Attachment_03_-_Drawings.pdf

PDF 7 MB Posted

Attached to
Duchesne Bunkhouse Construction Federal contract opportunity
Solicitation number
AG-84N8-S-14-0052
Issued by
Department of Agriculture Forest Service R4-Intermountain Region

About this file

Attachment 03 - Drawings

View the file

Other files for this federal contract opportunity

Other files attached to Duchesne Bunkhouse Construction, newest first.
File Type Posted
AG-84N8-S-14-0052_0002.pdf PDF
Questions_and_Answers.docx DOCX document
AG-84N8-S-14-0052_0001.pdf PDF
Questions_and_Answers.docx DOCX document
Site_Visit_Attendees.pdf PDF
Attachment_07_-_AGAR_452.209-70.docx DOCX document
Attachment_04_-_Wage_Detemination.pdf PDF
Attachment_01_-Schedule_of_Items.pdf PDF
Attachment_05_-_Geotechnical_Report.pdf PDF
Attachment_02_-_Specifications.docx DOCX document
Attachment_06_-_Subcontractor_Reporting_Form.docx DOCX document
AG-84N8-S-14-0052.docx DOCX document
Show all 12

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

fo r D av id J ep ps en

4/ 3/

4/ fo r D av id J ep ps en fo r D av id J ep ps en alanmckean Typewritten Text alanmckean Typewritten Text alanmckean Typewritten Text alanmckean Typewritten Text alanmckean Typewritten Text fo r D av id J ep fo r D av id J ep fo r D av id J ep fo r D av id J ep

D av id J ep fo r D av id J ep

D av id J ep fo r D av id J ep fo r D av id J ep fo r D av id J ep fo r D av id J ep fo r D av id J ep

D av id J ep fo r D av id J ep fo r D av id J ep fo r D av id J ep fo r D av id J ep fo r D av id J ep

FIRE SPRINKLER

FLOW SENSOR

CONNECT TO AND

ACTIVATES BELL

ONLY

SPRINKLER FLOW

ALARM BELL

A

A

A

A

A

A

BB

B

B

BB

B

A AA

A AA

B B

B

B

B

B

D

E E

C

M

M

A-4

A-4

A-4

A-4

A-4

A-10 A-10

A-10

A-10A-12

A-11

A-12+14

A-20

A-16,18

A- 13+15 A-17,19

A-21A-22

UNDER SINK FOR

DISHWASHER

A-4

A-23 A-23

A-23

A-23

A-23

J

J

A-24A-25

A-24

A-24 A-24A-25

A-25

A-25

A-29

A-26

A-26

A-26

A-27

A-28

A-29

A-29

A-29 A-30

A-30 A-30 A-30

A-22

A-22

A-22

A-31

A-31

A-31

A-31

A-31

A-31

A-31

A-31

A-23

A-23

SEE LEGEND FOR MORE

INFORMATION

SPLIT WIRE THE 20 AMP,

120 VAC RECEPTACLE

FOR 2 CIRCUITS,

MULTIWIRE IS ALLOWED

IN THESE CASES ONLY.

G

A-23

A-31

MOUNT BOTH TV

AND RECEPTACLE

AT 48" TO CENTER

ABOVE FINISHED

FLOOR.

MOUNT LIGHT ABOUT 12

FEET ABOVE FINISHED

GRADE.

SURGE SUPPRESSION FOR

SATELLITE TV ENTRANCE WITH

LOCAL GROUNDING ELECTRODE

AND BOND BACK TO ELECTRICAL

SERVICE.

GENERAL ELECTRICAL NOTES

THE WORK AT THE SITE INCLUDES:

1. COORDINATING ALL CUSTOMER REQUIRED WORK AND EQUIPMENT TO COMPLY WITH MOON

LAKE ELECTRIC (435-722-5400) REQUIREMENTS AND PROJECT SPECIFICATIONS TO PROVIDE

FOR UNDERGROUND ELECTRICAL SERVICES AND WITH STRATA NETWORKS (345-622-5007) FOR

PHONE AND RELATED SERVICES. VERIFY SERVICE ENTRANCE LOCATIONS WITH BUILDING

SITING IN COORDINATION WITH UTILITY PROVIDERS. SHEET W1 SHOWS UTILITY POLE

LOCATIONS THAT MOON LAKE ELECTRIC MAY USE FOR BEGINNING THE SERVICE LATERAL.

