Approved ELEC-105 COBBLESTONE-OPD23-04.pdf

PDF 212 KB Posted

Attached to
Cobblestone 105 IRA - Install Generator System
Solicitation number
2110299
Issued by
Wayne County, New York City, New York

About this file

This document is related to a state and local contract opportunity for the New York State Office for People With Developmental Disabilities (OPWDD) to install a generator system at their Cobblestone 105 IRA facility located in Newark, New York.

The solicitation requires the contractor to be responsible for installing a complete working propane generator system, including providing a concrete generator pad, coordinating with the generator manufacturer, and performing all necessary electrical work. There is a mandatory site visit on June 5, 2024 at 9:30 am that vendors must attend prior to submitting bids. Bids are due by June 13, 2024 at 8:00 pm. This is a New York State public works project, so prevailing wages must be paid. The contract term is 30 days after completion of the project.

View the file

Other files

File Type Posted
Bid Tab179.pdf PDF
RFQ85.pdf PDF
Approved CP-FL-H7847-2023124, Generator Install, 105 CT IRA.pdf PDF
SOW67.pdf PDF
KES Pre-Renovation Survey Report- Cobblestone 105 IRA - EMAIL.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

12" MIN. COMPACTED SUBBASE

MDOT TYPE "C" MATERIAL

NEW MIN. 5000 PSI CONCRETE PAD. TO FIT

PROPOSED GENERATOR

ASPHALT PAVEMENT SECTION

NEW 4" THICK RIGID INSULATION

TO FIT PROPOSED GENERATOR

UNDISTURBED NATIVE SOIL OR

COMPACTED SUBGRADE OR

STRUCT FILL

"3 " M

IN

FINAL GRADE

(1) 3" PVC CONDUIT

3" BETWEEN CONDUITS MIN. TYP.

COMPACTED BACKFILL

SAND ENCASE CONDUIT 3" MIN

ON ALL SIDES

WARNING MARKER OVER ENTIRE LENGTH

NEW ELECTRICAL TRENCH DETAIL NOTES:

A. PROVIDE COMPLETE SITE RESTORATION, SHALL INCLUDE BUT NOT LIMITED

TO, GRASS, ASPHALT, CONCRETE WORK, ETC. UPON COMPLETION OF WORK

NOTED ON DRAWINGS.

(2) 1" PVC CONDUIT

FOR CONTROLS AND

POWER FOR BLOCK

HEATER

A5- SECT

A

300A MCB

A5- SECT

B

N

E

SE RATED FUSED

DISCONNECT

400A NEMA1

120/240V, 1Ø, 3W

G

TO UTILITY

L

(3) #350 KCMIL, (1) #4G, 3"C

(3) #350 KCMIL, (1) #4G, 3"C

40kVA

PROPANE GENERATOR

(3) #4/0, (1) #4G, 3" PVC (UNDERGROUND AND

EXTERIOR)

400A OPEN TRANSITION

SE RATED ATS

(3) #4/0, (1) #4G, 2-1/2" RMC (INTERIOR TO BUILDING)

PROVIDE PULLBOX SIZED IN ACCORDANCE

WITH NFPA 70 TABLE 314.28

PB

GENERATOR SHALL BE UL 2200

COMPLIANT, EPSS LEVEL 2, VANDAL

RESISTANT, WITH SOUND ATTENUATING

WEATHERPROOF STEEL HOUSING

ENCLOSURE

M

150A NEMA 3R RATED ENCLOSED

CIRCUIT BREAKER MOUNTED TO

BUILDING EXTERIOR

GENERAL LINEWORK DESCRIPTIONS & DRAWINGS

NOTES

NEW WORK

EXISTING WORK (E) - TO REMAIN UNLESS NOTED OTHERWISE

WORK TO BE REMOVED - DEVICE AND ALL ASSOCIATED

ELECTRICAL WORK SHALL BE REMOVED BACK TO THE

SOURCE UNLESS NOTED OTHERWISE

DRAWING KEYED

NOTES

DEMOLITION KEYED

NOTES

FOR ALL ELECTRICAL DEVICES & SYMBOLS

ELECTRICAL EQUIPMENT, CONNECTIONS AND

CONTROLS

FUSED DISCONNECT SWITCH

PULL BOX

PANELBOARD

AUTOMATIC TRANSFER SWITCHATS

PB

GENERATORG

ELECTRICAL METERM

P

T R

I O

T S

T

IL

L S

E R

V

IN

G

D E

S I G

N

C O

N S

U L

T I N

G

C

A N

A L

V

IE

W B

L V

D S

U

IT

E

O

C H

E S

T E

R N

Y

(5

D A

T E

B Y

A P

P R

O V

E D

C H

E C

K E

D B

Y

D R

A W

N B

Y

S C

A L E

P R

O J E

C T

I D

E N

T

IF

IC

A

T

IO

N N

O

D A

T E

N U

M B

E R

S H

E E

T

S H

E E

T T

IT

L E

R E

V

IS

IO

N

IT IS A VIOLATION OF THE LAW FOR ANY PERSON, EXCEPT A LICENSED PROFESSIONAL ENGINEER OR LAND SURVEYOR, TO ALTER THIS DRAWING IN ANY WAY. IF A LICENSED PROFESSIONAL ENGINEER OR LAND SURVEYOR ALTERS THIS DRAWING THEY MUST ATTACH THEIR SEAL AND NOTATION

"ALTERED BY" FOLLOWED BY A SIGNATURE AND THE DATE AND A SPECIFIC DESCRIPTION OF THE ALTERATION.

