Arc Flash Analysis Oct 11 2010.pdf
PDF 3 MB Posted
- Attached to
- Arc Flash Analysis Federal contract opportunity
- Solicitation number
- 12505B21R0014
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| RFIs.pdf | ||
| SF-30 - Amendment 01.pdf | ||
| SOW - Revised 16JUNE2021.pdf | ||
| One Line Drawings for Buildings 20 and 24.pdf | ||
| Wage Determination.pdf | ||
| SF-1449.pdf | ||
| Statement of Work.pdf | ||
| Building Numbers with info.xlsx | XLSX spreadsheet | |
| Arc Flash Analysis Oct 2007.pdf | ||
| Items added since last Arc Flash Study.pdf | ||
| Arc Flash Analysis Oct 12 2010.pdf | ||
| Site Map.pdf |
Show all 12
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
United States Department of Agriculture Agricultural Research Service
Final Submittal Task Order No. AG-5114-D-09-0098
AG-5114-D-09-0096
Contract No. AG-3K15-53-3K15-4-1500 Order Date. 9/26/09 BE Project No. 0413-08-19
0413-08-20
Arc Flash Analysis and Labeling:
480V & 120V NCAH Ames, IA
BY: ARCHITECT CONSULTANT
Bailey Edward architecture KJWW Engineers
116 N Pelham 2882 106th Street Rhinelander, WI 54501 Des Moines, IA 50322
715-362-3662 515-344-4302
DATE: October 11, 2010
Table of Contents
1. EXECUTIVE SUMMARY
A. INTRODUCTION
B. OBJECTIVES
C. RESULTS, DEFICIENCIES AND RECOMMENDATIONS
D. METHODOLOGY
E. IEEE 1584 CALCULATION METHODOLOGY
2. ARC FLASH HAZARD RESULTS
A. ARC FLASH HAZARD CATEGORY TABLE
B. ARC FLASH HAZARD LABELING
APPENDIX A: PTW ELECTRICAL COMPONENT INPUT DATA REPORTS
North Campus Input Data Report South Campus Input Data Report
APPENDIX B: PTW SHORT CIRCUIT ANALYSIS DATA REPORT
North Campus Short Circuit Analysis Report South Campus Short Circuit Analysis Report
APPENDIX C: ARC FLASH HAZARD TABLE
North Campus Arc Flash Hazard Table South Campus Arc Flash Hazard Table
APPENDIX D: PTW ONE-LINE DIAGRAMS
North Campus:
1-7_153 UTL&GEN
2-7_154T1&T2 3-7_154T3&T4
4-7_E-MCC-1&2
5-7_153T5&T6 6-7_154T7&T8 7-7_156T9&T10 9_E1.03A 9-E1.01-A
BLDG 5
BLDG 10
BLDG 530
NORTH LOOP 4160
South Campus:
11-46
BLDG A1-A9
BLDG C1-C5
EMCC
MDP-1
MDP-2
MDP-3
PANEL CDP
USDA SOUTH LOOP
APPENDIX E: Label Printing Spreadsheet
North Campus Danger Labels Spreadsheet North Campus Warning Labels Spreadsheet South Campus Danger Labels Spreadsheet South Campus Warning Labels Spreadsheet
APPENDIX F: Sample Labels
Arc Flash Hazard Analysis & Labeling: 4801V & 120V, Ames, IA
October 11, 2010
1. EXECUTIVE SUMMARY
A. INTRODUCTION
KJWW Engineering was contracted to provide an arc flash hazard analysis for the USDA
Campus located in Ames, Iowa. The analysis was done during the time period of
December 2009 – June 2010 and reflects the conditions of the electrical power system at the time of the report. Input data used in the analysis was acquired by KJWW
Engineering and provided by others. Data was obtained from existing drawings, shop drawings, site visits, manufacturer’s published information, and the electrical contractor.
B. OBJECTIVES
Provide an arc-flash hazard analysis to determine the incident energy levels at specified working distance from selected electrical equipment, which can be used to select appropriate Personal Protective Equipment (PPE) to be used when working within the flash protection boundary. The flash protection boundary is the area within which a worker without proper protection would expect to receive second degree burns at a minimum. The potential for harm increases as the arc flash incident level increases.
This report does not purport to provide short circuit analysis or protective device coordination.
C. RESULTS, DEFICIENCIES AND RECOMMENDATIONS
1) Arc-flash Hazard Analysis Results and Deficiencies:
The results of the arc-flash hazard analysis show that the electrical equipment evaluated have incident energy levels that do not exceed 40 cal/cm2 with the following exceptions:
North Campus:
a) ALLIENT SERVICE FEED DANGEROUS
b) E-MCC-15 DANGEROUS
c) E-MCC-16 DANGEROUS
d) E-MCC-3 DANGEROUS
e) E-MCC-4 DANGEROUS
f) E-SWGR-1(A) DANGEROUS
g) E-SWGR-1(B) DANGEROUS
h) E-SWGR-11 BUS A DANGEROUS
i) E-SWGR-11 BUS B DANGEROUS
j) FP-1 DANGEROUS
k) MDP DANGEROUS
l) XF2-154T3 SEC DANGEROUS
m) XF2-154T4 SEC DANGEROUS
n) XF2-154T5(E-MCC-3) SEC DANGEROUS
o) XF2-154T6(E-MCC-4) SEC DANGEROUS
p) XF2-154T7 SEC DANGEROUS
q) XF2-154T8 SEC DANGEROUS
r) XF2-156T10(E-MCC-16) SEC DANGEROUS
s) XF2-156T9 SEC DANGEROUS
South Campus:
a) ATS-1 DANGEROUS
b) EMCC DANGEROUS
c) MDP(C8) DANGEROUS
d) MDP-B1 DANGEROUS
e) MDP-B2 DANGEROUS
f) MDS-C2-A DANGEROUS
g) MDS-C3 DANGEROUS
h) MDS-C4 DANGEROUS
i) XF2-T1(B1,B2) SEC DANGEROUS
j) XF2-T10(C2) Sec DANGEROUS
k) XF2-T11(C3) Sec DANGEROUS
l) XF2-T12(C4) SEC DANGEROUS
m) XF2-T8(C8) SEC DANGEROUS
NFPA 70E does not explicitly prohibit work at locations with incident energy levels above
40 cal/cm2 (Class 4). The potential for non-burn injuries from the arc blast (internal injuries, hearing damage, etc.) are a significant hazard at high-energy locations. KJWW
Engineering does not recommend work on energized electrical equipment in locations with incident energy levels above 40 cal/cm2. KJWW Engineering recommends that work in these locations be done when the equipment is de-energized and placed in an electrically safe work condition.
Other noted electrical deficiencies:
During the power system study items were noted that may be code compliance issues, equipment is missing proper labels and potential maintenance issues. These items were beyond the scope of KJWW Engineers work but were mentioned to bring them to the attention of the facility staff.
The following items or deficiencies were noted:
a) 1 engraved label needed on the circuit breaker for the 75 KVAR capacitor bank in MDP1 in building 400.
b) 1 engraved label needed on the circuit breaker for the 75 KVAR capacitor bank in MDP2 in building 400.
c) 2 blank breaker filler plates needed in panel OP12C in building 400 (Type:
Square D, QO, Load Center).
d) 1 blank breaker filler plate needed in panel LP-3 in building 400 (Type:
Westinghouse, DM).
e) 2 blank breaker filler plates needed in panel MDP outside building A2 (Type:
Square D).
2) Recommendations:
The arc-flash hazard labels should be placed on the electrical equipment and the analysis should be incorporated into the facilities operating and maintenance procedures.
