Asbestos_Containing_Materials_and_Hazardous_Materials_Report_101625.pdf

PDF 778 KB Posted

Attached to
Demolition of 1311 S. Martin Luther King Jr.
Solicitation number
2026-DEI-016
Issued by
Kalamazoo County, Huntington Woods City, Michigan

About this file

This is an Asbestos-Containing Materials and Hazardous Materials Report prepared for a demolition project at 1311 S. Martin Luther King Jr. in Michigan. The report documents the presence and assessment of asbestos-containing materials (ACM) and other hazardous materials identified within the structure scheduled for demolition. The report provides a comprehensive survey of hazardous material conditions throughout the property, including identification of ACM locations, material types, quantities, and condition assessments necessary for safe demolition planning and execution. This documentation is essential for establishing proper remediation and disposal protocols prior to structural demolition activities.

The hazardous materials assessment outlined in this report is a critical prerequisite for the demolition project, as it identifies all substances requiring special handling, abatement, or disposal in accordance with environmental regulations. The Michigan Homeowner Demolition Grant program, which provides partial funding for demolition costs with the homeowner responsible for any remaining balance, requires comprehensive hazardous materials documentation to ensure compliance with state and federal environmental standards. The detailed inventory and condition assessment of hazardous materials inform the scope of work, cost estimates, and timeline for safe removal and disposal activities that must precede structural demolition operations.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

P.O. Box 13216

Lansing, MI 48901

Phone: 888.449.4566

Fax: 888.448.8739 www.redcedarconsulting.net

October 16, 2025

Mr. Brian Taylor

City of Jackson

Community Development Department

Jackson, MI 49202

RE: Asbestos Containing Material and Hazardous Materials Inspection

1309 Martin Luther King Jr. Dr. Jackson, MI 49203

Parcel ID: 5-128100000

Dear Mr. Taylor:

Red Cedar Consulting has completed an asbestos-containing material (ACM) and hazardous materials inspection at 1309 Martin Luther King Jr. Dr. Jackson, Michigan (Subject Property). This inspection was completed at the request of the City of Jackson to comply with the United States Environmental

Protection Agency (USEPA) requirements for demolition and renovation set forth under the National

Emissions Standards for Hazardous Air Pollutants (NESHAP, 40 CFR Part 61). This inspection was also completed to comply with the Occupational Safety and Health Administration (OSHA) Asbestos

Standards for Construction (29 CFR 1926.1101) which limits employee exposure to asbestos.

SUBJECT PROPERTY

The Subject Property is comprised of a 0.12-acre commercial parcel which contains an approximate 3,132 square foot commercial building (the Building) with an unknown date of construction. The Building was constructed on a concrete foundation with one above-ground floor. The exterior walls of the Building were finished with stucco while the roof was sealed with multiple layers of roofing materials. The Building can be further divided into a five rooms and two bathrooms for inspection purposes.

VISUAL INSPECTION AND SAMPLING

Asbestos Containing Materials Inspection

Jeff Cain of Red Cedar Consulting (Red Cedar), accredited State Of Michigan/EPA Asbestos Building

Inspector (Accreditation Number A14057) who completed training per the Michigan Asbestos Workers

Accreditation Act 440, completed an inspection of the Subject Property on September 18, 2025, for suspected asbestos containing building materials.

Project No.: 12-1027

This inspection, and subsequent sample collection was completed in accordance with the USEPA

Asbestos Hazard Emergency Response Act (AHERA) (40 CFR Part 763) assessment and sampling protocol.

During the completion of the inspection, each area of the Subject Property was visually inspected for asbestos containing building materials (ACBM). Following the completion of the visual inspection, Red

Cedar staff identified each suspect area of friable and non-friable ACBM and sorted them into one of three homogenous categories for sampling purposes. AHERA defines friable as a material that when dry, may be crumbled, pulverized, or reduced to powder by hand pressure. A homogenous area is defined by

OSHA as an area of surfacing, thermal system insulation (TSI) or miscellaneous material that is uniform in color and texture. Surfacing materials are most commonly found in sprayed-on, troweled-on or otherwise applied to surfaces, such as acoustical plaster on ceilings and fireproofing materials on structural members. TSI refers to materials applied to pipes, fittings, boilers, ductwork, or other components to prevent heat loss or gain, or condensation. Any material that does not fall under the surfacing or TSI category, such as floor tile, drywall, and acoustical ceiling tile are placed into the miscellaneous materials category.

