APPENDIX B CONSTRUCTION PLANS.pdf

PDF 8 MB Posted

Attached to
Aztec Water Treatment Facility Clearwell Expansion
Solicitation number
2026-879
Issued by
San Juan County, New Mexico

About this file

These are engineering and design documents for the Aztec Water Treatment Plant Clearwell Expansion Project located in Aztec, New Mexico, within San Juan County. The project involves expanding the existing water treatment facility clearwell (water storage reservoir) by constructing three additional clearwell sections, installing new piping, removing and replacing an existing railroad tie retaining wall with a concrete retaining wall, and making connections between the new and existing clearwell structures. The project is documented in a comprehensive set of civil and structural engineering drawings prepared by GEOMAT and dated September 8, 2025, with a project number of 242-4792. The design includes detailed plans for grading, backwash piping, retaining wall profiles, reinforcing details, and specific construction sequencing.

The project documents indicate a structured approach to expansion, with specific technical requirements for concrete mixing, reinforcement, water stops, and connection methods between new and existing structures. The design incorporates specialized materials like Xypex concrete additives and waterproofing treatments, and includes precise specifications for reinforcing steel, concrete cover, and lap lengths. While no specific budget is mentioned in the documents, the comprehensive nature of the design suggests a significant municipal infrastructure investment aimed at improving water treatment capacity and facility infrastructure. The project appears to be funded through municipal engineering and infrastructure development channels, with careful attention to technical specifications and construction methodologies.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Navajo Dam

Road 2978

Az te c Bl vd

Navajo Dam Road

Ro ad

NM 173

US

Proj:

Project Date:

HC Eng ineer s , LLC

50 Valley Court Durango, CO 970-387-8765

C

AZ

TE

C

CL

EA

RW

EL

L

EX

PA

N

SI

O N

24009

Ci ty o f

Az te c

2025-07-29

CO

VE

R

SH

EE

T

Aztec Clearwell Expansion City of Aztec, New Mexico

San Juan County

Project Location

Project Location

Vicinity Map Scale: 1"= 2000'

N or th

3.3 miles from Us 550

Sheet List Table Sheet Number Sheet Title

000 Cover Sheet C-100 Layout Plan C-200 Grading Plan North C-201 Grading Plan South C-300 Backwash Pipe Plan and

Profile C-301 Retaining Wall Profile C-400 Details

S1 Notes S2 Overview and Retaining Wall S3 Clearwell Expansion Plan S4 Reinforcing Details

APPENDIX B

ITB 2026-879

AZTEC WATER TREATMENT FACILITY CLEARWELL EXPANSION

12" Steel Pipe Area Drain

15" AC Pipe Unknown

Existing 4" PVC #2 Waste Line

Exisitng 18" Filtered Water Feed To Clearwell

4" PVC Pipe

Backwash Pond

HWL 5700.1

Existing Raw Water for #1 (abandoned)

Inv 5701.5

Inv 5705.2

Ex ist in g

Cl ea rw el l

5705.14 Inv:5694.89

Remove existing concrete swale

5' wide Valley Gutter

Remove existing railroad tie retaining wall Replace with Concrete Retaining Wall ref. structural

Corner Transformer Pad Elev:5705.80

Pr op os ed

E xp an sio n

Waterline to be Abandoned

Proj:

Project Date:

HC Eng ineer s , LLC

50 Valley Court Durango, CO 970-387-8765

C

AZ

TE

C

CL

EA

RW

EL

L

EX

PA

N

SI

O N

24009

C-100

Ci ty o f

Az te c

2025-07-29

LA

YO

U T

PL

AN

N O R T H

Suggested Construction Sequence:

1. Rough Site Grading

2. Demo railroad tie retaining wall and concrete swale

3. Excavate for Clearwell

4. Construct Clearwell

5. Disinfect Clearwell

6. Coordinate with WTP to pump down existing clearwell. 3' of water will not be pumped out of clearwell (approximately 30,000 Gallons). This water must be dechlorinated before releasing into waterways.

3. Build new retaining wall

5. Build 24" Backwash Piping.

6. Remove existing piping.

7. Pump out 3' of existing clearwell.

8. Cut holes into existing clearwell.

9. Clean area and Spot Disinfect.

10. Fill and Leak Test.

11. Put clearwell into service.

5. Coordinate with WTP to pump down existing clearwell.

6. Pump out 3' of existing clearwell.

7. Build Baffle Wall in existing clearwell.

8. Clean area and Spot Disinfect.

9. Fill and Leak Test.

10. Put clearwell into service.

11. Finish Grade Site.

12. Build Concrete Valley Gutter.

20.63'

.7

9'

27'

.7

9'

6.38'

Corner Transformer Pad Elev:5705.80

Existing

4 SY 6"-9" River Rock, 18" deep

Flow Line (typ)

Remove Drain and Backfill

Remove Drain and Backfill

Remove Drain and Backfill

Remove Drain and Backfill

New 24" CMP Backwash Line (See Plan and Profile)

Grade Break (typ)

Grade Break (typ)

Grade Break (typ)

22'

9.83'

Completely remove exisitng 24" CMP Backwash Line

Note:

- Recent excavations in the clearwell expansion work area to full depth show no ground water.

- The backwash pond will have water in it during construction. The contractor shall use every caution to not introduce this water into the work area. This would include scheduling the required pipe removals and installations that would breach the water when it will not harm the work area.

Another option could be draining the pond by pumping to remove the danger. No payment will be made for dewatering.

Grade Area to elevations shown. Site Grading Volumes from finshed design surface to existing surface is ~600 CY Export. This does not include the required removal for the clearwell expansion, or imported material like concrete.

Proj:

Project Date:

HC Eng ineer s , LLC

50 Valley Court Durango, CO 970-387-8765

C

AZ

TE

C

CL

EA

RW

EL

L

EX

PA

N

SI

O N

24009

C-200

Ci ty o f

Az te c

2025-07-29

G

RA

DI

N

G P

LA

N

N O

RT

H

N O R T H

20.63'

.7

9'

27'

.7

9'

6.38'

Corner Transformer Pad Elev:5705.80

Existing 30" Culvert Invert: 5700.1

4 SY 6"-9" River Rock, 18" deep

Remove Drain and Backfill

Remove Drain and Backfill

Remove Drain and Backfill

Remove Drain and Backfill

New 24" CMP Backwash Line (See Plan and Profile)

22'

9.83'

Completely remove exisitng 24" CMP Backwash Line

Note:

- Recent excavations in the clearwell expansion work area to full depth show no ground water.

- The backwash pond will have water in it during construction. The contractor shall use every caution to not introduce this water into the work area. This would include scheduling the required pipe removals and installations that would breach the water when it will not harm the work area.

Another option could be draining the pond by pumping to remove the danger. No payment will be made for dewatering.

Grade Area to elevations shown. Site Grading Volumes from finshed design surface to existing surface is ~600 CY Export. This does not include the required removal for the clearwell expansion, or imported material like concrete.

