ALLIED SUPPORT BUILDING 30 - FINAL ELECTRICAL PLANS.pdf

PDF 721 KB Posted

Attached to
117th Bld. 30 Electrical Project Federal contract opportunity
Solicitation number
BRKR202006
Issued by
Department of the Army Alabama Army National Guard

View the file

Other files for this federal contract opportunity

Other files attached to 117th Bld. 30 Electrical Project, newest first.
File Type Posted
OF 1419A Bld 30 page 2.pdf PDF
OF 1419 Bld 30 page 1 KO.pdf PDF
W50S6M-21-B-0003-P00001.pdf PDF
W50S6M-21-B-0003 Allied Support Bld 30 Electrical 8-20-2021.pdf PDF
Allied Support Building 30 Electrical Specifications.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

AutoCAD SHX Text

ESD-1

AutoCAD SHX Text

DEMOLITION NOTES

AutoCAD SHX Text

8. REPAIR ADJACENT CONSTRUCTION AND FINISHES DAMAGED DURING DEMOLITION AND EXTENSION WORK.

AutoCAD SHX Text

7. MAINTAIN ACCESS TO EXISTING ELECTRICAL INSTALLATIONS WHICH REMAIN ACTIVE.

AutoCAD SHX Text INSTALL WIRE, CONDUIT, AND ACCESSORIES TO RESTORE SERVICE TO REMAINING DEVICES AND

AutoCAD SHX Text

6. WHEN A CIRCUIT IS INTERRUPTED BY REMOVAL OF A DEVICE OR FIXTURE FROM THAT CIRCUIT, AutoCAD SHX Text

FINISHES. CUT CONDUIT FLUSH WITH WALLS AND FLOORS, AND PATCH SURFACES.

AutoCAD SHX Text

5. REMOVE EXPOSED ABANDONED CONDUIT INCLUDING ABANDONED CONDUIT ABOVE ACCESSIBLE CEILING

AutoCAD SHX Text

4. REMOVE ABANDONED WIRING TO SOURCE OF SUPPLY.

AutoCAD SHX Text

3. REMOVE ELECTRICAL EQUIPMENT NOT REQUIRED TO REMAIN IN SERVICE. RECONNECT EXISTING

AutoCAD SHX Text

2. PROVIDE TEMPORARY WIRING AND CONNECTIONS TO MAINTAIN EXISTING SYSTEMS IN SERVICE DURING

AutoCAD SHX Text

1. DISCONNECT ELECTRICAL SYSTEMS IN WALLS, FLOORS, AND CEILINGS SCHEDULED FOR REMOVAL.

AutoCAD SHX Text

FIXTURES ON THAT CIRCUIT.

AutoCAD SHX Text

CIRCUITS TO OTHER SOURCES OF SUPPLY.

AutoCAD SHX Text

CONSTRUCTION.

AutoCAD SHX Text

CONDITIONS.

AutoCAD SHX Text

3. CONTRACTOR SHALL PROVIDE A COMPLETE ELECTRICAL INSTALLATION INCLUDING ALL WORK CUSTOMARILY INCLUDED EVEN IF

AutoCAD SHX Text

4. THE ELECTRICAL CONTRACTOR SHALL CAREFULLY COORDINATE HIS WORK WITH OTHER CONTRACTORS THROUGH THE GENERAL

AutoCAD SHX Text

5. SHOULD THE CONTRACTOR FIND DISCREPANCIES OR OMISSIONS IN THE CONTRACT DOCUMENTS OR BE IN DOUBT AS TO

AutoCAD SHX Text

6. THE ELECTRICAL DRAWINGS ARE SCHEMATIC AND ARE NOT INTENDED TO SHOW THE EXACT LOCATION OF CONDUIT, OUTLETS, AutoCAD SHX Text ETC.. THE CONTRACTOR SHALL REFER TO ARCHITECTURAL, MECHANICAL AND PLUMBING DRAWINGS AND SHALL FIT HIS WORK TO

AutoCAD SHX Text

8. ALL OUTLET BOXES MOUNTED BACK-TO-BACK IN WALLS SHALL HAVE FIREPROOF SOUND INSULATING MATERIAL INSTALLED

AutoCAD SHX Text COMMUNICATIONS CIRCUITS ABOVE OR BELOW GRADE THAT WOULD OBSTRUCT CONSTRUCTION OF THE PROJECT OR CONFLICT IN

AutoCAD SHX Text ANY MANNER WITH COMPLETION OF THE PROJECT OR ANY CODE PERTAINING THERETO. IF UTILITY COMPANY REQUIREMENTS ARE

AutoCAD SHX Text AT A VARIANCE WITH THESE DRAWINGS AND SPECIFICATIONS, THE CONTRACT PRICE SHALL INCLUDE THE ADDITIONAL COST.