Following the completion of the visual inspection, Red Cedar staff identified the following materials as suspect ACBM:

• Roofing Materials

• Flat Roofing

• Roof Tar

• Window Trim Caulk

• Floor Tar/Mastic

• Fiberboard with Glue

• Stucco

Red Cedar staff collected seventeen samples of suspect ACBM separated into seven distinct homogenous groups for laboratory analysis. Samples were collected and submitted to APEX Research Inc.

Laboratories (APEX) (Accreditation Number 102118-0) for laboratory analysis. Analysis was completed utilizing polarized light microscopy (PLM) which is the Environmental Protection Agency (EPA) approved method for analysis of bulk materials for asbestos. PLM analysis completed pursuant to method (EPA 600/M4-82-020) identifies asbestos fiber bundles by the visual properties displayed when the sample is treated with various dispersion staining liquids. The laboratory report completed following the sample analysis indicates if asbestos is present, and at what percentage along with a description and percentage of other fibrous and non-fibrous materials and sample color. Chain-of-custody documentation was followed from sample collection through shipping and receiving of the samples at the designated laboratory. The documentation assures that samples will meet the quality assurance/quality control measures defined by AHERA. The laboratory analytical report prepared by APEX for the seventeen samples is included as Attachment A.

Hazardous Materials Inspection

On September 18, 2025, the Subject Property was also inspected for the presence of hazardous materials which include but are not limited to polychlorinated biphenyls (PCBs) and potential mercury containing equipment and any items or containers that may contain or be classified as a hazardous or regulated material. Each material, if identified, was documented along with the approximate location. Any materials identified as hazardous are included in Table 1.

INSPECTION RESULTS AND RECOMMENDATIONS

During the completion of the asbestos inspection, seventeen samples of suspect ACM were collected and are documented in Table 2 along with the Red Cedar sample number, description, friability, material type, ACM classification, sample location, material quantity and laboratory analytical results. A Site Diagram was prepared which provides the general building layout and sample locations and is included as

Attachment B.

ACM, as defined by the USEPA NESHAP is “any material containing more than 1 percent asbestos as determined using the method specified in appendix E, subpart E, 40 CFR part 763 Section 1, Polarized

Light Microscopy”.

Friable ACM is defined by NESHAP as any material containing more than 1 percent asbestos that, when dry, can be crumbled, pulverized, or reduced to powder by hand pressure. Friable ACM is a concern due to the ease of unintentionally disturbing the ACM which may result in “visible emissions” which is known as a Fiber Release Episode.

Non-friable asbestos-containing material is defined as “material containing more than 1 percent asbestos that, when dry, cannot be crumbled, pulverized, or reduced to powder by hand pressure. Non-friable

ACMs are separated into Category I and Category II ACM. Category I ACM is any asbestos containing packing’s, gaskets, resilient floor coverings (vinyl floor tile and linoleum are examples of these) and asphalt roofing products. Category II ACM is stated by NESHAP as any material excluding Category I non-friable ACM such as drywall, plaster or fiberboard insulation.

Presumed Asbestos Containing Material

Presumed Asbestos Containing Materials (PACM) are suspect surfacing, TSI and miscellaneous materials found in buildings constructed prior to 1980 which are classified as and due to the age of the structure, are assumed to be ACM and do not require sample collection and analysis. OSHA dictates that PACM may be “rebutted” following a complete inspection pursuant to AHERA protocol.

No PACM was identified during the completion of this inspection. All suspect materials identified were sampled and analyzed for ACM.

Table 3 lists the location, material description, friability, condition, material type (surfacing, thermal or miscellaneous) and approximate quantity of all PACM documented at the Subject Property.

Table 4 provides a summary of all ACM documented at the Subject Property which includes the material location, description, and approximate quantity.

Friable ACM’s

No friable ACM’s were identified during the completion of this inspection.

Category I ACM

No Category I ACM was identified during the completion of this inspection.

Category II ACM

No Category II non-friable ACM was identified during the completion of this inspection.

RECOMMENDATIONS

Asbestos Containing Materials

No ACM was identified within the Building that would require abatement prior to demolition/renovation of the structure.