Assumptions:
The following assumptions were made in preparing the power system study, and result in worst-case conservative results:
a) The double-ended equipment was modeled with the tie-breaker open and the main breakers separately connected to their respective utility sources.
b) For fault calculations, system voltage was modeled at the no load value with transformer taps modeled.
c) All motors were assumed to be running.
d) Motors were modeled as shown on the Power Tools for Windows (PTW) study one line diagrams and in the PTW INPUT DATA REPORT.
e) Motors were modeled as standard PTW induction motor components.
D. METHODOLOGY
The PTW Arc Flash software module was used to calculate the arc flash incident energy and flash boundary at each device under study. The Arc Flash Hazard Analysis software module uses equations based on both NFPA 70E and IEEE 1584. The software calculates the arcing fault current at each bus in the model based on the available fault current determined during the short-circuit analysis and the equations in IEEE 1584. The arc duration is determined from the calculated arc fault current and the time-current characteristics of the upstream protective device. The arc fault current and fault duration are inputs into the IEEE 1584 equations to calculate the incident energy and flash-protection boundary. For low voltage (<1000 volts) buses, a second arcing fault current value is calculated to be 85% of the arcing fault value originally calculated and a second device operating time is determined, per IEEE 1584. The incident energy and protection boundary are calculated using both values and the worst case result is report in the summary.
The calculated incident energy levels are based on the “working distance”, defined as the distance from the fault to the worker’s head and torso. IEEE 1584 recommendations of
36 inches for medium voltage equipment, 24 inches for low-voltage switchgear and 18 inches for panelboards and motor control centers were assumed. The flash protection boundary distance is calculated as the distance from the equipment where the incident energy equals 1.2 cal/cm2. The 1.2 cal/cm2 is the accepted energy level that causes the onset of second degree burns on bare skin. PPE is required for working inside the flash protection boundary.
Induction motor contribution to the fault current was considered in the analysis.
Contribution from motors of 50 horsepower and above was assumed to be zero after 5 cycles, if the protective device had not already opened.
The values shown in the table for low-voltage switchboards, panelboards and motor control centers assumes that the fault is cleared by the upstream protective device. A fault on the incoming line terminals could propagate throughout the enclosure, since they do not have internal barriers or compartments. This assumption creates conservative calculation results.
The maximum trip delay time was set at 2 seconds in this study. That a worker exposed to an arcing fault will quickly move away from the source of the arc if physically possible, is recognized in IEEE 1584 Annex B.1.2 in the statement “… two seconds is a reasonable maximum time…”.
Buses with incident energy greater the 40 cal/cm2 are classified hazard risk category
“DANGEROUS” and NFPA 70E does not define protective clothing classes that excesses
Category 4. KJWW Engineering does not recommend energized work at any location where the arc-flash incident energy exceeds 40 cal/cm2 .
The results are based on the assumption that protective devices are in working order and will operate within their specified tolerances to clear faults from the system.
The results in this arc-flash hazard study are based solely on the IEEE 1584 calculation procedures.
E. IEEE 1584 CALCULATION METHODOLOGY
The IEEE Standard 1584-2002 IEEE Guide for Performing Arc-Flash Hazard Calculations presents a comprehensive methodology for arc-flash hazards. This standard based on extensive testing carried out on low-voltage and medium voltage systems (up to 15kV).
IEEE 1584 is applicable only to three-phase arcing faults and it does not consider the effects of arc blast or other by-products and arcing fault (sound level, ionized gases, molten metal, toxic vapors, etc.)
2. ARC FLASH HAZARD RESULTS
The arc-flash hazard analysis and recommended PPE levels are not substitutes for safe work practices. Protection from arc flash can be provided by working only on circuits or equipment that has been place in an electrically safe work condition, including lock-out/tag-out, voltage testing and grounding. NFPA 70E 130.7(A) fine print note No. 1 states that burn injuries can occur even when adequate PPE is employed, and recommended PPE may provide little or no protection against arc blast and its effects.
A. ARC FLASH HAZARD CATEGORY TABLE
TABLE HEADING DEFINITIONS
Hazard Risk Category – Category 0, 1, 2, 3, 4 or Dangerous!
Warning Label Text – Heading of WARNING or DANGER
Incident Energy (cal/cm2) – the amount of energy impressed on a surface, a certain distance from the source, generated during an electrical arc event.
Arc Flash Protection Boundary - distance from the equipment where the incident energy equals 1.2 cal/cm2. PPE is required for working inside the flash protection boundary
Shock Hazard - Voltage with covers and doors open.
Limited Approach Boundary - a boundary around exposed live parts that may not be crossed by an “unqualified” person unless accompanied by “qualified” persons.
Restricted Approach Boundary - is the area near the exposed live parts that may be crossed only by “qualified” persons using appropriate shock prevention techniques and equipment.
Prohibited Approach Boundary - is the area near exposed live parts that may be crossed only by “qualified” persons using the same protection as if direct contact with live parts is planned.
ARC FLASH HAZARD CATEGORY TABLE
Hazard
Risk
Category
Warning
Label Text
Incident
Energy
(cal/cm2)
Arc Flash
Protection
Boundary
Shock
Hazard
Voltage
Limited
Approach
Boundary
Restricted
Approach
Boundary
Prohibited
Approach
Boundary
0 WARNING 0.0 – 1.2 inches Vac inches inches Inches
1 WARNING 1.21 – 4.0 inches Vac inches inches Inches
2 WARNING 4.1 – 8.0 inches Vac inches inches Inches
3 WARNING 8.1 – 25.0 inches Vac inches inches Inches
4 WARNING 25.1 – 40.0 inches Vac inches inches Inches
Dangerous DANGER 40.0 Arc Flash Incident Energy Exceeds the Rating of Category 4 PPE
Do not work on live!
B. ARC FLASH HAZARD LABELING
PERSONAL PROTECTIVE EQUIPMENT TABLE
Hazard
Risk
Category
Protective Clothing
Description
Protective Equipment Minimum Arc
Rating of
PPE
Clothing
Layers
Non-melting, or untreated natural fiber
FR Protective Equipment
Head/Eye/Hearing Protection
Hand & Arm protection
N/A
FR Clothing
Head/Eye/Hearing Protection
Foot protection
Head/Eye/Hearing Protection
1 or 2
Head/Eye/Hearing Protection
2 or 3
Head/Eye/Hearing Protection
3 or more
Dangerous No FR Category found for > 40 cal/cm2
Do not work on live! Do not work on live!
N/A
Refer to NFPA 70E-2009 Table 130.7(C)(10) for additional requirements and notes.
REFERENCES
A. ABBREVIATIONS
A Amps, Amperes (RMS symmetrical)
AFIE Arc flash incident energy (cal/cm2)
AIC Amps interrupting capacity
ANG Phase angle
ANSI American National Standard Institute
ATPV Protective clothing arc rating
ATS Automatic transfer switch
CB Circuit breaker
CT Current transformer
DP Distribution panel
DS Disconnect switch
FLA Full load Amps
FPB Flash protection boundary
GEN Generator
HP Horsepower
Isc Short-circuit current
ICEA Insulated Cable Engineers Association
IEEE Institute of Electrical and Electronic Engineers
KA kilo-amps kVA kiloVolt-Amperes kW kilowatts
L-L Line to line
LRA Locked rotor amps
LSIG Long time, Short time, Instantaneous, Ground fault trip
MCC Motor control center
NEC National Electrical Code (NFPA 70)
NEMA National Electrical Manufacturers Association
OCPD Overcurrent protective device
O.L. Overload relay
PF Power factor
PPE Personal Protective Equipment
PU Per Unit
R Resistance
RMS Root-Means-Square
SCA Short-circuit amps
SCCR Short-circuit current rating
S.F. Service factor
Sym Symmetrical
TCC Time current curve
THD Total Harmonic Distortion
UL Underwriters Laboratories, Inc.
V Volts line to line (RMS sym)
WCR Withstand current rating
X Reactance
X/R Reactance / Resistance ratio
Z Impedance
%Z Percent Impedance
B. MANUFACTURERS ABBREVIATION
A-B ALLEN-BRADLEY
ABB ASEA BROWN BOVERI
ASCO AUTOMATIC SWITCH CO.
BAS BASLER
BUSS BUSSMANN
COOP COOPER
C-H CUTLER-HAMMER
FPE FEDERAL PACIFIC ELECTRIC
G&W G&W ELECTRIC
GE GENRAL ELECTRIC
GS GOULD SHWMUT
ITE I-T-E IMPERIAL
LIT LITTELFUSE
ME McGRAW EDISON
MG MERLIN GERIN
RTE RTE CORP.
RUSS RUSSELECTRIC
S&C S&C ELECTRIC
SEL SCHWEITZER ENGINEERING LABS
SIE SIEMENS
SQD SQUARE D
T-B THOMAS BETTS
WEST WESTINGHOUSE
ZEN GE-ZENITH CONTROLS
C. RESOURCES
1) Owner’s staff:
2) KJWW Engineering staff:
3) Electrical Contractor:
4) Utility Company
5) Equipment manufacturer’s representative
6) IEEE 1584 Guide for Performing Arc-Flash Hazard Calculations
7) National Electrical Code NEC 70E–2009 Standard for Electrical Safety in the
Work Place.
8) SKM Power Tools for Windows User Manual
9) Existing drawings
Appendix A PTW Electrical Component
Input Data Reports
Aug 06, 2010 14:40:08 Page 1
Project Name: north allient utility(Base Project)
ALL INFORMATION PRESENTED IS FOR REVIEW, APPROVAL, INTERPRETATION,
AND APPLICATION BY A REGISTERED ENGINEER ONLY.
SKM DISCLAIMS ANY RESPONSIBILITY AND LIABILITY RESULTING
FROM THE USE AND INTERPRETATION OF THIS SOFTWARE.
CAPTOR (Computer Aided Plotting for Time Overcurrent Reporting)
COPYRIGHT SKM SYSTEMS ANALYSIS, INC. 1983-2007
Device Name: PD-11-LA TCC Name:
Bus Name: 11-LA Bus Voltage: 208.0V Function Name: Phase Manufacturer: GE Description: 60-125A Type: TMQB AIC Rating: 42kA Fault Duty: 3012.2A Frame: TMQB 240V 125A Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0 Trip: 125A Setting: 1) Fixed
Device Name: PD-11-LB TCC Name:
Bus Name: 11-LA Bus Voltage: 208.0V Function Name: Phase Manufacturer: GE Description: 15-100A Type: FC, 2 & 3-Pole 240V AIC Rating: 42kA Fault Duty: 3012.2A Frame: FCS 240V 70A Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0 Trip: 70A Setting: 1) Fixed
Device Name: ATS#3 2 -IN TCC Name:
Bus Name: ATS#3(E-LP-2) Bus Voltage: 480.0V Function Name: Phase Manufacturer:
Description:
Type:
AIC Rating: 0kA Fault Duty: 15731.2A Frame: Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0
FLA: 0.00A
Setting:
Device Name: ATS-3 1-IN TCC Name:
Bus Name: ATS#3(E-LP-2) Bus Voltage: 480.0V Function Name: Phase Manufacturer:
Description:
Type:
AIC Rating: 0kA Fault Duty: 15731.2A Frame: Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0
FLA: 0.00A
Setting:
Aug 06, 2010 14:40:08 Page 2
Device Name: ATS#4 1-IN TCC Name:
Bus Name: ATS#4(T8(E-PP-2)) Bus Voltage: 480.0V Function Name: Phase Manufacturer:
Description:
Type:
AIC Rating: 0kA Fault Duty: 15731.2A Frame: Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0
FLA: 0.00A
Setting:
Device Name: ATS#4 2-IN TCC Name:
Bus Name: ATS#4(T8(E-PP-2)) Bus Voltage: 480.0V Function Name: Phase Manufacturer:
Description:
Type:
AIC Rating: 0kA Fault Duty: 15731.2A Frame: Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0
FLA: 0.00A
Setting:
Device Name: ATS#6 1-IN TCC Name:
Bus Name: ATS#6 Bus Voltage: 480.0V Function Name: Phase Manufacturer:
Description:
Type:
AIC Rating: 0kA Fault Duty: 13521.5A Frame: Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0
FLA: 0.00A
Setting:
Device Name: ATS#6 2-IN TCC Name:
Bus Name: ATS#6 Bus Voltage: 480.0V Function Name: Phase Manufacturer:
Description:
Type:
AIC Rating: 0kA Fault Duty: 13521.5A Frame: Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0
Aug 06, 2010 14:40:08 Page 3
Device Name: PD-0344 TCC Name:
Bus Name: ATS-1 Bus Voltage: 480.0V Function Name: Phase Manufacturer:
Description:
Type:
AIC Rating: 0kA Fault Duty: 37147.1A Frame: Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0
FLA: 0.00A
Setting:
Device Name: PD-0345 TCC Name:
Bus Name: ATS-1 Bus Voltage: 480.0V Function Name: Phase Manufacturer:
Description:
Type:
AIC Rating: 0kA Fault Duty: 37147.1A Frame: Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0
FLA: 0.00A
Setting:
Device Name: PD-ATS-1 IN-SW1 TCC Name:
Bus Name: ATS-1_1 Bus Voltage: 480.0V Function Name: Phase Manufacturer:
Description:
Type:
AIC Rating: 0kA Fault Duty: 27822.7A Frame: Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0
FLA: 0.00A
Setting:
Device Name: PD-ATS-1 IN-SW2 TCC Name:
Bus Name: ATS-1_1 Bus Voltage: 480.0V Function Name: Phase Manufacturer:
Description:
Type:
AIC Rating: 0kA Fault Duty: 27822.7A Frame: Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0
Aug 06, 2010 14:40:08 Page 4
Device Name: PD-0346 TCC Name:
Bus Name: ATS-2 Bus Voltage: 480.0V Function Name: Phase Manufacturer:
Description:
Type:
AIC Rating: 0kA Fault Duty: 19838.0A Frame: Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0
FLA: 0.00A
Setting:
Device Name: PD-0347 TCC Name:
Bus Name: ATS-2 Bus Voltage: 480.0V Function Name: Phase Manufacturer:
Description:
Type:
AIC Rating: 0kA Fault Duty: 19838.0A Frame: Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0
FLA: 0.00A
Setting:
Device Name: PD-ATS-2 IN-SW4 TCC Name:
Bus Name: ATS-2_1 Bus Voltage: 480.0V Function Name: Phase Manufacturer:
Description:
Type:
AIC Rating: 0kA Fault Duty: 27010.6A Frame: Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0
FLA: 0.00A
Setting:
Device Name: PD-ATS-2 IN-SW3 TCC Name:
Bus Name: ATS-2_1 Bus Voltage: 480.0V Function Name: Phase Manufacturer:
Description:
Type:
AIC Rating: 0kA Fault Duty: 27010.6A Frame: Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0
Aug 06, 2010 14:40:09 Page 5
Device Name: PD-0356 TCC Name:
Bus Name: ATS-5 Bus Voltage: 480.0V Function Name: Phase Manufacturer:
Description:
Type:
AIC Rating: 0kA Fault Duty: 23162.8A Frame: Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0
FLA: 0.00A
Setting:
Device Name: PD-0357 TCC Name:
Bus Name: ATS-5 Bus Voltage: 480.0V Function Name: Phase Manufacturer:
Description:
Type:
AIC Rating: 0kA Fault Duty: 23162.8A Frame: Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0
FLA: 0.00A
Setting:
Device Name: CB-BOILER DISCONNECT TCC Name:
Bus Name: BOILER DISCONNECT Bus Voltage: 208.0V Function Name: Phase Manufacturer: SQUARE D Description: 250-400A Type: Q4 AIC Rating: 25kA Fault Duty: 9166.7A Frame: Q4 240V 400A Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0 Trip: 400A Setting: 1) Thermal Curve
2) INST LO (2000A)
Device Name: PD-XFMR T1 TCC Name:
Bus Name: BUS-0045 Bus Voltage: 13200.0V Function Name: Phase Manufacturer: GE Description: 1E-100E Type: 9F60 EJ0-1, 15.5kV E-Rated AIC Rating: 38kA Fault Duty: 10135.7A Cartridge: EJO-1, 80E 15500V 80A Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0 Size: 80A
Aug 06, 2010 14:40:09 Page 6
Device Name: PD-FUSED CUT OUT TCC Name:
Bus Name: BUS-0427 Bus Voltage: 12470.0V Function Name: Phase Manufacturer: S&C Description: 15E-200E Slow Speed Type: SM-4, 14.4kV E-Rated AIC Rating: 13kA Fault Duty: 1337.0A Cartridge: SM-4, 15E 12470V 15A Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0 Size: 15A
Device Name: PD-FUSED CUT-OUT TCC Name:
Bus Name: BUS-0428 Bus Voltage: 12470.0V Function Name: Phase Manufacturer: S&C Description: 15E-200E Slow Speed Type: SM-4, 14.4kV E-Rated AIC Rating: 13kA Fault Duty: 1376.4A Cartridge: SM-4, 40E 12470V 40A Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0 Size: 40A
Device Name: PD-0486 TCC Name:
Bus Name: BUS-0457 Bus Voltage: 4160.0V Function Name: Phase Manufacturer: S&C Description: 15E-200E Slow Speed Type: SM-4, 7.2kV E-Rated AIC Rating: 17kA Fault Duty: 11112.4A Cartridge: SM-4, 200E 4160V 200A Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0 Size: 200A
Device Name: PD-ATS-1 SW1 TCC Name:
Bus Name: BUS-SW1 Bus Voltage: 480.0V Function Name: Phase Manufacturer: SQUARE D Description: LSI, 400-5000A, ANSI Type: Masterpact NW, 5.0 & 6.0 A/P/H AIC Rating: 100kA Override:85 ShortTime:85 Fault Duty: 29725.0A Frame: NW08H3 508V 800A Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0 Sensor: 600A Plug:
Setting: 1) LTPU/LTD (A 0.4-1.0 1 (600A) 4
2) STPU (1.5-10 x LTPU) 3 (1800A)
3) STD (INST-0.4) 0.4 I^2 t Out
4) INST (NW**N1,H1,H2) 4 (2400A)
Aug 06, 2010 14:40:09 Page 7
Device Name: PD-BUS TIE BKR TCC Name:
Bus Name: BUS-SW1 Bus Voltage: 480.0V Function Name: Phase Manufacturer: SQUARE D Description: LSI, 400-5000A, ANSI Type: Masterpact NW, 5.0 & 6.0 A/P/H AIC Rating: 100kA Override:85 ShortTime:85 Fault Duty: 29725.0A Frame: NW20H3 508V 2000A Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0 Sensor: 2000A Plug:
Setting: 1) LTPU/LTD (A 0.4-1.0 0.7 (1400A) 0.5
2) STPU (1.5-10 x LTPU) 5 (7000A)
3) STD (INST-0.4) 0.4 I^2 t Out
4) INST (NW**N1,H1,H2) 4 (8000A)
Device Name: PD-DSP1-1/XFMR T1-1 TCC Name:
Bus Name: BUS-SW1 Bus Voltage: 480.0V Function Name: Phase Manufacturer: SQUARE D Description: LSI, 400-5000A, ANSI Type: Masterpact NW, 5.0 & 6.0 A/P/H AIC Rating: 100kA Override:85 ShortTime:85 Fault Duty: 29725.0A Frame: NW08H3 508V 800A Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0 Sensor: 400A Plug:
Setting: 1) LTPU/LTD (A 0.4-1.0 0.9 (360A) 4
2) STPU (1.5-10 x LTPU) 10 (3600A)
3) STD (INST-0.4) 0.4 I^2 t Out
4) INST (NW**N1,H1,H2) 12 (4800A)
Device Name: PD-DSP1-3 TCC Name:
Bus Name: BUS-SW1 Bus Voltage: 480.0V Function Name: Phase Manufacturer: SQUARE D Description: LSI, 100-250AS, ANSI Type: Masterpact NW, 5.0 & 6.0 A/P/H AIC Rating: 85kA Override:24 ShortTime:85 Fault Duty: 29725.0A Frame: NW08H2 508V 800A Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0 Sensor: 250A Plug:
Setting: 1) LTPU (A);LTD 0.9 (225A) 2
2) STPU 8 (1800A)
3) STD 0.4 I^2 t Out
4) INST 10 (2500A)
Aug 06, 2010 14:40:09 Page 8
Device Name: PD-DSP1-4 TCC Name:
Bus Name: BUS-SW1 Bus Voltage: 480.0V Function Name: Phase Manufacturer: SQUARE D Description: LSI, 400-5000A, ANSI Type: Masterpact NW, 5.0 & 6.0 A/P/H AIC Rating: 100kA Override:85 ShortTime:85 Fault Duty: 29725.0A Frame: NW08H3 508V 800A Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0 Sensor: 400A Plug:
Setting: 1) LTPU/LTD (A 0.4-1.0 1 (400A) 0.5
2) STPU (1.5-10 x LTPU) 5 (2000A)
3) STD (INST-0.4) 0.4 I^2 t Out
4) INST (NW**N1,H1,H2) 6 (2400A)
Device Name: PD-SW1 TCC Name:
Bus Name: BUS-SW1 Bus Voltage: 480.0V Function Name: Phase Manufacturer: SQUARE D Description: LSI, 400-5000A, ANSI Type: Masterpact NW, 5.0 & 6.0 A/P/H AIC Rating: 100kA Override:85 ShortTime:85 Fault Duty: 29725.0A Frame: NW20H3 508V 2000A Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0 Sensor: 2000A Plug:
Setting: 1) LTPU/LTD (A 0.4-1.0 1 (2000A) 0.5
2) STPU (1.5-10 x LTPU) 5 (10000A)
3) STD (INST-0.4) 0.4 I^2 t Out
4) INST (NW**N1,H1,H2) 6 (12000A)
Device Name: PD-SW1(RL) TCC Name:
Bus Name: BUS-SW1 Bus Voltage: 480.0V Function Name: Phase Manufacturer:
Description:
Type: Class Desc:
AIC Rating: N/A Fault Duty: 29725.0A Current Rating: 0A / 0A Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0 Setting:
Test Points: @2.0X, 0.000s @5.0X, 0.000s @10.0X, 0.000s
Aug 06, 2010 14:40:09 Page 9
Device Name: PD-ATS-1 SW2 TCC Name:
Bus Name: BUS-SW2 Bus Voltage: 480.0V Function Name: Phase Manufacturer: SQUARE D Description: LSI, 400-5000A, ANSI Type: Masterpact NW, 5.0 & 6.0 A/P/H AIC Rating: 100kA Override:85 ShortTime:85 Fault Duty: 33024.9A Frame: NW08H3 508V 800A Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0 Sensor: 600A Plug:
Setting: 1) LTPU/LTD (A 0.4-1.0 1 (600A) 4
2) STPU (1.5-10 x LTPU) 3 (1800A)
3) STD (INST-0.4) 0.4 I^2 t Out
4) INST (NW**N1,H1,H2) 4 (2400A)
Device Name: PD-DSP2-1/XFMR T2-1 TCC Name:
Bus Name: BUS-SW2 Bus Voltage: 480.0V Function Name: Phase Manufacturer: SQUARE D Description: LSI, 400-5000A, ANSI Type: Masterpact NW, 5.0 & 6.0 A/P/H AIC Rating: 100kA Override:85 ShortTime:85 Fault Duty: 33024.9A Frame: NW08H3 508V 800A Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0 Sensor: 400A Plug:
Setting: 1) LTPU/LTD (A 0.4-1.0 0.8 (320A) 4
2) STPU (1.5-10 x LTPU) 10 (3200A)
3) STD (INST-0.4) 0.4 I^2 t Out
4) INST (NW**N1,H1,H2) 12 (4800A)
Device Name: PD-DSP2-3 TCC Name:
Bus Name: BUS-SW2 Bus Voltage: 480.0V Function Name: Phase Manufacturer: SQUARE D Description: LSI, 400-5000A, ANSI Type: Masterpact NW, 5.0 & 6.0 A/P/H AIC Rating: 100kA Override:85 ShortTime:85 Fault Duty: 33024.9A Frame: NW08H3 508V 800A Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0 Sensor: 800A Plug:
Setting: 1) LTPU/LTD (A 0.4-1.0 1 (800A) 0.5
2) STPU (1.5-10 x LTPU) 5 (4000A)
4) INST (NW**N1,H1,H2) 2 (1600A)
Aug 06, 2010 14:40:09 Page 10
Device Name: PD-DSP2-4 TCC Name:
Bus Name: BUS-SW2 Bus Voltage: 480.0V Function Name: Phase Manufacturer: SQUARE D Description: LSI, 100-250AS, ANSI Type: Masterpact NW, 5.0 & 6.0 A/P/H AIC Rating: 85kA Override:24 ShortTime:85 Fault Duty: 33024.9A Frame: NW08H2 508V 800A Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0 Sensor: 250A Plug:
Setting: 1) LTPU (A);LTD 0.9 (225A) 2
2) STPU 8 (1800A)
3) STD 0.4 I^2 t Out
4) INST 10 (2500A)
Device Name: PD-DSP2-5 TCC Name:
Bus Name: BUS-SW2 Bus Voltage: 480.0V Function Name: Phase Manufacturer: SQUARE D Description: LSI, 400-5000A, ANSI Type: Masterpact NW, 5.0 & 6.0 A/P/H AIC Rating: 100kA Override:85 ShortTime:85 Fault Duty: 33024.9A Frame: NW08H3 508V 800A Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0 Sensor: 400A Plug:
Setting: 1) LTPU/LTD (A 0.4-1.0 1 (400A) 0.5
2) STPU (1.5-10 x LTPU) 5 (2000A)
3) STD (INST-0.4) 0.4 I^2 t Out
4) INST (NW**N1,H1,H2) 6 (2400A)
Device Name: PD-SW2 TCC Name:
Bus Name: BUS-SW2 Bus Voltage: 480.0V Function Name: Phase Manufacturer: SQUARE D Description: LSI, 400-5000A, ANSI Type: Masterpact NW, 5.0 & 6.0 A/P/H AIC Rating: 100kA Override:85 ShortTime:85 Fault Duty: 33024.9A Frame: NW20H3 508V 2000A Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0 Sensor: 2000A Plug:
Setting: 1) LTPU/LTD (A 0.4-1.0 1 (2000A) 0.5
2) STPU (1.5-10 x LTPU) 5 (10000A)
4) INST (NW**N1,H1,H2) 6 (12000A)
Aug 06, 2010 14:40:09 Page 11
Device Name: PD-SW2(RL) TCC Name:
Bus Name: BUS-SW2 Bus Voltage: 480.0V Function Name: Phase Manufacturer:
Description:
Type: Class Desc:
AIC Rating: N/A Fault Duty: 33024.9A Current Rating: 0A / 0A Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0 Setting:
Test Points: @2.0X, 0.000s @5.0X, 0.000s @10.0X, 0.000s
Device Name: PD-ATS-2 SW3 TCC Name:
Bus Name: BUS-SW3 Bus Voltage: 480.0V Function Name: Phase Manufacturer: SQUARE D Description: LSI, 400-5000A, ANSI Type: Masterpact NW, 5.0 & 6.0 A/P/H AIC Rating: 100kA Override:85 ShortTime:85 Fault Duty: 28763.0A Frame: NW08H3 508V 800A Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0 Sensor: 600A Plug:
Setting: 1) LTPU/LTD (A 0.4-1.0 1 (600A) 4
2) STPU (1.5-10 x LTPU) 3 (1800A)
3) STD (INST-0.4) 0.4 I^2 t Out
4) INST (NW**N1,H1,H2) 4 (2400A)
Device Name: PD-BUS TIE BKR0 TCC Name:
Bus Name: BUS-SW3 Bus Voltage: 480.0V Function Name: Phase Manufacturer: SQUARE D Description: LSI, 400-5000A, ANSI Type: Masterpact NW, 5.0 & 6.0 A/P/H AIC Rating: 100kA Override:85 ShortTime:85 Fault Duty: 28763.0A Frame: NW20H3 508V 2000A Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0 Sensor: 2000A Plug:
Setting: 1) LTPU/LTD (A 0.4-1.0 0.7 (1400A) 0.5
2) STPU (1.5-10 x LTPU) 5 (7000A)
4) INST (NW**N1,H1,H2) 4 (8000A)
Aug 06, 2010 14:40:09 Page 12
Device Name: PD-DSP3-1/ T3-1 TCC Name:
Bus Name: BUS-SW3 Bus Voltage: 480.0V Function Name: Phase Manufacturer: SQUARE D Description: LSI, 400-5000A, ANSI Type: Masterpact NW, 5.0 & 6.0 A/P/H AIC Rating: 100kA Override:85 ShortTime:85 Fault Duty: 28763.0A Frame: NW08H3 508V 800A Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0 Sensor: 400A Plug:
Setting: 1) LTPU/LTD (A 0.4-1.0 0.8 (320A) 4
2) STPU (1.5-10 x LTPU) 10 (3200A)
3) STD (INST-0.4) 0.4 I^2 t Out
4) INST (NW**N1,H1,H2) 12 (4800A)
Device Name: PD-DSP3-3 TCC Name:
Bus Name: BUS-SW3 Bus Voltage: 480.0V Function Name: Phase Manufacturer: SQUARE D Description: LSI, 100-250AS, ANSI Type: Masterpact NW, 5.0 & 6.0 A/P/H AIC Rating: 85kA Override:24 ShortTime:85 Fault Duty: 28763.0A Frame: NW08H2 508V 800A Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0 Sensor: 250A Plug:
Setting: 1) LTPU (A);LTD 0.9 (225A) 2
2) STPU 8 (1800A)
3) STD 0.4 I^2 t Out
4) INST 10 (2500A)
Device Name: PD-DSP3-4 TCC Name:
Bus Name: BUS-SW3 Bus Voltage: 480.0V Function Name: Phase Manufacturer: SQUARE D Description: LSI, 400-5000A, ANSI Type: Masterpact NW, 5.0 & 6.0 A/P/H AIC Rating: 100kA Override:85 ShortTime:85 Fault Duty: 28763.0A Frame: NW08H3 508V 800A Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0 Sensor: 400A Plug:
Setting: 1) LTPU/LTD (A 0.4-1.0 1 (400A) 0.5
2) STPU (1.5-10 x LTPU) 3 (1200A)
4) INST (NW**N1,H1,H2) 4 (1600A)
Aug 06, 2010 14:40:09 Page 13
Device Name: PD-SW3 TCC Name:
Bus Name: BUS-SW3 Bus Voltage: 480.0V Function Name: Phase Manufacturer: SQUARE D Description: LSI, 400-5000A, ANSI Type: Masterpact NW, 5.0 & 6.0 A/P/H AIC Rating: 100kA Override:85 ShortTime:85 Fault Duty: 28763.0A Frame: NW20H3 508V 2000A Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0 Sensor: 2000A Plug:
Setting: 1) LTPU/LTD (A 0.4-1.0 1 (2000A) 0.5
2) STPU (1.5-10 x LTPU) 5 (10000A)
3) STD (INST-0.4) 0.4 I^2 t Out
4) INST (NW**N1,H1,H2) 6 (12000A)
Device Name: PD-SW3(RL) TCC Name:
Bus Name: BUS-SW3 Bus Voltage: 480.0V Function Name: Phase Manufacturer:
Description:
Type: Class Desc:
AIC Rating: N/A Fault Duty: 28763.0A Current Rating: 0A / 0A Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0 Setting:
Test Points: @2.0X, 0.000s @5.0X, 0.000s @10.0X, 0.000s
Device Name: PD-ATS-2 SW4 TCC Name:
Bus Name: BUS-SW4 Bus Voltage: 480.0V Function Name: Phase Manufacturer: SQUARE D Description: LSI, 400-5000A, ANSI Type: Masterpact NW, 5.0 & 6.0 A/P/H AIC Rating: 100kA Override:85 ShortTime:85 Fault Duty: 31194.0A Frame: NW08H3 508V 800A Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0 Sensor: 600A Plug:
Setting: 1) LTPU/LTD (A 0.4-1.0 1 (600A) 4
2) STPU (1.5-10 x LTPU) 3 (1800A)
4) INST (NW**N1,H1,H2) 4 (2400A)
Aug 06, 2010 14:40:10 Page 14
Device Name: PD-DSP4-1/XFMR T4-1 TCC Name:
Bus Name: BUS-SW4 Bus Voltage: 480.0V Function Name: Phase Manufacturer: SQUARE D Description: LSI, 400-5000A, ANSI Type: Masterpact NW, 5.0 & 6.0 A/P/H AIC Rating: 100kA Override:85 ShortTime:85 Fault Duty: 31194.0A Frame: NW08H3 508V 800A Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0 Sensor: 400A Plug:
Setting: 1) LTPU/LTD (A 0.4-1.0 0.8 (320A) 4
2) STPU (1.5-10 x LTPU) 10 (3200A)
3) STD (INST-0.4) 0.4 I^2 t Out
4) INST (NW**N1,H1,H2) 12 (4800A)
Device Name: PD-DSP4-3 TCC Name:
Bus Name: BUS-SW4 Bus Voltage: 480.0V Function Name: Phase Manufacturer: SQUARE D Description: LSI, 400-5000A, ANSI Type: Masterpact NW, 5.0 & 6.0 A/P/H AIC Rating: 100kA Override:85 ShortTime:85 Fault Duty: 31194.0A Frame: NW08H3 508V 800A Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0 Sensor: 800A Plug:
Setting: 1) LTPU/LTD (A 0.4-1.0 1 (800A) 0.5
2) STPU (1.5-10 x LTPU) 5 (4000A)
3) STD (INST-0.4) 0.4 I^2 t Out
4) INST (NW**N1,H1,H2) 6 (4800A)
Device Name: PD-DSP4-4 TCC Name:
Bus Name: BUS-SW4 Bus Voltage: 480.0V Function Name: Phase Manufacturer: SQUARE D Description: LSI, 100-250AS, ANSI Type: Masterpact NW, 5.0 & 6.0 A/P/H AIC Rating: 85kA Override:24 ShortTime:85 Fault Duty: 31194.0A Frame: NW08H2 508V 800A Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0 Sensor: 250A Plug:
Setting: 1) LTPU (A);LTD 0.9 (225A) 2
2) STPU 8 (1800A)
3) STD 0.4 I^2 t Out
4) INST 10 (2500A)
Aug 06, 2010 14:40:10 Page 15
Device Name: PD-DSP4-5 TCC Name:
Bus Name: BUS-SW4 Bus Voltage: 480.0V Function Name: Phase Manufacturer: SQUARE D Description: LSI, 400-5000A, ANSI Type: Masterpact NW, 5.0 & 6.0 A/P/H AIC Rating: 100kA Override:85 ShortTime:85 Fault Duty: 31194.0A Frame: NW08H3 508V 800A Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0 Sensor: 400A Plug:
Setting: 1) LTPU/LTD (A 0.4-1.0 1 (400A) 0.5
2) STPU (1.5-10 x LTPU) 5 (2000A)
3) STD (INST-0.4) 0.4 I^2 t Out
4) INST (NW**N1,H1,H2) 6 (2400A)
Device Name: PD-SW4 TCC Name:
Bus Name: BUS-SW4 Bus Voltage: 480.0V Function Name: Phase Manufacturer: SQUARE D Description: LSI, 400-5000A, ANSI Type: Masterpact NW, 5.0 & 6.0 A/P/H AIC Rating: 100kA Override:85 ShortTime:85 Fault Duty: 31194.0A Frame: NW20H3 508V 2000A Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0 Sensor: 2000A Plug:
Setting: 1) LTPU/LTD (A 0.4-1.0 1 (2000A) 0.5
2) STPU (1.5-10 x LTPU) 5 (10000A)
3) STD (INST-0.4) 0.4 I^2 t Out
4) INST (NW**N1,H1,H2) 6 (12000A)
Device Name: PD-SW4(RL) TCC Name:
Bus Name: BUS-SW4 Bus Voltage: 480.0V Function Name: Phase Manufacturer:
Description:
Type: Class Desc:
AIC Rating: N/A Fault Duty: 31194.0A Current Rating: 0A / 0A Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0 Setting:
Test Points: @2.0X, 0.000s @5.0X, 0.000s @10.0X, 0.000s
Aug 06, 2010 14:40:10 Page 16
Device Name: CB-CH-4 TCC Name:
Bus Name: CH-4 Bus Voltage: 4160.0V Function Name: Phase Manufacturer: CUTLER-HAMMER Description: Motor Protection Type: MP-3000 Class Desc: MP-3000 Fault Duty: 14288.4A Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0 Current Rating: 200A / 5A FLA: 100.00A Setting: 1) UTC (pu of FLA) 1.05 (105A) Test Points: @2.0X, 54.000s
2) Time in sec @LRC=6.0 6 @5.0X, 8.640s
3) IOC (pu of FLA) 7 (700A) @10.0X, 2.160s
4) IOCSD (cycles) 2 (cycles)
Device Name: CB-CH-5 TCC Name:
Bus Name: CH-5 Bus Voltage: 4160.0V Function Name: Phase Manufacturer: CUTLER-HAMMER Description: Motor Protection Type: MP-3000 Class Desc: MP-3000 Fault Duty: 14690.0A Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0 Current Rating: 200A / 5A FLA: 100.00A Setting: 1) UTC (pu of FLA) 1.05 (105A) Test Points: @2.0X, 54.000s
2) Time in sec @LRC=6.0 6 @5.0X, 8.640s
3) IOC (pu of FLA) 7 (700A) @10.0X, 2.160s
4) IOCSD (cycles) 2 (cycles)
Device Name: CB-CH-8(RLY) TCC Name:
Bus Name: CH-8 Bus Voltage: 4160.0V Function Name: Phase Manufacturer: CUTLER-HAMMER Description: Motor Protection Type: MP-3000 Class Desc: MP-3000 Fault Duty: 14230.6A Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0 Current Rating: 200A / 5A FLA: 100.00A Setting: 1) UTC (pu of FLA) 1.05 (105A) Test Points: @2.0X, 54.000s
2) Time in sec @LRC=6.0 6 @5.0X, 8.640s
3) IOC (pu of FLA) 7 (700A) @10.0X, 2.160s
4) IOCSD (cycles) 2 (cycles)
Device Name: CB-EX. AIR COMP-3 TCC Name:
Bus Name: CT-2 MCC Bus Voltage: 480.0V Function Name: Phase Manufacturer: CUTLER-HAMMER Description: 100-400A Type: HKD AIC Rating: 65kA Fault Duty: 21764.3A Frame: HKD 480V 400A Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0 Trip: 400A Setting: 1) Thermal Curve (Fixed
2) INST (5-10 x Trip) 10 (4000A)
Aug 06, 2010 14:40:10 Page 17
Device Name: PD-DC-4-1-1(MCB) TCC Name:
Bus Name: DC-4-1-1 Bus Voltage: 208.0V Function Name: Phase Manufacturer: SQUARE D Description: 15-125A Type: ED AIC Rating: 25kA Fault Duty: 9440.2A Frame: ED 240V 125A Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0 Trip: 125A Setting: 1) Fixed
Device Name: PD-DC-4-1-1(MCB)0 TCC Name:
Bus Name: DC-4-1-2 Bus Voltage: 208.0V Function Name: Phase Manufacturer: SQUARE D Description: 15-125A Type: ED AIC Rating: 25kA Fault Duty: 9440.2A Frame: ED 240V 125A Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0 Trip: 125A Setting: 1) Fixed
Device Name: PD-DC-4-1-3(MCB) TCC Name:
Bus Name: DC-4-1-3 Bus Voltage: 208.0V Function Name: Phase Manufacturer: SQUARE D Description: 15-125A Type: ED AIC Rating: 25kA Fault Duty: 9440.2A Frame: ED 240V 125A Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0 Trip: 125A Setting: 1) Fixed
Device Name: PD-DC2-1-1(MCB) TCC Name:
Bus Name: DC2-1-1 Bus Voltage: 208.0V Function Name: Phase Manufacturer: SQUARE D Description: 15-125A Type: ED AIC Rating: 18kA Fault Duty: 9507.8A Frame: ED 480V 125A Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0 Trip: 125A Setting: 1) Fixed
Aug 06, 2010 14:40:10 Page 18
Device Name: PD-DC2-1-1(MCB)0 TCC Name:
Bus Name: DC2-1-2 Bus Voltage: 208.0V Function Name: Phase Manufacturer: SQUARE D Description: 15-125A Type: ED AIC Rating: 18kA Fault Duty: 9507.8A Frame: ED 480V 125A Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0 Trip: 125A Setting: 1) Fixed
Device Name: PD-BOILER TCC Name:
Bus Name: DS-1 Bus Voltage: 208.0V Function Name: Phase Manufacturer: GOULD SHAWMUT Description: 15-600A Type: TRS, 600V Class RK5 AIC Rating: 200kA Fault Duty: 9356.6A Cartridge: TRS 600V 400A Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0 Size: 400A
Device Name: PD-DS-2 TCC Name:
Bus Name: DS-2 Bus Voltage: 208.0V Function Name: Phase Manufacturer: GOULD SHAWMUT Description: 15-600A Type: TRS, 600V Class RK5 AIC Rating: 200kA Fault Duty: 14993.2A Cartridge: TRS 600V 600A Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0 Size: 600A
Device Name: PD-AHU-A-3(DS) TCC Name:
Bus Name: DS-AHU-A-3 Bus Voltage: 480.0V Function Name: Phase Manufacturer:
Description:
Type:
AIC Rating: 0kA Fault Duty: 27713.0A Frame: Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0
FLA: 0.00A
Setting:
Device Name: PD-AHU-C-3(DS) TCC Name:
Bus Name: DS-AHU-C-3 Bus Voltage: 480.0V Function Name: Phase Manufacturer:
Description:
Type:
AIC Rating: 0kA Fault Duty: 26000.2A Frame: Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0
Aug 06, 2010 14:40:10 Page 19
Device Name: PD-AHU-E-2(DS) TCC Name:
Bus Name: DS-AHU-E-2 Bus Voltage: 480.0V Function Name: Phase Manufacturer:
Description:
Type:
AIC Rating: 0kA Fault Duty: 27303.7A Frame: Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0
FLA: 0.00A
Setting:
Device Name: PD-EAU-A-2(DS) TCC Name:
Bus Name: DS-EAU-A-2 Bus Voltage: 480.0V Function Name: Phase Manufacturer:
Description:
Type:
AIC Rating: 0kA Fault Duty: 25991.9A Frame: Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0
FLA: 0.00A
Setting:
Device Name: PD-EAU-A-4DS) TCC Name:
Bus Name: DS-EAU-A-4 Bus Voltage: 480.0V Function Name: Phase Manufacturer:
Description:
Type:
AIC Rating: 0kA Fault Duty: 25991.9A Frame: Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0
FLA: 0.00A
Setting:
Device Name: PD-EAU-A-6(DS) TCC Name:
Bus Name: DS-EAU-A-6 Bus Voltage: 480.0V Function Name: Phase Manufacturer:
Description:
Type:
AIC Rating: 0kA Fault Duty: 27713.0A Frame: Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0
Aug 06, 2010 14:40:10 Page 20
Device Name: PD-EAU-C-2(DS) TCC Name:
Bus Name: DS-EAU-C-2 Bus Voltage: 480.0V Function Name: Phase Manufacturer:
Description:
Type:
AIC Rating: 0kA Fault Duty: 25991.9A Frame: Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0
FLA: 0.00A
Setting:
Device Name: PD-EAU-C-4(DS) TCC Name:
Bus Name: DS-EAU-C-4 Bus Voltage: 480.0V Function Name: Phase Manufacturer:
Description:
Type:
AIC Rating: 0kA Fault Duty: 26000.2A Frame: Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0
FLA: 0.00A
Setting:
Device Name: PD-EAU-E-2(DS) TCC Name:
Bus Name: DS-EAU-E-2 Bus Voltage: 480.0V Function Name: Phase Manufacturer:
Description:
Type:
AIC Rating: 0kA Fault Duty: 25991.9A Frame: Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0
FLA: 0.00A
Setting:
Device Name: PD-EAU-E-4(DS) TCC Name:
Bus Name: DS-EAU-E-4 Bus Voltage: 480.0V Function Name: Phase Manufacturer:
Description:
Type:
AIC Rating: 0kA Fault Duty: 25991.9A Frame: Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0
Aug 06, 2010 14:40:10 Page 21
Device Name: PD-DSP1-1 TCC Name:
Bus Name: DSP1-1 Bus Voltage: 208.0V Function Name: Phase Manufacturer: SQUARE D Description: 125-1200A, Inst 5-10 Type: MH AIC Rating: 65kA Fault Duty: 9923.6A Frame: MH 240V 1000A Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0 Trip: 800A Setting: 1) Thermal Curve (Fixed
2) INST (5-10 x Trip) 5.0 (4000A)
Device Name: PD-PP1-1-1 TCC Name:
Bus Name: DSP1-1 Bus Voltage: 208.0V Function Name: Phase Manufacturer: SQUARE D Description: 15-125A Type: ED AIC Rating: 18kA Fault Duty: 9923.6A Frame: ED 480V 125A Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0 Trip: 125A Setting: 1) Fixed
Device Name: PD-PP1-1-2 TCC Name:
Bus Name: DSP1-1 Bus Voltage: 208.0V Function Name: Phase Manufacturer: SQUARE D Description: 15-125A Type: ED AIC Rating: 18kA Fault Duty: 9923.6A Frame: ED 480V 125A Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0 Trip: 125A Setting: 1) Fixed
Device Name: PD-PP1-1-3 TCC Name:
Bus Name: DSP1-1 Bus Voltage: 208.0V Function Name: Phase Manufacturer: SQUARE D Description: 15-125A Type: ED AIC Rating: 18kA Fault Duty: 9923.6A Frame: ED 480V 125A Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0
Aug 06, 2010 14:40:10 Page 22
Device Name: PD-PP1-1-4 TCC Name:
Bus Name: DSP1-1 Bus Voltage: 208.0V Function Name: Phase Manufacturer: SQUARE D Description: 15-125A Type: ED AIC Rating: 18kA Fault Duty: 9923.6A Frame: ED 480V 125A Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0 Trip: 125A Setting: 1) Fixed
Device Name: PD-PP1-1-5 TCC Name:
Bus Name: DSP1-1 Bus Voltage: 208.0V Function Name: Phase Manufacturer: SQUARE D Description: 15-125A Type: ED AIC Rating: 18kA Fault Duty: 9923.6A Frame: ED 480V 125A Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0 Trip: 125A Setting: 1) Fixed
Device Name: PD-LP1-2-1 TCC Name:
Bus Name: DSP1-2 Bus Voltage: 480.0V Function Name: Phase Manufacturer: SQUARE D Description: 110-250A Type: KC AIC Rating: 65kA Fault Duty: 27122.9A Frame: KC 480V 225A Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0 Trip: 225A Setting: 1) Thermal Curve
2) INST LO (1125A)
Device Name: PD-LP1-2-2 TCC Name:
Bus Name: DSP1-2 Bus Voltage: 480.0V Function Name: Phase Manufacturer: SQUARE D Description: 110-250A Type: KC AIC Rating: 65kA Fault Duty: 27122.9A Frame: KC 480V 225A Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0 Trip: 225A Setting: 1) Thermal Curve
2) INST LO (1125A)
Aug 06, 2010 14:40:11 Page 23
Device Name: PD-XMFR T1-2 TCC Name:
Bus Name: DSP1-2 Bus Voltage: 480.0V Function Name: Phase Manufacturer: SQUARE D Description: 15-100A Type: FC AIC Rating: 65kA Fault Duty: 27122.9A Frame: FC 480V 50A Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0 Trip: 50A Setting: 1) Fixed
Device Name: PD-DC2-1-1 TCC Name:
Bus Name: DSP2-1 Bus Voltage: 208.0V Function Name: Phase Manufacturer: SQUARE D Description: 15-125A Type: ED AIC Rating: 18kA Fault Duty: 10067.1A Frame: ED 480V 125A Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0 Trip: 125A Setting: 1) Fixed
Device Name: PD-DC2-1-1 0 TCC Name:
Bus Name: DSP2-1 Bus Voltage: 208.0V Function Name: Phase Manufacturer: SQUARE D Description: 15-125A Type: ED AIC Rating: 18kA Fault Duty: 10067.1A Frame: ED 480V 125A Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0 Trip: 125A Setting: 1) Fixed
Device Name: PD-DSP2-1 TCC Name:
Bus Name: DSP2-1 Bus Voltage: 208.0V Function Name: Phase Manufacturer: SQUARE D Description: 125-1200A, Inst 5-10 Type: MH AIC Rating: 65kA Fault Duty: 10067.1A Frame: MH 240V 1000A Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0 Trip: 800A Setting: 1) Thermal Curve (Fixed
2) INST (5-10 x Trip) 5.0 (4000A)
Aug 06, 2010 14:40:11 Page 24
Device Name: PD-PP2-1-3 TCC Name:
Bus Name: DSP2-1 Bus Voltage: 208.0V Function Name: Phase Manufacturer: SQUARE D Description: 70-250A Type: KA AIC Rating: 42kA Fault Duty: 10067.1A Frame: KA 240V 250A Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0 Trip: 175A Setting: 1) Thermal Curve
2) INST LO (875A)
Device Name: PD-PP2-1-4 TCC Name:
Bus Name: DSP2-1 Bus Voltage: 208.0V Function Name: Phase Manufacturer: SQUARE D Description: 15-125A Type: ED AIC Rating: 18kA Fault Duty: 10067.1A Frame: ED 480V 125A Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0 Trip: 125A Setting: 1) Fixed
Device Name: PD-UPS-A TCC Name:
Bus Name: DSP2-1 Bus Voltage: 208.0V Function Name: Phase Manufacturer: SQUARE D Description: 15-125A Type: ED AIC Rating: 18kA Fault Duty: 10067.1A Frame: ED 480V 125A Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0 Trip: 125A Setting: 1) Fixed
Device Name: PD-AHU-A-1 TCC Name:
Bus Name: DSP2-3 Bus Voltage: 480.0V Function Name: Phase Manufacturer: SQUARE D Description: 15-150A Type: HL AIC Rating: 100kA Fault Duty: 32214.2A Frame: HL 480V 150A Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0 Trip: 150A
Aug 06, 2010 14:40:11 Page 25
Device Name: PD-AHU-A-2 TCC Name:
Bus Name: DSP2-3 Bus Voltage: 480.0V Function Name: Phase Manufacturer: SQUARE D Description: 15-150A Type: HL AIC Rating: 100kA Fault Duty: 32214.2A Frame: HL 480V 150A Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0 Trip: 150A Setting: 1) Fixed
Device Name: PD-AHU-C-1 TCC Name:
Bus Name: DSP2-3 Bus Voltage: 480.0V Function Name: Phase Manufacturer: SQUARE D Description: 15-125A Type: EJ AIC Rating: 65kA Fault Duty: 32214.2A Frame: EJ 480V 70A Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0 Trip: 70A Setting: 1) Fixed
Device Name: PD-AHU-C-2 TCC Name:
Bus Name: DSP2-3 Bus Voltage: 480.0V Function Name: Phase Manufacturer: SQUARE D Description: 15-125A Type: EJ AIC Rating: 65kA Fault Duty: 32214.2A Frame: EJ 480V 70A Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0 Trip: 70A Setting: 1) Fixed
Device Name: PD-AHU-E-1 TCC Name:
Bus Name: DSP2-3 Bus Voltage: 480.0V Function Name: Phase Manufacturer: SQUARE D Description: 15-125A Type: EJ AIC Rating: 65kA Fault Duty: 32214.2A Frame: EJ 480V 125A Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0
Aug 06, 2010 14:40:11 Page 26
Device Name: PD-EAU-A-3 TCC Name:
Bus Name: DSP2-3 Bus Voltage: 480.0V Function Name: Phase Manufacturer: SQUARE D Description: 15-125A Type: EJ AIC Rating: 65kA Fault Duty: 32214.2A Frame: EJ 480V 80A Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0 Trip: 80A Setting: 1) Fixed
Device Name: PD-EAU-A-5 TCC Name:
Bus Name: DSP2-3 Bus Voltage: 480.0V Function Name: Phase Manufacturer: SQUARE D Description: 15-150A Type: HL AIC Rating: 100kA Fault Duty: 32214.2A Frame: HL 480V 150A Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0 Trip: 150A Setting: 1) Fixed
Device Name: PD-EAU-C-1 TCC Name:
Bus Name: DSP2-3 Bus Voltage: 480.0V Function Name: Phase Manufacturer: SQUARE D Description: 15-125A Type: EJ AIC Rating: 65kA Fault Duty: 32214.2A Frame: EJ 480V 70A Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0 Trip: 70A Setting: 1) Fixed
Device Name: PD-EAU-C-3 TCC Name:
Bus Name: DSP2-3 Bus Voltage: 480.0V Function Name: Phase Manufacturer: SQUARE D Description: 15-125A Type: EJ AIC Rating: 65kA Fault Duty: 32214.2A Frame: EJ 480V 70A Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0 Trip: 70A
Aug 06, 2010 14:40:11 Page 27
Device Name: PD-EAU-E-3 TCC Name:
Bus Name: DSP2-3 Bus Voltage: 480.0V Function Name: Phase Manufacturer: SQUARE D Description: 15-125A Type: EJ AIC Rating: 65kA Fault Duty: 32214.2A Frame: EJ 480V 70A Curve Multiplier: 1 Time Multiplier: 1 Time Adder: 0 Trip: 70A Setting: 1) Fixed
Device Name: PD-DS-EAU-E-1 TCC Name:
Bus Name: DSP2-4 Bus Voltage: 480.0V Function Name: Phase Manufacturer: SQUARE D Description: 15-125A Type: EJ AIC Rating: 65kA Fault Duty: 31009.3A Frame: EJ 480V 80A