2. PROVIDE A 36-INCH MINIMUM TRENCH DEPTH WITH A MINIMUM BURIAL DEPTH OF 30-INCHES

PER POWER COMPANY BEDDING AND BACKFILL REQUIREMENTS. SERVICE SHALL BE KEPT

36-INCHES FROM WATER OR GAS SERVICES.

3. ELECTRICAL SERVICE EQUIPMENT SHALL BE RATED FOR 200 AMP MINIMUM AND 22,000 SHORT

CIRCUIT CURRENT RATED (MAY BE SERIES RATED), EQUIVALENT TO SQUARE D HOMELINE OR

BETTER, NO TANDEM OR HALF SIZED BREAKERS ALLOWED.

4. ELECTRICAL SERVICE METERBASES SHALL BE INSTALLED WITH IMC AND SWEEP PER

SPECIFICATIONS, WITH CENTER OF METER LOCATED BETWEEN 5 AND 6-FEET ABOVE

FINISHED GRADE.

5. PROVIDE A 2-INCH CONDUIT FROM STRATA NETWORK APPROVED LOCATION FOR

PHONE/INTERNET SERVICE. DIRECT BURIED CABLE(S) THAT WILL MEET REQUIREMENTS FOR

ALL THREE SERVICES INSTALLED BEFORE CONTRACT IS COMPLETE MAY SUBSTITUTE FOR

THE CONDUIT. CONDUIT OR CABLES SHALL BE BURIED 24-INCHES MINIMUM. IF SERVICE

POINT IS AT THE POWER COMPANY POLE SHOWN IT MAY BE INSTALLED IN THE SAME TRENCH

AS THE ELECTRICAL SERVICE AT 30-INCHES MINIMUM. KEEP SEPARATE FROM POWER

COMPANY INSTALLED SECONDARY A MINIMUM OF 12-INCHES.

6. PHONE SERVICE SHALL BE BROUGHT INTO THE BUILDING NEXT TO THE ELECTRICAL SERVICE.

HOME RUN EACH EACH INTERNAL PHONE TO THIS LOCATION INTO COMBINER/SERVICE BOX.

LABEL EACH RUN IN A PERMANENT AND UNDERSTANDABLE MANNER. GROUND PER CODE

AND SPECIFICATIONS.

7. TELEVISION SERVICE SHALL BE SATELLITE BASED WITH DISH AND CABLE TO DISH FROM

SURGE ARRESTOR/GROUNDING POINT BY OTHERS. GROUND PER CODE, SPECIFICATIONS,

AND AS SHOWN.

8. ELECTRICAL IN HOUSING SHOWN IS A MINIMUM AND MAY VARY BASED ON SUBMITTED FLOOR PLANS. IF ALTERNATIVE SIZED BUILDING IS APPROVED, ELECTRICIAN SHALL SUBMIT MODIFIED

ELECTRICAL PLAN. ADDITIONAL LUMINAIRES AND OR TYPE CHANGES MAY BE REQUIRED AT

NO COST TO PROVIDE THE SAME LEVEL OF SERVICE. ADDITIONAL RECEPTACLES MAY BE

REQUIRED TO MEET INTENT AS SHOWN.

9. LOAD CENTER LOCATION(S) ARE NOT SHOWN. LOCATE IN HALLWAYS OR OTHER COMMON

WALL SPACE NOT CONFLICTING WITH OTHER USE, SUBJECT TO APPROVAL BEFORE

INSTALLATION BY CONTRACTING OFFICER.

10. SMOKE, CARBON DIOXIDE, VISUAL, AND COMBINATION ALARMS SHALL ALL BE

INTERCONNECTED.

RV PARKING OPTION

11. SEE SHEET W1 FOR SITE PLAN SHOWING THE LOCATIONS OF 3 TRAILER PEDESTALS TO BE

SERVED FROM A COMMON ELECTRICAL SERVICE SEPARATE FROM THE BUNKHOUSE.

12. INSTALL SEPARATE ELECTRICAL SERVICE AS CALLED FOR WITH ALL-IN-ONE COMBINATION

SERVICE ENTRANCE DEVICE.

