This document is a comprehensive lead paint survey report for Building 125 at Fort Bliss, Texas, conducted by ALL Consulting Team and ENCON International, Inc. on January 7-8, 2015. The survey was performed using x-ray fluorescence (XRF) analysis to identify lead-containing paint, with 165 total measurements taken across the building's first floor, exterior, and basement. Of these measurements, 46 tested positive for lead at or above 0.3 mg/cm², indicating the presence of lead-containing paint on various components including wood soffits, concrete risers, metal rails, brick walls, and other surfaces in different conditions ranging from fair to poor.
The report includes detailed findings such as lead concentrations on specific building components, location maps of sample points, and recommendations for handling lead-containing materials. Key recommendations include not disturbing lead paint without proper procedures, using trained personnel with appropriate protective equipment, stabilizing components in poor condition, conducting air monitoring during abatement, and collecting clearance wipe samples. The building, constructed in 1915 and previously used as a military police station, was unoccupied at the time of inspection. The survey was performed to comply with OSHA regulations and protect workers from potential lead exposure during future renovation or maintenance activities.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
February 13, 2015
Mr. Aaron Williams USACE, Tulsa District 1645 South 101st East Avenue Tulsa, OK 74128 Phone: (918) 669-4915
RE: Submittal of Hazardous Building Material Surveys
Contract No. W912BV-10-D-2011, Task Order 0002 Ft. Bliss Bldg. # 125
Dear Mr. Williams, This document summarizes the Asbestos Survey and/or Lead Paint Survey Reports for the subject building. The below listed information was utilized to complete the Scope of Work Tasks:
Bldg. No. 125 POC: Jesse Moncada Phone No: 915-568-1838 Building Square Footage (SF) Reported: 5,029 Technical Summary:
1. LEAD PAINT. A prior (2014) Regulated Materials Inspection Report confirmed the presence of lead in paint. ENCON performed a total of one-hundred sixty-five (165) XRF analyses, which included one-hundred fifty-one (151) building component measurements and fourteen (14) calibration checks. Forty-six
(46) of the building readings tested positive for lead paint. Refer to the attachments for more details.
2. ASBESTOS. An Asbestos Survey was not performed under this contract. Per Ft. Bliss, prior Asbestos Reports had been performed by others. The prior 2014 Regulated Materials Inspection Report indicated that seventeen (17) building materials were sampled and two (2) contained asbestos. The prior 1990 Asbestos Report stated that seventeen (17) suspect materials were sampled and five (5) contained asbestos.
Contact Ft. Bliss, DPW regarding the current asbestos status and the prior Asbestos related Reports (which were not performed per current TDSHS standards).
SUMMARY TABLE (with Action Level) Previously Surveyed by others
Were Found
Were Not Found
Actions Required Yes / No
1. Lead Containing Paint Materials (≥0.3 mg/cm2) X X Yes
2. Asbestos Containing Materials (>1 %) X X Yes
Please contact me with any technical questions, or follow-up needs that you may have.
Sincerely, David Epperly, Ph.D., P.E.
Project Manager – ALL Consulting CC: Jesse Moncada (Ft Bliss DPW) Barry Vercoe (CESFW-PEC-TM)
ATTACHMENTS
1. Lead Paint Survey Report
2. Prior (2014) Regulated Materials Inspection Report
3. Prior (1990) Asbestos Survey Report
ATTACHMENT 1
Lead Paint Survey Report
COMPREHENSIVE LEAD PAINT SURVEY
BUILDING 125
FORT BLISS, TEXAS 79916
Prepared for:
U.S. Army Corps of Engineers
Tulsa District
Prepared by:
ALL CONSULTING TEAM
ENCON International, Inc.
7307 Remcon Circle, #103
El Paso, TX 79912 and
ALL Consulting, LLC 1718 S. Cheyenne Ave.
Tulsa, OK 74119
Inspection Start Date:
January 07, 2015
LEAD PAINT SURVEY REPORT
Ft. Bliss, Texas ─ Building 125
PURPOSE
The ALL Consulting Team was contracted by the U.S. Army Corps of Engineers (USACE), Tulsa District, to perform comprehensive Hazardous Building Materials Surveys to identify the presence of any asbestos or lead paint at a number of facilities at Ft. Bliss, Texas. This project also included the development and population of a database to store the survey reports for access by the Ft. Bliss Directorate of Public Works, and others. The facilities that are included within this contract scope of work includes buildings within the New Mexico installations of McGregor
Range and Dona Ana Range, in addition to the Ft. Bliss facilities in Texas.
BACKGROUND
Ft. Bliss has a large number of buildings constructed before 1990 when the use of asbestos and lead paint was prevalent in the construction of buildings. Because the presence of these materials still exists in these facilities, Ft. Bliss is required to identify the extent of the lead paint remaining at these buildings, as well as their condition. Lead in paint is a hazard that is regulated by the
Occupational Safety and Health Administration (OSHA) under 29 CFR 1926.62 for worker exposure. In addition to the dangers of occupational exposure to construction and maintenance workers, as well as building occupants, lead particles and lead dust may be inadvertently carried home on clothes and shoes to expose their families. Identifying components containing lead paint will not only protect the workers and their families, but will help to indemnify Ft. Bliss by preemptively identifying the location of these potential hazardous materials.
INTRODUCTION
In accordance with OSHA Lead Regulation 29 CFR 1926.62, and the OSHA Hazard
Communication standard (29 CFR 1910.1200), where lead exists workers must be notified and steps must be taken to protect them from the inherent hazards. By identifying the lead containing components in these facilities, and, when appropriate, removing the hazards or potential hazards, Ft. Bliss avoids the liability of workers becoming exposed. Lead paint was banned for use in residential dwellings starting in January of 1978, but lead paint is still available for non-residential applications.
