Allied Support Building 30 Electrical Specifications.pdf
PDF 291 KB Posted
- Attached to
- 117th Bld. 30 Electrical Project Federal contract opportunity
- Solicitation number
- BRKR202006
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| OF 1419A Bld 30 page 2.pdf | ||
| OF 1419 Bld 30 page 1 KO.pdf | ||
| W50S6M-21-B-0003-P00001.pdf | ||
| W50S6M-21-B-0003 Allied Support Bld 30 Electrical 8-20-2021.pdf | ||
| ALLIED SUPPORT BUILDING 30 - FINAL ELECTRICAL PLANS.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
BASIC ELECTRICAL MATERIALS AND METHODS 26 0518 - 1
SECTION 26 0518 - BASIC ELECTRICAL MATERIALS AND METHODS
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section.
1.2 SUMMARY
A. This Section includes the following:
1. Supporting devices for electrical components.
2. Electrical identification.
3. Electricity-metering components.
4. Concrete equipment bases.
5. Electrical demolition.
6. Cutting and patching for electrical construction.
7. Touchup painting.
1.3 QUALITY ASSURANCE
A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for intended use.
B. Comply with NFPA 70.
1.4 COORDINATION
A. Coordinate chases, slots, inserts, sleeves, and openings with general construction work and arrange in building structure during progress of construction to facilitate the electri-cal installations that follow.
1. Set inserts and sleeves in poured-in-place concrete, masonry work, and other structural components as they are constructed.
B. Sequence, coordinate, and integrate installing electrical materials and equipment for ef-ficient flow of the Work. Coordinate installing large equipment requiring positioning before closing in the building.
BASIC ELECTRICAL MATERIALS AND METHODS 26 0518 - 2
C. Coordinate electrical service connections to components furnished by utility companies.
1. Coordinate installation and connection of exterior underground and overhead util-ities and services, including provision for electricity-metering components.
2. Comply with requirements of authorities having jurisdiction and of utility compa-ny providing electrical power and other services.
D. Coordinate location of access panels and doors for electrical items that are concealed by finished surfaces. Access doors and panels are specified in Division 8 Section "Access Doors."
E. Where electrical identification devices are applied to field-finished surfaces, coordinate installation of identification devices with completion of finished surface.
F. Where electrical identification markings and devices will be concealed by acoustical ceilings and similar finishes, coordinate installation of these items before ceiling instal-lation.
PART 2 - PRODUCTS
2.1 SUPPORTING DEVICES
A. Material: Cold-formed steel, with corrosion-resistant coating acceptable to authorities having jurisdiction.
B. Metal Items for Use Outdoors or in Damp Locations: Hot-dip galvanized steel.
C. Slotted-Steel Channel Supports: Flange edges turned toward web, and 9/16-inch- (14-mm-) diameter slotted holes at a maximum of 2 inches (50 mm) o.c., in webs.
1. Channel Thickness: Selected to suit structural loading.
2. Fittings and Accessories: Products of the same manufacturer as channel supports.
D. Raceway and Cable Supports: Manufactured clevis hangers, riser clamps, straps, threaded C-clamps with retainers, ceiling trapeze hangers, wall brackets, and spring-steel clamps or click-type hangers.
E. Pipe Sleeves: ASTM A 53, Type E, Grade A, Schedule 40, galvanized steel, plain ends.
F. Cable Supports for Vertical Conduit: Factory-fabricated assembly consisting of thread-ed body and insulating wedging plug for nonarmored electrical cables in riser conduits.
Plugs have number and size of conductor gripping holes as required to suit individual risers. Body constructed of malleable-iron casting with hot-dip galvanized finish.
G. Expansion Anchors: Carbon-steel wedge or sleeve type.
H. Toggle Bolts: All-steel springhead type.
BASIC ELECTRICAL MATERIALS AND METHODS 26 0518 - 3
I. Powder-Driven Threaded Studs: Heat-treated steel.
2.2 ELECTRICAL IDENTIFICATION
A. Identification Devices: A single type of identification product for each application cat-egory. Use colors prescribed by ANSI A13.1, NFPA 70, and these Specifications.
B. Underground Warning Tape: Permanent, bright-colored, continuous-printed, vinyl tape with the following features:
1. Not less than 6 inches wide by 4 mils thick (150 mm wide by 0.102 mm thick).
2. Compounded for permanent direct-burial service.
3. Embedded continuous metallic strip or core.
4. Printed legend that indicates type of underground line.
C. Tape Markers for Wire: Vinyl or vinyl-cloth, self-adhesive, wraparound type with pre-printed numbers and letters.
D. Color-Coding Cable Ties: Type 6/6 nylon, self-locking type. Colors to suit coding scheme.
E. Engraved-Plastic Labels, Signs, and Instruction Plates: Engraving stock, melamine plastic laminate punched or drilled for mechanical fasteners 1/16-inch (1.6-mm) mini-mum thickness for signs up to 20 sq. in. (129 sq. cm) and 1/8-inch (3.2-mm) minimum thickness for larger sizes. Engraved legend in black letters on white background.
F. Interior Warning and Caution Signs: Comply with 29 CFR, Chapter XVII, Part 1910.145. Preprinted, aluminum, baked-enamel-finish signs, punched or drilled for mechanical fasteners, with colors, legend, and size appropriate to the application.
G. Exterior Warning and Caution Signs: Comply with 29 CFR, Chapter XVII, Part 1910.145. Weather-resistant, nonfading, preprinted, cellulose-acetate butyrate signs with 0.0396-inch (1-mm), galvanized-steel backing, with colors, legend, and size appropriate to the application. 1/4-inch (6-mm) grommets in corners for mounting.
H. Fasteners for Nameplates and Signs: Self-tapping, stainless-steel screws or No. 10/32 stainless-steel machine screws with nuts and flat and lock washers.
2.3 EQUIPMENT FOR ELECTRICITY METERING
A. Meter: Comply with base requirements. Meter shall have remote monitoring capabili-ties and shall be OPC compliant with pulse output.
