PROJECT SPECIFICATIONS

A. ALL WORK ON THE PROJECT SHALL CONFORM TO ALL LOCAL CITY, STATE AND

NATIONAL CODES AND REGULATIONS, INCLUDING BUT NOT LIMITED TO THE

N.F.P.A., N.E.C., U.B.C., I.E.C.C., I.M.C., U.P.C., THE LOCAL UTILITY SERVING

COMPANIES AND THE AUTHORITY HAVING JURISDICTION.

B. THE WORK ON THIS PROJECT SHALL CONSIST OF ALL ITEMS, ARTICLES,

MATERIALS, EQUIPMENT, AND LABOR FURNISHED TOGETHER ALONG WITH ALL

INCIDENTAL ITEMS REQUIRED BY GOOD PRACTICE AND WORKMANSHIP TO

PROVIDE A SATISFACTORY, COMPLETE AND FUNCTIONAL SYSTEM IN

ACCORDANCE WITH THE DRAWINGS AT NO ADDITIONAL COST TO THE

CONTRACTING OFFICER.

C. THE CONTRACTOR SHALL BE RESPONSIBLE FOR AND PAY FOR ALL FEES AND

PERMITS REQUIRED FOR WORK UNDER THEIR CONTRACT AND UNDER THEIR

SUPERVISION BY SUBCONTRACT.

D. MANUFACTURER'S TRADE NAMES AND CATALOG NUMBERS ARE LISTED TO

INDICATE SPECIAL CONDITIONS AND QUALITY OF MATERIALS OR EQUIPMENT

SUPPLIED. ALTERNATIVE EQUIPMENT OR MATERIALS MAY BE SUBMITTED

DURING SHOP DRAWING REVIEW PROCESS AFTER AWARD OF BIDS.

E. ALL WORK BY THE CONTRACTOR IS SUBJECT TO REVIEW AT ANY TIME BY THE

CONTRACTING OFFICER.

F. ALL WORK TO BE PERFORMED SHALL FIRST BE SCHEDULED AND SUBMITTED TO

THE CONTRACTING OFFICER FOR ACCEPTANCE.

G. SMOKING SHALL NOT BE PERMITTED ANYWHERE IN THIS FACILITY.

H. THE CONTRACTOR SHALL BE CAREFUL NOT TO BLOCK ANY PATHS OF EGRESS

WHILE PERFORMING THE WORK SPECIFIED.

I. THE CONTRACTOR SHALL BE RESPONSIBLE FOR CLEANUP OF ALL MATERIALS

RESULTING FROM HIS/HER WORK. CLEANUP SHALL BE PERFORMED TO THE

LEVEL OF ACCEPTANCE OF THE CONTRACTING OFFICER.

J. THE CONTRACTOR SHALL AND HEREBY DOES WARRANT AND GUARANTEE THAT

ALL WORK EXECUTED UNDER HIS/HER CONTRACT SHALL BE FREE OF DEFECTS

OF MATERIALS AND WORKMANSHIP FOR A PERIOD OF ONE YEAR FROM THE

DATE OF SUBSTANTIAL COMPLETION.

K. SUBMIT ALL SHOP DRAWINGS FOR ALL EQUIPMENT ASSOCIATED WITH THIS

PROJECT TO THE CONTRACTING OFFICER FOR REVIEW/APPROVAL PRIOR TO

ORDERING ANY EQUIPMENT. U.N.O., ALL MATERIALS AND EQUIPMENT SHALL BE

NEW.

L. UPON SUBSTANTIAL COMPLETION THE CONTRACTOR SHALL SUBMIT AN

OPERATIONS AND MAINTENANCE (O&M) MANUAL/BROCHURE OF ALL EQUIPMENT

TO THE CONTRACTING OFFICER FOR REVIEW/APPROVAL. AFTER RECEIVING

APPROVAL FROM CONTRACTING OFFICER, PROVIDE (2 APPROVED COPIES) TO

CONTRACTING OFFICER AND PROVIDE THE NECESSARY TRAINING TO THE

FACILITIES PERSONNEL REGARDING ALL EQUIPMENT ASSOCIATED WITH THIS

PROJECT.