A s in d ic at ed

P R

O P

A N

E G

E N

S E

T A

N D

A S

S O

C

IA

T E

D I

N F

R A

S T

R U

C T

U R

E

O P

W D

D

C

O B

B L

E S

T O

N E

T E

R R

A C

E

N E

W A

R K

N

Y

G E

N E

R A

L N

O T E

S A

N D

S P

E C

IF

IC

A T

IO

N S

E

A C

S

JP

L

A C

S

O P

D -0

ELECTRICAL SPECIFICATIONS:

BASIC ELECTRICAL MATERIALS AND METHODS

SECTION 260501

RACEWAYS, FITTINGS AND ACCESSORIES

A. Electrical Metallic Tubing: Steel, galvanized on the outside and enameled on the inside, UL categorized as Electrical Metallic Tubing (identified on UL Listing Mark as Electrical Metallic Tubing), by Allied Tube & Conduit Corp., LTV Copperweld, or Wheatland Tube Co.

B. Flexible Metal Conduit: Galvanized steel strip shaped into interlocking convolutions, UL categorized as Flexible Metal Conduit (identified on UL Listing Mark as Flexible Steel Conduit or Flexible Steel Conduit Type RW), by AFC Cable Systems Inc., Anamet Electrical Inc., Electri-Flex Co., or International Metal Hose Co.

C. Liquid-tight Flexible Metal Conduit: UL categorized as liquid-tight flexible metal conduit (identified on UL Listing Mark as Liquid-Tight Flexible Metal Conduit, also specifically marked with temperature and environment application data), by AFC Cable Systems Inc., Anamet Electrical Inc., Electri-Flex Co., or Universal Metal Hose Co.

D. Wireways, Fittings and Accessories:

1.NEMA 1 (Without Knockouts): Hoffman Enclosures Inc. Bulletin F-40, Hubbell/Wegmann’s HSK, Lee Products Co.’s S Series, Rittal/Electromate’s EW & EWHC Lay-In Wireway System, or Square D Co.’s Square-Duct Class 5100.

E. Insulated Bushings, Plastic Bushings, and Insulated Grounding Bushings: By Appleton Electric Co., Cooper/Crouse-Hinds, OZ/Gedney Co., or Thomas & Betts Corp.

F. Connectors and Couplings:

1. Locknuts: UL, steel/zinc electroplate; Appleton Electric Co.’s BL-50 Series, Cooper/Crouse-Hinds’ 11 Series, OZ/Gedney Co.’s 1-50S Series, Raco Inc.’s 1002 Series, Steel City/T&B Corp.’s LN-101 Series, or Thomas & Betts Corp.’s 141 Series.

2. Couplings (For Rigid Metal and IMC Conduit): Standard galvanized threaded couplings as furnished by conduit manufacturer, Allied Tube & Conduit Corp.’s Kwik-Couple, or Thomas & Betts Corp.’s Shamrock.

3. Electrical Metallic Tubing Couplings and Insulated Connectors: Compression type, steel/zinc electroplate; Appleton Electric Co.’s TW-50CS1, TWC-50CS Series, Cooper/Crouse-Hinds’ 1650, 660S Series, Raco Inc.’s 2912, 2922 Series, Steel City/T & B Corp.’s TC-711 Series, or Thomas & Betts Corp.’s 5120, 5123 Series.

4. Flexible Metal Conduit Connectors: Arlington Industries Inc.’s Saddle-Grip, OZ/Gedney Co.’s C-8T, 24-34T, ACV-50T Series, or Thomas & Betts Corp.’s Nylon Insulated Tite-Bite Series.

5. Liquid-tight Flexible Metal Conduit Connectors:

a. Dry, Damp Locations: Steel, malleable iron, zinc electroplate, insulated throat; Appleton Electric Co.’s STB Series, Cooper/Crouse-Hinds’ LTB Series, OZ/Gedney Co.’s 4Q-50T Series, Raco Inc.’s 3512 Series, Steel City/T & B Corp.’s LT-701 Series, or Thomas & Betts Corp.’s 5332 Series.

b. Wet Locations: OZ/Gedney Co.’s 4Q-TG Series (hot-dip/mechanically galvanized), or Thomas & Betts Corp.’s 3322 Series (PVC coated).

G. Conduit Bodies (Threaded):

1. Dry, Damp Locations: Zinc electroplate malleable iron or cast iron alloy bodies with zinc electroplate steel covers; Appleton Electric Co.’s Unilets, Cooper/Crouse-Hinds’ Condulets, OZ/Gedney Co.’s Conduit Bodies, or Thomas & Betts Corp.’s Conduit Bodies.

2. Wet Locations: Malleable iron or cast iron alloy bodies and covers with hot dipped galvanized or other specified corrosion resistant finish; Cooper/Crouse-Hinds’ Condulets (Corro-free epoxy powder coat), Thomas & Betts Corp.’s Conduit Bodies (hot dipped galvanized), or OZ/Gedney Co.’s Conduit Bodies (hot dipped galvanized). Stainless steel cover screws, covers gasketed to suit application.