2.4 CONCRETE BASES
BASIC ELECTRICAL MATERIALS AND METHODS 26 0518 - 4
A. Concrete Forms and Reinforcement Materials: As specified in Division 3 Section "Cast-in-Place Concrete."
B. Concrete: 3000-psi (20.7-MPa), 28-day compressive strength as specified in Division 3 Section "Cast-in-Place Concrete."
2.5 TOUCHUP PAINT
A. For Equipment: Equipment manufacturer's paint selected to match installed equipment finish.
B. Galvanized Surfaces: Zinc-rich paint recommended by item manufacturer.
PART 3 - EXECUTION
3.1 ELECTRICAL EQUIPMENT INSTALLATION
A. Headroom Maintenance: If mounting heights or other location criteria are not indicat-ed, arrange and install components and equipment to provide the maximum possible headroom.
B. Materials and Components: Install level, plumb, and parallel and perpendicular to other building systems and components, unless otherwise indicated.
C. Equipment: Install to facilitate service, maintenance, and repair or replacement of com-ponents. Connect for ease of disconnecting, with minimum interference with other in-stallations.
D. Right of Way: Give to raceways and piping systems installed at a required slope.
3.2 WIRING INSTALLATION
A. Install splices and taps that are compatible with conductor material and that possess equivalent or better mechanical strength and insulation ratings than unspliced conduc-tors.
B. Install wiring at outlets with at least 12 inches (300 mm) of slack conductor at each out-let.
C. Connect outlet and component connections to wiring systems and to ground. Tighten electrical connectors and terminals, according to manufacturer's published torque-tightening values. If manufacturer's torque values are not indicated, use those specified in UL 486A.
BASIC ELECTRICAL MATERIALS AND METHODS 26 0518 - 5
3.3 ELECTRICAL SUPPORTING DEVICE APPLICATION
A. Damp Locations and Outdoors: Hot-dip galvanized materials or nonmetallic, U-channel system components.
B. Dry Locations: Steel materials.
C. Support Clamps for PVC Raceways: Click-type clamp system.
D. Selection of Supports: Comply with manufacturer's written instructions.
E. Strength of Supports: Adequate to carry present and future loads, times a safety factor of at least four; minimum of 200-lb (90-kg) design load.
3.4 SUPPORT INSTALLATION
A. Install support devices to securely and permanently fasten and support electrical com-ponents.
B. Install individual and multiple raceway hangers and riser clamps to support raceways.
Provide U-bolts, clamps, attachments, and other hardware necessary for hanger assem-blies and for securing hanger rods and conduits.
C. Support parallel runs of horizontal raceways together on trapeze- or bracket-type hang-ers.
D. Size supports for multiple raceway installations so capacity can be increased by a 25 percent minimum in the future.
E. Support individual horizontal raceways with separate, malleable-iron pipe hangers or clamps.
F. Install 1/4-inch- (6-mm-) diameter or larger threaded steel hanger rods, unless otherwise indicated.
G. Spring-steel fasteners specifically designed for supporting single conduits or tubing may be used instead of malleable-iron hangers for 3/4-inch and smaller raceways serving lighting and receptacle branch circuits above suspended ceilings and for fastening race-ways to slotted channel and angle supports.
H. Arrange supports in vertical runs so the weight of raceways and enclosed conductors is carried entirely by raceway supports, with no weight load on raceway terminals.
I. Simultaneously install vertical conductor supports with conductors.
J. Separately support cast boxes that are threaded to raceways and used for fixture support.
Support sheet-metal boxes directly from the building structure or by bar hangers. If bar
BASIC ELECTRICAL MATERIALS AND METHODS 26 0518 - 6
hangers are used, attach bar to raceways on opposite sides of the box and support the raceway with an approved fastener not more than 24 inches (610 mm) from the box.
K. Install metal channel racks for mounting cabinets, panelboards, disconnect switches, control enclosures, pull and junction boxes, transformers, and other devices unless components are mounted directly to structural elements of adequate strength.
L. Install sleeves for cable and raceway penetrations of concrete slabs and walls unless core-drilled holes are used. Install sleeves for cable and raceway penetrations of ma-sonry and fire-rated gypsum walls and of all other fire-rated floor and wall assemblies.
Install sleeves during erection of concrete and masonry walls.
M. Securely fasten electrical items and their supports to the building structure, unless oth-erwise indicated. Perform fastening according to the following unless other fastening methods are indicated:
1. Wood: Fasten with wood screws or screw-type nails.
2. Masonry: Toggle bolts on hollow masonry units and expansion bolts on solid masonry units.
3. New Concrete: Concrete inserts with machine screws and bolts.
4. Existing Concrete: Expansion bolts.
5. Instead of expansion bolts, threaded studs driven by a powder charge and provid-ed with lock washers may be used in existing concrete.
6. Steel: Welded threaded studs or spring-tension clamps on steel.
a. Field Welding: Comply with AWS D1.1.
7. Welding to steel structure may be used only for threaded studs, not for conduits, pipe straps, or other items.
8. Light Steel: Sheet-metal screws.
9. Fasteners: Select so the load applied to each fastener does not exceed 25 percent of its proof-test load.
3.5 IDENTIFICATION MATERIALS AND DEVICES
A. Install at locations for most convenient viewing without interference with operation and maintenance of equipment.
B. Coordinate names, abbreviations, colors, and other designations used for electrical iden-tification with corresponding designations indicated in the Contract Documents or re-quired by codes and standards. Use consistent designations throughout Project.
C. Self-Adhesive Identification Products: Clean surfaces before applying.
D. Tag and label circuits designated to be extended in the future. Identify source and cir-cuit numbers in each cabinet, pull and junction box, and outlet box. Color-coding may be used for voltage and phase identification.
BASIC ELECTRICAL MATERIALS AND METHODS 26 0518 - 7
E. Install continuous underground plastic markers during trench backfilling, for exterior underground power, control, signal, and communication lines located directly above power and communication lines. Locate 6 to 8 inches (150 to 200 mm) below finished grade. If width of multiple lines installed in a common trench or concrete envelope does not exceed 16 inches (400 mm), overall, use a single line marker.