Proj:

Project Date:

HC Eng ineer s , LLC

50 Valley Court Durango, CO 970-387-8765

C

AZ

TE

C

CL

EA

RW

EL

L

EX

PA

N

SI

O N

24009

C-201

Ci ty o f

Az te c

2025-07-29

G

RA

DI

N

G P

LA

N

S O

U

TH

N O R T H

Provide Manufactured 58° Bend

Existing Grade

Proposed Grade

Proj:

Project Date:

HC Eng ineer s , LLC

50 Valley Court Durango, CO 970-387-8765

C

AZ

TE

C

CL

EA

RW

EL

L

EX

PA

N

SI

O N

24009

C-300

Ci ty o f

Az te c

2025-07-29

BA

CK

W

AS

H P

IP

E

PL

AN

A N

D

PR

O

FI

LE

5705.0 5704.05

5710.0 Top Wall at wall corner

5704.71 Bottom Wall / Top Conc V Channel

5710.0 Top Wall

at existing building

5705.18

110.03'

55.12'54.9'

Proj:

Project Date:

HC Eng ineer s , LLC

50 Valley Court Durango, CO 970-387-8765

C

AZ

TE

C

CL

EA

RW

EL

L

EX

PA

N

SI

O N

24009

C-301

Ci ty o f

Az te c

2025-07-29

RE

TA

IN

IN

G W

AL

L

PR

O

FI

LE

Retaining Wall

30" Cover

Bottom of trench should be smooth with no rocks. If bedrock is encountered Place 4" of clean native material in bottom of trench below pipe.

Place clean native material around pipe. No rocks over 1/2" within 6" of pipe.

Carefully backfill and compact with native material at maximum 6" lifts.

Scale: NTS

Trench Detail

6"

5'

1"

#4 Rebar at 24" O.C.

#4 Rebar at 9" O.C.

Centered in slab

TYPICAL MANHOLE TYPE "C"

GENERAL NOTES:

CONSTRUCTION NOTES:

B

12"

MIN.

1 2"

M

IN

-6

' M

AX

3"

6"

1'-103 4"

12"

MIN. O.D. +12" MIN.

6"

2"

P PIPE

I.D.

P

12"

CONSTRUCTION NOTES:

TYPICAL CONCRETE MANHOLE COVER TYPE "C"

7'-4" FOR 6 FT. I.D. M.H.

2"

1'-103

4" DIA.

2"

1'-101 8"

1/2" Expansion Joint - Full Depth of Pour, Seal top 1/2" with polyurethane caulk

Proj:

Project Date:

HC Eng ineer s , LLC

50 Valley Court Durango, CO 970-387-8765

C

AZ

TE

C

CL

EA

RW

EL

L

EX

PA

N

SI

O N

24009

C-400

Ci ty o f

Az te c

2025-07-29

DE

TA

IL

S

GENERAL NOTES:

DRAWINGS SHOULD NOT BE SCALED TO OBTAIN DIMENSIONS.

DRAWINGS LABELED “PRELIMINARY” OR “NOT FOR CONSTRUCTION” ARE

SUBJECT TO CHANGE.

THE CONTRACTOR SHALL BE RESPONSIBLE FOR ADHERING TO ALL

APPLICABLE SAFETY STANDARDS SET FORTH BY THE OWNER AND/OR OHSA.

IT SHALL BE THE CONTRACTORS RESPONSIBILITY TO VERIFY ALL

DIMENSIONS IN THE FIELD PRIOR TO FABRICATION AND TO ADJUST THE

DETAILS ACCORDINGLY.

THE STRUCTURE SHOWN IN THE DRAWINGS HAS BEEN DESIGNED FOR

STABILITY IN ITS FINAL STATE. THE CONTRACTOR SHALL BE RESPONSIBLE

FOR ALL REQUIRED SHORING AND TEMPORARY BRACING FOR STABILITY

DURING CONSTRUCTION.

THE CONTRACTOR SHALL NOT NOTCH OR CUT ANY STRUCTURAL MEMBER

IN THE FIELD WITHOUT PERMISSION FROM THE STRUCTURAL ENGINEER.

CODES AND MANUALS:

IBC-21 INTERNATIONAL BUILDING CODE 2021

ASCE/SEI 7-05 MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER

STRUCTURES

ACI 318 BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE

DESIGN CRITERIA:

LIVE LOAD

FLOOR - 100 PSF

POINT LOAD @ LID = 16,000 POUNDS FOR TIRE LOAD

DEAD LOAD - SELF WEIGHT

SNOW LOAD:

GROUND SNOW LOAD - PF=30 PSF

SNOW EXPOSURE FACTOR - CE=1.0

SNOW LOAD IMPORTANCE FACTOR - IS=1.0

THERMAL FACTOR - CT=1.0

ALLOWABLE BEARING PRESSURE = 2,500 PSF.

FUTURE BUILDING EXPANSION: NONE

REQUIRED REINFORCING LAP LENGTH

TYPE OF USE BAR DIRECTION BAR SIZE MINIMUM LAP

LENGTH

FOOTINGS/STEM

WALLS ALL BARS ALL BARS

18 BAR DIAMETERS

(18" MINIMUM)

RETAINING WALLS

VERTICAL BARS NO. 6 AND SMALLER

NO.7 AND LARGER

57 DIAMETERS

72 DIAMETERS

HORIZONTAL

BARS ALL BARS

30 BAR DIAMETERS

(18" MINIMUM)

SLABS-ON-GRADE ALL BARS ALL BARS

30 BAR DIAMETERS

(18" MINIMUM)

CONCRETE REINFORCING COVER

TYPE OF USE BAR SIZE/ELEMENT COVER

CAST AGAINST AND PERMANENTLY

EXPOSED TO EARTH ALL BARS 3"

CAST AGAINST FORMS BUT EXPOSED

TO EARTH OR WEATHER

GREATER THAN NO. 5 2"

NO. 5 OR SMALLER 1 1/2"

CONCRETE NOT EXPOSED TO EARTH

OR WEATHER

COLUMNS, GIRDERS, AND

BEAMS 1 1/2"

STRUCTURAL SLABS, WALLS,

AND JOISTS 3/4"

SCOPE:

THESE PLANS WERE PREPARED BY GEOMAT INC. OF FARMINGTON, NEW

MEXICO TO SHOW THE STRUCTURAL REQUIREMENTS FOR THE

CONSTRUCTION OF AN ADDITION TO THE CITY OF AZTEC CLEARWELL

LOCATED AT THE THE CITY OF AZTEC WATER TREATMENT PLANT IN AZTEC,

NEW MEXICO. ANY OTHER USE OF THESE PLANS IS PROHIBITED.

GEOMAT'S SCOPE OF SERVICES WAS LIMITED TO THE STRUCTURAL DESIGN

OF THE CLEARWELL ADDITION. ALL OTHER ASPECTS OF THE DESIGN SUCH

AS CONFIGURATION, OPENING LOCATIONS, PIPES, ELEVATIONS, ETC, ARE

ALL BY OTHERS.

THESE PLANS SHALL BE USED IN CONJUNCTION WITH THE CLEARWELL

DESIGN PLANS BY CHC ENGINEERS, LLC OF DURANGO, COLORADO. IF

THERE ARE DISCREPANCIES , THEY SHALL BE BROUGHT TO THE ATTENTION

OF THE DESIGN TEAM FOR RESOLUTION.

