Appendix B 25QA102.pdf
PDF 2 MB Posted
- Solicitation number
- W912WJ25QA102
About this file
This Performance Work Statement (PWS) details HVAC system maintenance for the U.S. Army Corps of Engineers at the Otter Brook Lake facility in Keene, New Hampshire. The technical documents include comprehensive mechanical system drawings, schedules, and control diagrams for a new operations office building. Key systems include an air handling unit (AHU-1), energy recovery ventilator (ERV-1), radiant ceiling panels, cabinet unit heaters, air-cooled condensing units, and associated control infrastructure. The mechanical design supports multiple zones including office spaces, staff bathrooms, supervisors' offices, and building mechanical areas, with specific attention to temperature control, ventilation, and heating requirements across basement and first floor levels.
The design incorporates sophisticated control strategies with adjustable occupancy modes, economizer functionality, and safety features like freezestat protection. Specific equipment includes Trane and Mitsubishi systems, with precise specifications for airflow rates, temperature ranges, electrical requirements, and installation details. The documents provide extensive technical guidance for contractors, including mounting instructions, piping schematics, ductwork construction standards, and detailed equipment schedules that outline performance characteristics, electrical specifications, and manufacturer recommendations for each system component.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Amendment W912WJ25QA102-0001.pdf | ||
| Appendix A 25QA102.pdf | ||
| Appendix C 25QA102.pdf | ||
| Solicitation - W912WJ25QA102.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
HVAC SYSTEM MAINTENANCE
U.S. ARMY CORPS OF ENGINEERS
OTTER BROOK LAKE
KEENE, NH
PERFORMANCE WORK STATEMENT
APPENDIX B
Project Drawings
PLAN
NORTH
SCALE 1/4" = 1' - 0"
BASEMENT MECHANICAL PLAN
A2
0 4' 8'2'
U P
STAIRS
BASEMENT
8x6 EA UP
22x12 SA UP
22x12 OA UP
20x10 RA UP
AHU
FC
8x6 7
L-2
CU
ACCU
RS/RL UP
TO AC-1
UH
H W
R
H W
S
B
22x12
Ø
ERV
x
8x6
32x30
INSULATED
PLENUM
12Ø
RL/RS
(2 SETS)
RL/RS
RL/RS 4
HWR
HWS
HWR
HWS
CUH
Ø
3/4"
1-1/4"
1-1/4"
FC
20x10
(BELOW)
1"
ERV-1
SERVICE
CLEARANCE
3/4"
M-301
H3
22x12
12Ø
12Ø
DN
20x10 TO
PLENUM
M-301
A4
22x12
AS-1
2" HWS & HWR
MAKE-UP
WATER
SUPPLY
(WALL MOUNT)
P
2A
P
2B
LPG
NEUTRALIZATION KIT
EXT-115
CP
43/4" CD
CP
20x10
AHU-1
SERVICE
CLEARANCE
P
UP
FC
FC
RF
18 24
18 24
RISE
US Army Corps of Engineers
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
A
B
C
D
E
F
G
H
J
K
L
M
N
P
SHEET ID
U S
A
R M
Y
C
O R
P S
O
F
E
N G
I N
E E
R S
O T
T E
R
B
R O
K
D
A M
L
K E
N E
W
O
P E
R A
T I O
N
F
I C
E
GENERAL SHEET NOTES:
1. FOR MECHANICAL SYMBOLS, LEGENDS, AND
ABBREVIATIONS REFER TO SHEET M-001.
2. INSTALL EQUIPMENT TO ALLOW MAINTENANCE ACCESS AS
REQUIRED BY EQUIPMENT MANUFACTURER'S WRITTEN
INSTRUCTIONS. PROVIDE MINIMUM 12" MAINTENANCE
CLEARANCE AT VALVES AND OTHER ACCESS LOCATIONS.
3. FOR DUCTWORK FABRICATION, HANGER AND SUPPORT
DETAILS REFER TO SHEETS M-501, M-502, AND M-503.
4. DUCTWORK AND PIPING PENETRATIONS THROUGH
FIRE/SMOKE WALLS/FLOORS/BARRIERS SHALL BE SEALED
WITH FIRE STOPPING ACCORDING TO DIVISION 7
REQUIREMENTS.
5. NO FLEXIBLE DUCT SHALL PASS THROUGH FIRE/SMOKE
WALLS/FLOORS/BARRIERS.
6. COORDINATE INSTALLATION WITH FIRE ALARM, PLUMBING,
MECHANICAL, AND ELECTRICAL TRADES.
KEYNOTES:
1-1/4" HWS UP.
1-1/4" HWR UP.
8x6 EA UP.
ROUTE PIPING AS HIGH AS POSSIBLE.
3" BOILER COMBUSTION AIR AND EXHAUST UP
THRU ROOF. COORDINATE LOCATIONS WITH
ARCHITECTURAL DRAWINGS.
SEAL WALL PENETRATION WEATHERTIGHT.
ROUTE DUCTWORK AS HIGH AS POSSIBLE.
FIELD FABRICATE MIXING BOX.
DUCT SA VENTILATION AIR FROM ERV-1 INTO
RETURN OF AHU-1.
FOR SEQUENCE OF OPERATION AND
MOTORIZED DAMPER POSITIONS IN
ECONOMIZER MODE REFER TO A4/M-701.
FOR BOILER PIPING DIAGRAM REFER TO
F2/M-502.
CONDENSATE DRAIN TO DISCHARGE INTO
INDIRECT WASTE. REFER TO D16/P-601.
FOR CONTINUATION REFER TO SHEET P-101.
FOR LOUVER CONNECTION, REFER TO DETAIL
F1/M-501.
FOR EXPANSION TANK EXT-1 PIPING DIAGRAM,
REFER TO K4/M-502.
BOILER EMERGENCY SHUT-OFF SWITCH.
PROVIDE CONCRETE EQUIPMENT PAD. SEE
DETAIL L6/SB502.
PROVIDE DUCT ACCESS PANEL FOR
INSPECTION AND MAINTENANCE OF FIRE
DAMPER.
FOR UNIT HEATER PIPING DETAIL REFER TO
K7/M-501.
FOR CABINET UNIT HEATER PIPING DETAIL
REFER TO K10/M-502.
REFRIGERANT LINE SET; RS 1-1/8" AND RL 3/8".
REFRIGERANT LINE SET; RS 1/2" AND RL 1/4".
HOUSEKEEPING EQUIPMENT PAD.
PROVIDE DUCT MOUNTED FIRE DAMPER
BELOW FIRST FLOOR ASSEMBLY
05 Nov, 2021 - 1:37pm
Y:\22004.09\22004.09-MH100.dwg
B A
S E
M E
N T
M E
C H
A N
I C
A L
P L A
N
OTTER BROOK
MH100
(THIS SHEET ONLY)
AutoCAD SHX Text M
AutoCAD SHX Text M
AutoCAD SHX Text M
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text M
AutoCAD SHX Text
SCALE 1/4" = 1' - 0"
FIRST FLOOR MECHANICAL PLAN
A2
0 4' 8'2'
DN
RAMP DN
DN
OFFICE #4
RANGERS'S
OFFICE #3
RANGERS'S
OFFICE #2
RANGERS'S
OFFICE #1
RANGERS'S
AREA
COMMON
VESTIBULE
BATH
GUEST
KITCHEN
ROOM
MEETING
STORAGE
FILE
SHOWER
STAFF BATH/
STAIRS
OFFICE
SUPERVISOR'S
CORRIDOR
JAN
CLOSET
IT
COVERED PORCH
S-2
14x810x8 x
S-4
22x12
8Ø
10x610x6
S-1
S-1 x x
6Ø
8Ø
S-1
E-2
E-1
8Ø
8Ø
S-1
14x1014x12
6Ø
6Ø 6Ø 6Ø
6Ø
S-3
S-3
S-3
S-3
12x10 12x8 x
S-1
R-2
S-1 x
6Ø
E-3
E-1
8x6 x
8Ø
6Ø
R-3
R-3
10x8
8Ø
R-2
12x812x10
R-3
R-3
6Ø
6Ø
R-4
12x8 x
8x4
R-1
12x10
T-2
T-1
20x10
KH
6x6
AC
12x10
M-301
A4
M-301
H3
CUH-1
AHU-1
6Ø
8Ø
PLAN
NORTH
SCALE 1/8" = 1' - 0"
ATTIC MECHANICAL PLAN
K2
0 8'4' 16'
ATTIC
OPEN TO
BELOW
F1
M-501
L-1
PROVIDE
32x30
INSULATED
PLENUM
22x12
22x12
22x12
OA DN
3" BOILER
VENT DOWN
TO BASEMENT
ACCESS
DOOR
M-301
A4
M-301
H3
M
1. PROVIDE FOR DUCTWORK, PIPING, EQUIPMENT, AND FIXTURE SUPPORT FROM WOOD JOISTS AND TRUSSES.
2. COORDINATE WITH ELECTRICAL AND PLUMBING INSTALLERS TO AVOID CONFLICTS.
3. PROVIDE SUPPORT RODS PRIOR TO INSTALLATION OF AIR AND VAPOR BARRIER WHERE APPLICABLE.
4. PATCH AND RESTORE VAPOR AND AIR BARRIER.
5. PROVIDE DUCTS AND PIPES TIGHT TO CEILINGS TO MAXIMIZE CLEAR SPACE BELOW AS REQUIRED.
SUPPORT FROM WOOD JOIST AND TRUSSES DETAIL NOTES:
HORIZONTAL SCREW-IN FITTING.