Please note: The location of samples obtained during this inspection were in a random fashion and areas that were not identified during this inspection may be damaged or have become damaged since the inspection was completed. If Category I or Category II friable materials are discovered prior to or during the demolition/renovation process, these materials must be abated prior to commencement of any demolition/renovation activities at the Subject Property.

Hazardous Materials

Hazardous Materials identified at the Subject Property and documented in Table 1 which require proper removal and disposal consist of the following items:

• Automobile Tires (8)

• Gallon Container Misc. Paint (10)

• Spray Can Misc. Paint (6)

REGULATORY REQUIREMENTS

A Notification of intent to Renovate/Demolish form must be filed with the Michigan Department of

Environmental Quality- Air Quality Division at least 10 working days prior to any renovation or demolition activities at a site.

The Notification of Intent to Renovate/Demolish form must also be completed and submitted to the

MIOSHA-Asbestos Program whenever demolition, encapsulation and/or renovation activities at a site involving greater than ten lineal feet and/or fifteen square feet of ACM will be completed.

Regulated asbestos containing materials per NESHAP (40 CFR Part 61) which falls into any of the following categories are ACM’s that must be removed prior to any renovation/demolition activities at the

Subject Property.

• Friable asbestos material.

• Category I non-friable ACM that has become friable.

• Category I non-friable ACM that will be or has been subjected to sanding, grinding, cutting, or abrading.

• Category II non-friable ACM that has a high probability of becoming or has become crumbled, pulverized, or reduced to powder by the forces expected to act on the material in the course of renovation or demolition operations.

Asbestos abatement should only be performed by a certified asbestos abatement contractor licensed to complete abatement work. The contractor must also follow the standards and requirements set forth per the OSHA Asbestos Standards for Construction (29 CFR 1926.1101) and the USEPA NESHAP (40 CFR

Part 61).

Additional information regarding the OSHA Asbestos Standards for Construction (29 CFR 1926.1101) and the USEPA NESHAP (40 CFR Part 61) can be obtained by contacting the associated agency below.

NESHAP Asbestos Program MIOSHA-CSHD-Asbestos Program

Department of Environmental Quality State of Michigan

Phone: 517-284-6777 Phone: 517-284-7680

Email: asbestos@michigan.gov

DISCLAIMER

Red Cedar Consulting performed destructive testing methods in an attempt to access and inspect all areas of the Building. Unfortunately, due to the age of construction along with multiple additions/renovations that may have been completed on the Building, additional inspections may be required if suspect ACM material not documented within this report is encountered during renovation/demolition activities.

This report was prepared at the request and for exclusive use by the City of Jackson and may not be reproduced or sold without written permission from Red Cedar Consulting.

We appreciate the opportunity to provide the requested services. Please contact us at (888) 449-4566 with any questions or concerns.

Sincerely, Red Cedar Consulting

Aaron Paquet

Michigan/EPA Certified Asbestos Building Inspector

(A30955)

©2025 Red Cedar Consulting, LLC.

Attachment A

APEX Research Laboratory Analytical Results

Certificate of Laboratory Analysis Test Method, Polarized Light Microscopy (PLM)

Report To: ARI Report # 25-119892 Mr. Aaron Paquet Date Collected: 09/18/25 Red Cedar Consulting Date Received: 09/23/25 P.O. Box 13216 Date Analyzed: 09/29/25 Lansing, MI 48901 Date Reported: 09/30/25

Sample Information Asbestos Type/Percent Non-Asbestos Material

Lab ID #: 119892 - 01 Asbestos Present: NO Fiberglass - 30%

Cust. #: MD-HM-01A No Asbestos Observed Other - 70% Material: Roofing M/L Location:

Appearance: black,fibrous,nonhomogenous Layer: 1 of 4

Lab ID #: 119892 - 01a Asbestos Present: NO Fiberglass - 30% Cust. #: MD-HM-01A No Asbestos Observed Other - 70% Material: Brown Shingle Location:

Appearance: black,fibrous,nonhomogenous Layer: 2 of 4

Lab ID #: 119892 - 01b Asbestos Present: NO Cellulose - 40% Cust. #: MD-HM-01A No Asbestos Observed Other - 60% Material: Grey Shingle Location:

Appearance: black,fibrous,nonhomogenous Layer: 3 of 4

For Layered Samples, each component will be analyzed and reported separately.