FOUNDATION:

A GEOTECHNICAL INVESTIGATION WAS PERFORMED BY GEOMAT

INC. OF FARMINGTON, NEW MEXICO. A REPORT IS AVAILABLE FROM

THE OWNER (GEOMAT PROJECT # 242-4907). THE CONTRACTOR

SHALL REVIEW THAT REPORT AND ABIDE BY THE

RECOMMENDATIONS MADE THEREIN.

SUBGRADE AND STRUCTURAL FILL PREPARATION

CONCRETE REINFORCED SLAB FOUNDATION AND RETAINING WALL

FOOTINGS SHOULD BEAR ON ENGINEERED FILL OR ON COMPACTED

NATIVE COBBLES AND GRAVELS, BUT NOT A COMBINATION OF THE

TWO MATERIALS.

IF THE STRUCTURAL SLAB IS TO BE SUPPORTED ON COMPACTED

NATIVE COBBLES AND GRAVEL, THE SURFACE OF THE NATIVE

GRAVELS AND COBBLES SHOULD BE PROOF COMPACTED UNDER

OBSERVATION BY A REPRESENTATIVE OF GEOMAT. DUE TO THE

ROCKY NATURE OF THE NATIVE GRAVELS AND COBBLES, PLACE A

THREE TO FOUR-INCH LEVELING COURSE OF OPEN-GRADED GRAVEL

OR COMPACTED BASE BETWEEN THE BOTTOM OF THE FOOTINGS

AND THE UNDERLYING COMPACTED COBBLES AND GRAVELS.

IF THE ANTICIPATED COBBLES AND GRAVEL ARE NOT

ENCOUNTERED, REPLACE THE LEVELING COURSE WITH

COMPACTED AGGREGATE BASE COURSE (ABC) FOR A DEPTH BELOW

THE FOOTING OF NOT LESS THAN ONE (1.0) FOOT FOR THE

CLEARWELL & 2'-0" MINIMUM FOR THE RETAINING WALL. THE ABC

SHOULD EXTEND BEYOND THE EDGES OF THE FOOTINGS AS

INDICATED IN THE GEOTECHNICAL REPORT.

IF ANY EXISTING FILL MATERIAL IS ENCOUNTERED DURING

EXCAVATIONS, THE FILL SHOULD BE COMPLETELY REMOVED FROM

BENEATH THE STRUCTURE AND REPLACED WITH ENGINEERED FILL.

STRUCTURAL FILL SHALL BE PLACED IN LIFTS NOT EXCEEDING 8

INCHES IN THICKNESS WHEN COMPACTED. PLACE FILL AT NEAR

OPTIMUM MOISTURE CONTENTS AND COMPACT TO A MINIMUM

OF 95% OF A MODIFIED PROCTOR (ASTM D1557).

IMPORTED OR EXISTING SOILS THAT CONFORM TO THE FOLLOWING

MAY BE USED FOR STRUCTURAL FILL:

GRADATION PERCENT FINER BY WEIGHT (ASTM C136)

3”

NO. 4 SIEVE.......................................................50-100

NO. 200 SIEVE...................................................50 MAX

STRUCTURAL FILL SHALL HAVE A MAXIMUM EXPANSIVE POTENTIAL

OF 1.5% MEASURED ON A SAMPLE COMPACTED TO

APPROXIMATELY 95 PERCENT OF THE ASTM D1557 MAXIMUM DRY

DENSITY AT ABOUT 3 PERCENT BELOW OPTIMUM WATER CONTENT

WHEN THE SAMPLE IS CONFINED UNDER A 144-PSF SURCHARGE

AND SUBMERGED.

AGGREGATE BASE COURSE SHALL CONFORM TO NMDOT TYPE I

SPECIFICATIONS.

ALL ASPECTS OF THE SUBGRADE PREPARATION, INCLUDING THE

EXCAVATION, COMPACTION, GRAVEL, BASE COURSE, BACKFILL,

AND ANY OTHER PREPARATION FOR PLACING THE CLEARWELL

SHALL BE CONSIDERED INCIDENTAL TO THE CONSTRUCTION OF THE

CLEARWELL.

PROOF-ROLLED NATIVE

COBBLES & GRAVEL

3" TO 4" LEVELING

COURSE

2'-6"

MIN

FREE-DRAINING

GRANULAR

MATERIAL

12" COMPACTED BACKFILL

IMPERVIOUS SOIL OR PAVING

2'-0"

CLEARWELL

1'-0"

GEOTEXTILE

FILTER FABRIC

WEEP HOLES

FREE-DRAINING

GRANULAR

MATERIAL

BACKFILL

2'-0"

GEOTEXTILE

FILTER FABRIC

PROOF-ROLLED NATIVE

COBBLES & GRAVEL

3" TO 4" LEVELING

COURSE

OPTION 1 - NATIVE COBBLES & GRAVEL ENCOUNTERED

SCALE: N.T.S.

RETAINING WALL

1'-0" MIN.

AGGREGATE BASE

COURSE

2'-6"

MIN

IMPERVIOUS SOIL OR PAVING

2'-0"

CLEARWELL

1'-0" MINALL EXISTING FILL TO BE

REMOVED AND REPLACED

GEOTEXTILE

FILTER FABRIC

WEEP HOLES

BACKFILL

2'-0" MIN.

GEOTEXTILE

FILTER FABRIC

2'-0" MIN.

COMPACTED

ENGINEERED FILL

OPTION 2- ENGINEERED FILL

SCALE: N.T.S.

RETAINING WALL

SCARIFY MINIMUM 8",

MOISTURE

CONDITIONED AND

COMPACTED NATIVE

SUBGRADE.

1'-0" MIN

IMPERVIOUS SOIL OR PAVINGIMPERVIOUS SOIL OR PAVING

SPECIAL INSPECTION:

CERTIFIED INSPECTION (APPROVED BY THE BUILDING OFFICIAL OR THE

ENGINEER OF RECORD) SHALL BE PROVIDED FOR BY THE OWNER IN

ACCORDANCE WITH CHAPTER 17 OF THE INTERNATIONAL BUILDING

CODE.

FIELD OBSERVATION AND TESTING

THE OWNER SHALL EMPLOY A REGISTERED GEOTECHNICAL ENGINEER TO

OBSERVE ALL CONTROLLED EARTHWORK. THE CONTRACTOR SHALL

PROVIDE 24 HOUR NOTICE PRIOR TO CONTROLLED EARTHWORK

OPERATIONS.

TESTS OF MATERIALS SHALL BE MADE AT THE MINIMUM RATES OUTLINED

IN THE PROJECT SPECIFICATIONS.

RESULTS OF ALL TESTS SHALL BE SUBMITTED TO THE OWNER WITHIN

SEVEN DAYS EXCEPT WITHIN 1 DAY FOR THE BAFFLE WALL CONCRETE.