F. Install warning, caution, and instruction signs where required to comply with 29 CFR, Chapter XVII, Part 1910.145, and where needed to ensure safe operation and mainte-nance of electrical systems and of items to which they connect. Install engraved plastic-laminated instruction signs with approved legend where instructions are needed for sys-tem or equipment operation. Install metal-backed butyrate signs for outdoor items.
3.6 ELECTRICITY-METERING EQUIPMENT
A. Install equipment according to base requirements. Provide grounding and conduits as required by the base.
3.7 FIRESTOPPING
A. Apply firestopping to cable and raceway penetrations of fire-rated floor and wall as-semblies to achieve fire-resistance rating of the assembly. The firestopping shall be made in accordance with a UL listed assembly.
3.8 CONCRETE BASES
A. Construct concrete bases of dimensions indicated, but not less than 4 inches (100 mm) larger, in both directions, than supported unit. Follow supported equipment manufac-turer's anchorage recommendations and setting templates for anchor-bolt and tie loca-tions, unless otherwise indicated. Use 3000-psi (20.7-MPa), 28-day compressive-strength concrete and reinforcement as specified in Division 3 Section "Cast-in-Place Concrete."
3.9 DEMOLITION
A. Protect existing electrical equipment and installations indicated to remain. If damaged or disturbed in the course of the Work, remove damaged portions and install new prod-ucts of equal capacity, quality, and functionality.
B. Accessible Work: Remove exposed electrical equipment and installations, indicated to be demolished, in their entirety.
C. Abandoned Work: Cut and remove buried raceway and wiring, indicated to be aban-doned in place, 2 inches (50 mm) below the surface of adjacent construction. Cap raceways and patch surface to match existing finish.
BASIC ELECTRICAL MATERIALS AND METHODS 26 0518 - 8
D. Remove demolished material from Project site.
E. Remove, store, clean, reinstall, reconnect, and make operational components indicated for relocation.
3.10 CUTTING AND PATCHING
A. Cut, channel, chase, and drill floors, walls, partitions, ceilings, and other surfaces re-quired to permit electrical installations. Perform cutting by skilled mechanics of trades involved.
B. Repair and refinish disturbed finish materials and other surfaces to match adjacent un-disturbed surfaces. Install new fireproofing where existing firestopping has been dis-turbed. Repair and refinish materials and other surfaces by skilled mechanics of trades involved.
3.11 FIELD QUALITY CONTROL
A. Inspect installed components for damage and faulty work, including the following:
1. Supporting devices for electrical components.
2. Electrical identification.
3. Electricity-metering components.
4. Concrete bases.
5. Electrical demolition.
6. Cutting and patching for electrical construction.
7. Touchup painting.
3.12 REFINISHING AND TOUCHUP PAINTING
A. Refinish and touch up paint.
1. Clean damaged and disturbed areas and apply primer, intermediate, and finish coats to suit the degree of damage at each location.
2. Follow paint manufacturer's written instructions for surface preparation and for timing and application of successive coats.
3. Repair damage to galvanized finishes with zinc-rich paint recommended by man-ufacturer.
4. Repair damage to PVC or paint finishes with matching touchup coating recom-mended by manufacturer.
3.13 CLEANING AND PROTECTION
A. On completion of installation, including outlets, fittings, and devices, inspect exposed finish. Remove burrs, dirt, paint spots, and construction debris.
BASIC ELECTRICAL MATERIALS AND METHODS 26 0518 - 9
B. Protect equipment and installations and maintain conditions to ensure that coatings, fin-ishes, and cabinets are without damage or deterioration at time of Substantial Comple-tion.
END OF SECTION 26 0518
CONDUCTORS AND CABLES 26 0519 - 1
SECTION 26 0519 - CONDUCTORS AND CABLES
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section.
1.2 SUMMARY
A. This Section includes building wires and cables and associated connectors, splices, and terminations for wiring systems rated 600 V and less.
1.3 SUBMITTALS
A. Field Test Reports: Indicate and interpret test results for compliance with performance requirements.
1.4 QUALITY ASSURANCE
A. Listing and Labeling: Provide wires and cables specified in this Section that are listed and labeled.
1. The Terms "Listed" and "Labeled": As defined in NFPA 70, Article 100.
2. Listing and Labeling Agency Qualifications: A "Nationally Recognized Testing
Laboratory" as defined in OSHA Regulation 1910.7.
B. Comply with NFPA 70.
1.5 DELIVERY, STORAGE, AND HANDLING
A. Deliver wires and cables according to NEMA WC 26.
1.6 COORDINATION
A. Coordinate layout and installation of cables with other installations.
B. Revise locations and elevations from those indicated, as required to suit field conditions and as approved by Architect.
CONDUCTORS AND CABLES 26 0519 - 2
PART 2 - PRODUCTS
2.1 MANUFACTURERS
A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
1. Wires and Cables:
a. American Insulated Wire Corp.; Leviton Manufacturing Co.
b. BICC Brand-Rex Company.
c. Senator Wire & Cable Company.
d. Southwire Company.
2. Connectors for Wires and Cables:
a. AMP Incorporated.
b. General Signal; O-Z/Gedney Unit.
c. Monogram Co.; AFC.
d. Square D Co.; Anderson.
e. 3M Company; Electrical Products Division.
2.2 BUILDING WIRES AND CABLES
A. UL-listed building wires and cables with conductor material, insulation type, cable con-struction, and rating as specified in Part 3 "Wire and Insulation Applications" Article.
B. Rubber Insulation Material: Comply with NEMA WC 3.
C. Thermoplastic Insulation Material: Comply with NEMA WC 5.
D. Cross-Linked Polyethylene Insulation Material: Comply with NEMA WC 7.
E. Ethylene Propylene Rubber Insulation Material: Comply with NEMA WC 8.
F. Conductor Material: Copper.
G. Stranding: Solid conductor for No. 10 AWG and smaller; stranded conductor for larger than No. 10 AWG.
2.3 CONNECTORS AND SPLICES
A. UL-listed, factory-fabricated wiring connectors of size, ampacity rating, material, type, and class for application and service indicated. Comply with Project's installation re-quirements and as specified in Part 3 "Wire and Insulation Applications" Article.
