APPENDIX B CONSTRUCTION PLANS.pdf
PDF 8 MB Posted
- Solicitation number
- 2026-879
- Issued by
- San Juan County, New Mexico
About this file
These are engineering and design documents for the Aztec Water Treatment Plant Clearwell Expansion Project located in Aztec, New Mexico, within San Juan County. The project involves expanding the existing water treatment facility clearwell (water storage reservoir) by constructing three additional clearwell sections, installing new piping, removing and replacing an existing railroad tie retaining wall with a concrete retaining wall, and making connections between the new and existing clearwell structures. The project is documented in a comprehensive set of civil and structural engineering drawings prepared by GEOMAT and dated September 8, 2025, with a project number of 242-4792. The design includes detailed plans for grading, backwash piping, retaining wall profiles, reinforcing details, and specific construction sequencing.
The project documents indicate a structured approach to expansion, with specific technical requirements for concrete mixing, reinforcement, water stops, and connection methods between new and existing structures. The design incorporates specialized materials like Xypex concrete additives and waterproofing treatments, and includes precise specifications for reinforcing steel, concrete cover, and lap lengths. While no specific budget is mentioned in the documents, the comprehensive nature of the design suggests a significant municipal infrastructure investment aimed at improving water treatment capacity and facility infrastructure. The project appears to be funded through municipal engineering and infrastructure development channels, with careful attention to technical specifications and construction methodologies.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Navajo Dam
Road 2978
Az te c Bl vd
Navajo Dam Road
Ro ad
NM 173
US
Proj:
Project Date:
HC Eng ineer s , LLC
50 Valley Court Durango, CO 970-387-8765
C
AZ
TE
C
CL
EA
RW
EL
L
EX
PA
N
SI
O N
24009
Ci ty o f
Az te c
2025-07-29
CO
VE
R
SH
EE
T
Aztec Clearwell Expansion City of Aztec, New Mexico
San Juan County
Project Location
Project Location
Vicinity Map Scale: 1"= 2000'
N or th
3.3 miles from Us 550
Sheet List Table Sheet Number Sheet Title
000 Cover Sheet C-100 Layout Plan C-200 Grading Plan North C-201 Grading Plan South C-300 Backwash Pipe Plan and
Profile C-301 Retaining Wall Profile C-400 Details
S1 Notes S2 Overview and Retaining Wall S3 Clearwell Expansion Plan S4 Reinforcing Details
APPENDIX B
ITB 2026-879
AZTEC WATER TREATMENT FACILITY CLEARWELL EXPANSION
12" Steel Pipe Area Drain
15" AC Pipe Unknown
Existing 4" PVC #2 Waste Line
Exisitng 18" Filtered Water Feed To Clearwell
4" PVC Pipe
Backwash Pond
HWL 5700.1
Existing Raw Water for #1 (abandoned)
Inv 5701.5
Inv 5705.2
Ex ist in g
Cl ea rw el l
5705.14 Inv:5694.89
Remove existing concrete swale
5' wide Valley Gutter
Remove existing railroad tie retaining wall Replace with Concrete Retaining Wall ref. structural
Corner Transformer Pad Elev:5705.80
Pr op os ed
E xp an sio n
Waterline to be Abandoned
Proj:
Project Date:
HC Eng ineer s , LLC
50 Valley Court Durango, CO 970-387-8765
C
AZ
TE
C
CL
EA
RW
EL
L
EX
PA
N
SI
O N
24009
C-100
Ci ty o f
Az te c
2025-07-29
LA
YO
U T
PL
AN
N O R T H
Suggested Construction Sequence:
1. Rough Site Grading
2. Demo railroad tie retaining wall and concrete swale
3. Excavate for Clearwell
4. Construct Clearwell
5. Disinfect Clearwell
6. Coordinate with WTP to pump down existing clearwell. 3' of water will not be pumped out of clearwell (approximately 30,000 Gallons). This water must be dechlorinated before releasing into waterways.
3. Build new retaining wall
5. Build 24" Backwash Piping.
6. Remove existing piping.
7. Pump out 3' of existing clearwell.
8. Cut holes into existing clearwell.
9. Clean area and Spot Disinfect.
10. Fill and Leak Test.
11. Put clearwell into service.
5. Coordinate with WTP to pump down existing clearwell.
6. Pump out 3' of existing clearwell.
7. Build Baffle Wall in existing clearwell.
8. Clean area and Spot Disinfect.
9. Fill and Leak Test.
10. Put clearwell into service.
11. Finish Grade Site.
12. Build Concrete Valley Gutter.
20.63'
.7
9'
27'
.7
9'
6.38'
Corner Transformer Pad Elev:5705.80
Existing
4 SY 6"-9" River Rock, 18" deep
Flow Line (typ)
Remove Drain and Backfill
Remove Drain and Backfill
Remove Drain and Backfill
Remove Drain and Backfill
New 24" CMP Backwash Line (See Plan and Profile)
Grade Break (typ)
Grade Break (typ)
Grade Break (typ)
22'
9.83'
Completely remove exisitng 24" CMP Backwash Line
Note:
- Recent excavations in the clearwell expansion work area to full depth show no ground water.
- The backwash pond will have water in it during construction. The contractor shall use every caution to not introduce this water into the work area. This would include scheduling the required pipe removals and installations that would breach the water when it will not harm the work area.
Another option could be draining the pond by pumping to remove the danger. No payment will be made for dewatering.
Grade Area to elevations shown. Site Grading Volumes from finshed design surface to existing surface is ~600 CY Export. This does not include the required removal for the clearwell expansion, or imported material like concrete.
Proj:
Project Date:
HC Eng ineer s , LLC
50 Valley Court Durango, CO 970-387-8765
C
AZ
TE
C
CL
EA
RW
EL
L
EX
PA
N
SI
O N
24009
C-200
Ci ty o f
Az te c
2025-07-29
G
RA
DI
N
G P
LA
N
N O
RT
H
N O R T H
20.63'
.7
9'
27'
.7
9'
6.38'
Corner Transformer Pad Elev:5705.80
Existing 30" Culvert Invert: 5700.1
4 SY 6"-9" River Rock, 18" deep
Remove Drain and Backfill
Remove Drain and Backfill
Remove Drain and Backfill
Remove Drain and Backfill
New 24" CMP Backwash Line (See Plan and Profile)
22'
9.83'
Completely remove exisitng 24" CMP Backwash Line
Note:
- Recent excavations in the clearwell expansion work area to full depth show no ground water.
- The backwash pond will have water in it during construction. The contractor shall use every caution to not introduce this water into the work area. This would include scheduling the required pipe removals and installations that would breach the water when it will not harm the work area.
Another option could be draining the pond by pumping to remove the danger. No payment will be made for dewatering.
Grade Area to elevations shown. Site Grading Volumes from finshed design surface to existing surface is ~600 CY Export. This does not include the required removal for the clearwell expansion, or imported material like concrete.