Robert T. Letarte Jr., Laboratory Director

Project: 1309/1311 Martin Luther King Dr.

Project #: Jackson, MI

Test Method EPA 40 CFR - Part 763 and/or EPA 600/R-93/116 was used to analyze the above samples. Matrix interference and/or resolution limits may yield false/negative results in certain circumstances. Suspect floor tiles containing <1% should be tested with SEM or TEM. This certificate of analysis relates only to the samples as submitted and to insure the integrity of the results, may only be reproduced in full. This certificate must not be used by the customer to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal Government. Liability limited to cost of analysis.

NVLAP Lab Code 102118-0

APEX Research Inc., 7717 Kensington Ct., Brighton, MI 48116

(734) 449-9990, Fax (734) 449-9991 Page 1 of 10

Report To: ARI Report # 25-119892 Mr. Aaron Paquet Date Collected: 09/18/25 Red Cedar Consulting Date Received: 09/23/25 P.O. Box 13216 Date Analyzed: 09/29/25 Lansing, MI 48901 Date Reported: 09/30/25

Project: 1309/1311 Martin Luther King Dr.

Project #: Jackson, MI

Sample Information Asbestos Type/Percent Non-Asbestos Material

Lab ID #: 119892 - 01c Asbestos Present: NO Cellulose - 60%

Cust. #: MD-HM-01A No Asbestos Observed Other - 40% Material: Felt Location:

Appearance: black,fibrous,homogenous Layer: 4 of 4

Lab ID #: 119892 - 02 Asbestos Present: NO Fiberglass - 30% Cust. #: MD-HM-01B No Asbestos Observed Other - 70% Material: Roofing M/L Location:

Appearance: black,fibrous,nonhomogenous Layer: 1 of 4

Lab ID #: 119892 - 02a Asbestos Present: NO Fiberglass - 30% Cust. #: MD-HM-01B No Asbestos Observed Other - 70% Material: Brown Shingle Location:

Appearance: black,fibrous,nonhomogenous Layer: 2 of 4

For Layered Samples, each component will be analyzed and reported separately.

Robert T. Letarte Jr., Laboratory Director

Test Method EPA 40 CFR - Part 763 and/or EPA 600/R-93/116 was used to analyze the above samples. Matrix interference and/or resolution limits may yield false/negative results in certain circumstances. Suspect floor tiles containing <1% should be tested with SEM or TEM. This certificate of analysis relates only to the samples as submitted and to insure the integrity of the results, may only be reproduced in full. This certificate must not be used by the customer to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal

(734) 449-9990, Fax (734) 449-9991 Page 2 of 10

Report To: ARI Report # 25-119892 Mr. Aaron Paquet Date Collected: 09/18/25 Red Cedar Consulting Date Received: 09/23/25 P.O. Box 13216 Date Analyzed: 09/29/25 Lansing, MI 48901 Date Reported: 09/30/25

Project: 1309/1311 Martin Luther King Dr.

Project #: Jackson, MI

Sample Information Asbestos Type/Percent Non-Asbestos Material

Lab ID #: 119892 - 02b Asbestos Present: NO Cellulose - 40%

Cust. #: MD-HM-01B No Asbestos Observed Other - 60% Material: Grey Shingle Location:

Appearance: black,fibrous,nonhomogenous Layer: 3 of 4

Lab ID #: 119892 - 02c Asbestos Present: NO Cellulose - 60% Cust. #: MD-HM-01B No Asbestos Observed Other - 40% Material: Felt Location:

Appearance: black,fibrous,homogenous Layer: 4 of 4

Lab ID #: 119892 - 03 Asbestos Present: NO Fiberglass - 30% Cust. #: MD-HM-02A No Asbestos Observed Other - 70% Material: Flat Roofing M/L Location:

Appearance: black,fibrous,nonhomogenous Layer: 1 of 2

For Layered Samples, each component will be analyzed and reported separately.

