Appendix B 25QA102.pdf

PDF 2 MB Posted

Attached to
HVAC System Maintenance, Otter Brook Lake, Keene, NH
Solicitation number
W912WJ25QA102
Issued by

About this file

This Performance Work Statement (PWS) details HVAC system maintenance for the U.S. Army Corps of Engineers at the Otter Brook Lake facility in Keene, New Hampshire. The technical documents include comprehensive mechanical system drawings, schedules, and control diagrams for a new operations office building. Key systems include an air handling unit (AHU-1), energy recovery ventilator (ERV-1), radiant ceiling panels, cabinet unit heaters, air-cooled condensing units, and associated control infrastructure. The mechanical design supports multiple zones including office spaces, staff bathrooms, supervisors' offices, and building mechanical areas, with specific attention to temperature control, ventilation, and heating requirements across basement and first floor levels.

The design incorporates sophisticated control strategies with adjustable occupancy modes, economizer functionality, and safety features like freezestat protection. Specific equipment includes Trane and Mitsubishi systems, with precise specifications for airflow rates, temperature ranges, electrical requirements, and installation details. The documents provide extensive technical guidance for contractors, including mounting instructions, piping schematics, ductwork construction standards, and detailed equipment schedules that outline performance characteristics, electrical specifications, and manufacturer recommendations for each system component.

View the file

Other files

File Type Posted
Amendment W912WJ25QA102-0001.pdf PDF
Appendix A 25QA102.pdf PDF
Appendix C 25QA102.pdf PDF
Solicitation - W912WJ25QA102.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

HVAC SYSTEM MAINTENANCE

U.S. ARMY CORPS OF ENGINEERS

OTTER BROOK LAKE

KEENE, NH

PERFORMANCE WORK STATEMENT

APPENDIX B

Project Drawings

PLAN

NORTH

SCALE 1/4" = 1' - 0"

BASEMENT MECHANICAL PLAN

A2

0 4' 8'2'

U P

STAIRS

BASEMENT

8x6 EA UP

22x12 SA UP

22x12 OA UP

20x10 RA UP

AHU

FC

8x6 7

L-2

CU

ACCU

RS/RL UP

TO AC-1

UH

H W

R

H W

S

B

22x12

Ø

ERV

x

8x6

32x30

INSULATED

PLENUM

12Ø

RL/RS

(2 SETS)

RL/RS

RL/RS 4

HWR

HWS

HWR

HWS

CUH

Ø

3/4"

1-1/4"

1-1/4"

FC

20x10

(BELOW)

1"

ERV-1

SERVICE

CLEARANCE

3/4"

M-301

H3

22x12

12Ø

12Ø

DN

20x10 TO

PLENUM

M-301

A4

22x12

AS-1

2" HWS & HWR

MAKE-UP

WATER

SUPPLY

(WALL MOUNT)

P

2A

P

2B

LPG

NEUTRALIZATION KIT

EXT-115

CP

43/4" CD

CP

20x10

AHU-1

SERVICE

CLEARANCE

P

UP

FC

FC

RF

18 24

18 24

RISE

US Army Corps of Engineers

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

A

B

C

D

E

F

G

H

J

K

L

M

N

P

SHEET ID

U S

A

R M

Y

C

O R

P S

O

F

E

N G

I N

E E

R S

O T

T E

R

B

R O

K

D

A M

L

K E

N E

W

O

P E

R A

T I O

N

F

I C

E

GENERAL SHEET NOTES:

1. FOR MECHANICAL SYMBOLS, LEGENDS, AND

ABBREVIATIONS REFER TO SHEET M-001.

2. INSTALL EQUIPMENT TO ALLOW MAINTENANCE ACCESS AS

REQUIRED BY EQUIPMENT MANUFACTURER'S WRITTEN

INSTRUCTIONS. PROVIDE MINIMUM 12" MAINTENANCE

CLEARANCE AT VALVES AND OTHER ACCESS LOCATIONS.

3. FOR DUCTWORK FABRICATION, HANGER AND SUPPORT

DETAILS REFER TO SHEETS M-501, M-502, AND M-503.

4. DUCTWORK AND PIPING PENETRATIONS THROUGH

FIRE/SMOKE WALLS/FLOORS/BARRIERS SHALL BE SEALED

WITH FIRE STOPPING ACCORDING TO DIVISION 7

REQUIREMENTS.

5. NO FLEXIBLE DUCT SHALL PASS THROUGH FIRE/SMOKE

WALLS/FLOORS/BARRIERS.

6. COORDINATE INSTALLATION WITH FIRE ALARM, PLUMBING,

MECHANICAL, AND ELECTRICAL TRADES.

KEYNOTES:

1-1/4" HWS UP.

1-1/4" HWR UP.

8x6 EA UP.

ROUTE PIPING AS HIGH AS POSSIBLE.

3" BOILER COMBUSTION AIR AND EXHAUST UP

THRU ROOF. COORDINATE LOCATIONS WITH

ARCHITECTURAL DRAWINGS.

SEAL WALL PENETRATION WEATHERTIGHT.

ROUTE DUCTWORK AS HIGH AS POSSIBLE.

FIELD FABRICATE MIXING BOX.

DUCT SA VENTILATION AIR FROM ERV-1 INTO

RETURN OF AHU-1.

FOR SEQUENCE OF OPERATION AND

MOTORIZED DAMPER POSITIONS IN

ECONOMIZER MODE REFER TO A4/M-701.

FOR BOILER PIPING DIAGRAM REFER TO

F2/M-502.

CONDENSATE DRAIN TO DISCHARGE INTO

INDIRECT WASTE. REFER TO D16/P-601.

FOR CONTINUATION REFER TO SHEET P-101.

FOR LOUVER CONNECTION, REFER TO DETAIL

F1/M-501.

FOR EXPANSION TANK EXT-1 PIPING DIAGRAM,

REFER TO K4/M-502.

BOILER EMERGENCY SHUT-OFF SWITCH.

PROVIDE CONCRETE EQUIPMENT PAD. SEE

DETAIL L6/SB502.

PROVIDE DUCT ACCESS PANEL FOR

INSPECTION AND MAINTENANCE OF FIRE

DAMPER.

FOR UNIT HEATER PIPING DETAIL REFER TO

K7/M-501.

FOR CABINET UNIT HEATER PIPING DETAIL

REFER TO K10/M-502.

REFRIGERANT LINE SET; RS 1-1/8" AND RL 3/8".

REFRIGERANT LINE SET; RS 1/2" AND RL 1/4".

HOUSEKEEPING EQUIPMENT PAD.

PROVIDE DUCT MOUNTED FIRE DAMPER

BELOW FIRST FLOOR ASSEMBLY

05 Nov, 2021 - 1:37pm

Y:\22004.09\22004.09-MH100.dwg

B A

S E

M E

N T

M E

C H

A N

I C

A L

P L A

N

OTTER BROOK

MH100

(THIS SHEET ONLY)

AutoCAD SHX Text M

AutoCAD SHX Text M

AutoCAD SHX Text M

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text M

AutoCAD SHX Text

SCALE 1/4" = 1' - 0"

FIRST FLOOR MECHANICAL PLAN

A2

0 4' 8'2'

DN

RAMP DN

DN

OFFICE #4

RANGERS'S

OFFICE #3

RANGERS'S

OFFICE #2

RANGERS'S

OFFICE #1

RANGERS'S

AREA

COMMON

VESTIBULE

BATH

GUEST

KITCHEN

ROOM

MEETING

STORAGE

FILE

SHOWER

STAFF BATH/

STAIRS

OFFICE

SUPERVISOR'S

CORRIDOR

JAN

CLOSET

IT

COVERED PORCH

S-2

14x810x8 x

S-4

22x12

8Ø

10x610x6

S-1

S-1 x x

6Ø

8Ø

S-1

E-2

E-1

8Ø

8Ø

S-1

14x1014x12

6Ø

6Ø 6Ø 6Ø

6Ø

S-3

S-3

S-3

S-3

12x10 12x8 x

S-1

R-2

S-1 x

6Ø

E-3

E-1

8x6 x

8Ø

6Ø

R-3

R-3

10x8

8Ø

R-2

12x812x10

R-3

R-3

6Ø

6Ø

R-4

12x8 x

8x4

R-1

12x10

T-2

T-1

20x10

KH

6x6

AC

12x10

M-301

A4

M-301

H3

CUH-1

AHU-1

6Ø

8Ø

PLAN

NORTH

SCALE 1/8" = 1' - 0"

ATTIC MECHANICAL PLAN

K2

0 8'4' 16'

ATTIC

OPEN TO

BELOW

F1

M-501

L-1

PROVIDE

32x30

INSULATED

PLENUM

22x12

22x12

22x12

OA DN

3" BOILER

VENT DOWN

TO BASEMENT

ACCESS

DOOR

M-301

A4

M-301

H3

M

1. PROVIDE FOR DUCTWORK, PIPING, EQUIPMENT, AND FIXTURE SUPPORT FROM WOOD JOISTS AND TRUSSES.

2. COORDINATE WITH ELECTRICAL AND PLUMBING INSTALLERS TO AVOID CONFLICTS.

3. PROVIDE SUPPORT RODS PRIOR TO INSTALLATION OF AIR AND VAPOR BARRIER WHERE APPLICABLE.

4. PATCH AND RESTORE VAPOR AND AIR BARRIER.

5. PROVIDE DUCTS AND PIPES TIGHT TO CEILINGS TO MAXIMIZE CLEAR SPACE BELOW AS REQUIRED.

SUPPORT FROM WOOD JOIST AND TRUSSES DETAIL NOTES:

HORIZONTAL SCREW-IN FITTING.