FACILITY DESCRIPTION
The Facility known as Building 125 was constructed in 1915, and was unoccupied at the time of inspection. Its previous use was listed as “police / military police station.” A description of this facility is presented in the following table:
BUILDING 125
BUILDING ITEMS DESCRIPTION
Area of building 5029 square feet Date of Construction 1915 Number of floors One (1) floor with basement Exterior wall materials Brick Roof type Flat Roof material Undetermined Interior walls Plaster, brick, concrete, wood and drywall Interior floors Concrete Interior floor coverings Vinyl Floor tile; basement none Ceilings Plaster, concrete, wood, and drywall Notes:
UNIQUE PAINTING HISTORY
Lead can be found in paint, varnish, shellac, and stain, so any coated surface other than a factory coating is suspect for lead paint. In the first sentence of this section. A Lead Paint Survey is based upon coated components which are grouped into similar components with a similar
(unique) painting history. This would include components with the same substrate, built or installed at the same time, with a common painting history. Items such as window components
(sash and mullions), window frame (trim, header, sill, and apron), doors, and door frame materials, should be considered to have a possible separate painting history, and could have had different coatings applied throughout the years.
REGULATORY STANDARDS
Lead-based paint in residential structures, or Child Occupied Facilities (day care facilities, etc.), is regulated by the U.S. Department of Housing and Urban Development (HUD) under 24 CFR
35, and also by the U.S. Environmental Protection Agency (USEPA) under 40 CFR 745. Only a few of these types of facilities have been identified in the buildings included in this contract. For all facilities included in this category, both HUD and EPA regulations will apply. All other buildings identified in this project would be regulated under the OSHA standards pertaining to worker protection from hazards (29 CFR 1926.62).
Sampling protocols have already been thoroughly established by the HUD and the EPA for residential housing units. For non-residential structures, there is no specified lead paint sampling protocol, but HUD / EPA protocols were generally followed. These comprehensive lead paint surveys include thorough inspections to identify all lead painted components.
SAMPLING METHODOLOGY
The building materials survey tasks were performed in accordance with the Final Hazardous
Building Materials Surveys, Sampling Plan, Fort Bliss, Texas, December 2014, prepared by ALL
Consulting and ENCON International, Inc. A visual inspection of the Facility was conducted to develop a sampling strategy. This included identifying component groups with similar painting histories. Each component group was sampled throughout the facility to establish whether or not the building contained lead at the prescribed action level for this project, at the time of the survey.
This Lead Paint Inspection was performed on January 07, 2015, and January 08, 2015, using an x-ray fluorescence (XRF) analyzer, to identify if any lead amounts in the paint were at or above
0.3 mg/cm2. A total of one-hundred and sixty-five (165) XRF analyses were performed, which included one-hundred and fifty-one (151) building component measurements and fourteen
(14) calibration checks. Drawings that illustrate the locations of all building measurements have been provided in Appendix A of this Report.
XRF RESULTS
The XRF analyzer indicated that lead-containing paint was identified in the following building component types. The table also provides additional details regarding the location, color, condition, and substrate of these components.
COMPONENT SUBSTRATE CONDITION COLOR
OUTSIDE
SOFFIT WOOD FAIR BROWN
RISER CONCRETE POOR YELLOW
RAIL METAL POOR BLACK
EXT SILL CONCRETE POOR WHITE
PORCH
COLUMN BRICK FAIR RED
WALL BRICK FAIR RED
EXT SILL CONCRETE FAIR WHITE
FLOOR CONCRETE FAIR GREY
CEILING WOOD FAIR BROWN
DOOR
CASING WOOD FAIR BROWN
CURB CONCRETE POOR YELLOW
WALL BRICK POOR RED
EXT SILL CONCRETE POOR WHITE
WALL CONCRETE POOR GREEN
WALL CONCRETE POOR RED
AC STAND METAL POOR BROWN
PIPE METAL POOR BROWN
INSIDE
CEILING PLASTER FAIR WHITE
WALL PLASTER FAIR TAN
WALL WOOD FAIR TAN
MULLION WOOD FAIR BEIGE
WINDOW WOOD FAIR BEIGE
WINDOW WOOD FAIR TAN
WALL BRICK POOR WHITE
CEILING DRYWALL POOR WHITE
BASEMENT
WALL CONCRETE POOR YELLOW
WALL BRICK FAIR GREEN
CEILING WOOD FAIR TAN
FLOOR CONCRETE POOR GREY
WINDOW BRICK POOR TAN
HEATER METAL POOR YELLOW
BASEBOARD WOOD POOR YELLOW
WALL BRICK POOR TAN
CEILING CONCRETE POOR TAN
A total of forty-six (46) of the building measurements tested positive, which indicated the presence of lead at or above 0.3 mg/cm2. The complete XRF lead paint data have been provided in Appendix B of this Report. In this Report some of the XRF lead paint results indicated “<
LOD” (less than Limits of Detection). This reading indicates the concentration at which the instrument can determine whether an element was present or not; that is, the point at which the instrument can distinguish a measurement from the background levels. The LOD is not a fixed number, but is affected by the matrix (substrate) of the component and other factors such as temperature, etc. In addition, a result reading of “null” indicates that an inconclusive measurement was obtained, and was therefore repeated.
QUALIFICATIONS
This Comprehensive Lead Paint Survey was performed by a Texas Department of State Health
Services (DSHS) and New Mexico (USEPA) Licensed Lead Paint Inspector. This individual has received training under the HUD / EPA training criteria for the required Lead Paint Inspector and/or Risk Assessor courses and has received the refresher training within the prescribed period for each jurisdiction. Company and individual licenses and credentials have been provided and are available for review in the project sampling plan documents, which have been submitted to the USACE.
LIMITATIONS
The overall purpose of this Comprehensive Lead Paint Survey was to identify if lead-containing components were present, within the qualifications and limitations summarized below. Reliance on this Report is specifically limited to gathering initial information regarding the presence of lead in paint. Any time that lead-based paint may be identified during the performance of a lead inspection, the owner of the building is responsible to the occupants and to the public to properly manage these materials, per Local, State and Federal regulations. Prior to the abatement or removal of any lead containing materials, a Lead Project Design should be properly performed, by a qualified Lead Firm, to 1) ensure that materials will be properly managed, and 2) to prepare a more accurate estimate of actual materials to be addressed. This Survey Report was specifically prepared for ALL Consulting’s Client (USACE and Ft. Bliss), and the extent of liability incurred, is limited to the amount of the Report Fee paid by its Client. The USACE agrees that the ALL Consulting Team cannot be held responsible for any liability based on reliance of this Report by any third party.