Robert T. Letarte Jr., Laboratory Director

Test Method EPA 40 CFR - Part 763 and/or EPA 600/R-93/116 was used to analyze the above samples. Matrix interference and/or resolution limits may yield false/negative results in certain circumstances. Suspect floor tiles containing <1% should be tested with SEM or TEM. This certificate of analysis relates only to the samples as submitted and to insure the integrity of the results, may only be reproduced in full. This certificate must not be used by the customer to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal

(734) 449-9990, Fax (734) 449-9991 Page 3 of 10

Report To: ARI Report # 25-119892 Mr. Aaron Paquet Date Collected: 09/18/25 Red Cedar Consulting Date Received: 09/23/25 P.O. Box 13216 Date Analyzed: 09/29/25 Lansing, MI 48901 Date Reported: 09/30/25

Project: 1309/1311 Martin Luther King Dr.

Project #: Jackson, MI

Sample Information Asbestos Type/Percent Non-Asbestos Material

Lab ID #: 119892 - 03a Asbestos Present: NO Cellulose - 60%

Cust. #: MD-HM-02A No Asbestos Observed Other - 40% Material: Felt Location:

Appearance: black,fibrous,homogenous Layer: 2 of 2

Lab ID #: 119892 - 04 Asbestos Present: NO Fiberglass - 30% Cust. #: MD-HM-02B No Asbestos Observed Other - 70% Material: Flat Roofing M/L Location:

Appearance: black,fibrous,nonhomogenous Layer: 1 of 2

Lab ID #: 119892 - 04a Asbestos Present: NO Cellulose - 60% Cust. #: MD-HM-02B No Asbestos Observed Other - 40% Material: Felt Location:

Appearance: black,fibrous,homogenous Layer: 2 of 2

For Layered Samples, each component will be analyzed and reported separately.

Robert T. Letarte Jr., Laboratory Director

Test Method EPA 40 CFR - Part 763 and/or EPA 600/R-93/116 was used to analyze the above samples. Matrix interference and/or resolution limits may yield false/negative results in certain circumstances. Suspect floor tiles containing <1% should be tested with SEM or TEM. This certificate of analysis relates only to the samples as submitted and to insure the integrity of the results, may only be reproduced in full. This certificate must not be used by the customer to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal

(734) 449-9990, Fax (734) 449-9991 Page 4 of 10

Report To: ARI Report # 25-119892 Mr. Aaron Paquet Date Collected: 09/18/25 Red Cedar Consulting Date Received: 09/23/25 P.O. Box 13216 Date Analyzed: 09/29/25 Lansing, MI 48901 Date Reported: 09/30/25

Project: 1309/1311 Martin Luther King Dr.

Project #: Jackson, MI

Sample Information Asbestos Type/Percent Non-Asbestos Material

Lab ID #: 119892 - 05 Asbestos Present: NO Cellulose - 10%

Cust. #: MD-HM-03A No Asbestos Observed Other - 90% Material: Roof Tar Location:

Appearance: black,fibrous,homogenous Layer: 1 of 1

Lab ID #: 119892 - 06 Asbestos Present: NO Cellulose - 10% Cust. #: MD-HM-03B No Asbestos Observed Other - 90% Material: Roof Tar Location:

Appearance: black,fibrous,homogenous Layer: 1 of 1

Lab ID #: 119892 - 07 Asbestos Present: NO Other - 100% Cust. #: MD-HM-04A No Asbestos Observed Material: Window Trim Caulk Location:

Appearance: grey,nonfibrous,homogenous Layer: 1 of 1

For Layered Samples, each component will be analyzed and reported separately.

Robert T. Letarte Jr., Laboratory Director

Test Method EPA 40 CFR - Part 763 and/or EPA 600/R-93/116 was used to analyze the above samples. Matrix interference and/or resolution limits may yield false/negative results in certain circumstances. Suspect floor tiles containing <1% should be tested with SEM or TEM. This certificate of analysis relates only to the samples as submitted and to insure the integrity of the results, may only be reproduced in full. This certificate must not be used by the customer to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal

(734) 449-9990, Fax (734) 449-9991 Page 5 of 10

Report To: ARI Report # 25-119892 Mr. Aaron Paquet Date Collected: 09/18/25 Red Cedar Consulting Date Received: 09/23/25 P.O. Box 13216 Date Analyzed: 09/29/25 Lansing, MI 48901 Date Reported: 09/30/25

Project: 1309/1311 Martin Luther King Dr.