BASIS OF DESIGN: SIMPSON

STRONG-TIE RWH 37200

THREADED ROD

SECTION AT HANGER SECTION AT DUCT SUPPORT

WOOD TRUSS, WOOD JOIST (TYP)

HORIZONTAL SCREW-IN FITTING.

BASIS OF DESIGN: SIMPSON

STRONG-TIE RWH 37200

THREADED ROD

HEX NUT AND HEX

LOCK NUT

NOT TO SCALE

SUPPORT FROM WOOD JOISTS AND TRUSSES DETAIL

L10

NOTE 3,4 NOTE 3,4

PRE-ENGINEERED METAL

CHANNEL OR ANGLE

US Army Corps of Engineers

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

A

B

C

D

E

F

G

H

J

K

L

M

N

P

SHEET ID

U S

A

R M

Y

C

O R

E

N G

I N

E E

R S

O T

T E

R

B

R O

K E

N E

W

O

P E

R A

T I O

F

I C

E

GENERAL SHEET NOTES:

1. FOR MECHANICAL SYMBOLS, LEGENDS, AND

ABBREVIATIONS REFER TO SHEET M-001.

2. VAPOR BARRIER AND GYPSUM AT BOTTOM OF CEILING

JOISTS IS NOT TO BE PUNCTURED, AND/OR DAMAGED

DURING INSTALLATION OF MECHANICAL SYSTEMS AND

DAMAGE MUST BE REPAIRED AT NO COST TO

GOVERNMENT.

3. INSTALL EQUIPMENT TO ALLOW MAINTENANCE ACCESS AS

REQUIRED BY EQUIPMENT MANUFACTURER'S WRITTEN

INSTRUCTIONS. PROVIDE MINIMUM 12" MAINTENANCE

CLEARANCE AT VALVES AND OTHER ACCESS LOCATIONS.

4. FOR DUCTWORK FABRICATION, HANGER AND SUPPORT

DETAILS REFER TO SHEETS M-501, M-502, AND M-503.

5. DUCTWORK PENETRATIONS THROUGH FIRE/SMOKE

WALLS/FLOORS/BARRIERS SHALL BE SEALED WITH FIRE

STOPPING ACCORDING TO DIVISION 7 REQUIREMENTS.

6. NO FLEXIBLE DUCT SHALL PASS THROUGH FIRE/SMOKE

WALLS/FLOORS/BARRIERS.

7. COORDINATE INSTALLATION WITH FIRE ALARM, PLUMBING,

MECHANICAL, AND ELECTRICAL TRADES.

KEYNOTES:

8x6 EA DN TO ERV-1.

20x10 RA DN TO AHU-1.

22x12 OA UP AND DOWN.

22x12 SA DOWN TO AHU-1.

3" BOILER COMBUSTION AIR AND EXHAUST UP THRU

ROOF. PROVIDE MANUFACTURERS VENT KIT AT ROOF

PENETRATION. PROVIDE INSULATION PER

MANUFACTURER RECOMMENDATIONS. COORDINATE

LOCATION WITH ARCHITECTURAL DRAWINGS.

LOUVER L-1, COORDINATE LOCATION WITH

ARCHITECTURAL DRAWINGS.

3" BOILER COMBUSTION AIR AND EXHAUST UP AND DOWN

IN CHASE.

PROVIDE MANUFACTURERS THRU WALL VENT WITH

EXHAUST KIT.

COORDINATE INSTALLATION OF KITCHEN HOOD WITH

KITCHEN CABINETS. REFER TO G11/AE740.

PROVIDE DUCT MOUNTED FIRE DAMPERS AT FIRST

FLOOR.

PROVIDE DUCT ACCESS PANEL FOR INSPECTION AND

MAINTENANCE OF FIRE DAMPERS. COORDINATE ACCESS

WITH CHASE ACCESS PANELS, REFER TO

ARCHITECTURAL DRAWINGS.

05 Nov, 2021 - 9:15am

C:\dfile\22004.09-MH101.dwg

F I R

T

O

R

T

I C

M E

C H

A N

I C

A L

P

L A

N S

OTTER BROOK

MH101

(THIS SHEET ONLY)

AutoCAD SHX Text T

AutoCAD SHX Text

RH

SCALE 1/4" = 1' - 0"

MECHANICAL SECTION 2

A4

0 4' 8'2'

PLAN

NORTH

SCALE 1/4" = 1' - 0"

MECHANICAL SECTION 1

H3

0 4' 8'2'

8x6 EA

8Ø RA

R-2

R-3

6Ø RA

8x6 EA

8x6 EA

AHU

ERV

SERVICE

CLEARANCE

SERVICE

CLEARANCE

30x32

INSULATED

PLENUM

L-2

12Ø EA

8x6 EA

12Ø OA

12Ø OA

(BEYOND)

22x12 OA

22x12 SA

FC

22x12 OA

20x10 RA

12Ø

EA

CU

ACCU

20x10 RA

(BEYOND)

8x6 EA

AHU

20x10 RA

22x12 OA

22x12 SA

FC

20x10 RA

12Ø OA

UH

FC

FC

12Ø OA

ROOM

MEETING

STORAGE

FILE

SHOWER

STAFF BATH/

OFFICE

SUPERVISOR'S

COVERED PORCH

S-2

S-1

S-1

E-1

8x10 SA

14x10 RA

10x20 RA10x12 RA

8x4 RA

16x12 SA

8x14 SA

8x6 SA

10x6 SA

12x22 SA

(BEYOND)

12x22 SA

(BEYOND)

12x8 RA

20x10 RA

12x10 RA

12x10 RA

22x12 OA

S-1

6x8 SA

6Ø EA

12x22 OA

10x6 SA8x6 SA

M-301

A4

M-301

H3

(BEYOND)

MH100,MH101

MH100,MH101

30x32

INSULATED

PLENUM

12Ø EA

12x22

10x20

22x12 SA

8x6 EA

RF

FC

FC

RF

(BEYOND)

US Army Corps of Engineers

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

A

B

C

D

E

F

G

H

J

K

L

M

N

P

SHEET ID

U S

A

R M

Y

C

O R

E

N G

I N

E E

R S

O T

T E

R

B

R O

K E

N E

W

O

P E

R A

T I O

F

I C

E

05 Nov, 2021 - 1:37pm

Y:\22004.09\22004.09-M301.dwg

M E

C H

A N

I C

A L

S E

C T

I O

N S

OTTER BROOK

M-301

GENERAL SHEET NOTES:

1. FOR MECHANICAL SYMBOLS, LEGENDS, AND ABBREVIATIONS REFER TO SHEET

M-001.

2. INSTALL EQUIPMENT TO ALLOW MAINTENANCE ACCESS AS REQUIRED BY

EQUIPMENT MANUFACTURER'S WRITTEN INSTRUCTIONS. PROVIDE MINIMUM 12"

MAINTENANCE CLEARANCE AT VALVES AND OTHER ACCESS LOCATIONS.

3. FOR DUCTWORK FABRICATION, HANGER AND SUPPORT DETAILS REFER TO

SHEETS M-501, M-502 AND M-503.

4. DUCTWORK AND PIPING PENETRATIONS THROUGH FIRE/SMOKE

WALLS/FLOORS/BARRIERS SHALL BE SEALED WITH FIRE STOPPING ACCORDING

TO DIVISION 7 REQUIREMENTS.

5. COORDINATE INSTALLATION WITH FIRE ALARM, PLUMBING, MECHANICAL PIPING

AND DUCTWORK, AND ELECTRICAL TRADES.

6. DUCTWORK AND PIPING ARE SHOWN DIAGRAMMATICALLY, EXACT LOCATION

SHALL BE DETERMINED IN THE FIELD. COORDINATE IN THE FIELD WITH

STRUCTURAL ELEMENTS.