SEISMIC GENERAL NOTES

A. ALL MECHANICAL AND PLUMBING EQUIPMENT SHALL BE SEISMICALLY BRACED

PER THE 2012 INTERNATIONAL BUILDING CODE. SEISMIC DESIGN

REQUIREMENTS FOR THE PROJECT ARE AS FOLLOWS:

• SEISMIC DESIGN CATEGORY: D

• IMPORTANCE FACTOR (Ip): 1.0

• IMPORTANCE FACTOR FOR GAS PIPING: 1.5

B. THE MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE TO INCLUDE BRACING

AND RESTRAINTS. BRACING & RESTRAINT DETAILS SHALL BE INCLUDED IN SHOP

DRAWING SUBMITTAL FOR REVIEW AND BY THE ENGINEER.

18x12

16 �

RECTANGULAR DUCTWORK

ROUND DUCTWORK

AIR DEVICE NUMBER AND CFM

CEILING SUPPLY DIFFUSER

CEILING RETURN GRILLE

CEILING EXHAUST GRILLE

CEILING SLOT DIFFUSER

FLOOR REGISTER

SIDEWALL DIFFUSER OR GRILLE

VERTICAL TRANSITION-

RECTANGULAR SUPPLY DUCT

VERTICAL TRANSITION-

ROUND SUPPLY DUCT

VERTICAL TRANSITION-

RECTANGULAR RETURN DUCT

VERTICAL TRANSITION-

ROUND RETURN DUCT

VERTICAL TRANSITION-

RECTANGULAR EXHAUST DUCT

VERTICAL TRANSITION-

ROUND EXHAUST DUCT

TURNING VANE

MANUAL VOLUME DAMPER

REMOTE VOLUME DAMPER

MOTORIZED DAMPER

ZONE DAMPER

FIRE DAMPER

SMOKE DAMPER

FIRE/SMOKE DAMPER

HVAC LEGEND

MARK

CFM

T

C

H

SP

D S

THERMOSTAT

CARBON DIOXIDE SENSOR

HUMIDISTAT

WALL SWITCH

STATIC PRESSURE SENSOR

DUCT SMOKE DETECTOR

HVAC CONTROLS LEGEND

AIR SEPARATOR

AUTOMATIC AIR VENT

MANUAL AIR VENT

AUTOFLOW VALVE

BACKFLOW PREVENTER

BALL VALVE

BUTTERFLY VALVE

CIRCUIT SETTER

CHECK VALVE

COMBINATION FLOW CONTROL

VALVE

COMBINATION STRAINER VALVE

TWO-WAY CONTROL VALVE

THREE-WAY CONTROL VALVE

HOSE END DRAIN

FLEXIBLE CONNECTOR

FLOW METERING STATION

FLOW SWITCH

GATE VALVE

MULTI-PURPOSE VALVE

PIPE WELL- EMPTY

PRESSURE GAUGE AND COCK

PRESSURE REDUCING VALVE

PRESSURE RELIEF VALVE

PRESSURE SENSOR

PRESSURE SWITCH

PRESSURE/TEMPERATURE PORT

SOLENOID VALVE

STRAINER

STRAINER W/ BLOWOUT

TEMPERATURE SENSOR

THERMOMETER

THREE-WAY VALVE

HVAC PIPING SPECIALTIES LEGEND

PROJECT LOCATION: MISSOULA, MT

PROJECT ALTITUDE: 3,200 FEET ABOVE SEA LEVEL

SUMMER DESIGN TEMP: 92.8°F DRY BULB, 62.1°F WET BULB (ASHRAE 0.4% DESIGN)

WINTER DESIGN TEMP: -20°F DRY BULB

TEMP. CONTROL GEN'L NOTES

A. THE MECHANICAL CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR THE

SUCCESSFUL OPERATION OF THE MECHANICAL INSTALLATION AND SYSTEMS

INCLUDING CONTROLS. THE M.C. SHALL HIRE AN ELECTRICAL CONTRACTOR AS

NECESSARY TO ACHIEVE THE SPECIFIED SEQUENCE OF OPERATIONS.

CONTROL WIRING IS NOT SHOWN ON THE ELECTRICAL DRAWINGS.

ELECTRICAL WORK REQUIRED FOR SYSTEM OPERATION BUT NOT SHOWN ON

THE ELECTRICAL DRAWINGS SHALL BE THE RESPONSIBILITY OF THE

MECHANICAL CONTRACTOR TO HIRE AN ELECTRICIAN INDEPENDENT FROM

THIS PROJECT'S CONTRACT DOCUMENTS.