AutoCAD SHX Text CONDUCTORS. USE OF CONDUIT AS THE ONLY GROUND CONDUCTOR WILL NOT BE ALLOWED. SIZE GROUND CONDUCTORS PER

AutoCAD SHX Text

12. COORDINATE SERVICES WITH POWER AND COMMUNICATION COMPANIES. REMOVE OR RELOCATE ALL POWER AND

AutoCAD SHX Text

13. THIS CONTRACTOR SHALL INSTALL EQUIPMENT GROUNDS THROUGHOUT THIS PROJECT, USING GREEN INSULATED

AutoCAD SHX Text N.E.C..

AutoCAD SHX Text

CONFORM WITH THE BUILDING CONSTRUCTION AND WITH THE OTHER TRADES.

AutoCAD SHX Text

WALL SWITCHES.............................4'-0"

AutoCAD SHX Text

RECEPTACLES.................................1'-6"

AutoCAD SHX Text

7. MOUNTING HEIGHTS OF ALL WALL OUTLETS SHALL BE AS FOLLOWS UNLESS OTHERWISE INDICATED:

AutoCAD SHX Text

BETWEEN THE BOXES TO PREVENT SOUND TRANSMISSION FROM ONE ROOM TO ANOTHER.

AutoCAD SHX Text

CONTRACTOR FOR SPACE REQUIREMENTS, ETC.

AutoCAD SHX Text INTENT, HE SHALL IMMEDIATELY OBTAIN CLARIFICATION FROM THE ARCHITECT OR ENGINEER.

AutoCAD SHX Text

SEE SPECIFICATIONS FOR INSULATION TYPE.

AutoCAD SHX Text

9. BRANCH CIRCUITS SHALL BE #12 AWG AND 1/2" CONDUIT MINIMUM. CONDUCTORS SHALL BE 98%%% CONDUCTIVITY COPPER.

AutoCAD SHX Text

10. ALL CONDUITS CROSSING EXPANSION JOINTS SHALL HAVE EXPANSION TYPE FITTINGS.

AutoCAD SHX Text

11. VERIFY EXACT LOCATION OF ALL MOTORS AND EQUIPMENT BEFORE ROUGHING IN.

AutoCAD SHX Text

NOT SPECIFICALLY CALLED OUT.

AutoCAD SHX Text

1. ALL ELECTRICAL WORK SHALL BE DONE IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE AND LOCAL ORDINANCES.

AutoCAD SHX Text

2. CONTRACTOR SHALL VISIT THE SITE AND FAMILIARIZE HIMSELF WITH ALL DETAILS OF THE WORK AND ALL EXISTING FIELD

AutoCAD SHX Text

GENERAL NOTES

AutoCAD SHX Text

CONTRACTOR SHALL OBTAIN AND PAY FOR ALL NECESSARY PERMITS.

AutoCAD SHX Text

14. ALL UTILITY FEES ASSOCIATED WITH THIS PROJECT SHALL BE INCLUDED IN BID. IF THESE FEES CANNOT BE OBTAINED FROM

AutoCAD SHX Text

THE UTILITY PRIOR TO BID, THE CONTRACTOR SHALL INFORM THE ENGINEER IMMEDIATELY.

AutoCAD SHX Text

15. CONTRACTOR SHALL FIELD MARK ALL ELECTRICAL EQUIPMENT WITH ARC-FLASH WARNING LABELS PER NEC 110.16.

AutoCAD SHX Text

16. CONTRACTOR SHALL PROVIDE RECORD DRAWINGS AND MANUALS THAT PROVIDE INSTRUCTION ABOUT OPERATION AND MAINTENANCE

AutoCAD SHX Text OF THE BUILDING ELECTRICAL DISTRIBUTION SYSTEM TO THE OWNER WITHIN 30 DAYS AFTER THE DATE OF SYSTEM ACCEPTANCE.

AutoCAD SHX Text

17. CONTRACTOR SHALL COORDINATE VOLTAGE AND PHASE OF EACH PIECE OF ELECTRICAL EQUIPMENT WITH THE ELECTRICAL CONTRACTOR

AutoCAD SHX Text

PRIOR TO SUBMITTING AND ORDERING EQUIPMENT.