BASIS OF DESIGN: SIMPSON
STRONG-TIE RWH 37200
THREADED ROD
SECTION AT HANGER SECTION AT DUCT SUPPORT
WOOD TRUSS, WOOD JOIST (TYP)
HORIZONTAL SCREW-IN FITTING.
BASIS OF DESIGN: SIMPSON
STRONG-TIE RWH 37200
THREADED ROD
HEX NUT AND HEX
LOCK NUT
NOT TO SCALE
SUPPORT FROM WOOD JOISTS AND TRUSSES DETAIL
L10
NOTE 3,4 NOTE 3,4
PRE-ENGINEERED METAL
CHANNEL OR ANGLE
US Army Corps of Engineers
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
A
B
C
D
E
F
G
H
J
K
L
M
N
P
SHEET ID
U S
A
R M
Y
C
O R
E
N G
I N
E E
R S
O T
T E
R
B
R O
K E
N E
W
O
P E
R A
T I O
F
I C
E
GENERAL SHEET NOTES:
1. FOR MECHANICAL SYMBOLS, LEGENDS, AND
ABBREVIATIONS REFER TO SHEET M-001.
2. VAPOR BARRIER AND GYPSUM AT BOTTOM OF CEILING
JOISTS IS NOT TO BE PUNCTURED, AND/OR DAMAGED
DURING INSTALLATION OF MECHANICAL SYSTEMS AND
DAMAGE MUST BE REPAIRED AT NO COST TO
GOVERNMENT.
3. INSTALL EQUIPMENT TO ALLOW MAINTENANCE ACCESS AS
REQUIRED BY EQUIPMENT MANUFACTURER'S WRITTEN
INSTRUCTIONS. PROVIDE MINIMUM 12" MAINTENANCE
CLEARANCE AT VALVES AND OTHER ACCESS LOCATIONS.
4. FOR DUCTWORK FABRICATION, HANGER AND SUPPORT
DETAILS REFER TO SHEETS M-501, M-502, AND M-503.
5. DUCTWORK PENETRATIONS THROUGH FIRE/SMOKE
WALLS/FLOORS/BARRIERS SHALL BE SEALED WITH FIRE
STOPPING ACCORDING TO DIVISION 7 REQUIREMENTS.
6. NO FLEXIBLE DUCT SHALL PASS THROUGH FIRE/SMOKE
WALLS/FLOORS/BARRIERS.
7. COORDINATE INSTALLATION WITH FIRE ALARM, PLUMBING,
MECHANICAL, AND ELECTRICAL TRADES.
KEYNOTES:
8x6 EA DN TO ERV-1.
20x10 RA DN TO AHU-1.
22x12 OA UP AND DOWN.
22x12 SA DOWN TO AHU-1.
3" BOILER COMBUSTION AIR AND EXHAUST UP THRU
ROOF. PROVIDE MANUFACTURERS VENT KIT AT ROOF
PENETRATION. PROVIDE INSULATION PER
MANUFACTURER RECOMMENDATIONS. COORDINATE
LOCATION WITH ARCHITECTURAL DRAWINGS.
LOUVER L-1, COORDINATE LOCATION WITH
ARCHITECTURAL DRAWINGS.
3" BOILER COMBUSTION AIR AND EXHAUST UP AND DOWN
IN CHASE.
PROVIDE MANUFACTURERS THRU WALL VENT WITH
EXHAUST KIT.
COORDINATE INSTALLATION OF KITCHEN HOOD WITH
KITCHEN CABINETS. REFER TO G11/AE740.
PROVIDE DUCT MOUNTED FIRE DAMPERS AT FIRST
FLOOR.
PROVIDE DUCT ACCESS PANEL FOR INSPECTION AND
MAINTENANCE OF FIRE DAMPERS. COORDINATE ACCESS
WITH CHASE ACCESS PANELS, REFER TO
ARCHITECTURAL DRAWINGS.
05 Nov, 2021 - 9:15am
C:\dfile\22004.09-MH101.dwg
F I R
T
O
R
T
I C
M E
C H
A N
I C
A L
P
L A
N S
OTTER BROOK
MH101
(THIS SHEET ONLY)
AutoCAD SHX Text T
AutoCAD SHX Text
RH
SCALE 1/4" = 1' - 0"
MECHANICAL SECTION 2
A4
0 4' 8'2'
PLAN
NORTH
SCALE 1/4" = 1' - 0"
MECHANICAL SECTION 1
H3
0 4' 8'2'
8x6 EA
8Ø RA
R-2
R-3
6Ø RA
8x6 EA
8x6 EA
AHU
ERV
SERVICE
CLEARANCE
SERVICE
CLEARANCE
30x32
INSULATED
PLENUM
L-2
12Ø EA
8x6 EA
12Ø OA
12Ø OA
(BEYOND)
22x12 OA
22x12 SA
FC
22x12 OA
20x10 RA
12Ø
EA
CU
ACCU
20x10 RA
(BEYOND)
8x6 EA
AHU
20x10 RA
22x12 OA
22x12 SA
FC
20x10 RA
12Ø OA
UH
FC
FC
12Ø OA
ROOM
MEETING
STORAGE
FILE
SHOWER
STAFF BATH/
OFFICE
SUPERVISOR'S
COVERED PORCH
S-2
S-1
S-1
E-1
8x10 SA
14x10 RA
10x20 RA10x12 RA
8x4 RA
16x12 SA
8x14 SA
8x6 SA
10x6 SA
12x22 SA
(BEYOND)
12x22 SA
(BEYOND)
12x8 RA
20x10 RA
12x10 RA
12x10 RA
22x12 OA
S-1
6x8 SA
6Ø EA
12x22 OA
10x6 SA8x6 SA
M-301
A4
M-301
H3
(BEYOND)
MH100,MH101
MH100,MH101
30x32
INSULATED
PLENUM
12Ø EA
12x22
10x20
22x12 SA
8x6 EA
RF
FC
FC
RF
(BEYOND)
US Army Corps of Engineers
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
A
B
C
D
E
F
G
H
J
K
L
M
N
P
SHEET ID
U S
A
R M
Y
C
O R
E
N G
I N
E E
R S
O T
T E
R
B
R O
K E
N E
W
O
P E
R A
T I O
F
I C
E
05 Nov, 2021 - 1:37pm
Y:\22004.09\22004.09-M301.dwg
M E
C H
A N
I C
A L
S E
C T
I O
N S
OTTER BROOK
M-301
GENERAL SHEET NOTES:
1. FOR MECHANICAL SYMBOLS, LEGENDS, AND ABBREVIATIONS REFER TO SHEET
M-001.
2. INSTALL EQUIPMENT TO ALLOW MAINTENANCE ACCESS AS REQUIRED BY
EQUIPMENT MANUFACTURER'S WRITTEN INSTRUCTIONS. PROVIDE MINIMUM 12"
MAINTENANCE CLEARANCE AT VALVES AND OTHER ACCESS LOCATIONS.
3. FOR DUCTWORK FABRICATION, HANGER AND SUPPORT DETAILS REFER TO
SHEETS M-501, M-502 AND M-503.
4. DUCTWORK AND PIPING PENETRATIONS THROUGH FIRE/SMOKE
WALLS/FLOORS/BARRIERS SHALL BE SEALED WITH FIRE STOPPING ACCORDING
TO DIVISION 7 REQUIREMENTS.
5. COORDINATE INSTALLATION WITH FIRE ALARM, PLUMBING, MECHANICAL PIPING
AND DUCTWORK, AND ELECTRICAL TRADES.
6. DUCTWORK AND PIPING ARE SHOWN DIAGRAMMATICALLY, EXACT LOCATION
SHALL BE DETERMINED IN THE FIELD. COORDINATE IN THE FIELD WITH
STRUCTURAL ELEMENTS.
AutoCAD SHX Text M
FLOW
CONCENTRIC TRANSITION
CONVERGING TEE
15°
15°
F L O
W
W
FLOW
45°FLOW
FLOW
45°
F L O
W
W
ECCENTRIC TRANSITION
DIVERGING TEE
30°
HWS
HWR
DRAIN VALVE
3/4" THREADED CAP
UNION (TYP)
NOT TO SCALE
RECTANGULAR DUCT TRANSITIONS DETAIL
K1
A2
MH100 NOT TO SCALE
COIL PIPING SCHEMATIC
K7
UNIT HEATER WATER
STRAINER
1. VALVES MUST BE SAME SIZE AS PIPE.
2. PROVIDE SPRING VIBRATION ISOLATORS FOR PUMP.
NOTES
PROVIDE
CONCENTRIC
REDUCER
WHERE
REQUIRED
CALIBRATED BALANCING
VALVE WITH POSITIVE
SHUTOFF
FLANGE
PRESSURE
GAUGE (TYP)
SPRING
VIBRATION
ISOLATORS
VERTICAL
INLINE
PUMP
AUTOMATIC
AIR VENT
SUSPENDED
UNIT HEATER
SHUTOFF
VALVE
CALIBRATED
BALANCING
VALVE WITH
POSITIVE
SHUTOFF
NOT TO SCALE
INLINE PUMP PIPING DETAIL
K16
SHUTOFF
VALVE
SILENT
CHECK VALVE
HWS & HWR PIPING FOR COIL
PIPING SCHEMATIC. SEE
HOT WATER PREHEAT COIL
W/ INSULATED DRAIN PAN
12" MOUNTING FRAME
SLOTTED ENGINEERED
CHANNEL, SECURED TO
FLOOR, GALVANIZED
OUTSIDE AIR INTAKE
MERV 13 FILTER
RETURN
AIR
SUPPLY FAN MOUNTED
ON SPRING VIBRATION
ISOLATORS
INSULATED WALL
CASING
FRONT
DISCHARGE
NOT TO SCALE
AHU AIR HANDLING UNIT DIAGRAM
B13
PITCH TO OUTSIDE
1/2" BIRDSCREEN
D
N
A2,K2
MH100,MH101 NOT TO SCALE
LOUVER CONNECTION DETAIL
F1
STORM
PROOF
DRAINABLE
LOUVER
CAULK ALL
AROUND
INSULATION-
EXTEND TO
ISOLATION
DAMPER
SOLDER JOINTS ON
BOTTOM OF DUCT AND
UP DUCT SIDES 12" MIN
AIR FLOW
BELLMOUTH FITTING WITH BUTTERFLY DAMPER. PROVIDE RIGID DUCT
FROM DAMPER TO DIFFUSER EXCEPT LAST 5 FEET MAY BE FLEX DUCT.