13. PROVIDE ELECTRICAL POWER ONLY TO EACH PAD FROM COMMON SERVICE AS SHOWN. NO

PHONE OR OTHER RELATED SERVICES SHALL BE PROVIDED AT THE PADS. RV PEDESTALS

SHALL BE SQUARE D PAK75PG OR EQUAL. CIRCUITS SHALL BE HOME RUN SIZE 1" CONDUIT

WITH 3#6 THWN AND 1 #10 GROUND.

CRAWL SPACES AND ATTIC SPACES LIGHTING AND RECEPTACLES

1- AT EACH CRAWL OR ATTIC ACCESS, INSTALL ONE GFCI RECEPTACLE AND SWITCH ON THE CIRCUIT SERVING THE

ROOM WITH THE ACCESS.

2- WITHIN EACH CRAWL AND ATTIC SPACE SECTION INSTALL 2 TYPE "N" LUMINAIRES LOCATED TO LIGHT THE AREA.

LOCATIONS SHALL BE APPROVED BY THE CONTRACTING OFFICER BEFORE INSTALLATION.

3- A CRAWL SPACE OR ATTIC ACCESS SECTION SHALL BE DEFINED AS MINIMALLY 1 PER BUILDING MAJOR AXIS WITH FIRE WALL SEPARATIONS OR OTHER SIMILAR BARRIERS CREATING ADDITION SECTIONS THAT SHALL HAVE

ACCESS, RECEPTACLE, AND SWITCH LOCATIONS.

LAMPS FOR SPOT LIGHT

LED PAR38 26W SHALL HAVE THE FOLLOWING MINIMUM SPECIFICATIONS: RATED 26 WATTS OR LESS, >1400 INITIAL LUMENS, 2700-3000 K COLOR TEMPERATURE, CRI>80, 25 DEGREE BEAM SPREAD, WET LOCATIONS RATED. GE

LIGHTING #68184 LED26DP38S830/25 MEETS THIS REQUIREMENT.

LOAD CENTER DISTRIBUTION

THE FOLLOWING IS A LIST OF COMMON CIRCUITS MINIMUM:

# AMPS DESCRIPTION

A-1 20 3 NORTHEAST BEDROOMS AND EXTERIOR LIGHTS AND

RECEPTACLES, NORTHEAST HALL AND EXTERIOR LIGHTS

A-2 20 3 NORTHWEST BEDROOMS LIGHTS AND RECEPTACLES, HALL AND

EXTERIOR RECEPTACLES

A-3 20 4 SOUTHEAST BEDROOMS LIGHTS AND RECEPTACLES, SOUTH SIDE

SOUTH HALL AND EXTERIOR RECEPTACLES

A-4 20 LIGHTS-BATHROOMS, MECH, SOUTH AND SOUTHEAST HALL,

STORAGE, JANITOR, MUDROOM, LAUNDRY, PANTRY

A-5 20 RECEPTACLE-EAST DORM BATHROOM NORTH SINK

A-6 20 RECEPTACLE-EAST DORM BATHROOM SOUTH SINK

A-7 20 RECEPTACLE-WEST DORM BATHROOM SOUTH SINK

A-8 20 RECEPTACLE-WEST DORM BATHROOM NORTH SINK

A-9 20 RECEPTACLE-ADA BATHROOM SINK

A-10 20 RECEPTACLE-SOUTHEAST HALL, NORTH SIDE SOUTH HALL, MECH,

JANITOR, MUDROOM, EXTERIOR

A-11 20 RECEPTACLE- SMALL BATHROOM

A-12+14 20 SPLIT CIRCUIT RECEPTACLE-WASHERS (MULTIWIRE)

A-13+15 20 SPLIT CIRCUIT RECEPTACLE- GAS DRYERS (MULTIWIRE)