AutoCAD SHX Text M

FLOW

CONCENTRIC TRANSITION

CONVERGING TEE

15°

15°

F L O

W

W

FLOW

45°FLOW

FLOW

45°

F L O

W

W

ECCENTRIC TRANSITION

DIVERGING TEE

30°

HWS

HWR

DRAIN VALVE

3/4" THREADED CAP

UNION (TYP)

NOT TO SCALE

RECTANGULAR DUCT TRANSITIONS DETAIL

K1

A2

MH100 NOT TO SCALE

COIL PIPING SCHEMATIC

K7

UNIT HEATER WATER

STRAINER

1. VALVES MUST BE SAME SIZE AS PIPE.

2. PROVIDE SPRING VIBRATION ISOLATORS FOR PUMP.

NOTES

PROVIDE

CONCENTRIC

REDUCER

WHERE

REQUIRED

CALIBRATED BALANCING

VALVE WITH POSITIVE

SHUTOFF

FLANGE

PRESSURE

GAUGE (TYP)

SPRING

VIBRATION

ISOLATORS

VERTICAL

INLINE

PUMP

AUTOMATIC

AIR VENT

SUSPENDED

UNIT HEATER

SHUTOFF

VALVE

CALIBRATED

BALANCING

VALVE WITH

POSITIVE

SHUTOFF

NOT TO SCALE

INLINE PUMP PIPING DETAIL

K16

SHUTOFF

VALVE

SILENT

CHECK VALVE

HWS & HWR PIPING FOR COIL

PIPING SCHEMATIC. SEE

HOT WATER PREHEAT COIL

W/ INSULATED DRAIN PAN

12" MOUNTING FRAME

SLOTTED ENGINEERED

CHANNEL, SECURED TO

FLOOR, GALVANIZED

OUTSIDE AIR INTAKE

MERV 13 FILTER

RETURN

AIR

SUPPLY FAN MOUNTED

ON SPRING VIBRATION

ISOLATORS

INSULATED WALL

CASING

FRONT

DISCHARGE

NOT TO SCALE

AHU AIR HANDLING UNIT DIAGRAM

B13

PITCH TO OUTSIDE

1/2" BIRDSCREEN

D

N

A2,K2

MH100,MH101 NOT TO SCALE

LOUVER CONNECTION DETAIL

F1

STORM

PROOF

DRAINABLE

LOUVER

CAULK ALL

AROUND

INSULATION-

EXTEND TO

ISOLATION

DAMPER

SOLDER JOINTS ON

BOTTOM OF DUCT AND

UP DUCT SIDES 12" MIN

AIR FLOW

BELLMOUTH FITTING WITH BUTTERFLY DAMPER. PROVIDE RIGID DUCT

FROM DAMPER TO DIFFUSER EXCEPT LAST 5 FEET MAY BE FLEX DUCT.

FOR CONNECTION TO ROUND MAIN DUCT PROVIDE CONICAL TEE OR WYE

NOT TO SCALE

DIFFUSER AND REGISTER RUNOUT DETAIL

F13

MAIN DUCT SUPPLY,

RETURN OR EXHAUST

PROVIDE 3" MIN HEIGHT

TRANSITION W/ ROUND

DUCT COLLAR

OBD INTEGRAL WITH

REGISTER WHERE

SCHEDULED

SQUARE/RECTANGULAR

REGISTER OR GRILLE

NYLON DRAW BAND

CONNECTION TO

DIFFUSER NECK

ROUND NECK DIFFUSER

ROUND FLEXIBLE

DUCT 90° MAXIMUM

FOR TOTAL BENDS

1. VALVES MUST BE SAME SIZE AS PIPE.

2. SHUT-OFF VALVES MAY BE BALL OR BUTTERFLY. REFER TO

SPECIFICATIONS FOR VALVE TYPE AND SIZE RESTRICTIONS.

3. PROVIDE UNIONS AND/OR FLANGES AS REQUIRED FOR FIT-UP AND

REMOVAL OF COIL.

NOTES

NOT TO SCALE

COIL PIPING SCHEMATIC

K11

AIR HANDLING UNIT HOT

FOR DUCT SIZES UP TO AND INCLUDING 10"Ø FOR DUCTS SIZES LARGER THAN 10"Ø

HANGER STRAP

BOLT

RADIANT PANELS SHALL BE

SUPPORTED INDEPENDENTLY OF

THE CEILING STRUCTURE (TYP)

SUPPORT WIRE

(TYP)

RADIANT PANEL

CROSS BRACE

1"-THICK

FIBERGLASS

INSULATION (TYP)

RADIANT PANEL

SAT CEILING

SUSPENSION

SYSTEM (SIM)

NOT TO SCALE

ROUND DUCT HANGER DETAIL

B1

NOT TO SCALE

RADIANT PANEL HANGING DETAIL

B7

MIN 1-1/4" WIDE x 12 GAUGE GALVANIZED STEEL

HANGER STRAP WITH NUTS ON BOTH SIDES OF CLAMP

MIN 1-1/4" WIDE x 12 GAUGE

GALVANIZED STEEL CLAMP

CLAMP SAME

SIZE AS

HANGER STRAP

MIN 3/8"Ø THREADED

RODS WITH NUTS ON

BOTH SIDES OF CLAMP

MIN 1-1/4" WIDE x 12

GAUGE GALVANIZED

STEEL SPLIT RING CLAMP

3/4 W

(MIN)

3/4 W

(MIN)

K11

M-501

SUPPLY

AIR

DX COOLING COIL

HWS

HWR

CONTROL

VALVE

STRAINER

BALL VALVE (TYP)

CALIBRATED BALANCING VALVE

RADIANT PANEL

FLEXIBLE HOSE CONNECTOR (TYP)

MANUAL AIR VENT INSTALLED AT

HIGH POINT

NOT TO SCALE

RADIANT PANEL PIPING SCHEMATIC

F7

STRAINER

A13

M-502

CONCRETE

HOUSEKEEPING PAD

ADJUSTABLE

STRAP-ON

AQUASTAT

(SET AT 100°F)

UNION (TYP)

DRAIN

HWR

HWS

SHUT-OFF VALVE

STRAINER

NC

CALIBRATED BALANCING VALVE

WITH POSITIVE SHUTOFF (TYP)

3-WAY MIXING VALVE

(3 PSI MAX PD)

BALANCE TO PROVIDE SAME

PRESSURE DROP AS COIL

AUTOMATIC

AIR VENT

THERMOMETER

IN WELL (TYP)

WATER COIL

SEAL AND CAULK

ALL AROUND

SPRING TYPE VIBRATION

ISOLATOR (TYP)

FIELD FABRICATED

MIXING BOX

US Army Corps of Engineers

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

A

B

C

D

E

F

G

H

J

K

L

M

N

P

SHEET ID

U S

A

R M

Y

C

O R

E

N G

I N

E E

R S

O T

T E

R

B

R O

K E

N E

W

O

P E

R A

T I O

F

I C

E

05 Nov, 2021 - 9:20am

C:\dfile\22004.09-M501.dwg

M E

C H

A N

I C

A L

D E

T A

I

OTTER BROOK

M-501

DOOR

STRUCTURE ABOVE

GRADE

5/8" INSULATED CONDENSATE

DRAIN TO MOP RECEPTOR

CENTER AC-1 ABOVE DOOR

CHECK VALVE

ISOLATION VALVE

WALL MOUNTED

EVAPORATOR FAN UNIT

CONDENSING

UNIT CU-1

REFRIGERANT LINES TO

ROOM UNIT AC-1, REFER TO

A2/MH100 FOR ROUTING

CONCRETE PAD

REFRIGERANT

LINES TO CU-1

REFRIGERANT PIPE

PENETRATIONS THRU WALL

IT CLOSET 105

EXTERIOR LOCATION

MANUFACTURERS

18" HIGH STAND

FASTEN STAND TO

CONCRETE PAD WITH

APPROPRIATE HARDWARE

AS-1

EXT-1

1/2"

HOSE BIBB W/ INTEGRAL

VACUUM BREAKER AND CAP

FOR FILLING SNOW MELT

SYSTEM

3/4" TO

FLOOR

DRAIN

3/4" MAKE-UP

WATER

CONNECTION

PRESSURE

REDUCING VALVE

LINE SIZED

BYPASS

A2

MH100 NOT TO SCALE

AIR CONTROL PIPING DIAGRAM

K4

A2

MH100 NOT TO SCALE

CABINET HEATER PIPING SCHEMATIC

K10

RPZ BACKFLOW

PREVENTER

3/4"

HIGH CAPACITY

AUTO AIR VENT

3/4"

HWS FROM

BOILER

3/4"

HWS TO SYSTEM

DRAIN VALVE WITH

3/4" THREADED CAP

AUTO AIR

VENT

4" THICK

CONCRETE

PAD

3/4"

EXPANSION TANK

MOUNT ON PAD

DRAIN VALVE

W/ HOSE BIBB

FLOOR

A2

MH100 NOT TO SCALE

BOILER HEATING SYSTEM DIAGRAM

F2

MOUNT UNIT AS HIGH

AS POSSIBLE WHILE

MAINTAINING

MANUFACTURER'S

REQUIRED

CLEARANCES

FILTER

DRAIN VALVE

UNION (TYP)

SHUTOFF VALVE

CEILING

RA

SA

HWR

HWS

FLOOR

MANUAL AIR VENT

CALIBRATED

BALANCING

VALVE

WITH

POSITIVE

SHUTOFF

3/4" THREADED CAP

LOCATE PIPING IN

WALL OR CHASE

INDICATED

WALL

FAN

ADJUSTABLE

STRAP-ON

AQUASTAT

(SET AT 100°F)

FLOOR

MOUNTED

CABINET

UNIT

HEATER

DRAIN LINE SIZE SHALL BE

MIN SIZE AS THE NIPPLE ON

THE DRAIN PAN

DRAIN PAN

SLOPE BOTTOM

OF PAN TO

DRAIN INLET

FLOOR

CLEAN

OUT

30"

PACKAGED FIRE

SUPPRESSION

SYSTEM WITH

STORAGE TANK

MOUNTED

INSIDE CABINET

NOTE

RECTANGULAR MAIN

RECTANGULAR MAIN

1. SPIN-IN TYPE STRAIGHT TAKE-OFF FITTINGS SHALL NOT BE PERMITTED.

ROUND

BRANCH

DUCT

BELLMOUTH

TAKE-OFF

FITTING

ROUND

BRANCH

DUCT

TRANSITION

RECTANGULAR

TO ROUND

TAKEOFF

AIRFLOW

RETURN

AIRFLOW

SUPPLY

NOT TO SCALE

RANGE HOOD DETAIL

F7

NOT TO SCALE

AHU-1 CONDENSATE PUMP DETAIL

A2

NOT TO SCALE

CONNECTIONS TO RECTANGULAR MAIN

A7

TYPICAL ROUND BRANCH DETAIL

CONDENSATE

PUMP

TO INDIRECT WASTE

FOR ROUTING

REFER TO MH100

INTEGRAL FAN WITH

THRU WALL DISCHARGE

COORDINATE

INSTALLATION HEIGHT

WITH ARCHITECTURAL

DRAWINGS

NOTES

FRONT VIEW SIDE VIEW

(4) 5/8" DIA EXPANSION

BOLTS W/ 3" EMBEDMENT

(TYP)

1-5/8", 12 GAUGE

COLD-FORMED STEEL

SLOTTED CHANNEL (TYP)

INTERMEDIATE STRUT (TYP)

ADJUST LOCATION TO SUIT

EQUIP BOLT DOWN

ARRANGEMENT.