CONCLUSIONS
1. Specific Conclusions. Lead-containing paint was found on components inside and/or outside of this building.
• Lead paint should not be disturbed without proper procedures in place. Should the lead paint need to be disturbed, personnel should be evacuated in advance, and only properly trained persons with adequate personal protective equipment (PPE) should be allowed to disturb the lead paint material.
• Lead painted components in poor condition should be stabilized with interim controls or abatement procedures by properly trained personnel.
• Lead Hazard air monitoring should be performed during abatement activities.
• Following abatement activities, clearance wipe samples should be collected and sent to an approved lead laboratory for analysis.
• The OSHA Hazard Communication Standard and the Lead Paint Standard both require anyone working in such areas to be informed of lead paint hazards and methods to avoid the hazards.
2. General Conclusions. Proper notification should be made to the appropriate authorities prior to disturbance of any lead-containing materials, including abatement activity, renovations, or operations and maintenance (O&M) activities, or demolition of any facilities or public buildings.
Other personnel working in the area must be alerted by signage and the appropriate regulated area designations. OSHA specifies worker protection and engineering controls, as well as work practices to ensure the safety of workers and anyone who will be in the area after the conclusion of the work.
Contact the personnel listed below with any clarifications that may be needed.
Inspected by: Reviewed by: Approved by:
Tim Jones, RPIH Alex Woelper, P.E., RPIH David Epperly, Ph.D., P.E.
Lead Inspector Environmental Consultant Project Manager License # 2070306
APPENDICES:
A. Lead Paint Sample Location Drawing(s) B. XRF Lead Paint Data
APPENDIX A
Lead Paint Sample Location Drawing(s)
Project: # 139-14
Hazardous Materials Surveys
Draw by: JC Location:
Building # 125 Fort Bliss, TX 7307 Remcon Cir, Ste 103
El Paso, Texas, 79912 915.833.3740
Sheet
ENV-1
Date:
01-13-2014
ENCON INTERNATIONAL, INC
NOT TO SCALE
LEAD PAINT Sample Location Drawing - Building # 125
Lead Sample Locations
Positive Lead Sample Locations##
1st Floor
77 71 72 74
66 67 68 69
75 76
94 96
105 107 106 108
97 98 99 100
110 111
N
Hazardous Materials Surveys
Draw by: JC Location:
Building # 125 Fort Bliss, TX 7307 Remcon Cir, Ste 103
El Paso, Texas, 79912 915.833.3740
Sheet
ENV-2
Date:
01-13-2014
ENCON INTERNATIONAL, INC
NOT TO SCALE
LEAD PAINT Sample Location Drawing - Building # 125
Lead Sample Locations
Positive Lead Sample Locations##
1st Floor Exterior
N
39 41
36 33 29
35 34 37 30 27
24,25,26 23,22
50,49,48 47 51 54
52,53
10,11, 12 16 13 14
6 7,8,9
Hazardous Materials Surveys
Draw by: JC Location:
Building # 125 Fort Bliss, TX 7307 Remcon Cir, Ste 103
El Paso, Texas, 79912 915.833.3740
Sheet
ENV-3
3 of3
Date:
01-06-2014
ENCON INTERNATIONAL, INC
NOT TO SCALE
LEAD PAINT Sample Location Drawing - Building # 125
Lead Sample Locations
Positive Lead Sample Locations##
Basement
157, 158
160 161
129, 130
153 155 156 150, 151
136, 137
140, 141
144 145
N
APPENDIX B
XRF Lead Paint Data
Fort Bliss, Texas XRF Lead Paint Data Bldg. 125
No. Type Component Substrate Condition Color Room Results Action Level
PbC
1 SHUTTER_CAL 7.81
2 PAINT CALIBRATE N/A 0.3 1
3 PAINT CALIBRATE N/A 0.3 1
4 PAINT CALIBRATE N/A 0.3 1.1
5 PAINT SOFFIT WOOD FAIR BROWN OUTSIDE Positive 0.3 11.6 6 PAINT SOFFIT WOOD FAIR BROWN OUTSIDE Positive 0.3 14.5 7 PAINT DOOR WOOD FAIR BROWN OUTSIDE Negative 0.3 < LOD 8 PAINT DOOR CASING WOOD FAIR BROWN OUTSIDE Negative 0.3 < LOD 9 PAINT THRESHOD WOOD FAIR BROWN OUTSIDE Negative 0.3 < LOD
10 PAINT FLOOR CONCRETE POOR GREY OUTSIDE Negative 0.3 < LOD 11 PAINT FLOOR CONCRETE POOR GREY OUTSIDE Negative 0.3 < LOD 12 PAINT RISER CONCRETE POOR YELLOW OUTSIDE Positive 0.3 6.8 13 PAINT RAIL METAL POOR BLACK OUTSIDE Positive 0.3 1.2 14 PAINT RAIL METAL POOR BLACK OUTSIDE Positive 0.3 2.2 15 PAINT WINDOW CASING WOOD POOR BROWN OUTSIDE Negative 0.3 < LOD 16 PAINT EXT SILL CONCRETE POOR WHITE OUTSIDE Positive 0.3 2.6 17 PAINT RAIL METAL POOR RAIL OUTSIDE Negative 0.3 < LOD 18 PAINT RAIL METAL POOR RAIL PORCH Negative 0.3 < LOD 19 PAINT COLUMN BRICK FAIR RED PORCH Positive 0.3 10.1 20 PAINT COLUMN BRICK FAIR RED PORCH Positive 0.3 3.3 21 PAINT WALL BRICK FAIR RED PORCH Positive 0.3 12.3 22 PAINT DOOR CASING METAL FAIR BROWN PORCH Negative 0.3 < LOD 23 PAINT DOOR WOOD FAIR BROWN PORCH Null 0.3 0.21 24 PAINT DOOR WOOD FAIR BROWN PORCH Negative 0.3 < LOD 25 PAINT DOOR CASING WOOD FAIR BROWN PORCH Negative 0.3 < LOD 26 PAINT GRILL WOOD FAIR BROWN PORCH Negative 0.3 < LOD 27 PAINT GRILL WOOD FAIR BROWN PORCH Negative 0.3 < LOD 28 PAINT EXT SILL CONCRETE FAIR WHITE PORCH Positive 0.3 1.4 29 PAINT EXT SILL CONCRETE FAIR WHITE PORCH Positive 0.3 9 30 PAINT FLOOR CONCRETE FAIR GREY PORCH Negative 0.3 < LOD 31 PAINT FLOOR CONCRETE FAIR GREY PORCH Positive 0.3 3.3 32 PAINT CEILING WOOD FAIR BROWN PORCH Positive 0.3 7