Proj:
Project Date:
HC Eng ineer s , LLC
50 Valley Court Durango, CO 970-387-8765
C
AZ
TE
C
CL
EA
RW
EL
L
EX
PA
N
SI
O N
24009
C-201
Ci ty o f
Az te c
2025-07-29
G
RA
DI
N
G P
LA
N
S O
U
TH
N O R T H
Provide Manufactured 58° Bend
Existing Grade
Proposed Grade
Proj:
Project Date:
HC Eng ineer s , LLC
50 Valley Court Durango, CO 970-387-8765
C
AZ
TE
C
CL
EA
RW
EL
L
EX
PA
N
SI
O N
24009
C-300
Ci ty o f
Az te c
2025-07-29
BA
CK
W
AS
H P
IP
E
PL
AN
A N
D
PR
O
FI
LE
5705.0 5704.05
5710.0 Top Wall at wall corner
5704.71 Bottom Wall / Top Conc V Channel
5710.0 Top Wall
at existing building
5705.18
110.03'
55.12'54.9'
Proj:
Project Date:
HC Eng ineer s , LLC
50 Valley Court Durango, CO 970-387-8765
C
AZ
TE
C
CL
EA
RW
EL
L
EX
PA
N
SI
O N
24009
C-301
Ci ty o f
Az te c
2025-07-29
RE
TA
IN
IN
G W
AL
L
PR
O
FI
LE
Retaining Wall
30" Cover
Bottom of trench should be smooth with no rocks. If bedrock is encountered Place 4" of clean native material in bottom of trench below pipe.
Place clean native material around pipe. No rocks over 1/2" within 6" of pipe.
Carefully backfill and compact with native material at maximum 6" lifts.
Scale: NTS
Trench Detail
6"
5'
1"
#4 Rebar at 24" O.C.
#4 Rebar at 9" O.C.
Centered in slab
TYPICAL MANHOLE TYPE "C"
GENERAL NOTES:
CONSTRUCTION NOTES:
B
12"
MIN.
1 2"
M
IN
-6
' M
AX
3"
6"
1'-103 4"
12"
MIN. O.D. +12" MIN.
6"
2"
P PIPE
I.D.
P
12"
CONSTRUCTION NOTES:
TYPICAL CONCRETE MANHOLE COVER TYPE "C"
7'-4" FOR 6 FT. I.D. M.H.
2"
1'-103
4" DIA.
2"
1'-101 8"
1/2" Expansion Joint - Full Depth of Pour, Seal top 1/2" with polyurethane caulk
Proj:
Project Date:
HC Eng ineer s , LLC
50 Valley Court Durango, CO 970-387-8765
C
AZ
TE
C
CL
EA
RW
EL
L
EX
PA
N
SI
O N
24009
C-400
Ci ty o f
Az te c
2025-07-29
DE
TA
IL
S
GENERAL NOTES:
DRAWINGS SHOULD NOT BE SCALED TO OBTAIN DIMENSIONS.
DRAWINGS LABELED “PRELIMINARY” OR “NOT FOR CONSTRUCTION” ARE
SUBJECT TO CHANGE.
THE CONTRACTOR SHALL BE RESPONSIBLE FOR ADHERING TO ALL
APPLICABLE SAFETY STANDARDS SET FORTH BY THE OWNER AND/OR OHSA.
IT SHALL BE THE CONTRACTORS RESPONSIBILITY TO VERIFY ALL
DIMENSIONS IN THE FIELD PRIOR TO FABRICATION AND TO ADJUST THE
DETAILS ACCORDINGLY.
THE STRUCTURE SHOWN IN THE DRAWINGS HAS BEEN DESIGNED FOR
STABILITY IN ITS FINAL STATE. THE CONTRACTOR SHALL BE RESPONSIBLE
FOR ALL REQUIRED SHORING AND TEMPORARY BRACING FOR STABILITY
DURING CONSTRUCTION.
THE CONTRACTOR SHALL NOT NOTCH OR CUT ANY STRUCTURAL MEMBER
IN THE FIELD WITHOUT PERMISSION FROM THE STRUCTURAL ENGINEER.
CODES AND MANUALS:
IBC-21 INTERNATIONAL BUILDING CODE 2021
ASCE/SEI 7-05 MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER
STRUCTURES
ACI 318 BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE
DESIGN CRITERIA:
LIVE LOAD
FLOOR - 100 PSF
POINT LOAD @ LID = 16,000 POUNDS FOR TIRE LOAD
DEAD LOAD - SELF WEIGHT
SNOW LOAD:
GROUND SNOW LOAD - PF=30 PSF
SNOW EXPOSURE FACTOR - CE=1.0
SNOW LOAD IMPORTANCE FACTOR - IS=1.0
THERMAL FACTOR - CT=1.0
ALLOWABLE BEARING PRESSURE = 2,500 PSF.
FUTURE BUILDING EXPANSION: NONE
REQUIRED REINFORCING LAP LENGTH
TYPE OF USE BAR DIRECTION BAR SIZE MINIMUM LAP
LENGTH
FOOTINGS/STEM
WALLS ALL BARS ALL BARS
18 BAR DIAMETERS
(18" MINIMUM)
RETAINING WALLS
VERTICAL BARS NO. 6 AND SMALLER
NO.7 AND LARGER
57 DIAMETERS
72 DIAMETERS
HORIZONTAL
BARS ALL BARS
30 BAR DIAMETERS
(18" MINIMUM)
SLABS-ON-GRADE ALL BARS ALL BARS
30 BAR DIAMETERS
(18" MINIMUM)
CONCRETE REINFORCING COVER
TYPE OF USE BAR SIZE/ELEMENT COVER
CAST AGAINST AND PERMANENTLY
EXPOSED TO EARTH ALL BARS 3"
CAST AGAINST FORMS BUT EXPOSED
TO EARTH OR WEATHER
GREATER THAN NO. 5 2"
NO. 5 OR SMALLER 1 1/2"
CONCRETE NOT EXPOSED TO EARTH
OR WEATHER
COLUMNS, GIRDERS, AND
BEAMS 1 1/2"
STRUCTURAL SLABS, WALLS,
AND JOISTS 3/4"
SCOPE:
THESE PLANS WERE PREPARED BY GEOMAT INC. OF FARMINGTON, NEW
MEXICO TO SHOW THE STRUCTURAL REQUIREMENTS FOR THE
CONSTRUCTION OF AN ADDITION TO THE CITY OF AZTEC CLEARWELL
LOCATED AT THE THE CITY OF AZTEC WATER TREATMENT PLANT IN AZTEC,
NEW MEXICO. ANY OTHER USE OF THESE PLANS IS PROHIBITED.
GEOMAT'S SCOPE OF SERVICES WAS LIMITED TO THE STRUCTURAL DESIGN
OF THE CLEARWELL ADDITION. ALL OTHER ASPECTS OF THE DESIGN SUCH
AS CONFIGURATION, OPENING LOCATIONS, PIPES, ELEVATIONS, ETC, ARE
ALL BY OTHERS.
THESE PLANS SHALL BE USED IN CONJUNCTION WITH THE CLEARWELL
DESIGN PLANS BY CHC ENGINEERS, LLC OF DURANGO, COLORADO. IF
THERE ARE DISCREPANCIES , THEY SHALL BE BROUGHT TO THE ATTENTION
OF THE DESIGN TEAM FOR RESOLUTION.
