Air Change Test Result SPS - June 2.xlsx
XLSX spreadsheet 20 KB Posted
- Solicitation number
- 36C25625Q0549
About this file
This file is an Excel spreadsheet containing air change test results for multiple rooms across different buildings, conducted by Barnett & Williams and scheduled for June 2024. The document tracks air flow measurements for clean supply rooms, soiled utility rooms, and other medical facility spaces, measuring supply air CFM (cubic feet per minute), exhaust air CFM, minimum required air changes, and total air changes to determine pass/fail status for each room. The testing appears to be related to HVAC systems in medical facilities, particularly focusing on sterile processing areas and rooms requiring specific positive or negative air pressure differentials.
The related federal opportunity (36C25625Q0549) is a pre-solicitation for HVAC Controls Critical Systems Calibration, Testing and Adjustments Service at Overton Brooks VA Medical Center in Shreveport, Louisiana. The Department of Veterans Affairs is seeking responses by March 5, 2025, at 6:00 PM EST, with questions due by March 3, 2025. The opportunity will be a firm-fixed-price task order if on FSS or purchase order if open market, with NAICS code 238220. The agency is conducting market research to determine appropriate small business set-aside status and requires respondents to demonstrate capabilities, qualifications, and authorized service provider status.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Sheet1
| SPS Satellite Rooms - AIR CHANGE TEST RESULTS (Rev: 07/2022) | |||||||||||||
| Test Date: June 2024 | Tested By: Barnett & Williams | ||||||||||||
| Bld. | Rm. | Room | Rm. Vol. | Press. | Supply Air CFM | Exhaust Air CFM | Min Air | Total Air | Pass | ||||
| No. | No. | Function | CF | Diff. | Grill 1 | Grill 2 | Total | Grill 1 | Grill 2 | Total | Changes | Changes | or Fail |
| 1 | BW35 | SPEECH LAB | 1670 | Positive | X | X | 585 | -151 | -359 | -510 | 4 | 21.02 | PASS |
| 1 | BD19 | SOILED UTILITY | 612 | Negative | X | X | 67 | X | X | -129 | 10 | 12.65 | PASS |
| 1 | BD22 | CLEAN SUPPLY | 335 | Positive | X | X | 65 | Can't Reach With Hood | 4 | 11.64 | PASS | ||
| 1 | BE30A | CLEAN SUPPLY | 525 | Positive | FAN COIL UNIT ONLY | 4 | N/A | N/A | |||||
| 1 | BS21 | IMPLANT COORDINATOR OFFICE | 68 | Positive | NOT CURRENTLY USED BY SPS | 4 | N/A | N/A | |||||
| 1 | 1N16 | CLEAN SUPPLY | 730 | Positive | X | X | 211 | X | X | -57 | 4 | 17.34 | PASS |
| 1 | 1N23 | SOILED UTILITY | 480 | Negative | X | X | X | X | X | -91 | 10 | 11.38 | PASS |
| 1 | 3E 11 | SOILED UTILITY | 771 | Negative | X | X | 61 | X | X | -133 | 10 | 10.35 | PASS |
| 1 | 3N9 | SOILED UTILITY | 539 | Negative | X | X | X | X | X | -389 | 10 | 43.3 | PASS |
| 1 | 3N10 | CLEAN SUPPLY | 1337 | Positive | X | X | 484 | X | X | X | 4 | 21.72 | PASS |
| 1 | 3W40C | MAIN INSTRUMENT & SUPPLY | 1590 | Positive | X | X | 126 | X | X | -35 | 4 | 4.75 | PASS |
| 1 | 3W40H | ORTHO SUPPLY | 1230 | Positive | X | X | 221 | X | X | -109 | 4 | 10.78 | PASS |
| 1 | 3W40L | STERILE SUPPLY | 1526 | Positive | X | X | 253 | X | X | -169 | 4 | 9.95 | PASS |
| 1 | 3W48A | CLEAN SUPPLY | 1860 | Positive | X | X | 145 | X | X | -111 | 4 | 4.68 | PASS |
| 1 | 3W53 | ANESTHESIA SUPPLY | 1500 | Positive | 60 | 108 | 168 | X | X | N/A | 4 | 6.72 | PASS |
| 1 | 4W41 | CLEAN SUPPLY | 1452 | Positive | X | X | 135 | X | X | N/A | 4 | 5.58 | PASS |
| 1 | 4E 15 | UNIT SUPPLY | 1150 | Positive | NOT CURRENTLY USED BY SPS | 4 | N/A | N/A | |||||
| 1 | 4E 16 | SOILED UTILITY | 1550 | Negative | NOT CURRENTLY USED BY SPS | 10 | N/A | N/A | |||||
| 1 | 5E 22 | ULTRA-SOUND | 1400 | Positive | X | X | 522 | X | X | -304 | 4 | 22.37 | PASS |
| 1 | 5E 23 | UROLOGY SERVICE CYSTO SUITE | 2150 | Positive | X | X | 805 | X | X | -430 | 4 | 22.47 | PASS |