1/7/2015 ALL CONSULTING TEAM
Action Level
PbC
33 PAINT CEILING WOOD FAIR BROWN PORCH Positive 0.3 8.7 34 PAINT DOOR WOOD FAIR BROWN PORCH Negative 0.3 < LOD 35 PAINT DOOR WOOD FAIR BROWN PORCH Negative 0.3 < LOD 36 PAINT DOOR CASING WOOD FAIR BROWN PORCH Positive 0.3 0.7 37 PAINT DOOR CASING WOOD FAIR BROWN PORCH Negative 0.3 < LOD 38 PAINT CURB CONCRETE POOR YELLOW PORCH Negative 0.3 < LOD 39 PAINT CURB CONCRETE POOR YELLOW PORCH Positive 0.3 7.7 40 PAINT WALL BRICK POOR RED PORCH Null 0.3 0.25 41 PAINT WALL BRICK POOR RED PORCH Positive 0.3 9.5 42 PAINT EXT SILL CONCRETE POOR WHITE PORCH Positive 0.3 1.2 43 PAINT AC STAND CONCRETE POOR BROWN PORCH Negative 0.3 < LOD 44 PAINT AC STAND CONCRETE POOR BROWN PORCH Negative 0.3 < LOD 45 PAINT WALL CONCRETE POOR GREEN PORCH Positive 0.3 1.1 46 PAINT WALL CONCRETE POOR RED PORCH Positive 0.3 1.1 47 PAINT EXT SILL CONCRETE POOR WHITE PORCH Positive 0.3 1.6 48 PAINT WINDOW WOOD POOR BROWN PORCH Negative 0.3 < LOD 49 PAINT WINDOW SILL WOOD POOR BROWN PORCH Null 0.3 < LOD 50 PAINT WINDOW SILL WOOD POOR BROWN PORCH Negative 0.3 0.15 51 PAINT ELEC BOX METAL POOR BROWN PORCH Negative 0.3 < LOD 52 PAINT AC STAND METAL POOR BROWN PORCH Null 0.3 0.24 53 PAINT AC STAND METAL POOR BROWN PORCH Negative 0.3 < LOD 54 PAINT DUCT METAL POOR BROWN PORCH Negative 0.3 < LOD 55 PAINT DUCT METAL POOR BROWN PORCH Negative 0.3 < LOD 56 PAINT AC STAND METAL POOR BROWN PORCH Positive 0.3 9.9 57 PAINT PIPE METAL POOR BROWN PORCH Positive 0.3 0.9 58 PAINT WALL BRICK POOR BROWN PORCH Null 0.3 0.05
59 PAINT CALIBRATE N/A 0.3 1
60 PAINT CALIBRATE N/A 0.3 1.1
61 PAINT CALIBRATE N/A 0.3 1.1
62 SHUTTER_CAL 8.66
63 PAINT CALIBRATE N/A 0.3 0.9
64 PAINT CALIBRATE N/A 0.3 1
Action Level
PbC
65 PAINT CALIBRATE N/A 0.3 1
66 PAINT CEILING PLASTER FAIR WHITE INSIDE Null 0.3 < LOD 67 PAINT CEILING PLASTER FAIR WHITE INSIDE Positive 0.3 1 68 PAINT CROWN MOLDING WOOD FAIR TAN INSIDE Negative 0.3 < LOD 69 PAINT TRIM WOOD FAIR TAN INSIDE Negative 0.3 < LOD 70 PAINT WALL DRYWALL FAIR TAN INSIDE Negative 0.3 < LOD 71 PAINT WALL DRYWALL FAIR TAN INSIDE Negative 0.3 < LOD 72 PAINT BASEBOARD WOOD FAIR BEIGE INSIDE Negative 0.3 < LOD 73 PAINT DOOR CASING WOOD FAIR BEIGE INSIDE Negative 0.3 < LOD 74 PAINT DOOR WOOD FAIR BEIGE INSIDE Negative 0.3 < LOD 75 PAINT WINDOW WOOD FAIR BEIGE INSIDE Negative 0.3 < LOD 76 PAINT SILL WOOD FAIR BROWN INSIDE Negative 0.3 < LOD 77 PAINT APRON WOOD FAIR BROWN INSIDE Negative 0.3 < LOD 78 PAINT HEATER METAL FAIR GREY INSIDE Null 0.3 < LOD 79 PAINT WALL PLASTER FAIR TAN INSIDE Positive 0.3 8.3 80 PAINT DOOR CASING WOOD FAIR BEIGE INSIDE Negative 0.3 < LOD 81 PAINT DOOR CASING WOOD FAIR BEIGE INSIDE Negative 0.3 < LOD 82 PAINT DOOR WOOD FAIR BEIGE INSIDE Negative 0.3 < LOD 83 PAINT BASEBOARD WOOD FAIR BEIGE INSIDE Negative 0.3 < LOD 84 PAINT CEILING DRYWALL FAIR WHITE INSIDE Null 0.3 < LOD 85 PAINT CEILING DRYWALL FAIR WHITE INSIDE Negative 0.3 < LOD 86 PAINT DOOR DRYWALL FAIR TAN INSIDE Negative 0.3 < LOD 87 PAINT CEILING DRYWALL FAIR WHITE INSIDE Null 0.3 0.3 88 PAINT CEILING DRYWALL FAIR WHITE INSIDE Null 0.3 0.4 89 PAINT WALL PLASTER FAIR TAN INSIDE Positive 0.3 7 90 PAINT WALL DRYWALL FAIR TAN INSIDE Negative 0.3 < LOD 91 PAINT SCUTTLE WOOD FAIR WHITE INSIDE Negative 0.3 < LOD 92 PAINT DOOR FRAME WOOD FAIR WHITE INSIDE Null 0.3 < LOD 93 PAINT DOOR FRAME WOOD FAIR WHITE INSIDE Null 0.3 0.4 94 PAINT DOOR WOOD FAIR TAN INSIDE Negative 0.3 < LOD 95 PAINT DOOR CASING WOOD FAIR TAN INSIDE Negative 0.3 < LOD 96 PAINT WALL WOOD FAIR TAN INSIDE Positive 0.3 3.6
Action Level
PbC
97 PAINT CEILING DRYWALL FAIR WHITE INSIDE Negative 0.3 < LOD 98 PAINT MULLION WOOD FAIR BEIGE INSIDE Positive 0.3 0.8 99 PAINT WINDOW WOOD FAIR BEIGE INSIDE Positive 0.3 17.7