FOUNDATION:
A GEOTECHNICAL INVESTIGATION WAS PERFORMED BY GEOMAT
INC. OF FARMINGTON, NEW MEXICO. A REPORT IS AVAILABLE FROM
THE OWNER (GEOMAT PROJECT # 242-4907). THE CONTRACTOR
SHALL REVIEW THAT REPORT AND ABIDE BY THE
RECOMMENDATIONS MADE THEREIN.
SUBGRADE AND STRUCTURAL FILL PREPARATION
CONCRETE REINFORCED SLAB FOUNDATION AND RETAINING WALL
FOOTINGS SHOULD BEAR ON ENGINEERED FILL OR ON COMPACTED
NATIVE COBBLES AND GRAVELS, BUT NOT A COMBINATION OF THE
TWO MATERIALS.
IF THE STRUCTURAL SLAB IS TO BE SUPPORTED ON COMPACTED
NATIVE COBBLES AND GRAVEL, THE SURFACE OF THE NATIVE
GRAVELS AND COBBLES SHOULD BE PROOF COMPACTED UNDER
OBSERVATION BY A REPRESENTATIVE OF GEOMAT. DUE TO THE
ROCKY NATURE OF THE NATIVE GRAVELS AND COBBLES, PLACE A
THREE TO FOUR-INCH LEVELING COURSE OF OPEN-GRADED GRAVEL
OR COMPACTED BASE BETWEEN THE BOTTOM OF THE FOOTINGS
AND THE UNDERLYING COMPACTED COBBLES AND GRAVELS.
IF THE ANTICIPATED COBBLES AND GRAVEL ARE NOT
ENCOUNTERED, REPLACE THE LEVELING COURSE WITH
COMPACTED AGGREGATE BASE COURSE (ABC) FOR A DEPTH BELOW
THE FOOTING OF NOT LESS THAN ONE (1.0) FOOT FOR THE
CLEARWELL & 2'-0" MINIMUM FOR THE RETAINING WALL. THE ABC
SHOULD EXTEND BEYOND THE EDGES OF THE FOOTINGS AS
INDICATED IN THE GEOTECHNICAL REPORT.
IF ANY EXISTING FILL MATERIAL IS ENCOUNTERED DURING
EXCAVATIONS, THE FILL SHOULD BE COMPLETELY REMOVED FROM
BENEATH THE STRUCTURE AND REPLACED WITH ENGINEERED FILL.
STRUCTURAL FILL SHALL BE PLACED IN LIFTS NOT EXCEEDING 8
INCHES IN THICKNESS WHEN COMPACTED. PLACE FILL AT NEAR
OPTIMUM MOISTURE CONTENTS AND COMPACT TO A MINIMUM
OF 95% OF A MODIFIED PROCTOR (ASTM D1557).
IMPORTED OR EXISTING SOILS THAT CONFORM TO THE FOLLOWING
MAY BE USED FOR STRUCTURAL FILL:
GRADATION PERCENT FINER BY WEIGHT (ASTM C136)
3”
NO. 4 SIEVE.......................................................50-100
NO. 200 SIEVE...................................................50 MAX
STRUCTURAL FILL SHALL HAVE A MAXIMUM EXPANSIVE POTENTIAL
OF 1.5% MEASURED ON A SAMPLE COMPACTED TO
APPROXIMATELY 95 PERCENT OF THE ASTM D1557 MAXIMUM DRY
DENSITY AT ABOUT 3 PERCENT BELOW OPTIMUM WATER CONTENT
WHEN THE SAMPLE IS CONFINED UNDER A 144-PSF SURCHARGE
AND SUBMERGED.
AGGREGATE BASE COURSE SHALL CONFORM TO NMDOT TYPE I
SPECIFICATIONS.
ALL ASPECTS OF THE SUBGRADE PREPARATION, INCLUDING THE
EXCAVATION, COMPACTION, GRAVEL, BASE COURSE, BACKFILL,
AND ANY OTHER PREPARATION FOR PLACING THE CLEARWELL
SHALL BE CONSIDERED INCIDENTAL TO THE CONSTRUCTION OF THE
CLEARWELL.
PROOF-ROLLED NATIVE
COBBLES & GRAVEL
3" TO 4" LEVELING
COURSE
2'-6"
MIN
FREE-DRAINING
GRANULAR
MATERIAL
12" COMPACTED BACKFILL
IMPERVIOUS SOIL OR PAVING
2'-0"
CLEARWELL
1'-0"
GEOTEXTILE
FILTER FABRIC
WEEP HOLES
FREE-DRAINING
GRANULAR
MATERIAL
BACKFILL
2'-0"
GEOTEXTILE
FILTER FABRIC
PROOF-ROLLED NATIVE
COBBLES & GRAVEL
3" TO 4" LEVELING
COURSE
OPTION 1 - NATIVE COBBLES & GRAVEL ENCOUNTERED
SCALE: N.T.S.
RETAINING WALL
1'-0" MIN.
AGGREGATE BASE
COURSE
2'-6"
MIN
IMPERVIOUS SOIL OR PAVING
2'-0"
CLEARWELL
1'-0" MINALL EXISTING FILL TO BE
REMOVED AND REPLACED
GEOTEXTILE
FILTER FABRIC
WEEP HOLES
BACKFILL
2'-0" MIN.
GEOTEXTILE
FILTER FABRIC
2'-0" MIN.
COMPACTED
ENGINEERED FILL
OPTION 2- ENGINEERED FILL
SCALE: N.T.S.
RETAINING WALL
SCARIFY MINIMUM 8",
MOISTURE
CONDITIONED AND
COMPACTED NATIVE
SUBGRADE.
1'-0" MIN
IMPERVIOUS SOIL OR PAVINGIMPERVIOUS SOIL OR PAVING
SPECIAL INSPECTION:
CERTIFIED INSPECTION (APPROVED BY THE BUILDING OFFICIAL OR THE
ENGINEER OF RECORD) SHALL BE PROVIDED FOR BY THE OWNER IN
ACCORDANCE WITH CHAPTER 17 OF THE INTERNATIONAL BUILDING
CODE.
FIELD OBSERVATION AND TESTING
THE OWNER SHALL EMPLOY A REGISTERED GEOTECHNICAL ENGINEER TO
OBSERVE ALL CONTROLLED EARTHWORK. THE CONTRACTOR SHALL
PROVIDE 24 HOUR NOTICE PRIOR TO CONTROLLED EARTHWORK
OPERATIONS.
TESTS OF MATERIALS SHALL BE MADE AT THE MINIMUM RATES OUTLINED
IN THE PROJECT SPECIFICATIONS.
RESULTS OF ALL TESTS SHALL BE SUBMITTED TO THE OWNER WITHIN
SEVEN DAYS EXCEPT WITHIN 1 DAY FOR THE BAFFLE WALL CONCRETE.
CAST-IN-PLACE CONCRETE
CONCRETE SHALL MEET AT A MINIMUM THE REQUIREMENTS OF THE
FOLLOWING REFERENCES. THE MOST CURRENT VOLUME OF THE REFERENCE
SHALL BE APPLICABLE.
ACI 301 - STRUCTURAL CONCRETE FOR BUILDINGS
ACI 302 - GUIDE FOR CONCRETE FLOOR AND SLAB CONSTRUCTION
ACI 305 - SPECIFICATION FOR HOT WEATHERING CONCRETING
ACI 306 - SPECIFICATION FOR COLD WEATHER CONCRETING
ASTM C 260 - AIR ENTRAINING ADMIXTURES FOR CONCRETE
ASTM C 494 - CHEMICAL ADMIXTURES FOR CONCRETE
ACI 347 - REMOVAL OF FORMS
ALL CONCRETE SHALL HAVE THE MINIMUM SPECIFIED STRENGTH OF 4000 PSI.
AIR ENTRAINMENT SHALL BE USED IN ALL CONCRETE EXCEPT FOR THOSE TO
RECEIVE A STEEL TROWEL FINISH. THE AIR CONTENT FOR EXTERIOR CONCRETE
SHALL BE 6 PERCENT PLUS OR MINUS 1.5 PERCENT.
THE CONCRETE USED FOR THE CLEARWELL AND BAFFLES SHALL INCLUDE
XYPEX ADMIX C-SERIES OR EQUAL IN ACCORDANCE WITH THE
MANUFACTURER'S RECOMMENDATION FOR THE CLEARWELL STRUCTURE.
CONSTRUCTION AND COLD JOINTS AT CLEARWELL: IN ADDITION TO SPECIFIED
WATERSTOPS APPLY ONE COAT OF XYPEX CONCENTRATE SLURRY PER
MANUFACTURER'S RECOMMENDATION TO JOINT SURFACES BETWEEN
CONCRETE PLACEMENTS. MOISTEN THE SURFACES PRIOR TO THE SLURRY
APPLICATION. APPLY THE SLURRY AND KEEP IT MOIST FOR 12 HOURS THEN
ALLOW THE SLURRY TO SET OR DRY. USE XYPEX SEALING STRIPS PER
MANUFACTURER'S RECOMMENDATION AT THE JOINTS.
CONTRACTOR SHALL NOT CAST CONCRETE FOR FOUNDATIONS OR VERTICAL
WALLS DIRECTLY AGAINST EXCAVATED SURFACES.
CHAMFER ALL EXPOSED EDGES OF CONCRETE 3/4” UNLESS SPECIFIED
OTHERWISE.
SEE DRAWINGS OF OTHER TRADES FOR LOCATIONS OF PIPE, ANCHOR BOLTS
AND OTHER FEATURES
CONCRETE MATERIALS SHALL MEET THE FOLLOWING REQUIREMENTS:
1) PORTLAND CEMENT - ASTM C150, TYPE II, LOW ALKALI
2) AGGREGATES - ASTM C33 AND/OR 330.
3) WATER - POTABLE
4) AIR ENTRAINMENT - ASTM C260
5) WATER REDUCING ADMIXTURE - ASTM C494
6) FLY ASH - ASTM C618 CLASS F
ALL ADMIXTURES EXCEPT THE HIGH RANGE WATER REDUCERS SHALL BE
ADDED AT THE BATCH PLANT.
CONCRETE MIX DESIGNS SHALL BE SUBMITTED FOR EACH SPECIFIC MIX DESIGN
TO BE USED IN ACCORDANCE WITH ACI 301. EACH MIX DESIGN SUBMITTED
SHALL HAVE ITS INTENDED USE (FOOTINGS, SLABS, EXTERIOR FLATWORK ETC.)
CLEARLY IDENTIFIED. SUBMIT COPIES OF THE TEST REPORTS FOR CONCRETE
COMPRESSIVE STRENGTH, TEMPERATURE, SLUMP, AND AIR CONTENT.
SUBMIT RESULTS OF LABORATORY TESTING OF THE AGGREGATES SHOWING
COMPLIANCE WITH ATSM C 33 OR C 330.
SUBMIT PRODUCT DATA FOR ADMIXTURES, PROPRIETARY MATERIALS, OR
CURING COMPOUNDS.
CONCRETE SHALL BE PLACED AGAINST FORMWORK. ALL FORMWORK SHALL
BE STRAIGHT AND SECURELY FASTENED.
CONCRETE SHALL BE VIBRATED BY MECHANICAL MEANS IN ACCORDANCE
WITH ACI RECOMMENDED PRACTICES. HAND SPADING, TAMPING, OR
RODDING SHALL BE USED TO SUPPLEMENT MECHANICAL VIBRATION.
CONCRETE SHALL NOT BE OVER VIBRATED TO A POINT OF CAUSING
SEGREGATION OF THE CONCRETE.
ALL FINISHED SLAB SURFACES SHALL BE TROWELED, WALKABLE SURFACES
SHALL HAVE A BROOM FINISH.
NEWLY PLACED CONCRETE SHALL BE IMMEDIATELY PROTECTED FROM
ELEMENTS THAT COULD CAUSE PREMATURE DRYING OR EXCESSIVE COLD
TEMPERATURES.
IMPERFECTIONS SUCH AS HONEYCOMBING, AIR VOIDS, HOLES LEFT BY
TIE-RODS, OR DEBRIS SHALL BE PATCHED WITH CEMENT MORTAR. AREAS OF
EXCESSIVE HONEYCOMBING SHALL BE BROUGHT TO THE ATTENTION OF THE
STRUCTURAL ENGINEER.
FIELD INSPECTION AND TESTING SHALL BE PERFORMED IN ACCORDANCE WITH
ACI 301. THE OWNER SHALL EMPLOY THE SERVICES OF GEOMAT OR A
QUALIFIED TESTING LABORATORY TO PERFORM TESTS AND SUBMIT TEST
REPORTS.
THE CONTRACTOR SHALL PROVIDE FREE ACCESS TO WORK FOR THE
DESIGNATED TESTING FIRM. FRESH CONCRETE SHALL BE SAMPLED IN
ACCORDANCE WITH ASTM C 172. THE SLUMP AND AIR CONTENT OF THE
CONCRETE SHALL BE TAKEN FOR EACH SET OF COMPRESSIVE STRENGTH
SPECIMENS TAKEN IN ACCORDANCE WITH ASTM C 143 AND ASTM C 173 OR C
231, RESPECTIVELY.
CONCRETE TEST CYLINDERS SHALL BE CAST IN ACCORDANCE WITH ASTM C 31.
FIVE STANDARD CYLINDERS SHALL BE CAST FOR EACH COMPRESSIVE
STRENGTH TEST, UNLESS OTHERWISE DIRECTED. MOLD AND STORE
CYLINDERS FOR LABORATORY CURED TEST SPECIMENS EXCEPT WHEN FIELD
CURE TEST SPECIMENS ARE REQUIRED. CYLINDERS SHALL BE CAST FOR EVERY
50 CUBIC YARDS OF EACH TYPE OF CONCRETE PLACED. A MINIMUM OF ONE
SET OF FIVE CYLINDERS SHALL BE CAST FOR EACH DAY THAT CONCRETE IS
PLACED.