FOR CONNECTION TO ROUND MAIN DUCT PROVIDE CONICAL TEE OR WYE
NOT TO SCALE
DIFFUSER AND REGISTER RUNOUT DETAIL
F13
MAIN DUCT SUPPLY,
RETURN OR EXHAUST
PROVIDE 3" MIN HEIGHT
TRANSITION W/ ROUND
DUCT COLLAR
OBD INTEGRAL WITH
REGISTER WHERE
SCHEDULED
SQUARE/RECTANGULAR
REGISTER OR GRILLE
NYLON DRAW BAND
CONNECTION TO
DIFFUSER NECK
ROUND NECK DIFFUSER
ROUND FLEXIBLE
DUCT 90° MAXIMUM
FOR TOTAL BENDS
1. VALVES MUST BE SAME SIZE AS PIPE.
2. SHUT-OFF VALVES MAY BE BALL OR BUTTERFLY. REFER TO
SPECIFICATIONS FOR VALVE TYPE AND SIZE RESTRICTIONS.
3. PROVIDE UNIONS AND/OR FLANGES AS REQUIRED FOR FIT-UP AND
REMOVAL OF COIL.
NOTES
NOT TO SCALE
COIL PIPING SCHEMATIC
K11
AIR HANDLING UNIT HOT
FOR DUCT SIZES UP TO AND INCLUDING 10"Ø FOR DUCTS SIZES LARGER THAN 10"Ø
HANGER STRAP
BOLT
RADIANT PANELS SHALL BE
SUPPORTED INDEPENDENTLY OF
THE CEILING STRUCTURE (TYP)
SUPPORT WIRE
(TYP)
RADIANT PANEL
CROSS BRACE
1"-THICK
FIBERGLASS
INSULATION (TYP)
RADIANT PANEL
SAT CEILING
SUSPENSION
SYSTEM (SIM)
NOT TO SCALE
ROUND DUCT HANGER DETAIL
B1
NOT TO SCALE
RADIANT PANEL HANGING DETAIL
B7
MIN 1-1/4" WIDE x 12 GAUGE GALVANIZED STEEL
HANGER STRAP WITH NUTS ON BOTH SIDES OF CLAMP
MIN 1-1/4" WIDE x 12 GAUGE
GALVANIZED STEEL CLAMP
CLAMP SAME
SIZE AS
HANGER STRAP
MIN 3/8"Ø THREADED
RODS WITH NUTS ON
BOTH SIDES OF CLAMP
MIN 1-1/4" WIDE x 12
GAUGE GALVANIZED
STEEL SPLIT RING CLAMP
3/4 W
(MIN)
3/4 W
(MIN)
K11
M-501
SUPPLY
AIR
DX COOLING COIL
HWS
HWR
CONTROL
VALVE
STRAINER
BALL VALVE (TYP)
CALIBRATED BALANCING VALVE
RADIANT PANEL
FLEXIBLE HOSE CONNECTOR (TYP)
MANUAL AIR VENT INSTALLED AT
HIGH POINT
NOT TO SCALE
RADIANT PANEL PIPING SCHEMATIC
F7
STRAINER
A13
M-502
CONCRETE
HOUSEKEEPING PAD
ADJUSTABLE
STRAP-ON
AQUASTAT
(SET AT 100°F)
UNION (TYP)
DRAIN
HWR
HWS
SHUT-OFF VALVE
STRAINER
NC
CALIBRATED BALANCING VALVE
WITH POSITIVE SHUTOFF (TYP)
3-WAY MIXING VALVE
(3 PSI MAX PD)
BALANCE TO PROVIDE SAME
PRESSURE DROP AS COIL
AUTOMATIC
AIR VENT
THERMOMETER
IN WELL (TYP)
WATER COIL
SEAL AND CAULK
ALL AROUND
SPRING TYPE VIBRATION
ISOLATOR (TYP)
FIELD FABRICATED
MIXING BOX
US Army Corps of Engineers
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
A
B
C
D
E
F
G
H
J
K
L
M
N
P
SHEET ID
U S
A
R M
Y
C
O R
E
N G
I N
E E
R S
O T
T E
R
B
R O
K E
N E
W
O
P E
R A
T I O
F
I C
E
05 Nov, 2021 - 9:20am
C:\dfile\22004.09-M501.dwg
M E
C H
A N
I C
A L
D E
T A
I
OTTER BROOK
M-501
DOOR
STRUCTURE ABOVE
GRADE
5/8" INSULATED CONDENSATE
DRAIN TO MOP RECEPTOR
CENTER AC-1 ABOVE DOOR
CHECK VALVE
ISOLATION VALVE
WALL MOUNTED
EVAPORATOR FAN UNIT
CONDENSING
UNIT CU-1
REFRIGERANT LINES TO
ROOM UNIT AC-1, REFER TO
A2/MH100 FOR ROUTING
CONCRETE PAD
REFRIGERANT
LINES TO CU-1
REFRIGERANT PIPE
PENETRATIONS THRU WALL
IT CLOSET 105
EXTERIOR LOCATION
MANUFACTURERS
18" HIGH STAND
FASTEN STAND TO
CONCRETE PAD WITH
APPROPRIATE HARDWARE
AS-1
EXT-1
1/2"
HOSE BIBB W/ INTEGRAL
VACUUM BREAKER AND CAP
FOR FILLING SNOW MELT
SYSTEM
3/4" TO
FLOOR
DRAIN
3/4" MAKE-UP
WATER
CONNECTION
PRESSURE
REDUCING VALVE
LINE SIZED
BYPASS
A2
MH100 NOT TO SCALE
AIR CONTROL PIPING DIAGRAM
K4
A2
MH100 NOT TO SCALE
CABINET HEATER PIPING SCHEMATIC
K10
RPZ BACKFLOW
PREVENTER
3/4"
HIGH CAPACITY
AUTO AIR VENT
3/4"
HWS FROM
BOILER
3/4"
HWS TO SYSTEM
DRAIN VALVE WITH
3/4" THREADED CAP
AUTO AIR
VENT
4" THICK
CONCRETE
PAD
3/4"
EXPANSION TANK
MOUNT ON PAD
DRAIN VALVE
W/ HOSE BIBB
FLOOR
A2
MH100 NOT TO SCALE
BOILER HEATING SYSTEM DIAGRAM
F2
MOUNT UNIT AS HIGH
AS POSSIBLE WHILE
MAINTAINING
MANUFACTURER'S
REQUIRED
CLEARANCES
FILTER
DRAIN VALVE
UNION (TYP)
SHUTOFF VALVE
CEILING
RA
SA
HWR
HWS
FLOOR
MANUAL AIR VENT
CALIBRATED
BALANCING
VALVE
WITH
POSITIVE
SHUTOFF
3/4" THREADED CAP
LOCATE PIPING IN
WALL OR CHASE
INDICATED
WALL
FAN
ADJUSTABLE
STRAP-ON
AQUASTAT
(SET AT 100°F)
FLOOR
MOUNTED
CABINET
UNIT
HEATER
DRAIN LINE SIZE SHALL BE
MIN SIZE AS THE NIPPLE ON
THE DRAIN PAN
DRAIN PAN
SLOPE BOTTOM
OF PAN TO
DRAIN INLET
FLOOR
CLEAN
OUT
30"
PACKAGED FIRE
SUPPRESSION
SYSTEM WITH
STORAGE TANK
MOUNTED
INSIDE CABINET
NOTE
RECTANGULAR MAIN
RECTANGULAR MAIN
1. SPIN-IN TYPE STRAIGHT TAKE-OFF FITTINGS SHALL NOT BE PERMITTED.
ROUND
BRANCH
DUCT
BELLMOUTH
TAKE-OFF
FITTING
ROUND
BRANCH
DUCT
TRANSITION
RECTANGULAR
TO ROUND
TAKEOFF
AIRFLOW
RETURN
AIRFLOW
SUPPLY
NOT TO SCALE
RANGE HOOD DETAIL
F7
NOT TO SCALE
AHU-1 CONDENSATE PUMP DETAIL
A2
NOT TO SCALE
CONNECTIONS TO RECTANGULAR MAIN
A7
TYPICAL ROUND BRANCH DETAIL
CONDENSATE
PUMP
TO INDIRECT WASTE
FOR ROUTING
REFER TO MH100
INTEGRAL FAN WITH
THRU WALL DISCHARGE
COORDINATE
INSTALLATION HEIGHT
WITH ARCHITECTURAL
DRAWINGS
NOTES
FRONT VIEW SIDE VIEW
(4) 5/8" DIA EXPANSION
BOLTS W/ 3" EMBEDMENT
(TYP)
1-5/8", 12 GAUGE
COLD-FORMED STEEL
SLOTTED CHANNEL (TYP)
INTERMEDIATE STRUT (TYP)
ADJUST LOCATION TO SUIT
EQUIP BOLT DOWN
ARRANGEMENT.
