Asbestos Lead Survey_Bldg-125_20150213.pdf

PDF 1 MB Posted

Attached to
Replace roof of Building 125, Fort Bliss, TX
Solicitation number
W911SG25BA034
Issued by

About this file

This document is a comprehensive lead paint survey report for Building 125 at Fort Bliss, Texas, conducted by ALL Consulting Team and ENCON International, Inc. on January 7-8, 2015. The survey was performed using x-ray fluorescence (XRF) analysis to identify lead-containing paint, with 165 total measurements taken across the building's first floor, exterior, and basement. Of these measurements, 46 tested positive for lead at or above 0.3 mg/cm², indicating the presence of lead-containing paint on various components including wood soffits, concrete risers, metal rails, brick walls, and other surfaces in different conditions ranging from fair to poor.

The report includes detailed findings such as lead concentrations on specific building components, location maps of sample points, and recommendations for handling lead-containing materials. Key recommendations include not disturbing lead paint without proper procedures, using trained personnel with appropriate protective equipment, stabilizing components in poor condition, conducting air monitoring during abatement, and collecting clearance wipe samples. The building, constructed in 1915 and previously used as a military police station, was unoccupied at the time of inspection. The survey was performed to comply with OSHA regulations and protect workers from potential lead exposure during future renovation or maintenance activities.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

February 13, 2015

Mr. Aaron Williams USACE, Tulsa District 1645 South 101st East Avenue Tulsa, OK 74128 Phone: (918) 669-4915

RE: Submittal of Hazardous Building Material Surveys

Contract No. W912BV-10-D-2011, Task Order 0002 Ft. Bliss Bldg. # 125

Dear Mr. Williams, This document summarizes the Asbestos Survey and/or Lead Paint Survey Reports for the subject building. The below listed information was utilized to complete the Scope of Work Tasks:

Bldg. No. 125 POC: Jesse Moncada Phone No: 915-568-1838 Building Square Footage (SF) Reported: 5,029 Technical Summary:

1. LEAD PAINT. A prior (2014) Regulated Materials Inspection Report confirmed the presence of lead in paint. ENCON performed a total of one-hundred sixty-five (165) XRF analyses, which included one-hundred fifty-one (151) building component measurements and fourteen (14) calibration checks. Forty-six

(46) of the building readings tested positive for lead paint. Refer to the attachments for more details.

2. ASBESTOS. An Asbestos Survey was not performed under this contract. Per Ft. Bliss, prior Asbestos Reports had been performed by others. The prior 2014 Regulated Materials Inspection Report indicated that seventeen (17) building materials were sampled and two (2) contained asbestos. The prior 1990 Asbestos Report stated that seventeen (17) suspect materials were sampled and five (5) contained asbestos.

Contact Ft. Bliss, DPW regarding the current asbestos status and the prior Asbestos related Reports (which were not performed per current TDSHS standards).

SUMMARY TABLE (with Action Level) Previously Surveyed by others

Were Found

Were Not Found

Actions Required Yes / No

1. Lead Containing Paint Materials (≥0.3 mg/cm2) X X Yes

2. Asbestos Containing Materials (>1 %) X X Yes

Please contact me with any technical questions, or follow-up needs that you may have.

Sincerely, David Epperly, Ph.D., P.E.

Project Manager – ALL Consulting CC: Jesse Moncada (Ft Bliss DPW) Barry Vercoe (CESFW-PEC-TM)

ATTACHMENTS

1. Lead Paint Survey Report

2. Prior (2014) Regulated Materials Inspection Report

3. Prior (1990) Asbestos Survey Report

ATTACHMENT 1

Lead Paint Survey Report

COMPREHENSIVE LEAD PAINT SURVEY

BUILDING 125

FORT BLISS, TEXAS 79916

Prepared for:

U.S. Army Corps of Engineers

Tulsa District

Prepared by:

ALL CONSULTING TEAM

ENCON International, Inc.

7307 Remcon Circle, #103

El Paso, TX 79912 and

ALL Consulting, LLC 1718 S. Cheyenne Ave.

Tulsa, OK 74119

Inspection Start Date:

January 07, 2015

LEAD PAINT SURVEY REPORT

Ft. Bliss, Texas ─ Building 125

PURPOSE

The ALL Consulting Team was contracted by the U.S. Army Corps of Engineers (USACE), Tulsa District, to perform comprehensive Hazardous Building Materials Surveys to identify the presence of any asbestos or lead paint at a number of facilities at Ft. Bliss, Texas. This project also included the development and population of a database to store the survey reports for access by the Ft. Bliss Directorate of Public Works, and others. The facilities that are included within this contract scope of work includes buildings within the New Mexico installations of McGregor

Range and Dona Ana Range, in addition to the Ft. Bliss facilities in Texas.

BACKGROUND

Ft. Bliss has a large number of buildings constructed before 1990 when the use of asbestos and lead paint was prevalent in the construction of buildings. Because the presence of these materials still exists in these facilities, Ft. Bliss is required to identify the extent of the lead paint remaining at these buildings, as well as their condition. Lead in paint is a hazard that is regulated by the

Occupational Safety and Health Administration (OSHA) under 29 CFR 1926.62 for worker exposure. In addition to the dangers of occupational exposure to construction and maintenance workers, as well as building occupants, lead particles and lead dust may be inadvertently carried home on clothes and shoes to expose their families. Identifying components containing lead paint will not only protect the workers and their families, but will help to indemnify Ft. Bliss by preemptively identifying the location of these potential hazardous materials.

INTRODUCTION

In accordance with OSHA Lead Regulation 29 CFR 1926.62, and the OSHA Hazard

Communication standard (29 CFR 1910.1200), where lead exists workers must be notified and steps must be taken to protect them from the inherent hazards. By identifying the lead containing components in these facilities, and, when appropriate, removing the hazards or potential hazards, Ft. Bliss avoids the liability of workers becoming exposed. Lead paint was banned for use in residential dwellings starting in January of 1978, but lead paint is still available for non-residential applications.