CONDUCTORS AND CABLES 26 0519 - 3
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine raceways and building finishes to receive wires and cables for compliance with requirements for installation tolerances and other conditions affecting performance of wires and cables. Do not proceed with installation until unsatisfactory conditions have been corrected.
3.2 WIRE AND INSULATION APPLICATIONS
A. Service Entrance: Type RHW or THWN, in raceway.
B. Feeders: Type THHN/THWN, in raceway.
C. Branch Circuits: Type THHN/THWN, in raceway.
D. Fire Alarm Circuits: Type THHN/THWN, in raceway.
E. Class 1 Control Circuits: Type THHN/THWN, in raceway.
F. Class 2 Control Circuits: Type THHN/THWN, in raceway.
3.3 INSTALLATION
A. Install wires and cables as indicated, according to manufacturer's written instructions and NECA's "Standard of Installation."
B. Remove existing wires from raceway before pulling in new wires and cables.
C. Pull Conductors: Use manufacturer-approved pulling compound or lubricant where necessary; compound used must not deteriorate conductor or insulation. Do not exceed manufacturer's recommended maximum pulling tensions and sidewall pressure values.
D. Use pulling means, including fish tape, cable, rope, and basket-weave wire/cable grips, that will not damage cables or raceway.
E. Install exposed cables, parallel and perpendicular to surfaces of exposed structural members, and follow surface contours where possible.
F. Support cables according to Division 26 Section "Basic Electrical Materials and Meth-ods."
G. Seal around cables penetrating fire-rated elements according to Division 7 Section "Firestopping."
CONDUCTORS AND CABLES 26 0519 - 4
H. Identify wires and cables according to Division 26 Section "Basic Electrical Materials and Methods."
3.4 CONNECTIONS
A. Conductor Splices: Keep to minimum.
B. Install splices and tapes that possess equivalent or better mechanical strength and insu-lation ratings than conductors being spliced.
C. Use splice and tap connectors compatible with conductor material.
D. Wiring at Outlets: Install conductor at each outlet, with at least 12 inches (300 mm) of slack.
E. Connect outlets and components to wiring and to ground as indicated and instructed by manufacturer.
F. Tighten electrical connectors and terminals according to manufacturer's published torque-tightening values. If manufacturer's torque values are not indicated, use those specified in UL 486A and UL 486B.
3.5 FIELD QUALITY CONTROL
A. Testing: On installation of wires and cables and before electrical circuitry has been en-ergized, demonstrate product capability and compliance with requirements.
1. Procedures: Perform each visual and mechanical inspection and electrical test stated in NETA ATS, Section 7.3.1. Certify compliance with test parameters.
B. Correct malfunctioning conductors and cables at Project site, where possible, and retest to demonstrate compliance; otherwise, remove and replace with new units and retest.
END OF SECTION 26 0519
GROUNDING AND BONDING 26 0526 - 1
SECTION 16060 - GROUNDING AND BONDING
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section.
1.2 SUMMARY
A. This Section includes grounding of electrical systems and equipment. Grounding re-quirements specified in this Section may be supplemented by special requirements of systems described in other Sections.
1.3 QUALITY ASSURANCE
A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for intended use.
1. Comply with UL 467.
PART 2 - PRODUCTS
2.1 MANUFACTURERS
A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
1. Grounding Conductors, Cables, Connectors, and Rods:
a. Apache Grounding/Erico Inc.
b. Chance/Hubbell.
c. Copperweld Corp.
d. Dossert Corp.
e. Erico Inc.; Electrical Products Group.
f. Framatome Connectors/Burndy Electrical.
g. Galvan Industries, Inc.
h. Ideal Industries, Inc.
i. ILSCO.
j. Kearney/Cooper Power Systems.
GROUNDING AND BONDING 26 0526 - 2
k. Lyncole XIT Grounding.
l. O-Z/Gedney Co.; a business of the EGS Electrical Group.
m. Raco, Inc.; Division of Hubbell.
n. Thomas & Betts, Electrical.
2.2 GROUNDING CONDUCTORS
A. For insulated conductors, comply with Division 26 Section "Conductors and Cables."
B. Equipment Grounding Conductors: Insulated with green-colored insulation.
C. Isolated Ground Conductors: Insulated with green-colored insulation with yellow stripe. On feeders with isolated ground, use colored tape, alternating bands of green and yellow tape to provide a minimum of three bands of green and two bands of yellow.
D. Grounding Electrode Conductors: Stranded cable.
E. Underground Conductors: Bare, tinned, stranded, unless otherwise indicated.
F. Bare Copper Conductors: Comply with the following:
1. Solid Conductors: ASTM B 3.
2. Assembly of Stranded Conductors: ASTM B 8.
3. Tinned Conductors: ASTM B 33.
G. Copper Bonding Conductors: As follows:
1. Bonding Cable: 28 kcmil, 14 strands of No. 17 AWG copper conductor, 1/4 inch (6.4 mm) in diameter.
2. Bonding Conductor: No. 4 or No. 6 AWG, stranded copper conductor.
3. Bonding Jumper: Bare copper tape, braided bare copper conductors, terminated with copper ferrules; 1-5/8 inches (42 mm) wide and 1/16 inch (1.5 mm) thick.
4. Tinned Bonding Jumper: Tinned-copper tape, braided copper conductors, termi-nated with copper ferrules; 1-5/8 inches (42 mm) wide and 1/16 inch (1.5 mm) thick.
H. Grounding Bus: Bare, annealed copper bars of rectangular cross section, with insula-tors.
2.3 CONNECTOR PRODUCTS
A. Comply with IEEE 837 and UL 467; listed for use for specific types, sizes, and combi-nations of conductors and connected items.