CAST-IN-PLACE CONCRETE

CONCRETE SHALL MEET AT A MINIMUM THE REQUIREMENTS OF THE

FOLLOWING REFERENCES. THE MOST CURRENT VOLUME OF THE REFERENCE

SHALL BE APPLICABLE.

ACI 301 - STRUCTURAL CONCRETE FOR BUILDINGS

ACI 302 - GUIDE FOR CONCRETE FLOOR AND SLAB CONSTRUCTION

ACI 305 - SPECIFICATION FOR HOT WEATHERING CONCRETING

ACI 306 - SPECIFICATION FOR COLD WEATHER CONCRETING

ASTM C 260 - AIR ENTRAINING ADMIXTURES FOR CONCRETE

ASTM C 494 - CHEMICAL ADMIXTURES FOR CONCRETE

ACI 347 - REMOVAL OF FORMS

ALL CONCRETE SHALL HAVE THE MINIMUM SPECIFIED STRENGTH OF 4000 PSI.

AIR ENTRAINMENT SHALL BE USED IN ALL CONCRETE EXCEPT FOR THOSE TO

RECEIVE A STEEL TROWEL FINISH. THE AIR CONTENT FOR EXTERIOR CONCRETE

SHALL BE 6 PERCENT PLUS OR MINUS 1.5 PERCENT.

THE CONCRETE USED FOR THE CLEARWELL AND BAFFLES SHALL INCLUDE

XYPEX ADMIX C-SERIES OR EQUAL IN ACCORDANCE WITH THE

MANUFACTURER'S RECOMMENDATION FOR THE CLEARWELL STRUCTURE.

CONSTRUCTION AND COLD JOINTS AT CLEARWELL: IN ADDITION TO SPECIFIED

WATERSTOPS APPLY ONE COAT OF XYPEX CONCENTRATE SLURRY PER

MANUFACTURER'S RECOMMENDATION TO JOINT SURFACES BETWEEN

CONCRETE PLACEMENTS. MOISTEN THE SURFACES PRIOR TO THE SLURRY

APPLICATION. APPLY THE SLURRY AND KEEP IT MOIST FOR 12 HOURS THEN

ALLOW THE SLURRY TO SET OR DRY. USE XYPEX SEALING STRIPS PER

MANUFACTURER'S RECOMMENDATION AT THE JOINTS.

CONTRACTOR SHALL NOT CAST CONCRETE FOR FOUNDATIONS OR VERTICAL

WALLS DIRECTLY AGAINST EXCAVATED SURFACES.

CHAMFER ALL EXPOSED EDGES OF CONCRETE 3/4” UNLESS SPECIFIED

OTHERWISE.

SEE DRAWINGS OF OTHER TRADES FOR LOCATIONS OF PIPE, ANCHOR BOLTS

AND OTHER FEATURES

CONCRETE MATERIALS SHALL MEET THE FOLLOWING REQUIREMENTS:

1) PORTLAND CEMENT - ASTM C150, TYPE II, LOW ALKALI

2) AGGREGATES - ASTM C33 AND/OR 330.

3) WATER - POTABLE

4) AIR ENTRAINMENT - ASTM C260

5) WATER REDUCING ADMIXTURE - ASTM C494

6) FLY ASH - ASTM C618 CLASS F

ALL ADMIXTURES EXCEPT THE HIGH RANGE WATER REDUCERS SHALL BE

ADDED AT THE BATCH PLANT.

CONCRETE MIX DESIGNS SHALL BE SUBMITTED FOR EACH SPECIFIC MIX DESIGN

TO BE USED IN ACCORDANCE WITH ACI 301. EACH MIX DESIGN SUBMITTED

SHALL HAVE ITS INTENDED USE (FOOTINGS, SLABS, EXTERIOR FLATWORK ETC.)

CLEARLY IDENTIFIED. SUBMIT COPIES OF THE TEST REPORTS FOR CONCRETE

COMPRESSIVE STRENGTH, TEMPERATURE, SLUMP, AND AIR CONTENT.

SUBMIT RESULTS OF LABORATORY TESTING OF THE AGGREGATES SHOWING

COMPLIANCE WITH ATSM C 33 OR C 330.

SUBMIT PRODUCT DATA FOR ADMIXTURES, PROPRIETARY MATERIALS, OR

CURING COMPOUNDS.

CONCRETE SHALL BE PLACED AGAINST FORMWORK. ALL FORMWORK SHALL

BE STRAIGHT AND SECURELY FASTENED.

CONCRETE SHALL BE VIBRATED BY MECHANICAL MEANS IN ACCORDANCE

WITH ACI RECOMMENDED PRACTICES. HAND SPADING, TAMPING, OR

RODDING SHALL BE USED TO SUPPLEMENT MECHANICAL VIBRATION.

CONCRETE SHALL NOT BE OVER VIBRATED TO A POINT OF CAUSING

SEGREGATION OF THE CONCRETE.

ALL FINISHED SLAB SURFACES SHALL BE TROWELED, WALKABLE SURFACES

SHALL HAVE A BROOM FINISH.

NEWLY PLACED CONCRETE SHALL BE IMMEDIATELY PROTECTED FROM

ELEMENTS THAT COULD CAUSE PREMATURE DRYING OR EXCESSIVE COLD

TEMPERATURES.

IMPERFECTIONS SUCH AS HONEYCOMBING, AIR VOIDS, HOLES LEFT BY

TIE-RODS, OR DEBRIS SHALL BE PATCHED WITH CEMENT MORTAR. AREAS OF

EXCESSIVE HONEYCOMBING SHALL BE BROUGHT TO THE ATTENTION OF THE

STRUCTURAL ENGINEER.

FIELD INSPECTION AND TESTING SHALL BE PERFORMED IN ACCORDANCE WITH

ACI 301. THE OWNER SHALL EMPLOY THE SERVICES OF GEOMAT OR A

QUALIFIED TESTING LABORATORY TO PERFORM TESTS AND SUBMIT TEST

REPORTS.

THE CONTRACTOR SHALL PROVIDE FREE ACCESS TO WORK FOR THE

DESIGNATED TESTING FIRM. FRESH CONCRETE SHALL BE SAMPLED IN

ACCORDANCE WITH ASTM C 172. THE SLUMP AND AIR CONTENT OF THE

CONCRETE SHALL BE TAKEN FOR EACH SET OF COMPRESSIVE STRENGTH

SPECIMENS TAKEN IN ACCORDANCE WITH ASTM C 143 AND ASTM C 173 OR C

231, RESPECTIVELY.

CONCRETE TEST CYLINDERS SHALL BE CAST IN ACCORDANCE WITH ASTM C 31.

FIVE STANDARD CYLINDERS SHALL BE CAST FOR EACH COMPRESSIVE

STRENGTH TEST, UNLESS OTHERWISE DIRECTED. MOLD AND STORE

CYLINDERS FOR LABORATORY CURED TEST SPECIMENS EXCEPT WHEN FIELD

CURE TEST SPECIMENS ARE REQUIRED. CYLINDERS SHALL BE CAST FOR EVERY

50 CUBIC YARDS OF EACH TYPE OF CONCRETE PLACED. A MINIMUM OF ONE

SET OF FIVE CYLINDERS SHALL BE CAST FOR EACH DAY THAT CONCRETE IS

PLACED.