B. IN GENERAL ALL TEMPERATURE CONTROLS ARE STAND-ALONE FOR EACH

SPECIFIC PIECE OF MECHANICAL EQUIPMENT. THERE IS NOT A CENTRAL

BUILDING MANAGEMENT SYSTEM. ROUGH-IN WIRING FOR THERMOSTATS,

SENSORS, AND OTHER CONTROL COMPONENTS ARE THE RESPONSIBILITY OF

THE MECHANICAL CONTRACTOR.

HVAC GENERAL NOTES

A. ALL NEW PIPING, DUCTWORK AND EQUIPMENT TO BE INSTALLED IN

ACCORDANCE WITH THE 2012 INTERNATIONAL MECHANICAL CODE AND THE 2012

INTERNATIONAL BUILDING CODE REQUIREMENTS.

B. DRAWINGS ARE DIAGRAMMATIC IN NATURE AND DO NOT NECESSARILY SHOW

EXACT LOCATIONS AND SIZES OF ALL EXISTING DUCTWORK, PIPING, SYSTEM

AND EQUIPMENT UNLESS SPECIFICALLY DIMENSIONED. IT IS NOT THE INTENT OF

THESE DRAWINGS TO GRAPHICALLY REPRESENT ALL OF THE WORK REQUIRED

FOR A COMPLETE INSTALLATION IN EVERY RESPECT. THE PURPOSE OF THESE

PLANS IS TO INDICATE THE INTENDED SIZES, APPROXIMATE LOCATION AND

ROUTING OF MAJOR COMPONENTS. ADJUST TO FIELD CONDITIONS. ACTUAL

CONDITIONS AND LOCATIONS SHALL BE FIELD-VERIFIED.

C. EXAMINE AND REFER TO ALL ARCHITECTURAL, STRUCTURAL, ELECTRICAL,

MECHANICAL, FIRE PROTECTION AND SITE CIVIL DRAWINGS FOR

CONSTRUCTION CONDITIONS WHICH MAY AFFECT THE CONTRACTOR'S WORK.

INSPECT THE EXISTING FACILITIES FOR VERIFICATION OF CONDITIONS AND

SYSTEMS WHICH MAY HAVE AN EFFECT ON WORK PROR TO SUBMISSION OF BID.

D. IT IS NECESSARY FOR ALL TRADES INVOLVED TO COORDINATE WITH EACH

OTHER AND VERIFY THAT THERE ARE NO CONFLICTS IN LOCATION OF DUCTS,

CONDUITS, DIFFUSERS, BOXES AND OTHER ITEMS THROUGHOUT THIS PROJECT

BEFORE FINAL PLACEMENT OF MATERIALS. REFER TO ARCHITECTURAL,

STRUCTURAL, MECHANICAL, AND ELECTRICAL DRAWINGS AND FIRE

PROTECTION SHOP DRAWINGS FOR ADDITIONAL DETAILS NECESSARY FOR

COORDINATION.

E. THE CONTRACTOR SHALL PROVIDE MATERIALS, LABOR, TRANSPORTATION,

TOOLS, PERMITS, FEES, INSPECTIONS, UTILITIES AND INCIDENTALS NECESSARY

FOR THE COMPLETE INSTALLATION OF THE WORK INDICATED AND DESCRIBED

IN THESE CONTRACT DOCUMENTS.

F. LOCATIONS AND DIMENSIONS OF EXISTING FACILITIES IDENTIFIED ON THIS

DRAWING ARE APPROXIMATE AND REPRESENT THE BEST AVAILABLE

INFORMATION AVAILABLE AT THE TIME OF DESIGN. FIELD VERIFY LOCATIONS

AND DIMENSIONS PRIOR TO ORDERING EQUIPMENT AND DURING

PERFORMANCE OF THE WORK. PROVIDE ALL DEMOLITION WORK, NECESSARY

FITTINGS, TRANSITIONS, AND OTHER COMPONENTS AS REQUIRED FOR A

COMPLETE AND FUNCTIONAL INSTALLATION OF NEW SYSTEMS AT NO

ADDITIONAL COST TO THE OWNER.

G. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ANY ADDITIONAL DETAILS OR

SPECIAL CONSTRUCTION REQUIRED IN ORDER TO COMPLETE THE

INSTALLATION, WHETHER MENTIONED OR NOT. THE CONTRACTOR SHALL

PROVIDE ALL MATERIALS AND EQUIPMENT FOR THE PROPER INSTALLATION OF

THE TYPE OF EQUIPMENT AND SYSTEMS INDICATED AT NO ADDITIONAL COST TO

C.O.

H. ALL EQUIPMENT SHALL BE INSTALLED LEVEL, PLUMB, AND FIRMLY ANCHORED IN

LOCATIONS INDICATED. OBSERVE MANUFACTURER'S INSTALLATION

INSTRUCTIONS AND RECOGNIZED INDUSTRY PRACTICES TO INSURE THAT

PRODUCTS SERVE THEIR INTENDED FUNCTION.

I. FOLLOW MANUFACTURE'S WRITTEN INSTALLATION INSTRUCTIONS FOR

RUNNING THE COMBUSTION AIR AND VENT PIPING AS WELL AS THE

TERMINATION THROUGH THE ROOF OR WALL. FOLLOW ALL SAFETY

INSTRUCTIONS.

J. CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTING ALL FIRE BARRIERS,

FIRE PARTITIONS, FIRE WALLS OR ANY OTHER FIRE AND/OR SMOKE SEPARATION

WITHIN THE BUILDING AS DEFINED BY THE ARCHITECTURAL CODE PLAN WITH A

UL LISTED FIRE AND/OR SMOKE STOP SYSTEM.

K. ALL MATERIAL IN A PLENUM RATED SPACE SHALL HAVE A SPREAD RATING NOT

EXCEEDING 25 AND A SMOKE DEVELOPMENT RATING NOT EXCEEDING 50.

L. PROVIDE ACCESS DOORS TO ALLOW SERVICE AND INSPECTION OF EQUIPMENT,

VALVES, DAMPERS, & DEVICES INSTALLED ABOVE NON-REMOVABLE CEILINGS.

M. ALL ELEMENTS PENETRATING BUILDING COMPONENTS (ROOF ASSEMBLIES,

WALL ASSEMBLIES, ETC.) SHALL BE SEALED WEATHER AND WATER TIGHT.

N. ALL NEW PIPING SHALL BE IDENTIFIED WITH SETON SETMARK PIPE MARKERS,

LETTERED TO MATCH EXISTING AND MARKED AT A MAXIMUM OF EVERY 25 FT.

ALSO, ALL NEW VALVES SHALL BE IDENTIFIED WITH BRASS OR ALUMINUM VALVE

TAGS.

O. PROVIDE PIPE GUIDES, EXPANSION JOINTS, AND HANGERS PER

MANUFACTURER'S RECOMMENDATIONS.

P. ALL PIPING WALL PENETRATIONS SHALL HAVE A CHROME ESCUTCHEON PLATE.

ALL SOLDER TO BE LEAD-FREE TYPE.

Q. VERIFY THE LOCATION OF ALL THERMOSTATS AND SENSORS WITH THE

ENGINEER AND ARCHITECT PRIOR TO INSTALLATION. INSTALL THERMOSTATS 60"

ABOVE FINISHED FLOOR PER ADA REQUIREMENTS.

R. ALL DUCT WORK SHALL BE CONSTRUCTED IN ACCORDANCE WITH THE LATEST

REQUIREMENTS OF SMACNA DUCT WORK CONSTRUCTION MANUALS, MINIMUM

GAUGE OF 24, GALVANIZED STEEL. DUCTWORK SHALL BE AIRTIGHT (5%

LEAKAGE). ALL TRANSVERSE JOINTS AND LONGITUDINAL SEAMS SHALL BE

SEALED. FABRICATE ELBOWS WITH CENTERLINE RADIUS EQUAL TO 1.5 TIMES

THE DUCT WIDTH IN THE PLANE OF THE TURN; AND FABRICATE TO INCLUDE

FACTORY MANUFACTURED TURNING VANES IN ELBOWS WHERE SHORTER

RADIUS IS NECESSARY.

S. PROVIDE FLEX CONNECTIONS FROM ALL DUCT WORK TO EQUIPMENT

CONNECTIONS ON THIS PROJECT.