FASTEN STRUT TO FRAME AND

AHU-1 OR ERV-1 TO STRUT.

1. SECURE POST BASE TO EXISTING CONCRETE PAD WITH MECHANICAL EXPANSION ANCHORS.

2. FASTENERS AND FITTINGS SHALL BE INSTALLED IN ACCORDANCE WITH THE MFG PRINTED INSTRUCTIONS.

OR

1/2" HEX HEAD BOLT

W/LOCKWASHER

AND NUT (TYP)

COLD-FORMED STEEL

2-WING FITTING (TYP)

1/4"x6"x6" COLD-FORMED

STEEL BASEPLATE (TYP)

COLD-FORMED STEEL

3-WING FITTING (TYP)

1" COLD-FORMED STEEL

KNEE BRACE (TYP)

OR

B13

M-501 NOT TO SCALE

PRE-ENGINEERED SLOTTED METAL EQUIPMENT FRAME DETAIL

A13

L6

SB502

(FOR PIPE 3" THROUGH 6")

ADJUSTABLE HANGER W/ROLLER

INSULATION

PIPE

(FOR PIPES 2 1/2" & SMALLER)

CLEVIS HANGER

PIPE

COVERING

PROTECTIVE

SADDLE

GALVANIZED

INSULATION

SHIELD 12"

LONG

LOCKING NUT

(TYP)

SUPPORT NUT

(TYP)

HEAVY-DUTY

CLEVIS

HANGER

NOT TO SCALE

PIPE HANGER ATTACHMENT DETAILS

K15

HWS

HWR

BOILER B-1

PRESSURE

RELIEF

LOW LOSS

HEADER

BUILDING CIRCULATION

PUMPS P-2A AND P-2B

FROM HEATING SYSTEM

TO HEATING SYSTEM

K16

M-501

FROM MAKE-UP WATER,

SEE AIR CONTROL PIPING

DIAGRAM

K4

M-502

G

FOR GAS SHUT-OFF

REFER TO

A11

P-601

THERMOMETER (TYP)

PRESSURE

GAUGE (TYP)

SHUTOFF

VALVE (TYP)

UNION (TYP)

K16

M-501

UNION (TYP)

DRAIN

VALVE (TYP)

D3

MP101 NOT TO SCALE

DUCTLESS SPLIT SYSTEM ELEVATION

F13

4" THICK CONCRETE

HOUSEKEEPING PAD

L6

SB502

4" THICK CONCRETE

HOUSEKEEPING PAD

L6

SB502

US Army Corps of Engineers

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

A

B

C

D

E

F

G

H

J

K

L

M

N

P

SHEET ID

U S

A

R M

Y

C

O R

E

N G

I N

E E

R S

O T

T E

R

B

R O

K E

N E

W

O

P E

R A

T I O

F

I C

E

05 Nov, 2021 - 9:21am

C:\dfile\22004.09-M502.dwg

M E

C H

A N

I C

A L

D E

T A

I

M-502

AutoCAD SHX Text

KH

AutoCAD SHX Text

AutoCAD SHX Text 45%%D

AutoCAD SHX Text

AHU

AutoCAD SHX Text

AutoCAD SHX Text

ERV

AutoCAD SHX Text

AutoCAD SHX Text

AHU

AutoCAD SHX Text

AutoCAD SHX Text

ERV

AutoCAD SHX Text

AutoCAD SHX Text P

FOR HORIZONTAL FLOOR INSTALLATION PROVIDE FIRE DAMPER WITH SPRING LOADED

DAMPER BLADES.

FASTEN ANGLES TO SLEEVE WITH POP-RIVETS, SCREWS OR WELDS AT 8-INCH ON

CENTER, MINIMUM 2 PER SIDE, 4 SIDES OF OPENING ON BOTH SIDES OF DAMPER.

PROVIDE CLEARANCE BETWEEN DAMPER SLEEVE OR DAMPER AND THE FIRE-RATED

WALL, PARTITION OR FLOOR IN ACCORDANCE WITH THE FIRE DAMPER MANUFACTURER.

IF REQUIRED BY THE DAMPER MANUFACTURER, PROVIDE FIRESTOPPING IN THIS SPACE

ON ALL SIDES TO MAINTAIN FIRE RATING.

USE FOR GALVANIZED SHEET METAL DUCT ONLY.

1.

2.

NOTES

3.

4.

A

A2-B2 (4" MIN

OR 12" MAX)

A

B

45°

B

A1-B1 (4" MIN OR 12" MAX)

SIZE AND RATING OF HANGERS AND SUPPORTS

SHALL BE PER LATEST SMACNA STANDARDS.

60" MAX DUCT

1" 1"

NOTE:

CHANNEL OR ANGLE

PREENGINEERED METAL

OVER 60" DUCT

THREADED

ROD

HANGER

HANGER

STRAP

NOT TO SCALE

DUCT SUPPORT ATTACHMENTS DETAIL

K2

NOT TO SCALE

REDUCING LATERAL

K13

ROUND DUCT-CONICAL

NOT TO SCALE

FIRE DAMPER DETAIL

E2

V

A

2" C

2"

A

2" C

2"

V

C D

L

L

L

O1 O2

2" (TYP)

A

B

B

OR 12" MAX)

A-B (1" MIN

A-B (1" MIN

OR 12" MAX)

REDUCING CONICAL TEECONICAL TEE

VEE FITTING CONCENTRIC REDUCER

NOT TO SCALE

TYPICAL ROUND DUCT FITTINGS DETAIL

K8

6" MAX

RETAINING

ANGLE (TYP)

UL LISTED TYPE B

FIRE DAMPER

FUSIBLE LINK

ASSEMBLY

RATED FOR

165°F

12x12 ACCESS

DOOR

UL APPROVED

FLOOR

DUCT

FACTORY SUPPLIED

THERMAL BLANKET

(4 SIDES, TYP)

6" MAX

RETAINING

ANGLE (TYP)

UL LISTED TYPE B

FIRE DAMPER

12x12 ACCESS

DOOR

DUCT

UL APPROVED

FLOOR

FUSIBLE LINK

ASSEMBLY

RATED FOR 165°F

FACTORY SUPPLIED

THERMAL BLANKET

(4 SIDES, TYP)

US Army Corps of Engineers

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

A

B

C

D

E

F

G

H

J

K

L

M

N

P

SHEET ID

U S

A

R M

Y

C

O R

E

N G

I N

E E

R S

O T

T E

R

B

R O

K E

N E

W

O

P E

R A

T I O

F

I C

E

05 Nov, 2021 - 9:24am

C:\dfile\22004.09-M503.dwg

M E

C H

A N

I C

A L

D E

T A

I

M-503

FUELUNIT NO NOTES

VOLTS/PHASE/AMPS

HOT WATER BOILER SCHEDULE

NOTES:

UNIT NO NOTESTYPE

DIFFUSER / REGISTER SCHEDULE

S-1 24x24 8Ø 0.1 <25 101-200 LAY-IN CEILING SUPPLY DIFFUSER PRICE SCD 1,2,3,6

NOTES

ENERGY RECOVERY VENTILATOR SCHEDULE

BASIS OF DESIGN

ERV-1 AHU-1 GREENHECK MINICORE-5215 1,2,3,4,5

SERVES

NOTE ON BASIS OF DESIGN

PRODUCTS OF OTHER MANUFACTURERS ARE ACCEPTABLE IF

THEY MEET THE OPERATIONAL REQUIREMENTS INDICATED. ANY

ADJUSTMENTS TO DUCTING, PIPING, WIRING OR CONFIGURATION

DUE TO THE SELECTION OF A MANUFACTURER OTHER THAN THAT

LISTED AS THE BASIS OF DESIGN WILL BE ACCOMPLISHED BY THE

CONTRACTOR AT NO ADDITIONAL EXPENSE TO THE GOVERNMENT.