COMPRESSIVE STRENGTH TESTS SHALL BE PERFORMED IN ACCORDANCE WITH

ASTM C 39.

THE CONTRACTOR MAY REQUEST ADDITIONAL SPECIMENS TO BE CAST AT NO

ADDITIONAL COST TO THE OWNER UNLESS OTHERWISE AGREED UPON

BETWEEN THE OWNER AND CONTRACTOR.

IN THE CASE OF CONCRETE NOT CONFORMING TO PROJECT REQUIREMENTS,

ADDITIONAL TESTING OR REPAIR/REPLACEMENT MAY BE REQUIRED AS

DIRECTED BY THE STRUCTURAL ENGINEER AT NO ADDITIONAL COST TO THE

OWNER.

THE CONCRETE USED FOR THE BAFFLE WALL EXTENSION SHALL HAVE A HIGH

EARLY STRENGTH ADMIXTURE SUCH THAT THE DESIGN STRENGTH IS

ACHIEVED IN 24 HOURS. 3 TEST CYLINDERS SHALL BE TESTED AT 24 HOURS

AND TWO HELD IN RESERVE FOR FUTURE TESTING.

ALL FORMING, REINFORCING, WATER-STOPS, STRIPPING, FINISHING,

ADMIXTURES, ETC SHALL E CONSIDERED INCIDENTAL TO THE CONSTRUCTION

OF THE CLEARWELL.

REINFORCING STEEL:

ALL REINFORCING STEEL SHALL CONFORM TO ASTM A615 GRADE 60.

CONCRETE COVER SHALL BE AS SHOWN IN THE CONCRETE REINFORCING

COVER TABLE ON THIS SHEET.

TENSION AND COMPRESSION LAPS IN REINFORCING SHALL BE IN

ACCORDANCE WITH ACI 318, CHAPTER 12. THE MINIMUM LAP LENGTH

SHALL BE AS SHOWN IN THE REINFORCING LAP LENGTH TABLE ON THIS

SHEET.

HORIZONTAL REINFORCING SHALL HAVE BENT (CORNER) BARS OF THE

SAME SIZE AND SPACING WITH THE APPROPRIATE LAP LENGTH.

BAR SUPPORTS AND SPACERS SHALL BE SECURELY FASTENED TO

SUPPORTS AND PROVIDED IN ACCORDANCE WITH ACI 315.

CHAIRS WITH 22 GAGE SAND PLATES OR PRECAST BLOCKS SHALL BE

PROVIDED FOR ALL REINFORCING OF CONCRETE IN CONTACT WITH

GRADE.

ACCESS HATCHES:

PROVIDE HALLIDAY W1S3636 ALUMINUM HATCHES (OR APPROVED

EQUAL) IN THE LOCATIONS SHOWN.

HATCHES SHALL INCLUDE SIDE DRAINS THAT DRAIN TO THE SIDE OF THE

HATCH CURB AND ON TOP OF THE CLEARWELL LID.

ALUMINUM SURFACES IN CONTACT WITH CONCRETE SHALL BE COATED

WITH AN APPROVED COATING TO PREVENT CHEMICAL INTERACTIONS

WITH THE CONCRETE.

POST INSTALLED ANCHORS:

ALL POST INSTALLED ANCHORS SHALL BE AS SPECIFIED IN THE DETAILS

OF THESE DRAWINGS. THE CONTRACTOR MAY ONLY SUBSTITUTE

PRODUCTS WITH ENGINEER'S APPROVAL AT NO ADDITIONAL COST TO

THE OWNER.

SUBMIT ALL PROPOSED ANCHORING SYSTEMS, AS WELL AS, THE ICC-ES

REPORTS TO THE ENGINEER FOR REVIEW PRIOR TO INSTALLATION.

FREE-DRAINING

GRANULAR

MATERIAL

FREE-DRAINING

GRANULAR

MATERIAL

12" COMPACTED BACKFILL

REV. No. DATE COMMENT

GEOMAT

1"

SCALE BAR

0 2"

CITY OF AZTEC

WATER TREATMENT PLANT

2025 CLEARWELL EXPANSION

SCALE: AS SHOWN

DRAWN BY: DATE:

GEOMAT PROJECT: 242-4792

APR'D BY: SHT:

PAR SEPT 8, 2025

0 2025-09-08 ISSUED FOR CONSTRUCTION

GENERAL STRUCTURAL

S1

NOTES, TABLES & DETAILS

UNO UNLESS NOTED OTHERWISE

HORIZONTAL HORIZ

W/ W/O

VERT.

WITHOUT

WITH

VERTICAL

TRANSVERSE

TOP OF CONCRETE

TOP OF BEAM

THROUGH

STANDARD

SPECIFICATIONS

REQUIRED

REINFORCING/REINFORCEMENT

POUNDS PER SQUARE FOOT

POUNDS PER LINEAR FOOT

ON CENTER

NOT TO SCALE

MISCELLANEOUS

MINIMUM

MASONRY CONTROL JOINT

MANUFACTURER

LONGITUDINAL

BM

MISC

BEAM

DWLS DOWELS

EMBEDMENT

ELEVATION

FOUNDATION

FOOTING

FEET

FTG

FDN

FT

EA

EMBED

EXTERIOR

EQUAL

EACH

EXT

EQ

EL

T&B

TYP

TOB

TOC

TRANS.

TYPICAL

TOP & BOTTOM

SIM

THRU

SPECS

STD

SIMILAR

DIMENSION

DIAMETER

CONTROL / CONSTRUCTION JOINT

CONTINUOUS

CONCRETE MASONRY UNIT

CONCRETE

CAST-IN-PLACE

CONC

DIM

DIA

CMU

CONT

CJ

BOTT

CLEAR

BOTTOM

CIP

CLR

LBS

SECT

PLF

PSF

REINF

REQD

SHT SHEET

SECTION

POUNDS

PL

NTS

OC

PLATE

AMERICAN WELDING SOCIETY

AMERICAN SOCIETY TESTING MATERIALS

APPROXIMATE

AMERICAN INSTITUTE OF STEEL CONSTRUCTION

ALTERNATE

AMERICAN CONCRETE INSTITUTION

APPROX

ASTM

AWS

AISC

ALT

ACI

LONG.

MFR

MCJ

MIN

ABBREVIATIONS

TOF TOP OF FOOTING

B/F BOTTOM OF FOOTING

E.W. EACH WAY

F.F. FINISHED FLOOR

E.F. EACH FACE

TO TOP OF

TOS TOP OF STEEL

LEGEND

INDICATES A KEYED NOTE. SEE THE KEYED

NOTE SCHEDULE.

INDICATES A CUT SECTION LOCATION,

NUMBER AND SHEET

INDICATES A CONCRETE WALL SLAB OR

OTHER FEATURE.

GRID LINEGL

INDICATES A CONTROL JOINT IN THE

SLAB-ON-GRADE. SEE DETAIL 11/S401.