FASTEN STRUT TO FRAME AND
AHU-1 OR ERV-1 TO STRUT.
1. SECURE POST BASE TO EXISTING CONCRETE PAD WITH MECHANICAL EXPANSION ANCHORS.
2. FASTENERS AND FITTINGS SHALL BE INSTALLED IN ACCORDANCE WITH THE MFG PRINTED INSTRUCTIONS.
OR
1/2" HEX HEAD BOLT
W/LOCKWASHER
AND NUT (TYP)
COLD-FORMED STEEL
2-WING FITTING (TYP)
1/4"x6"x6" COLD-FORMED
STEEL BASEPLATE (TYP)
COLD-FORMED STEEL
3-WING FITTING (TYP)
1" COLD-FORMED STEEL
KNEE BRACE (TYP)
OR
B13
M-501 NOT TO SCALE
PRE-ENGINEERED SLOTTED METAL EQUIPMENT FRAME DETAIL
A13
L6
SB502
(FOR PIPE 3" THROUGH 6")
ADJUSTABLE HANGER W/ROLLER
INSULATION
PIPE
(FOR PIPES 2 1/2" & SMALLER)
CLEVIS HANGER
PIPE
COVERING
PROTECTIVE
SADDLE
GALVANIZED
INSULATION
SHIELD 12"
LONG
LOCKING NUT
(TYP)
SUPPORT NUT
(TYP)
HEAVY-DUTY
CLEVIS
HANGER
NOT TO SCALE
PIPE HANGER ATTACHMENT DETAILS
K15
HWS
HWR
BOILER B-1
PRESSURE
RELIEF
LOW LOSS
HEADER
BUILDING CIRCULATION
PUMPS P-2A AND P-2B
FROM HEATING SYSTEM
TO HEATING SYSTEM
K16
M-501
FROM MAKE-UP WATER,
SEE AIR CONTROL PIPING
DIAGRAM
K4
M-502
G
FOR GAS SHUT-OFF
REFER TO
A11
P-601
THERMOMETER (TYP)
PRESSURE
GAUGE (TYP)
SHUTOFF
VALVE (TYP)
UNION (TYP)
K16
M-501
UNION (TYP)
DRAIN
VALVE (TYP)
D3
MP101 NOT TO SCALE
DUCTLESS SPLIT SYSTEM ELEVATION
F13
4" THICK CONCRETE
HOUSEKEEPING PAD
L6
SB502
4" THICK CONCRETE
HOUSEKEEPING PAD
L6
SB502
US Army Corps of Engineers
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
A
B
C
D
E
F
G
H
J
K
L
M
N
P
SHEET ID
U S
A
R M
Y
C
O R
E
N G
I N
E E
R S
O T
T E
R
B
R O
K E
N E
W
O
P E
R A
T I O
F
I C
E
05 Nov, 2021 - 9:21am
C:\dfile\22004.09-M502.dwg
M E
C H
A N
I C
A L
D E
T A
I
M-502
AutoCAD SHX Text
KH
AutoCAD SHX Text
AutoCAD SHX Text 45%%D
AutoCAD SHX Text
AHU
AutoCAD SHX Text
AutoCAD SHX Text
ERV
AutoCAD SHX Text
AutoCAD SHX Text
AHU
AutoCAD SHX Text
AutoCAD SHX Text
ERV
AutoCAD SHX Text
AutoCAD SHX Text P
FOR HORIZONTAL FLOOR INSTALLATION PROVIDE FIRE DAMPER WITH SPRING LOADED
DAMPER BLADES.
FASTEN ANGLES TO SLEEVE WITH POP-RIVETS, SCREWS OR WELDS AT 8-INCH ON
CENTER, MINIMUM 2 PER SIDE, 4 SIDES OF OPENING ON BOTH SIDES OF DAMPER.
PROVIDE CLEARANCE BETWEEN DAMPER SLEEVE OR DAMPER AND THE FIRE-RATED
WALL, PARTITION OR FLOOR IN ACCORDANCE WITH THE FIRE DAMPER MANUFACTURER.
IF REQUIRED BY THE DAMPER MANUFACTURER, PROVIDE FIRESTOPPING IN THIS SPACE
ON ALL SIDES TO MAINTAIN FIRE RATING.
USE FOR GALVANIZED SHEET METAL DUCT ONLY.
1.
2.
NOTES
3.
4.
A
A2-B2 (4" MIN
OR 12" MAX)
A
B
45°
B
A1-B1 (4" MIN OR 12" MAX)
SIZE AND RATING OF HANGERS AND SUPPORTS
SHALL BE PER LATEST SMACNA STANDARDS.
60" MAX DUCT
1" 1"
NOTE:
CHANNEL OR ANGLE
PREENGINEERED METAL
OVER 60" DUCT
THREADED
ROD
HANGER
HANGER
STRAP
NOT TO SCALE
DUCT SUPPORT ATTACHMENTS DETAIL
K2
NOT TO SCALE
REDUCING LATERAL
K13
ROUND DUCT-CONICAL
NOT TO SCALE
FIRE DAMPER DETAIL
E2
V
A
2" C
2"
A
2" C
2"
V
C D
L
L
L
O1 O2
2" (TYP)
A
B
B
OR 12" MAX)
A-B (1" MIN
A-B (1" MIN
OR 12" MAX)
REDUCING CONICAL TEECONICAL TEE
VEE FITTING CONCENTRIC REDUCER
NOT TO SCALE
TYPICAL ROUND DUCT FITTINGS DETAIL
K8
6" MAX
RETAINING
ANGLE (TYP)
UL LISTED TYPE B
FIRE DAMPER
FUSIBLE LINK
ASSEMBLY
RATED FOR
165°F
12x12 ACCESS
DOOR
UL APPROVED
FLOOR
DUCT
FACTORY SUPPLIED
THERMAL BLANKET
(4 SIDES, TYP)
6" MAX
RETAINING
ANGLE (TYP)
UL LISTED TYPE B
FIRE DAMPER
12x12 ACCESS
DOOR
DUCT
UL APPROVED
FLOOR
FUSIBLE LINK
ASSEMBLY
RATED FOR 165°F
FACTORY SUPPLIED
THERMAL BLANKET
(4 SIDES, TYP)
US Army Corps of Engineers
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
A
B
C
D
E
F
G
H
J
K
L
M
N
P
SHEET ID
U S
A
R M
Y
C
O R
E
N G
I N
E E
R S
O T
T E
R
B
R O
K E
N E
W
O
P E
R A
T I O
F
I C
E
05 Nov, 2021 - 9:24am
C:\dfile\22004.09-M503.dwg
M E
C H
A N
I C
A L
D E
T A
I
M-503
FUELUNIT NO NOTES
VOLTS/PHASE/AMPS
HOT WATER BOILER SCHEDULE
NOTES:
UNIT NO NOTESTYPE
DIFFUSER / REGISTER SCHEDULE
S-1 24x24 8Ø 0.1 <25 101-200 LAY-IN CEILING SUPPLY DIFFUSER PRICE SCD 1,2,3,6
NOTES
ENERGY RECOVERY VENTILATOR SCHEDULE
BASIS OF DESIGN
ERV-1 AHU-1 GREENHECK MINICORE-5215 1,2,3,4,5
SERVES
NOTE ON BASIS OF DESIGN
PRODUCTS OF OTHER MANUFACTURERS ARE ACCEPTABLE IF
THEY MEET THE OPERATIONAL REQUIREMENTS INDICATED. ANY
ADJUSTMENTS TO DUCTING, PIPING, WIRING OR CONFIGURATION
DUE TO THE SELECTION OF A MANUFACTURER OTHER THAN THAT
LISTED AS THE BASIS OF DESIGN WILL BE ACCOMPLISHED BY THE
CONTRACTOR AT NO ADDITIONAL EXPENSE TO THE GOVERNMENT.