AutoCAD SHX Text

18. VERIFY EXACT LOCATION AND EXACT MOUNTING HEIGHT OF ALL ELECTRICAL EQUIPMENT AND ELECTRICAL CONNECTIONS WITH THE

AutoCAD SHX Text

ARCHITECT AND THE OWNER PRIOR TO ROUGH-IN.

AutoCAD SHX Text SHOP EQUIPMENT THAT WILL BE INSTALLED IN THIS BUILDING. CONTRACTOR SHALL VERIFY ALL EQUIPMENT POWER REQUIREMENTS

AutoCAD SHX Text

AND INSTALL NEW CIRCUITS AS REQUIRED.

AutoCAD SHX Text

19. CONTRACTOR SHALL PROVIDE CIRCUITS FROM NEW PANELS PPAH AND PPAL AS REQUIRED FOR OWNER'S SHEET METAL AND MACHINE

AutoCAD SHX Text

BRANCH CIRCUIT CONCEALED IN FLOOR OR GROUND.

AutoCAD SHX Text

BRANCH CIRCUIT CONCEALED IN WALL OR CEILING.

AutoCAD SHX Text HOMERUN TO PANELBOARD - ANY CIRCUIT WITHOUT FURTHER DESIGNATION 2 # 12 & 1 # 12(G) - 1/2" C.

AutoCAD SHX Text

ELECTRICAL SYMBOLS

AutoCAD SHX Text

3 # 12 & 1 # 12(G) - 3/4" CONDUIT.

AutoCAD SHX Text

LIGHTING PANEL - SEE SPECIFICATIONS AND SCHEDULE.

AutoCAD SHX Text

POWER PANELS - SEE SPECIFICATIONS AND SCHEDULE.

AutoCAD SHX Text

NATIONAL ELECTRICAL CODE.

AutoCAD SHX Text N.E.C.

AutoCAD SHX Text

ABOVE FINISHED FLOOR.

AutoCAD SHX Text

ABOVE FINISHED GRADE.

AutoCAD SHX Text

VERIFY LOCATION.

AutoCAD SHX Text A.F.G.

AutoCAD SHX Text A.F.F.

AutoCAD SHX Text

VER.

AutoCAD SHX Text

NON-FUSED DISCONNECT SWITCH. (RT - RAINTIGHT).

AutoCAD SHX Text

FUSED DISCONNECT SWITCH. (RT - RAINTIGHT).

AutoCAD SHX Text

4 # 12 & 1 # 12(G) - 3/4" CONDUIT.

AutoCAD SHX Text

SCALE: AS SHOWN

AutoCAD SHX Text

DATE: 8-12-21

AutoCAD SHX Text

DWG. NO.: ESD-1

AutoCAD SHX Text

BIRMINGHAM, ALABAMA

ALLIED SUPPORT BUILDING 3O ELECTRICAL

FINISHED GRADE

AutoCAD SHX Text

ELECTRICAL SINGLE LINE DIAGRAM

AutoCAD SHX Text N.T.S.

AutoCAD SHX Text

FINISHED FLOOR

AutoCAD SHX Text

ROOF

AutoCAD SHX Text

250-4WG

AutoCAD SHX Text

CABINET

AutoCAD SHX Text

EXISTING SECTIONALIZING

AutoCAD SHX Text

SEE NOTE 3

AutoCAD SHX Text

%%UNOTES:

AutoCAD SHX Text

1. SEE SCHEDULE ON THIS SHEET FOR WIRE SIZE. (TYP)

AutoCAD SHX Text

ESD-2

AutoCAD SHX Text

METER

AutoCAD SHX Text

3 %%C WIRE TAG

AutoCAD SHX Text

THREE PHASE FEEDER/EQUIPMENT

AutoCAD SHX Text

AMPS

AutoCAD SHX Text

3 #4/0 & 1 #4(G) IN 2" C.

AutoCAD SHX Text

225 W/ GND

AutoCAD SHX Text

225S-3WG

AutoCAD SHX Text

MISCELLANEOUS TAGS

AutoCAD SHX Text

METER

AutoCAD SHX Text

CONDUCTOR SCHEDULE

AutoCAD SHX Text

FEEDER/GROUND

AutoCAD SHX Text

250 W/ GND

AutoCAD SHX Text

250-4WG

AutoCAD SHX Text

4 #250 MCM & 1 #4(G) IN 2-1/2" C.