FACILITY DESCRIPTION

The Facility known as Building 125 was constructed in 1915, and was unoccupied at the time of inspection. Its previous use was listed as “police / military police station.” A description of this facility is presented in the following table:

BUILDING 125

BUILDING ITEMS DESCRIPTION

Area of building 5029 square feet Date of Construction 1915 Number of floors One (1) floor with basement Exterior wall materials Brick Roof type Flat Roof material Undetermined Interior walls Plaster, brick, concrete, wood and drywall Interior floors Concrete Interior floor coverings Vinyl Floor tile; basement none Ceilings Plaster, concrete, wood, and drywall Notes:

UNIQUE PAINTING HISTORY

Lead can be found in paint, varnish, shellac, and stain, so any coated surface other than a factory coating is suspect for lead paint. In the first sentence of this section. A Lead Paint Survey is based upon coated components which are grouped into similar components with a similar

(unique) painting history. This would include components with the same substrate, built or installed at the same time, with a common painting history. Items such as window components

(sash and mullions), window frame (trim, header, sill, and apron), doors, and door frame materials, should be considered to have a possible separate painting history, and could have had different coatings applied throughout the years.

REGULATORY STANDARDS

Lead-based paint in residential structures, or Child Occupied Facilities (day care facilities, etc.), is regulated by the U.S. Department of Housing and Urban Development (HUD) under 24 CFR

35, and also by the U.S. Environmental Protection Agency (USEPA) under 40 CFR 745. Only a few of these types of facilities have been identified in the buildings included in this contract. For all facilities included in this category, both HUD and EPA regulations will apply. All other buildings identified in this project would be regulated under the OSHA standards pertaining to worker protection from hazards (29 CFR 1926.62).

Sampling protocols have already been thoroughly established by the HUD and the EPA for residential housing units. For non-residential structures, there is no specified lead paint sampling protocol, but HUD / EPA protocols were generally followed. These comprehensive lead paint surveys include thorough inspections to identify all lead painted components.

SAMPLING METHODOLOGY

The building materials survey tasks were performed in accordance with the Final Hazardous

Building Materials Surveys, Sampling Plan, Fort Bliss, Texas, December 2014, prepared by ALL

Consulting and ENCON International, Inc. A visual inspection of the Facility was conducted to develop a sampling strategy. This included identifying component groups with similar painting histories. Each component group was sampled throughout the facility to establish whether or not the building contained lead at the prescribed action level for this project, at the time of the survey.

This Lead Paint Inspection was performed on January 07, 2015, and January 08, 2015, using an x-ray fluorescence (XRF) analyzer, to identify if any lead amounts in the paint were at or above

0.3 mg/cm2. A total of one-hundred and sixty-five (165) XRF analyses were performed, which included one-hundred and fifty-one (151) building component measurements and fourteen

(14) calibration checks. Drawings that illustrate the locations of all building measurements have been provided in Appendix A of this Report.

XRF RESULTS

The XRF analyzer indicated that lead-containing paint was identified in the following building component types. The table also provides additional details regarding the location, color, condition, and substrate of these components.

COMPONENT SUBSTRATE CONDITION COLOR

OUTSIDE

SOFFIT WOOD FAIR BROWN

RISER CONCRETE POOR YELLOW

RAIL METAL POOR BLACK

EXT SILL CONCRETE POOR WHITE

PORCH

COLUMN BRICK FAIR RED

WALL BRICK FAIR RED

EXT SILL CONCRETE FAIR WHITE

FLOOR CONCRETE FAIR GREY

CEILING WOOD FAIR BROWN

DOOR

CASING WOOD FAIR BROWN

CURB CONCRETE POOR YELLOW

WALL BRICK POOR RED

EXT SILL CONCRETE POOR WHITE

WALL CONCRETE POOR GREEN

WALL CONCRETE POOR RED

AC STAND METAL POOR BROWN

PIPE METAL POOR BROWN

INSIDE

CEILING PLASTER FAIR WHITE

WALL PLASTER FAIR TAN

WALL WOOD FAIR TAN

MULLION WOOD FAIR BEIGE

WINDOW WOOD FAIR BEIGE

WINDOW WOOD FAIR TAN

WALL BRICK POOR WHITE

CEILING DRYWALL POOR WHITE

BASEMENT

WALL CONCRETE POOR YELLOW

WALL BRICK FAIR GREEN

CEILING WOOD FAIR TAN

FLOOR CONCRETE POOR GREY

WINDOW BRICK POOR TAN

HEATER METAL POOR YELLOW

BASEBOARD WOOD POOR YELLOW

WALL BRICK POOR TAN

CEILING CONCRETE POOR TAN

A total of forty-six (46) of the building measurements tested positive, which indicated the presence of lead at or above 0.3 mg/cm2. The complete XRF lead paint data have been provided in Appendix B of this Report. In this Report some of the XRF lead paint results indicated “<

LOD” (less than Limits of Detection). This reading indicates the concentration at which the instrument can determine whether an element was present or not; that is, the point at which the instrument can distinguish a measurement from the background levels. The LOD is not a fixed number, but is affected by the matrix (substrate) of the component and other factors such as temperature, etc. In addition, a result reading of “null” indicates that an inconclusive measurement was obtained, and was therefore repeated.

QUALIFICATIONS

This Comprehensive Lead Paint Survey was performed by a Texas Department of State Health

Services (DSHS) and New Mexico (USEPA) Licensed Lead Paint Inspector. This individual has received training under the HUD / EPA training criteria for the required Lead Paint Inspector and/or Risk Assessor courses and has received the refresher training within the prescribed period for each jurisdiction. Company and individual licenses and credentials have been provided and are available for review in the project sampling plan documents, which have been submitted to the USACE.

LIMITATIONS

The overall purpose of this Comprehensive Lead Paint Survey was to identify if lead-containing components were present, within the qualifications and limitations summarized below. Reliance on this Report is specifically limited to gathering initial information regarding the presence of lead in paint. Any time that lead-based paint may be identified during the performance of a lead inspection, the owner of the building is responsible to the occupants and to the public to properly manage these materials, per Local, State and Federal regulations. Prior to the abatement or removal of any lead containing materials, a Lead Project Design should be properly performed, by a qualified Lead Firm, to 1) ensure that materials will be properly managed, and 2) to prepare a more accurate estimate of actual materials to be addressed. This Survey Report was specifically prepared for ALL Consulting’s Client (USACE and Ft. Bliss), and the extent of liability incurred, is limited to the amount of the Report Fee paid by its Client. The USACE agrees that the ALL Consulting Team cannot be held responsible for any liability based on reliance of this Report by any third party.

CONCLUSIONS

1. Specific Conclusions. Lead-containing paint was found on components inside and/or outside of this building.

• Lead paint should not be disturbed without proper procedures in place. Should the lead paint need to be disturbed, personnel should be evacuated in advance, and only properly trained persons with adequate personal protective equipment (PPE) should be allowed to disturb the lead paint material.

• Lead painted components in poor condition should be stabilized with interim controls or abatement procedures by properly trained personnel.

• Lead Hazard air monitoring should be performed during abatement activities.

• Following abatement activities, clearance wipe samples should be collected and sent to an approved lead laboratory for analysis.

• The OSHA Hazard Communication Standard and the Lead Paint Standard both require anyone working in such areas to be informed of lead paint hazards and methods to avoid the hazards.

2. General Conclusions. Proper notification should be made to the appropriate authorities prior to disturbance of any lead-containing materials, including abatement activity, renovations, or operations and maintenance (O&M) activities, or demolition of any facilities or public buildings.

Other personnel working in the area must be alerted by signage and the appropriate regulated area designations. OSHA specifies worker protection and engineering controls, as well as work practices to ensure the safety of workers and anyone who will be in the area after the conclusion of the work.

Contact the personnel listed below with any clarifications that may be needed.

Inspected by: Reviewed by: Approved by:

Tim Jones, RPIH Alex Woelper, P.E., RPIH David Epperly, Ph.D., P.E.

Lead Inspector Environmental Consultant Project Manager License # 2070306

APPENDICES:

A. Lead Paint Sample Location Drawing(s) B. XRF Lead Paint Data

APPENDIX A

Lead Paint Sample Location Drawing(s)

Project: # 139-14

Hazardous Materials Surveys

Draw by: JC Location:

Building # 125 Fort Bliss, TX 7307 Remcon Cir, Ste 103

El Paso, Texas, 79912 915.833.3740

Sheet

ENV-1

Date:

01-13-2014

ENCON INTERNATIONAL, INC

NOT TO SCALE

LEAD PAINT Sample Location Drawing - Building # 125

Lead Sample Locations

Positive Lead Sample Locations##

1st Floor

77 71 72 74

66 67 68 69

75 76

94 96

105 107 106 108

97 98 99 100

110 111

N

Hazardous Materials Surveys

Draw by: JC Location:

Building # 125 Fort Bliss, TX 7307 Remcon Cir, Ste 103

El Paso, Texas, 79912 915.833.3740

Sheet

ENV-2

Date:

01-13-2014

ENCON INTERNATIONAL, INC

NOT TO SCALE

LEAD PAINT Sample Location Drawing - Building # 125

Lead Sample Locations

Positive Lead Sample Locations##

1st Floor Exterior

N

39 41

36 33 29

35 34 37 30 27

24,25,26 23,22

50,49,48 47 51 54

52,53

10,11, 12 16 13 14

6 7,8,9

Hazardous Materials Surveys

Draw by: JC Location:

Building # 125 Fort Bliss, TX 7307 Remcon Cir, Ste 103

El Paso, Texas, 79912 915.833.3740

Sheet

ENV-3

3 of3

Date:

01-06-2014

ENCON INTERNATIONAL, INC

NOT TO SCALE

LEAD PAINT Sample Location Drawing - Building # 125

Lead Sample Locations

Positive Lead Sample Locations##

Basement

157, 158

160 161

129, 130

153 155 156 150, 151

136, 137

140, 141

144 145

N

APPENDIX B

XRF Lead Paint Data

Fort Bliss, Texas XRF Lead Paint Data Bldg. 125

No. Type Component Substrate Condition Color Room Results Action Level

PbC

1 SHUTTER_CAL 7.81

2 PAINT CALIBRATE N/A 0.3 1

3 PAINT CALIBRATE N/A 0.3 1

4 PAINT CALIBRATE N/A 0.3 1.1

5 PAINT SOFFIT WOOD FAIR BROWN OUTSIDE Positive 0.3 11.6 6 PAINT SOFFIT WOOD FAIR BROWN OUTSIDE Positive 0.3 14.5 7 PAINT DOOR WOOD FAIR BROWN OUTSIDE Negative 0.3 < LOD 8 PAINT DOOR CASING WOOD FAIR BROWN OUTSIDE Negative 0.3 < LOD 9 PAINT THRESHOD WOOD FAIR BROWN OUTSIDE Negative 0.3 < LOD

10 PAINT FLOOR CONCRETE POOR GREY OUTSIDE Negative 0.3 < LOD 11 PAINT FLOOR CONCRETE POOR GREY OUTSIDE Negative 0.3 < LOD 12 PAINT RISER CONCRETE POOR YELLOW OUTSIDE Positive 0.3 6.8 13 PAINT RAIL METAL POOR BLACK OUTSIDE Positive 0.3 1.2 14 PAINT RAIL METAL POOR BLACK OUTSIDE Positive 0.3 2.2 15 PAINT WINDOW CASING WOOD POOR BROWN OUTSIDE Negative 0.3 < LOD 16 PAINT EXT SILL CONCRETE POOR WHITE OUTSIDE Positive 0.3 2.6 17 PAINT RAIL METAL POOR RAIL OUTSIDE Negative 0.3 < LOD 18 PAINT RAIL METAL POOR RAIL PORCH Negative 0.3 < LOD 19 PAINT COLUMN BRICK FAIR RED PORCH Positive 0.3 10.1 20 PAINT COLUMN BRICK FAIR RED PORCH Positive 0.3 3.3 21 PAINT WALL BRICK FAIR RED PORCH Positive 0.3 12.3 22 PAINT DOOR CASING METAL FAIR BROWN PORCH Negative 0.3 < LOD 23 PAINT DOOR WOOD FAIR BROWN PORCH Null 0.3 0.21 24 PAINT DOOR WOOD FAIR BROWN PORCH Negative 0.3 < LOD 25 PAINT DOOR CASING WOOD FAIR BROWN PORCH Negative 0.3 < LOD 26 PAINT GRILL WOOD FAIR BROWN PORCH Negative 0.3 < LOD 27 PAINT GRILL WOOD FAIR BROWN PORCH Negative 0.3 < LOD 28 PAINT EXT SILL CONCRETE FAIR WHITE PORCH Positive 0.3 1.4 29 PAINT EXT SILL CONCRETE FAIR WHITE PORCH Positive 0.3 9 30 PAINT FLOOR CONCRETE FAIR GREY PORCH Negative 0.3 < LOD 31 PAINT FLOOR CONCRETE FAIR GREY PORCH Positive 0.3 3.3 32 PAINT CEILING WOOD FAIR BROWN PORCH Positive 0.3 7

1/7/2015 ALL CONSULTING TEAM

Action Level

PbC

33 PAINT CEILING WOOD FAIR BROWN PORCH Positive 0.3 8.7 34 PAINT DOOR WOOD FAIR BROWN PORCH Negative 0.3 < LOD 35 PAINT DOOR WOOD FAIR BROWN PORCH Negative 0.3 < LOD 36 PAINT DOOR CASING WOOD FAIR BROWN PORCH Positive 0.3 0.7 37 PAINT DOOR CASING WOOD FAIR BROWN PORCH Negative 0.3 < LOD 38 PAINT CURB CONCRETE POOR YELLOW PORCH Negative 0.3 < LOD 39 PAINT CURB CONCRETE POOR YELLOW PORCH Positive 0.3 7.7 40 PAINT WALL BRICK POOR RED PORCH Null 0.3 0.25 41 PAINT WALL BRICK POOR RED PORCH Positive 0.3 9.5 42 PAINT EXT SILL CONCRETE POOR WHITE PORCH Positive 0.3 1.2 43 PAINT AC STAND CONCRETE POOR BROWN PORCH Negative 0.3 < LOD 44 PAINT AC STAND CONCRETE POOR BROWN PORCH Negative 0.3 < LOD 45 PAINT WALL CONCRETE POOR GREEN PORCH Positive 0.3 1.1 46 PAINT WALL CONCRETE POOR RED PORCH Positive 0.3 1.1 47 PAINT EXT SILL CONCRETE POOR WHITE PORCH Positive 0.3 1.6 48 PAINT WINDOW WOOD POOR BROWN PORCH Negative 0.3 < LOD 49 PAINT WINDOW SILL WOOD POOR BROWN PORCH Null 0.3 < LOD 50 PAINT WINDOW SILL WOOD POOR BROWN PORCH Negative 0.3 0.15 51 PAINT ELEC BOX METAL POOR BROWN PORCH Negative 0.3 < LOD 52 PAINT AC STAND METAL POOR BROWN PORCH Null 0.3 0.24 53 PAINT AC STAND METAL POOR BROWN PORCH Negative 0.3 < LOD 54 PAINT DUCT METAL POOR BROWN PORCH Negative 0.3 < LOD 55 PAINT DUCT METAL POOR BROWN PORCH Negative 0.3 < LOD 56 PAINT AC STAND METAL POOR BROWN PORCH Positive 0.3 9.9 57 PAINT PIPE METAL POOR BROWN PORCH Positive 0.3 0.9 58 PAINT WALL BRICK POOR BROWN PORCH Null 0.3 0.05

59 PAINT CALIBRATE N/A 0.3 1

60 PAINT CALIBRATE N/A 0.3 1.1

61 PAINT CALIBRATE N/A 0.3 1.1

62 SHUTTER_CAL 8.66

63 PAINT CALIBRATE N/A 0.3 0.9

64 PAINT CALIBRATE N/A 0.3 1

Action Level

PbC

65 PAINT CALIBRATE N/A 0.3 1

66 PAINT CEILING PLASTER FAIR WHITE INSIDE Null 0.3 < LOD 67 PAINT CEILING PLASTER FAIR WHITE INSIDE Positive 0.3 1 68 PAINT CROWN MOLDING WOOD FAIR TAN INSIDE Negative 0.3 < LOD 69 PAINT TRIM WOOD FAIR TAN INSIDE Negative 0.3 < LOD 70 PAINT WALL DRYWALL FAIR TAN INSIDE Negative 0.3 < LOD 71 PAINT WALL DRYWALL FAIR TAN INSIDE Negative 0.3 < LOD 72 PAINT BASEBOARD WOOD FAIR BEIGE INSIDE Negative 0.3 < LOD 73 PAINT DOOR CASING WOOD FAIR BEIGE INSIDE Negative 0.3 < LOD 74 PAINT DOOR WOOD FAIR BEIGE INSIDE Negative 0.3 < LOD 75 PAINT WINDOW WOOD FAIR BEIGE INSIDE Negative 0.3 < LOD 76 PAINT SILL WOOD FAIR BROWN INSIDE Negative 0.3 < LOD 77 PAINT APRON WOOD FAIR BROWN INSIDE Negative 0.3 < LOD 78 PAINT HEATER METAL FAIR GREY INSIDE Null 0.3 < LOD 79 PAINT WALL PLASTER FAIR TAN INSIDE Positive 0.3 8.3 80 PAINT DOOR CASING WOOD FAIR BEIGE INSIDE Negative 0.3 < LOD 81 PAINT DOOR CASING WOOD FAIR BEIGE INSIDE Negative 0.3 < LOD 82 PAINT DOOR WOOD FAIR BEIGE INSIDE Negative 0.3 < LOD 83 PAINT BASEBOARD WOOD FAIR BEIGE INSIDE Negative 0.3 < LOD 84 PAINT CEILING DRYWALL FAIR WHITE INSIDE Null 0.3 < LOD 85 PAINT CEILING DRYWALL FAIR WHITE INSIDE Negative 0.3 < LOD 86 PAINT DOOR DRYWALL FAIR TAN INSIDE Negative 0.3 < LOD 87 PAINT CEILING DRYWALL FAIR WHITE INSIDE Null 0.3 0.3 88 PAINT CEILING DRYWALL FAIR WHITE INSIDE Null 0.3 0.4 89 PAINT WALL PLASTER FAIR TAN INSIDE Positive 0.3 7 90 PAINT WALL DRYWALL FAIR TAN INSIDE Negative 0.3 < LOD 91 PAINT SCUTTLE WOOD FAIR WHITE INSIDE Negative 0.3 < LOD 92 PAINT DOOR FRAME WOOD FAIR WHITE INSIDE Null 0.3 < LOD 93 PAINT DOOR FRAME WOOD FAIR WHITE INSIDE Null 0.3 0.4 94 PAINT DOOR WOOD FAIR TAN INSIDE Negative 0.3 < LOD 95 PAINT DOOR CASING WOOD FAIR TAN INSIDE Negative 0.3 < LOD 96 PAINT WALL WOOD FAIR TAN INSIDE Positive 0.3 3.6

Action Level

PbC

97 PAINT CEILING DRYWALL FAIR WHITE INSIDE Negative 0.3 < LOD 98 PAINT MULLION WOOD FAIR BEIGE INSIDE Positive 0.3 0.8 99 PAINT WINDOW WOOD FAIR BEIGE INSIDE Positive 0.3 17.7

100 PAINT WINDOW WOOD FAIR BEIGE INSIDE Positive 0.3 0.7 101 PAINT WALL DRYWALL FAIR TAN INSIDE Negative 0.3 < LOD 102 PAINT ELEC BOX DRYWALL FAIR TAN INSIDE Negative 0.3 < LOD 103 PAINT WINDOW WOOD FAIR TAN INSIDE Positive 0.3 11.8 104 PAINT DOOR CASING WOOD FAIR TAN INSIDE Negative 0.3 < LOD 105 PAINT COLUMN WOOD FAIR TAN INSIDE Null 0.3 < LOD 106 PAINT COLUMN WOOD FAIR TAN INSIDE Null 0.3 < LOD 107 PAINT COLUMN WOOD FAIR TAN INSIDE Null 0.3 < LOD 108 PAINT COLUMN WOOD FAIR TAN INSIDE Negative 0.3 < LOD 109 PAINT DOOR WOOD FAIR TAN INSIDE Negative 0.3 < LOD 110 PAINT DOOR WOOD FAIR TAN INSIDE Negative 0.3 < LOD 111 PAINT DOOR CASING WOOD FAIR TAN INSIDE Negative 0.3 < LOD 112 PAINT WALL BRICK POOR WHITE INSIDE Positive 0.3 7.2 113 PAINT CEILING DRYWALL POOR WHITE INSIDE Positive 0.3 0.5 114 PAINT BASEBOARD WOOD POOR BEIGE INSIDE Negative 0.3 < LOD 115 PAINT WINDOW CASING WOOD FAIR TAN INSIDE Null 0.3 < LOD 116 PAINT WALL PLASTER FAIR TAN INSIDE Positive 0.3 10.3 117 PAINT WALL PLASTER FAIR TAN INSIDE Positive 0.3 9.4 118 PAINT GRILL PLASTER FAIR TAN INSIDE Negative 0.3 < LOD 119 PAINT DOOR WOOD FAIR TAN INSIDE Negative 0.3 < LOD 120 PAINT WINDOW WOOD FAIR TAN INSIDE Positive 0.3 12 121 PAINT DOOR CASING WOOD FAIR TAN INSIDE Negative 0.3 < LOD 122 PAINT DOOR WOOD FAIR BROWN INSIDE Negative 0.3 < LOD 123 PAINT DOOR WOOD FAIR BROWN INSIDE Negative 0.3 < LOD 124 PAINT DOOR WOOD FAIR BROWN INSIDE Negative 0.3 < LOD 125 PAINT WALL DRYWALL FAIR TAN INSIDE Negative 0.3 < LOD 126 PAINT WALL DRYWALL FAIR TAN INSIDE Negative 0.3 < LOD 127 PAINT WALL PLASTER FAIR TAN INSIDE Positive 0.3 5.2 128 PAINT TREAD CONCRETE POOR TAN STAIR Null 0.3 < LOD

Action Level

PbC

129 PAINT WALL BRICK POOR RED STAIR Null 0.3 < LOD 130 PAINT WALL BRICK POOR RED STAIR Null 0.3 < LOD 131 PAINT WALL CONCRETE POOR YELLOW BASEMENT Positive 0.3 1.9 132 PAINT DOOR METAL POOR YELLOW BASEMENT Negative 0.3 < LOD 133 PAINT DOOR WOOD POOR BROWN BASEMENT Negative 0.3 < LOD 134 PAINT CEILING CONCRETE FAIR BROWN BASEMENT Null 0.3 < LOD 135 PAINT CEILING CONCRETE FAIR BROWN BASEMENT Null 0.3 0.04 136 PAINT WALL CONCRETE FAIR BROWN BASEMENT Negative 0.3 0.07 137 PAINT SHELF WOOD FAIR BROWN BASEMENT Negative 0.3 0.23 138 PAINT DOOR CASING WOOD FAIR BROWN BASEMENT Negative 0.3 0.12 139 PAINT WALL DRYWALL FAIR TAN BASEMENT Negative 0.3 < LOD 140 PAINT FIREPLACE WOOD FAIR BROWN BASEMENT Negative 0.3 < LOD 141 PAINT FIREPLACE WOOD FAIR TAN BASEMENT Negative 0.3 < LOD 142 PAINT WALL BRICK FAIR GREEN BASEMENT Positive 0.3 6.5 143 PAINT WINDOW WOOD FAIR BROWN BASEMENT Negative 0.3 < LOD 144 PAINT CEILING WOOD FAIR TAN BASEMENT Positive 0.3 3.4 145 PAINT COLUMN WOOD FAIR TAN BASEMENT Negative 0.3 < LOD 146 PAINT WALL WOOD FAIR WHITE BASEMENT Negative 0.3 < LOD 147 PAINT FLOOR CONCRETE POOR GREY BASEMENT Null 0.3 0.25 148 PAINT FLOOR CONCRETE POOR GREY BASEMENT Positive 0.3 0.4 149 PAINT DOOR CASING WOOD POOR YELLOW BASEMENT Negative 0.3 < LOD 150 PAINT DOOR WOOD POOR YELLOW BASEMENT Negative 0.3 < LOD 151 PAINT DOOR WOOD POOR WHITE BASEMENT Negative 0.3 < LOD 152 PAINT PIPE METAL POOR YELLOW BASEMENT Negative 0.3 < LOD 153 PAINT WINDOW BRICK POOR TAN BASEMENT Positive 0.3 5.4 154 PAINT COLUMN WOOD POOR YELLOW BASEMENT Negative 0.3 < LOD 155 PAINT HEATER METAL POOR YELLOW BASEMENT Positive 0.3 1.1 156 PAINT BASEBOARD WOOD POOR YELLOW BASEMENT Positive 0.3 1.1 157 PAINT DOOR WOOD POOR GREEN BASEMENT Negative 0.3 < LOD 158 PAINT DOOR CASING WOOD POOR BLACK BASEMENT Negative 0.3 < LOD 159 PAINT PANEL METAL POOR BLACK BASEMENT Negative 0.3 < LOD 160 PAINT WALL BRICK POOR TAN BASEMENT Positive 0.3 1.8

Action Level

PbC

161 PAINT WALL BRICK POOR RED BASEMENT Negative 0.3 0.12 162 PAINT CEILING CONCRETE POOR TAN BASEMENT Positive 0.3 3.9

163 PAINT CALIBRATE N/A 0.3 1

164 PAINT CALIBRATE N/A 0.3 1.2

165 PAINT CALIBRATE N/A 0.3 1

1/7/2015 ALL CONSULTING TEAM

LOD - Limit of Detection

Null - indicates that an inconclusive measurement was obtained, and was therefore repeated

ATTACHMENT 2

Prior (2014) Regulated Materials Inspection Report

Regulated Materials Inspection Report Building 125

Fort Bliss, Texas August 2014

Lead-based paint (LBP) and asbestos containing material (ACM) inspections at Building 125 were conducted on 12 August 2014 by Ms. Suzanne Simpson and Mr.

Barry Vercoe of the U.S. Army Corps of Engineers, Fort Worth District, Regional Planning & Environmental Center (USAED, CESWF-PEC). The purpose of the inspections was to identify regulated materials at this building including LBP and ACM, which may require abatement prior to proposed renovation.

The LBP inspection included screening of painted surfaces to indicate the presence of lead in paint with an x-ray fluorescence (XRF) analyzer, model LPA-1 manufactured by RMD Instruments, LLC, Watertown, Massachusetts. Mr. Vercoe is certified through manufacturer training to operate this model of analyzer, and is also certified by the Texas Department of State Health Services (DSHS) as a Lead Inspector, License Number 2060570, and Lead Risk Assessor, License Number 2070346, both with expiration date 25 April 2016. For the purpose of this inspection, the presence of LBP was confirmed on surfaces where XRF readings were equal to or greater than the HUD and U.S. Environmental Protection Agency (EPA) regulatory threshold of 1.0 mg/cm2, and the presence of lead containing paint (LCP) was indicated on surfaces where XRF readings were 0.2 mg/cm2 or greater based on data in the Performance Characteristic Sheet (PCS) for this XRF model provided by HUD. Worker protection measures are required under Occupational Safety and Health Administration (OSHA) regulations listed in 29 CFR 1926.62 where materials containing any lead, including LBP or LCP, will be disturbed. XRF screening results are summarized in Table 1 of this report.

The presence of LBP was confirmed on a brick plaster wall outside room of room 7 (3.1 mg/cm2), wood window in restroom 4 (>9.9mg/cm2), exterior wood ceiling on the porch (6.8 mg/cm2), on the exterior porch brick walls (5.6 mg/cm2) and texture on the brick wall in the basement (1.0 mg/cm2). The presence of LCP at concentrations below the regulatory threshold for LBP was confirmed on a gypsum ceiling board outside of room 7 (0.3 mg/cm2) and a gypsum wall board in restroom 5 (0.3 mg/cm2).

The ACM inspection included collection of bulk samples of suspect material for laboratory analyses by polarized light microscopy (PLM). Ms. Simpson and Mr. Vercoe are certified as an Asbestos Inspectors by EPA approved training provided through GEBCO Associates, LP, Hurst, Texas, with respective Certificate Numbers 14033 (expiration date 29 January 2015) and 13007 (expiration date 02 January 2015). Samples were analyzed by EMC Labs Inc., Phoenix, Arizona, which is certified by the Texas DSHS for PLM analyses, License Number 300296, expiration date 30 July 2016.

Analytical results are summarized in Table 2 of this report, with the complete laboratory analytical report included as Appendix A. ACM is defined by the EPA to be any material containing greater than 1% asbestos as determined by PLM analysis.

Results reported by the analytical laboratory indicated ACM is present in the following materials: gypsum ceiling panel/joint compound (3% chrysotile), floor tile/black mastic (2% - 8% Chrysotile).

Table 1 Fort Bliss - Building 125

Lead Containing Paint XRF Screening Results

Reading XRF Result XRF Number (mg/cm2) Mode

001 1.0 002 0.9 003 1.0 004 0.0 005 0.0 006 -0.1 016 -0.1 Quick Mode Interior Corridor Wall Gypsum Board White 017 -0.1 Quick Mode Room 13 Door Trim Wood Beige 018 0.1 Quick Mode Room 9 Door Wood Beige 019 3.1 Quick Mode Outside Room 7 Wall Plaster on Brick White 020 >9.9 Quick Mode Restroom 4 Window Wood White 021 0.3 Quick Mode Outside Room 7 Ceiling Gypsum Board White 022 0.3 Quick Mode Restroom 5 Wall Gypsum Board Light Beige 023 -0.2 Quick Mode Room 2 Door Wood Beige 024 0.1 Quick Mode Outside Restroom 4 Baseboard Wood Beige 025 6.8 Quick Mode Exterior Porch Ceiling Wood Brown 026 5.6 Quick Mode Exterior Porch Wall Brick Dark Red 027 1.0 Quick Mode Basement Wall Texture on Brick White

NOTE: Readings in bold indicate the presence of lead containing paint as determined by XRF analysis

