Air Change Test Result SPS - June 2.xlsx

XLSX spreadsheet 20 KB Posted

Attached to
J041--HVAC Controls Critical Systems Calibration, Testing and Adjustments Service
Solicitation number
36C25625Q0549
Issued by

About this file

This file is an Excel spreadsheet containing air change test results for multiple rooms across different buildings, conducted by Barnett & Williams and scheduled for June 2024. The document tracks air flow measurements for clean supply rooms, soiled utility rooms, and other medical facility spaces, measuring supply air CFM (cubic feet per minute), exhaust air CFM, minimum required air changes, and total air changes to determine pass/fail status for each room. The testing appears to be related to HVAC systems in medical facilities, particularly focusing on sterile processing areas and rooms requiring specific positive or negative air pressure differentials.

The related federal opportunity (36C25625Q0549) is a pre-solicitation for HVAC Controls Critical Systems Calibration, Testing and Adjustments Service at Overton Brooks VA Medical Center in Shreveport, Louisiana. The Department of Veterans Affairs is seeking responses by March 5, 2025, at 6:00 PM EST, with questions due by March 3, 2025. The opportunity will be a firm-fixed-price task order if on FSS or purchase order if open market, with NAICS code 238220. The agency is conducting market research to determine appropriate small business set-aside status and requires respondents to demonstrate capabilities, qualifications, and authorized service provider status.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Sheet1