AutoCAD SHX Text

(150KVA)

AutoCAD SHX Text

%%UT-A

AutoCAD SHX Text

TO BUILDING STEEL

AutoCAD SHX Text

SGND 5

AutoCAD SHX Text

500S-4WG

AutoCAD SHX Text

225S-3WG

AutoCAD SHX Text

150 KVA TRANSFORMER.

AutoCAD SHX Text 480:120/208V, 3%%C, 4W

AutoCAD SHX Text

1 #2/0 CU IN 3/4" C.

AutoCAD SHX Text

SGND 6

AutoCAD SHX Text

500 W/ GND

AutoCAD SHX Text

500S-4WG

AutoCAD SHX Text

600 W/ GND

AutoCAD SHX Text 600-4W

AutoCAD SHX Text

2 RUNS OF 4 #350 MCM

AutoCAD SHX Text

IN (2)-3" C.

AutoCAD SHX Text

2 RUNS OF 4 #250 MCM & 1 #1/0(G)

AutoCAD SHX Text

IN (2) 2-1/2" C.

AutoCAD SHX Text

GROUNDING DETAIL

AutoCAD SHX Text N.T.S.

AutoCAD SHX Text

WELD

AutoCAD SHX Text

EXOTHERMIC

AutoCAD SHX Text

GROUND ROD (TYP)

AutoCAD SHX Text

3/4" X 10' COPPER

AutoCAD SHX Text

WELD (WHERE APPLICABLE)

AutoCAD SHX Text

GROUND BUS AT

AutoCAD SHX Text

SERVICE ENTRANCE

AutoCAD SHX Text

EQUIPMENT

AutoCAD SHX Text

METAL WITH EXOTHERMIC

AutoCAD SHX Text

BOND TO STRUCTURAL

AutoCAD SHX Text

WATER PIPE

AutoCAD SHX Text

METAL UNDERGROUND

AutoCAD SHX Text

#2/0 CU

AutoCAD SHX Text

AS INDICATED

AutoCAD SHX Text

TO BUILDING

AutoCAD SHX Text

REBAR

AutoCAD SHX Text

TBB(EX)

AutoCAD SHX Text

#6 CU

AutoCAD SHX Text

10' MIN

AutoCAD SHX Text

10' MIN

AutoCAD SHX Text

EX

AutoCAD SHX Text 277/480V, 3%%C, 4W.

AutoCAD SHX Text

EXISTING 200 KW DIESEL GENERATOR.

AutoCAD SHX Text G

AutoCAD SHX Text

350-4WG

AutoCAD SHX Text

(36" DEEP MIN.)

AutoCAD SHX Text

EX

AutoCAD SHX Text

MTS

AutoCAD SHX Text

600-4WG

AutoCAD SHX Text

(SEE DETAIL)

AutoCAD SHX Text

GROUND RODS

AutoCAD SHX Text

PER N.E.C.

AutoCAD SHX Text 600/3

AutoCAD SHX Text

MPA

AutoCAD SHX Text

SGND 6

AutoCAD SHX Text 600-4W

AutoCAD SHX Text

600A NEMA 3R

AutoCAD SHX Text

MANUAL TRANSFER

AutoCAD SHX Text

SWITCH

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text

2. REMOVE EXISTING NEUTRAL-TO-GROUND BOND. REMOVE EXISTING SERVICE CONDUCTORS FROM PADMOUNT

AutoCAD SHX Text

NEW METER SHALL HAVE REMOTE MONITORING CAPABILITIES AND

AutoCAD SHX Text

SHALL BE OPC COMPLIANT WITH A PULSE OUTPUT.

AutoCAD SHX Text

PPAH

AutoCAD SHX Text

MSP

AutoCAD SHX Text

(EX)

AutoCAD SHX Text

600-4WG

AutoCAD SHX Text

SEE NOTE 1

AutoCAD SHX Text

SEE NOTE 2

AutoCAD SHX Text

1-1/4" C. WITH METERING CONDUCTORS AS

AutoCAD SHX Text

REQUIRED.(30" DEEP MIN.)

AutoCAD SHX Text

(4)-1/2" DIA.X3" SELF DRILLING ANCHORS(TYP)

AutoCAD SHX Text

EQUIPMENT MOUNTING RACK DETAIL

AutoCAD SHX Text

N.TS.