GENERAL NOTE

TRANE BCHD05481.2/65.863.9 48.301520 460 4.9BUILDING HVAC 49.15 1.0 1,2,3,4140 120 230/1

AIR HANDLING UNIT SCHEDULE

GPM

DX COOLING COIL

TC MBH

CFMSERVESUNIT NO NOTES

ELECTRICAL

VOLTS/PHASEMBHLWTEWT

HEATING

SC MBH

AHU-1

HOT WATER UNIT HEATER SCHEDULE

GPM

LEAVING

WATER TEMP °F

ENTERING

CFM

UNIT NO

NOTES

VOLTS/PHASERPMHP

LOCATION

ELECTRICAL DATA

UH-1 BASEMENT 370 21.6 140 110 2.2 4.9 1/6 1075 120/1 MODINE LODRONIC HCH 22 1,2,3

NOTES:

1. INSTALL PER MANUFACTURERS WRITTEN INSTRUCTIONS.

2. PROVIDE WITH FINGER PROOF FAN GUARD.

3. HORIZONTAL SUSPENDED UNIT.

B-1

NOTES:

1. INSTALL PER MANUFACTURERS WRITTEN INSTRUCTIONS.

2. PROVIDE INJECTION PUMP. REFER TO PUMP SCHEDULE.

3. PROVIDE MANUFACTURERS STAINLESS STEEL VENTING WITH TERMINATION KITS FOR COMBUSTION AIR

AND FLUE VENT.

4. PROVIDE ACCESSORIES: SAFETY RELIEF VALVE, PRESSURE/TEMP GAUGES, CIRCULATOR HARNESS, LOW WATER CUT-OFF, MANUAL RESET HIGH LIMIT.

LPG 155 142 95.1 3" 3" 120/1/6.3

BASIS OF DESIGN

HTP EFT-155 1,2,3,4,5,6,7,8

SUPPLY

CFM

460 0.75

ESP

IN

WC

FAN

HP

1/4

EXHAUST

CFM

335 0.7

ESP

IN

WC

FAN

HP

1/4

ELECTRICAL

VOLTS/

PHASE

MCA

115/1 6.4

NOTES:

1. INSTALL PER MANUFACTURERS WRITTEN INSTRUCTIONS.

2. PROVIDE FIBER MEMBRANE CORE.

3. PROVIDE TIMED FROST CONTROL.

4. PROVIDE VARI-GREEN VARIABLE SPEED MOTOR.

5. PROVIDE INTEGRAL BACKDRAFT DAMPERS.

S-2

S-3

24x24

12x12

6Ø

6Ø

<25

<25

0-100

70-100

LAY-IN CEILING SUPPLY DIFFUSER

LAY-IN CEILING SUPPLY DIFFUSER

PRICE SCD

PRICE SCD

0.1

0.1

R-1 24x24 <25 251-360 PERFORATED RETURN GRILLE PRICE PDDR0.1 1,3,6

R-3 12x12

R-4 24x24

R-2 24x24 0.1

0.1

0.1

<25

<25

<25

100-250

65-90

0-100

PERFORATED RETURN GRILLE PRICE PDDR

PERFORATED RETURN GRILLE PRICE PDDR

PERFORATED RETURN GRILLE PRICE PDDR

E-2 24x24 0.1 <25 115 PERFORATED EXHUAST GRILLE PRICE PDDR 1,4,6

E-1 12x12 0.1 <2512x12 0-120 LOUVERED FACE EXHAUST GRILLE PRICE 530

RADIANT CEILING PANEL SCHEDULE

NOTES:

1. PROVIDE FULL TRIM ACCESSORIES AS REQUIRED.

2. COLOR AND FINISH SELECTION BY CONTRACTING OFFICER.

3. AVERAGE WATER TEMPERATURE BASED ON 140°F EWT AND 130°F LWT.

LOCATION

ELEMENT

PASSES SIZE

BASIS OF DESIGN NOTES

RP-1 4 135 STERLING RADIANT CEILING PANEL 1,2,3,4,5

RP-2 135

RP-3 135

RP-4 135

RP-5 135

RP-6 135

RP-7 135

RP-8 135

RP-9 135

RP-10 135

RP-11 135

RP-12 135

RP-13 135

RP-14B 135

RP-15 135

RP-16 135

RP-17 135

RP-18 135

NOTES

AIR CONDITIONING UNIT SCHEDULE

AC-1/CU-1

INDOOR UNIT

LOCATION

OUTDOOR

UNIT

LOCATION

CFM

MBH

MAX/MIN

VOLTS/PH

230/1

BASIS OF DESIGN

TRANE MITSUBISHI PKA-12HA7/PUY-A12NKA7GRADE 320-425 12/5.8IT CLOSET 105

NOTES:

1. INDOOR UNIT AC-1: PROVIDE WITH MANUFACTURER'S WIRED, WALL MOUNTED CONTROLLER.

2. COOLING ONLY UNIT.

3. OUTDOOR CONDENSING UNIT CU-1: PROVIDE 18" PRE-MANUFACTURED, GALVANIZED STEEL,

MODULAR EQUIPMENT SUPPORT FRAME WITH EQUIPMENT CLAMPS FOR INSTALLATION.

1,2,3,4,5,6

ELECTRICAL

AC

MCA

CU

MCA

CU

MOCP

11 28

COMMON 103

RANGER 106

RANGER 109

RANGER 112

RANGER 113

RANGER 113

SUPER 111

SUPER 111

FILE 104

MEETING 114

MEETING 114

KITCHEN 115

KITCHEN 115

VESTIBULE 101

GUEST BATH 116

STAFF BATH 110

CORRIDOR 102

CORRIDOR 102

24"Wx8'-0"L

24"Wx6'-0"L

24"Wx6'-0"L

24"Wx6'-0"L

24"Wx4'-0"L

24"Wx5'-0"L

24"Wx7'-0"L

24"Wx7'-0"L

24"Wx12'-0"L

24"Wx10'-0"L

24"Wx12'-0"L

STERLING RADIANT CEILING PANEL

STERLING RADIANT CEILING PANEL

STERLING RADIANT CEILING PANEL

STERLING RADIANT CEILING PANEL

STERLING RADIANT CEILING PANEL

STERLING RADIANT CEILING PANEL

STERLING RADIANT CEILING PANEL

STERLING RADIANT CEILING PANEL

STERLING RADIANT CEILING PANEL

STERLING RADIANT CEILING PANEL

STERLING RADIANT CEILING PANEL

STERLING RADIANT CEILING PANEL

STERLING RADIANT CEILING PANEL

STERLING RADIANT CEILING PANEL

STERLING RADIANT CEILING PANEL

STERLING RADIANT CEILING PANEL

STERLING RADIANT CEILING PANEL

24"Wx6'-0"L

24"Wx6'-0"L

24"Wx6'-0"L

24"Wx5'-0"L

24"Wx5'-6"L

24"Wx5'-0"L

24"Wx14-0"L

SERVES

ELECTRICAL

MCA

NOTES

AIR COOLED CONDENSING UNIT SCHEDULE

VOLTS/PHASE

ACCU-1 AHU-1 5 410A - 2 230/1 37 60 1,2,3,4,5

BASIS OF DESIGN

TRANE 4TTR7060A

NOTES:

1. 2-STAGE COMPRESSOR.

2. PROVIDE RUBBER ISOLATOR KIT.

3. OUTDOOR DESIGN TEMP 95°F.

4. PROVIDE PRE-INSULATED REFRIGERANT LINESET.

5. PROVIDE SERVICE VALVE PANEL COVER.

OA

CFM

RA

CFM

EAT

DB/WB

MOTOR

POWER (HP)

BASIS OF

DESIGN

NOMINAL

CAPACITY

TONS

REFRIG

TYPE

EER

FULL

LOAD

CAPACITY

STEPS

HEATING

MBH

MAX PRESSURE

DROP IN WC

BASIS OF

DESIGN

AIR

INTAKE

GAS

VENT

MINIMUM

EFFICIENCY

CAPACITY

MBH

INPUT

MBH

UNIT

NO

INSTALLED

WEIGHT

LBS

MAX

PRESSURE

DROP IN

WC

MAX

NOISE

CRITERIA

CFM

RANGE

NECK

SIZE

IN

FACE

SIZE

IN

BASIS OF DESIGN

UNIT

NO

UNIT

NO

UNIT

NO

LOUVER SCHEDULE

DIMENSIONS

UNIT NO TYPESERVES

HEIGHT

CFM

WIDTH DEPTH

NOTES

DENLAR D1000 SERIESKH-1

UNIT NO

KITCHEN 115

SERVES

RANGE HOOD SCHEDULE

140-250

CFM

0.2

NOTES

1,2,3,4,5,6,7

NOTES:

1. INSTALL PER MANUFACTURER'S WRITTEN INSTRUCTIONS AND CLEARANCE REQUIREMENTS.

2. PROVIDE WET CHEMICAL FIRE SUPPRESSION SYSTEM. FIRE SUPPRESSION AGENT MUST NOT

CONTAIN CHEMICALS THAT ARE CLASSIFIED AS REFRIGERANTS.