CJ

CONTINUOUS FOOTINGCF

XX

X

CENTERLINECL

HEADED ANCHOR STUDHAS

PROJ PROJECTION

X

OVERVIEW OF IMPROVEMENTS

SCALE: 3/16" = 1'-0"

PL

AN

N O

RT

H

24" NPW

"W

"N

PW

4" PVC

6" P

VC

24" NPW

TR

UE

N

OR

TH

WATER TREATMENT PLANT

FIRST CLEARWELL

ADDTION

SECOND CLEARWELL

ADDITION

PROPOSED

CLEARWELL

ADDITION

PI

PE

G

AL

LE

RY

OVERVIEW - KEYED NOTES

GENERAL: THESE KEYED NOTES APPLY ONLY TO THE STRUCTURAL

SCOPE. SEE CIVIL DESIGN PLANS FOR LAY-OUT, PIPING, GRADING,

AND OTHER DESIGN ELEMENTS.

1. PROPOSED CLEARWELL ADDITION: CONSTRUCT AN ADDITION TO

THE EXISTING CLEARWELL AS SHOWN. SEE PLAN ON SHEET S3.

2. BAFFLE WALL EXTENSION: CONSTRUCT AN EXTENSION TO AN

EXISTING BAFFLE WALL IN THE SECOND CLEARWELL ADDITION AS

SHOWN. SEE DETAILS ON SHEET S4

3. WALL OPENINGS: CUT TWO OPENINGS THROUGH THE WALL OF

THE EXISTING SECOND CLEARWELL ADDITION TO ALLOW WATER

FLOW TO AND FROM THE PROPOSED CLEARWELL ADDITION. SEE

DETAILS ON SHEET S4

4. PROPOSED RETAINING WALL: REMOVE THE EXISTING RAILROAD

TIE RETAINING WALL AND CONSTRUCT A CONCRETE RETAINING

WALL WITH RAILING AS SHOWN. SEE DETAILS ON THIS SHEET.

REPLACE EXISTING R.R. TIE RETAINING WALL

4" P

VC

6" P

VC

5710.005705.05

5710.00

5704.71

5705.00

5704.05

"TOE" "W" "HEEL"

"T"

3" CLR

2" CLR

#4 @ 12"

O.C. TYP

"TOP BAR"

DOWELS TO MATCH VERT.

BAR SIZE & SPACING.

VERT. LAP TO BE 57d.

"H"

30" MIN.

#4 @ 12" O.C.

TYP HORIZ.

3/4" CHAMFER TYP AT

ALL EXPOSED EDGES

2-FEET WIDE CRUSHED

STONE OR GRANULAR SOIL

1"Ø WEEP HOLES @ 6'-0" O.C.

"FACE BAR" VERT.

"BACK BAR" VERT.

"H"

0' TO 3'-11"

4' TO 7'

"W" "T" "TOE" "HEEL" "BOTTOM BAR" "TOP BAR" "FACE BAR" "BACK BAR"

RETAINING WALL SCHEDULE

SCALE: N.T.S.

10" 14" 1'-6" 1'-5" #5@10" O.C. #5@10" O.C.

10" 14" 3'-8" 1'-8" #5@8" O.C. #5@8" O.C. #5@8" O.C. #5@8" O.C.

GEOTEXTILE FILTER FABRIC

IMPERVIOUS SOIL

BACKFILL OR

CONCRETE PAVING

#5@10" O.C. #5@10" O.C.

1/4 TYP

5"

5"

1" TYP

RAILING DETAIL

SCALE: N.T.S.

8'-0" MAX

1/4

1 1/2"Ø STD.

PIPE IN CTR

PL 1/4x5 x 0'-5" LONG W/ (2)

HOLES FOR 5/8"Ø BOLTS

1'-9"

3'-6"

PL 1 4"x 1 7/8"Ø

RAIL: 1 1/4" Ø STD PIPE TYP.

POST: 1 1/2"Ø

STD. PIPE TYP.

RAIL: 1 1/4" Ø STD PIPE TYP.

BASE PLATE: PL 1/4x5 x 0'-5"

W/ (2) HOLES FOR 5/8"Ø

EXPANSION ANCHORS

5/8"Ø EXPANSION ANCHORS.

TWO AT EA. POST.

6" MIN EMBED

BASE PLATE DETAIL

RAILING

VALLEY GUTTER - SEE CIVIL

RAILING NOTE:

· INSTALL RAILING IN LOCATIONS WHERE "H" IS

4-FEET OR MORE.

· THE RAILING SHALL BE COATED SAFETY YELLOW

WITH A TWO-PART EPOXY COATING. ANY

DAMAGED AREA SHALL BE TOUCHED UP IN THE

FIELD.

"BOTTOM BAR"

REV. No. DATE COMMENT

GEOMAT

1"

SCALE BAR

0 2"

CITY OF AZTEC

WATER TREATMENT PLANT

2025 CLEARWELL EXPANSION

SCALE: AS SHOWN

DRAWN BY: DATE:

GEOMAT PROJECT: 242-4792

APR'D BY: SHT:

PAR SEPT 8, 2025

0 2025-09-08 ISSUED FOR CONSTRUCTION

OVERVIEW OF IMPROVEMENTS

S2

& RETAINING WALL DETAIL

TYP

S4

E

F

G

25'-2"

4'-10"

5'-11"

4'-1 3/16"

4'-1 3/16"

4'-8 3/16"

18'-9 1/2"

30'-0"

48'-9 1/2"

27'-0"

20'-7 1/2"

6'-4 1/2"

4'-0"

4'-0"

4'-0"

4'-3 3/8" 8" 4'-2 3/8" 8" 4'-2 3/8" 8" 4'-3 3/8" 10"10"

4'-0"

2 3 4

4'-10 3/8" 4'-10 3/8" 5'-5 3/8"5'-5 3/8"

20'-7 1/2"

B

C

D

18'-9 1/2"

CLEARWELL EXPANSION PLAN

SCALE: 1/4" = 1'-0"

PL

AN

N O

RT

H

TYP

S4

TYP

S4

S4

" N

PW

6" P

VC

TR

UE

N

OR

TH

S4

S4

S4

BA

FF

LE

W

AL

L

(T

YP

BAFFLE WALL (TYP.)

36"x36"

HATCH

36"x36"

HATCH

EXISTING CLEARWELL

FIRST ADDITION

EXISTING CLEARWELL

SECOND ADDITION

PROPOSED CLEARWELL

THIRD ADDITION

BAFFLE WALL EXTENSION

SEE DETAIL 5/S4

36"x36"

HATCH

REV. No. DATE COMMENT

GEOMAT

1"

SCALE BAR

0 2"

CITY OF AZTEC

WATER TREATMENT PLANT

2025 CLEARWELL EXPANSION

SCALE: AS SHOWN

DRAWN BY: DATE:

GEOMAT PROJECT: 242-4792

APR'D BY: SHT:

PAR SEPT 8, 2025

0 2025-09-08 ISSUED FOR CONSTRUCTION

CLEARWELL EXPANSION PLAN

S3

GENERAL NOTES:

SEE CIVIL DRAWINGS FOR THE SUGGESTED SEQUENCE

OF CONSTRUCTION ACTIVITIES

9"

HATCH 36" x 36"

W/ SIDE DRAIN

(HALLIDAY W1S3636

OR EQUAL) 9"

4'-6"

(1) #4 CONTINUOUS

AROUND PERIMETER IN

CENTER SUPPORTED ON

1/2"Ø DRILL & EPOXY BOLTS

@ 24" O.C. W/ 4" EMBED

SIDE-DRAIN

PROVIDE ADDITIONAL REINFORCING AROUND

LID PENETRATIONS IN ACCORDANCE WITH 7/S4

5"

8"

ACCESS

HATCH CURB

10"

3" CLR

2" CLR

9'-7"

8"

1 1/2" CLR

1 1/2" CLR

CLEARWELL LID - 8" THICK

W/ #5 BARS @ 8" EA.WAY,

TOP & BOTT. 1 1/2" CLR.

