit switches for isolated alarm and auxiliary contacts, 7 A, 125-V ac and 0.25

A, 24-V dc; complete with factory-set, field-adjustable retard element to prevent false signals and tamperproof cover that sends signal if removed.

D. Pressure Switches: UL 753; electrical-supervision-type, water-flow switch with retard feature.

Include single-pole, double-throw, normally closed contacts and design that operates on rising pressure and signals water flow.

E. Valve Supervisory Switches: UL 753; electrical; single-pole, double throw; with normally closed contacts. Include design that signals controlled valve is in other than fully open position.

F. Low Temperature Supervisory Switch: UL listed, electrical-supervisory-type, temperature activated, normally open contact, operated at set temperature of 40°F.

2.11 PRESSURE GAGES

A. Pressure Gages: UL 393, 3-1/2- to 4-1/2-inch diameter dial with dial range of 0 to 250 psig.

2.12 See Specification Section 21 01 72 Alternate CPVC Sprinkler System Piping for alternative sprinkler piping material and fittings for wet-pipe, light hazard occupancy sprinkler pipe 3” or smaller.

PART 3 – EXECUTION

3.1 PREPARATION OF WORKING PLANS

A. The contractor shall be responsible for reviewing the Architectural and Structural Design

Drawings and verifying with the General Contractor, that substitutions of noncombustible building materials with combustible building materials have not been made that alter the requirements of the sprinkler system shown on the Fire Protection Design Drawings. Report such

FIRE SUPPRESSION SPRINKLER AND STANDPIPE SYSTEMS 21 01 70-13

substitutions to the Architect and Engineer for review, prior to the design of sprinkler systems.

Combustible framing or construction is not allowed above ceilings, below floors or in concealed spaces, unless specifically protected by sprinklers.

B. The final arrangement, positions and connections of pipes, drains, valves, sprinklers etc., shall be established by the fire protection contractor’s design, and shall be configured to drain fully, avoiding trapped piping sections and excessive auxiliary drains. Sprinkler systems shall be installed concealed above architectural suspended ceilings where ceilings are provided, unless indicated otherwise.

C. Design the specified fire protection systems from the fire service entry riser, in accordance with the mandatory requirements and all advisory provisions of NFPA#13 and NFPA#14, the requirements of the authority having jurisdiction and the Owner’s insurance agent, utilizing hydraulic calculations, with uniform water distribution over each most remote design area and/or specified demand.

D. Establish each sprinkler position, giving full consideration to the vertical and horizontal obstructions to sprinkler spray pattern development that may be presented by building construction, ductwork, mechanical and electrical equipment, piping, soffits and ceilings constructed with different adjacent elevations, suspended and surface mounted lighting fixtures etc.; coordinate the position and location of sprinklers, piping and system components, referencing the detailed working drawings of all other trades, to avoid installation conflicts.

E. Contractor shall be responsible for planning and providing the required penetrations of fire rated walls, floors and smoke partitions, in such a manner that U.L. listed details that restore their fire rating integrity and that have prior approval of the Delaware State Fire Marshal’s Office where they are utilized.

F. Where practical, uniformly space sprinklers on branchlines; sprinklers shall be spaced in architectural patterns consistent with symmetrical positions of lights, air diffusers, speakers, and other ceiling elements, where sprinklers are shown on architectural reflected ceiling grid plans.

1. Pendent sprinklers in architectural ceilings shall be centered in square ceiling tiles in both directions, and centered in the short dimension of rectangular tiles, with sprinkler positions acceptable at quarter points of the long dimension, +/- 12”.

2. Provide sprinkler spacing and locations per NFPA#13 requirements, in areas without suspended ceilings.

G. Wet sprinkler systems may be “tree”, “loop” or “grid” type systems, as may be hydraulically advantageous, unless a specific piping arrangement is indicated on the design drawings. System piping arrangement shall be configured above the top of recessed lighting fixtures, within suspended ceilings.