3. PROVIDE WITH INLINE FAN WITH REAR DISCHARGE.

4. PROVIDE WITH THRU-WALL EXHAUST AND VENT KIT.

120/130"

SP

IN

WC

HOOD

DEPTH

19.3" 10.5" 60

HOOD

LENGTH

HOOD

HEIGHT

WEIGHT

(LBS)

VOLTS/

PHASE

BASIS OF DESIGN

MIN FREE AREA

SQUARE FT

BASIS OF DESIGN

L-1

L-2

OA INTAKE

EXHAUST AIR

1,2,3,4,5

1,2,3,4,5

1,2,3,4,5

1,2,3,5

1,2,3,5

1,2,3,5,6

1,2,3,4,5,6

1,2,3,4,5

1,2,3,4,5

1,2,3,5

1,2,3,4,5

1,2,3,5

1,2,3,4,5

1,2,3,4,5

1,2,3,4,5

1,2,3,4,5

1,2,3,4,5

4. PROVIDE SAME END PIPING.

5. MOUNT RADIANT PANEL IN ACCORDANCE WITH MANUFACTURER'S WRITTEN INSTRUCTIONS.

6. PROVIDE 3-WAY MIXING VALVE AT PANEL INDICATED.

INTAKE 1520 30" 32" 6" 3.5 RUSKIN ELF 6375 DX 1,2,3

EXHAUST 1400 30" 32" 6" 3.5 RUSKIN ELF 6375 DX

NOTES:

1. PROVIDE FIXED DRAINABLE BLADES, SELF FLASHING.

2. PROVIDE WIRE MESH BIRDSCREEN.

1. COLOR; WHITE.

2. PROVIDE 4-WAY THROW.

3. MOUNTING FRAME FOR INSTALLATION IN SAT CEILING.

4. MOUNTING FRAME FOR INSTALLATION IN GYP BOARD CEILING.

T-1 24x24 6x6 <25 85-150 PERFORATED TRANSFER GRILLE PRICE PDDR0.1

1,2,3,6

1,2,3,6

1,3,6

1,3,6

1,3,6

1,5,6,7,8,9

1,3,6

3. PROVIDE FINISH IN MANUFACTURER'S STANDARD COLOR SELECTED BY ARCHITECT.

1,2,3

1.0

ESP

IN

WC

PANEL

MBUTH

1.9

1.42

1.42

1.42

1.3

1.19

0.95

1.19

1.19

2.38

2.85

2.85

3.33

AVG

WATER TEMP

PANEL

CAPACITY

BUTH/LF

ROOM

MBUTH

4.5

1.9

1.2

1.2

1.2

1.9

3.2

2.2

5.7

2.5

1.0

1.3

1.42

1.42

1.66

1.66

1.42

NOTES:

1. INSTALL PER MANUFACTURERS WRITTEN INSTRUCTIONS.

2. PROVIDE 2" PLEATED MERV-13 FILTERS.

3/4"

GAS

CONNECTION

5. PROVIDE OUTDOOR AIR SYSTEM TEMPERATURE SENSORS.

6. PROVIDE CONDENSATE ACID NEUTRALIZATION KIT.

7. PROVIDE BOILER MANUFACTURER RACKING SYSTEM.

8. PROVIDE DDC INTERFACE EQUIPMENT AND PROGRAMMING.

5. PROVIDE WITH ELECTRICAL STOVE SHUT-OFF CONTROL MODULE.

6. RANGE HOOD TO BE INSTALLED IN ACCORDANCE WITH NFPA REQUIREMENTS.

7. PROVIDE MANUAL PULL STATION FOR FIRE SUPPRESSION SYSTEM.

WEIGHT

LBS

5. PROVIDE WITH INTEGRAL OPPOSED BLADE DAMPER.

6. PROVIDE TRANSITION FROM DUCTWORK TO DIFFUSER/GRILLE.

7. SURFACE MOUNTED.

8. 3/4" BLADE SPACING, 45-DEG DEFLECTION.

9. BLADE PARALLEL TO LONG DIMENSION.

4. OUTDOOR CONDENSING UNIT CU-1: PROVIDE LOW AMBIENT WIND BAFFLES FOR

OPERATION DOWN TO -20°F.

5. STANDARD OPERATION DESIGN TEMPERATURE -20°F TO 95°F. INDOOR UNIT AC-1 USER

ADJUSTED THERMOSTAT TO BE SET TO IT/DATA EQUIPMENT RECOMMENDED SETPOINT.

6. CONDENSATE DRAIN SHALL BE INSTALLED TO DRAIN BY GRAVITY.

3. PROVIDE HORIZONTAL TYPE WITH INLET AND OUTLET DUCT COLLAR.

4. PROVIDE DRAIN PAN FLOAT SWITCH.

S-4 24x24 8Ø <25 101-200 LAY-IN CEILING SUPPLY DIFFUSER PRICE SCD0.1 1,2,4,6

T-2 24x24 <25 PERFORATED TRANSFER GRILLE PRICE PDDR0.1 1,4,685-1506x6

8Ø

8Ø

6Ø

6Ø

10Ø

E-3 12x12 0.1 <2512x12 0-100 LOUVERED FACE EXHAUST GRILLE PRICE 530 1,6,7,8,9

RP-14A 135VESTIBULE 101 STERLING RADIANT CEILING PANEL24"Wx7'-0"L 1,2,3,4,5238

3.0

4 1.66

52.2/51.6

LAT

DB/WB

R-410A

REFRIG

TYPE

MOP

CONDENSER FAN(S)

QTY

1 1/4 1.3

FAN

HP EA

FLA

EA

COMPRESSOR(S)

QTY

1 28.8 152.9

FLA

EA

RLA

EA

US Army Corps of Engineers

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

A

B

C

D

E

F

G

H

J

K

L

M

N

P

SHEET ID

U S

A

R M

Y

C

O R

E

N G

I N

E E

R S

O T

T E

R

B

R O

K E

N E

W

O

P E

R A

T I O

F

I C

E

05 Nov, 2021 - 9:26am

C:\dfile\22004.09-M601.dwg

M E

C H

A N

I C

A L

S C

H E

D U

L E

S

M-601

NOTE ON BASIS OF DESIGN

PRODUCTS OF OTHER MANUFACTURERS ARE ACCEPTABLE IF

THEY MEET THE OPERATIONAL REQUIREMENTS INDICATED. ANY

ADJUSTMENTS TO DUCTING, PIPING, WIRING OR CONFIGURATION

DUE TO THE SELECTION OF A MANUFACTURER OTHER THAN THAT

LISTED AS THE BASIS OF DESIGN WILL BE ACCOMPLISHED BY THE

CONTRACTOR AT NO ADDITIONAL EXPENSE TO THE GOVERNMENT.

GENERAL NOTE

EXPANSION TANK SCHEDULE

LOCATION

LOCATION

NOTES:

NOTES:

UNIT NO

UNIT NO TYPE

AIR SEPARATOR SCHEDULE

NOTES

DIMENSIONS NOTES

EXT-1

AS-1

SERVES

SERVES

BASEMENT HEATING SYSTEM 12 GAL 39"x16" TACO CBX84-125 1,2

BASEMENT HEATING SYSTEM TANK 17 0.15 - TACO-ACT02 1

PUMP SCHEDULE

UNIT NO SERVES TYPE GPM

MOTOR DATA

HP RPM VOLTS/PHASE

NOTES

BHP

BASIS OF

DESIGN

BASIS OF

DESIGN

ACCEPTANCE

VOLUME

CAPACITY

(GPM)

PRESSURE

DROP (FT)

STRAINER

FREE AREA

(SQ IN)

TOTAL

HEAD

PUMP

EFF(%)

SUCTION/

DISCHARGE (IN)

BASIS OF

DESIGN

P-1

P-2A

1. PRE-CHARGED TO 40 PSI.

2. VERTICAL TANK CONFIGURATION.

1. PROVIDE WITH STRAINER.

BOILER INJECTION IN-LINE 14.6 10FT - 1/8 3250 115/1 TACO IL0012 2

HEATING SYSTEM IN-LINE 17.8 25FT 38% 0.28 1/2 1760 208/1

1-1/2" / 1-1/2"

TACO 1915 1,6

NOTES:

1. PROVIDE ORIENTATION FOR HORIZONTAL MOUNTING.

2. PROVIDE INTEGRAL CHECK VALVE.

3. SPARE/LAG PUMP.

HOT WATER CABINET UNIT HEATER SCHEDULE

CFM

UNIT NO

LOCATION

ENTERING

WATER TEMP °F

GPM

LEAVING VOLTS/PHASE

HP

RPM

FAN DATA

NOTES

1,2,3,4STERLING F-02120/11/1510500.151201401.55.7230STAIR 107CUH-1

HEATING

MBH

PD FT

WC

BASIS OF

DESIGN

NOTES:

1. PROVIDE CABINET ENCLOSURE WITH TOP DISCHARGE AND FLOOR INLET CONFIGURATION.

2. COLOR BY ARCHITECT.

3. 1-ROW HEATING HOT WATER COIL.