AutoCAD SHX Text 12"X12"X1/2"

AutoCAD SHX Text

BASE PLATE

AutoCAD SHX Text

EACH SIDE

AutoCAD SHX Text

EXISTING CONRETE

AutoCAD SHX Text

SLAB

AutoCAD SHX Text 3'-0"

AutoCAD SHX Text 7'-0"

AutoCAD SHX Text

UNISTRUT(TYP FOR

AutoCAD SHX Text

MOUNTING EQUIPMENT.)

AutoCAD SHX Text

4" CHANNEL.(TYP OF

AutoCAD SHX Text

CROSS MEMBERS)

AutoCAD SHX Text

END POST 4"X4"X3/16"

AutoCAD SHX Text

TUBE STOCK W/ CAP

AutoCAD SHX Text

PLATE. PAINT ALL STEEL

AutoCAD SHX Text

ADJUST LENGTH AS REQUIRED

AutoCAD SHX Text

IF OVER 6', ADD CENTER STANTION

AutoCAD SHX Text

SAME AS END POSTS

AutoCAD SHX Text

600 W/ GND

AutoCAD SHX Text

600-4WG

AutoCAD SHX Text

2 RUNS OF 4 #350 MCM & 1 #1(G)

AutoCAD SHX Text

IN (2)-3" C.

AutoCAD SHX Text

%%UMECH. EQUIP.

AutoCAD SHX Text

%%UELECTRICAL

AutoCAD SHX Text %%U30-06

AutoCAD SHX Text %%U30-07

AutoCAD SHX Text

INSTALL NEW EQUIPMENT RACK AS REQUIRED. SEE

AutoCAD SHX Text

DETAIL ON THIS SHEET

AutoCAD SHX Text (S1)

AutoCAD SHX Text

PPAH

AutoCAD SHX Text (S2)

AutoCAD SHX Text

PPAL

AutoCAD SHX Text (S2)

AutoCAD SHX Text

PPAL

AutoCAD SHX Text (S1)

AutoCAD SHX Text

350 W/ GND

AutoCAD SHX Text

350-4WG

AutoCAD SHX Text

4 #500 MCM & 1 #3(G) IN 3-1/2" C.

AutoCAD SHX Text

1 #1/0 CU IN 3/4" C.

AutoCAD SHX Text

SGND 5

AutoCAD SHX Text

BUTT-WELD JOINTS

AutoCAD SHX Text

ANSI 61 GRAY.

AutoCAD SHX Text

3. REPLACE EXISTING 150 KVA PADMOUNT TRANSFORMER WITH A 500 KVA PADMOUNT

AutoCAD SHX Text

TRANSFORMER, 13,200:277/480 V, 3 PHASE, 4 WIRE AS REQUIRED. REPLACE CONCRETE

AutoCAD SHX Text

PAD AS REQUIRED FOR NEW PADMOUNT. CONTRACTOR SHALL LOCATE NEW TRANSFORMER

AutoCAD SHX Text SUCH THAT EXISTING PRIMARY CONDUCTORS CAN BE REUSED. TURN EXISTING PADMOUNT TRANSFORMER

AutoCAD SHX Text

OVER TO THE OWNER.

AutoCAD SHX Text

SCALE: AS SHOWN

AutoCAD SHX Text

DATE: 8-12-21

AutoCAD SHX Text

DWG. NO.: ESD-2

AutoCAD SHX Text

BIRMINGHAM, ALABAMA

AutoCAD SHX Text

ALLIED SUPPORT BUILDING 3O ELECTRICAL

TRANSFOMER AS REQUIRED.