B. Bolted Connectors: Bolted-pressure-type connectors, or compression type.
GROUNDING AND BONDING 26 0526 - 3
C. Welded Connectors: Exothermic-welded type, in kit form, and selected per manufac-turer's written instructions.
2.4 GROUNDING ELECTRODES
A. Ground Rods: Copper-clad steel.
1. Size: 3/4 by 120 inches.
PART 3 - EXECUTION
3.1 APPLICATION
A. In raceways, use insulated equipment grounding conductors.
B. Exothermic-Welded Connections: Use for connections to structural steel and for un-derground connections.
C. Equipment Grounding Conductor Terminations: Use bolted pressure clamps.
3.2 EQUIPMENT GROUNDING CONDUCTORS
A. Comply with NFPA 70, Article 250, for types, sizes, and quantities of equipment grounding conductors, unless specific types, larger sizes, or more conductors than re-quired by NFPA 70 are indicated.
B. Install equipment grounding conductors in all feeders and circuits.
C. Isolated Grounding Receptacle Circuits: Install an insulated equipment grounding con-ductor connected to the receptacle grounding terminal. Isolate grounding conductor from raceway and from panelboard grounding terminals. Terminate at equipment grounding conductor terminal of the applicable derived system or service, unless other-wise indicated.
D. Nonmetallic Raceways: Install an equipment grounding conductor in nonmetallic raceways unless they are designated for telephone or data cables.
E. Air-Duct Equipment Circuits: Install an equipment grounding conductor to duct-mounted electrical devices operating at 120 V and more, including air cleaners and heaters. Bond conductor to each unit and to air duct.
F. Water Heater, Heat-Tracing, and Antifrost Heating Cables: Install a separate equipment grounding conductor to each electric water heater, heat-tracing, and antifrost heating cable. Bond conductor to heater units, piping, connected equipment, and components.
GROUNDING AND BONDING 26 0526 - 4
G. Signal and Communication Systems: For telephone, alarm, voice and data, and other communication systems, provide insulated grounding conductor in raceway from grounding electrode system to each service location, terminal cabinet, wiring closet, and central equipment location.
1. Service and Central Equipment Locations and Wiring Closets: Terminate ground-ing conductor on a grounding bus.
2. Terminal Cabinets: Terminate grounding conductor on cabinet grounding termi-nal.
H. Metal Poles Supporting Outdoor Lighting Fixtures: Provide a grounding electrode in addition to installing a separate equipment grounding conductor with supply branch-circuit conductors.
I. Fencing: Ground all fences and equipment attached to the fence. Ground fences on each side of all gates, at each corner, at the closest approach to each building located within 50 feet of the fence, and where the fence alignment changes more than 15 de-grees. Grounding locations can not exceed 650 feet. Bond each gate panel with a flexi-ble bond strap to its gate post. Ground fences crossed by powerlines of 600 volts or more at or near the point of crossing and at distances not exceeding 150 feet on each side of crossing. Provide ground conductor consisting of No. 8 AWG solid copper wire.
Provide copper-clad steel rod grounding electrodes 3/4 inch by 10 foot long. Drive elec-trodes into the earth so that the top of the electrode is at least 6 inches below the grade.
Where driving is impracticable, bury electrodes a minimum of 12 inches deep and radi-ally from the fence, with top of the electrode not less than 2 feet or more than 8 feet from the fence. Clamp ground conductor to the fence and electrodes with bronze grounding clamps to create electrical continuity between fence posts, fence fabric, and ground rods. Total resistance of the fence to ground cannot exceed 25 ohms.
3.3 INSTALLATION
A. Ground Rods: Install at least three rods spaced at least one-rod length from each other and located at least the same distance from other grounding electrodes.
1. Drive ground rods until tops are 2 inches (50 mm) below finished floor or final grade, unless otherwise indicated.
2. Interconnect ground rods with grounding electrode conductors. Use exothermic welds, except at test wells and as otherwise indicated. Make connections without exposing steel or damaging copper coating.
B. Grounding Conductors: Route along shortest and straightest paths possible, unless oth-erwise indicated. Avoid obstructing access or placing conductors where they may be subjected to strain, impact, or damage.
C. Bonding Straps and Jumpers: Install so vibration by equipment mounted on vibration isolation hangers and supports is not transmitted to rigidly mounted equipment. Use exothermic-welded connectors for outdoor locations, unless a disconnect-type connec-
GROUNDING AND BONDING 26 0526 - 5
tion is required; then, use a bolted clamp. Bond straps directly to the basic structure taking care not to penetrate any adjacent parts. Install straps only in locations accessi-ble for maintenance.
D. Metal Water Service Pipe: Provide insulated copper grounding conductors, in conduit, from building's main service equipment, or grounding bus, to main metal water service entrances to building. Connect grounding conductors to main metal water service pipes by grounding clamp connectors. Where a dielectric main water fitting is installed, con-nect grounding conductor to street side of fitting. Bond metal grounding conductor conduit or sleeve to conductor at each end.
E. Water Meter Piping: Use braided-type bonding jumpers to electrically bypass water meters. Connect to pipe with grounding clamp connectors.
F. Bond interior metal piping systems and metal air ducts to equipment grounding conduc-tors of associated pumps, fans, blowers, electric heaters, and air cleaners. Use braided-type bonding straps.
G. Bond each aboveground portion of gas piping system upstream from equipment shutoff valve.
3.4 CONNECTIONS
A. General: Make connections so galvanic action or electrolysis possibility is minimized.
Select connectors, connection hardware, conductors, and connection methods so metals in direct contact will be galvanically compatible.
1. Use electroplated or hot-tin-coated materials to ensure high conductivity and to make contact points closer to order of galvanic series.
2. Make connections with clean, bare metal at points of contact.
3. Coat and seal connections having dissimilar metals with inert material to prevent future penetration of moisture to contact surfaces.
B. Exothermic-Welded Connections: Comply with manufacturer's written instructions.
Welds that are puffed up or that show convex surfaces indicating improper cleaning are not acceptable.
C. Equipment Grounding Conductor Terminations: For No. 8 AWG and larger, use pres-sure-type grounding lugs. No. 10 AWG and smaller grounding conductors may be ter-minated with winged pressure-type connectors.
D. Noncontact Metal Raceway Terminations: If metallic raceways terminate at metal housings without mechanical and electrical connection to housing, terminate each con-duit with a grounding bushing. Connect grounding bushings with a bare grounding conductor to grounding bus or terminal in housing. Bond electrically noncontinuous conduits at entrances and exits with grounding bushings and bare grounding conductors, unless otherwise indicated.