100 PAINT WINDOW WOOD FAIR BEIGE INSIDE Positive 0.3 0.7 101 PAINT WALL DRYWALL FAIR TAN INSIDE Negative 0.3 < LOD 102 PAINT ELEC BOX DRYWALL FAIR TAN INSIDE Negative 0.3 < LOD 103 PAINT WINDOW WOOD FAIR TAN INSIDE Positive 0.3 11.8 104 PAINT DOOR CASING WOOD FAIR TAN INSIDE Negative 0.3 < LOD 105 PAINT COLUMN WOOD FAIR TAN INSIDE Null 0.3 < LOD 106 PAINT COLUMN WOOD FAIR TAN INSIDE Null 0.3 < LOD 107 PAINT COLUMN WOOD FAIR TAN INSIDE Null 0.3 < LOD 108 PAINT COLUMN WOOD FAIR TAN INSIDE Negative 0.3 < LOD 109 PAINT DOOR WOOD FAIR TAN INSIDE Negative 0.3 < LOD 110 PAINT DOOR WOOD FAIR TAN INSIDE Negative 0.3 < LOD 111 PAINT DOOR CASING WOOD FAIR TAN INSIDE Negative 0.3 < LOD 112 PAINT WALL BRICK POOR WHITE INSIDE Positive 0.3 7.2 113 PAINT CEILING DRYWALL POOR WHITE INSIDE Positive 0.3 0.5 114 PAINT BASEBOARD WOOD POOR BEIGE INSIDE Negative 0.3 < LOD 115 PAINT WINDOW CASING WOOD FAIR TAN INSIDE Null 0.3 < LOD 116 PAINT WALL PLASTER FAIR TAN INSIDE Positive 0.3 10.3 117 PAINT WALL PLASTER FAIR TAN INSIDE Positive 0.3 9.4 118 PAINT GRILL PLASTER FAIR TAN INSIDE Negative 0.3 < LOD 119 PAINT DOOR WOOD FAIR TAN INSIDE Negative 0.3 < LOD 120 PAINT WINDOW WOOD FAIR TAN INSIDE Positive 0.3 12 121 PAINT DOOR CASING WOOD FAIR TAN INSIDE Negative 0.3 < LOD 122 PAINT DOOR WOOD FAIR BROWN INSIDE Negative 0.3 < LOD 123 PAINT DOOR WOOD FAIR BROWN INSIDE Negative 0.3 < LOD 124 PAINT DOOR WOOD FAIR BROWN INSIDE Negative 0.3 < LOD 125 PAINT WALL DRYWALL FAIR TAN INSIDE Negative 0.3 < LOD 126 PAINT WALL DRYWALL FAIR TAN INSIDE Negative 0.3 < LOD 127 PAINT WALL PLASTER FAIR TAN INSIDE Positive 0.3 5.2 128 PAINT TREAD CONCRETE POOR TAN STAIR Null 0.3 < LOD
Action Level
PbC
129 PAINT WALL BRICK POOR RED STAIR Null 0.3 < LOD 130 PAINT WALL BRICK POOR RED STAIR Null 0.3 < LOD 131 PAINT WALL CONCRETE POOR YELLOW BASEMENT Positive 0.3 1.9 132 PAINT DOOR METAL POOR YELLOW BASEMENT Negative 0.3 < LOD 133 PAINT DOOR WOOD POOR BROWN BASEMENT Negative 0.3 < LOD 134 PAINT CEILING CONCRETE FAIR BROWN BASEMENT Null 0.3 < LOD 135 PAINT CEILING CONCRETE FAIR BROWN BASEMENT Null 0.3 0.04 136 PAINT WALL CONCRETE FAIR BROWN BASEMENT Negative 0.3 0.07 137 PAINT SHELF WOOD FAIR BROWN BASEMENT Negative 0.3 0.23 138 PAINT DOOR CASING WOOD FAIR BROWN BASEMENT Negative 0.3 0.12 139 PAINT WALL DRYWALL FAIR TAN BASEMENT Negative 0.3 < LOD 140 PAINT FIREPLACE WOOD FAIR BROWN BASEMENT Negative 0.3 < LOD 141 PAINT FIREPLACE WOOD FAIR TAN BASEMENT Negative 0.3 < LOD 142 PAINT WALL BRICK FAIR GREEN BASEMENT Positive 0.3 6.5 143 PAINT WINDOW WOOD FAIR BROWN BASEMENT Negative 0.3 < LOD 144 PAINT CEILING WOOD FAIR TAN BASEMENT Positive 0.3 3.4 145 PAINT COLUMN WOOD FAIR TAN BASEMENT Negative 0.3 < LOD 146 PAINT WALL WOOD FAIR WHITE BASEMENT Negative 0.3 < LOD 147 PAINT FLOOR CONCRETE POOR GREY BASEMENT Null 0.3 0.25 148 PAINT FLOOR CONCRETE POOR GREY BASEMENT Positive 0.3 0.4 149 PAINT DOOR CASING WOOD POOR YELLOW BASEMENT Negative 0.3 < LOD 150 PAINT DOOR WOOD POOR YELLOW BASEMENT Negative 0.3 < LOD 151 PAINT DOOR WOOD POOR WHITE BASEMENT Negative 0.3 < LOD 152 PAINT PIPE METAL POOR YELLOW BASEMENT Negative 0.3 < LOD 153 PAINT WINDOW BRICK POOR TAN BASEMENT Positive 0.3 5.4 154 PAINT COLUMN WOOD POOR YELLOW BASEMENT Negative 0.3 < LOD 155 PAINT HEATER METAL POOR YELLOW BASEMENT Positive 0.3 1.1 156 PAINT BASEBOARD WOOD POOR YELLOW BASEMENT Positive 0.3 1.1 157 PAINT DOOR WOOD POOR GREEN BASEMENT Negative 0.3 < LOD 158 PAINT DOOR CASING WOOD POOR BLACK BASEMENT Negative 0.3 < LOD 159 PAINT PANEL METAL POOR BLACK BASEMENT Negative 0.3 < LOD 160 PAINT WALL BRICK POOR TAN BASEMENT Positive 0.3 1.8
Action Level
PbC
161 PAINT WALL BRICK POOR RED BASEMENT Negative 0.3 0.12 162 PAINT CEILING CONCRETE POOR TAN BASEMENT Positive 0.3 3.9
163 PAINT CALIBRATE N/A 0.3 1
164 PAINT CALIBRATE N/A 0.3 1.2
165 PAINT CALIBRATE N/A 0.3 1
1/7/2015 ALL CONSULTING TEAM
LOD - Limit of Detection
Null - indicates that an inconclusive measurement was obtained, and was therefore repeated
ATTACHMENT 2
Prior (2014) Regulated Materials Inspection Report
Regulated Materials Inspection Report Building 125
Fort Bliss, Texas August 2014
Lead-based paint (LBP) and asbestos containing material (ACM) inspections at Building 125 were conducted on 12 August 2014 by Ms. Suzanne Simpson and Mr.
Barry Vercoe of the U.S. Army Corps of Engineers, Fort Worth District, Regional Planning & Environmental Center (USAED, CESWF-PEC). The purpose of the inspections was to identify regulated materials at this building including LBP and ACM, which may require abatement prior to proposed renovation.