MOUNTING

AutoCAD SHX Text

SERVICE

AutoCAD SHX Text

TYPE

AutoCAD SHX Text

MARK

AutoCAD SHX Text

AMPS

AutoCAD SHX Text

TYPE

AutoCAD SHX Text

MAINS

AutoCAD SHX Text

SPARES

AutoCAD SHX Text

2 POLE

AutoCAD SHX Text

1 POLE

AutoCAD SHX Text

3 POLE

AutoCAD SHX Text

BRANCHES

AutoCAD SHX Text

SPACES

AutoCAD SHX Text

LOCATION

AutoCAD SHX Text

LUG

AutoCAD SHX Text

REMARKS

AutoCAD SHX Text

AIC

AutoCAD SHX Text

MINIMUM

AutoCAD SHX Text

RATING

AutoCAD SHX Text

TYPE

AutoCAD SHX Text

PANELBOARD SCHEDULE

AutoCAD SHX Text

AutoCAD SHX Text

SURFACE

AutoCAD SHX Text

VERIFY WITH

AutoCAD SHX Text

PADMOUNT

AutoCAD SHX Text 3%%C, 4W

AutoCAD SHX Text 277/480V

AutoCAD SHX Text

MLO

AutoCAD SHX Text

MB

AutoCAD SHX Text

MPA

AutoCAD SHX Text

PPAH

AutoCAD SHX Text

AutoCAD SHX Text 3-20/3

AutoCAD SHX Text

2. PANEL SHALL BE EQUIPPED WITH BUILT-IN SURGE PROTECTION, CAPABLE OF WITHSTANDING A TRANSIENT SURGE OF 160,000 AMPS.

AutoCAD SHX Text

1. PANEL SHALL BE RATED FOR SERVICE ENTRANCE EQUIPMENT.

AutoCAD SHX Text

3. PANEL SHALL BE FULLY RATED AND SHALL HAVE A HINGED FRONT TRIM.

AutoCAD SHX Text

%%UNOTES:

AutoCAD SHX Text

4. PANEL SHALL BE FULLY RATED AND NEMA 3R RATED.

AutoCAD SHX Text

ENCL.

AutoCAD SHX Text

CKT.

AutoCAD SHX Text

BOTTOM

AutoCAD SHX Text

SEE NOTES 1 & 4

AutoCAD SHX Text

TOP

AutoCAD SHX Text

SURFACE

AutoCAD SHX Text

PPAL

AutoCAD SHX Text

NQOD

AutoCAD SHX Text

MB

AutoCAD SHX Text

AutoCAD SHX Text 3%%C, 4W

AutoCAD SHX Text 120/208V

AutoCAD SHX Text

BOTTOM

AutoCAD SHX Text

SURFACE

AutoCAD SHX Text

SEE NOTES 2, 3, 5 & 6

AutoCAD SHX Text

(TWO SECTION PANEL)

AutoCAD SHX Text 5-20

AutoCAD SHX Text

SEE NOTES 3 & 5

AutoCAD SHX Text

(TWO SECTION PANEL)

AutoCAD SHX Text

15-1PS

AutoCAD SHX Text 1-15

AutoCAD SHX Text 1-40

AutoCAD SHX Text 1-60

AutoCAD SHX Text 1-30

AutoCAD SHX Text 3-20

AutoCAD SHX Text 5-15

AutoCAD SHX Text 1-100

AutoCAD SHX Text 1-15

AutoCAD SHX Text 5-20

AutoCAD SHX Text 7-30

AutoCAD SHX Text 1-40

AutoCAD SHX Text 1-80

AutoCAD SHX Text

ESD-3

AutoCAD SHX Text

TRANSFORMER SCHEDULE

AutoCAD SHX Text

1. BOND TRANSFORMER LOWSIDE NEUTRAL TO THE TRANSFORMER CASE, TO THE "INCOMING" AND "OUTGOING" GROUND WIRES, AND TO

AutoCAD SHX Text GROUNDING ELECTRODE (AS PER NEC 250-30) AT EACH TRANSFORMER AS INDICATED ON THE SINGLE LINE DIAGRAM.

AutoCAD SHX Text

%%UNOTES:

AutoCAD SHX Text

SEE NOTE 1

AutoCAD SHX Text

REMARKS

AutoCAD SHX Text

120/208V 3%%C, 4W, WYE

AutoCAD SHX Text

SECONDARY

AutoCAD SHX Text T-A

AutoCAD SHX Text

MARK

AutoCAD SHX Text

SIZE

AutoCAD SHX Text

480V 3%%C DELTA

AutoCAD SHX Text

PRIMARY

AutoCAD SHX Text

MANUFACTURER

AutoCAD SHX Text

SQUARE D

AutoCAD SHX Text

CATALOG NUMBER

AutoCAD SHX Text

EX150T3H

AutoCAD SHX Text

150 KVA

AutoCAD SHX Text

PANEL LABEL DETAIL

AutoCAD SHX Text

N.T.S. (TYPICAL)

AutoCAD SHX Text

MPA

AutoCAD SHX Text 277/480V, 3%%C, 4W

AutoCAD SHX Text 3"

AutoCAD SHX Text

4" WIDE MICARTA

AutoCAD SHX Text

LABEL

AutoCAD SHX Text

BLACK)

AutoCAD SHX Text

(WHITE ON

AutoCAD SHX Text

3/8" TEXT

AutoCAD SHX Text

BLACK)

AutoCAD SHX Text

(WHITE ON

AutoCAD SHX Text

1/2" TEXT

AutoCAD SHX Text

INDICATE VOLTAGE, NO. OF PHASES

AutoCAD SHX Text

AND NO. OF WIRES

AutoCAD SHX Text

ATTACH LABEL WITH

AutoCAD SHX Text

STAINLESS STEEL

AutoCAD SHX Text

SCREWS

AutoCAD SHX Text

FED FROM

AutoCAD SHX Text

XXX

AutoCAD SHX Text

INDICATE SWITCHBOARD/PANEL

AutoCAD SHX Text

WHERE FEE ORIGINATES.