GROUNDING AND BONDING 26 0526 - 6
E. Tighten screws and bolts for grounding and bonding connectors and terminals accord-ing to manufacturer's published torque-tightening values. If manufacturer's torque val-ues are not indicated, use those specified in UL 486A.
F. Compression-Type Connections: Use hydraulic compression tools to provide correct circumferential pressure for compression connectors. Use tools and dies recommended by connector manufacturer. Provide embossing die code or other standard method to make a visible indication that a connector has been adequately compressed on ground-ing conductor.
G. Moisture Protection: If insulated grounding conductors are connected to ground rods or grounding buses, insulate entire area of connection and seal against moisture penetra-tion of insulation and cable.
3.5 FIELD QUALITY CONTROL
A. Testing: Perform the following field quality-control testing:
1. After installing grounding system but before permanent electrical circuitry has been energized, test for compliance with requirements.
a. Equipment Rated 500 kVA and Less: 10 ohms.
b. Equipment Rated 500 to 1000 kVA: 5 ohms.
c. Equipment Rated More Than 1000 kVA: 3 ohms.
2. Excessive Ground Resistance: If resistance to ground exceeds specified values, notify Architect promptly and include recommendations to reduce ground re-sistance.
END OF SECTION 26 0526
RACEWAYS AND BOXES 26 0533 - 1
SECTION 26 0533 - RACEWAYS AND BOXES
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section.
1.2 SUMMARY
A. This Section includes raceways, fittings, boxes, enclosures, and cabinets for electrical wiring.
1. Raceways include the following:
a. RMC.
b. IMC.
c. EMT.
d. FMC.
e. LFMC.
f. LFNC.
g. RNC.
2. Boxes, enclosures, and cabinets include the following:
a. Device boxes.
b. Outlet boxes.
c. Pull and junction boxes.
B. Related Sections include the following:
1. Division 7 Section "Firestopping."
2. Division 26 Section "Basic Electrical Materials and Methods" for raceways and box supports.
3. Division 26 Section "Wiring Devices" for devices installed in boxes and for floor-box service fittings.
1.3 DEFINITIONS
A. EMT: Electrical metallic tubing.
B. ENT: Electrical nonmetallic tubing.
RACEWAYS AND BOXES 26 0533 - 2
C. FMC: Flexible metal conduit.
D. IMC: Intermediate metal conduit.
E. LFMC: Liquidtight flexible metal conduit.
F. LFNC: Liquidtight flexible nonmetallic conduit.
G. RMC: Rigid metal conduit.
H. RNC: Rigid nonmetallic conduit.
1.4 QUALITY ASSURANCE
A. Listing and Labeling: Provide raceways and boxes specified in this Section that are listed and labeled.
1. The Terms "Listed" and "Labeled": As defined in NFPA 70, Article 100.
2. Listing and Labeling Agency Qualifications: A "Nationally Recognized Testing
Laboratory" as defined in OSHA Regulation 1910.7.
B. Comply with NECA's "Standard of Installation."
C. Comply with NFPA 70.
1.5 COORDINATION
A. Coordinate layout and installation of raceways and boxes with other construction ele-ments to ensure adequate headroom, working clearance, and access.
PART 2 - PRODUCTS
2.1 MANUFACTURERS
A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
1. Metal Conduit and Tubing:
a. Alflex Corp.
b. Anamet, Inc.; Anaconda Metal Hose.
c. Anixter Brothers, Inc.
d. Grinnell Co.; Allied Tube and Conduit Div.
e. Monogram Co.; AFC.
f. Wheatland Tube Co.
RACEWAYS AND BOXES 26 0533 - 3
2. Nonmetallic Conduit and Tubing:
a. Anamet, Inc.; Anaconda Metal Hose.
b. Hubbell, Inc.; Raco, Inc.
c. Lamson & Sessions; Carlon Electrical Products.
d. R&G Sloan Manufacturing Co., Inc.
e. Thomas & Betts Corp.
3. Conduit Bodies and Fittings:
a. American Electric; Construction Materials Group.
b. Crouse-Hinds; Div. of Cooper Industries.
c. Emerson Electric Co.; Appleton Electric Co.
d. Hubbell, Inc.; Killark Electric Manufacturing Co.
e. Lamson & Sessions; Carlon Electrical Products.
f. O-Z/Gedney; Unit of General Signal.
g. Scott Fetzer Co.; Adalet-PLM.
h. Spring City Electrical Manufacturing Co.
4. Boxes, Enclosures, and Cabinets:
a. Crouse-Hinds; Div. of Cooper Industries.
b. Electric Panelboard Co., Inc.
c. Erickson Electrical Equipment Co.
d. Hoffman Engineering Co.; Federal-Hoffman, Inc.
e. Hubbell Inc.; Killark Electric Manufacturing Co.
f. Hubbell Inc.; Raco, Inc.
g. Lamson & Sessions; Carlon Electrical Products.
h. O-Z/Gedney; Unit of General Signal.
i. Thomas & Betts Corp.
j. Woodhead Industries, Inc.; Daniel Woodhead Co.
2.2 METAL CONDUIT AND TUBING
A. Rigid Steel Conduit: ANSI C80.1.
B. IMC: ANSI C80.6.
C. Plastic-Coated Steel Conduit and Fittings: NEMA RN 1.
D. Plastic-Coated IMC and Fittings: NEMA RN 1.
E. EMT and Fittings: ANSI C80.3.
1. Fittings: Compression type.
F. FMC: Zinc-coated steel.
RACEWAYS AND BOXES 26 0533 - 4
G. LFMC: Flexible steel conduit with PVC jacket.
H. Fittings: NEMA FB 1; compatible with conduit/tubing materials.
2.3 NONMETALLIC CONDUIT AND TUBING
A. RNC: NEMA TC 2, Schedule 40 or 80 PVC.
B. RNC Fittings: NEMA TC 3; match to conduit or conduit/tubing type and material.
C. LFNC: UL 1660.
2.4 OUTLET AND DEVICE BOXES
A. Sheet Metal Boxes: NEMA OS 1.
B. Cast-Metal Boxes: NEMA FB 1, Type FD, cast box with gasketed cover.
C. Nonmetallic Boxes: NEMA OS 2.
2.5 PULL AND JUNCTION BOXES
A. Small Sheet Metal Boxes: NEMA OS 1.
B. Cast-Metal Boxes: NEMA FB 1, cast aluminum with gasketed cover.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine surfaces to receive raceways, boxes, enclosures, and cabinets for compliance with installation tolerances and other conditions affecting performance of raceway in-stallation. Do not proceed with installation until unsatisfactory conditions have been corrected.