Project #: Jackson, MI

Sample Information Asbestos Type/Percent Non-Asbestos Material

Lab ID #: 119892 - 08 Asbestos Present: NO Other - 100%

Cust. #: MD-HM-04B No Asbestos Observed Material: Window Trim Caulk Location:

Appearance: grey,nonfibrous,homogenous Layer: 1 of 1

Lab ID #: 119892 - 09 Asbestos Present: NO Other - 100% Cust. #: MD-HM-05A No Asbestos Observed Material: Floor Tar Location:

Appearance: black,nonfibrous,homogenous Layer: 1 of 2

Lab ID #: 119892 - 09a Asbestos Present: NO Other - 100% Cust. #: MD-HM-05A No Asbestos Observed Material: Mastic Location:

Appearance: black,nonfibrous,homogenous Layer: 2 of 2

For Layered Samples, each component will be analyzed and reported separately.

Robert T. Letarte Jr., Laboratory Director

Test Method EPA 40 CFR - Part 763 and/or EPA 600/R-93/116 was used to analyze the above samples. Matrix interference and/or resolution limits may yield false/negative results in certain circumstances. Suspect floor tiles containing <1% should be tested with SEM or TEM. This certificate of analysis relates only to the samples as submitted and to insure the integrity of the results, may only be reproduced in full. This certificate must not be used by the customer to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal

(734) 449-9990, Fax (734) 449-9991 Page 6 of 10

Report To: ARI Report # 25-119892 Mr. Aaron Paquet Date Collected: 09/18/25 Red Cedar Consulting Date Received: 09/23/25 P.O. Box 13216 Date Analyzed: 09/29/25 Lansing, MI 48901 Date Reported: 09/30/25

Project: 1309/1311 Martin Luther King Dr.

Project #: Jackson, MI

Sample Information Asbestos Type/Percent Non-Asbestos Material

Lab ID #: 119892 - 10 Asbestos Present: NO Other - 100%

Cust. #: MD-HM-05B No Asbestos Observed Material: Floor Tar Location:

Appearance: black,nonfibrous,homogenous Layer: 1 of 2

Lab ID #: 119892 - 10a Asbestos Present: NO Other - 100% Cust. #: MD-HM-05B No Asbestos Observed Material: Mastic Location:

Appearance: black,nonfibrous,homogenous Layer: 2 of 2

Lab ID #: 119892 - 11 Asbestos Present: NO Cellulose - 90% Cust. #: MD-HM-06A No Asbestos Observed Other - 10% Material: Fiberboard Location:

Appearance: brown,fibrous,homogenous Layer: 1 of 2

For Layered Samples, each component will be analyzed and reported separately.

Robert T. Letarte Jr., Laboratory Director

Test Method EPA 40 CFR - Part 763 and/or EPA 600/R-93/116 was used to analyze the above samples. Matrix interference and/or resolution limits may yield false/negative results in certain circumstances. Suspect floor tiles containing <1% should be tested with SEM or TEM. This certificate of analysis relates only to the samples as submitted and to insure the integrity of the results, may only be reproduced in full. This certificate must not be used by the customer to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal

(734) 449-9990, Fax (734) 449-9991 Page 7 of 10

Report To: ARI Report # 25-119892 Mr. Aaron Paquet Date Collected: 09/18/25 Red Cedar Consulting Date Received: 09/23/25 P.O. Box 13216 Date Analyzed: 09/29/25 Lansing, MI 48901 Date Reported: 09/30/25

Project: 1309/1311 Martin Luther King Dr.

Project #: Jackson, MI

Sample Information Asbestos Type/Percent Non-Asbestos Material

Lab ID #: 119892 - 11a Asbestos Present: NO Cellulose - 1%

Cust. #: MD-HM-06A No Asbestos Observed Other - 99% Material: Glue Location:

Appearance: brown,nonfibrous,homogenous Layer: 2 of 2

Lab ID #: 119892 - 12 Asbestos Present: NO Cellulose - 80% Cust. #: MD-HM-06B No Asbestos Observed Other - 20% Material: Fiberboard Location:

Appearance: brown,fibrous,homogenous Layer: 1 of 2

Lab ID #: 119892 - 12a Asbestos Present: NO Cellulose - 1% Cust. #: MD-HM-06B No Asbestos Observed Other - 99% Material: Glue Location:

Appearance: brown,nonfibrous,homogenous Layer: 2 of 2

For Layered Samples, each component will be analyzed and reported separately.

Robert T. Letarte Jr., Laboratory Director

Test Method EPA 40 CFR - Part 763 and/or EPA 600/R-93/116 was used to analyze the above samples. Matrix interference and/or resolution limits may yield false/negative results in certain circumstances. Suspect floor tiles containing <1% should be tested with SEM or TEM. This certificate of analysis relates only to the samples as submitted and to insure the integrity of the results, may only be reproduced in full. This certificate must not be used by the customer to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal

(734) 449-9990, Fax (734) 449-9991 Page 8 of 10

Report To: ARI Report # 25-119892 Mr. Aaron Paquet Date Collected: 09/18/25 Red Cedar Consulting Date Received: 09/23/25 P.O. Box 13216 Date Analyzed: 09/29/25 Lansing, MI 48901 Date Reported: 09/30/25

Project: 1309/1311 Martin Luther King Dr.

Project #: Jackson, MI

Sample Information Asbestos Type/Percent Non-Asbestos Material

Lab ID #: 119892 - 13 Asbestos Present: NO Cellulose - 1%

Cust. #: MD-HS-01A No Asbestos Observed Other - 99% Material: Stucco on Mesh Location:

Appearance: white,nonfibrous,homogenous Layer: 1 of 1

Lab ID #: 119892 - 14 Asbestos Present: NO Cellulose - 1% Cust. #: MD-HS-01B No Asbestos Observed Other - 99% Material: Stucco on Mesh Location:

Appearance: white,nonfibrous,homogenous Layer: 1 of 1

Lab ID #: 119892 - 15 Asbestos Present: NO Cellulose - 1% Cust. #: MD-HS-01C No Asbestos Observed Other - 99% Material: Stucco on Mesh Location:

Appearance: white,nonfibrous,homogenous Layer: 1 of 1

For Layered Samples, each component will be analyzed and reported separately.

Robert T. Letarte Jr., Laboratory Director

Test Method EPA 40 CFR - Part 763 and/or EPA 600/R-93/116 was used to analyze the above samples. Matrix interference and/or resolution limits may yield false/negative results in certain circumstances. Suspect floor tiles containing <1% should be tested with SEM or TEM. This certificate of analysis relates only to the samples as submitted and to insure the integrity of the results, may only be reproduced in full. This certificate must not be used by the customer to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal

(734) 449-9990, Fax (734) 449-9991 Page 9 of 10

Report To: ARI Report # 25-119892 Mr. Aaron Paquet Date Collected: 09/18/25 Red Cedar Consulting Date Received: 09/23/25 P.O. Box 13216 Date Analyzed: 09/29/25 Lansing, MI 48901 Date Reported: 09/30/25

Project: 1309/1311 Martin Luther King Dr.

Project #: Jackson, MI

Sample Information Asbestos Type/Percent Non-Asbestos Material

Lab ID #: 119892 - 16 Asbestos Present: NO Cellulose - 1%

Cust. #: MD-HS-01D No Asbestos Observed Other - 99% Material: Stucco on Mesh Location:

Appearance: white,nonfibrous,homogenous Layer: 1 of 1

Lab ID #: 119892 - 17 Asbestos Present: NO Cellulose - 1% Cust. #: MD-HS-01E No Asbestos Observed Other - 99% Material: Stucco on Mesh Location:

Appearance: white,nonfibrous,homogenous Layer: 1 of 1

Lab ID #: Asbestos Present:

Cust. #:

Material:

Location:

Appearance:

Layer: of

For Layered Samples, each component will be analyzed and reported separately.

Robert T. Letarte Jr., Laboratory Director

Test Method EPA 40 CFR - Part 763 and/or EPA 600/R-93/116 was used to analyze the above samples. Matrix interference and/or resolution limits may yield false/negative results in certain circumstances. Suspect floor tiles containing <1% should be tested with SEM or TEM. This certificate of analysis relates only to the samples as submitted and to insure the integrity of the results, may only be reproduced in full. This certificate must not be used by the customer to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal

(734) 449-9990, Fax (734) 449-9991 Page 10 of 10

Attachment B Figure 1 Site Diagram

Figure 1 Site Diagram

Note: Figure created by Red Cedar Consulting Asbestos Sample Locations 1309-1311 MLK Dr.

-Not To Scale- Jackson, MI

Tables

Table 1 - Summary of Hazardous Materials, 1309 Martin Luther King Jr. Dr. Jackson, Michigan

Hazardous Materials Description and Location

Location Material Description Quantity

Interior Automobile Tires 8

Interior Gallon Container Misc. Paint 10

Interior Spray Can Misc. Paint 6

Table 2 - Summary of Sample Descriptions and Asbestos Laboratory Results, 1309 Martin Luther King Jr. Dr. Jackson, Michigan

Sample Number Sample Description Friable Material

Type Material

Classification

% Asbestos Laboratory

Result Sample Location Approx. Material

Quantity

MD-HM-01A Roofing Multilayer No M Category I ND/ND/ND/ND NE Exterior NA

MD-HM-01B Roofing Multilayer No M Category I ND/ND/ND/ND SW Exterior NA

MD-HM-02A Flat Roofing Multilayer No M Category I ND/ND NW Exterior NA MD-HM-02B Flat Roofing Multilayer No M Category I ND/ND SE Exterior NA

MD-HM-03A Roof Tar No M Category I ND Building Exterior NA

MD-HM-03B Roof Tar No M Category I ND Building Exterior NA MD-HM-04A Window Trim Caulk No M Category II ND W Exterior NA

MD-HM-04B Window Trim Caulk No M Category II ND E Exterior NA

MD-HM-05A Floor Tar/Mastic No M Category I ND/ND Bathroom 1 NA MD-HM-05B Floor Tar/Mastic No M Category I ND/ND Bathroom 2 NA

MD-HM-06A Fiberboard with Glue Yes M Category II ND/ND Interior NA

MD-HM-06B Fiberboard with Glue Yes M Category II ND/ND Interior NA MD-HS-01A Stucco on Mesh No S Category II ND NW Exterior NA

MD-HS-01B Stucco on Mesh No S Category II ND W Exterior NA

MD-HS-01C Stucco on Mesh No S Category II ND SW Exterior NA MD-HS-01D Stucco on Mesh No S Category II ND NE Exterior NA

MD-HS-01E Stucco on Mesh No S Category II ND E Exterior NA

Notes:

Material Types Abbreviations

M = Miscellaneous building material NQ = Not quantified TSI = Thermal System Insulation NA = Not Analyzed S = Surfacing Material ND = Not detected. Laboratory result is less than 1 % asbestos PC = Point Count Analysis lin. ft. = linear feet CH = Chrysotile Asbestos sq. ft. = square feet

Asbestos Containing Material (ACM) is defined as any material containing more than 1 percent asbestos as determined utilizing Polarized Light Microscopy.

Table 3 - Summary of Presumed Asbestos Containing Materials, 1309 Martin Luther King Jr. Dr. Jackson, Michigan

Asbestos Containing Material Description and Location

Location Material Description Friable Condition Material Type Approx. Quantity

No Presumed Asbestos Containing Materials Identified

Notes:

Material Types Abbreviations

M = Miscellaneous building material lin. ft. = linear feet TSI = Thermal System Insulation sq. ft. = square feet S = Surfacing Material

Table 4 - Summary of All Asbestos Containing Materials, 1309 Martin Luther King Jr. Dr. Jackson, Michigan

Exterior/Interior - Asbestos Containing Materials

Location Material Description Friable Approx. Quantity

No Asbestos Containing Materials Identified

Notes:

Abbreviations lin. ft. = linear feet

sq. ft. = square feet

Shaded/Bolded = Friable ACM and any Category I and Category II non-friable ACM that has a high probability of becoming crumbled, pulverized, or reduced to powder by the demolition or renovation activities that must be properly abated prior to commencement of any demolition/renovation activities.

Demolition/renovation activities completed with intact Category I non-friable ACM are regulated by OSHA and must be completed following the OSHA Asbestos Standards for Construction (29 CFR 1926.1101) which limits employee exposure to asbestos.

Please note that a Negative Pressure Enclosure must be utilized during abatement when Site Conditions Warrant. Examples of these conditions include the abatement of Plaster and Vermiculite insulation, HVAC Duct Wrap in Poor Condition, and Air-O-Cell/Mag Pipe Wrap. Conditions outside of these should be assessed on a case by case basis during the Asbestos Abatement Contractors site walk and Work Plan Preparation.