| 1 | 5E 24 | CLEAN SUPPLY | 780 | Positive | X | X | 250 | X | X | -19 | 4 | 19.23 | PASS |
| 1 | 5E 28 | BRONCHOCSCOPE TEST ROOM | 2935 | Negative | FAN COIL UNIT | X | X | -326 | 4 | 6.66 | PASS | ||
| 1 | 5E 29 | G. U. CLEAN SUPPLY | 1430 | Positive | FAN COIL UNIT ONLY | 4 | N/A | N/A | |||||
| 1 | 5W31 | CLINIC SUPPLIES | 1056 | Positive | FAN COIL UNIT ONLY | 4 | N/A | N/A | |||||
| 1 | 5W35 | SOILED UTILITY | 1116 | Negative | X | X | N/A | X | X | -272 | 10 | 14.62 | PASS |
| 1 | 6E 15 | CLEAN SUPPLY | 1230 | Positive | NOT CURRENTLY USED BY SPS | 4 | N/A | N/A | |||||
| 1 | 6E 16 | SOILED UTILITY | 1552 | Negative | X | X | N/A | X | X | * | 10 | * | * |
| 1 | 6E 21A | SUPPLY ROOM | 1162 | Positive | FAN COIL UNIT ONLY | 4 | N/A | N/A | |||||
| 1 | 6N30 | INFECTIOUS WASTE | 422 | Negative | X | X | 41 | X | X | -124 | 10 | 17.63 | PASS |
| 1 | 6N34 | CLEAN SUPPLY | 2527 | Positive | 188 | 195 | 383 | X | X | N/A | 4 | 9.09 | PASS |
| 1 | 7E 11 | SOILED UTILITY | 1116 | Negative | X | X | N/A | X | X | -203 | 10 | 10.91 | PASS |
| 1 | 7E 16 | ENDOSCOPY PROCEDURE - ROOM 2 | 2085 | Positive | FAN COIL UNITS | X | X | -165 | 4 | 4.75 | PASS | ||
| 1 | 7E20B1 | G. I. CLEAN ROOM | 789 | Positive | FAN COIL UNIT ONLY | 4 | N/A | N/A | |||||
| * CONSTRUCTION | |||||||||||||
| SPS Satellite Rooms - AIR CHANGE TEST RESULTS (Rev: 07/2022) | |||||||||||||
| Test Date: June 2024 | Tested By: Barnett & Williams | ||||||||||||
| Bld. | Rm. | Room | Rm. Vol. | Press. | Supply Air CFM | Exhaust Air CFM | Min Air | Total Air | Pass | ||||
| No. | No. | Function | CF | Diff. | Grill 1 | Grill 2 | Total | Grill 1 | Grill 2 | Total | Changes | Changes | or Fail |
| 1 | 9W28 | CLEAN SUPPLY | 550 | Positive | NOT CURRENTLY USED BY SPS | 4 | N/A | N/A | |||||
| 1 | 10E 20 | CLEAN STORAGE | 1624 | Positive | NOT CURRENTLY USED BY SPS | 4 | N/A | N/A |
| 55 | 105 | DIRTY ROOM / BIOHAZARD | 660 | Negative | X | X | 82 | X | X | -177 | 10 | 16.09 | PASS |
| 55 | 115 | CLEAN ROOM | 588 | Positive | X | X | 85 | X | X | N/A | 4 | 8.67 | PASS |
| 55 | 213 | SOILDED ROOM / BIOHAZARD | 564 | Negative | X | X | N/A | X | X | -105 | 10 | 11.17 | PASS |
| 55 | 214 | CLEAN ROOM | 576 | Positive | X | X | 59 | X | X | N/A | 4 | 6.15 | PASS |
| 55 | 312 | NO I.D. / BIOHAZARD | 514 | Negative | X | X | N/A | X | X | -110 | 10 | 12.84 | PASS |
| 55 | 317 | NO I.D. (CLEAN SUPPLIES) | 963 | Positive | X | X | 98 | X | X | -71 | 4 | 6.11 | PASS |
| 55 | 318 | NO I.D. (CLEAN AREA) | 518 | Positive | X | X | 53 | X | X | N/A | 4 | 6.14 | PASS |
| 57 | 122 | BIOHAZARD | 470 | Negative | X | X | 43 | X | X | -92 | 10 | 11.74 | PASS |
| 57 | 124 | STERILE SUPPLIES | 491 | Positive | X | X | 149 | -119 | -159 | -278 | 4 | 18.21 | PASS |
| 57 | 222 | BIOHAZARD | 470 | Negative | X | X | 64 | X | X | -93 | 10 | 11.87 | PASS |
| 57 | 224 | STERILE SUPPLIES | 486 | Positive | 110 | 182 | 3292 | X | X | -90 | 4 | 36.05 | PASS |
| Sterile Processing Area | ||||
| BE27-1 Clean Storage (Positive) | BE27B-1 Sterile Prep. (Positive) | BE28-1 Decon (Negative) | Medivator Rm. (Positive) | |
| Grill #1 CFM: 95 | ||||
| Grill #2 CFM: | 539 | |||
| Grill #3 CFM: BLOCKED | Grill #12 CFM: -403 | |||
| Grill #4 CFM: 150 | Grill #7 CFM: 1179 | Grill #13 CFM: -390 | ||
| Grill #5 CFM: BLOCKED | Grill #8 CFM: 627 | Grill #14 CFM: REMOVED | Supply Grill CFM: 227 | |
| Grill #6 CFM: 181 | Grill #9 CFM: 983976 | Grill #15 CFM: -298 | Exhaust Grill CFM: 0 | |
| Total CFM: 965 | Total CFM: 2782 | Total CFM: -1091 | Total CFM: N/A | |
| Room Volume: 8960 CF | Room Volume: 8100 CF | Room Volume: 7400 CF | Room Volume: 723 CF | |
| Min Total Air Changes: 4 | Min Total Air Changes: 4 | Min Total Air Changes: 6 | Min Air Changes: 6 | |
| Total Air Changes: 6.46 | Total Air Changes: 20.61 | Total Air Changes: 8.85 | Total Air Changes: 18.84 | |
| Pass or Fail: PASS | Pass or Fail: PASS | Pass or Fail: PASS | Pass or Fail: PASS |