3.2 WIRING METHODS
A. Outdoors: Use the following wiring methods:
1. Exposed: Rigid steel or IMC.
2. Concealed: Rigid steel or IMC.
3. Underground, Single Run: RNC.
4. Underground, Grouped: RNC.
RACEWAYS AND BOXES 26 0533 - 5
5. Connection to Vibrating Equipment (Including Transformers and Hydraulic, Pneumatic, Electric Solenoid, or Motor-Driven Equipment): LFMC.
6. Boxes and Enclosures: NEMA 250, Type 3R or Type 4.
B. Indoors: Use the following wiring methods:
1. Exposed: Rigid steel or IMC.
2. Concealed: EMT.
3. Connection to Vibrating Equipment (Including Transformers and Hydraulic, Pneumatic, Electric Solenoid, or Motor-Driven Equipment): FMC; except in wet or damp locations, use LFMC.
4. Damp or Wet Locations: Rigid steel conduit.
5. Boxes and Enclosures: NEMA 250, Type 1, except as follows:
a. Damp or Wet Locations: NEMA 250, Type 3R.
3.3 INSTALLATION
A. Install raceways, boxes, enclosures, and cabinets as indicated, according to manufactur-er's written instructions.
B. Minimum Raceway Size: 1/2-inch trade size (DN16).
C. Conceal conduit and EMT, unless otherwise indicated, within finished walls, ceilings, and floors.
D. Keep raceways at least 6 inches (150 mm) away from parallel runs of flues and steam or hot-water pipes. Install horizontal raceway runs above water and steam piping.
E. Install raceways level and square and at proper elevations. Provide adequate headroom.
F. Complete raceway installation before starting conductor installation.
G. Support raceways as specified in Division 26 Section "Basic Electrical Materials and Methods."
H. Use temporary closures to prevent foreign matter from entering raceways.
I. Protect stub-ups from damage where conduits rise through floor slabs. Arrange so curved portion of bends is not visible above the finished slab.
J. Make bends and offsets so ID is not reduced. Keep legs of bends in the same plane and straight legs of offsets parallel, unless otherwise indicated.
K. Use raceway fittings compatible with raceways and suitable for use and location. For intermediate steel conduit, use threaded rigid steel conduit fittings, unless otherwise in-dicated.
RACEWAYS AND BOXES 26 0533 - 6
L. Run concealed raceways, with a minimum of bends, in the shortest practical distance considering the type of building construction and obstructions, unless otherwise indicat-ed.
M. Raceways Embedded in Slabs: Install in middle third of slab thickness where practical, and leave at least 1-inch (25-mm) concrete cover.
1. Secure raceways to reinforcing rods to prevent sagging or shifting during concrete placement.
2. Space raceways laterally to prevent voids in concrete.
3. Run conduit larger than 1-inch trade size (DN27) parallel to or at right angles to main reinforcement. Where at right angles to reinforcement, place conduit close to slab support.
4. Transition from nonmetallic tubing to rigid steel conduit before rising above floor.
N. Install exposed raceways parallel to or at right angles to nearby surfaces or structural members, and follow the surface contours as much as practical.
1. Run parallel or banked raceways together, on common supports where practical.
2. Make bends in parallel or banked runs from same centerline to make bends paral-lel. Use factory elbows only where elbows can be installed parallel; otherwise, provide field bends for parallel raceways.
O. Join raceways with fittings designed and approved for the purpose and make joints tight.
1. Make raceway terminations tight. Use bonding bushings or wedges at connec-tions subject to vibration. Use bonding jumpers where joints cannot be made tight.
2. Use insulating bushings to protect conductors.
P. Terminations: Where raceways are terminated with locknuts and bushings, align race-ways to enter squarely and install locknuts with dished part against the box. Where terminations are not secure with 1 locknut, use 2 locknuts: 1 inside and 1 outside the box.
Q. Where raceways are terminated with threaded hubs, screw raceways or fittings tightly into the hub so the end bears against the wire protection shoulder. Where chase nipples are used, align raceways so the coupling is square to the box and tighten the chase nip-ple so no threads are exposed.
R. Install pull wires in empty raceways. Use No. 14 AWG zinc-coated steel or monofila-ment plastic line with not less than 200-lb (90-kg) tensile strength. Leave at least 12 inches (300 mm) of slack at each end of the pull wire.
S. Flexible Connections: Use maximum of 6 feet (1830 mm) of flexible conduit for re-cessed and semirecessed lighting fixtures; for equipment subject to vibration, noise
RACEWAYS AND BOXES 26 0533 - 7
transmission, or movement; and for all motors. Use liquidtight flexible conduit in wet or damp locations. Install separate ground conductor across flexible connections.
T. Do not install aluminum conduits embedded in or in contact with concrete.
U. Install hinged-cover enclosures and cabinets plumb. Support at each corner.
V. All PVC conduit runs shall have rigid galvanized steel 90’s and rigid stub ups.
3.4 PROTECTION
A. Provide final protection and maintain conditions, in a manner acceptable to manufactur-er and Installer, that ensure coatings, finishes, and cabinets are without damage or dete-rioration at the time of Substantial Completion.
1. Repair damage to galvanized finishes with zinc-rich paint recommended by man-ufacturer.
2. Repair damage to PVC or paint finishes with matching touchup coating recom-mended by manufacturer.
3.5 CLEANING
A. On completion of installation, including outlet fittings and devices, inspect exposed fin-ish. Remove burrs, dirt, and construction debris and repair damaged finish, including chips, scratches, and abrasions.
END OF SECTION 26 0533
Liquid-Filled, Medium-Voltage Transformers 26 1219-1
SECTION 26 1219 - LIQUID-FILLED, MEDIUM-VOLTAGE TRANSFORMERS
1.01 SCOPE
A. This specification provides the technical requirements for the design, manufacture and test of liquid-type secondary unit substation transformers. Provide all accessories and equipment as described herein and shown on Project Drawings as necessary for a complete installation.
1.02 SUBMITTALS
A. The manufacturer shall provide the following information for review and evaluation by the Engineer:
1. Shop Drawings showing layout, dimensions, voltage, phasing and continuous current capacity.
B. Manufacturer shall provide final, as- built drawings. Installation, Operation and Maintenance manuals shall also be supplied.
1.03 RELATED STANDARDS
A. The liquid-filled type transformer and protection devices in this specification are designed and manufactured according to latest revision of the following standards.
1. American National Standards Institute, Inc. (ANSI)
2. Institute of Electrical and Electronic Engineers (IEEE)
3. National Electrical Manufacturers Association (NEMA)
4. American Society of Testing and Materials (ASTM)
5. National Electrical Code (NEC)
6. Underwriter’s Laboratories (UL)
1.04 QUALITY ASSURANCE
A. The manufacturer shall have specialized in the design, manufacture and assembly of liquid filled secondary substation transformers for a minimum of 10 years.
B. The manufacturer shall have a well documented quality assurance program, which includes procedures for all activities in order entry, design, material procurement, manufacturing processes, testing, shipping and post shipment product follow.
C. The manufacturer’s test floor shall have a documented calibration program. All equipment shall receive regular calibrations. Calibration standards shall be traceable to National Bureau of Standards. Records of all equipment calibration shall be made available to the Buyer upon request.
D. The transformers shall be manufactured by a company, which is certified to ISO 9001, or ISO 9002 as a minimum, for design and manufacture of Power Liquid Filled Type Transformers.
1.05 DELIVERY, STORAGE AND HANDLING
Liquid-Filled, Medium-Voltage Transformers 26 1219-2
A. Handle and store equipment in accordance with manufacturer’s Installation and Maintenance Manuals. One (1) copy of this document to be provided with the equipment at time of shipment.
PART 2 - PRODUCTS
2.01 MANUFACTURERS
A. The medium voltage, liquid filled substation transformer shall be provided by Siemens Energy and Automation or pre-approved equal. Approved manufacturers are as follows:
1. Cooper Industries; Cooper Power Systems Division
2. Federal Pacific Transformer Company
3. GE Electrical Distribution & Control
4. Siemens
5. Square D
6. Virginia Transformer Co.
2.02 TECHNICAL REQUIREMENTS
A. Winding Characteristics
1. All windings and internal connections shall be copper.
2. The windings shall be tightly wound utilizing tension devices to place the conductor into the coils.
3. Sheet conductor shall be used in secondary winding to minimize vertical short circuit forces.
4. Insulation between layers of the windings shall be Insuldur paper or equal.
5. The transformer shall be designed and constructed to be completely self protected by its ability to withstand the external short-circuits, as defined by
ANSI C57. 12.00.
6. Evidence of compliance to these short-circuit requirements as required in C57.12.00 and C57.12.90 shall be submitted to the Buyer at the time of quotation.
7. The transformer design shall be capable of operating above rated voltage or below rated frequency in accordance with ANSI C57.12.00.
8. The impedance shall be per ANSI tolerance.
B. Sound Level
1. The secondary unit substation transformer and auxiliary cooling equipment shall be designed and constructed to minimize the audible noise generated with the transformer energized at rated voltage and with all auxiliary cooling equipment in operation. The acceptable noise level shall be in accordance with NEMA standard TR 1. The measurement procedure shall be as specified in
ANSI C57.12.90.
C. Bushings
1. High voltage and low voltage bushings shall be furnished with the ratings shown on the Transformer Data Sheet.
2. The bushings shall be sidewall mounted and suitable for high and low voltage terminations as indicated on the Transformer Data Sheet.
Liquid-Filled, Medium-Voltage Transformers 26 1219-3
D. Core
1. The core shall be clamped and braced to resist distortion caused by short-circuit stresses within rating or transportation handling and to prevent the shifting of core laminations.
2. The core shall be constructed of high-grade, grain oriented, silicon steel laminations, with high magnetic permeability. Core construction shall include step-lap mitered joints to keep core losses, excitation current and noise level at a minimum.
E. De-Energized Tap Changer
1. A manually operated de-energized tap changer shall be provided for changing the primary winding taps.
2. Full capacity taps shall be located in the high voltage windings and shall be in accordance with the Transformer Data Sheet.
3. The tap changer shall be capable of carrying the full transformer short-circuit current without damage or contact separation.
4. The sidewall mounted tap changer shall be gang operated from a single operating point and shall have a position indicator.
5. The tap changer operating mechanism shall include provisions for pad locking in each tap position.
F. Insulating Fluid And Preservation System
1. The fluid preservation system shall be a sealed tank type.
2. The insulating fluid shall be mineral oil.
3. The transformer insulating fluid shall be certified to contain no detectable
PCB’s at the time of shipment and the tank shall be so labeled. Certification shall also be provided that the transformer and components have not been contaminated with PCB’s prior to shipment.
4. The transformer insulating fluid shall meet or exceed the requirements of the appropriate ANSI and ASTM fluid Standards. The transformer fluid shall be tested for dielectric breakdown and moisture content just prior at the time of shipment.
G. Tank Design
1. The transformer tank, cooling equipment and compartments subject to pressures shall be designed to withstand, without permanent deformation, pressures of at least twenty-five percent greater than maximum operating pressures. The maximum design withstand pressure shall be indicated on the nameplate.
2. Tank design shall include sufficient expansion volume to allow operation under specified load conditions.
3. The main cover shall be of welded onto the tank.
4. One or more handholds shall be provided in the tank cover for access to bushing connections and current transformers, when required. The opening shall be of sufficient size to allow removal of any CT.
5. The transformer base shall be suitable for rolling or…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .