This document is an Appendix B Building Walkthrough Analysis for the City of Peoria, Illinois, detailing comprehensive building condition assessments for multiple properties including the PNC Bank Building, Creve Coeur Building, and associated parking garage. The walkthrough report systematically examines various building components across multiple floors, highlighting structural, mechanical, and maintenance issues. Key observations include water damage in multiple locations, mold presence in the basement, non-functioning elevators, aging mechanical systems with asbestos insulation, and deteriorating infrastructure such as rusted pipes and support beams.
The report suggests significant potential for building renovation and repurposing, noting that floors have flexibility for subdivision and potential residential conversion. Major systems requiring attention include elevators, HVAC, plumbing, and electrical infrastructure. The properties appear to have been previously used by various tenants including PNC Bank, CliftonLarsonAllen, and potentially Caterpillar, with some spaces currently vacant. Substantial capital investment would be needed to bring the buildings to contemporary standards, addressing issues like water intrusion, structural wear, outdated mechanical systems, and compliance with current building codes. The walkthrough analysis provides a detailed baseline assessment that would be crucial for any redevelopment planning or property acquisition strategy.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PNC Bank Building Review 05.17.2024
Appendix B
Table of Contents
Contents Table of Contents
General Summary
Rich Storm Notes
PNC Bank Section
CliftonLarsonAllen Floor
Vacant Floor
Low Roof
High Roof
Basement
General Summary
Total Floors: 11 Square Feet per Floor: 12,910 square feet Total Square Feet for Building: 166,948 square feet Floors have availability to be subdivided
Elevators: 3, with no single elevator accessing all floors
Lead flashing on roof piping speaks to age of building
Freight elevator has shared access between buildings
Residential conversion would require some plumbing on the east side of building, but floor plan is conducive for residential.
Only floors that are sprinkled are floors 10 & 11
CliftonLarsonAllen built independent stairway between floors 10 & 11
Safe in basement which has 2 feet thick of steel
Rich Storm Notes
Requires Resolution Before Occupancy of Building
• Elevators that function between all floors for residential conversion
• Service elevator needs to have crack repaired in basement
Should be Resolved
• Utilize a check of all mechanical systems
PNC Bank Section Note: PNC did not allow photographs in many sections
Elevators on mezzanine
Elevators accessible on 1st floor
Executive meeting room above customer space
Window in executive conference room
View of PNC bank public area from executive conference room
CliftonLarsonAllen Floor Note: CLA did not allow photographs in many sections
Updated offices and meeting rooms from hallway
Updated offices and meeting rooms from hallway
Hallway off elevators
Employee Break Room
Floor of meeting room
Meeting room with ceiling removed
CLA is replacing the HVAC unit
Employee work area of
CLA
Stairwell connecting floors 10 & 11
Vacant Floor Example of a layout of the vacant floor
Elevator landing on 7th floor
Elevators and reception area on floor
Floor layout example provided from brochure
Low Roof Standing water on roof due to a clogged drain
Rooftop chiller unit
Serial number on unit
Low roof entrance
Water drainage on low roof to clogged drain
Entrance to second room on low roof
Access above PNC main lobby
Steam pipe system
Wear on insulation in section above main lobby
No issues, but needs addressed for efficiency utilization
High Roof View from roof of Peoria
PNC sign affixed to roof and building
Elevator systems
Elevator systems
Lead flashing on rooftop pipe
Rusted out drain cap on roof
Basement Elevator doors in basement
Publicly accessible restrooms off the elevator in the basement
Hallway in basement
Water heater in
Damage on wall and bulging rusted pipe
Plastering around vent work
Communications board in
Crack in basement for service elevator shaft
Airflow comes through the crack
Will need to be repaired
Second picture of crack
Water damage and rust in ceiling of basement
Hallway in basement
Workshop in basement
Bank vault outer cage
Bank vault where PNC security deposits are held
Ceiling in basement of bank vault cage area
Creve Coeur Building Review 05.17.2024
Table of Contents
Contents Table of Contents
General Summary
Rich Storm Notes
Creve Coeur 1st Floor (Street Level)
Creve Coeur Mezzanine
Creve Coeur Floor Two
Creve Coeur Floor Three
Creve Coeur Floor Four
Creve Coeur Building Basement
Parking Garage Office Space
Parking Garage Lower Level
Shared Boiler Room above Parking Garage
General Summary
Total Floors: 4 + Mezzanine Square Feet per Floor: Approximately 13,000.