The LBP inspection included screening of painted surfaces to indicate the presence of lead in paint with an x-ray fluorescence (XRF) analyzer, model LPA-1 manufactured by RMD Instruments, LLC, Watertown, Massachusetts. Mr. Vercoe is certified through manufacturer training to operate this model of analyzer, and is also certified by the Texas Department of State Health Services (DSHS) as a Lead Inspector, License Number 2060570, and Lead Risk Assessor, License Number 2070346, both with expiration date 25 April 2016. For the purpose of this inspection, the presence of LBP was confirmed on surfaces where XRF readings were equal to or greater than the HUD and U.S. Environmental Protection Agency (EPA) regulatory threshold of 1.0 mg/cm2, and the presence of lead containing paint (LCP) was indicated on surfaces where XRF readings were 0.2 mg/cm2 or greater based on data in the Performance Characteristic Sheet (PCS) for this XRF model provided by HUD. Worker protection measures are required under Occupational Safety and Health Administration (OSHA) regulations listed in 29 CFR 1926.62 where materials containing any lead, including LBP or LCP, will be disturbed. XRF screening results are summarized in Table 1 of this report.
The presence of LBP was confirmed on a brick plaster wall outside room of room 7 (3.1 mg/cm2), wood window in restroom 4 (>9.9mg/cm2), exterior wood ceiling on the porch (6.8 mg/cm2), on the exterior porch brick walls (5.6 mg/cm2) and texture on the brick wall in the basement (1.0 mg/cm2). The presence of LCP at concentrations below the regulatory threshold for LBP was confirmed on a gypsum ceiling board outside of room 7 (0.3 mg/cm2) and a gypsum wall board in restroom 5 (0.3 mg/cm2).
The ACM inspection included collection of bulk samples of suspect material for laboratory analyses by polarized light microscopy (PLM). Ms. Simpson and Mr. Vercoe are certified as an Asbestos Inspectors by EPA approved training provided through GEBCO Associates, LP, Hurst, Texas, with respective Certificate Numbers 14033 (expiration date 29 January 2015) and 13007 (expiration date 02 January 2015). Samples were analyzed by EMC Labs Inc., Phoenix, Arizona, which is certified by the Texas DSHS for PLM analyses, License Number 300296, expiration date 30 July 2016.
Analytical results are summarized in Table 2 of this report, with the complete laboratory analytical report included as Appendix A. ACM is defined by the EPA to be any material containing greater than 1% asbestos as determined by PLM analysis.
Results reported by the analytical laboratory indicated ACM is present in the following materials: gypsum ceiling panel/joint compound (3% chrysotile), floor tile/black mastic (2% - 8% Chrysotile).
Table 1 Fort Bliss - Building 125
Lead Containing Paint XRF Screening Results
Reading XRF Result XRF Number (mg/cm2) Mode
001 1.0 002 0.9 003 1.0 004 0.0 005 0.0 006 -0.1 016 -0.1 Quick Mode Interior Corridor Wall Gypsum Board White 017 -0.1 Quick Mode Room 13 Door Trim Wood Beige 018 0.1 Quick Mode Room 9 Door Wood Beige 019 3.1 Quick Mode Outside Room 7 Wall Plaster on Brick White 020 >9.9 Quick Mode Restroom 4 Window Wood White 021 0.3 Quick Mode Outside Room 7 Ceiling Gypsum Board White 022 0.3 Quick Mode Restroom 5 Wall Gypsum Board Light Beige 023 -0.2 Quick Mode Room 2 Door Wood Beige 024 0.1 Quick Mode Outside Restroom 4 Baseboard Wood Beige 025 6.8 Quick Mode Exterior Porch Ceiling Wood Brown 026 5.6 Quick Mode Exterior Porch Wall Brick Dark Red 027 1.0 Quick Mode Basement Wall Texture on Brick White
NOTE: Readings in bold indicate the presence of lead containing paint as determined by XRF analysis
Time Corrected
Mode
0.0 mg/cm2
Unpainted Standard
Paint ColorComponentLocation Substrate
Time Corrected
Mode
1.0 mg/cm2
Paint Standard Calibration
Calibration
FORT BLISS BUILDING 125 ACM RESULTS 2014
Description Sample Identification Analytical Results Location Floortile 1-A None Detected Hall Outside of Room 14
1-B None Detected Hall Outside of Room 13 2-B None Detected Room 13
Gypsum Wall Panel 2-C None Detected Outside of Room 8 2-D None Detected Room 14 3-A None Detected Hall
Floor Tile 3-B None Detected Outside of Room 8 3-C None Detected Stairs going into Room 7 4-A None Detected Prisoner Holding Cell
Wall Texture 4-B None Detected Basement 5-A 3% Chrysotile Prisoner Holding Cell
Gypsum Ceiling Panel 5-B None Detected Mens Restroom Floor Tile 6-A None Detected
6-B None Detected Floor Tile 7-A 2% Chrysotile, 8% Chrysotile Basement
2'X2' Drop Tile Panel 8-A None Detected Basement Roofing Shingle 9-A None Detected Off of Porch Over Hang
Appendix A
Asbestos Analytical Reports EMC Labs, Inc.