H. Sealing Fittings:

1. Dry, Damp Locations: Appleton Electric Co.’s EYS, ESU w/Kwiko sealing compound and fiber filler, Cooper/Crouse-Hinds’ EYS, EZS w/Chico A sealing compound and Chico X filler, OZ/Gedney Co.’s EY, EYA with EYC sealing compound and EYF damming fiber, or Thomas & Betts Corp.’s. EYS w/Chico A sealing compound and Chico X filler.

a. Other Type Fittings: As required to suit installation requirements, by Appleton Electric Co., Cooper/Crouse-Hinds, OZ/Gedney Co, or Thomas & Betts Corp.

2. Wet Locations: Malleable iron body with hot dipped/mechanically galvanized finish, neoprene sleeve, and stainless steel bands, Appleton electric Co.’s CF; or bronze couplings, neoprene sleeve, and stainless steel bands, OZ/Gedney Co.’s Type DX.

a. Horizontal: Cooper/Crouse-Hinds’ EYS with Chico A sealing compound and Chico X filler, OZ/Gedney Co.’s EYD with EYC sealing compound and EYF damming fiber, or Thomas & Betts Corp.’s. EYS w/Chico A sealing compound and Chico X filler.

b. Vertical (with Drain): Cooper/Crouse-Hinds with Chico A sealing compound and Chico X filler, OZ/Gedney Co.’s EY, EYA with EYC sealing compound and EYF damming fiber, or Thomas & Betts Corp.’s. w/Chico A sealing compound and Chico X filler.

c. Other Type Fittings. As required to suit installation requirements, by Cooper/Crouse- Hinds, OZ/Gedney Co., or Thomas & Betts Corp. with hot dipped/mechanically galvanized finish or epoxy powder coat.

I. Sealant for Raceways Exposed to Different Temperatures: Sealing compounds and accessories to suit installation; Appleton Electric Co.’s DUC, or Kwiko Sealing Compound with fiber filler, Cooper/Crouse-Hinds’ Chico A Sealing Compound with Chico X fiber, Electrical Products Division 3M Scotch products, OZ Gedney Co.’s DUX or EYC sealing compound with EYF damming fiber, or Thomas & Betts Corp.’s Blackburn DX.

J. Vertical Conductor Supports:

1. Dry, Damp Locations: Kellems/Hubbell Inc.’s Conduit Riser Grips, or OZ/Gedney Co.’s Type M, Type R.

2. Wet Locations: Kellems/Hubbell Inc.’s Conduit Riser Grips (stainless steel or tin coated bronze), or OZ/Gedney Co.’s hot dipped galvanized finish Type CMT or Type W.

PULL BOXES

A. Galvanized Steel Junction and Pull Boxes: Code gage, galvanized steel screw cover boxes by Delta Metal Products Inc., Hoffman Enclosures Inc., Hubbell Wiegmann, Lee Products Co., or Rittal/Electromate.

CONDUCTORS AND ACCESSORIES

A. Date of Manufacture: No insulated conductor more than one year old when delivered to the site will be acceptable.

B. Acceptable Companies: American Insulated Wire Corp., BICC General Cable Industries Inc., Cerro Wire & Cable Co. Inc., Pirelli Cable Corp., Rome Cable Corp., or Southwire Co..

C. Conductors: Annealed uncoated copper or annealed coated copper in conformance with the applicable standards for the type of insulation to be applied on the conductor. Conductor sizes No. 8 and larger shall be stranded.

D. Types:

1. Electric Power Wiring:

a. General: Rated 600V, NFPA 70 Type FEP, THHN, THW, THW-2, THWN, THWN-2, XHH, XHHW, XHHW-2.

SUPPORTING DEVICES

A. Fasteners: Furnish all fasteners and hardware compatible with the materials and methods required for attachment of supporting devices.

1. Slotted Type Concrete Inserts: Galvanized pressed steel plate complying with ASTM A 283; box-type welded construction with slot designed to receive steel nut and with knockout cover, hot-dipped galvanized in compliance with ASTM A 123.

2. Masonry Anchorage Devices: Expansion shields complying with FS FF-S-325, as follows:

a. Furnish lead expansion shields for machine screws and bolts 1/4 inch and smaller;

head-out embedded nut type, single unit class, Group I, Type l, Class 1.

b. Furnish lead expansion shields for machine screws and bolts larger than 1/4 inch in size; head-out embedded nut type, multiple unit class, Group I, Type 1, Class 2.

c. Furnish bolt anchor expansion shields for lag bolts, zinc alloy, long-shield anchors class, Group II, Type 1, Class 1.

d. Furnish bolt anchor expansion shields for bolts, closed-end bottom bearing class, Group II, Type 2, Class 1.

3. Toggle Bolts: Tumble-wing type, complying with FS FF-B-588C, Type, class and style as required.

4. Nuts, Bolts, Screws, Washers:

a. General: Furnish zinc-coated fasteners, with galvanizing complying with ASTM A 153 for exterior use or where built into exterior walls. Furnish fasteners for the type, grade and class required for the particular installation.

b. Standard Nuts and Bolts: Regular hexagon head type, complying with ASTM A 307, Grade A.

c. Lag Bolts: Square head type, complying with FS FF-B-561C.

d. Machine Screws: Cadmium plated steel, complying with FS FF-S-92.

e. Wood Screws: Flat head carbon steel, complying with FS FF-S-111.

f. Plain Washers: Round, general assembly grade carbon steel, complying with FS

FF-W-92.

g. Lock Washers: Helical spring type carbon steel, complying with FS FF-W-84.

GENERAL DEMOLITION NOTES:

1. DRAWINGS ARE DIAGRAMMATIC ONLY AND REPRESENT GENERAL SCOPE OF WORK.

CONTRACTOR IS RESPONSIBLE TO REVIEW GENERAL CONSTRUCTION DRAWINGS,

ARCHITECTURAL, CIVIL, STRUCTURAL, MECHANICAL, ELECTRICAL AND PLUMBING

DRAWINGS, EXISTING SITE CONDITIONS AND ASSOCIATED SPECIFICATIONS FOR

ADDITIONAL REQUIREMENTS THAT MAY NOT BE SPECIFICALLY CALLED OUT IN THIS

PORTION OF CONSTRUCTION. NOTIFY ARCHITECT OF ANY CONFLICT OR

DISCREPANCIES PRIOR TO BID.

2. DRAWINGS INDICATE GENERAL EXTENT OF DEMOLITION WORK. ALL ITEMS NOTED TO

BE REMOVED ON DRAWINGS SHALL BE REMOVED, UNLESS NOTED OTHERWISE.

CONTRACTOR SHALL REMOVE ALL ELECTRICAL EQUIPMENT, DEVICES, CONDUITS,

CONDUCTORS, ELECTRICAL CONNECTIONS, ETC. NOT TO BE REUTILIZED IN THE

COMPLETED PROJECT UNLESS NOTED OTHERWISE. EQUIPMENT SHOWN IS FOR

REFERENCE ONLY AND DOES NOT SHOW ALL ITEMS TO BE REMOVED.

3. PRIOR TO SUBMITTING BID, CONTRACTOR SHALL VISUALLY INSPECT ALL EXISTING

CONDITIONS TO ASSIST IN DETERMINING THE FULL EXTENT OF DEMOLITION

WORK.

4. ASSEMBLIES BEING REMOVED SHALL BE REMOVED IN THEIR ENTIRETY, INCLUDING

HANGERS, CLIPS, ETC. BACK TO A CLEAN STRUCTURE, WITH PATCHING OF ANY

FIRE PROOFING.

5. DEMO ITEMS SHALL BE TAKEN BACK TO BEYOND THE INDICATED AREA OF

CONSTRUCTION OR AS OTHERWISE NOTED. TERMINATIONS SHALL BE PER GOOD

ENGINEERING PRACTICE WITH PROTECTIVE CAPS OVER ELECTRICAL WIRING.

CAPS FOR CONDUIT.

6. ALL HOLES THRU FIREWALLS, FLOOR TO FLOOR, AND FLOOR TO ROOF RATED

ASSEMBLIES SHALL BE PATCHED OR PLUGGED WITH A FIRE RATED UL LISTED

ASSEMBLY AS REQUIRED BY THE CONSTRUCTION MATERIALS ENCOUNTERED AND

THE HOLE SIZE.

7. ALL UNUSED WIRING (POWER AND LOW VOLTAGE) SHALL BE REMOVED FROM THE

WORK AREA BACK TO SOURCE.

8. MAINTAIN & RESTORE, IF INTERRUPTED, ALL CONDUITS & CONDUCTORS PASSING

THROUGH RENOVATED AREA(S) AND SERVING UNDISTURBED AREA(S).

GENERAL CONSTRUCTION NOTES:

1.01 PROJECT OVERVIEW

1.02 GENERAL

A. GENERAL CONTRACTOR WILL PERFORM THE WORK. THIS IS A NYS PUBLIC WORKS

PROJECT WHICH REQUIRES A PREVAILING WAGE.

B. THE GENERAL CONTRACTOR WILL WORK WITH AND COOPERATE WITH OPWDD

PROJECT MANGER FOR THE COORDINATION AND INSTALLATION OF THE WORK

DESCRIBED HEREIN CONTRACTOR SHALL FAMILIARIZE THEMSELVES WITH THE WORK

PERTAINING TO EACH TRADE. CONTRACTOR SHALL VERIFY EXISTING CONDITIONS AND

MEASUREMENTS INCLUDING DEMOLITION WORK. CONTRACTOR SHALL INSPECT ALL

DRAWINGS AND IMMEDIATELY REPORT ANY DISCREPANCIES TO THE OPWDD PROJECT

MANAGER AND ENGINEER.

C. PRIOR TO THE COMMENCEMENT OF ANY WORK, CONTRACTOR SHALL NOTIFY THE

OPWDD PROJECT MANAGER. CONTRACTOR SHALL KEEP THE GROUNDS CLEAR OF ALL

DEBRIS, DUST, AND ANY OTHER HAZARDOUS CONDITIONS THROUGHOUT THE PROJECT

EACH DAY. TAKE ALL NECESSARY STEPS TO KEEP ALL AREAS CLEAN.

D. ALL GENERAL CONSTRUCTION AND ELECTRICAL WORK SHALL BE PROVIDED IN

ACCORDANCE WITH NEW YORK STATE BUILDING CODE, AND ALL OTHER AGENCIES

HAVING JURISDICTION.

E. CONTRACTOR SHALL REVIEW OPWDD REQUIREMENTS AND COORDINATE WORK FOR

COMPLIANCE. CONTRACTOR SHALL NOTIFY THE OPWDD PROJECT MANAGER AT EACH

STAGE OF COMPLETION OF THE PROJECT.

1.03 PROJECT CONDITIONS

A. EXISTING CONDITIONS: DO NOT DISTURB EXISTING STRUCTURES, CONSTRUCTION,

MATERIALS, OR EQUIPMENT UNLESS REQUIRED BY THE CONTRACT.

1. DO NOT CUT, DRILL, OR REMOVE STRUCTURAL MEMBERS SUCH AS JOISTS, BEAMS,

AND COLUMNS WHICH SUPPORT CONSTRUCTION WHICH IS SCHEDULED TO REMAIN

UNLESS EXPRESSLY REQUIRED BY THE CONTRACT DOCUMENTS.

2. REMOVE ALL DEMOLISHED MATERIALS FROM THE PREMISES AND DISPOSE OF ON

A DAILY BASIS.

3. PERFORM A HAZARDOUS MATERIALS STUDY ON ALL AREAS OF THE PROJECT TO

BE DISTURBED. ADVISE OPWDD PROJECT MANAGER OF RESULTS BEFORE START OF

ANY DEMOLITION WORK.

B. ITEMS TO REMAIN THE PROPERTY OF OPWDD. THE FOLLOWING ITEMS SHALL REMAIN

THE PROPERTY OF OPWDD AN SHALL BE STORED AT THE SITE WHERE DIRECTED BY THE

OPWDD PROJECT MANAGER. THIS INCLUDES APPLIANCES IF REQUESTED. COORDINATE

WITH OPWDD PROJECT MANAGER.

1. CONSTRUCTION WORK CONTRACT. REMOVE AND SALVAGE EXISTING BUILDING

MATERIALS OR OTHER ACCESSORIES AS DESIGNATED BY OPWDD.

2. STORE ALL ITEMS AT A LOCATION AS DIRECTED BY OPWDD.

3. PROPERLY DISPOSE OF ALL REMAINING SCRAP ITEMS AND REMOVE FROM THE

SITE EACH DAY.

2.01 MATERIALS

A. MATCH THE APPEARANCE AND PERFORMANCE OF EXISTING CORRESPONDING

MATERIALS AS CLOSELY AS POSSIBLE

3.01 EXAMINATION

A. PRIOR TO CUTTING, DRILLING OR REMOVAL INVESTIGATE BOTH SIDES OF THE

SURFACE INVOLVED WITH THE WORK. DETERMINE THE EXACT LOCATION OF ALL

STRUCTURAL MEMBERS.

B. IF UNFORESEEN OBSTRUCTIONS ARE ENCOUNTERED, TAKE NECESSARY

PRECAUTIONS TO PREVENT DAMAGE AND OBTAIN INSTRUCTION FROM THE OPWDD

PROJECT MANAGER BEFORE PROCEEDING WITH THE WORK.

3.02 PREPARATION

A. PREPARE EXISTING SURFACES PROPERLY TO RECEIVE, AND WHERE REQUIRED, BOND

WITH THE NEW WORK.

3.03 PATCHING

A. PATCH EXISTING CONSTRUCTION AND FINISHES WHICH ARE DISTURBED, DAMAGED

OR LEFT INCOMPLETE DUE TO ALTERATIONS AND REMOVALS. PATCHING: EXCEPT AS

OTHERWISE INDICATED, SHALL BE LIMITED TO AREAS WHICH HAVE BEEN CUT OR

ALTERED WITH THIS WORK. FINISH PATCHED SURFACES TO MATCH EXITING ADJACENT

SURFACES AS CLOSELY AS POSSIBLE.

B. PERFORM PATCHING AROUND ITEMS IN A MANNER WHICH WILL MAINTAIN WITH

WATER AND FIRE RESISTANCE CAPABILITIES OF THE EXISTING CONSTRUCTION

C. PAINT PATCHED AREAS AND COVER PLATES TO MATCH EXISTING ADJACENT

SURFACES OTHERWISE INDICATED, SHALL BE LIMITED TO AREAS WHICH HAVE BEEN

PATCHED.

D. WHERE SURFACES EXPOSED BY REMOVALS ARE TO REMAIN AS EXPOSED SURFACES,

PAINT THESE AREAS TO MATCH EXISTING SURFACES AS CLOSELY AS POSSIBLE USING

THE SAME TYPE OF PAINT.

CONCRETE PAD DETAIL

NEW ELECTRICAL TRENCH DETAIL

ELECTRICAL ONE-LINE DIAGRAM

LINEWORK & SYMBOLS

GROUNDING AND BONDING

A. Ground Clamps (Cable to Pipe): Blackburn/T&B Corp.’s GUV, Framatome Connectors/Burndy Corp.’s GAR, GD, GP, GK, or OZ/Gedney Co.’s ABG, CG.

B. Ground Clamps (Cable to Rod): Blackburn/T&B Corp.’s GG, GGH, JAB, JABH, GUV, Dossert Corp.’s GN, GPC, Framatome Connectors/Burndy Corp.’s GP, GX, GRC, or OZ/Gedney Co.’s ABG.

C. Ground Lugs: Copper, one or 2 hole style (to suit conditions), long barrel; Anderson/Hubbell’s VERSAtile VHCL, Blackburn/T&B Corp.’s Color-Coded CTL, LCN, Framatome Connectors/Burndy’s Hylug YA, Electrical Products Div./3M Scotchlok 31036 or 31145 Series, Ideal Industries Inc.’s CCB or CCBL, or Thomas & Betts Corp.’s 54930BE or 54850BE Series.

D. Grounding Electrode Conductors and Bonding Conductors: Copper conductors, bare or insulated with THW, THW-2, XHHW, XHHW-2, THWN, THWN-2 or THHN insulation.

AUTOMATIC TRANSFER SWITCH

SECTION 263623

REFERENCES

A. UL 1008 listed, CSA certified.

B. NFPA 110.

C. NEMA Standard ICS2-447-AC Transfer Switches.

D. IEEE Standard 446.

E. ISO 9001.

AUTOMATIC TRANSFER SWITCH

A. Automatic Switch Co.'s ASCO 940, Onan OT Series, Russelectric Inc.'s, Model RMT, or Zenith Controls Inc.'s ZTS, or Approved Equivalent with:

1. Double throw construction.

2. Ratings as indicated on drawings.

3. Accessories to perform the functions specified in TRANSFER SWITCH OPERATING

DESCRIPTION.

4. NEMA 1 enclosure.

5. Electrically operated and mechanically held.

6. Adjustable time delay, 0-6 seconds, to override momentary outages before initiating engine starting. Once engine is signalled to start it must run for at least the duration of the time delay before engine shut down.

7. Adjustable time delay, 0-30 minutes, on retransfer to normal feeder with bypass of time delay in event of emergency feeder failure.

8. Adjustable time delay, 0-10 minutes, on engine cool down.

9. Adjustable time delay, 0-5 seconds, on transfer to emergency feeder.

10. Test switch, momentary type, (permanent type are acceptable when accompanied by flashing red lights at the transfer switch and generator set to indicate switch is not in automatic mode), to simulate normal feeder failure (unit to start and transfer to emergency feeder).

B. Generator is Furnished by Owner and Installed by Electrical Contractor. Coordinate ATS and Generator with owner prior to any purchase.

INSTALLATION

A. Install all required engine starting signal circuitry from switches to engine start conductor junction box. Engine start signal shall be transmitted automatically upon loss of normal source voltage. The start signal shall prevent dry cranking of the generator by requiring the generator to reach proper output and run for at least the duration of the cooldown timer.

B. Install switch so that the maximum height above the floor to the center of the operating handle does not exceed 6'-0".

C. Identify switch, indicating designation, load served and normal feeder designation, by riveting or bolting nameplate to cover.

FIELD QUALITY CONTROL

A. Preliminary Switch/System Test:

1.Preparation: Have the Company Field Advisor adjust the switch for the completed system (including the related equipment) and then operate it long enough to assure that it is performing properly.

2. Run a preliminary test for the purpose of:

a. Determining whether the switch is in a suitable condition to conduct an acceptance test.

b. Checking and adjusting equipment.

c. Training facility personnel.

B. Switch/System Acceptance Test:

1. Preparation: Coordinate test with related equipment manufacturer and notify the Director's Representative at least 3 working days prior to the test so arrangements can be made to have a Facility Representative witness the test.

2. Make the following tests:

a. Test each switch function step by step as summarized under TRANSFER

SWITCH OPERATING DESCRIPTION.

3. Submit written report of test results signed by Company Field Advisor and the Director's Representative. Give a copy of the final report to the Director's Representative.

MAIN SERVICE DISCONNECT - UNDER 600V

SECTION 262811

MATERIALS

A. Fusible Disconnect Switch: General Electric Co.’s Type TH, Westinghouse Elec. Corp.’s H-600, Square D Co.’s Heavy Duty Series, or Challenge/FPE Heavy Duty Series having:

1. Fuses - See Section 262813.

2. NEMA 1 enclosure.

3. Solid neutral.

4. UL label “Suitable For Use As Service Equipment”.

5. Voltage rating, current rating and number of poles as indicated on the drawings.

INSTALLATION

A. Mount main service disconnect on wall so that maximum height above the floor to the center of the operating handle does not exceed 6-1/2 feet.

B. Stencil on front cover of main service disconnect with white paint in minimum 1 inch lettering, the words MAIN SERVICE DISCONNECT,1-phase, 3 wire, 240 volts.

ENCLOSED CIRCUIT BREAKERS

SECTION 262817

MATERIALS

A. Enclosed Circuit Breakers: As produced by Eaton/ Cutler-Hammer Corp.., General Electric Co., Siemens Power Systems Inc., or Square-D Co. having:

1. NEMA 1 enclosure unless otherwise indicated on the drawings.

2. Solid neutral.

3. Voltage rating, current rating, symmetrical current interrupt rating 10,000 AIC (unless otherwise indicated on drawing or specified elsewhere) and number of poles as indicated on the drawings.

4. Circuit breakers to suit requirements.

5. Ampere trip elements 50 and above have industrial type enclosure with door and side handle. Handle position is lockable using standard padlock.

NAMEPLATES

A. Phenolic: Engraved plates, minimum 3/4” wide and length as required by inscription:

Seton Name Plate Corp.

B. Stamped Metal: Standard stamped or embossed aluminum tags, minimum 3/4” wide and length as required by inscription: Tech Products, Inc.; Seton Name Plate Corp.

INSTALLATION

A. Mount enclosed circuit breakers on wall so that maximum height above the floor to the center of operating handle does not exceed 6-1/2’.

B. Provide phenolic or stamped metal nameplates on cover of each enclosed circuit breaker indicating purpose or load served by the circuit breaker.

M

PB

M

PB

PB

A T

S

PORCH

ACTIVITY ROOM

LAUNDRY ROOM

MED.

STOR.

OFFICE

BATH

BEDROOM

BEDROOM

BEDROOM

BEDROOM

BEDROOM

7BEDROOM

BEDROOM

BATHROOM

MECH.

BATHROOM

19VESTIBULE

LIVING

20KITCHEN

PANTRY

DINING ROOM

GARAGE

Room

A5-SECT1

WESTINGHOUSE TYPE B10B

120/240, 300A MCB, 1Ø, 3WIRE

42 CKT, NO SPACES/SPARES

A5-SECT2

WESTINGHOUSE TYPE B10B

120/240, 400A, 1Ø, 3WIRE

42 CKT, SPACES 30, 32-42

PORCH

ACTIVITY ROOM

LAUNDRY ROOM

MED.

STOR.

OFFICE

BATH

BEDROOM

BEDROOM

BEDROOM

BEDROOM

BEDROOM

7BEDROOM

BEDROOM

BATHROOM

MECH.

BATHROOM

19VESTIBULE

LIVING

20KITCHEN

PANTRY

DINING ROOM

GARAGE

Room

A5-SECT1

WESTINGHOUSE TYPE B10B

120/240, 300A MCB, 1Ø, 3WIRE

42 CKT, NO SPACES/SPARES

A5-SECT2

WESTINGHOUSE TYPE B10B

120/240, 400A, 1Ø, 3WIRE

42 CKT, SPACES 30, 32-42

ATS

SE RATED

DISCONNECT 400A

P

T

I O

T S

T

IL

L S

E R

V

IN

G

D E

S I G

N

C O

N S

U L

T I N

G

C

A N

A L

V

IE

W B

L V

D S

U

IT

E

O

C H

E S

T E

R N

Y

(5

D A

T E

B Y

A P

P R

O V

E D

C H

E C

K E

D B

Y

D R

A W

N B

Y

S C

A L E

P R

O J E

C T

I D

E N

T

IF

IC

A

T

IO

N N

O

D A

T E

N U

M B

E R

S H

E E

T

S H

E E

T T

IT

L E

R E

V

IS

IO

N

IT IS A VIOLATION OF THE LAW FOR ANY PERSON, EXCEPT A LICENSED PROFESSIONAL ENGINEER OR LAND SURVEYOR, TO ALTER THIS DRAWING IN ANY WAY. IF A LICENSED PROFESSIONAL ENGINEER OR LAND SURVEYOR ALTERS THIS DRAWING THEY MUST ATTACH THEIR SEAL AND NOTATION

"ALTERED BY" FOLLOWED BY A SIGNATURE AND THE DATE AND A SPECIFIC DESCRIPTION OF THE ALTERATION.

P R

O P

A N

E G

E N

S E

T A

N D

A S

S O

C

IA

T E

D I

N F

R A

S T

R U

C T

U R

E

O P

W D

D

C

O B

B L

E S

T O

N E

T E

R R

A C

E

N E

W A

R K

N

Y

F L

O O

R P

L A

N S

E

A C

S

JL

P

A C

S

O P

D -0

1/8" = 1'-0"E01

1 FIRST FLOOR PLAN - DEMOLITION

1/8" = 1'-0"E01

2 FIRST FLOOR PLAN - ELECTRICAL

KEYED NOTES:

1. PROVIDE GENERATOR PAD AND INSTALL GENERATOR AS DETAILED WITHIN THESE DOCUMENTS. LOCATE GENERATOR PAD AS DIRECTED BY OWNER. EXHAUST MUST BE A MINIMUM OF FIVE (5) FEET AWAY FROM OPERABLE WINDOWS AND ANY OTHER BUILDING INTAKES. IT IS THE RESPONSIBILITY OF CONTRACTOR TO CONTACT LOCAL UTILITY TO IDENTIFY AND FLAG ALL EXISTING UNDERGROUND UTILITIES WHICH MAY INTERFERE WITH PROPOSED GENERATOR PAD AND UNDERGROUND FEEDERS.

2. UNDERGROUND FEED TO EXTERIOR OF BUILDING. REFER TO ELECTRICAL ONE LINE AND NEW ELECTRICAL TRENCH DETAIL.

3. PROVIDE EXTERIOR RISER FASTENED TO BUILDING ABOVE ROOF DECK AND PROVIDE INTO CEILING SOFFIT.

4. PROVIDE PULLBOX IN BUILDING SOFFIT AS INDICATED IN ELECTRICAL ONE LINE. FIELD VERIFY EXACT LOCATION.

5. ROUTE RMC FEEDER THROUGH CEILING SOFFIT. FIELD VERIFY EXACT ROUTING PATH.

6. MOUNT ENCLOSED CIRCUIT BREAKER TO BUILDING EXTERIOR; COORDINATE LOCATION WITH OWNER.

GENERAL DEMO NOTES:

A. ELECTRICAL CONTRACTOR SHALL REVIEW ALL TRADE'S DRAWINGS. ALL EXISTING EQUIPMENT SHALL REMAIN ON EXISTING SURFACES UNLESS SPECIFICALLY NOTED OTHERWISE.

B. ALL DEVICES AND EQUIPMENT SHOWN ARE EXISTING TO REMAIN UNLESS OTHERWISE NOTED.

C. ALL RACEWAYS AND CABLES, NO LONGER IN USE, SHALL BE REMOVED BACK TO THE SOURCE.

D. MAINTAIN, OR RESTORE IF INTERRUPTED BY REMOVALS OR IN PATH OF NEW CONSTRUCTION, ALL CONDUITS, BRANCH CIRCUITS, AND FEEDERS PASSING THROUGH AND SERVING UNDISTURBED

AREAS (SHOWN OR NOT SHOWN)

E. ENSURE REMOVAL OF ELECTRICAL DEVICES IN CONSTRUCTION AREA DOES NOT AFFECT ADJACENT AREAS.

F. ALL REMOVED ELECTRICAL FIXTURES, DEVICES AND EQUIPMENT SHALL BE TURNED OVER TO THE OWNER. IF OWNER DOES NOT WISH TO KEEP ITEMS, THEY BECOME THE PROPERTY OF THE

ELECTRICAL CONTACTOR AND MUST BE REMOVED FROM THE SITE.

GENERAL ELECTRICAL NOTES:

A. ALL WORK SHALL BE INSTALLED IN A NEAT AND WORKMAN LIKE MANNER, RECTINLINEAR TO THE BUILDING STRUCTURE, AND IN ACCORDANCE WITH ALL APPLICABLE CODES, INCLUDING, BUT NOT

LIMITED TO NFPA 70, 90A, 101 AND UNDER THE AUTHORITY HAVING JURISDICTION.

B. SPECIFICALLY, ALL WORK MUST BE PROVIDED UNDER GUIDANCE OF NFPA 70 ARTICLE 445.

C. CONTRACTOR SHALL FIELD VERIFY TO DETERMINE SPECIFIC MOUNTING HEIGHTS AND LOCATIONS FOR ALL ELECTRICAL EQUIPMENT AND CONDUITS. ALL INFORMATION SHOWN IS DIAGRAMMATIC ONLY

AND MUST BE FIELD VERIFIED BY CONTRACTOR PRIOR TO SUBMITTING BID.

D. COORDINATE ARRANGEMENT, MOUNTING, AND SUPPORT OF ELECTRICAL CONDUIT AND EQUIPMENT TO PROVIDE FOR EASE OF DISCONNECTING THE EQUIPMENT WITH MINIMUM INTERFERENCE TO OTHER INSTALLATIONS; TO ALLOW RIGHT OF WAY FOR PIPING INSTALLED AT A REQUIRED SLOPE; AND SO CONNECTING RACEWAYS SHALL BE CLEAR OF OBSTRUCTIONS AND OF THE WORKING AND

ACCESS SPACE OF OTHER EQUIPMENT.

E. CONTRACTOR TO COORDINATE ALL CONNECTIONS WITH GENERATOR SHOP DRAWINGS AND EQUIPMENT SUPPLIER AND INSTALL IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS.

F. CONTRACTOR TO COORDINATE START UP AND TESTING.

G. GENERATOR FURNISHED BY OWNER. GENERATOR INSTALLED BY CONTRACTOR. CONTRACTOR TO INSTALL AND PROVIDE COMPLETE WORKING PROPANE GENERATOR SYSTEM TO THE SATISFACTION

OF THE OWNER.

H. CONTRACTOR TO PROVIDE GENERATOR PAD. SEE DETAIL 'CONCRETE PAD DETAIL' AND PROVIDE CONCRETE PAD IN ACCORDANCE WITH GENERATOR MANUFACTURER'S REQUIREMENTS.

I. OWNER TO PROVIDE PROPANE TANK, PROPANE TANK PAD, AND PROPANE LINE AND CONNECTION TO GENERATOR. NOT SHOWN ON DOCUMENTATION.

KEYED DEMOLITION NOTES:

1. PROVIDE ALL WORK TO DISCONNECT EXISTING SERVICE FEEDER FROM EXISTING PANELBOARD TO ACCOMMODATE WORK; COORDINATE DISCONNECTION WITH OWNER.

REFER TO ELECTRICAL ONE LINE DIAGRAM FOR ADDITIONAL INFORMATION.

Sheets
E00 - GENERAL NOTES AND SPECIFICATIONS
E01 - FLOOR PLANS