SPS Satellite Rooms - AIR CHANGE TEST RESULTS (Rev: 07/2022)
Test Date: June 2024Tested By: Barnett & Williams
Bld.Rm.RoomRm. Vol.Press.Supply Air CFMExhaust Air CFMMin AirTotal AirPass
No.No.FunctionCFDiff.Grill 1Grill 2TotalGrill 1Grill 2TotalChangesChangesor Fail
1BW35SPEECH LAB1670PositiveXX585-151-359-510421.02PASS
1BD19SOILED UTILITY612NegativeXX67XX-1291012.65PASS
1BD22CLEAN SUPPLY335PositiveXX65Can't Reach With Hood411.64PASS
1BE30ACLEAN SUPPLY525PositiveFAN COIL UNIT ONLY4N/AN/A
1BS21IMPLANT COORDINATOR OFFICE68PositiveNOT CURRENTLY USED BY SPS4N/AN/A
11N16CLEAN SUPPLY730PositiveXX211XX-57417.34PASS
11N23SOILED UTILITY480NegativeXXXXX-911011.38PASS
13E 11SOILED UTILITY771NegativeXX61XX-1331010.35PASS
13N9SOILED UTILITY539NegativeXXXXX-3891043.3PASS
13N10CLEAN SUPPLY1337PositiveXX484XXX421.72PASS
13W40CMAIN INSTRUMENT & SUPPLY1590PositiveXX126XX-3544.75PASS
13W40HORTHO SUPPLY1230PositiveXX221XX-109410.78PASS
13W40LSTERILE SUPPLY1526PositiveXX253XX-16949.95PASS
13W48ACLEAN SUPPLY1860PositiveXX145XX-11144.68PASS
13W53ANESTHESIA SUPPLY1500Positive60108168XXN/A46.72PASS
14W41CLEAN SUPPLY1452PositiveXX135XXN/A45.58PASS
14E 15UNIT SUPPLY1150PositiveNOT CURRENTLY USED BY SPS4N/AN/A
14E 16SOILED UTILITY1550NegativeNOT CURRENTLY USED BY SPS10N/AN/A
15E 22ULTRA-SOUND1400PositiveXX522XX-304422.37PASS
15E 23UROLOGY SERVICE CYSTO SUITE2150PositiveXX805XX-430422.47PASS
15E 24CLEAN SUPPLY780PositiveXX250XX-19419.23PASS
15E 28BRONCHOCSCOPE TEST ROOM2935NegativeFAN COIL UNITXX-32646.66PASS
15E 29G. U. CLEAN SUPPLY1430PositiveFAN COIL UNIT ONLY4N/AN/A
15W31CLINIC SUPPLIES1056PositiveFAN COIL UNIT ONLY4N/AN/A
15W35SOILED UTILITY1116NegativeXXN/AXX-2721014.62PASS
16E 15CLEAN SUPPLY1230PositiveNOT CURRENTLY USED BY SPS4N/AN/A
16E 16SOILED UTILITY1552NegativeXXN/AXX*10**
16E 21ASUPPLY ROOM1162PositiveFAN COIL UNIT ONLY4N/AN/A
16N30INFECTIOUS WASTE422NegativeXX41XX-1241017.63PASS
16N34CLEAN SUPPLY2527Positive188195383XXN/A49.09PASS
17E 11SOILED UTILITY1116NegativeXXN/AXX-2031010.91PASS
17E 16ENDOSCOPY PROCEDURE - ROOM 22085PositiveFAN COIL UNITSXX-16544.75PASS
17E20B1G. I. CLEAN ROOM789PositiveFAN COIL UNIT ONLY4N/AN/A
* CONSTRUCTION
SPS Satellite Rooms - AIR CHANGE TEST RESULTS (Rev: 07/2022)
Test Date: June 2024Tested By: Barnett & Williams
Bld.Rm.RoomRm. Vol.Press.Supply Air CFMExhaust Air CFMMin AirTotal AirPass
No.No.FunctionCFDiff.Grill 1Grill 2TotalGrill 1Grill 2TotalChangesChangesor Fail
19W28CLEAN SUPPLY550PositiveNOT CURRENTLY USED BY SPS4N/AN/A
110E 20CLEAN STORAGE1624PositiveNOT CURRENTLY USED BY SPS4N/AN/A
55105DIRTY ROOM / BIOHAZARD660NegativeXX82XX-1771016.09PASS
55115CLEAN ROOM588PositiveXX85XXN/A48.67PASS
55213SOILDED ROOM / BIOHAZARD564NegativeXXN/AXX-1051011.17PASS
55214CLEAN ROOM576PositiveXX59XXN/A46.15PASS
55312NO I.D. / BIOHAZARD514NegativeXXN/AXX-1101012.84PASS
55317NO I.D. (CLEAN SUPPLIES)963PositiveXX98XX-7146.11PASS
55318NO I.D. (CLEAN AREA)518PositiveXX53XXN/A46.14PASS
57122BIOHAZARD470NegativeXX43XX-921011.74PASS
57124STERILE SUPPLIES491PositiveXX149-119-159-278418.21PASS
57222BIOHAZARD470NegativeXX64XX-931011.87PASS
57224STERILE SUPPLIES486Positive1101823292XX-90436.05PASS
Sterile Processing Area
BE27-1 Clean Storage (Positive)BE27B-1 Sterile Prep. (Positive)BE28-1 Decon (Negative)Medivator Rm. (Positive)
Grill #1 CFM: 95
Grill #2 CFM:539
Grill #3 CFM: BLOCKEDGrill #12 CFM: -403
Grill #4 CFM: 150Grill #7 CFM: 1179Grill #13 CFM: -390
Grill #5 CFM: BLOCKEDGrill #8 CFM: 627Grill #14 CFM: REMOVEDSupply Grill CFM: 227
Grill #6 CFM: 181Grill #9 CFM: 983976Grill #15 CFM: -298Exhaust Grill CFM: 0
Total CFM: 965Total CFM: 2782Total CFM: -1091Total CFM: N/A
Room Volume: 8960 CFRoom Volume: 8100 CFRoom Volume: 7400 CFRoom Volume: 723 CF
Min Total Air Changes: 4Min Total Air Changes: 4Min Total Air Changes: 6Min Air Changes: 6
Total Air Changes: 6.46Total Air Changes: 20.61Total Air Changes: 8.85Total Air Changes: 18.84
Pass or Fail: PASSPass or Fail: PASSPass or Fail: PASSPass or Fail: PASS