H. Where sprinkler piping within concealed spaces provides protection for occupancies below, sprinklers for protection of concealed spaces may be attached to the same piping system.

Hydraulically calculate each set of sprinklers separately and provide pipe sizes for the hydraulically more demanding group.

I. Sprinklers for the protection of attic spaces may be conventional upright or pendent types, or a combination of these types of sprinklers. The position of sprinklers in attics framed of combustible construction, shall establish sprinkler protection into the eaves overhanging the outside of the building.

J. Provide sprinkler protection in combustible framed, horizontal and vertical soffits and wall cavities, with outside finished dimensions greater than 14.” Where combustible concealed construction and spaces are permitted to be unsprinklered, meeting one or more of the exceptions of NFPA#13, Section 8.15.1.1, the design area of application shall be increased to a minimum of

21 01 70-14 FIRE SUPPRESSION SPRINKLER AND STANDPIPE SYSTEMS

3,000 sq.ft., without revising the hydraulic density, per NFPA#13, Section 11.2.3.1.5 and

11.2.3.2.

K. Provide standpipe system hose connections at all locations as required by NFPA #14, the

Delaware State Fire Prevention Regulations, the Authority having Jurisdiction and thoughs locations as directed by the Owner, Architects, and/or the Engineer. Provide hose valve cabinets in locations as indicated on the Architectural and Design drawings.

3.2 PIPING APPLICATIONS

A. Flanges, unions, transitions and special fittings shall have pressure ratings the same as or higher than system's static pressure rating for use in aboveground applications, unless otherwise indicated.

B. Piping between Fire Department Connections and Check Valves: Use galvanized, standard-weight steel pipe with grooved ends; steel, grooved-end fittings; steel, keyed couplings; and grooved joints.

C. Underground Service-Entrance Piping: Use ductile-iron, push-on-joint pipe and fittings and restrained joints.

Fire Suppression Bulk Mains and Risers: See Fire Protection Drawings.

D. Wet-Pipe Sprinkler Branch and Standpipe Piping: See Fire Protection Drawings.

1. NPS 2-1/2” and Larger: Standard weight (Schedule 10) steel pipe with roll-grooved ends;

steel, grooved-end fittings; and grooved couplings.

2. NPS 2” and Smaller: Standard-weight steel pipe with threaded ends, cast- or malleable-iron threaded fittings, and threaded joints.

E. Drypipe Sprinkler Branch Piping: See Fire Protection Drawings.

1. NPS 2-1/2” and larger: Standard weight, hot dipped galvanized steel pipe with grooved ends, steel grooved-end fittings and grooved couplings.

2. NPS 2” and smaller: Standard weight, hot dipped galvanized, steel pipe with threaded ends, cast or malleable iron, threaded fittings and threaded joints.

3.3 VALVE APPLICATIONS

A. Drawings indicate valve types to be used. Where specific valve types are not indicated, the following requirements apply:

1. Fire-Protection-Service Valves: UL listed and approved for applications where required by

NFPA#13.

Shutoff Duty: Use gate and/or butterfly valves.

2. General-Duty Valves: For applications where UL-listed and approved valves are not required by NFPA #13.

Shutoff Duty: Use gate, ball, or butterfly valves.

3.4 JOINT CONSTRUCTION

A. Refer to Division 22 Section "Basic Mechanical Materials and Methods" for basic piping joint construction. Apply joint compound or tape to male threads only.

B. Steel-Piping, Grooved Joints: Use Schedule 40 steel pipe with cut or roll-grooved ends and

Schedule 30 or thinner steel pipe with only roll-grooved ends; steel, grooved-end fittings; and steel, keyed couplings. Assemble joints with couplings, gaskets, lubricant, and bolts according to coupling manufacturer's written instructions. Use gaskets listed for dry-pipe service for dry piping.

C. Locking-Lug-Fitting, Twist-Locked Joints: Follow fitting manufacturer's…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .