APPENDIX I - Design Plans.pdf
PDF 8 MB Posted
- Solicitation number
- ITB-14722
- Issued by
- Leon County, Florida
About this file
This document comprises the design plans for a new boardwalk construction project at Myakka State Forest in Englewood, Florida, prepared by the Weiler Engineering Corporation under the oversight of Florida Department of Agriculture and Consumer Services. The project encompasses approximately 610 linear feet of composite boardwalk featuring ADA-compliant design with multiple components including an entrance ramp (two sections with slopes of 6.71% and 7.85%), a main boardwalk section, two observation decks, a mid-walk bench area, and an interpretive kiosk. The design incorporates 142 treated timber piles (10-inch diameter) with 10-foot minimum embedment, 4,000 square feet of composite decking, pressure-treated structural members, wire mesh-reinforced guardrails, ADA-compliant benches and drop rails, and an interpretive signage display area. The construction plans comply with the 2023 Florida Building Code (8th edition) and are designed for Wind Risk Category I with ultimate design wind speed of 141 mph (nominal 111 mph) in Exposure D, and base flood elevation of 9.80 feet NAVD per FEMA FIRM Map 12115C0460G. The design accommodates ramp slopes varying from 3.84 to 4.49 degrees with appropriate landing elevations, and includes specialized details for pile cap connections, rail assemblies, and observational deck framing.
The design parameters establish a vertical bearing capacity of 1,500 psf with lateral bearing pressure of 100 psf per foot of depth, utilizing presumptive soil load-bearing values from the Florida Building Code for soil types identified via USGS web soil survey. All lumber specified is Southern Pine No. 2 grade with pressure treatment per AWPA standards; 2X and 3X ground-contact members require structural HDPE equivalents. Metal connectors are galvanized or stainless steel (triple galvanized Z-max for pressure-treated lumber connections), and all fasteners must meet ASTM A153 specifications. The kiosk structure features a pitched roof design with Gulfseam aluminum standing seam roofing (KYNAR coated) over weather-resistant underlayment, mounted on pressure-treated wood framing. Wind load calculations indicate maximum positive pressures of +80.45 psf and maximum negative pressures of -86.40 psf for the observation deck, and +46.65 psf positive and -32.97 psf negative for the kiosk. All construction must achieve strict compaction standards (98% maximum density per ASTM D698), and the contractor is responsible for verifying existing site conditions, utility locations, and obtaining all necessary permits prior to commencement of work.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| ITB GS 25 26 48_Final.pdf | ||
| Addendum I.pdf | ||
| EXHIBIT A.pdf | ||
| APPENDIX I - Design Plans.pdf | ||
| EXHIBIT A.pdf | ||
| APPENDIX II - Maps.pdf | ||
| EXHIBIT A.pdf | ||
| Addendum II - Timeline Revision.pdf | ||
| APPENDIX II - Maps.pdf | ||
| APPENDIX II - Maps.pdf | ||
| ITB GS 25 26 48_Final.pdf | ||
| Addendum I.pdf | ||
| APPENDIX I - Design Plans.pdf | ||
| ITB GS 25 26 48_Final.pdf |
Show all 14
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
De sc rip tio n Re vi sio ns Pr oj ec t I nf or m at io n
Ap pr ov ed
B y:
Sc al e:
Jo b
N o.
Da te
Is su ed
De sig n:
Dr aw n:
Ch ec ke d:
Sheet No.
THIS SHEET IS NOT VALID WITHOUT
THE SIGNATURE AND ORIGINAL SEAL
OF A FLORIDA LICENSED ENGINEER.
W
ES
T M
AR
IO
N A
VE
N
U E
SU
IT
E
PU
N
TA
G O
R D
A, F
LO
R
ID
A
(9
) 5
-1
EB
CO
N
ST
RU
CT
IO
N P
LA
N
S
FO
R
Max Morgan Professional Engineer
State of Florida Registration No. 94877
Max Morgan, Professional Engineer, State of Florida, License No. 94877 This item has been digitally signed and sealed by Max Morgan, P.E.
on the date indicated here.
Signature must be verified on any electronic copies.
08-29-2025
THE WEILER ENGINEERING CORPORATION
WIND PARAMETERS
Method of Design: ASCE 7-22 Building Risk Category: RISK 1 Design Wind Speed: Ultimate Vult=141 MPH / Nominal Vasd = 111 MPH Wind Importance Factor: 1.00 / Wind Exposure: D Internal Pressure Coefficient: ±0.00 (OPEN) Component & Cladding Wind Pressure: per Calcs
FLOOD PARAMETERS
FEMA FIRM Map Number: 12115C0460G Base Flood Elevation: AE 9.80' NAVD 100-year, 1-hour Design Rainfall: 4.5 in (FBC 2023 Fig. 1611.1)
GEOTECHNICAL PARAMETERS
Data Source: Presumptive Load-Bearing Values of Soils, FBC 2023 1806.2 Vertical Bearing Capacity: 1,500 psf (FBC 2023 Table 1806.2) Lateral Bearing Pressure: 100 psf/ft (FBC 2023 Table 1806.2)
FOUNDATION SOIL AND TREATMENT
Soil Bearing Capacity Listed & the resultant foundation design assumes the soil type noted as per USGS web soil survey (or geotechnical engineering if provided). if inadequate substrate is discovered during site preparation the engineer shall be notified prior to placement of foundations.
These plans are in Compliance with Florida Building Code 2023 8th edition (FBC) for the parameters indicated.
G102
S . R
IV
ER
R D.
M
YA
KK
A
ST
AT
E F
OR
ES
T B
OA
RD
W
AL
K D
ES
IG
N
EN
GL
EW
O
O D, F L
/2 8/
5.0
BT
C
TW
P
TW
P
NOTE:
1) ALL 2X AND 3X MEMBERS (GIRDERS, RIM JOIST AND JOIST) THAT HAVE GROUND CONTACT SHALL BE STRUCTURAL HDPE OR EQUAL.
CONCRETE OR GROUND CONTACT, IN-GROUND USE, DECKING, ROOF
COMPONENTS (SEE NOTE 1 BELOW) UC4A
0.40 PCF ACQ OR EQUAL ± (0.14 PCF UCA-C , 0.15 PCF MCA, OR 0.15 PCF
CA)
STRINGERS & BENTS 2X6 - 2X10, ROOF POSTS 6X6-10X10 UC4A/B 0.60 PCF ACQ OR 0.31 PCF CA OR 0.23 PCF OF UCA-C OR MCA
SPLIT PILE CAP 3X10, STRINGERS & BENTS 2X8-3X10 UC4B 0.60 PCF CCA
UPLAND PILES IN-GROUND OR FRESHWATER PILES UC4C 0.80 PCF CCA OR 0.41 CA
SALTWATER EXPOSURE PILES, CROSS BRACING, AND WALERS UC5C DUAL TREATMENT AS PHOLADS OR SPHAEROMA TEREBRANS ARE
PRESENT: FIRST: CCA 1.00 SECOND: CR OR CR-S 20.00
STRUCTURAL
ABBREVIATIONS
# NUMBER OR POUND
Ø ROUND OR DIAMETER
□ SQUARE
& AND
@ AT
ALUM ALUMINUM
AR ANCHOR ROD
ARCH ARCHITECTURE
ASSY ASSEMBLY
B/ BOTTOM OF
BETWN BETWEEN
BOT BOTTOM
BM BEAM
BLDG BUILDING
BPL BASE PLATE
BRG BEARING
C TO C CENTER TO CENTER
CANT CANTILEVER
CJ CONSTRUCTION JOINT
CL CENTER LINE
CLR CLEAR
CMU CONCRETE MASONRY UNIT
COL COLUMN
CONC CONCRETE
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTINUOUS
CONTR CONTRACTION
CTR CENTER
CTRD CENTERED
DBA DEFORMED BAR ANCHOR
DEFL DEFLECTION
DET DETAIL
DIAG DIAGONAL
DIA DIAMETER
DIFF DIFFERENT
DIM DIMENSION
DO DITTO
DWG DRAWING
EA EACH
EF EACH FACE
EF EXPANSION JOINT
EL ELEVATION
ELEC ELECTRICAL
ELEV ELEVATOR
ENGR ENGINEER
EOR ENGINEER OF RECORD
EQ EQUAL
EQUIP EQUIPMENT
EXIST EXISTING
EXP EXPANSION
EXT EXTERIOR
EW EACH WAY
FB FLAT BAR
FD FLOOR DRAIN
FDN FOUNDATION
FF FINISH FLOOR
FLR FLOOR
FS FAR SIDE
FTG FOOTING
GA GAGE
GALV GALVANIZED
GC GENERAL CONTRACTOR
GT GIRDER TRUSS
HGT HEIGHT
HM HOLLOW METAL
HORIZ HORIZONTAL
HSA HEADED STUD ANCHOR
HT HEIGHT
IF INSIDE FACE
INFO INFORMATION
INT INTERIOR
JNT JOINT
JST JOIST
LB POUND
LG LONG
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LSH LONG SIDE HORIZONTAL
LSV LONG SIDE VERTICAL
MANUF MANUFACTURER
MAT'L MATERIAL
MAX MAXIMUM
MECH MECHANICAL
MIN MINIMUM
MISC MISCELLANEOUS
NIC NOT IN CONTRACT
NO NUMBER
NS NEAR SIDE
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OF OUTSIDE FACE
O/O OUT TO OUT
OPNG OPENING
OPP OPPOSITE
PERP PERPENDICULAR
PL PLATE
PNL PANEL
PREFAB PREFABRICATED
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
QTY QUANTITY
R OR RA RADIUS
RD ROUND
REF REFERENCE
REINF REINFORCE(MENT)
REQ REQUIRE
REQ'D REQUIRED
RET RETAINING
REV REVISION
SCHED SCHEDULE
SECT SECTION
SIM SIMILAR
SOG SLAB ON GRADE
SPA SPACE
SPEC SPECIFICATION
SQ SQUARE
STD STANDARD
STIFF STIFFENER
STL STEEL
STR STRAIGHT
STRUCT STRUCTURAL
SYM SYMMETRICAL
T&B TOP & BOTTOM
T/ TOP OF
T/U PAN TILT-UP PANEL
TE THICKENED EDGE
THK THICK
THRD THREADED
TRANSV TRANSVERSE
TS THICKENED SLAB
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
VER VERIFY
VERT VERTICAL
W/ WITH
W/O WITHOUT
WP WORK POINT
WS WATERSTOP
WWF WELDED WIRE FABRIC
WOOD PRESERVATION TREATMENT
APPLICATION AWPA USE
CATEGORY
TREATMENT (LBS/CU FT.)
IN CONTACT WITH METAL ROOFING UC2
0.018 PCF PTI OR EQUAL ± (0.019 PCF EL2, 0.14 PCF UCA-C, 0.15 PCF
MCA, OR 0.17 PCF SBX)
ABOVE GROUND USE UC3B ACQ 0.25
N
PLAN, SECTION OR DETAIL NO.
SHEET NUMBER
KEYED NOTE TO PLAN
REVISION NUMBER
NORTH ARROW
GENERAL SYMBOLS
LUMBER
1. CODES AND STANDARDS (CURRENT EDITIONS)
1.1. AMERICAN WOOD COUNCIL (AWC) NATIONAL DESIGN SPECIFICATION FOR WOOD CONSTRUCTION" (NDS-2023)
2. DIMENSIONAL LUMBER SHALL BE SOUTHERN PINE WITH THE MINIMUM NOMINAL DESIGN VALUES PER AWC NDS-20232.
3. WHERE SPECIFIED, ENGINEERED LUMBER PRODUCTS SHALL BE PER MANUFACTURER PROVIDED DESIGN VALUES. CONTRACTOR
SHALL PROVIDE SUBMITTAL FOR ALL ENGINEERED LUMBER PRODUCTS.
4. ALL WOOD IN CONTACT WITH CONCRETE, MASONRY, OR SOIL, EXPOSED TO WEATHER, OR AT OTHER LOCATIONS AS SHOWN ON STRUCTURAL DRAWINGS, SHALL BE PROTECTED OR PRESSURE TREATED IN ACCORDANCE WITH AWPA U1 REQUIREMENTS.
PRESSURE TREATMENT APPROPRIATE FOR LUMBER IN CONTACT WITH SOIL SHALL BE PROVIDED WHERE APPLICABLE.
5. NAILING, AND JOIST BLOCKING SHALL MEET THE MINIMUM REQUIREMENTS OF CHAPTER 23 OF THE FLORIDA BUILDING CODE UNLESS
MORE STRINGENT REQUIREMENTS ARE INDICATED ON THE PLANS.
6. ALL CONNECTORS SHALL BE GALVANIZED. CONNECTOR MODEL NUMBERS SHOWN ARE STRONG-TIE CONNECTORS AS MANUFACTURED BY SIMPSON STRONG-TIE CO, PO BOX 10789, PLEASANTON, CA 94588 OR USP CONNECTORS AS MANUFACTURED BY MITEK, INC, 16023 SWINGLEY RIDGE RD, CHESTERFIELD, MO 63017. SUBSTITUTIONS ARE ACCEPTABLE WITH THE APPROVAL OF THE STRUCTURAL ENGINEER. UNLESS SHOWN OTHERWISE, INSTALL SIZE AND NUMBER OF FASTENERS PER MANUFACTURER INSTALLATION INSTRUCTIONS. ALL CONNECTORS TO PRESSURE TREATED LUMBER SHALL BE TRIPLE GALVANIZED (Z MAX) OR
STAINLESS STEEL.
7. ANY NOTE REQUIRING A RING SHANK MAY BE SCREW SHANK FOR AUTOMATIC NAILING
GENERAL REQUIREMENTS
1. CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND DETAILS AND SHALL NOTIFY ENGINEER OF RECORD IMMEDIATELY OF ANY
ERRORS, OMISSIONS OR DISCREPANCIES PRIOR TO COMMENCEMENT OF WORK.
2. ALL MATERIALS, EQUIPMENT, CONNECTORS, AND WORK SHALL MEET OR EXCEED THE DESIGN DATA AND COMPLIANCE CODE CITED.
3. ENGINEER IS NOT RESPONSIBLE FOR ANY SUPERVISION DURING CONSTRUCTION.
4. CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS PRIOR TO COMMENCING WORK AND DETERMINE THE LOCATION OF ALL ADJACENT UNDERGROUND UTILITIES PRIOR TO COMMENCING EXCAVATION AND NOTIFY ENGINEER OF ANY DISCREPANCIES PRIOR
TO CONSTRUCTION.
5. THE CONTRACTOR MAINTAINS THE RESPONSIBILITY FOR ALL CONSTRUCTION MEANS, METHODS AND TECHNIQUES REQUIRED FOR THE CONNECTIONS OF ALL GUARDRAIL, SAFETY CURB, BOARDWALK AND PILINGS. ALL WORK SHALL BE PERFORMED IN A
WORKMANLIKE MANNER.
6. THE STRUCTURAL INTEGRITY OF THE STRUCTURES SHOWN ON THESE PLANS IS DEPENDENT UPON COMPLETION ACCORDING TO PLANS AND SPECIFICATIONS. STRUCTURAL MEMBERS ARE NOT SELF SUPPORTING DURING CONSTRUCTION AND REQUIRE TEMPORARY BRACING UNTIL PERMANENTLY APPLIED TO STRUCTURE AS DIRECTED. THE STRUCTURAL ENGINEER ASSUMES NO LIABILITY FOR THE STRUCTURE DURING CONSTRUCTION UNLESS THE CONSTRUCTION METHOD AND BRACING ARE INCLUDED IN THE PLANS AND SPECIFICATIONS, OR ARE SUPERVISED BY THE STRUCTURAL ENGINEER DURING CONSTRUCTION.
7. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL SAFETY PRECAUTIONS AND THE METHODS, TECHNIQUES, SEQUENCES OR PROCEDURES REQUIRED TO PERFORM THE WORK. THE STRUCTURAL ENGINEER HAS NO OVERALL SUPERVISION / AUTHORITY OR ACTUAL AND/ OR DIRECT RESPONSIBILITY FOR THE SPECIFIC WORKING CONDITIONS AT THE SITE AND/ OR FOR ANY HAZARDS RESULTING FROM THE ACTIONS OF ANY TRADE CONTRACTOR. THE STRUCTURAL ENGINEER HAS NO DUTY TO INSPECT, SUPERVISE, NOTE, CORRECT, OR REPORT ANY HEALTH OR SAFETY DEFICIENCIES OF THE OWNER, CONTRACTORS, OR OTHER ENTITIES OR
PERSONS AT THE PROJECT SITE.
8. IN ADDITION TO THE DEMOLITION WORK INDICATED ON THE DRAWINGS, MINOR LOCAL DEMOLITION OF EXISTING ELEMENTS MAY BE REQUIRED TO PERFORM THE STRUCTURAL WORK AS INDICATED ON THE PLANS, SECTIONS, AND DETAILS.
9. ANY CHANGES OR SUBSTITUTIONS SHALL BE APPROVED BY THE ENGINEER.
10. DISSIMILAR METALS SHALL BE ISOLATED TO PREVENT GALVANIC ACTION.
11. FIELD VERIFY ALL EXISTING ABOVE AND BELOW GROUND CONDITIONS PRIOR TO FABRICATION AND CONSTRUCTION.
12. STRUCTURAL DRAWINGS INDICATE TYPICAL AND CERTAIN SPECIFIC CONDITIONS ONLY. SHOP DRAWINGS SHALL DETAIL ALL CONDITIONS IN ACCORDANCE WITH SPECIFIED STANDARDS AND SPECIFIC REQUIREMENTS OF THIS PROJECT AS INDICATED ON THE
DRAWINGS.
13. CONTRACTOR SHALL APPLY FOR AND OBTAIN ALL NECESSARY PERMITS FROM ALL RELEVANT AUTHORITIES HAVING JURISDICTION, INCLUDING STRUCTURAL, ELECTRICAL, PLUMBING, AND ALL OTHERS REQUIRED TO COMPLETE THE JOB.
SHOP DRAWINGS
1. SHOP DRAWINGS SHALL BE SUBMITTED TO THE ENGINEER OF RECORD FOR REVIEW. NO MODIFICATIONS OR SUBSTITUTION OF
DRAWINGS AND SPECIFICATIONS WILL BE ACCEPTED VIA SHOP DRAWINGS REVIEW. THE FOLLOWING SHOP DRAWINGS SHALL BE
SUBMITTED FOR REVIEW:
1.1. SUBMIT CONCRETE TEST RESULTS FOR CYLINDER STRENGTH TESTS AND SLUMP TESTS
1.2. SUBMIT CONCRETE MIX DESIGN PER SPECIFICATIONS IN "CAST IN PLACE CONCRETE" ITEM 26.1
1.3. SUBMIT REBAR SHOP DRAWINGS PER SPECIFICATIONS IN "CAST IN PLACE CONCRETE" ITEM 26.2
1.4. SUBMIT DENSITY TEST RESULTS PER SPECIFICATIONS IN "FOUNDATION SOIL & TREATMENT" ITEM 2.1
1.5. ANY PROPOSED ALTERNATIVES TO PRODUCTS SPECIFIED IN PLANS
2. CONTRACTOR SHALL REVIEW AND STAMP SHOP DRAWINGS PRIOR TO SUBMISSION TO THE STRUCTURAL ENGINEER. CONTRACTOR
SHALL REVIEW FOR COMPLETENESS AND COMPLIANCE WITH CONTRACT DOCUMENTS.
3. SUBMIT SHOP DRAWINGS TO THE STRUCTURAL ENGINEER AS INDICATED OR SPECIFIED FOR REVIEW PRIOR TO FABRICATION.
REVIEW WILL BE FOR GENERAL CONFORMANCE WITH THE DESIGN INTENT CONVEYED IN CONTRACT DOCUMENTS.
4. WHEN ENGINEER IS REQUIRED TO SIGN AND STAMP SHOP DRAWINGS AND CALCULATIONS, ENSURE SEAL INDICATES ENGINEER AS
REGISTERED IN THE STATE WHERE PROJECT SITE OCCURS.
5. SHOP DRAWINGS ARE NOT PART OF CONTRACT DOCUMENTS. THEREFORE, STRUCTURAL ENGINEER'S REVIEW DOES NOT CONSTITUTE ON AUTHORIZATION TO DEVIATE FROM THE TERMS AND CONDITIONS OF THE CONTRACT.
6. SHOP DRAWINGS WILL BE REJECTED FOR INCOMPLETENESS, LACK OF COORDINATION WITH OTHER PORTIONS OF CONTRACT DOCUMENTS, LACK OF CALCULATIONS (IF REQUIRED), OR WHERE MODIFICATIONS OR SUBSTITUTIONS ARE INDICATED WITHOUT PRIOR REVIEW PER PARAGRAPH ABOVE 6. - SUBMIT SHOP DRAWINGS AND CALCULATIONS TO GOVERNING CODE AUTHORITY WHEN
SPECIFICALLY INDICATED OR REQUESTED.
7. MAINTAIN A COPY OF ALL SHOP DRAWINGS ACCEPTED BY THE STRUCTURAL ENGINEER AT SITE DURING CONSTRUCTION PERIOD.
8. STRUCTURAL ENGINEER REQUIRES 10 WORKING DAYS AFTER RECEIPT OF SHOP DRAWINGS AND CALCULATIONS FOR PROCESSING.
FOUNDATION SOIL & TREATMENT
1. WHERE GEOTECHNICAL INFORMATION IS UNAVAILABLE, RESULTANT FOUNDATION DESIGN ASSUMES PRESCRIBED SOIL BEARING
CAPACITIES PER FBC 2023 FOR SOIL TYPE NOTED AS PER NRCS WEB SOIL SURVEY. CONTRACTOR SHALL CONFIRM SITE CONDITIONS
MEET DESIGN SPECIFICATIONS PRIOR TO CONSTRUCTION.
2. FOUNDATION AND SLAB NOTES: SUB-GRADE PREPARATION INCLUDING DRAINAGE, EXCAVATION, COMPACTION, AND FILLING REQUIREMENTS, SHALL CONFORM STRICTLY WITH RECOMMENDATIONS GIVEN IN THE SOILS REPORT OR AS DIRECTED BY THE
PROJECT REPRESENTATIVE.
3. ALL FILL SHALL BE CLEAN SELECT MATERIAL FREE OF DELETERIOUS MATERIALS SUCH AS WOOD, ROOTS, TRASH, OR OTHER EXTRANEOUS MATERIALS. PLACE FILL IN 8" LIFTS, MEASURED LOOSE, AND COMPACT EACH LIFT TO 98% MAXIMUM DENSITY AT
OPTIMUM MOISTURE CONTENT AS MEASURED BY ASTM D698 (2021).
3.1. 98% COMPACTION SHALL BE ACHIEVED AT ALL LOCATIONS WHERE NEW CONCRETE IS TO BE POURED, INCLUDING ALL SLABS AND FOUNDATIONS. NUMBER AND LOCATION OF TESTS SHALL BE DIRECTED BY THE ENGINEER OF RECORD.
4. FOUNDATION CONCRETE SHALL BE PLACED BEFORE DETERIORATION OF THE SUBGRADE DUE TO WEATHER, GROUND WATER SEEPAGE, FOOT TRAFFIC, OR CONSTRUCTION OPERATIONS. ANY PORTIONS OF THE SUBGRADE PERMITTED TO DETERIORATE SHALL BE REMOVED AND REPLACED WITH AN APPROVED COMPACTED BACKFILL OR LEAN CONCRETE (FLOWABLE FILL) WITHOUT
ADDITIONAL COMPENSATION TO THE CONTRACTOR.
WIND BORNE DEBRIS REGION REQUIREMENTS
1. ALL STRUCTURAL COMPONENTS AND CLADDING AS REQUIRED SHALL BE DESIGNED BY THE MANUFACTURER IN ACCORDANCE WITH
SECTION 1609 OF THE 2023 FLORIDA BUILDING CODE FOR DESIGN PRESSURES GENERATED BY AN ULTIMATE DESIGN WIND VELOCITY
OF 180MPH (3-SECOND GUST).
2. THE BUILDER SHALL PROVIDE NECESSARY COPIES OF DETAILS, CERTIFICATIONS, ETC... TO THE BUILDING DEPARTMENT TO SHOW
COMPLIANCE WITH THIS PARAGRAPH.
3. THE ENGINEER OF RECORD DOES NOT CERTIFY THE STRUCTURAL INTEGRITY OF THESE ITEMS.
4. DESIGN WIND PRESSURES ARE BASED ON AN OPEN STRUCTURE CLASSIFICATION.
CHEMICAL (ADHESIVE) ANCHORS
CHEMICAL (ADHESIVE) ANCHORS SHALL BE AN EQUAL TWO PART EPOXY POLYMER INJECTION SYSTEM, SUCH AS RED-HEAD EPCON, SIMPSON SET EPOXY, OR HILTI HSE2411 EPOXY DOWELING SYSTEM, OR ENGINEER APPROVED SUBSTITUTION, INSTALLED IN ACCORDANCE WITH MANUFACTURERS INSTRUCTIONS. INSTALLERS SHALL BE TRAINED BY THE MANUFACTURER'S REPRESENTATIVE.
MINIMUM EMBEDMENT SHALL BE TWELVE (12) TIMES FASTENER DIAMETER UNLESS NOTED OTHERWISE.
CONSTRUCTION OBSERVATION
THE STRUCTURAL ENGINEER OF RECORD HAS NOT BEEN RETAINED TO PERFORM CONSTRUCTION OBSERVATION SERVICES FOR THIS PROJECT. THEREFORE, ANY AS-BUILT CONSTRUCTION OR CHANGES MADE TO THE STRUCTURE OR TO THESE PLANS WITHOUT THE ENGINEER'S WRITTEN CONSENT SHALL RENDER THE DESIGN AND THE ENGINEERS SEAL ON THESE PLANS NULL AND VOID.
EXISTING STRUCTURE
1. DRAWINGS FOR THE EXISTING STRUCTURE WERE NOT AVAILABLE. ALL OF THE EXISTING CONDITIONS WERE NOT VERIFIABLE WITHIN
THE SCOPE OF ENGINEERING SERVICES; THEREFORE, IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY THE CONDITIONS RELATING TO THE EXISTING STRUCTURE AND TO NOTIFY THE ENGINEER IMMEDIATELY OF ANY DISCREPANCIES OR
CONFLICTS.
2. THE EXISTING STRUCTURE HAS NOT BEEN REVIEWED OR IMPROVED TO MEET THE REQUIREMENTS OF THE 2023 FLORIDA BUILDING
CODE.
APPLICABLE CODES
CODE LIST
FLORIDA BUILDING CODE, BUILDING (FBC-B).........................................2023 8TH EDITION FLORIDA BUILDING CODE, EXISTING BUILDING (FBC-EB).....................2023 8TH EDITION FLORIDA FIRE PREVENTION CODE (FFPC)..............................................2023 8TH EDITION FLORIDA ACCESSIBILITY CODE.................................................................2023 8TH EDITION
FDOT STANDARD SPECIFICATIONS FOR ROAD & BRIDGE CONST. .....LATEST EDITION
FDOT DESIGN STANDARDS.........................................................................LATEST EDITION
STRUCTURAL LOADS
1. GOVERNING BUILDING CODE: 2023 FLORIDA BUILDING CODE
2. DESIGN LOADS:
STRUCTURAL LOADS (LIVE LOADS PER FBC TABLE 1607.1)
LIVE LOAD ................................................................... 60 PSF DEAD LOAD ................................................................. 15 PSF
HANDRAIL AND GUARDRAIL DESIGN LOADS
CONCENTRATED LOAD .......................................................... 200 LB UNIFORM LINEAR LOAD ........................................................ 50 PLF
WIND LOADS (PER ASCE 7-22)
BUILDING RISK CATEGORY (TABLE 1.5-1) ................................... Category I
BASIC WIND SPEED (FIG. 26.5-1A)
Ultimate (Vult) (THREE SECOND GUST) .................................... 141 MPH Nominal (Vasd) ............................................................................. 111 MPH
IMPORTANCE FACTOR (TABLE 1.5-2) .................................................. 1.00 EXPOSURE CATEGORY (26.7.3) ........................................................... EXPOSURE D INTERNAL PRESSURE COEFFICIENT (TABLE 26.13-1) ...................... ±0.00 (OPEN)
COMPONENTS & CLADDING WIND PRESSURES ................................ PER PLAN
GEOTECHNICAL DESIGN DATA (PER FBC 1806)
DATA SOURCE: UES PROJECT NUMBER 0630.2300139.0000
ALLOWABLE COMPRESSIVE CAPACITY .............................................................. 4 KIP ALLOWABLE TENSION CAPACITY ......................................................................... 2 KIP
RAIN DESIGN DATA (PER FBC 1611)
DESIGN RAIN EVENT ............................................................................ 100-YEAR, 1-HR DESIGN RAINFALL (FIG. 1611.1) ........................................................... 4.5-IN DESIGN RAIN LOAD ............................................................................... 0 PSF
FLOOD DESIGN DATA (PER FBC 1612)
FEMA FIRM MAP ................................................................................... 12115C0460G BASE FLOOD ELEVATION .................................................................... AE-9.80' NAVD GE
NE
RA
L S
TR
UC
TU
RA
L N
OT
ES
N.T.S.1
PILE INDEX
PILE ID DESC
TOP OF
DECK
ELEV
PILE
TOP
ELEV
RAMP
SLOPE %
RAMP
RISE/RUN
RAMP
DEGREES PILE ID DESC
TOP OF
DECK
ELEV
PILE
TOP
ELEV
RAMP
SLOPE %
RAMP
RISE/RUN
RAMP
DEGREES
1 BOARDWALK ENTRANCE 10.10 9.81 69 BOARDWALK 14.08 13.79
2 BOARDWALK ENTRANCE 10.10 9.81 70 BOARDWALK 14.08 13.79
3 RAMP BASE 10.10 9.81 71 BOARDWALK 14.08 13.79
4 RAMP BASE 10.10 9.81 72 BOARDWALK 14.08 13.79
(3,4-5,6) RAMP RUN 6.71% 01:14.9 3.84 73 BOARDWALK 14.08 13.79
5 RAMP 10.76 10.47 74 BOARDWALK 14.08 13.79
6 RAMP 10.76 10.47 75 BOARDWALK 14.08 13.79
(5,6-7,8) RAMP RUN 6.71% 01:14.9 3.84 76 BOARDWALK 14.08 13.79
7 RAMP 11.43 11.13 77 BOARDWALK 14.08 13.79
8 RAMP 11.43 11.14 78 BOARDWALK 14.08 13.79
(7,8-9,10) RAMP RUN 6.71% 01:14.9 3.84 79 BOARDWALK 14.08 13.79
9 RAMP TOP 12.09 11.80 80 BOARDWALK 14.08 13.79
10 RAMP TOP 12.09 11.80 81 BOARDWALK 14.08 13.79
11 BOARDWALK 12.09 11.80 82 BOARDWALK 14.08 13.79
12 BOARDWALK 12.09 11.80 83 BOARDWALK 14.08 13.79
13 BOARDWALK 12.09 11.80 84 BOARDWALK 14.08 13.79
14 BOARDWALK 12.09 11.80 85 BOARDWALK 14.08 13.79
15 BOARDWALK 12.09 11.80 86 BOARDWALK 14.08 13.79
16 BOARDWALK 12.09 11.80 87 BOARDWALK 14.08 13.79
17 RAMP BASE 12.09 11.80 88 BOARDWALK 14.08 13.79
18 RAMP BASE 12.09 11.80 89 BOARDWALK 14.08 13.79
(17,18-19,20) RAMP RUN 7.85% 01:12.7 4.49 90 BOARDWALK 14.08 13.79
19 RAMP 12.73 12.44 91 BOARDWALK 14.08 13.79
20 RAMP 12.73 12.44 92 BOARDWALK 14.08 13.79
(19,20-21,22) RAMP RUN 7.85% 01:12.7 4.49 93 BOARDWALK 14.08 13.79
21 RAMP 13.38 13.09 94 BOARDWALK 14.08 13.79
22 RAMP 13.38 13.09 95 BOARDWALK 14.08 13.79
(21,22-23,24) RAMP RUN 7.85% 01:12.7 4.49 96 BOARDWALK 14.08 13.79
23 RAMP TOP 14.08 13.79 97 BOARDWALK 14.08 13.79
24 RAMP TOP 14.08 13.79 98 BOARDWALK 14.08 13.79
25 BOARDWALK 14.08 13.79 99 BOARDWALK 14.08 13.79
26 BOARDWALK 14.08 13.79 100 BOARDWALK 14.08 13.79
27 BOARDWALK 14.08 13.79 101 BOARDWALK 14.08 13.79
28 BOARDWALK 14.08 13.79 102 BOARDWALK 14.08 13.79
29 BOARDWALK 14.08 13.79 103 BOARDWALK 14.08 13.79
30 BOARDWALK 14.08 13.79 104 BOARDWALK 14.08 13.79
31 BOARDWALK 14.08 13.79 105 BOARDWALK 14.08 13.79
32 BOARDWALK 14.08 13.79 106 BOARDWALK 14.08 13.79
33 BOARDWALK 14.08 13.79 107 BOARDWALK 14.08 13.79
34 BOARDWALK 14.08 13.79 108 BOARDWALK 14.08 13.79
35 BOARDWALK 14.08 13.79 109 BOARDWALK 14.08 13.79
36 BOARDWALK 14.08 13.79 110 BOARDWALK 14.08 13.79
37 BOARDWALK 14.08 13.79 111 BOARDWALK 14.08 13.79
38 BOARDWALK 14.08 13.79 112 BOARDWALK 14.08 13.79
39 BOARDWALK 14.08 13.79 113 BOARDWALK 14.08 13.79
40 BOARDWALK 14.08 13.79 114 BOARDWALK 14.08 13.79
41 BOARDWALK 14.08 13.79 115 BOARDWALK 14.08 13.79
42 BOARDWALK 14.08 13.79 116 BOARDWALK 14.08 13.79
43 BOARDWALK 14.08 13.79 117 BOARDWALK 14.08 13.79
44 BOARDWALK 14.08 13.79 118 BOARDWALK 14.08 13.79
45 BOARDWALK 14.08 13.79 119 BOARDWALK 14.08 13.79
46 BOARDWALK 14.08 13.79 120 BOARDWALK 14.08 13.79
47 BOARDWALK 14.08 13.79 121 BOARDWALK 14.08 13.79
48 BOARDWALK 14.08 13.79 122 BOARDWALK 14.08 13.79
49 BOARDWALK 14.08 13.79 123 BOARDWALK 14.08 13.79
50 BOARDWALK 14.08 13.79 124 BOARDWALK 14.08 13.79
51 BOARDWALK 14.08 13.79 125 BOARDWALK 14.08 13.79
52 BOARDWALK 14.08 13.79 126 BOARDWALK 14.08 13.79
53 BOARDWALK 14.08 13.79 127 BOARDWALK 14.08 13.79
54 BOARDWALK 14.08 13.79 128 BOARDWALK 14.08 13.79
55 BOARDWALK 14.08 13.79 129 BOARDWALK 14.08 13.79
56 BOARDWALK 14.08 13.79 130 BOARDWALK 14.08 13.79
57 BOARDWALK 14.08 13.79 131 BOARDWALK 14.08 13.79
58 BOARDWALK 14.08 13.79 132 BOARDWALK 14.08 13.79
59 BOARDWALK 14.08 13.79 133 BOARDWALK 14.08 13.79
60 BOARDWALK 14.08 13.79 134 BOARDWALK 14.08 13.79
61 BOARDWALK 14.08 13.79 135 OBSERVATION DECK 14.08 22.71
62 BOARDWALK 14.08 13.79 136 OBSERVATION DECK 14.08 22.71
63 BOARDWALK 14.08 13.79 137 OBSERVATION DECK 14.08 22.71
64 BOARDWALK 14.08 13.79 138 OBSERVATION DECK 14.08 22.71
65 BOARDWALK 14.08 13.79 139 OBSERVATION DECK 14.08 25.08
66 BOARDWALK 14.08 13.79 140 OBSERVATION DECK 14.08 25.08
67 BOARDWALK 14.08 13.79 141 OBSERVATION DECK 14.08 25.08
68 BOARDWALK 14.08 13.79 142 OBSERVATION DECK 14.08 25.08
INTERPRETIVE SIGNAGE
(ADA DROP RAIL LOCATION)
1. INTERPRETIVE SIGNAGE MOUNT SHALL BE MANUFACTURED BY
BCE (BUREAU OF CORRECTIONAL ENTERPRISES), MODEL
SERIES INT-XXXX-30-REG-0, OR APPROVED EQUAL. MOUNT
TYPE SHALL BE REGULAR WOOD POST BRACKET WITH A 30°
VIEWING ANGLE.
2. PART NUMBER FORMAT: INT-[WIDTH][HEIGHT]-30-REG-0
2.1.EXAMPLE: INT-1836-30-REG-0 REPRESENTS AN 18" WIDE × 36"
TALL FRAME, 30° VIEWING ANGLE, REGULAR WOOD POST
MOUNT, WITH NO GRAPHIC PANEL INCLUDED.
3. SIGNAGE SHALL BE INSTALLED AND MOUNTED BY
CONTRACTOR ON THE EXTERIOR SIDE OF THE GUARDRAIL AT
DESIGNATED LOCATIONS, AT DROPPED RAIL SECTIONS TO
MAINTAIN ADA VISIBILITY REQUIREMENTS. THE ADA DROP RAIL
WIDTH SHALL BE DETERMINED AS FOLLOWS:
3.1. ADA DROP RAIL WIDTH = SIGN PANEL WIDTH + 12 INCHES
3.2.MINIMUM ADA DROP RAIL WIDTH = 36 INCHES
4. SIGNS ≤ 24" WIDE SHALL BE MOUNTED TO A SINGLE POST;
SIGNS > 24" WIDE SHALL BE MOUNTED TO DOUBLE POSTS.
5. THE CLIENT SHALL SELECT THE FINAL SIGNAGE SIZE PRIOR TO
FABRICATION OR ORDERING OF MOUNTS.
6. THE CLIENT SHALL PROVIDE THE FINAL GRAPHIC PANEL,
WHICH SHALL BE INSTALLED BY THE CONTRACTOR INTO THE
MOUNTING FRAME IN THE FIELD.
7. ALL SIGNAGE INSTALLATIONS SHALL COMPLY WITH ADA
MOUNTING HEIGHT AND VISIBILITY REQUIREMENTS. SIGNAGE
SHALL NOT OBSTRUCT EGRESS ROUTES, CIRCULATION PATHS,
OR REQUIRED PASSING CLEARANCES. CENTERLINE OF SIGN
PANEL SHALL BE MOUNTED 40" TO 48" ABOVE THE STANDING
SURFACE.
9" X 12" 36" 1
SIGN SIZE
(W X H)
ADA RAIL
WIDTH
MOUNTING POST
(4X4 PT)
12" X 18" 36" 1 18" X 24" 36" 1
24" X 24" 36" 1 24" X 36" 36" 1 24" X 48" 36" 36" X 48" 48" 48" X 48" 60" * 48" X 60" 72" *
18" X 36" 36" 1
INTERPRETIVE SIGNAGE SIZE TABLE
* NOTE: FOR ADA DROP RAIL WIDTH GREATER THAN
60" 4X4 PT GUARDRAIL POST SHALL BE SPACED AT
A MAX OF 48" O.C.
(FOR USE WITH BCE OR APPROVED EQUAL – PART
SERIES: INT-XXXX-30-REG-0)
AutoCAD SHX Text USER: Tom.Parker PLOTTED THE G102 LAYOUT OF C:\Users\TOM~1.PAR\AppData\Local\Temp\AcPublish_7956\25035001MyakkaBoardwalk20250828.dwg, ON Aug 29, 2025 @ 9:14am
8" 9'-2" 9'-9"
9'-11"
9'-11"
10'-0"
10'-0"
7'-4" 6'-11"
8'-0"
8'-3"
8'-11"
29'-7" RAMP
25'-2" RAMP
9'-10"
20'-0"
14'-3"
7'-7"
4'-0"
171.7°
177.02°
178.96°
174.65°
DN
DN
7'-7"
8'-5"
9'-11"
16'-0"
9'-11"
9'-11" 19'-10"
9'-11"
9'-11"
59'-7"
49'-9"
9'-11" 9'-11"
9'-11" 9'-11"
9'-11"
165.28°
176.18°
8'-9" 8'-9"
17'-7"
8'-6"
8'-5"
8'-5"
33'-7"
8'-3" 5'-8"
5'-8" 7'-11"
7'-10" 7'-10"
7'-10" 7'-10"
4'- 0"
2'- 7"
4'- 0"
2'- 7"
7'-11"
6'- 7"
6'- 7"
50'-7"
9'-11"
9'-11"
175.23°
175.4°
176.23°
179.81°
90°
DN
DN
DN
De sc rip tio n Re vi sio ns Pr oj ec t I nf or m at io n
Ap pr ov ed
B y:
Sc al e:
Jo b
N o.
Da te
Is su ed
De sig n:
Dr aw n:
Ch ec ke d:
Sheet No.
THIS SHEET IS NOT VALID WITHOUT
THE SIGNATURE AND ORIGINAL SEAL
OF A FLORIDA LICENSED ENGINEER.
W
ES
T M
AR
IO
N A
VE
N
U E
SU
IT
E
PU
N
TA
G O
R D
A, F
LO
R
ID
A
(9
) 5
-1
EB
CO
N
ST
RU
CT
IO
N P
LA
N
S
FO
R
Max Morgan Professional Engineer
State of Florida Registration No. 94877
Max Morgan, Professional Engineer, State of Florida, License No. 94877 This item has been digitally signed and sealed by Max Morgan, P.E.
on the date indicated here.
Signature must be verified on any electronic copies.
08-29-2025
THE WEILER ENGINEERING CORPORATION
WIND PARAMETERS
Method of Design: ASCE 7-22 Building Risk Category: RISK 1 Design Wind Speed: Ultimate Vult=141 MPH / Nominal Vasd = 111 MPH Wind Importance Factor: 1.00 / Wind Exposure: D Internal Pressure Coefficient: ±0.00 (OPEN) Component & Cladding Wind Pressure: per Calcs
FLOOD PARAMETERS
FEMA FIRM Map Number: 12115C0460G Base Flood Elevation: AE 9.80' NAVD 100-year, 1-hour Design Rainfall: 4.5 in (FBC 2023 Fig. 1611.1)
GEOTECHNICAL PARAMETERS
Data Source: Presumptive Load-Bearing Values of Soils, FBC 2023 1806.2 Vertical Bearing Capacity: 1,500 psf (FBC 2023 Table 1806.2) Lateral Bearing Pressure: 100 psf/ft (FBC 2023 Table 1806.2)
FOUNDATION SOIL AND TREATMENT
Soil Bearing Capacity Listed & the resultant foundation design assumes the soil type noted as per USGS web soil survey (or geotechnical engineering if provided). if inadequate substrate is discovered during site preparation the engineer shall be notified prior to placement of foundations.
These plans are in Compliance with Florida Building Code 2023 8th edition (FBC) for the parameters indicated.
S100
S . R
IV
ER
R D.
M
YA
KK
A
ST
AT
E F
OR
ES
T B
OA
RD
W
AL
K D
ES
IG
N
EN
GL
EW
O
O D, F L
/2 8/
5.0
BT
C
TW
P
TW
P
BOARDWALK PLAN A 1/4" = 1'-0"
GENERAL NOTES:
1. PILES SHALL HAVE EMBEDMENT TO 10'-0" MIN. DEPTH INDICATED
OR TO PRACTICAL REFUSAL AS DEFINED AS 20 BLOWS PER INCH
OR LESS THAN ONE INCH PENETRATION, WITH THE HAMMER
OPERATING AT THE HIGHEST SETTING DETERMINED BY THE
ENGINEER AND LESS THAN 1/4 INCHES REBOUND PER BLOW THEN
PILE SHALL BE CUT TO REQUIRED HEIGHT.
2. ALL BOLTS SHALL EXTEND PASS THE NUT BY A MINIMUM OF THREE
(3) THREADS AND A MAX OF 2".
3. CUTTING OF BOLTS SHALL BE AVOIDED. IF CUTTING IS REQUIRED,
THE FOLLOWING PROCEDURE SHALL BE USED:
3.1. FOR STAINLESS STEEL BOLTS, USE A VIRGIN CERAMIC
GRINDING DISC TO MAKE THE CUT, THEN TREAT THE
EXPOSED END WITH PASSIVATION PASTE.
3.2. FOR GALVANIZED BOLTS, USE A NEW CERAMIC GRINDING
DISC, THEN APPLY TWO COATS OF COLD GALVANIZING PAINT
TO THE CUT END IN ACCORDANCE WITH ASTM A780.
BOARDWALK PLAN B 1/4" = 1'-0"
BOARDWALK PLAN C 1/4" = 1'-0"
BOARDWALK INDEX 1/4" = 1'-0"
A
B C D E FF
MIDWALK BENCH
BO
AR
DW
AL
K P
LA
N
RAMP
RAMP
S101
1S101
S200
S200
S200
AutoCAD SHX Text USER: Tom.Parker PLOTTED THE S100 LAYOUT OF C:\Users\TOM~1.PAR\AppData\Local\Temp\AcPublish_7956\25035001MyakkaBoardwalk20250828.dwg, ON Aug 29, 2025 @ 9:14am
AutoCAD SHX Text N
AutoCAD SHX Text N
AutoCAD SHX Text N
N
49'-8"
9'-11"
9'-11"
9'-11"
9'-11" 176.8°
179.97°
9'-9"
19'-9"
9'-11"
9'-11"
49'-4"
9'-9"
9'-9"
9'-9"
9'-9"
48'-8"
'-0"
8'-10"
7'-2"
6'-4"
90°
8'-9
8'-9
'-7"
4'-0"
ADA DROP RAIL WITH INTERPRETIVE SIGNAGE
WIDTH VARIES, ADA RAIL MAX WIDTH OF 72" –
REFER TO INTERPRETIVE SIGNAGE SIZE TABLE
ON SHEET G102ADA DROP RAIL
22'-4"
ADA DROP RAIL
AD
A
DR
O
P
RA
IL
AD
A
DR
O
P
RA
IL
3'-7
4'-4
2'-1
3'-7
4'-4
2'-1
'-0"
1'-0"
4'-4"
VARIES
VARIES
VARIES
4'-4"
2'-3"
ADA BENCH
ADACLEARANCE
30"X48"
ADATURNING
CLEARANCE60" DIA.
110 112
111 113
114 116
115 117
176.08°
151.95°
.12
9'-7" 8'-3" 8'-5" 8'-5" 8'-5" 8'-5" 8'-2"
50'-0" 8'-6"
8'-9"
8'-9"
8'-9"
43'-11"
9'-1
8'-9
'-7"
9'-1"
PLATE
LINE
PLATE
LINE
17.58' NAVD
(+) 3'-6" TOP OF RAIL
2x6 #2 SYP P.T. BOTTOM RAILING W/ CHAMFERED TOP EDGE INSTALLED BETWEEN POSTS, FASTEN TO INSIDE 2x6 W/ #10
2-1/2" SS SCREWS @ 6" O.C. (TYP.)
2x6 #2 SYP P.T. BOTTOM RAILING W/ CHAMFERED TOP EDGE
W/ WIRE MESH IN-BETWEEN FASTEN W/ SDS SS SCREWS TO
POST AND BASE
2" x 2" 10.5G 36W BLACK PVC COATED WIRE
MESH EQUAL TO RIVERDALE AQUAMESH
4x4 #1 SYP P.T. POST AT 60" O.C. MAX
2x4 #2 SYP P.T. INSTALLED BETWEEN POSTS, FASTEN TO INSIDE 2x4 W/ #10 2-1/2" SS SCREWS @ 6" O.C. (TYP.)
2x4 #2 SYP P.T. TOP RAILING W/ WIRE MESH IN-BETWEEN
FASTEN W/ 1/2"∅ SS CARRIAGE BOLT TO POST
2x8 WEARDECK CAP W/ ROUNDED EDGES (OR EQUAL) , FASTEN TO POST & 2x4 W/ 3" LONG SS SCREWS AT 12"
O.C. (CLIENT TO SELECT COLOR)
5/8"∅ GALVANIZED STEEL THRU
BOLTS W/ 2" WASHERS (TYP.)
3X12 PT BENT EACH SIDE OF 10" PILE. FASTEN TO PILE WITH 5X8"
GALVENIZED STEEL THOUGH BOLT WITH 2" WASHER AND NUT (TYP)
(2) 2X12 PT RIM JOIST EXTERIOR SIDE AND (1) 2X12 PT JOIST INTERIOR
SIDE OF 10" PILE. FASTEN TO PILE WITH 5X8" GALVANIZED STEEL
THOUGH BOLT WITH 2" WASHER AND NUT (TYP)
FASTEN 4X4 #1 SYP PT RAIL POST TO DOUBLE RIM JOIST WITH (2) 1/2"∅
THRU BOLTS W/ NUT AND 2" FLAT WASHERS (TYP.)
23 4" 3'-
31 4"
2X6 WEARDECK (OR EQUAL) FASTEN TO JOIST PER
MANUF. SPECIFICATION W/ STAINLESS STEEL
FASTENERS (CLIENT TO SELECT COLOR) (TYP)
3'- 6"
4" 4'-0" 73
4" 6'-11
4" 5" 5"
5'-03 4"
SIMPSON 2.5 CLIP STAINLESS STEEL OR EQUAL (TYP)
10" ROUND TIMBER PILE w/ 10'-0" EMBEDMENT MIN. (TYP)
2X12 PT JOIST AT 12" O.C. MAX (TYP)
14.08' NAVD
(+/-) 0'-0" TOP OF DECK
12.08' NAVD
(-) 2'-0" LOWEST HORZ MEMBER
9.58' NAVD
(-) 4'-7" AVG. EX. GRADE
EXTERIOR RAIL ELEV INTERIOR RAIL ELEV
PLATE
LINE
PLATE
LINE
5/8"∅ GALVANIZED STEEL THRU
BOLTS W/ 2" WASHERS (TYP.)
9" 2'-
1"
2X6 WEARDECK (OR EQUAL) FASTEN TO JOIST
PER MANUF. SPECIFICATION W/ STAINLESS STEEL
FASTENERS (CLIENT TO SELECT COLOR) (TYP)
3'- 6"
4" 4'-0" 73
4" 6'-11
4" 5" 5"
5'-03 4"
8" ADA OBSERVATIONAL RAILING DROP
8"
2'-
2x6 #2 SYP P.T. BOTTOM RAILING W/ CHAMFERED TOP EDGE INSTALLED BETWEEN POSTS, FASTEN TO INSIDE 2x6 W/ #10
2-1/2" SS SCREWS @ 6" O.C. (TYP.)
2x6 #2 SYP P.T. BOTTOM RAILING W/ CHAMFERED TOP EDGE
W/ WIRE MESH IN-BETWEEN FASTEN W/ SDS SS SCREWS TO
POST AND BASE
2" x 2" 10.5G 36W BLACK PVC COATED WIRE
MESH EQUAL TO RIVERDALE AQUAMESH
4x4 #1 SYP P.T. POST AT 60" O.C. MAX
2x4 #2 SYP P.T. INSTALLED BETWEEN POSTS, FASTEN TO INSIDE 2x4 W/ #10 2-1/2" SS SCREWS @ 6" O.C. (TYP.)
2x4 #2 SYP P.T. TOP RAILING W/ WIRE MESH IN-BETWEEN
FASTEN W/ 1/2"∅ SS CARRIAGE BOLT TO POST
2x8 WEARDECK CAP W/ ROUNDED EDGES (OR EQUAL) , FASTEN TO POST & 2x4 W/ 3" LONG SS SCREWS (CLIENT
TO SELECT COLOR)
3X12 PT BENT EACH SIDE OF 10" PILE. FASTEN TO PILE WITH 5X8"
GALVENIZED STEEL THOUGH BOLT WITH 2" WASHER AND NUT (TYP)
(2) 2X12 PT RIM JOIST EXTERIOR SIDE AND (1) 2X12 PT JOIST INTERIOR
SIDE OF 10" PILE. FASTEN TO PILE WITH 5X8" GALVANIZED STEEL
THOUGH BOLT WITH 2" WASHER AND NUT (TYP)
FASTEN (2) 2X12 PT TO 4X4 #1 SYP PT RAIL POST THAT IS
THEN FASTEN TO DOUBLE RIM JOIST WITH (2) 1/2"∅ THRU
BOLTS W/ NUT AND 2" FLAT WASHERS (TYP.)
SIMPSON 2.5 CLIP STAINLESS STEEL OR EQUAL (TYP)
10" ROUND TIMBER PILE w/ 10'-0" EMBEDMENT MIN. (TYP)
2X12 PT JOIST AT 12" O.C. MAX (TYP)
17.58' NAVD
(+) 3'-6" TOP OF RAIL
14.08' NAVD
(+/-) 0'-0" TOP OF DECK
12.08' NAVD
(-) 2'-0" LOWEST HORZ MEMBER
9.58' NAVD
(-) 6'-7" AVG. EX. GRADE
1'-0"
EXTERIOR DROP GUARDRAIL ELEV
3'-0" MIN. TO 5'-0" MAX
8" 2'-
" M
IN
3'- 6"
9"
INTERIOR DROP GUARDRAIL ELEV
3'-0" MIN. TO 5'-0" MAX
8" 2'-
" M
IN
3'- 6"
De sc rip tio n Re vi sio ns Pr oj ec t I nf or m at io n
Ap pr ov ed
B y:
Sc al e:
Jo b
N o.
Da te
Is su ed
De sig n:
Dr aw n:
Ch ec ke d:
Sheet No.
THIS SHEET IS NOT VALID WITHOUT
THE SIGNATURE AND ORIGINAL SEAL
OF A FLORIDA LICENSED ENGINEER.
W
ES
T M
AR
IO
N A
VE
N
U E
SU
IT
E
PU
N
TA
G O
R D
A, F
LO
R
ID
A
(9
) 5
-1
EB
CO
N
ST
RU
CT
IO
N P
LA
N
S
FO
R
Max Morgan Professional Engineer
State of Florida Registration No. 94877
Max Morgan, Professional Engineer, State of Florida, License No. 94877 This item has been digitally signed and sealed by Max Morgan, P.E.
on the date indicated here.
Signature must be verified on any electronic copies.
08-29-2025
THE WEILER ENGINEERING CORPORATION
WIND PARAMETERS
Method of Design: ASCE 7-22 Building Risk Category: RISK 1 Design Wind Speed: Ultimate Vult=141 MPH / Nominal Vasd = 111 MPH Wind Importance Factor: 1.00 / Wind Exposure: D Internal Pressure Coefficient: ±0.00 (OPEN) Component & Cladding Wind Pressure: per Calcs
FLOOD PARAMETERS
FEMA FIRM Map Number: 12115C0460G Base Flood Elevation: AE 9.80' NAVD 100-year, 1-hour Design Rainfall: 4.5 in (FBC 2023 Fig. 1611.1)
GEOTECHNICAL PARAMETERS
Data Source: Presumptive Load-Bearing Values of Soils, FBC 2023 1806.2 Vertical Bearing Capacity: 1,500 psf (FBC 2023 Table 1806.2) Lateral Bearing Pressure: 100 psf/ft (FBC 2023 Table 1806.2)
FOUNDATION SOIL AND TREATMENT
Soil Bearing Capacity Listed & the resultant foundation design assumes the soil type noted as per USGS web soil survey (or geotechnical engineering if provided). if inadequate substrate is discovered during site preparation the engineer shall be notified prior to placement of foundations.
These plans are in Compliance with Florida Building Code 2023 8th edition (FBC) for the parameters indicated.
S101
S . R
IV
ER
R D.
M
YA
KK
A
ST
AT
E F
OR
ES
T B
OA
RD
W
AL
K D
ES
IG
N
EN
GL
EW
O
O D, F L
/2 8/
5.0
BT
C
TW
P
TW
P
BOARDWALK PLAN D 1/4" = 1'-0"
GENERAL NOTES:
1. PILES SHALL HAVE EMBEDMENT TO MIN. DEPTH INDICATED OR TO
PRACTICAL REFUSAL AS DEFINED AS 20 BLOWS PER INCH OR LESS
THAN ONE INCH PENETRATION, WITH THE HAMMER OPERATING AT
THE HIGHEST SETTING DETERMINED BY THE ENGINEER AND LESS
THAN 1/4 INCHES REBOUND PER BLOW THEN PILE SHALL BE CUT TO
REQUIRED HEIGHT.
2. ALL BOLTS SHALL EXTEND PASS THE NUT BY A MINIMUM OF THREE (3)
THREADS AND A MAX OF 2".
3. THE CUTTING OF BOLTS SHALL BE AVOIDED. SHOULD BOLTS REQUIRE
CUTTING THE BOLT SHALL BE CUT USING VIRGIN CERAMIC GRINDING
DISK, THEN TREATED WITH PASSIVATION PASTE AND THE CUT SHALL
HAVE TWO COATS APPLIED OF COLD GALVANIZING PAINT.
BOARDWALK PLAN E 1/4" = 1'-0"
BOARDWALK PLAN F 1/4" = 1'-0"
BO
AR
DW
AL
K P
LA
N
WOOD BENCH
OBSERVATION DECK
1/2" = 1'-0"1
BOARDWALK CROSS SECTION
1/2" = 1'-0"2
BOARDWALK ADA DROP RAIL CROSS SECTION
1/2" = 1'-0"3
BOARDWALK RAIL ELEVATION
AutoCAD SHX Text USER: Tom.Parker PLOTTED THE S101 LAYOUT OF C:\Users\TOM~1.PAR\AppData\Local\Temp\AcPublish_7956\25035001MyakkaBoardwalk20250828.dwg, ON Aug 29, 2025 @ 9:14am
AutoCAD SHX Text N
AutoCAD SHX Text N
PLATE
LINE
PLATE
LINE
PLATE
LINE
PLATE
LINE
PLATE
LINE
PLATE
LINE
PLATE
LINE
PLATE
LINE
PLATE
LINE
PLATE
LINE
PLATE
LINE
PLATE
LINE
PLATE
LINE
PLATE
LINE
PLATE
LINE
PLATE
LINE
PLATE
LINE
PLATE
LINE
PLATE
LINE
PLATE
LINE
PLATE
LINE
PLATE
LINE
PLATE
LINE
PLATE
LINE
PLATE
LINE
14.08' NAVD
(+/-) 0'-0" TOP OF DECK (TYP.)
17.58' NAVD
(+) 3'-6" TOP OF RAIL (TYP.)
15.50' NAVD
(+) 1'-5" TOP OF SEAT (TYP.)
9.58' NAVD
(-) 4'-7" MEAN AVG EXISTING GRADE
12.08' NAVD
(-) 2'-0" LOWEST HORZ MEMBER
26.33' NAVD
(+) 12'-3" TOP OF ROOF (TYP.)
25.08' NAVD
(+) 11'-0" TOP OF UPPER BEARING
22.71' NAVD
(+) 8'-8" TOP OF LOWER BEARING
INTERPRETIVE
SIGNAGE
SIMPSON H10ASS CLIP AT EACH RAFTER
TO BEAM CONNECTION. UNO (TYP)
SIMPSON H3SS CLIP AT EACH RAFTER TO
END OF BEAM CONNECTION. UNO (TYP)
FASTEN CROSS BRACING TO RAFTER AND PILE
WITH 58" STAINLESS STEEL BOLT AND WASHERS
(TYP)
2'-4" O.H.
2'-4" O.H.
14.08' NAVD
(+/-) 0'-0" TOP OF DECK (TYP.)
17.58' NAVD
(+) 3'-6" TOP OF RAIL (TYP.)
15.50' NAVD
(+) 1'-5" TOP OF SEAT (TYP.)
9.58' NAVD
(-) 4'-7" MEAN AVG EXISTING GRADE
12.08' NAVD
(-) 2'-0" LOWEST HORZ MEMBER
25.08' NAVD
(+) 11'-0" TOP OF UPPER BEARING
26.33' NAVD
(+) 12'-3" TOP OF ROOF (TYP.)
22.71' NAVD
(+) 8'-8" TOP OF LOWER BEARING
INTERPRETIVE SIGNAGE
FASTEN 2X8 PT CROSS BRACING TO RAFTER AND
PILE WITH 58" STAINLESS STEEL BOLT AND
WASHERS (TYP)
2'-0" O.H.
2'-0" O.H.
2X10 PT RAFTERS @ 1'-4" O.C.
PROVIDE KYNAR COATING OVER FL33818.2 1.75 GULFSEAM
0.040 GA ALUMINUM X 16" STANDING SEAM ROOF OVER
FL27076.15 WEATHER-ARMOR HT3 UNDERLAYMENT OR
EQUIVALENT INSTALLED PER MANUFACTURER
SPECIFICATIONS OVER 3/4" SHEATHING NAILED W/
STAINLESS STEEL 12d RING SHANK AT 4" O/C AT EDGES & 6"
O/C IN FIELD AND W/ H-CLIPS OR TONGUE AND GROOVE ON
RAFTER TRUSSES SPACED 16" O.C.
ADA DROP RAIL (TYP)42" HIGH GUARDRAIL (TYP)
10" TIMBER PILE (TYP)
14.08' NAVD
(+/-) 0'-0" TOP OF DECK (TYP.)
17.58' NAVD
(+) 3'-6" TOP OF RAIL (TYP.)
15.50' NAVD
(+) 1'-5" TOP OF SEAT (TYP.)
9.58' NAVD
(-) 4'-7" MEAN AVG EXISTING GRADE
12.08' NAVD
(-) 2'-0" LOWEST HORZ MEMBER
25.08' NAVD
(+) 11'-0" TOP OF BEARING
26.33' NAVD
(+) 12'-3" TOP OF ROOF (TYP.)
9'- 3"
6'-
22.71' NAVD
(+) 8'-8" TOP OF LOWER BEARING
INTERPRETIVE SIGNAGE
2'-0" O.H.
2'-0" O.H.
PLATE
LINE
PLATE
LINE
14.08' NAVD
(+/-) 0'-0" TOP OF DECK (TYP.)
17.58' NAVD
(+) 3'-6" TOP OF RAIL (TYP.)
15.50' NAVD
(+) 1'-5" TOP OF SEAT (TYP.)
9.58' NAVD
(-) 4'-7" MEAN AVG EXISTING GRADE
12.08' NAVD
(-) 2'-0" LOWEST HORZ MEMBER
INTERPRETIVE SIGNAGE
ADA WOOD BENCH
14.08' NAVD
(+/-) 0'-0" TOP OF DECK (TYP.)
17.58' NAVD
(+) 3'-6" TOP OF RAIL (TYP.)
15.50' NAVD
(+) 1'-5" TOP OF SEAT (TYP.)
9.58' NAVD
(-) 4'-7" MEAN AVG EXISTING GRADE
12.08' NAVD
(-) 2'-0" LOWEST HORZ MEMBER
INTERPRETIVE SIGNAGE
ADA WOOD BENCH
14.08' NAVD
(+/-) 0'-0" TOP OF DECK (TYP.)
17.58' NAVD
(+) 3'-6" TOP OF RAIL (TYP.)
15.50' NAVD
(+) 1'-5" TOP OF SEAT (TYP.)
9.58' NAVD
(-) 4'-7" MEAN AVG EXISTING GRADE
12.08' NAVD
(-) 2'-0" LOWEST HORZ MEMBER
INTERPRETIVE SIGNAGE
ADA COMPLIANT WOOD BENCH.
FASTEN 2X6 PT WITH 3" FLAT HEAD SS
SCREWS AT 12"
1'- 5"
11"2'-0"
1'- 9"
4"
3'- 6"
11"2"2'-0"
14.08' NAVD
(+/-) 0'-0" TOP OF DECK (TYP.)
17.58' NAVD
(+) 3'-6" TOP OF RAIL (TYP.)
15.50' NAVD
(+) 1'-5" TOP OF SEAT (TYP.)
9.58' NAVD
(-) 4'-7" MEAN AVG EXISTING GRADE
12.08' NAVD
(-) 2'-0" LOWEST HORZ MEMBER
90°
84°
1"
STAINLESS STEEL 5
16" CARRIAGE BOLT
OF SUFFICIENT LENGTH TO FASTEN
BENCH PT WOOD MEMBERS WITH
WASHER AND NUT (TYP)
2X6 PT SYP (TYP)
80°
(2) 2X12 HDPE RIM JOIST FASTEN TO
PILES WITH 58" STAINLESS STEEL BOLT
AND WASHERS. FASTEN TO END OF
JOIST WITH (2) 30d COMMON NAIL
4X4 P.T. POST FASTEN TO DOUBLE RIM
JOIST WITH 12"X7" STAINLESS STEEL
BOLT W/ NUT AND WASHER
CONTINUOUS 2X4 P.T. RAIL FASTEN
TO 4X4 P.T. POST WITH 12"X5 12"
STAINLESS STEEL BOLT AND NUT,
PROVIDE WASHER
2X8 WEARDECK CAP W/ ROUNDED
EDGES (OR EQUAL) FASTEN TO 2X4
AND 4X4 POST WITH 3" FLAT HEAD
STAINLESS DECK SCREWS @ 12"O.C.
5'-8" 7'-11"
7'-10" 7'-10"
4'- 0"
2'- 7"
4'- 0"
2'- 7"
7'-11"
6'- 7"
6'- 7"
50'-7"
90°
ADA DROP RAIL WITH INTERPRETIVE SIGNAGE
WIDTH VARIES, ADA RAIL MAX WIDTH OF 72" –
REFER TO INTERPRETIVE SIGNAGE SIZE
TABLE ON SHEET G102
14.08' NAVD
(+/-) 0'-0" TOP OF DECK
10.10' NAVD
(-) 3'-11" START OF DECK
12.09' NAVD
(-) 2'-0" TOP OF LANDING DECK
RAMP SLOPE:
6.71%
1:14.9 RISE / RUN
3.84 DEGREES
RAMP SLOPE:
7.85%
1:12.7 RISE / RUN
4.49 DEGREES
3'- 6"
PLATE
LINE
9" 2'-
1"
3'- 6"
4" 5"
8"
2'-
INTERPRETIVE SIGNAGE MOUNT SHALL BE MANUFACTURED
BY BCE (BUREAU OF CORRECTIONAL ENTERPRISES), MODEL
SERIES INT-XXXX-30-REG-0, OR APPROVED EQUAL. MOUNT
TYPE SHALL BE REGULAR WOOD 4X4 PT POST BRACKET WITH
A 30° VIEWING ANGLE
17.58' NAVD
(+) 3'-6" TOP OF RAIL
14.08' NAVD
(+/-) 0'-0" TOP OF DECK
12.08' NAVD
(-) 2'-0" LOWEST HORZ MEMBER
9.58' NAVD
(-) 6'-7" AVG. EX. GRADE
1'-0"
NOTE:
INTERPRETIVE SIGNAGE IS A SITE-CONSTRUCTED, NON-ILLUMINATED,
NON‑FREESTANDING ASSEMBLY, ENGINEERED AND ATTACHED TO THE EXISTING
PERMITTED BOARDWALK STRUCTURE. PER FBC 2023 CHAPTER 1 AND CHAPTER 16 AND
FLORIDA ADMINISTRATIVE CODE RULE 61G20‑3.001, THE SIGNAGE DOES NOT CONSTITUTE
A BUILDING OR ENVELOPE COMPONENT AND THEREFORE IS EXEMPT FROM FLORIDA
PRODUCT APPROVAL REQUIREMENTS FOR LISTED PRODUCT CATEGORIES.
VA
RI
ES
SIG
N
CE
NT
ER
"-4
8"
30°
4X4 PT SIGNAGE POST FASTEN TO TO DOUBLE RIM
JOIST WITH (2) 1/2"∅ THRU BOLTS W/ NUT AND 2" FLAT
WASHERS (TYP.)
INTERPRETIVE SIGNAGE MOUNT (BCE MODEL
INT-XXXX-30-REG-0 OR APPROVED EQUAL) TO BE INSTALLED
ON EXTERIOR SIDE OF GUARDRAIL AT (2) ADA DROP RAIL
LOCATIONS AS INDICATED IN PLAN. REFER TO SHEET G102
INTERPRETIVE SIGNAGE FOR ADDITIONAL INFORMATION.
CONTRACTOR TO FURNISH AND INSTALL SIGN MOUNT PER
MANUFACTURER REQUIREMENTS. CLIENT TO PROVIDE
COMPLETED GRAPHIC PANEL TO BE INSTALLED BY
CONTRACTOR IN FIELD. SIGNAGE SIZE VARIES – CLIENT
SHALL SELECT FINAL SIZE AS REFERENCED ON SHEET G102.
De sc rip tio n Re vi sio ns Pr oj ec t I nf or m at io n
Ap pr ov ed
B y:
Sc al e:
Jo b
N o.
Da te
Is su ed
De sig n:
Dr aw n:
Ch ec ke d:
Sheet No.
THIS SHEET IS NOT VALID WITHOUT
THE SIGNATURE AND ORIGINAL SEAL
OF A FLORIDA LICENSED ENGINEER.
W
ES
T M
AR
IO
N A
VE
N
U E
SU
IT
E
PU
N
TA
G O
R D
A, F
LO
R
ID
A
(9
) 5
-1
EB
CO
N
ST
RU
CT
IO
N P
LA
N
S
FO
R
Max Morgan Professional Engineer
State of Florida Registration No. 94877
Max Morgan, Professional Engineer, State of Florida, License No. 94877 This item has been digitally signed and sealed by Max Morgan, P.E.
on the date indicated here.
Signature must be verified on any electronic copies.
08-29-2025
THE WEILER ENGINEERING CORPORATION
WIND PARAMETERS
Method of Design: ASCE 7-22 Building Risk Category: RISK 1 Design Wind Speed: Ultimate Vult=141 MPH / Nominal Vasd = 111 MPH Wind Importance Factor: 1.00 / Wind Exposure: D Internal Pressure Coefficient: ±0.00 (OPEN) Component & Cladding Wind Pressure: per Calcs
FLOOD PARAMETERS
FEMA FIRM Map Number: 12115C0460G Base Flood Elevation: AE 9.80' NAVD 100-year, 1-hour Design Rainfall: 4.5 in (FBC 2023 Fig. 1611.1)
GEOTECHNICAL PARAMETERS
Data Source: Presumptive Load-Bearing Values of Soils, FBC 2023 1806.2 Vertical Bearing Capacity: 1,500 psf (FBC 2023 Table 1806.2) Lateral Bearing Pressure: 100 psf/ft (FBC 2023 Table 1806.2)
FOUNDATION SOIL AND TREATMENT
Soil Bearing Capacity Listed & the resultant foundation design assumes the soil type noted as per USGS web soil survey (or geotechnical engineering if provided). if inadequate substrate is discovered during site preparation the engineer shall be notified prior to placement of foundations.
These plans are in Compliance with Florida Building Code 2023 8th edition (FBC) for the parameters indicated.
S200
S . R
IV
ER
R D.
M
YA
KK
A
ST
AT
E F
OR
ES
T B
OA
RD
W
AL
K D
ES
IG
N
EN
GL
EW
O
O D, F L
/2 8/
5.0
BT
C
TW
P
TW
P
NORTHEAST OBSERVATION DECK ELEVATION 1/4" = 1'-0" SOUTHWEST OBSERVATION DECK ELEVATION 1/4" = 1'-0" SOUTHEAST OBSERVATION DECK ELEVATION 1/4" = 1'-0"
EL
EV
AT
IO
NS
RAMP ELEVATION 1/4" = 1'-0"
NORTHWEST MIDWALK BENCH ELEVATION 1/4" = 1'-0"SOUTHEAST MIDWALK BENCH ELEVATION 1/4" = 1'-0"
3/4" = 1'-0"1
BENCH SECTION MIDWALK BENCH PLAN 1/2" = 1'-0"
5'-9" 3'-3"
2"
4'- 6"
S200.0
3/4" = 1'-0"2
BENCH SECTION
1/2" = 1'-0"3
INTERPRETIVE SIGNAGE
AutoCAD SHX Text USER: Tom.Parker PLOTTED THE S200 LAYOUT OF C:\Users\TOM~1.PAR\AppData\Local\Temp\AcPublish_7956\25035001MyakkaBoardwalk20250828.dwg, ON Aug 29, 2025 @ 9:14am
CL
2X6 BEAM
RIDGE CAP 24 GAUGE 5-V
CRIMP METAL
ROOFING
METAL ROOF GABLE
END FLASHING
ASSEMBLY
6' X 4' DISPLAY
PANEL ULINE
ENCLOSED CORK
BOARD H-5823
2X6 PT BOTTOM RAILS
6X6 PT POSTS (SEE
FRAMING)
1'- 6"
6'-6"
2X6 FASCIA BEAM
1'- 0"
6" 3'-
7" 1'-
0"
8'- 0"
9'-10"
2X6 CROSS
BRACKING
PROVIDE KYNAR COATING OVER FL33818.2 1.75 GULFSEAM
0.040 GA ALUMINUM X 16" STANDING SEAM ROOF OVER
FL27076.15 WEATHER-ARMOR HT3 UNDERLAYMENT OR
EQUIVALENT INSTALLED PER MANUFACTURER
SPECIFICATIONS OVER 3/4" SHEATHING NAILED W/
STAINLESS STEEL 12d RING SHANK AT 4" O/C AT EDGES & 6"
O/C IN FIELD AND W/ H-CLIPS OR TONGUE AND GROOVE ON
RAFTER TRUSSES SPACED 16" O.C.
3/4" SHEATHING
ED-1 EAVE DRIP FLASHING PER
MANUFACTURER
TWIST STRAP (SIMPSON LTS12 OR APPROVED
EQUAL) BOTH SIDES @ EA. END OF BEAM
PAVING AS PER SITE SPECIFIC SITE PLAN
(LAYOUT TO BE DETERMINED BY PROJECT)
RC-8 RIDGE CAP W/
CLOSURE STRIPS PER MANU.
2X6 PT RAFTERS @ 1'-6"
O.C., PLUMB CUT
2X6 PT BEAMS, CONNECT TO POST W/ (2)
1/2"Ø BOLTS
DISPLAY PANEL
2X6 PT RAILS LET-IN & BOLTED TO POST (2) 1/2"Ø
BOLTS, NUTS & WASHERS (RECESS BOLT HEADS
INTO POSTS) (TYP.)
6X6 PT POST (SEE FRAMING)
2X6 PT BRACING, ATTACH @ EA. BEAM
W/ (2) 1/2" X 8" LAG SCREW
2X6 BOTTOM CORD
TORCH APPLIED ROT PROTECTOR POST SAVER
PRO-SLEEVE OR EQUAL APPLY PER MANUFACTURER
SPEC.
(+) 8'-0" BEARING HGT
(+) 10.40' NAVD
(-) 7'-0" PILE BOTTOM
(-) 9.4' NAVD
(+/-) 0'-0" FINISHED GRADE
(+) 2.4' NAVD
(+) 10'-0" ROOF HEIGHT
(+) 12.37' NAVD
7' EMBED
INSTALL CORK BOARD DISPLAY PER
MANUFACTURERS SPECIFICATIONS
2X8 RIDGEBOARD, FASTEN
RAFTERS TO RIDGEBOARD W/ (1)
#8X3" SCREW EA. RAFTER BOARD
SIMPSON ML23Z ANGLE OR
EQUAL W/ (4) 1/4"X1 1/2" SDS
FASTENERS BEAM TO BEAM
SIMPSON H3 HURRICANE CLIPS (BOTH
SIDES) @ EA. END OF RAFTERS (BOTH
SIDES) TO BEAMS BELOW, TYP.
PITCH: 6 58"
12"
2X6 PT FASCIA
1X PT NAILER
2X6 PT CROSS BRACING
2X6 PT BLOCKING
2X6 PT BLOCKING
FASTEN 2X6 FASCIA TO BEAMS
W/ (2) 16d RINGSHANK NAILS
EA. END
ATTACH W/
SIMPSON LTS12
OR EQUAL
2X6 BEAM BELOW, ATTACH
TO 6X6 POSTS W/ W/ (2)
1/2"Ø THRU BOLTS W/ NUTS
& WASHERS EA. WAY. BEAM
TO BEAM
2X6 BEAMS @
1'-6" O.C. (TYP)
9'-8"
4'- 9"
2'- 5"
2'- 5"
6'-6"1'-7" 1'-7"
1'-4"1'-4"1'-4"9" 1'-4" 1'-4"1'-4" 9"
SIMPSON ML23Z ANGLE OR
EQUAL W/ (4) 1/4"X1 1/2" SDS
FASTENERS BEAM TO BEAM
SIMPSON H3 HURRICANE CLIPS
(BOTH SIDES) @ EA. END OF
RAFTERS (BOTH SIDES) TO
BEAMS BELOW, (TYP.)
RAFTER
FRAMING AT 16" O/C
MIN. 3/4" SHEATHING
PLYWOOD CLIPS OR T&G
SHEATHING
12d RING SHANK NAILS
AT 6"O/C IN FIELD
12d RING SHANK NAILS
AT 4" O/C AT EDGES
KIOSK COMPONENTS AND CLADDING SCHEDULE
DESCRIPTION REMARKSNOA/FBC
APPROVALMODEL OR SERIESMANUFACTURE
FPA#: FL33818.2
EXP: 10/06/2026
WIND: +/- 164.25 PSF
GULFSEAMGULFCOAST1.75" GULFSEAM 0.040" STANDING SEAM ALUMINUM ROOF
FPA#: 20-0714.01
EXP: 03/28/2028WEATHER ARMORAPOCWEATHER-ARMOR HT3 UNDERLAYMENT MODIFIED BITUMINOUS SELF-ADHERING UNDERLAYMENT
0.040 GA X16" ALUMINUM W/ KYNAR COATING
De sc rip tio n Re vi sio ns Pr oj ec t I nf or m at io n
Ap pr ov ed
B y:
Sc al e:
Jo b
N o.
Da te
Is su ed
De sig n:
Dr aw n:
Ch ec ke d:
Sheet No.
THIS SHEET IS NOT VALID WITHOUT
THE SIGNATURE AND ORIGINAL SEAL
OF A FLORIDA LICENSED ENGINEER.
W
ES
T M
AR
IO
N A
VE
N
U E
SU
IT
E
PU
N
TA
G O
R D
A, F
LO
R
ID
A
(9
) 5
-1
EB
CO
N
ST
RU
CT
IO
N P
LA
N
S
FO
R
Max Morgan Professional Engineer
State of Florida Registration No. 94877
Max Morgan, Professional Engineer, State of Florida, License No. 94877 This item has been digitally signed and sealed by Max Morgan, P.E.
on the date indicated here.
Signature must be verified on any electronic copies.
08-29-2025
THE WEILER ENGINEERING CORPORATION
WIND PARAMETERS
Method of Design: ASCE 7-22 Building Risk Category: RISK 1 Design Wind Speed: Ultimate Vult=141 MPH / Nominal Vasd = 111 MPH Wind Importance Factor: 1.00 / Wind Exposure: D Internal Pressure Coefficient: ±0.00 (OPEN) Component & Cladding Wind Pressure: per Calcs
FLOOD PARAMETERS
FEMA FIRM Map Number: 12115C0460G Base Flood Elevation: AE 9.80' NAVD 100-year, 1-hour Design Rainfall: 4.5 in (FBC 2023 Fig. 1611.1)
GEOTECHNICAL PARAMETERS
Data Source: Presumptive Load-Bearing Values of Soils, FBC 2023 1806.2 Vertical Bearing Capacity: 1,500 psf (FBC 2023 Table 1806.2) Lateral Bearing Pressure: 100 psf/ft (FBC 2023 Table 1806.2)
FOUNDATION SOIL AND TREATMENT
Soil Bearing Capacity Listed & the resultant foundation design assumes the soil type noted as per USGS web soil survey (or geotechnical engineering if provided). if inadequate substrate is discovered during site preparation the engineer shall be notified prior to placement of foundations.
These plans are in Compliance with Florida Building Code 2023 8th edition (FBC) for the parameters indicated.
S300
S . R
IV
ER
R D.
M
YA
KK
A
ST
AT
E F
OR
ES
T B
OA
RD
W
AL
K D
ES
IG
N
EN
GL
EW
O
O D, F L
/2 8/
5.0
BT
C
TW
P
TW
P
KI
OS
K P
LA
N
3/4" = 1'-0"C
KIOSK SECTION DETAIL
3/4" = 1'-0"B
KIOSK ROOF FRAMING
3/4" = 1'-0"D
KIOSK ROOF SHEATHING ATTACHMENT
3/4" = 1'-0"A
KIOSK ELEVATION
KIOSK CONSTRUCTION NOTES AND SPECIFICATIONS:
1. REFER TO CIVIL PLANS FOR LOCATION OF KIOSK
2. DO NOT SCALE FROM DRAWINGS.
3. ALL WORK SHALL BE IN ACCORDANCE WITH THE FLORIDA BUILDING CODE 8TH EDITION, 2023.
4. VERIFY ALL DIMENSIONS AND SITE CONDITIONS PRIOR TO START OF CONSTRUCTION. NOTIFY THE ARCHITECT / ENGINEER
OF ANY DISCREPANCIES OR INCONSISTENCIES.
5. NO CHANGES OF INFORMATION SHOWN ON THE DRAWINGS SHALL BE MADE WITHOUT THE SPECIFIC WRITTEN APPROVAL
OF THE ARCHITECT / ENGINEER.
6. DESIGN INFORMATION SHOWN ON THE DRAWINGS PROVIDE OVERALL DIMENSIONAL PARAMETERS AND DESCRIBE ELEMENTS TO BE CONSTRUCTED. THE CONTRACTOR SHALL ADJUST DIMENSIONS AND DETAILS AS REQUIRED TO FIT EXISTING CONDITIONS. THE ARCHITECT / ENGINEER SHALL BE NOTIFIED OF ANY PROPOSED MODIFICATIONS.
7. DEMOLITION SHALL INCLUDE REMOVAL, TRANSPORT AND DISPOSAL OF ALL WASTE MATERIAL RELATED TO THE
CONSTRUCTION OF THE PROJECT TO AN APPROVED DISPOSAL FACILITY.
8. THE CONTRACTOR IS TO FLAG THE CONSTRUCTION BOUNDARIES FOR INSPECTION AND APPROVAL BY THE OWNER.
9. ALL EXTERIOR WOOD, UNLESS NOTED OTHERWISE (UNO) SHALL BE S4S NO. 2 SOUTHERN YELLOW PINE K.D. AFTER TREATMENT. TREATMENT SHALL BE IN ACCORDANCE WITH AWPA STANDARDS FOR MCQ .40P/CF. FOR ABOVE GROUND, .40P/CF. FOR GROUND & FRESHWATER CONTACT, .60P/CF. FOR PERMANENT FOUNDATION USE. CUT SURFACES OF TREATED WOOD SHALL BE TREATED WITH PRESERVATIVE IN ACCORDANCE WITH AWPA STANDARD M4. COPPER
NAPHTHENATE SOLUTION SHALL BE BRUSHED INTO ALL BOLT HOLES.
10. PLYWOOD ROOF DECK SHALL BE 34" PRESSURE TREATED EXT. GRADE BC (UNO) WITH "B" FACE VISIBLE.
11. ROOF MATERIAL SHALL BE 5 'V' CRIMP, 24 GA. FOREST GREEN, GALV. OR GALVALUME. PROVIDE PROPER SEPARATION BETWEEN METAL AND ANY TREATED WOOD. APPLY ROOFING METAL OVER 30# ROOF FELT ON PLYWOOD SHEATHING, IN ACCORDANCE WITH MANU. RECOMMENDATIONS FOR CODE AND WIND UPLIFT PER LOCATION OF INSTALLATION. (ROOF PANELS BY GULF COAST OR EQ.). PANELS SHALL BE FASTENED, AT A MINIMUM, WITH 1-1/2" LONG #9 GALVANIZED OR STAINLESS STEEL WOODS WITH BONDED NEOPRENE WASHERS. COLOR OF FASTENER TO MATCH PANEL COLOR. SPACED AT 6" O.C. ALONG PANEL FLASHING, TRIMS, EDGES, EAVES VALLEYS, GABLED ENDS, HIPS, AND RIDGES. SPACED 16" O.C.
ON PANEL RIBS AT INTERMEDIATE FIELDS. DO NOT OVER TIGHTEN FASTENERS. NO DIMPLES ALLOWED.
12. WOOD PILINGS/POSTS SHALL COMPLY WITH SECTION 1809 FBC, LATEST EDITION, AND SHALL BE NO. 2 SYP. PILES SHALL COMPLY WITH DOC PS-20. TREATMENT SHALL BE IN ACCORDANCE WITH AWPA STANDARDS FOR ROUND OR SAWN TIMBER PILES. PILINGS MAY BE DRIVEN OR JETTED WITH THE LAST ONE FOOT DRIVEN. DEPTH WILL VARY BY SITE PER GEOTECH.
RECOMMENDATIONS.
13. UNLESS NOTED OTHERWISE (UNO) ALL METAL CONNECTORS SHALL BE STAINLESS STEEL MANUFACTURED SIMPSON
STRONG TIE OR EQ. FASTEN IN ACCORD WITH MANUFACTURER'S REQUIREMENTS.
14. UNLESS NOTED OTHERWISE (UNO) ALL FASTENERS, SCREWS, ANGLES AND METAL CLIPS TO BE STAINLESS STEEL WITH
STAINLESS STEEL BOLTS, NUTS AND WASHERS. MEET SPECIFICATIONS OF ASTM A153
15. DESIGN LOADS:
15.1. SUPERIMPOSED DEAD LOADS:
15.2. DEAD LOADS SHALL BE TAKEN AS THE ACTUAL WEIGHTS OF MATERIALS AND CONSTRUCTIONS OR OTHERWISE
SATISFACTORY VALUES DESCRIBED IN THE FLORIDA BUILDING CODE.
15.3. SUPERIMPOSED LIVE LOADS:
15.3.1. ROOF 20 PSF
15.3.2. DESIGN WIND LOADS:
15.3.1.1. GOVERNING CODE ASCE 7-22
15.3.1.2. ULTIMATE DESIGN WIND SPEED V=141 MPH
15.3.1.3. BUILDING RISK CATEGORY I
15.3.1.4. EXPOSURE - MWFRS D
15.3.1.5. CLADDING AND COMPONENT SEE SCHEDULE
15.3.1.6. INTERNAL PRESS. COEF. GCPI=/-0.00 (OPEN BUILDING)
15.3.1.7. MEAN ROOF HIGH 8.5 FEET
15.3.1.8. WIND DIRECTIONAL FACTOR Kd=0.85
15.3.1.9. ULTIMATE DESIGN PRESSURES (PSF) FOR COMPONENTS AND CLADDING SURFACES:
15.3.1.9.1. ROOF SURFACE(+46, -88 PSF)
15.3.1.9.2. VERTICAL SURFACE(+53, -53 PSF)
16. DISPLAY PANEL BACKING TO BE 34" BC TREATED PLYWOOD, "B" FACE ON THE DISPLAY PANEL SIDE. DISPLAY PANEL GRAPHICS TO BE PROVIDED BY OTHERS. IT IS THE SOLE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY AND ENSURE THAT DISPLAY PANELS ARE SIZED IN ACCORDANCE WITH PANEL GRAPHICS. INCORRECT DISPLAY PANELS SIZES ARE NOT ACCEPTABLE. BACKBOARD PANEL & TRIM FINISH: APPLY ALKYD BASED PRIMER & 2 TOP COATS PAINT COLOR TO MATCH
BENJ.. MOORE #HC 130.
USER: Tom.Parker PLOTTED THE S300 LAYOUT OF C:\Users\TOM~1.PAR\AppData\Local\Temp\AcPublish_7956\25035001MyakkaBoardwalk20250828.