Total Square Feet for Building: Approximately 65,000 square feet.
Floors have availability to be subdivided.
Elevators: 3 elevators facing street, only one operational, one is a façade, other one is broken. 2 broken interior elevators that are not operational.
Basement has mold, a water ingress, and a newer A/C unit that was installed, likely for use for the more recently operated Caterpillar offices.
Walkway: Connects floors 2, 3, and 4.
Water leaks: Entering floor 3, noting a significant water leak with water damage coming from restroom. Additional severe water leak on roof.
Piping by roof access has asbestos insulation.
Roof has lead flashing and some damaged concrete exterior.
The fire escape has been certified within the last 5 years.
Freight elevator has shared access between buildings.
Commissary Kitchen on the 4th floor has been unused for approximately 10 years.
Building likely has A/C issues.
Rich Storm Notes
Requires Resolution Before Occupancy of Building
• Elevators that function between all floors for residential conversion
• All elevator shafts completely sealed
• HVAC system will need to be checked
Should be Resolved
• Repair water leaks through roof
• Repair damaged plumbing
• Asbestos insulation can stay, until mechanicals are changed in building o Would require asbestos abatement
• Hydraulic elevators will need to be repaired
Creve Coeur 1st Floor (Street Level) Rigging of bathrooms in the first floor
Needs short wall bracing
Picture of interior
Hole in elevator shaft
Needs to be sealed
Picture of hole with elevator
Needs to be sealed
Non-functioning elevator
Needs to be repaired prior to occupancy
Doorway with damaged hole above it
Old layout during Creve Coeur Club tenure
First floor hallway between sections
Creve Coeur Mezzanine Crack in drywall in hallway
Breakroom
Inactive office space
High ceilings in the mezzanine above drop ceiling tiles
Old office space on mezzanine
Moisture damage on old wallpapered office
Creve Coeur Floor Two Office space used as storage
Hydronic heat system, coverings off due to repairs
Employee break room
Internal space
Water damage down wall
Office space
Creve Coeur Floor Three Conference room in center of floor
Conference room in center of floor
Data hookup
Water damage in wall
Bathrooms accessible by PNC building on third floor (blocked by propped up tables)
Two walk-in vaults
Office space on floor
Vault as part of office space
Connecting hallway between open office areas
Office area
Built out room
Creve Coeur Floor Four Storage room as part of kitchen
Office by commercial kitchen
Damage by freight
Damaged wall
Dining area
Commercial kitchen
Commercial kitchen
Walk in cooler/freezer
Water damage in stairwell
Ductwork with asbestos
HVAC system
Chilling tower
Lead flashing on rooftop pipe
Doesn’t need replaced
Insulation on piping
Water damage at top of the stairwell
Hallway
Water damage
Training room
Training room
Creve Coeur Building Basement Built out AC room and elevation
Open main room
Open main room
Mold on drywall
Broken button by
Needs to be repaired if publicly accessible
Built frames for basement restroom
Rust damage on pipe and replaced section
Basement spare room
Elevator and damage outside of it
Replaced piping section
Standing water in mechanical room
Parking Garage Office Space Entrance to parking garage room
Exterior of parking garage room
Room shot
Safe in inner room
Safe as part of room
Parking Garage Lower Level Note: Active case by Community Development for things that need rectification in parking garage.
Basement of parking garage
Tunnel to underground power source
New switch gear for building
New switch gear for building
Worn down piping in
Blocked flam cabinet
Storage central room in basement of parking
Rusted air mover in basement central room
Rusted support beam in basement of parking
Shared Boiler Room above Parking
Garage Boiler 1
Boiler 2
| Appendix B PNC Building |
| Table of Contents |
| General Summary |
| Rich Storm Notes |
| PNC Bank Section |
| CliftonLarsonAllen Floor |
| Vacant Floor |
| Low Roof |
| High Roof |
| Basement |
| Appendix C Creve Coeur Building |
| Table of Contents |
| General Summary |
| Rich Storm Notes |
| Creve Coeur 1st Floor (Street Level) |
| Creve Coeur Mezzanine |
| Creve Coeur Floor Two |
| Creve Coeur Floor Three |
| Creve Coeur Floor Four |
| Creve Coeur Building Basement |
| Parking Garage Office Space |
| Parking Garage Lower Level |
| Shared Boiler Room above Parking Garage |