August 2014
Asbestos Detected
Layer Name / Sample Description
Lab ID Sample Location
Bulk Asbestos Analysis by Polarized Light Microscopy
Non-Asbestos Constituents
Laboratory Report
0144968
NVLAP#101926-0
Client ID
Client:
Address: 819 TAYLOR ST.
FT. WORTH TX 76102
U.S. ARMY CORPS OF ENGINEERS
Date Received: 08/14/2014
08/26/2014Date Analyzed:
444064Job# / P.O. #:
EMC LABS, INC.
Collected: 08/12/2014 EPA Method: Project Name: FT. BLISS BLDG 125 Submitted By: BARRY VERCOEAddress: PO #W9126G-11-A-0002 Collected By:
9830 S. 51st Street, Suite B109, Phoenix, AZ 85044 Phone: 800-362-3373 or 480-940-5294 - Fax: (480) 893-1726
08/26/2014Date Reported:
EPA 600/R-93/116
Asbestos Type
NoLAYER 1 12"x12" Floor Tile, Brown/ Off White
None Detected0144968-001 125-1A Carbonates
Quartz Binder/Filler
100%
Cellulose FiberNoLAYER 2 Mastic, Yellow
None Detected <1%
Carbonates Gypsum
99%
NoLAYER 1 12"x12" Floor Tile, Brown/ Off White
None Detected0144968-002 125-1B Carbonates
Mastic, Yellow
None Detected <1%
Carbonates Gypsum
Cellulose FiberNoLAYER 1 Gypsum Wall Panel, Off White/ Brown
None Detected0144968-003 125-2A
10%
Gypsum
Carbonates
90%
NoLAYER 2 Joint Compound, White
None Detected
Carbonates Mica
Cellulose FiberNoLAYER 3 Tape, Off White
None Detected 95%
Carbonates Gypsum
5%
Cellulose FiberNoLAYER 4 Texture, White/ Off White
None Detected 1%
Carbonates Gypsum
Layer Name / Sample Description
Lab ID Sample Location
Bulk Asbestos Analysis by Polarized Light Microscopy
Non-Asbestos Constituents
Laboratory Report
0144968
NVLAP#101926-0
Client ID
Client:
Address: 819 TAYLOR ST.
FT. WORTH TX 76102
U.S. ARMY CORPS OF ENGINEERS
Date Received: 08/14/2014
08/26/2014Date Analyzed:
444064Job# / P.O. #:
EMC LABS, INC.
Collected: 08/12/2014 EPA Method: Project Name: FT. BLISS BLDG 125 Submitted By: BARRY VERCOEAddress: PO #W9126G-11-A-0002 Collected By:
9830 S. 51st Street, Suite B109, Phoenix, AZ 85044 Phone: 800-362-3373 or 480-940-5294 - Fax: (480) 893-1726
08/26/2014Date Reported:
EPA 600/R-93/116
Asbestos Type
Cellulose FiberNoLAYER 1 Gypsum Wall Panel, Off White/ Brown
None Detected0144968-004 125-2B
10%
Gypsum
NoLAYER 2 Joint Compound, White
None Detected
Carbonates Mica
Tape, Off White
None Detected 95%
Carbonates
Texture, White/ Off White
None Detected 1%
Carbonates Gypsum
Gypsum Wall Panel, Off White/ Brown
None Detected0144968-005 125-2C
10%
Gypsum
Texture, White/ Beige
None Detected <1%
Carbonates Mica
Floor Tile, Brown w/ Specks
None Detected0144968-006 125-3A Carbonates
Mastic, Yellow
None Detected 1%
Carbonates Gypsum
Layer Name / Sample Description
Lab ID Sample Location
Bulk Asbestos Analysis by Polarized Light Microscopy
Non-Asbestos Constituents
Laboratory Report
0144968
NVLAP#101926-0
Client ID
Client:
Address: 819 TAYLOR ST.
FT. WORTH TX 76102
U.S. ARMY CORPS OF ENGINEERS
Date Received: 08/14/2014
08/26/2014Date Analyzed:
444064Job# / P.O. #:
EMC LABS, INC.
Collected: 08/12/2014 EPA Method: Project Name: FT. BLISS BLDG 125 Submitted By: BARRY VERCOEAddress: PO #W9126G-11-A-0002 Collected By:
9830 S. 51st Street, Suite B109, Phoenix, AZ 85044 Phone: 800-362-3373 or 480-940-5294 - Fax: (480) 893-1726
08/26/2014Date Reported:
EPA 600/R-93/116
Asbestos Type
NoLAYER 1 Floor Tile, Brown w/ Specks
None Detected0144968-007 125-3B Carbonates
Mastic, Yellow
None Detected 1%
Carbonates Gypsum
Floor Tile, Brown w/ Specks
None Detected0144968-008 125-3C Carbonates
Synthetic FiberNoLAYER 2 Mastic, Yellow
None Detected <1%
Carbonates Gypsum
Wall Texture, White/ Beige
None Detected0144968-009 125-4A Gypsum
Mica
Tape, Off White
None Detected 95%
Carbonates
Joint Compound, White
None Detected <1%
Gypsum Mica
Layer Name / Sample Description
Lab ID Sample Location
Bulk Asbestos Analysis by Polarized Light Microscopy
Non-Asbestos Constituents
Laboratory Report
0144968
NVLAP#101926-0
Client ID
Client:
Address: 819 TAYLOR ST.