GENERAL NOTE
TRANE BCHD05481.2/65.863.9 48.301520 460 4.9BUILDING HVAC 49.15 1.0 1,2,3,4140 120 230/1
AIR HANDLING UNIT SCHEDULE
GPM
DX COOLING COIL
TC MBH
CFMSERVESUNIT NO NOTES
ELECTRICAL
VOLTS/PHASEMBHLWTEWT
HEATING
SC MBH
AHU-1
HOT WATER UNIT HEATER SCHEDULE
GPM
LEAVING
WATER TEMP °F
ENTERING
CFM
UNIT NO
NOTES
VOLTS/PHASERPMHP
LOCATION
ELECTRICAL DATA
UH-1 BASEMENT 370 21.6 140 110 2.2 4.9 1/6 1075 120/1 MODINE LODRONIC HCH 22 1,2,3
NOTES:
1. INSTALL PER MANUFACTURERS WRITTEN INSTRUCTIONS.
2. PROVIDE WITH FINGER PROOF FAN GUARD.
3. HORIZONTAL SUSPENDED UNIT.
B-1
NOTES:
1. INSTALL PER MANUFACTURERS WRITTEN INSTRUCTIONS.
2. PROVIDE INJECTION PUMP. REFER TO PUMP SCHEDULE.
3. PROVIDE MANUFACTURERS STAINLESS STEEL VENTING WITH TERMINATION KITS FOR COMBUSTION AIR
AND FLUE VENT.
4. PROVIDE ACCESSORIES: SAFETY RELIEF VALVE, PRESSURE/TEMP GAUGES, CIRCULATOR HARNESS, LOW WATER CUT-OFF, MANUAL RESET HIGH LIMIT.
LPG 155 142 95.1 3" 3" 120/1/6.3
BASIS OF DESIGN
HTP EFT-155 1,2,3,4,5,6,7,8
SUPPLY
CFM
460 0.75
ESP
IN
WC
FAN
HP
1/4
EXHAUST
CFM
335 0.7
ESP
IN
WC
FAN
HP
1/4
ELECTRICAL
VOLTS/
PHASE
MCA
115/1 6.4
NOTES:
1. INSTALL PER MANUFACTURERS WRITTEN INSTRUCTIONS.
2. PROVIDE FIBER MEMBRANE CORE.
3. PROVIDE TIMED FROST CONTROL.
4. PROVIDE VARI-GREEN VARIABLE SPEED MOTOR.
5. PROVIDE INTEGRAL BACKDRAFT DAMPERS.
S-2
S-3
24x24
12x12
6Ø
6Ø
<25
<25
0-100
70-100
LAY-IN CEILING SUPPLY DIFFUSER
LAY-IN CEILING SUPPLY DIFFUSER
PRICE SCD
PRICE SCD
0.1
0.1
R-1 24x24 <25 251-360 PERFORATED RETURN GRILLE PRICE PDDR0.1 1,3,6
R-3 12x12
R-4 24x24
R-2 24x24 0.1
0.1
0.1
<25
<25
<25
100-250
65-90
0-100
PERFORATED RETURN GRILLE PRICE PDDR
PERFORATED RETURN GRILLE PRICE PDDR
PERFORATED RETURN GRILLE PRICE PDDR
E-2 24x24 0.1 <25 115 PERFORATED EXHUAST GRILLE PRICE PDDR 1,4,6
E-1 12x12 0.1 <2512x12 0-120 LOUVERED FACE EXHAUST GRILLE PRICE 530
RADIANT CEILING PANEL SCHEDULE
NOTES:
1. PROVIDE FULL TRIM ACCESSORIES AS REQUIRED.
2. COLOR AND FINISH SELECTION BY CONTRACTING OFFICER.
3. AVERAGE WATER TEMPERATURE BASED ON 140°F EWT AND 130°F LWT.
LOCATION
ELEMENT
PASSES SIZE
BASIS OF DESIGN NOTES
RP-1 4 135 STERLING RADIANT CEILING PANEL 1,2,3,4,5
RP-2 135
RP-3 135
RP-4 135
RP-5 135
RP-6 135
RP-7 135
RP-8 135
RP-9 135
RP-10 135
RP-11 135
RP-12 135
RP-13 135
RP-14B 135
RP-15 135
RP-16 135
RP-17 135
RP-18 135
NOTES
AIR CONDITIONING UNIT SCHEDULE
AC-1/CU-1
INDOOR UNIT
LOCATION
OUTDOOR
UNIT
LOCATION
CFM
MBH
MAX/MIN
VOLTS/PH
230/1
BASIS OF DESIGN
TRANE MITSUBISHI PKA-12HA7/PUY-A12NKA7GRADE 320-425 12/5.8IT CLOSET 105
NOTES:
1. INDOOR UNIT AC-1: PROVIDE WITH MANUFACTURER'S WIRED, WALL MOUNTED CONTROLLER.
2. COOLING ONLY UNIT.
3. OUTDOOR CONDENSING UNIT CU-1: PROVIDE 18" PRE-MANUFACTURED, GALVANIZED STEEL,
MODULAR EQUIPMENT SUPPORT FRAME WITH EQUIPMENT CLAMPS FOR INSTALLATION.
1,2,3,4,5,6
ELECTRICAL
AC
MCA
CU
MCA
CU
MOCP
11 28
COMMON 103
RANGER 106
RANGER 109
RANGER 112
RANGER 113
RANGER 113
SUPER 111
SUPER 111
FILE 104
MEETING 114
MEETING 114
KITCHEN 115
KITCHEN 115
VESTIBULE 101
GUEST BATH 116
STAFF BATH 110
CORRIDOR 102
CORRIDOR 102
24"Wx8'-0"L
24"Wx6'-0"L
24"Wx6'-0"L
24"Wx6'-0"L
24"Wx4'-0"L
24"Wx5'-0"L
24"Wx7'-0"L
24"Wx7'-0"L
24"Wx12'-0"L
24"Wx10'-0"L
24"Wx12'-0"L
STERLING RADIANT CEILING PANEL
STERLING RADIANT CEILING PANEL
STERLING RADIANT CEILING PANEL
STERLING RADIANT CEILING PANEL
STERLING RADIANT CEILING PANEL
STERLING RADIANT CEILING PANEL
STERLING RADIANT CEILING PANEL
STERLING RADIANT CEILING PANEL
STERLING RADIANT CEILING PANEL
STERLING RADIANT CEILING PANEL
STERLING RADIANT CEILING PANEL
STERLING RADIANT CEILING PANEL
STERLING RADIANT CEILING PANEL
STERLING RADIANT CEILING PANEL
STERLING RADIANT CEILING PANEL
STERLING RADIANT CEILING PANEL
STERLING RADIANT CEILING PANEL
24"Wx6'-0"L
24"Wx6'-0"L
24"Wx6'-0"L
24"Wx5'-0"L
24"Wx5'-6"L
24"Wx5'-0"L
24"Wx14-0"L
SERVES
ELECTRICAL
MCA
NOTES
AIR COOLED CONDENSING UNIT SCHEDULE
VOLTS/PHASE
ACCU-1 AHU-1 5 410A - 2 230/1 37 60 1,2,3,4,5
BASIS OF DESIGN
TRANE 4TTR7060A
NOTES:
1. 2-STAGE COMPRESSOR.
2. PROVIDE RUBBER ISOLATOR KIT.
3. OUTDOOR DESIGN TEMP 95°F.
4. PROVIDE PRE-INSULATED REFRIGERANT LINESET.
5. PROVIDE SERVICE VALVE PANEL COVER.
OA
CFM
RA
CFM
EAT
DB/WB
MOTOR
POWER (HP)
BASIS OF
DESIGN
NOMINAL
CAPACITY
TONS
REFRIG
TYPE
EER
FULL
LOAD
CAPACITY
STEPS
HEATING
MBH
MAX PRESSURE
DROP IN WC
BASIS OF
DESIGN
AIR
INTAKE
GAS
VENT
MINIMUM
EFFICIENCY
CAPACITY
MBH
INPUT
MBH
UNIT
NO
INSTALLED
WEIGHT
LBS
MAX
PRESSURE
DROP IN
WC
MAX
NOISE
CRITERIA
CFM
RANGE
NECK
SIZE
IN
FACE
SIZE
IN
BASIS OF DESIGN
UNIT
NO
UNIT
NO
UNIT
NO
LOUVER SCHEDULE
DIMENSIONS
UNIT NO TYPESERVES
HEIGHT
CFM
WIDTH DEPTH
NOTES
DENLAR D1000 SERIESKH-1
UNIT NO
KITCHEN 115
SERVES
RANGE HOOD SCHEDULE
140-250
CFM
0.2
NOTES
1,2,3,4,5,6,7
NOTES:
1. INSTALL PER MANUFACTURER'S WRITTEN INSTRUCTIONS AND CLEARANCE REQUIREMENTS.
2. PROVIDE WET CHEMICAL FIRE SUPPRESSION SYSTEM. FIRE SUPPRESSION AGENT MUST NOT
CONTAIN CHEMICALS THAT ARE CLASSIFIED AS REFRIGERANTS.
3. PROVIDE WITH INLINE FAN WITH REAR DISCHARGE.
4. PROVIDE WITH THRU-WALL EXHAUST AND VENT KIT.
120/130"
SP
IN
WC
HOOD
DEPTH
19.3" 10.5" 60
HOOD
LENGTH
HOOD
HEIGHT
WEIGHT
(LBS)
VOLTS/
PHASE
BASIS OF DESIGN
MIN FREE AREA
SQUARE FT
BASIS OF DESIGN
L-1
L-2
OA INTAKE
EXHAUST AIR
1,2,3,4,5
1,2,3,4,5
1,2,3,4,5
1,2,3,5
1,2,3,5
1,2,3,5,6
1,2,3,4,5,6
1,2,3,4,5
1,2,3,4,5
1,2,3,5
1,2,3,4,5
1,2,3,5
1,2,3,4,5
1,2,3,4,5
1,2,3,4,5
1,2,3,4,5
1,2,3,4,5
4. PROVIDE SAME END PIPING.
5. MOUNT RADIANT PANEL IN ACCORDANCE WITH MANUFACTURER'S WRITTEN INSTRUCTIONS.
6. PROVIDE 3-WAY MIXING VALVE AT PANEL INDICATED.
INTAKE 1520 30" 32" 6" 3.5 RUSKIN ELF 6375 DX 1,2,3
EXHAUST 1400 30" 32" 6" 3.5 RUSKIN ELF 6375 DX
NOTES:
1. PROVIDE FIXED DRAINABLE BLADES, SELF FLASHING.
2. PROVIDE WIRE MESH BIRDSCREEN.
1. COLOR; WHITE.
2. PROVIDE 4-WAY THROW.
3. MOUNTING FRAME FOR INSTALLATION IN SAT CEILING.
4. MOUNTING FRAME FOR INSTALLATION IN GYP BOARD CEILING.
T-1 24x24 6x6 <25 85-150 PERFORATED TRANSFER GRILLE PRICE PDDR0.1
1,2,3,6
1,2,3,6
1,3,6
1,3,6
1,3,6
1,5,6,7,8,9
1,3,6
3. PROVIDE FINISH IN MANUFACTURER'S STANDARD COLOR SELECTED BY ARCHITECT.
1,2,3
1.0
ESP
IN
WC
PANEL
MBUTH
1.9
1.42
1.42
1.42
1.3
1.19
0.95
1.19
1.19
2.38
2.85
2.85
3.33
AVG
WATER TEMP
PANEL
CAPACITY
BUTH/LF
ROOM
MBUTH
4.5
1.9
1.2
1.2
1.2
1.9
3.2
2.2
5.7
2.5
1.0
1.3
1.42
1.42
1.66
1.66
1.42
NOTES:
1. INSTALL PER MANUFACTURERS WRITTEN INSTRUCTIONS.
2. PROVIDE 2" PLEATED MERV-13 FILTERS.
3/4"
GAS
CONNECTION
5. PROVIDE OUTDOOR AIR SYSTEM TEMPERATURE SENSORS.
6. PROVIDE CONDENSATE ACID NEUTRALIZATION KIT.
7. PROVIDE BOILER MANUFACTURER RACKING SYSTEM.
8. PROVIDE DDC INTERFACE EQUIPMENT AND PROGRAMMING.
5. PROVIDE WITH ELECTRICAL STOVE SHUT-OFF CONTROL MODULE.
6. RANGE HOOD TO BE INSTALLED IN ACCORDANCE WITH NFPA REQUIREMENTS.
7. PROVIDE MANUAL PULL STATION FOR FIRE SUPPRESSION SYSTEM.
WEIGHT
LBS
5. PROVIDE WITH INTEGRAL OPPOSED BLADE DAMPER.
6. PROVIDE TRANSITION FROM DUCTWORK TO DIFFUSER/GRILLE.
7. SURFACE MOUNTED.
8. 3/4" BLADE SPACING, 45-DEG DEFLECTION.
9. BLADE PARALLEL TO LONG DIMENSION.
4. OUTDOOR CONDENSING UNIT CU-1: PROVIDE LOW AMBIENT WIND BAFFLES FOR
OPERATION DOWN TO -20°F.
5. STANDARD OPERATION DESIGN TEMPERATURE -20°F TO 95°F. INDOOR UNIT AC-1 USER
ADJUSTED THERMOSTAT TO BE SET TO IT/DATA EQUIPMENT RECOMMENDED SETPOINT.
6. CONDENSATE DRAIN SHALL BE INSTALLED TO DRAIN BY GRAVITY.
3. PROVIDE HORIZONTAL TYPE WITH INLET AND OUTLET DUCT COLLAR.
4. PROVIDE DRAIN PAN FLOAT SWITCH.
S-4 24x24 8Ø <25 101-200 LAY-IN CEILING SUPPLY DIFFUSER PRICE SCD0.1 1,2,4,6
T-2 24x24 <25 PERFORATED TRANSFER GRILLE PRICE PDDR0.1 1,4,685-1506x6
8Ø
8Ø
6Ø
6Ø
10Ø
E-3 12x12 0.1 <2512x12 0-100 LOUVERED FACE EXHAUST GRILLE PRICE 530 1,6,7,8,9
RP-14A 135VESTIBULE 101 STERLING RADIANT CEILING PANEL24"Wx7'-0"L 1,2,3,4,5238
3.0
4 1.66
52.2/51.6
LAT
DB/WB
R-410A
REFRIG
TYPE
MOP
CONDENSER FAN(S)
QTY
1 1/4 1.3
FAN
HP EA
FLA
EA
COMPRESSOR(S)
QTY
1 28.8 152.9
FLA
EA
RLA
EA
US Army Corps of Engineers
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
A
B
C
D
E
F
G
H
J
K
L
M
N
P
SHEET ID
U S
A
R M
Y
C
O R
E
N G
I N
E E
R S
O T
T E
R
B
R O
K E
N E
W
O
P E
R A
T I O
F
I C
E
05 Nov, 2021 - 9:26am
C:\dfile\22004.09-M601.dwg
M E
C H
A N
I C
A L
S C
H E
D U
L E
S
M-601
NOTE ON BASIS OF DESIGN
PRODUCTS OF OTHER MANUFACTURERS ARE ACCEPTABLE IF
THEY MEET THE OPERATIONAL REQUIREMENTS INDICATED. ANY
ADJUSTMENTS TO DUCTING, PIPING, WIRING OR CONFIGURATION
DUE TO THE SELECTION OF A MANUFACTURER OTHER THAN THAT
LISTED AS THE BASIS OF DESIGN WILL BE ACCOMPLISHED BY THE
CONTRACTOR AT NO ADDITIONAL EXPENSE TO THE GOVERNMENT.
GENERAL NOTE
EXPANSION TANK SCHEDULE
LOCATION
LOCATION
NOTES:
NOTES:
UNIT NO
UNIT NO TYPE
AIR SEPARATOR SCHEDULE
NOTES
DIMENSIONS NOTES
EXT-1
AS-1
SERVES
SERVES
BASEMENT HEATING SYSTEM 12 GAL 39"x16" TACO CBX84-125 1,2
BASEMENT HEATING SYSTEM TANK 17 0.15 - TACO-ACT02 1
PUMP SCHEDULE
UNIT NO SERVES TYPE GPM
MOTOR DATA
HP RPM VOLTS/PHASE
NOTES
BHP
BASIS OF
DESIGN
BASIS OF
DESIGN
ACCEPTANCE
VOLUME
CAPACITY
(GPM)
PRESSURE
DROP (FT)
STRAINER
FREE AREA
(SQ IN)
TOTAL
HEAD
PUMP
EFF(%)
SUCTION/
DISCHARGE (IN)
BASIS OF
DESIGN
P-1
P-2A
1. PRE-CHARGED TO 40 PSI.
2. VERTICAL TANK CONFIGURATION.
1. PROVIDE WITH STRAINER.
BOILER INJECTION IN-LINE 14.6 10FT - 1/8 3250 115/1 TACO IL0012 2
HEATING SYSTEM IN-LINE 17.8 25FT 38% 0.28 1/2 1760 208/1
1-1/2" / 1-1/2"
TACO 1915 1,6
NOTES:
1. PROVIDE ORIENTATION FOR HORIZONTAL MOUNTING.
2. PROVIDE INTEGRAL CHECK VALVE.
3. SPARE/LAG PUMP.
HOT WATER CABINET UNIT HEATER SCHEDULE
CFM
UNIT NO
LOCATION
ENTERING
WATER TEMP °F
GPM
LEAVING VOLTS/PHASE
HP
RPM
FAN DATA
NOTES
1,2,3,4STERLING F-02120/11/1510500.151201401.55.7230STAIR 107CUH-1
HEATING
MBH
PD FT
WC
BASIS OF
DESIGN
NOTES:
1. PROVIDE CABINET ENCLOSURE WITH TOP DISCHARGE AND FLOOR INLET CONFIGURATION.
2. COLOR BY ARCHITECT.
3. 1-ROW HEATING HOT WATER COIL.