COMPRESSIVE STRENGTH TESTS SHALL BE PERFORMED IN ACCORDANCE WITH
ASTM C 39.
THE CONTRACTOR MAY REQUEST ADDITIONAL SPECIMENS TO BE CAST AT NO
ADDITIONAL COST TO THE OWNER UNLESS OTHERWISE AGREED UPON
BETWEEN THE OWNER AND CONTRACTOR.
IN THE CASE OF CONCRETE NOT CONFORMING TO PROJECT REQUIREMENTS,
ADDITIONAL TESTING OR REPAIR/REPLACEMENT MAY BE REQUIRED AS
DIRECTED BY THE STRUCTURAL ENGINEER AT NO ADDITIONAL COST TO THE
OWNER.
THE CONCRETE USED FOR THE BAFFLE WALL EXTENSION SHALL HAVE A HIGH
EARLY STRENGTH ADMIXTURE SUCH THAT THE DESIGN STRENGTH IS
ACHIEVED IN 24 HOURS. 3 TEST CYLINDERS SHALL BE TESTED AT 24 HOURS
AND TWO HELD IN RESERVE FOR FUTURE TESTING.
ALL FORMING, REINFORCING, WATER-STOPS, STRIPPING, FINISHING,
ADMIXTURES, ETC SHALL E CONSIDERED INCIDENTAL TO THE CONSTRUCTION
OF THE CLEARWELL.
REINFORCING STEEL:
ALL REINFORCING STEEL SHALL CONFORM TO ASTM A615 GRADE 60.
CONCRETE COVER SHALL BE AS SHOWN IN THE CONCRETE REINFORCING
COVER TABLE ON THIS SHEET.
TENSION AND COMPRESSION LAPS IN REINFORCING SHALL BE IN
ACCORDANCE WITH ACI 318, CHAPTER 12. THE MINIMUM LAP LENGTH
SHALL BE AS SHOWN IN THE REINFORCING LAP LENGTH TABLE ON THIS
SHEET.
HORIZONTAL REINFORCING SHALL HAVE BENT (CORNER) BARS OF THE
SAME SIZE AND SPACING WITH THE APPROPRIATE LAP LENGTH.
BAR SUPPORTS AND SPACERS SHALL BE SECURELY FASTENED TO
SUPPORTS AND PROVIDED IN ACCORDANCE WITH ACI 315.
CHAIRS WITH 22 GAGE SAND PLATES OR PRECAST BLOCKS SHALL BE
PROVIDED FOR ALL REINFORCING OF CONCRETE IN CONTACT WITH
GRADE.
ACCESS HATCHES:
PROVIDE HALLIDAY W1S3636 ALUMINUM HATCHES (OR APPROVED
EQUAL) IN THE LOCATIONS SHOWN.
HATCHES SHALL INCLUDE SIDE DRAINS THAT DRAIN TO THE SIDE OF THE
HATCH CURB AND ON TOP OF THE CLEARWELL LID.
ALUMINUM SURFACES IN CONTACT WITH CONCRETE SHALL BE COATED
WITH AN APPROVED COATING TO PREVENT CHEMICAL INTERACTIONS
WITH THE CONCRETE.
POST INSTALLED ANCHORS:
ALL POST INSTALLED ANCHORS SHALL BE AS SPECIFIED IN THE DETAILS
OF THESE DRAWINGS. THE CONTRACTOR MAY ONLY SUBSTITUTE
PRODUCTS WITH ENGINEER'S APPROVAL AT NO ADDITIONAL COST TO
THE OWNER.
SUBMIT ALL PROPOSED ANCHORING SYSTEMS, AS WELL AS, THE ICC-ES
REPORTS TO THE ENGINEER FOR REVIEW PRIOR TO INSTALLATION.
FREE-DRAINING
GRANULAR
MATERIAL
FREE-DRAINING
GRANULAR
MATERIAL
12" COMPACTED BACKFILL
REV. No. DATE COMMENT
GEOMAT
1"
SCALE BAR
0 2"
CITY OF AZTEC
WATER TREATMENT PLANT
2025 CLEARWELL EXPANSION
SCALE: AS SHOWN
DRAWN BY: DATE:
GEOMAT PROJECT: 242-4792
APR'D BY: SHT:
PAR SEPT 8, 2025
0 2025-09-08 ISSUED FOR CONSTRUCTION
GENERAL STRUCTURAL
S1
NOTES, TABLES & DETAILS
UNO UNLESS NOTED OTHERWISE
HORIZONTAL HORIZ
W/ W/O
VERT.
WITHOUT
WITH
VERTICAL
TRANSVERSE
TOP OF CONCRETE
TOP OF BEAM
THROUGH
STANDARD
SPECIFICATIONS
REQUIRED
REINFORCING/REINFORCEMENT
POUNDS PER SQUARE FOOT
POUNDS PER LINEAR FOOT
ON CENTER
NOT TO SCALE
MISCELLANEOUS
MINIMUM
MASONRY CONTROL JOINT
MANUFACTURER
LONGITUDINAL
BM
MISC
BEAM
DWLS DOWELS
EMBEDMENT
ELEVATION
FOUNDATION
FOOTING
FEET
FTG
FDN
FT
EA
EMBED
EXTERIOR
EQUAL
EACH
EXT
EQ
EL
T&B
TYP
TOB
TOC
TRANS.
TYPICAL
TOP & BOTTOM
SIM
THRU
SPECS
STD
SIMILAR
DIMENSION
DIAMETER
CONTROL / CONSTRUCTION JOINT
CONTINUOUS
CONCRETE MASONRY UNIT
CONCRETE
CAST-IN-PLACE
CONC
DIM
DIA
CMU
CONT
CJ
BOTT
CLEAR
BOTTOM
CIP
CLR
LBS
SECT
PLF
PSF
REINF
REQD
SHT SHEET
SECTION
POUNDS
PL
NTS
OC
PLATE
AMERICAN WELDING SOCIETY
AMERICAN SOCIETY TESTING MATERIALS
APPROXIMATE
AMERICAN INSTITUTE OF STEEL CONSTRUCTION
ALTERNATE
AMERICAN CONCRETE INSTITUTION
APPROX
ASTM
AWS
AISC
ALT
ACI
LONG.
MFR
MCJ
MIN
ABBREVIATIONS
TOF TOP OF FOOTING
B/F BOTTOM OF FOOTING
E.W. EACH WAY
F.F. FINISHED FLOOR
E.F. EACH FACE
TO TOP OF
TOS TOP OF STEEL
LEGEND
INDICATES A KEYED NOTE. SEE THE KEYED
NOTE SCHEDULE.
INDICATES A CUT SECTION LOCATION,
NUMBER AND SHEET
INDICATES A CONCRETE WALL SLAB OR
OTHER FEATURE.
GRID LINEGL
INDICATES A CONTROL JOINT IN THE
SLAB-ON-GRADE. SEE DETAIL 11/S401.