CLEARWELL FLOOR - 10" THICK W/

#4 BARS @ 8" EA.WAY, TOP & BOTT.

3" CLR.@BOTT, 2" CLR.@TOP

3 1/2" x 1 1/2"

KEYED JOINT W/

9" RCB TVR

WATER STOP

3 1/2" x 1 1/2" KEYED JOINT

CLEARWELL WALL - 10" THICK

W/ #4 BARS @ 8" EA.WAY,

EA.FACE. 2" CLR. TYP

ACCESS HATCH CURB

SCALE: 3/4" = 1'-0"6

TYP. FLOOR, WALL, ROOF SECTION

NTS1

10"

9'-7"

8"

CLEARWELL LID

SEE 1/S4

3 1/2" x 1 1/2" KEYED JOINT

W/ 9" RCB TVR WATER STOP

INTERIOR WALL - 8" THICK W/

#5 BARS @ 8" EA.WAY IN CENTER

TYP. BAFFLE WALL SECTION

NTS2

3 1/2" x 1 1/2" KEYED JOINT

DOWELS MATCHING SIZE & SPACING

OF VERT. REBAR 30" LAP

DOWELS MATCHING SIZE & SPACING

OF VERT. REBAR 30" LAP

DOWELS MATCHING SIZE & SPACING

OF VERT. REBAR 30" LAP.

ALTERNATE DIRECTION

DOWELS MATCHING SIZE & SPACING

OF VERT. REBAR 30" LAP.

ALTERNATE DIRECTION

3 1/2" x 1 1/2" KEYED JOINT

W/ 9" RCB TVR WATER STOP

WALL SECTION AT ADJOINING BUILDING

NTS3

10"

9'-7"

8"

CLEARWELL LID

SEE 1/S4

3 1/2" x 1 1/2" KEYED JOINT

W/ 9" RCB TVR WATER STOP

1 1/2" HIGH x 1" WIDE XYPEX DRY PAC IN

ACCORDANCE WITH MANUFACTURER'S

RECOMMENDATIONS.

3 1/2" x 1 1/2" KEYED JOINT

WALL SECTION AT NEW / EXISTING CLEARWELL

NTS4

10"

8"

CLEARWELL FLOOR; SEE 1/S4

ACCESS HATCH;

SEE 6/S4

TOP OF LID = 5705.14 *

INV.= 5694.89 *

EXISTING

CLEARWELL

SECOND

ADDITION

EXISTING

WATER

TREATMENT

PLANT

CLEARWELL WALL

SEE 1/S4

3 1/2" x 1 1/2" KEYED JOINT

CLEARWELL WALL

SEE 1/S4

RECTANGULAR

OPENING

REINFORCING AROUND PENETRATIONS

SCALE: N.T.S.7

PENETRATIONS NOTES:

· AT ALL PENETRATIONS: ADD (4) #4 x 36" LONG DIAGONAL BARS NEXT TO EACH

REINFORCING MAT. 1 1/2" CLEAR FROM OPENING.

· AT PENETRATIONS LESS THAT 12" IN THE GREATEST DIMENSION: DEFLECT THE TYPICAL

REINFORCING AROUND THE PENETRATION. MAINTAIN 1 1/2" CLEAR.

· AT PENETRATIONS 12" TO 30" IN THE GREATEST DIMENSION: DISCONTINUE TYP.

REINFORCING AT THE OPENING AND ADD (1) #5 BARS FOR EACH REINFORCING MAT ON

EACH SIDE OF THE PENETRATION. BAR LENGTH TO BE x (OPENING + 36"). MAINTAIN 1

1/2" CLEAR.

· AT PENETRATIONS 30" TO 48" IN THE GREATEST DIMENSION: DISCONTINUE TYP.

REINFORCING AT OPENING. ADD (2) #5 BARS FR EACH REINFORCING MAT ON EACH SIDE

OF THE PENETRATION. BAR LENGTH TO BE x (OPENING + 36"). MAINTAIN 1 1/2" CLEAR &

3" BETWEEN.

ROUND

OPENING

CLEARWELL LID

SEE X/SXX

EXISTING LID

EXISTING FLOOR

EXISTING

WALL

EXISTING BAFFLE WALL

CONSTRUCT BAFFLE

WALL EXTENSION

APPROX 3'-0" FIELD VERIFY

3/4" x 1" BENTONITE

WATERSTOP EA.FACE

BAFFLE WALL EXTENSION DETAIL

SCALE: 3/4" = 1'-0"5

#5 DOWEL W/ MINIMUM 24"

LAP. DRILL & EPOXY DOWELS,

SEE ELEVATION

EXISTING LID

EXISTING FLOOR

ELEVATION SECTION

EXISTING CMU

BAFFLE WALL BAFFLE WALL EXTENSION:

8" THICK W/ #5 BARS @

8" EA.WAY IN CENTER

DIAGONAL

BARS DIAGONAL

BARSADDED

BARS

ADDED

BARS

NOTE: TYP. REINFORCING IS

NOT SHOWN IN THIS DETAIL

VOID FORM

8"10"

EXISTING CONCRETE WALL

NOTE: PREVIOUS POTHOLING

INDICATES FOUNDATIONS EXTEND

TO BOTTOM OF EXSITING

CLEARWELL. IF CONDITIONS

DIFFERENT, DISCONTINUE

EXCAVATING AND CONTACT

ENGINEER OF RECORD. UNDER

PINNING WILL BE REQUIRED

9'-7"

1'-6"

5-#5 VERTS , SPACED

EVENLY; #5 HORIZ

@ 8" O.C.

#5 REBAR W/ HILTI

HIT-HY 200 A V3

ADHESIVE ANCHOR

6-3/4" MIN. EMBED

TYP. BOTTOM & SIDES

CONNECTION PIPE DETAIL KEYED NOTES:

THESE KEYED NOTES IN CONJUNCTION WITH DETAIL 8/S4 SUGGEST ONE

POSSIBLE WAY TO CONSTRUCT THE CONNECTION BETWEEN THE OLD AND

NEW CLEARWELLS. THE CONTRACTOR MAY ELECT TO USE A DIFFERENT

MEANS AND METHODS, BUT THE CONTRACTOR'S MEANS AND METHODS

MUST BE SUBMITTED IN DETAIL AND APPROVED BEFORE CONSTRUCTION

BEGINS.