DESIGN CONDITION SCHEDULE
NOTES:
LOCATION NOTES
ROOM
NO
INDOOR COOLING
DESIGN TEMP °F
VESTIBULE
CORRIDOR
COMMON AREA
FILE STORAGE
IT CLOSET
RANGERS OFFICE #1
STAIRS
JAN
STAFF BATH/SHOWER
SUPERVISORS OFFICE
RANGERS OFFICE #2
RANGERS OFFICE #3
RANGERS OFFICE #4
MEETING ROOM
KITCHEN
GUEST BATH
OUTDOOR COOLING
DESIGN TEMP °F
INDOOR HEATING
DESIGN TEMP °F
OUTDOOR HEATING
DESIGN TEMP °F
85.7
85.7
85.7
85.7
85.7
85.7
85.7
85.7
85.7
85.7
85.7
85.7
85.7
85.7
85.7
85.7
-2.1
-2.1
-2.1
-2.1
-2.1
-2.1
-2.1
-2.1
-2.1
-2.1
-2.1
-2.1
-2.1
-2.1
-2.1
-2.1
CONTROL VALVE SCHEDULE
NOTES
AHU-1
RADIANT PANELS
CUH-1
QTY
EQUIPMENT
SERVED
LOCATION SERVICE TYPE ACTION
WATER VALVES
GPM SIZING
FAIL POSITION
UH-1
BASEMENT 001
BASEMENT 001
STAIR 107
VARIOUS
HOT WATER
HOT WATER
HOT WATER
HOT WATER
3-WAY
2-WAY
2-WAY
2-WAY
MODULATING
2-POSITION
2-POSITION
2-POSITION
4.88
NOTE 1
2.2
1.5
3 PSID WPD MAX
LINE SIZE
LINE SIZE
LINE SIZE OPEN
OPEN
OPEN
OPEN
NOTES:
1. REFER TO RADIANT CEILING PANEL SCHEDULE ON M-601.
DUCTWORK CONSTRUCTION AND LEAKAGE TESTING SCHEDULE
SUPPLY
DUCT
DUCT PRESSURE CLASS
INCHES OF WATER COLUMN
RETURN
DUCT
EXHAUST
DUCT
OUTSIDE
AIR
DUCT
SUPPLY
ROUND/OVAL RECTANGULAR
DUCT
SEAL
CLASS
DUCT
SEAL
CLASS
DUCT
LEAK
CLASS
DUCT
LEAK
CLASS
DUCT
SEAL
CLASS
DUCT
LEAK
CLASS
RETURN/
OUTSIDE AIR
DUCT TEST
PRESSURE:
INCHES OF
WATER
COLUMN
SYSTEM
ERV-CONSTANT
VOLUME
SYSTEM
DUCTED BLOWER
COILS
2 - - - - -
NOTES
A 8 A 16 2.0 1
- -2 - - - - - - 2.0 1
- 2 - - - - - 2.0 1
- - - - - - 2.0 1
2 - - - - -A 8 A 16 2.0 1
-1 - - - - - - 2.0 1
-2
A 16
A 16
A 16
A 16
NOTES:
1. PROVIDE DUCT AIR LEAKAGE TESTING IN ACCORDANCE WITH SPECIFICATION SECTION 23 05 93 TESTING, ADJUSTING, AND BALANCING FOR
HVAC AND THE PROCEDURES IN SMACNA HVAC AIR DUCT LEAKAGE TEST MANUAL. DUCTWORK SHALL BE LEAK TESTED IN ACCORDANCE WITH
ITS DUCT PRESSURE CLASS, NOT ITS DUCT SEAL CLASS.
DESIGN CONDITION SCHEDULE
LOCATION
ROOM
NO
AREA
(SF)
VESTIBULE
CORRIDOR
COMMON AREA
FILE STORAGE
IT CLOSET
RANGERS OFFICE #1
STAIRS
JAN
STAFF BATH/SHOWER
SUPERVISORS OFFICE
RANGERS OFFICE #2
RANGERS OFFICE #3
RANGERS OFFICE #4
MEETING ROOM
KITCHEN
GUEST BATH
DESIGN
OCCUPANCY
DENSITY
PEOPLE OA
RATE CFM/
PERSON
AREA OA
RATE
CFM/FT
MIN
AIRFLOW
AREA OA
CFM
BREATHING
ZONE OA
(PEOPLE+
AREA) CFM
AIR
DISTRIBUTION
EFFECTIVENESS
SPACE OA
(CORRECTED
PEOPLE+
AREA) CFM
REQUIRED
EA
AIRFLOW
RATE
REQUIRED
EA
MINIMUM
CFM
DESIGN
SUPPLY
AIR CFM
DESIGN
OUTSIDE
AIR CFM
DESIGN
RETURN
AIR CFM
DESIGN
EXHUAST
AIR CFM
0.06
0.12
1.0
1.0/SF
70/FIXT
0.3/SF
7070/FIXT
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
0.06
0.06
0.06
0.06
0.06
0.06
0.06
0.06
7.5
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
P-2B HEATING SYSTEM IN-LINE 17.8 25FT 38% 0.28 1/2 1760 208/1 TACO 1915 1,3
001 BASEMENT - 85.7 -2.140
CP-1 AHU-1 DX COND. CENTRIFUGAL <10 10FT - - 1/30 1795 115/1 1" / 1/2" VCC-20ULS 2,4,5
CP-2 B-1 CONDENSATE <10 10FT - - 1/30 1795 115/1 2,4,5CENTRIFUGAL 1" / 1/2" VCC-20ULS
4. PROVIDE 6'-0" CORD.
5. BASIS OF DESIGN VCC-20ULS PART #554200.
6. ACTIVE/LEAD PUMP.
2 HOT WATER 3-WAY 2-POSITION LINE SIZE CLOSEDRADIANT PANELS NOTE 1
4. PROVIDE FINISH IN MANUFACTURER'S STANDARD COLOR
SELECTED BY ARCHITECT.
SUPERVISOR 111,
STAFF BATH 110
1-1/2" / 1-1/2"
1-1/2" / 1-1/2"
SERVESUNIT NO NOTES
HP
PHASE
VOLTS/
SONES
TYPE RPM
FAN FAN
DESIGN
BASIS OF
TYPE
DRIVE
CFM
IN WC
ESP
RF-1 AHU-1 1060 0.7 DIRECT INCLINE 1368 8.0 1/2 115/1 GREENHECK SQ-120-VG 1,2,3
NOTES:
A,B
ACCESSORIES
FAN SCHEDULE
1. PROVIDE COMPANION FLANGES FOR INLET AND OUTLET DUCT CONNECTIONS.
2. PROVIDE TWO SIDED ACCESS PANELS.
3. MANUFACTURER MOUNTED DISCONNECT SWITCH.
ACCESSORIES:
A. MFR FAN MOUNTED DISCONNECT SWITCH.
B. NEOPRENE VIBRATION ISOLATORS.
US Army Corps of Engineers
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
A
B
C
D
E
F
G
H
J
K
L
M
N
P
SHEET ID
U S
A
R M
Y
C
O R
E
N G
I N
E E
R S
O T
T E
R
B
R O
K E
N E
W
O
P E
R A
T I O
F
I C
E
05 Nov, 2021 - 9:27am
C:\dfile\22004.09-M602.dwg
M E
C H
A N
I C
A L
S C
H E
D U
L E
S
M-602
HWR
HWS
DP
EA
OA
EA
ERV SUPPLY FAN START/STOP
ERV SUPPLY FAN STATUS 1
X X X
XX XX
ERV EXHAUST FAN START/STOP
ERV EXHAUST FAN STATUS 1
X X X
XX XX
ERV OUTSIDE AIR DAMPER
X X X
ERV EXHAUST AIR DAMPER
X X X
SA
CS
CS
ERV EA DAMPER
ERV EXHAUST AIR TEMPERATURE 4
XXX X
ERV SUPPLY AIR TEMPERATURE 5
XXX X
ERV RETURN AIR TEMPERATURE
XX X
ERV RETURN AIR FILTER SWITCH 3
XX XX
ERV OUTSIDE AIR FILTER SWITCH 3
XX XX
OCCUPANT OVERRIDE ENABLE
XXX
T
BLOWER COIL UNIT (AHU-1) AND ERV-1 POINTS LIST
NOTES:
AHU FAN START/STOP
AHU FAN STATUS CURRENT SENSOR 1
SUPPLY AIR TEMPERATURE 2
H
C
CS
HWS
HWR
DX COOLING STAGE 1
D X
RL
RS
HEATING COIL CONTROL VALVE
DX COOLING STAGE 2
ERV SUPPLY AIR
TEMPERATURE
SENSOR
SUPPLY FAN
CURRENT SENSOR
RA FILTER
SWITCH
SUPPLY FAN
START/STOP
ERV EXHAUST AIR
TEMPERATURE
SENSOR
EXHAUST FAN
START/STOP
EXHAUST AIR FAN
EXHAUST FAN
CURRENT SENSOR
OA FILTER
SWITCH ERV OA
DAMPER
ERV RETURN AIR
TEMPERATURE
SENSOR
T
M
M
T
DP
SCALE: N.T.S.
TYPICAL CABINET UNIT HEATER CONTROL DIAGRAM (NON-DDC)
H14
SEQUENCE OF OPERATION
ON CALL FOR HEAT FROM THE THERMOSTAT, (50°F
ADJUSTABLE) THE FAN SHALL RUN.
WALL MOUNTED LINE
VOLTAGE THERMOSTAT WITH
TAMPERPROOF GUARD
T
SCALE: N.T.S.
BLOWER COIL UNIT (AHU-1) AND ERV-1 CONTROL DIAGRAM
A4
B I N
A R
Y
O
U T
P U
T
A N
A L O
G
I N
P U
T
A N
A L O
G
O
U T
P U
T
B I N
A R
Y
I N
P U
T
B I N
A R
Y
V
A R
I A
B L E
A N
A L O
G
V
A R
I A
B L E
T R
E N
D
L O
G
G R
A P
H I C
A L A
R M
SYSTEM
POINT
DESCRIPTION
NOTES
SEQUENCE OF OPERATION
THE OCCUPIED AND UNOCCUPIED MODES SHALL BE DETERMINED BY A
USER ADJUSTABLE 24-HOUR/7-DAY SCHEDULE THAT IS ACCESSIBLE TO
THE BUILDING OPERATOR THROUGH THE GUI.