FT. WORTH TX 76102
U.S. ARMY CORPS OF ENGINEERS
Date Received: 08/14/2014
08/26/2014Date Analyzed:
444064Job# / P.O. #:
EMC LABS, INC.
Collected: 08/12/2014 EPA Method: Project Name: FT. BLISS BLDG 125 Submitted By: BARRY VERCOEAddress: PO #W9126G-11-A-0002 Collected By:
9830 S. 51st Street, Suite B109, Phoenix, AZ 85044 Phone: 800-362-3373 or 480-940-5294 - Fax: (480) 893-1726
08/26/2014Date Reported:
EPA 600/R-93/116
Asbestos Type
NoWall Texture, White/ Beige None Detected0144968-010 125-4B Gypsum
Mica
Gypsum Ceiling Panel, Off White/ Brown
None Detected0144968-011 125-5A
10%
Gypsum
Cellulose FiberYesLAYER 2 Joint Compound, White
Chrysotile 3% 2%
Carbonates Mica
95%
Tape, Off White
None Detected 95%
Carbonates
Texture, White/ Off White
None Detected <1%
Carbonates Mica
Layer Name / Sample Description
Lab ID Sample Location
Bulk Asbestos Analysis by Polarized Light Microscopy
Non-Asbestos Constituents
Laboratory Report
0144968
NVLAP#101926-0
Client ID
Client:
Address: 819 TAYLOR ST.
FT. WORTH TX 76102
U.S. ARMY CORPS OF ENGINEERS
Date Received: 08/14/2014
08/26/2014Date Analyzed:
444064Job# / P.O. #:
EMC LABS, INC.
Collected: 08/12/2014 EPA Method: Project Name: FT. BLISS BLDG 125 Submitted By: BARRY VERCOEAddress: PO #W9126G-11-A-0002 Collected By:
9830 S. 51st Street, Suite B109, Phoenix, AZ 85044 Phone: 800-362-3373 or 480-940-5294 - Fax: (480) 893-1726
08/26/2014Date Reported:
EPA 600/R-93/116
Asbestos Type
Cellulose FiberNoLAYER 1 Gypsum Ceiling Panel, Off White/ Brown
None Detected0144968-012 125-5B
10%
Gypsum
Joint Compound, White
Chrysotile 3% 2%
Carbonates Mica
95%
Texture, White/ Off White
None Detected <1%
Carbonates Mica
12"x12" Floor Tile, Dk. Brown/ Gray/ Black
None Detected0144968-013 125-6A Carbonates
Mastic, Yellow
None Detected <1%
Carbonates Gypsum
NoLAYER 3 12"x12" Floor Tile, Off White
None Detected
Carbonates
12"x12" Floor Tile, Dk. Brown/ Gray/ Black
None Detected0144968-014 125-6B Carbonates
Mastic, Yellow
None Detected <1%
Carbonates Gypsum
Layer Name / Sample Description
Lab ID Sample Location
Bulk Asbestos Analysis by Polarized Light Microscopy
Non-Asbestos Constituents
Laboratory Report
0144968
NVLAP#101926-0
Client ID
Client:
Address: 819 TAYLOR ST.
FT. WORTH TX 76102
U.S. ARMY CORPS OF ENGINEERS
Date Received: 08/14/2014
08/26/2014Date Analyzed:
444064Job# / P.O. #:
EMC LABS, INC.
Collected: 08/12/2014 EPA Method: Project Name: FT. BLISS BLDG 125 Submitted By: BARRY VERCOEAddress: PO #W9126G-11-A-0002 Collected By:
9830 S. 51st Street, Suite B109, Phoenix, AZ 85044 Phone: 800-362-3373 or 480-940-5294 - Fax: (480) 893-1726
08/26/2014Date Reported:
EPA 600/R-93/116
Asbestos Type
YesLAYER 1 9"x9" Floor Tile, Lt. Green
Chrysotile0144968-015 125-7A
2%
Carbonates
98%
Mastic, Black
Chrysotile 8% 2%
Carbonates
Cellulose Fiber Mineral Wool
No2x2 Drop Tile Ceilng Panel, White/ Beige
None Detected0144968-016 125-8A
75% 5%
Carbonates Gypsum Perlite
20%
Fibrous GlassNoLAYER 1 Roofing Shingle, Gray/ Off White/ Black
None Detected0144968-017 125-9A
20%
Carbonates Gypsum
80%
Fibrous GlassNoLAYER 2 Tar, Black
None Detected 30%
Carbonates
70%
Distinctly stratified, easily separable layers of samples are analyzed as subsamples of the whole and are reported separately for each discernible layer. All analyses are derived from calibrated visual estimate and measured in area percent unless otherwise noted. The report applies to the standards or procedures identified and to the sample(s) tested. The test results are not necessarily indicated or representative of the qualities of the lot from which the sample was taken or of apparently identical or similar products, nor do they represent an ongoing quality assurance program unless so noted. These reports are for the exclusive use of the addressed client and that they will not be reproduced wholly or in part for advertising or other purposes over our signature or in connection with our name without special written permission. The report shall not be reproduced except in full, without written approval by our laboratory. The samples not destroyed in testing are retained a maximum of thirty days. The laboratory measurement of uncertainty for the test method is approximately less than 1 by area percent.
Accredited by the National Institute of Standards and Technology, Voluntary Laboratory Accreditation Program for selected test method for asbestos. The accreditation or any reports generated by this laboratory in no way constitutes or implies product certification, approval, or endorsement by the National Institute of Standards and Technology. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal Government. Polarized Light Microscopy may not be consistently reliable in detecting asbestos in floor coverings and similar non-friable organically bound materials.
Analyst - Kurt Kettler Signatory - Lab Manager - Ken Scheske
ATTACHMENT 3
Prior (1990) Asbestos Report