CJ
CONTINUOUS FOOTINGCF
XX
X
CENTERLINECL
HEADED ANCHOR STUDHAS
PROJ PROJECTION
X
OVERVIEW OF IMPROVEMENTS
SCALE: 3/16" = 1'-0"
PL
AN
N O
RT
H
24" NPW
"W
"N
PW
4" PVC
6" P
VC
24" NPW
TR
UE
N
OR
TH
WATER TREATMENT PLANT
FIRST CLEARWELL
ADDTION
SECOND CLEARWELL
ADDITION
PROPOSED
CLEARWELL
ADDITION
PI
PE
G
AL
LE
RY
OVERVIEW - KEYED NOTES
GENERAL: THESE KEYED NOTES APPLY ONLY TO THE STRUCTURAL
SCOPE. SEE CIVIL DESIGN PLANS FOR LAY-OUT, PIPING, GRADING,
AND OTHER DESIGN ELEMENTS.
1. PROPOSED CLEARWELL ADDITION: CONSTRUCT AN ADDITION TO
THE EXISTING CLEARWELL AS SHOWN. SEE PLAN ON SHEET S3.
2. BAFFLE WALL EXTENSION: CONSTRUCT AN EXTENSION TO AN
EXISTING BAFFLE WALL IN THE SECOND CLEARWELL ADDITION AS
SHOWN. SEE DETAILS ON SHEET S4
3. WALL OPENINGS: CUT TWO OPENINGS THROUGH THE WALL OF
THE EXISTING SECOND CLEARWELL ADDITION TO ALLOW WATER
FLOW TO AND FROM THE PROPOSED CLEARWELL ADDITION. SEE
DETAILS ON SHEET S4
4. PROPOSED RETAINING WALL: REMOVE THE EXISTING RAILROAD
TIE RETAINING WALL AND CONSTRUCT A CONCRETE RETAINING
WALL WITH RAILING AS SHOWN. SEE DETAILS ON THIS SHEET.
REPLACE EXISTING R.R. TIE RETAINING WALL
4" P
VC
6" P
VC
5710.005705.05
5710.00
5704.71
5705.00
5704.05
"TOE" "W" "HEEL"
"T"
3" CLR
2" CLR
#4 @ 12"
O.C. TYP
"TOP BAR"
DOWELS TO MATCH VERT.
BAR SIZE & SPACING.
VERT. LAP TO BE 57d.
"H"
30" MIN.
#4 @ 12" O.C.
TYP HORIZ.
3/4" CHAMFER TYP AT
ALL EXPOSED EDGES
2-FEET WIDE CRUSHED
STONE OR GRANULAR SOIL
1"Ø WEEP HOLES @ 6'-0" O.C.
"FACE BAR" VERT.
"BACK BAR" VERT.
"H"
0' TO 3'-11"
4' TO 7'
"W" "T" "TOE" "HEEL" "BOTTOM BAR" "TOP BAR" "FACE BAR" "BACK BAR"
RETAINING WALL SCHEDULE
SCALE: N.T.S.
10" 14" 1'-6" 1'-5" #5@10" O.C. #5@10" O.C.
10" 14" 3'-8" 1'-8" #5@8" O.C. #5@8" O.C. #5@8" O.C. #5@8" O.C.
GEOTEXTILE FILTER FABRIC
IMPERVIOUS SOIL
BACKFILL OR
CONCRETE PAVING
#5@10" O.C. #5@10" O.C.
1/4 TYP
5"
5"
1" TYP
RAILING DETAIL
SCALE: N.T.S.
8'-0" MAX
1/4
1 1/2"Ø STD.
PIPE IN CTR
PL 1/4x5 x 0'-5" LONG W/ (2)
HOLES FOR 5/8"Ø BOLTS
1'-9"
3'-6"
PL 1 4"x 1 7/8"Ø
RAIL: 1 1/4" Ø STD PIPE TYP.
POST: 1 1/2"Ø
STD. PIPE TYP.
RAIL: 1 1/4" Ø STD PIPE TYP.
BASE PLATE: PL 1/4x5 x 0'-5"
W/ (2) HOLES FOR 5/8"Ø
EXPANSION ANCHORS
5/8"Ø EXPANSION ANCHORS.
TWO AT EA. POST.
6" MIN EMBED
BASE PLATE DETAIL
RAILING
VALLEY GUTTER - SEE CIVIL
RAILING NOTE:
· INSTALL RAILING IN LOCATIONS WHERE "H" IS
4-FEET OR MORE.
· THE RAILING SHALL BE COATED SAFETY YELLOW
WITH A TWO-PART EPOXY COATING. ANY
DAMAGED AREA SHALL BE TOUCHED UP IN THE
FIELD.
"BOTTOM BAR"
REV. No. DATE COMMENT
GEOMAT
1"
SCALE BAR
0 2"
CITY OF AZTEC
WATER TREATMENT PLANT
2025 CLEARWELL EXPANSION
SCALE: AS SHOWN
DRAWN BY: DATE:
GEOMAT PROJECT: 242-4792
APR'D BY: SHT:
PAR SEPT 8, 2025
0 2025-09-08 ISSUED FOR CONSTRUCTION
OVERVIEW OF IMPROVEMENTS
S2
& RETAINING WALL DETAIL
TYP
S4
E
F
G
25'-2"
4'-10"
5'-11"
4'-1 3/16"
4'-1 3/16"
4'-8 3/16"
18'-9 1/2"
30'-0"
48'-9 1/2"
27'-0"
20'-7 1/2"
6'-4 1/2"
4'-0"
4'-0"
4'-0"
4'-3 3/8" 8" 4'-2 3/8" 8" 4'-2 3/8" 8" 4'-3 3/8" 10"10"
4'-0"
2 3 4
4'-10 3/8" 4'-10 3/8" 5'-5 3/8"5'-5 3/8"
20'-7 1/2"
B
C
D
18'-9 1/2"
CLEARWELL EXPANSION PLAN
SCALE: 1/4" = 1'-0"
PL
AN
N O
RT
H
TYP
S4
TYP
S4
S4
" N
PW
6" P
VC
TR
UE
N
OR
TH
S4
S4
S4
BA
FF
LE
W
AL
L
(T
YP
BAFFLE WALL (TYP.)
36"x36"
HATCH
36"x36"
HATCH
EXISTING CLEARWELL
FIRST ADDITION
EXISTING CLEARWELL
SECOND ADDITION
PROPOSED CLEARWELL
THIRD ADDITION
BAFFLE WALL EXTENSION
SEE DETAIL 5/S4
36"x36"
HATCH
REV. No. DATE COMMENT
GEOMAT
1"
SCALE BAR
0 2"
CITY OF AZTEC
WATER TREATMENT PLANT
2025 CLEARWELL EXPANSION
SCALE: AS SHOWN
DRAWN BY: DATE:
GEOMAT PROJECT: 242-4792
APR'D BY: SHT:
PAR SEPT 8, 2025
0 2025-09-08 ISSUED FOR CONSTRUCTION
CLEARWELL EXPANSION PLAN
S3
GENERAL NOTES:
SEE CIVIL DRAWINGS FOR THE SUGGESTED SEQUENCE
OF CONSTRUCTION ACTIVITIES
9"
HATCH 36" x 36"
W/ SIDE DRAIN
(HALLIDAY W1S3636
OR EQUAL) 9"
4'-6"
(1) #4 CONTINUOUS
AROUND PERIMETER IN
CENTER SUPPORTED ON
1/2"Ø DRILL & EPOXY BOLTS
@ 24" O.C. W/ 4" EMBED
SIDE-DRAIN
PROVIDE ADDITIONAL REINFORCING AROUND
LID PENETRATIONS IN ACCORDANCE WITH 7/S4
5"
8"
ACCESS
HATCH CURB
10"
3" CLR
2" CLR
9'-7"
8"
1 1/2" CLR
1 1/2" CLR
CLEARWELL LID - 8" THICK
W/ #5 BARS @ 8" EA.WAY,
TOP & BOTT. 1 1/2" CLR.