DESIGN CONDITION SCHEDULE

NOTES:

LOCATION NOTES

ROOM

NO

INDOOR COOLING

DESIGN TEMP °F

VESTIBULE

CORRIDOR

COMMON AREA

FILE STORAGE

IT CLOSET

RANGERS OFFICE #1

STAIRS

JAN

STAFF BATH/SHOWER

SUPERVISORS OFFICE

RANGERS OFFICE #2

RANGERS OFFICE #3

RANGERS OFFICE #4

MEETING ROOM

KITCHEN

GUEST BATH

OUTDOOR COOLING

DESIGN TEMP °F

INDOOR HEATING

DESIGN TEMP °F

OUTDOOR HEATING

DESIGN TEMP °F

85.7

85.7

85.7

85.7

85.7

85.7

85.7

85.7

85.7

85.7

85.7

85.7

85.7

85.7

85.7

85.7

-2.1

-2.1

-2.1

-2.1

-2.1

-2.1

-2.1

-2.1

-2.1

-2.1

-2.1

-2.1

-2.1

-2.1

-2.1

-2.1

CONTROL VALVE SCHEDULE

NOTES

AHU-1

RADIANT PANELS

CUH-1

QTY

EQUIPMENT

SERVED

LOCATION SERVICE TYPE ACTION

WATER VALVES

GPM SIZING

FAIL POSITION

UH-1

BASEMENT 001

BASEMENT 001

STAIR 107

VARIOUS

HOT WATER

HOT WATER

HOT WATER

HOT WATER

3-WAY

2-WAY

2-WAY

2-WAY

MODULATING

2-POSITION

2-POSITION

2-POSITION

4.88

NOTE 1

2.2

1.5

3 PSID WPD MAX

LINE SIZE

LINE SIZE

LINE SIZE OPEN

OPEN

OPEN

OPEN

NOTES:

1. REFER TO RADIANT CEILING PANEL SCHEDULE ON M-601.

DUCTWORK CONSTRUCTION AND LEAKAGE TESTING SCHEDULE

SUPPLY

DUCT

DUCT PRESSURE CLASS

INCHES OF WATER COLUMN

RETURN

DUCT

EXHAUST

DUCT

OUTSIDE

AIR

DUCT

SUPPLY

ROUND/OVAL RECTANGULAR

DUCT

SEAL

CLASS

DUCT

SEAL

CLASS

DUCT

LEAK

CLASS

DUCT

LEAK

CLASS

DUCT

SEAL

CLASS

DUCT

LEAK

CLASS

RETURN/

OUTSIDE AIR

DUCT TEST

PRESSURE:

INCHES OF

WATER

COLUMN

SYSTEM

ERV-CONSTANT

VOLUME

SYSTEM

DUCTED BLOWER

COILS

2 - - - - -

NOTES

A 8 A 16 2.0 1

- -2 - - - - - - 2.0 1

- 2 - - - - - 2.0 1

- - - - - - 2.0 1

2 - - - - -A 8 A 16 2.0 1

-1 - - - - - - 2.0 1

-2

A 16

A 16

A 16

A 16

NOTES:

1. PROVIDE DUCT AIR LEAKAGE TESTING IN ACCORDANCE WITH SPECIFICATION SECTION 23 05 93 TESTING, ADJUSTING, AND BALANCING FOR

HVAC AND THE PROCEDURES IN SMACNA HVAC AIR DUCT LEAKAGE TEST MANUAL. DUCTWORK SHALL BE LEAK TESTED IN ACCORDANCE WITH

ITS DUCT PRESSURE CLASS, NOT ITS DUCT SEAL CLASS.

DESIGN CONDITION SCHEDULE

LOCATION

ROOM

NO

AREA

(SF)

VESTIBULE

CORRIDOR

COMMON AREA

FILE STORAGE

IT CLOSET

RANGERS OFFICE #1

STAIRS

JAN

STAFF BATH/SHOWER

SUPERVISORS OFFICE

RANGERS OFFICE #2

RANGERS OFFICE #3

RANGERS OFFICE #4

MEETING ROOM

KITCHEN

GUEST BATH

DESIGN

OCCUPANCY

DENSITY

PEOPLE OA

RATE CFM/

PERSON

AREA OA

RATE

CFM/FT

MIN

AIRFLOW

AREA OA

CFM

BREATHING

ZONE OA

(PEOPLE+

AREA) CFM

AIR

DISTRIBUTION

EFFECTIVENESS

SPACE OA

(CORRECTED

PEOPLE+

AREA) CFM

REQUIRED

EA

AIRFLOW

RATE

REQUIRED

EA

MINIMUM

CFM

DESIGN

SUPPLY

AIR CFM

DESIGN

OUTSIDE

AIR CFM

DESIGN

RETURN

AIR CFM

DESIGN

EXHUAST

AIR CFM

0.06

0.12

1.0

1.0/SF

70/FIXT

0.3/SF

7070/FIXT

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

0.06

0.06

0.06

0.06

0.06

0.06

0.06

0.06

7.5

5.0

5.0

5.0

5.0

5.0

5.0

5.0

5.0

P-2B HEATING SYSTEM IN-LINE 17.8 25FT 38% 0.28 1/2 1760 208/1 TACO 1915 1,3

001 BASEMENT - 85.7 -2.140

CP-1 AHU-1 DX COND. CENTRIFUGAL <10 10FT - - 1/30 1795 115/1 1" / 1/2" VCC-20ULS 2,4,5

CP-2 B-1 CONDENSATE <10 10FT - - 1/30 1795 115/1 2,4,5CENTRIFUGAL 1" / 1/2" VCC-20ULS

4. PROVIDE 6'-0" CORD.

5. BASIS OF DESIGN VCC-20ULS PART #554200.

6. ACTIVE/LEAD PUMP.

2 HOT WATER 3-WAY 2-POSITION LINE SIZE CLOSEDRADIANT PANELS NOTE 1

4. PROVIDE FINISH IN MANUFACTURER'S STANDARD COLOR

SELECTED BY ARCHITECT.

SUPERVISOR 111,

STAFF BATH 110

1-1/2" / 1-1/2"

1-1/2" / 1-1/2"

SERVESUNIT NO NOTES

HP

PHASE

VOLTS/

SONES

TYPE RPM

FAN FAN

DESIGN

BASIS OF

TYPE

DRIVE

CFM

IN WC

ESP

RF-1 AHU-1 1060 0.7 DIRECT INCLINE 1368 8.0 1/2 115/1 GREENHECK SQ-120-VG 1,2,3

NOTES:

A,B

ACCESSORIES

FAN SCHEDULE

1. PROVIDE COMPANION FLANGES FOR INLET AND OUTLET DUCT CONNECTIONS.

2. PROVIDE TWO SIDED ACCESS PANELS.

3. MANUFACTURER MOUNTED DISCONNECT SWITCH.

ACCESSORIES:

A. MFR FAN MOUNTED DISCONNECT SWITCH.

B. NEOPRENE VIBRATION ISOLATORS.

US Army Corps of Engineers

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

A

B

C

D

E

F

G

H

J

K

L

M

N

P

SHEET ID

U S

A

R M

Y

C

O R

E

N G

I N

E E

R S

O T

T E

R

B

R O

K E

N E

W

O

P E

R A

T I O

F

I C

E

05 Nov, 2021 - 9:27am

C:\dfile\22004.09-M602.dwg

M E

C H

A N

I C

A L

S C

H E

D U

L E

S

M-602

HWR

HWS

DP

EA

OA

EA

ERV SUPPLY FAN START/STOP

ERV SUPPLY FAN STATUS 1

X X X

XX XX

ERV EXHAUST FAN START/STOP

ERV EXHAUST FAN STATUS 1

X X X

XX XX

ERV OUTSIDE AIR DAMPER

X X X

ERV EXHAUST AIR DAMPER

X X X

SA

CS

CS

ERV EA DAMPER

ERV EXHAUST AIR TEMPERATURE 4

XXX X

ERV SUPPLY AIR TEMPERATURE 5

XXX X

ERV RETURN AIR TEMPERATURE

XX X

ERV RETURN AIR FILTER SWITCH 3

XX XX

ERV OUTSIDE AIR FILTER SWITCH 3

XX XX

OCCUPANT OVERRIDE ENABLE

XXX

T

BLOWER COIL UNIT (AHU-1) AND ERV-1 POINTS LIST

NOTES:

AHU FAN START/STOP

AHU FAN STATUS CURRENT SENSOR 1

SUPPLY AIR TEMPERATURE 2

H

C

CS

HWS

HWR

DX COOLING STAGE 1

D X

RL

RS

HEATING COIL CONTROL VALVE

DX COOLING STAGE 2

ERV SUPPLY AIR

TEMPERATURE

SENSOR

SUPPLY FAN

CURRENT SENSOR

RA FILTER

SWITCH

SUPPLY FAN

START/STOP

ERV EXHAUST AIR

TEMPERATURE

SENSOR

EXHAUST FAN

START/STOP

EXHAUST AIR FAN

EXHAUST FAN

CURRENT SENSOR

OA FILTER

SWITCH ERV OA

DAMPER

ERV RETURN AIR

TEMPERATURE

SENSOR

T

M

M

T

DP

SCALE: N.T.S.

TYPICAL CABINET UNIT HEATER CONTROL DIAGRAM (NON-DDC)

H14

SEQUENCE OF OPERATION

ON CALL FOR HEAT FROM THE THERMOSTAT, (50°F

ADJUSTABLE) THE FAN SHALL RUN.

WALL MOUNTED LINE

VOLTAGE THERMOSTAT WITH

TAMPERPROOF GUARD

T

SCALE: N.T.S.

BLOWER COIL UNIT (AHU-1) AND ERV-1 CONTROL DIAGRAM

A4

B I N

A R

Y

O

U T

P U

T

A N

A L O

G

I N

P U

T

A N

A L O

G

O

U T

P U

T

B I N

A R

Y

I N

P U

T

B I N

A R

Y

V

A R

I A

B L E

A N

A L O

G

V

A R

I A

B L E

T R

E N

D

L O

G

G R

A P

H I C

A L A

R M

SYSTEM

POINT

DESCRIPTION

NOTES

SEQUENCE OF OPERATION

THE OCCUPIED AND UNOCCUPIED MODES SHALL BE DETERMINED BY A

USER ADJUSTABLE 24-HOUR/7-DAY SCHEDULE THAT IS ACCESSIBLE TO

THE BUILDING OPERATOR THROUGH THE GUI.