OCCUPIED MODE: DURING THE OCCUPIED MODE THE AHU-1 SUPPLY FAN,
RETURN FAN AND ERV SUPPLY AND EXHAUST FANS SHALL RUN
CONTINUOUSLY. THE ERV OUTSIDE AND EXHAUST AIR DAMPERS,
BUILDING OUTSIDE AIR DAMPER AND AHU-1 RETURN AIR DAMPER SHALL
REMAIN OPEN. AHU-1 OUTSIDE AIR DAMPER SHALL REMAIN CLOSED.
HEATING MODE: THE DX COOLING SHALL REMAIN OFF AND THE HEATING
COIL CONTROL VALVE SHALL MODULATE TO MAINTAIN THE SUPPLY AIR
TEMPERATURE SET POINT, ACCORDING TO THE FOLLOWING, BUILDING
OPERATOR ADJUSTABLE, RESET SCHEDULE;
OUTSIDE AIR TEMP SUPPLY AIR SET POINT
60 DEF F 60 DEG F
40 DEG F 68 DEG F
COOLING MODE: THE HEATING COIL CONTROL VALVE SHALL REMAIN
CLOSED AND THE DX COOLING SHALL REMAIN ON UNTIL THE ZONE
TEMPERATURE IS SATISFIED. THE COMPRESSOR SHALL START WHEN
THERE IS A CALL FOR COOLING AND STOP WHEN THE TEMPERATURE IS
SATISFIED.
ECONOMIZER MODE: THE ECONOMIZER MODE SHALL BE ENABLED
WHENEVER THE OUTSIDE AIR ENTHALPY IS 10 PERCENT (OR MORE
ADJUSTABLE) BELOW THE RETURN AIR ENTHALPY, THE OUTSIDE AIR
TEMPERATURE IS BELOW 60°F (ADJUSTABLE), AND THERE IS A CALL FOR
COOLING. OTHERWISE ECONOMIZER COOLING SHALL BE DISABLED.
DURING THE ECONOMIZER MODE THE ERV SUPPLY FAN SHALL REMAIN
OFF. THE ERV OUTSIDE AIR DAMPER SHALL BE CLOSED AND THE DX
COOLING SHALL BE OFF. THE AHU OUTSIDE AIR, RETURN AIR, AND RELIEF
DAMPERS SHALL ACT IN UNISON AS A MIXED AIR DAMPER (RA DAMPER
SHALL CLOSE AS THE OA AND RELIEF DAMPERS OPEN) AND SHALL
MODULATE TO MAINTAIN THE SUPPLY AIR ECONOMIZER COOLING
SETPOINT, 55°F (ADJUSTABLE).
UNOCCUPIED MODE: DURING UNOCCUPIED MODE THE AHU-1 SUPPLY
FAN, RETURN FAN AND ERV SUPPLY AND EXHAUST FANS SHALL REMAIN
OFF, THE DX COOLING SHALL REMAIN OFF, AND THE HEATING COIL
CONTROL VALVE SHALL REMAIN CLOSED IF THE OUTSIDE TEMPERATURE
IS ABOVE 35°F (ADJUSTABLE). IF THE OUTSIDE AIR TEMPERATURE FALLS
BELOW 35°F (ADJUSTABLE) THEN THE HEATING COIL CONTROL VALVE
SHALL REMAIN 10% (ADJUSTABLE) OPEN TO HELP PREVENT FREEZING.
THE OUTSIDE AIR, EXHAUST AIR AND RELIEF AIR DAMPERS SHALL REMAIN
CLOSED.
SAFETY: THE LOW TEMPERATURE THERMOSTAT (FREEZESTAT), WHICH
SHALL BE SERPENTINED ACROSS THE DOWNSTREAM FACE OF THE
HEATING COIL, SHALL STOP THE SUPPLY AND EXHAUST FANS, CLOSE THE
LOUVER OUTSIDE AIR, RELIEF AIR AND ERV EXHAUST AIR DAMPERS IF THE
COIL DISCHARGE TEMPERATURE FALLS BELOW 38°F. THE DX COOLING
SHALL BE DISABLED, AND THE HEATING COIL CONTROL VALVE SHALL BE
FULLY OPEN.
1. GENERATE AN ALARM IF FAN FAILS TO SHOW PROOF OF OPERATION.
2. GENERATE AN ALARM IF THE ROOM TEMPERATURE FALLS BELOW 60°F (ADJUSTABLE).
3. GENERATE ALARM IF FILTER SWITCH PRESSURE DROP EXCEEDS 0.75 IN H2O.
4. GENERATE ALARM IF TEMPERATURE FALLS BELOW 15°F.
5. GENERATE ALARM IF TEMPERATURE IS NOT ±5°F OF SET POINT.
S
S
T
FAN STATUS
CURRENT
SENSOR
FAN
START/STOP
FILTER
RA
FROM
BLDG
HEATING COIL
CONTROL VALVE
SA TO
BUILDING
SUPPLY AIR
TEMPERATURE
LT
FREEZESTAT
FILTER SWITCH
LOW TEMPERATURE FREEZESTAT
FILTER SWITCH
DP
OA
FROM
ERV
AHU RA DAMPER
M
S
S
RELIEF
DAMPER
M
EXHAUST
LOUVER
S
S
M
AHU OA
DAMPER
MIXING
BOX
RH
RHT
WALL MOUNTED
SPACE
TEMPERATURE
SENSOR
WALL MOUNTED
SPACE RELATIVE
HUMIDITY SENSOR
BUILDING OA
DAMPER
M
OUTSIDE
AIR
LOUVER
SPACE TEMPERATURE SENSOR
XX X
SPACE RELATIVE HUMIDITY SENSOR
XX X
RETURN AIR RELATIVE HUMIDITY SENSOR
XX X
AHU-1 OUTSIDE AIR DAMPER
BUILDING OUTSIDE AIR DAMPER
RETURN AIR
RELATIVE
HUMIDITY
SENSOR
AFMS
OUTSIDE AIRFLOW
MEASURING STATION.
INSTALL NEAR ATTIC
ACCESS DOOR
AHU-1 RETURN AIR DAMPER
OUTSIDE AIRFLOW MEASURING STATION
X
X X X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
RELIEF AIR DAMPER XX X
SCALE: N.T.S.
DIRECT DIGITAL CONTROL SYSTEM ARCHITECTURE
B14
CONTROL UNIT
HEATING HOT
WATER SYSTEM
CONTROL UNIT
AHU-1/ERV-1
METAL ENCLOSURE
W/ KEYED LOCK
JACE
DATA COMMUNICATIONS
PORT FOR LAPTOP
LCU-101 LCU-102 LCU-1XX
PROVIDE LOCAL CONTROL UNITS
AS REQUIRED TO CONTROL
RADIANT CEILING PANELS.
MOUNT CONTROLLERS ON WALL
ABOVE FIRST FLOOR CEILING
LOCAL CONTROL
UNIT (TYP)
METAL ENCLOSURE
W/ KEYED LOCK
CONTROL SYSTEM NON-IP
COMMUNICATION
NETWORK WIRING
ERV
AHU
RETURN FAN START/STOP
RETURN FAN STATUS CURRENT SENSOR 1X
X
X
X
X
X
X
CS
S
S
FAN STATUS
CURRENT
SENSOR
FAN
START/STOP
RF
US Army Corps of Engineers
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
A
B
C
D
E
F
G
H
J
K
L
M
N
P
SHEET ID
U S
A
R M
Y
C
O R
E
N G
I N
E E
R S
O T
T E
R
B
R O
K E
N E
W
O
P E
R A
T I O
F
I C
E
05 Nov, 2021 - 10:26am
Y:\22004.09\22004.09-M701.dwg
C O
N T
R O
L
D I A
G R
A M
S
OTTER BROOK
M-701
DRAWING NOTES:
1. ALARMS SHALL BE RECORDED AND STORED IN THE JACE
AND SHALL BE ANNUNCIATED ON THE GRAPHICAL USER
INTERFACE (GUI) WHEN CONNECTED.
2. SETTING, MODES, AND SET POINTS THAT ARE INDICATED
AS BEING ADJUSTABLE SHALL BE ADJUSTABLE BY THE
BUILDING OPERATORS THROUGH THE GUI WITHOUT THE
NEED TO CHANGE OR EDIT PROGRAMMING.
3. COMPLY WITH CYBER SECURITY REQUIREMENTS AND
PERFORM REQUIRED PROGRAMMING AND TESTING PER
SPECIFICATIONS.
4. CONTROL WIRING IN BASEMENT MUST BE IN CONDUIT.
5. PROVIDE LOCKABLE CONTROL PANELS.
6. DISABLE UNUSED COMMUNICATION PORTS ON ALL
DEVICES.
(ALL CONTROL DRAWINGS)
| Appendix B Page 1 |
| Appendix B |
| 06_Mechanical |
| MH100 |
| Sheets and Views |
| MH100 |
| MH101 |
| Sheets and Views |
| MH101 |
| M-301 |
| Sheets and Views |
| M-301 |
| M-501 |
| Sheets and Views |
| M-501 |
| M-502 |
| Sheets and Views |
| M-502 |
| M-503 |
| Sheets and Views |
| M-503 |
| M-601 |
| Sheets and Views |
| M-601 |
| M-602 |
| Sheets and Views |
| M-602 |
| M-701 |
| Sheets and Views |
| M-701 |
File details come from the government source that posted it. Updated .