A-16,18 30 RECEPTACLE-NORTH ELECTRIC DRYER

A-17,19 30 RECETPACLE-SOUTH ELECTRIC DRYER

A-20 20 RECEPTACLE-LAUNDRY COUNTER

A-21 20 RECEPTACLE-PANTRY ICE MACHINE

A-22 20 RECEPTACLE-PANTRY, KITCHEN NORTH WALL

A-23 20 LIGHTS-KITCHEN, EXTERIOR AND SITE, COMMON AREA,

RANGEHOODS

A-24 20 RECEPTACLE-EAST COUNTERS, FRIDGE

A-25 20 RECEPTACLE-SOUTHEAST COUNTERS, EAST STOVE

A-26 20 RECEPTACLE-ISLAND

A-27 20 RECEPTACLE-EAST DISHWASHER

A-28 20 RECEPTACLE-WEST DISHWASHER

A-29 20 RECEPTACLE-SOUTH COUNTER WEST SIDE

A-30 20 RECEPTACLE-WEST COUNTER, FRIDGE

A-31 15 RECEPTACLE- COMMON ROOM, EXTERIOR

A-32 15 SMOKE ALARMS, ALARM BELL CIRCUIT

OTHER CIRCUITS THAT ARE NOT SHOWN INCLUDE BUT ARE NOT LIMITED TO:

FIRE PUMP DISCONNECT AND PROTECTION IF REQUIRED SHALL BE BEFORE THE

BUILDINGS MAIN.

FURNACE(S) AND SINGLE POLE SWITCH DISCONNECTS

AIR CONDITIONER(S) AND GENERAL DUTY DISCONNECTS

WATER HEATER(S) - GAS WATER HEATERS WITH SMALL LOADS MAY BE PLACED ON

OTHER CIRCUITS.

REQUIRED CRAWL SPACE AND ATTIC SPACE LIGHTING AND RECEPTACLES AS

DESCRIBED MAY BE PLACED ON OTHER CIRCUITS.

THE SITE LIGHT (SEE SITE PLAN) IS SHOWN ON CIRCUIT A-23.

HAND DRYER CIRCUITS A-7 AND A-10 REQUIRE FIXED-IN PLACE, HANDLE PADLOCK

ATTACHMENTS ON CIRCUIT BREAKERS.

fo r D av id J ep

FIRE SPRINKLER

A

A-1

A-1

A-1

A-1

A-1

S

A

A-1

A-1

A-1

A-1

A-1

S

A

A-1

A-1

A-1

A-1

A-1

S

A

A-2

A-2

A-2

A-2

A-2A

A-2

A-2

A-2

A-2

A-2A

A-2

A-2

A-2

A-2

A-2

A

A-3

A-3

A-3

A-3

A-3

S

A

A-3

A-3

A-3

A-3

A-3

S

A

A-3

A-3

A-3

A-3

A-3

S

A

A-3

A-3

A-3

A-3

A-3

B

BB B B B B B B

C

E

D

D

F

F

M

M

M

A-1

A-1

A-1

A-2

A-2

A-3

A-3

A-4

A-4

A-4

A-4

A-4

A-4A-4

A-4

A-5

A-6

A-10 A-8A-7A-10

A-9

A-10

C

SS

B

F

F

A-4

A-4

F

F

A-4

A-4

A-10 A-2

A-1

S

S

C

M M

SERVICE CALCULATIONS

NEC 220.82

(3VA/FT2)(~3860FT2)= 11,580

(1.5KW)(6 SMALL APPL)= 9,000

(1.5KW)(2 LAUNDRY)= 3,000

TOTAL= 23,580

3,000 @ 100%= 3,000 20,580 @ 35%= 7,203

TOTAL= 10,203

ICE MAKER= 1,400

2 FREEZERS= 1,200

2 DISHWASHERS= 2,060

2 DISPOSALS= 1,380

TOTAL= 6,040

4+ APPLIANCES @75%= 4,530

2 DRYERS DEMAND LOAD= 10,000

TOTAL VA= 24,733

OTHER LOADS THAT SHALL BE INCLUDED:

FURNACE MOTORS @ 75%

A/C CONDENSERS @ 100%

SERVICE SHALL BE 200 AMP MINIMUM

WITH FULL SIZED NEUTRAL.

fo r D av id J ep

FINISH GRADE

4"

24"

CONCRETE

6"x6"

PRESSURE

TREATED

WOOD

POST

(TYPICAL)

UNISTRUT

SUPPORT

(TYPICAL)

ALL-IN-ONE

COMBINATION

SERVICE

ENTRANCE

WITH METER

HEIGHT PER

MOON LAKE

REQUIREMENTS