OCCUPIED MODE: DURING THE OCCUPIED MODE THE AHU-1 SUPPLY FAN,

RETURN FAN AND ERV SUPPLY AND EXHAUST FANS SHALL RUN

CONTINUOUSLY. THE ERV OUTSIDE AND EXHAUST AIR DAMPERS,

BUILDING OUTSIDE AIR DAMPER AND AHU-1 RETURN AIR DAMPER SHALL

REMAIN OPEN. AHU-1 OUTSIDE AIR DAMPER SHALL REMAIN CLOSED.

HEATING MODE: THE DX COOLING SHALL REMAIN OFF AND THE HEATING

COIL CONTROL VALVE SHALL MODULATE TO MAINTAIN THE SUPPLY AIR

TEMPERATURE SET POINT, ACCORDING TO THE FOLLOWING, BUILDING

OPERATOR ADJUSTABLE, RESET SCHEDULE;

OUTSIDE AIR TEMP SUPPLY AIR SET POINT

60 DEF F 60 DEG F

40 DEG F 68 DEG F

COOLING MODE: THE HEATING COIL CONTROL VALVE SHALL REMAIN

CLOSED AND THE DX COOLING SHALL REMAIN ON UNTIL THE ZONE

TEMPERATURE IS SATISFIED. THE COMPRESSOR SHALL START WHEN

THERE IS A CALL FOR COOLING AND STOP WHEN THE TEMPERATURE IS

SATISFIED.

ECONOMIZER MODE: THE ECONOMIZER MODE SHALL BE ENABLED

WHENEVER THE OUTSIDE AIR ENTHALPY IS 10 PERCENT (OR MORE

ADJUSTABLE) BELOW THE RETURN AIR ENTHALPY, THE OUTSIDE AIR

TEMPERATURE IS BELOW 60°F (ADJUSTABLE), AND THERE IS A CALL FOR

COOLING. OTHERWISE ECONOMIZER COOLING SHALL BE DISABLED.

DURING THE ECONOMIZER MODE THE ERV SUPPLY FAN SHALL REMAIN

OFF. THE ERV OUTSIDE AIR DAMPER SHALL BE CLOSED AND THE DX

COOLING SHALL BE OFF. THE AHU OUTSIDE AIR, RETURN AIR, AND RELIEF

DAMPERS SHALL ACT IN UNISON AS A MIXED AIR DAMPER (RA DAMPER

SHALL CLOSE AS THE OA AND RELIEF DAMPERS OPEN) AND SHALL

MODULATE TO MAINTAIN THE SUPPLY AIR ECONOMIZER COOLING

SETPOINT, 55°F (ADJUSTABLE).

UNOCCUPIED MODE: DURING UNOCCUPIED MODE THE AHU-1 SUPPLY

FAN, RETURN FAN AND ERV SUPPLY AND EXHAUST FANS SHALL REMAIN

OFF, THE DX COOLING SHALL REMAIN OFF, AND THE HEATING COIL

CONTROL VALVE SHALL REMAIN CLOSED IF THE OUTSIDE TEMPERATURE

IS ABOVE 35°F (ADJUSTABLE). IF THE OUTSIDE AIR TEMPERATURE FALLS

BELOW 35°F (ADJUSTABLE) THEN THE HEATING COIL CONTROL VALVE

SHALL REMAIN 10% (ADJUSTABLE) OPEN TO HELP PREVENT FREEZING.

THE OUTSIDE AIR, EXHAUST AIR AND RELIEF AIR DAMPERS SHALL REMAIN

CLOSED.

SAFETY: THE LOW TEMPERATURE THERMOSTAT (FREEZESTAT), WHICH

SHALL BE SERPENTINED ACROSS THE DOWNSTREAM FACE OF THE

HEATING COIL, SHALL STOP THE SUPPLY AND EXHAUST FANS, CLOSE THE

LOUVER OUTSIDE AIR, RELIEF AIR AND ERV EXHAUST AIR DAMPERS IF THE

COIL DISCHARGE TEMPERATURE FALLS BELOW 38°F. THE DX COOLING

SHALL BE DISABLED, AND THE HEATING COIL CONTROL VALVE SHALL BE

FULLY OPEN.

1. GENERATE AN ALARM IF FAN FAILS TO SHOW PROOF OF OPERATION.

2. GENERATE AN ALARM IF THE ROOM TEMPERATURE FALLS BELOW 60°F (ADJUSTABLE).

3. GENERATE ALARM IF FILTER SWITCH PRESSURE DROP EXCEEDS 0.75 IN H2O.

4. GENERATE ALARM IF TEMPERATURE FALLS BELOW 15°F.

5. GENERATE ALARM IF TEMPERATURE IS NOT ±5°F OF SET POINT.

S

S

T

FAN STATUS

CURRENT

SENSOR

FAN

START/STOP

FILTER

RA

FROM

BLDG

HEATING COIL

CONTROL VALVE

SA TO

BUILDING

SUPPLY AIR

TEMPERATURE

LT

FREEZESTAT

FILTER SWITCH

LOW TEMPERATURE FREEZESTAT

FILTER SWITCH

DP

OA

FROM

ERV

AHU RA DAMPER

M

S

S

RELIEF

DAMPER

M

EXHAUST

LOUVER

S

S

M

AHU OA

DAMPER

MIXING

BOX

RH

RHT

WALL MOUNTED

SPACE

TEMPERATURE

SENSOR

WALL MOUNTED

SPACE RELATIVE

HUMIDITY SENSOR

BUILDING OA

DAMPER

M

OUTSIDE

AIR

LOUVER

SPACE TEMPERATURE SENSOR

XX X

SPACE RELATIVE HUMIDITY SENSOR

XX X

RETURN AIR RELATIVE HUMIDITY SENSOR

XX X

AHU-1 OUTSIDE AIR DAMPER

BUILDING OUTSIDE AIR DAMPER

RETURN AIR

RELATIVE

HUMIDITY

SENSOR

AFMS

OUTSIDE AIRFLOW

MEASURING STATION.

INSTALL NEAR ATTIC

ACCESS DOOR

AHU-1 RETURN AIR DAMPER

OUTSIDE AIRFLOW MEASURING STATION

X

X X X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

RELIEF AIR DAMPER XX X

SCALE: N.T.S.

DIRECT DIGITAL CONTROL SYSTEM ARCHITECTURE

B14

CONTROL UNIT

HEATING HOT

WATER SYSTEM

CONTROL UNIT

AHU-1/ERV-1

METAL ENCLOSURE

W/ KEYED LOCK

JACE

DATA COMMUNICATIONS

PORT FOR LAPTOP

LCU-101 LCU-102 LCU-1XX

PROVIDE LOCAL CONTROL UNITS

AS REQUIRED TO CONTROL

RADIANT CEILING PANELS.

MOUNT CONTROLLERS ON WALL

ABOVE FIRST FLOOR CEILING

LOCAL CONTROL

UNIT (TYP)

METAL ENCLOSURE

W/ KEYED LOCK

CONTROL SYSTEM NON-IP

COMMUNICATION

NETWORK WIRING

ERV

AHU

RETURN FAN START/STOP

RETURN FAN STATUS CURRENT SENSOR 1X

X

X

X

X

X

X

CS

S

S

FAN STATUS

CURRENT

SENSOR

FAN

START/STOP

RF

US Army Corps of Engineers

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

A

B

C

D

E

F

G

H

J

K

L

M

N

P

SHEET ID

U S

A

R M

Y

C

O R

E

N G

I N

E E

R S

O T

T E

R

B

R O

K E

N E

W

O

P E

R A

T I O

F

I C

E

05 Nov, 2021 - 10:26am

Y:\22004.09\22004.09-M701.dwg

C O

N T

R O

L

D I A

G R

A M

S

OTTER BROOK

M-701

DRAWING NOTES:

1. ALARMS SHALL BE RECORDED AND STORED IN THE JACE

AND SHALL BE ANNUNCIATED ON THE GRAPHICAL USER

INTERFACE (GUI) WHEN CONNECTED.

2. SETTING, MODES, AND SET POINTS THAT ARE INDICATED

AS BEING ADJUSTABLE SHALL BE ADJUSTABLE BY THE

BUILDING OPERATORS THROUGH THE GUI WITHOUT THE

NEED TO CHANGE OR EDIT PROGRAMMING.

3. COMPLY WITH CYBER SECURITY REQUIREMENTS AND

PERFORM REQUIRED PROGRAMMING AND TESTING PER

SPECIFICATIONS.

4. CONTROL WIRING IN BASEMENT MUST BE IN CONDUIT.

5. PROVIDE LOCKABLE CONTROL PANELS.

6. DISABLE UNUSED COMMUNICATION PORTS ON ALL

DEVICES.

(ALL CONTROL DRAWINGS)

Appendix B Page 1
Appendix B
06_Mechanical
MH100
Sheets and Views
MH100
MH101
Sheets and Views
MH101
M-301
Sheets and Views
M-301
M-501
Sheets and Views
M-501
M-502
Sheets and Views
M-502
M-503
Sheets and Views
M-503
M-601
Sheets and Views
M-601
M-602
Sheets and Views
M-602
M-701
Sheets and Views
M-701

File details come from the government source that posted it. Updated .