CLEARWELL FLOOR - 10" THICK W/
#4 BARS @ 8" EA.WAY, TOP & BOTT.
3" CLR.@BOTT, 2" CLR.@TOP
3 1/2" x 1 1/2"
KEYED JOINT W/
9" RCB TVR
WATER STOP
3 1/2" x 1 1/2" KEYED JOINT
CLEARWELL WALL - 10" THICK
W/ #4 BARS @ 8" EA.WAY,
EA.FACE. 2" CLR. TYP
ACCESS HATCH CURB
SCALE: 3/4" = 1'-0"6
TYP. FLOOR, WALL, ROOF SECTION
NTS1
10"
9'-7"
8"
CLEARWELL LID
SEE 1/S4
3 1/2" x 1 1/2" KEYED JOINT
W/ 9" RCB TVR WATER STOP
INTERIOR WALL - 8" THICK W/
#5 BARS @ 8" EA.WAY IN CENTER
TYP. BAFFLE WALL SECTION
NTS2
3 1/2" x 1 1/2" KEYED JOINT
DOWELS MATCHING SIZE & SPACING
OF VERT. REBAR 30" LAP
DOWELS MATCHING SIZE & SPACING
OF VERT. REBAR 30" LAP
DOWELS MATCHING SIZE & SPACING
OF VERT. REBAR 30" LAP.
ALTERNATE DIRECTION
DOWELS MATCHING SIZE & SPACING
OF VERT. REBAR 30" LAP.
ALTERNATE DIRECTION
3 1/2" x 1 1/2" KEYED JOINT
W/ 9" RCB TVR WATER STOP
WALL SECTION AT ADJOINING BUILDING
NTS3
10"
9'-7"
8"
CLEARWELL LID
SEE 1/S4
3 1/2" x 1 1/2" KEYED JOINT
W/ 9" RCB TVR WATER STOP
1 1/2" HIGH x 1" WIDE XYPEX DRY PAC IN
ACCORDANCE WITH MANUFACTURER'S
RECOMMENDATIONS.
3 1/2" x 1 1/2" KEYED JOINT
WALL SECTION AT NEW / EXISTING CLEARWELL
NTS4
10"
8"
CLEARWELL FLOOR; SEE 1/S4
ACCESS HATCH;
SEE 6/S4
TOP OF LID = 5705.14 *
INV.= 5694.89 *
EXISTING
CLEARWELL
SECOND
ADDITION
EXISTING
WATER
TREATMENT
PLANT
CLEARWELL WALL
SEE 1/S4
3 1/2" x 1 1/2" KEYED JOINT
CLEARWELL WALL
SEE 1/S4
RECTANGULAR
OPENING
REINFORCING AROUND PENETRATIONS
SCALE: N.T.S.7
PENETRATIONS NOTES:
· AT ALL PENETRATIONS: ADD (4) #4 x 36" LONG DIAGONAL BARS NEXT TO EACH
REINFORCING MAT. 1 1/2" CLEAR FROM OPENING.
· AT PENETRATIONS LESS THAT 12" IN THE GREATEST DIMENSION: DEFLECT THE TYPICAL
REINFORCING AROUND THE PENETRATION. MAINTAIN 1 1/2" CLEAR.
· AT PENETRATIONS 12" TO 30" IN THE GREATEST DIMENSION: DISCONTINUE TYP.
REINFORCING AT THE OPENING AND ADD (1) #5 BARS FOR EACH REINFORCING MAT ON
EACH SIDE OF THE PENETRATION. BAR LENGTH TO BE x (OPENING + 36"). MAINTAIN 1
1/2" CLEAR.
· AT PENETRATIONS 30" TO 48" IN THE GREATEST DIMENSION: DISCONTINUE TYP.
REINFORCING AT OPENING. ADD (2) #5 BARS FR EACH REINFORCING MAT ON EACH SIDE
OF THE PENETRATION. BAR LENGTH TO BE x (OPENING + 36"). MAINTAIN 1 1/2" CLEAR &
3" BETWEEN.
ROUND
OPENING
CLEARWELL LID
SEE X/SXX
EXISTING LID
EXISTING FLOOR
EXISTING
WALL
EXISTING BAFFLE WALL
CONSTRUCT BAFFLE
WALL EXTENSION
APPROX 3'-0" FIELD VERIFY
3/4" x 1" BENTONITE
WATERSTOP EA.FACE
BAFFLE WALL EXTENSION DETAIL
SCALE: 3/4" = 1'-0"5
#5 DOWEL W/ MINIMUM 24"
LAP. DRILL & EPOXY DOWELS,
SEE ELEVATION
EXISTING LID
EXISTING FLOOR
ELEVATION SECTION
EXISTING CMU
BAFFLE WALL BAFFLE WALL EXTENSION:
8" THICK W/ #5 BARS @
8" EA.WAY IN CENTER
DIAGONAL
BARS DIAGONAL
BARSADDED
BARS
ADDED
BARS
NOTE: TYP. REINFORCING IS
NOT SHOWN IN THIS DETAIL
VOID FORM
8"10"
EXISTING CONCRETE WALL
NOTE: PREVIOUS POTHOLING
INDICATES FOUNDATIONS EXTEND
TO BOTTOM OF EXSITING
CLEARWELL. IF CONDITIONS
DIFFERENT, DISCONTINUE
EXCAVATING AND CONTACT
ENGINEER OF RECORD. UNDER
PINNING WILL BE REQUIRED
9'-7"
1'-6"
5-#5 VERTS , SPACED
EVENLY; #5 HORIZ
@ 8" O.C.
#5 REBAR W/ HILTI
HIT-HY 200 A V3
ADHESIVE ANCHOR
6-3/4" MIN. EMBED
TYP. BOTTOM & SIDES
CONNECTION PIPE DETAIL KEYED NOTES:
THESE KEYED NOTES IN CONJUNCTION WITH DETAIL 8/S4 SUGGEST ONE
POSSIBLE WAY TO CONSTRUCT THE CONNECTION BETWEEN THE OLD AND
NEW CLEARWELLS. THE CONTRACTOR MAY ELECT TO USE A DIFFERENT
MEANS AND METHODS, BUT THE CONTRACTOR'S MEANS AND METHODS
MUST BE SUBMITTED IN DETAIL AND APPROVED BEFORE CONSTRUCTION
BEGINS.