1. REMOVE SOIL, LOOSE CONCRETE OR OTHER DEBRIS, FROM THE OUTSIDE OF

THE EXISTING CLEARWELL WALL. COAT WALL USED TO FORM NEW

CLEARWELL WALL WITH XYPEX SLURRY CONCENTRATE.

2. CONSTRUCT THE NEW CLEARWELL WALL.

2.1. INCLUDE XYPEX C500 SERIES IN THE MIX DESIGN IN ACCORDANCE WITH

THE MANUFACTURER'S RECOMMENDATIONS.

2.2. CAST A 3-FOOT HIGH x 3-FOOT WIDE OPENING CENTERED ON THE

LOCATION FOR THE PIPE.

2.3. CAST A 1" WIDE x 1 1/2" DEEP NOTCH AROUND THE PERIMETER OF THE 3x3 OPENING AS SHOWN.

2.4. PROVIDE ADDITIONAL REINFORCING AROUND THE OPENING SIMILAR TO

DETAIL 7/S4.

3. CUT THE HOLE IN THE OLD CLEARWELL WALL

3.1. CORE DRILL PILOT HOLES IN THE CORNERS OF PROPOSED OPENING.

3.2. SAWCUT THE OLD WALL TO OUTSIDE TANGENT OF CORE DRILLED HOLES

RESULTING IN A 3-FOOT HIGH x 3-FOOT WIDE OPENING IN THE OLD

CLEARWELL WALL.

3.3. REMOVE SAWCUT PORTION OF WALL, CLEAN DEBRIS

3.4. CUT A 1" WIDE x 1 1/2" DEEP NOTCH AROUND THE PERIMETER OF THE

OPENING.

3.5. ROUGHEN OPENING AND COAT W/ XYPEX SLURRY CONCENTRATE.

4. INSTALL 32" DIAMETER STUB PIPE THROUGH THE OPENING.

4.1. THOROUGHLY CLEAN & ROUGHEN THE OUTSIDE SURFACE OF PIPE AND

APPLY XYPEX CONCENTRATE SLURRY.

4.2. PLACE TWO CONSEAL CR-231 (OR EQUAL) WATERSTOPS AROUND THE

PIPE.

4.3. INSERT PIPE & WATERSTOPS THROUGH THE OPENING AND SUPPORT IN

PLACE WITH TEMPORARY SHORING.

5. SEAL THE OPENING

5.1. INSTALL XYPEX CONCENTRATE PATCH & PLUG AROUND THE PIPE IN

ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS. (2" TO 3"

LIFTS FULL DEPTH)

INV.= 5694.89 *INV.= 5694.89 * INV.= 5694.89 * INV.= 5694.89 *

* ELEVATIONS NOTES:

· THE TOP OF LID AND INVERT ELEVATIONS

SHOWN ARE BASED ON SURVEY INFORMATION

AVAILABLE AT THE TIME OF DESIGN.

· THE INTENT OF THE DESIGN IS TO MATCH THE

EXISTING TOP OF LID AND INVERT ELEVATIONS

WITH THE NEW CONSTRUCTION.

· IF THE ACTUAL ELEVATIONS DIFFER FROM

THOSE SHOWN, HOLD THE ACTUAL

ELEVATIONS.

· IF THE DIFFERENCE IS MORE THAN 2 INCHES,

NOTIFY THE DESIGN TEAM BEFORE

PROCEEDING.

* SEE ELEVATIONS NOTES ON THIS SHEET* SEE ELEVATIONS NOTES ON THIS SHEET* SEE ELEVATIONS NOTES ON THIS SHEET* SEE ELEVATIONS NOTES ON THIS SHEET

X

2.2

2.3

3.1 3.2 3.4

5.1

TYP

4.1

4.2

2.2

2.3

5.1

4.2

3.5

5.1

3.2

CONNECTION PIPE DETAIL

SCALE: N.T.S.8

ELEVATION

SECTION

CONNECTION PIPE

SEE DETAIL 8/S4

TOP OF LID = 5705.14 *TOP OF LID = 5705.14 *TOP OF LID = 5705.14 *

10"

2'-8"Ø

2"

2"

3'-0"

SQ.

2"

2'-8"Ø 3'-0"

SQ.

2"

ADDITIONAL REINFORCING

AROUND OPENING.

SEE DETAIL 7/S4

1'-3"

2"

2'-8"Ø

2"

3'-0"

SQ.

2"

2'-8"Ø 3'-0"

SQ.

1'-3"

3.3

1 1/2"

1"

4.2

3.4

3.5

2.1

4.3

CLEARWELL FLOOR; SEE 1/S4CLEARWELL FLOOR; SEE 1/S4

1 1/2" HIGH x 1" WIDE XYPEX DRY PAC IN

ACCORDANCE WITH MANUFACTURER'S

RECOMMENDATIONS.

1 1/2" HIGH x 1" WIDE XYPEX DRY PAC IN

ACCORDANCE WITH MANUFACTURER'S

RECOMMENDATIONS.

1 1/2" HIGH x 1" WIDE XYPEX DRY PAC IN

ACCORDANCE WITH MANUFACTURER'S

RECOMMENDATIONS.

8" 10"

CONNECTION PIPE NOTE:

THE CITY WILL REDUCE THE WATER LEVEL IN THE EXISTING

CLEARWELL TO FACILITATE THE MAKING OF THE CONNECTION

BETWEEN THE NEW AND THE OLD CLEARWELLS.

THE REDUCED WATER LEVEL CAN ONLY BE MAINTAINED FOR

48 HURS MAX.

THE CONTRACTOR SHALL PLAN TO WORK CONTINUOUSLY, 24

HOURS PER DAY, UNTIL THE CONNECTION IS COMPLETE AND

THE WATER LEVEL CAN BE RESTORED.

SEE THE CIVIL PLANS AND PROJECT SPECIFICATIONS FOR

MORE INFORMATION.

REV. No. DATE COMMENT

GEOMAT

1"

SCALE BAR

0 2"

CITY OF AZTEC

WATER TREATMENT PLANT

2025 CLEARWELL EXPANSION

SCALE: AS SHOWN

DRAWN BY: DATE:

GEOMAT PROJECT: 242-4792

APR'D BY: SHT:

PAR SEPT 8, 2025

0 2025-09-08 ISSUED FOR CONSTRUCTION

REINFORCING DETAILS

S4

000 Cover Sheet
C-100 Layout Plan
C-200 Grading Plan North
C-201 Grading Plan South
C-300 Backwash Pipe Plan and Profile
C-301 Retaining Wall Profile
C-400 Details
2025-09-08 CoA CLEARWELL-1-COVER
Sheets and Views
1-COVER
2025-09-08 CoA CLEARWELL-2-SITE
Sheets and Views
2-SITE
2025-09-08 CoA CLEARWELL-3-CLEARWELL
Sheets and Views
3-CLEARWELL
2025-09-08 CoA CLEARWELL-4-CLEARWELL DETAILS
Sheets and Views
4-CLEARWELL DETAILS

File details come from the government source that posted it. Updated .