AutoCAD SHX Text

5. CONTRACTOR SHALL VERIFY ALL BREAKER SIZES FOR ALL EQUIPMENT IN THIS PANEL PRIOR TO ORDERING.

AutoCAD SHX Text

SCALE: AS SHOWN

AutoCAD SHX Text

DATE: 8-12-21

AutoCAD SHX Text

DWG. NO.: ESD-3

AutoCAD SHX Text

BIRMINGHAM, ALABAMA

AutoCAD SHX Text

ALLIED SUPPORT BUILDING 3O ELECTRICAL

AutoCAD SHX Text 1-600

AutoCAD SHX Text

BRKR.

AutoCAD SHX Text 1-25

AutoCAD SHX Text

5-3PS

AutoCAD SHX Text

ELECTRICAL SITE PLAN

AutoCAD SHX Text N.T.S.

AutoCAD SHX Text

EXISTING GENERATOR. SEE PHOTO

AutoCAD SHX Text

TRANSFORMER

AutoCAD SHX Text

VERIFY WITH

AutoCAD SHX Text

PADMOUNT

AutoCAD SHX Text

TRANSFORMER

AutoCAD SHX Text

VERIFY WITH

AutoCAD SHX Text

PADMOUNT

AutoCAD SHX Text

TRANSFORMER

AutoCAD SHX Text 3%%C, 4W

AutoCAD SHX Text 277/480V

AutoCAD SHX Text

%%UNOTES:

AutoCAD SHX Text

1. CONTRACTOR SHALL CUT AND PATCH EXISTING CONCRETE

AutoCAD SHX Text

AND ASPHALT AS REQUIRED TO INSTALL NEW FEEDERS

AutoCAD SHX Text

AND SERVICE ENTRANCE CONDUCTORS.

AutoCAD SHX Text 1-40

AutoCAD SHX Text 1-60

AutoCAD SHX Text 1-250

AutoCAD SHX Text 1-225

AutoCAD SHX Text 6-20/1

AutoCAD SHX Text 3-20/3

AutoCAD SHX Text

I-LINE

AutoCAD SHX Text

(HCW)

AutoCAD SHX Text

6. I-LINE PANELBOARD SHALL HAVE MICARTA LABELS BESIDE EACH BREAKER, INDICATING LOAD SERVED.

AutoCAD SHX Text

2. REPLACE EXISTING 150 KVA PADMOUNT TRANSFORMER WITH A

AutoCAD SHX Text

500 KVA PADMOUNT TRANSFORMER, 13,200:277/480 V, 3

AutoCAD SHX Text

PHASE, 4 WIRE AS REQUIRED. CONTRACTOR SHALL MODIFY

AutoCAD SHX Text

EXISTING PRIMARY AS REQUIRED TO CONNECT NEW

AutoCAD SHX Text

TRANSFORMER. FUSE TRANSFORMER PER MANUFACTURERS

AutoCAD SHX Text

RECOMMENDATIONS. SEE PHOTO #1 ON SHEET ESD-4 FOR

AutoCAD SHX Text

#2 ON SHEET ESD-4.

AutoCAD SHX Text

SEE NOTE 2

AutoCAD SHX Text

EXISTING PADMOUNT TRANSFORMER CONDITIONS.