Time Corrected

Mode

0.0 mg/cm2

Unpainted Standard

Paint ColorComponentLocation Substrate

Time Corrected

Mode

1.0 mg/cm2

Paint Standard Calibration

Calibration

FORT BLISS BUILDING 125 ACM RESULTS 2014

Description Sample Identification Analytical Results Location Floortile 1-A None Detected Hall Outside of Room 14

1-B None Detected Hall Outside of Room 13 2-B None Detected Room 13

Gypsum Wall Panel 2-C None Detected Outside of Room 8 2-D None Detected Room 14 3-A None Detected Hall

Floor Tile 3-B None Detected Outside of Room 8 3-C None Detected Stairs going into Room 7 4-A None Detected Prisoner Holding Cell

Wall Texture 4-B None Detected Basement 5-A 3% Chrysotile Prisoner Holding Cell

Gypsum Ceiling Panel 5-B None Detected Mens Restroom Floor Tile 6-A None Detected

6-B None Detected Floor Tile 7-A 2% Chrysotile, 8% Chrysotile Basement

2'X2' Drop Tile Panel 8-A None Detected Basement Roofing Shingle 9-A None Detected Off of Porch Over Hang

Appendix A

Asbestos Analytical Reports EMC Labs, Inc.

August 2014

Asbestos Detected

Layer Name / Sample Description

Lab ID Sample Location

Bulk Asbestos Analysis by Polarized Light Microscopy

Non-Asbestos Constituents

Laboratory Report

0144968

NVLAP#101926-0

Client ID

Client:

Address: 819 TAYLOR ST.

FT. WORTH TX 76102

U.S. ARMY CORPS OF ENGINEERS

Date Received: 08/14/2014

08/26/2014Date Analyzed:

444064Job# / P.O. #:

EMC LABS, INC.

Collected: 08/12/2014 EPA Method: Project Name: FT. BLISS BLDG 125 Submitted By: BARRY VERCOEAddress: PO #W9126G-11-A-0002 Collected By:

9830 S. 51st Street, Suite B109, Phoenix, AZ 85044 Phone: 800-362-3373 or 480-940-5294 - Fax: (480) 893-1726

08/26/2014Date Reported:

EPA 600/R-93/116

Asbestos Type

NoLAYER 1 12"x12" Floor Tile, Brown/ Off White

None Detected0144968-001 125-1A Carbonates

Quartz Binder/Filler

100%

Cellulose FiberNoLAYER 2 Mastic, Yellow

None Detected <1%

Carbonates Gypsum

99%

NoLAYER 1 12"x12" Floor Tile, Brown/ Off White

None Detected0144968-002 125-1B Carbonates

Mastic, Yellow

None Detected <1%

Carbonates Gypsum

Cellulose FiberNoLAYER 1 Gypsum Wall Panel, Off White/ Brown

None Detected0144968-003 125-2A

10%

Gypsum

Carbonates

90%

NoLAYER 2 Joint Compound, White

None Detected

Carbonates Mica

Cellulose FiberNoLAYER 3 Tape, Off White

None Detected 95%

Carbonates Gypsum

5%

Cellulose FiberNoLAYER 4 Texture, White/ Off White

None Detected 1%

Carbonates Gypsum

Layer Name / Sample Description

Lab ID Sample Location

Bulk Asbestos Analysis by Polarized Light Microscopy

Non-Asbestos Constituents

Laboratory Report

0144968

NVLAP#101926-0

Client ID

Client:

Address: 819 TAYLOR ST.

FT. WORTH TX 76102

U.S. ARMY CORPS OF ENGINEERS

Date Received: 08/14/2014

08/26/2014Date Analyzed:

444064Job# / P.O. #:

EMC LABS, INC.

Collected: 08/12/2014 EPA Method: Project Name: FT. BLISS BLDG 125 Submitted By: BARRY VERCOEAddress: PO #W9126G-11-A-0002 Collected By:

9830 S. 51st Street, Suite B109, Phoenix, AZ 85044 Phone: 800-362-3373 or 480-940-5294 - Fax: (480) 893-1726

08/26/2014Date Reported:

EPA 600/R-93/116

Asbestos Type

Cellulose FiberNoLAYER 1 Gypsum Wall Panel, Off White/ Brown

None Detected0144968-004 125-2B

10%

Gypsum

NoLAYER 2 Joint Compound, White

None Detected

Carbonates Mica

Tape, Off White

None Detected 95%

Carbonates

Texture, White/ Off White

None Detected 1%

Carbonates Gypsum

Gypsum Wall Panel, Off White/ Brown

None Detected0144968-005 125-2C

10%

Gypsum

Texture, White/ Beige

None Detected <1%

Carbonates Mica

Floor Tile, Brown w/ Specks

None Detected0144968-006 125-3A Carbonates

Mastic, Yellow

None Detected 1%

Carbonates Gypsum

Layer Name / Sample Description

Lab ID Sample Location

Bulk Asbestos Analysis by Polarized Light Microscopy

Non-Asbestos Constituents

Laboratory Report

0144968

NVLAP#101926-0

Client ID

Client:

Address: 819 TAYLOR ST.

FT. WORTH TX 76102

U.S. ARMY CORPS OF ENGINEERS

Date Received: 08/14/2014

08/26/2014Date Analyzed:

444064Job# / P.O. #:

EMC LABS, INC.

Collected: 08/12/2014 EPA Method: Project Name: FT. BLISS BLDG 125 Submitted By: BARRY VERCOEAddress: PO #W9126G-11-A-0002 Collected By:

9830 S. 51st Street, Suite B109, Phoenix, AZ 85044 Phone: 800-362-3373 or 480-940-5294 - Fax: (480) 893-1726

08/26/2014Date Reported:

EPA 600/R-93/116

Asbestos Type

NoLAYER 1 Floor Tile, Brown w/ Specks

None Detected0144968-007 125-3B Carbonates

Mastic, Yellow

None Detected 1%

Carbonates Gypsum

Floor Tile, Brown w/ Specks

None Detected0144968-008 125-3C Carbonates

Synthetic FiberNoLAYER 2 Mastic, Yellow

None Detected <1%

Carbonates Gypsum

Wall Texture, White/ Beige

None Detected0144968-009 125-4A Gypsum

Mica

Tape, Off White

None Detected 95%

Carbonates

Joint Compound, White

None Detected <1%

Gypsum Mica

Layer Name / Sample Description

Lab ID Sample Location

Bulk Asbestos Analysis by Polarized Light Microscopy

Non-Asbestos Constituents

Laboratory Report

0144968

NVLAP#101926-0

Client ID

Client:

Address: 819 TAYLOR ST.

FT. WORTH TX 76102

U.S. ARMY CORPS OF ENGINEERS

Date Received: 08/14/2014

08/26/2014Date Analyzed:

444064Job# / P.O. #:

EMC LABS, INC.

Collected: 08/12/2014 EPA Method: Project Name: FT. BLISS BLDG 125 Submitted By: BARRY VERCOEAddress: PO #W9126G-11-A-0002 Collected By:

9830 S. 51st Street, Suite B109, Phoenix, AZ 85044 Phone: 800-362-3373 or 480-940-5294 - Fax: (480) 893-1726

08/26/2014Date Reported:

EPA 600/R-93/116

Asbestos Type

NoWall Texture, White/ Beige None Detected0144968-010 125-4B Gypsum

Mica

Gypsum Ceiling Panel, Off White/ Brown

None Detected0144968-011 125-5A

10%

Gypsum

Cellulose FiberYesLAYER 2 Joint Compound, White

Chrysotile 3% 2%

Carbonates Mica

95%

Tape, Off White

None Detected 95%

Carbonates

Texture, White/ Off White

None Detected <1%

Carbonates Mica

Layer Name / Sample Description

Lab ID Sample Location

Bulk Asbestos Analysis by Polarized Light Microscopy

Non-Asbestos Constituents

Laboratory Report

0144968

NVLAP#101926-0

Client ID

Client:

Address: 819 TAYLOR ST.

FT. WORTH TX 76102

U.S. ARMY CORPS OF ENGINEERS

Date Received: 08/14/2014

08/26/2014Date Analyzed:

444064Job# / P.O. #:

EMC LABS, INC.

Collected: 08/12/2014 EPA Method: Project Name: FT. BLISS BLDG 125 Submitted By: BARRY VERCOEAddress: PO #W9126G-11-A-0002 Collected By:

9830 S. 51st Street, Suite B109, Phoenix, AZ 85044 Phone: 800-362-3373 or 480-940-5294 - Fax: (480) 893-1726

08/26/2014Date Reported:

EPA 600/R-93/116

Asbestos Type

Cellulose FiberNoLAYER 1 Gypsum Ceiling Panel, Off White/ Brown

None Detected0144968-012 125-5B

10%

Gypsum

Joint Compound, White

Chrysotile 3% 2%

Carbonates Mica

95%

Texture, White/ Off White

None Detected <1%

Carbonates Mica

12"x12" Floor Tile, Dk. Brown/ Gray/ Black

None Detected0144968-013 125-6A Carbonates

Mastic, Yellow

None Detected <1%

Carbonates Gypsum

NoLAYER 3 12"x12" Floor Tile, Off White

None Detected

Carbonates

12"x12" Floor Tile, Dk. Brown/ Gray/ Black

None Detected0144968-014 125-6B Carbonates

Mastic, Yellow

None Detected <1%

Carbonates Gypsum

Layer Name / Sample Description

Lab ID Sample Location

Bulk Asbestos Analysis by Polarized Light Microscopy

Non-Asbestos Constituents

Laboratory Report

0144968

NVLAP#101926-0

Client ID

Client:

Address: 819 TAYLOR ST.

FT. WORTH TX 76102

U.S. ARMY CORPS OF ENGINEERS

Date Received: 08/14/2014

08/26/2014Date Analyzed:

444064Job# / P.O. #:

EMC LABS, INC.

Collected: 08/12/2014 EPA Method: Project Name: FT. BLISS BLDG 125 Submitted By: BARRY VERCOEAddress: PO #W9126G-11-A-0002 Collected By:

9830 S. 51st Street, Suite B109, Phoenix, AZ 85044 Phone: 800-362-3373 or 480-940-5294 - Fax: (480) 893-1726

08/26/2014Date Reported:

EPA 600/R-93/116

Asbestos Type

YesLAYER 1 9"x9" Floor Tile, Lt. Green

Chrysotile0144968-015 125-7A

2%

Carbonates

98%

Mastic, Black

Chrysotile 8% 2%

Carbonates

Cellulose Fiber Mineral Wool

No2x2 Drop Tile Ceilng Panel, White/ Beige

None Detected0144968-016 125-8A

75% 5%

Carbonates Gypsum Perlite

20%

Fibrous GlassNoLAYER 1 Roofing Shingle, Gray/ Off White/ Black

None Detected0144968-017 125-9A

20%

Carbonates Gypsum

80%

Fibrous GlassNoLAYER 2 Tar, Black

None Detected 30%

Carbonates

70%

Distinctly stratified, easily separable layers of samples are analyzed as subsamples of the whole and are reported separately for each discernible layer. All analyses are derived from calibrated visual estimate and measured in area percent unless otherwise noted. The report applies to the standards or procedures identified and to the sample(s) tested. The test results are not necessarily indicated or representative of the qualities of the lot from which the sample was taken or of apparently identical or similar products, nor do they represent an ongoing quality assurance program unless so noted. These reports are for the exclusive use of the addressed client and that they will not be reproduced wholly or in part for advertising or other purposes over our signature or in connection with our name without special written permission. The report shall not be reproduced except in full, without written approval by our laboratory. The samples not destroyed in testing are retained a maximum of thirty days. The laboratory measurement of uncertainty for the test method is approximately less than 1 by area percent.

Accredited by the National Institute of Standards and Technology, Voluntary Laboratory Accreditation Program for selected test method for asbestos. The accreditation or any reports generated by this laboratory in no way constitutes or implies product certification, approval, or endorsement by the National Institute of Standards and Technology. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal Government. Polarized Light Microscopy may not be consistently reliable in detecting asbestos in floor coverings and similar non-friable organically bound materials.

Analyst - Kurt Kettler Signatory - Lab Manager - Ken Scheske

ATTACHMENT 3

Prior (1990) Asbestos Report

File details come from the government source that posted it. Updated .