1. REMOVE SOIL, LOOSE CONCRETE OR OTHER DEBRIS, FROM THE OUTSIDE OF
THE EXISTING CLEARWELL WALL. COAT WALL USED TO FORM NEW
CLEARWELL WALL WITH XYPEX SLURRY CONCENTRATE.
2. CONSTRUCT THE NEW CLEARWELL WALL.
2.1. INCLUDE XYPEX C500 SERIES IN THE MIX DESIGN IN ACCORDANCE WITH
THE MANUFACTURER'S RECOMMENDATIONS.
2.2. CAST A 3-FOOT HIGH x 3-FOOT WIDE OPENING CENTERED ON THE
LOCATION FOR THE PIPE.
2.3. CAST A 1" WIDE x 1 1/2" DEEP NOTCH AROUND THE PERIMETER OF THE 3x3 OPENING AS SHOWN.
2.4. PROVIDE ADDITIONAL REINFORCING AROUND THE OPENING SIMILAR TO
DETAIL 7/S4.
3. CUT THE HOLE IN THE OLD CLEARWELL WALL
3.1. CORE DRILL PILOT HOLES IN THE CORNERS OF PROPOSED OPENING.
3.2. SAWCUT THE OLD WALL TO OUTSIDE TANGENT OF CORE DRILLED HOLES
RESULTING IN A 3-FOOT HIGH x 3-FOOT WIDE OPENING IN THE OLD
CLEARWELL WALL.
3.3. REMOVE SAWCUT PORTION OF WALL, CLEAN DEBRIS
3.4. CUT A 1" WIDE x 1 1/2" DEEP NOTCH AROUND THE PERIMETER OF THE
OPENING.
3.5. ROUGHEN OPENING AND COAT W/ XYPEX SLURRY CONCENTRATE.
4. INSTALL 32" DIAMETER STUB PIPE THROUGH THE OPENING.
4.1. THOROUGHLY CLEAN & ROUGHEN THE OUTSIDE SURFACE OF PIPE AND
APPLY XYPEX CONCENTRATE SLURRY.
4.2. PLACE TWO CONSEAL CR-231 (OR EQUAL) WATERSTOPS AROUND THE
PIPE.
4.3. INSERT PIPE & WATERSTOPS THROUGH THE OPENING AND SUPPORT IN
PLACE WITH TEMPORARY SHORING.
5. SEAL THE OPENING
5.1. INSTALL XYPEX CONCENTRATE PATCH & PLUG AROUND THE PIPE IN
ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS. (2" TO 3"
LIFTS FULL DEPTH)
INV.= 5694.89 *INV.= 5694.89 * INV.= 5694.89 * INV.= 5694.89 *
* ELEVATIONS NOTES:
· THE TOP OF LID AND INVERT ELEVATIONS
SHOWN ARE BASED ON SURVEY INFORMATION
AVAILABLE AT THE TIME OF DESIGN.
· THE INTENT OF THE DESIGN IS TO MATCH THE
EXISTING TOP OF LID AND INVERT ELEVATIONS
WITH THE NEW CONSTRUCTION.
· IF THE ACTUAL ELEVATIONS DIFFER FROM
THOSE SHOWN, HOLD THE ACTUAL
ELEVATIONS.
· IF THE DIFFERENCE IS MORE THAN 2 INCHES,
NOTIFY THE DESIGN TEAM BEFORE
PROCEEDING.
* SEE ELEVATIONS NOTES ON THIS SHEET* SEE ELEVATIONS NOTES ON THIS SHEET* SEE ELEVATIONS NOTES ON THIS SHEET* SEE ELEVATIONS NOTES ON THIS SHEET
X
2.2
2.3
3.1 3.2 3.4
5.1
TYP
4.1
4.2
2.2
2.3
5.1
4.2
3.5
5.1
3.2
CONNECTION PIPE DETAIL
SCALE: N.T.S.8
ELEVATION
SECTION
CONNECTION PIPE
SEE DETAIL 8/S4
TOP OF LID = 5705.14 *TOP OF LID = 5705.14 *TOP OF LID = 5705.14 *
10"
2'-8"Ø
2"
2"
3'-0"
SQ.
2"
2'-8"Ø 3'-0"
SQ.
2"
ADDITIONAL REINFORCING
AROUND OPENING.
SEE DETAIL 7/S4
1'-3"
2"
2'-8"Ø
2"
3'-0"
SQ.
2"
2'-8"Ø 3'-0"
SQ.
1'-3"
3.3
1 1/2"
1"
4.2
3.4
3.5
2.1
4.3
CLEARWELL FLOOR; SEE 1/S4CLEARWELL FLOOR; SEE 1/S4
1 1/2" HIGH x 1" WIDE XYPEX DRY PAC IN
ACCORDANCE WITH MANUFACTURER'S
RECOMMENDATIONS.
1 1/2" HIGH x 1" WIDE XYPEX DRY PAC IN
ACCORDANCE WITH MANUFACTURER'S
RECOMMENDATIONS.
1 1/2" HIGH x 1" WIDE XYPEX DRY PAC IN
ACCORDANCE WITH MANUFACTURER'S
RECOMMENDATIONS.
8" 10"
CONNECTION PIPE NOTE:
THE CITY WILL REDUCE THE WATER LEVEL IN THE EXISTING
CLEARWELL TO FACILITATE THE MAKING OF THE CONNECTION
BETWEEN THE NEW AND THE OLD CLEARWELLS.
THE REDUCED WATER LEVEL CAN ONLY BE MAINTAINED FOR
48 HURS MAX.
THE CONTRACTOR SHALL PLAN TO WORK CONTINUOUSLY, 24
HOURS PER DAY, UNTIL THE CONNECTION IS COMPLETE AND
THE WATER LEVEL CAN BE RESTORED.
SEE THE CIVIL PLANS AND PROJECT SPECIFICATIONS FOR
MORE INFORMATION.
REV. No. DATE COMMENT
GEOMAT
1"
SCALE BAR
0 2"
CITY OF AZTEC
WATER TREATMENT PLANT
2025 CLEARWELL EXPANSION
SCALE: AS SHOWN
DRAWN BY: DATE:
GEOMAT PROJECT: 242-4792
APR'D BY: SHT:
PAR SEPT 8, 2025
0 2025-09-08 ISSUED FOR CONSTRUCTION
REINFORCING DETAILS
S4
| 000 Cover Sheet |
| C-100 Layout Plan |
| C-200 Grading Plan North |
| C-201 Grading Plan South |
| C-300 Backwash Pipe Plan and Profile |
| C-301 Retaining Wall Profile |
| C-400 Details |
| 2025-09-08 CoA CLEARWELL-1-COVER |
| Sheets and Views |
| 1-COVER |
| 2025-09-08 CoA CLEARWELL-2-SITE |
| Sheets and Views |
| 2-SITE |
| 2025-09-08 CoA CLEARWELL-3-CLEARWELL |
| Sheets and Views |
| 3-CLEARWELL |
| 2025-09-08 CoA CLEARWELL-4-CLEARWELL DETAILS |
| Sheets and Views |
| 4-CLEARWELL DETAILS |
File details come from the government source that posted it. Updated .