SEE NOTE 1

30-9A

AutoCAD SHX Text

COMPUTER

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

FE

AutoCAD SHX Text

EXISTING

AutoCAD SHX Text

FE

AutoCAD SHX Text

EXISTING

AutoCAD SHX Text

FE

AutoCAD SHX Text

EXISTING

AutoCAD SHX Text

FE

AutoCAD SHX Text

EXISTING

AutoCAD SHX Text 30-14

AutoCAD SHX Text

REPAIR & RECLAIM

AutoCAD SHX Text

WOMEN

AutoCAD SHX Text 30-04

AutoCAD SHX Text 30-06

AutoCAD SHX Text

MECH. EQUIPMENT

AutoCAD SHX Text 30-08

AutoCAD SHX Text

ENGINE SHOP

AutoCAD SHX Text

ENGINE SHOP OFFICE

AutoCAD SHX Text 30-09

AutoCAD SHX Text 30-10

AutoCAD SHX Text 30-12

AutoCAD SHX Text

MAINTENANCE

AutoCAD SHX Text

NON-POWERED AGE

AutoCAD SHX Text 30-13

AutoCAD SHX Text

EXISTING FE

AutoCAD SHX Text

STORAGE

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text 30-05

AutoCAD SHX Text 30-02

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text 30-03

AutoCAD SHX Text

MEN

AutoCAD SHX Text 8A

AutoCAD SHX Text

BREAK ROOM

AutoCAD SHX Text 30-01

AutoCAD SHX Text 30-11

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

ELEC. ROOM

AutoCAD SHX Text 30-07

AutoCAD SHX Text (G.F.C.I.)

AutoCAD SHX Text

OVEN

AutoCAD SHX Text

ELECTRIC

AutoCAD SHX Text

BEAD

AutoCAD SHX Text

BREAKER

AutoCAD SHX Text (G.F.C.I.)

AutoCAD SHX Text (G.F.C.I.)

AutoCAD SHX Text

HOTSEY

AutoCAD SHX Text

WASHER

AutoCAD SHX Text

MECH. MEZZANINE

AutoCAD SHX Text

SEE DTAIL 2/A1

AutoCAD SHX Text

EXISTING LADDER

AutoCAD SHX Text

TO MEZZANINE.

AutoCAD SHX Text 13A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 15G

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 44A

AutoCAD SHX Text

AutoCAD SHX Text 7C

AutoCAD SHX Text

ESD-4

AutoCAD SHX Text

SCALE: AS SHOWN

AutoCAD SHX Text

DATE: 8-12-21

AutoCAD SHX Text

DWG. NO.: ESD-4

AutoCAD SHX Text

BIRMINGHAM, ALABAMA

AutoCAD SHX Text

ALLIED SUPPORT BUILDING 3O ELECTRICAL

AutoCAD SHX Text

%%UMSP(EX)

AutoCAD SHX Text

BUILDING 30 ELECTRICAL PLAN

AutoCAD SHX Text

SCALE: 1/16" = 1'-0"

AutoCAD SHX Text

INSTALL NEW EQUIPMENT ON NEW EQUIPMENT RACK AS

AutoCAD SHX Text

REQUIRED. VERIFY EXACT RACK LOCATION WITH THE

AutoCAD SHX Text

%%UPPAH

AutoCAD SHX Text

%%UPPAL

AutoCAD SHX Text

%%UT-A

AutoCAD SHX Text

%%UMPA

AutoCAD SHX Text

%%UMTS

AutoCAD SHX Text

COORDINATE ALL EQUIPMENT LOCATIONS WITH

AutoCAD SHX Text

THE OWNER

AutoCAD SHX Text

OWNER. SEE SINGLE LINE DIAGRAM AND EQUIPMENT

AutoCAD SHX Text

PHOTO #1

AutoCAD SHX Text

PHOTO #2

AutoCAD SHX Text

1. APPROXIMATE LOCATION OF NEW

AutoCAD SHX Text

ENCLOSED CIRCUIT BREAKER (MPA)

AutoCAD SHX Text

AND MANUAL TRANSFER SWITCH (MTS).

AutoCAD SHX Text

(VER.)

AutoCAD SHX Text SHOP EQUIPMENT THAT WILL BE INSTALLED IN THIS BUILDING. CONTRACTOR SHALL VERIFY ALL EQUIPMENT POWER REQUIREMENTS

AutoCAD SHX Text

AND INSTALL NEW CIRCUITS AS REQUIRED.

AutoCAD SHX Text

1. CONTRACTOR SHALL PROVIDE CIRCUITS FROM NEW PANELS PPAH AND PPAL AS REQUIRED FOR OWNER'S SHEET METAL AND MACHINE

AutoCAD SHX Text

SEE NOTE 1

AutoCAD SHX Text

%%UNOTES:

AutoCAD SHX Text

%%UNOTES:

AutoCAD SHX Text

(EXISTING PADMOUNT TRANSFOMER)

RACK DETAIL.

E-2124-1
Sheets and Views
Model
E-2124-2
Sheets and Views
Model
E-2124-3
Sheets and Views
Model
E-2124-4
Sheets and Views
Model

File details come from the government source that posted it. Updated .