T. FLEXIBLE DUCT SHALL NOT BE USED IN PLACE OF ELBOWS.

U. A COMPLETE AIR AND WATER SYSTEM TEST AND BALANCE (T&B) SHALL BE

PERFORMED BY A NEBB OR AABC CERTIFIED T&B CONTRACTOR FOR ALL NEW

AND MODIFIED DEVICES. MECHANICAL CONTRACTOR SHALL MODIFY EQUIPMENT

AS DIRECTED BY BALANCING CONTRACTOR, IF REQUIRED, TO ACHIEVE DESIGN

PARAMETERS WITH NO EXTRA COST TO THE C.O. T&B REPORT SHALL BE

PREPARED AND SUBMITTED TO C.O. REPORT SHALL INCLUDE ALL AIR AND

WATER FLOW READINGS, ALL TEMPERATURE AND PRESSURE SETPOINTS AND

ALL ELECTRICAL CONDITIONS FOR ALL DEVICES. REPORT SHALL ALSO VERIFY

PROPER OPERATION OF ENTIRE CONTROL SYSTEM. WHERE REQUIRED FOR AIR

BALANCING, INSTALL ADDITIONAL MANUAL VOLUME DAMPERS & BALANCING

VALVES.

V. THE MECHANICAL CONTRACTOR SHALL PROVIDE THE C.O.'S REPRESENTATIVES

WITH UP TO 4 HOURS OF TRAINING TO ENSURE PROPER OPERATION AND

MAINTENANCE OF THE SYSTEMS.

PROJECT INFORMATION

HEAT PUMP RETURN

HEAT PUMP SUPPLY

HOT WATER RETURN

HOT WATER SUPPLY

REFRIGERANT

CONDENSATE

HVAC PIPING SYSTEMS LEGEND

HVAC DEMO NOTES

A. IT IS THE INTENT OF THIS PROJECT TO DEMOLISH

EXISTING MECHANICAL SYSTEMS. COORDINATE ALL

UTILITY OUTAGES WITH THE OWNER PLANNING

DESIGN AND CONSTRUCTION THROUGHOUT THE

DURATION OF CONSTRUCTION.

B. ALL EXISTING MECHANICAL EQUIPMENT, DUCTWORK,

PIPING SHOWN HATCHED AND NOTED FOR

DEMOLITION SHALL BE DEMOLISHED. EXISTING

MECHANICAL EQUIPMENT SHOWN GRAY, UNHATCHED,

AND NOT NOTED FOR DEMOLITION IS TO REMAIN

UNCHANGED. PROTECT ALL EXISTING EQUIPMENT TO

REMAIN.

C. PRESENT ALL DEMOLISHED EQUIPMENT TO THE

OWNER FOR SALVAGE. REMOVE ANY UNWANTED

EQUIPMENT FROM SITE.

D. COORDINATE WITH THE GENERAL CONTRACTOR TO

PATCH AND REPAIR THE FLOORS, ROOF, WALLS AND

ALL OTHER ARCHITECTURAL ASSEMBLIES

ASSOCIATED WITH THE MECHANICAL DEMOLITION.

GEN. SYMBOLS LEGEND

KEY NOTE SYMBOL

TERMINATION POINT OF DEMOLITION WORK

POINT OF CONNECTION TO EXISTING WORK

AC ALTERNATING CURRENT (OR) AIR CONDITIONER

AHU AIR HANDLING UNIT

ADJ ADJUSTABLE

AV AIR VENT

AWG AMERICAN WIRE GAUGE

B.D.D. BACKDRAFT DAMPER

BMS BUILDING MANAGEMENT SYSTEM

BOD BASIS OF DESIGN

BTU/HR BRITISH THERMAL UNITS PER HOUR

C COMMON

CD CONDENSATION DRAIN (OR ) CONTROL DAMPER

CFM CUBIC FEET PER MINUTE

C.O. CONTRACTING OFFICER

CxA COMMISSIONING AUTHORITY / AGENT

(D) DEMOLISH / DEMOLITION

CUH CABINET UNIT HEATER

DSF DESTRATIFICATION FAN

(E) EXISTING

EA EXHAUST AIR / EACH

EAT ENTERING AIR TEMPERATURE

E.C. ELECTRICAL CONTRACTOR

EF EXHAUST FAN

ESP EXTERNAL STATIC PRESSURE

EWH ELECTRIC WALL HEATER

EWT ENTERING WATER TEMPERATURE

(F) FUTURE

FPM FEET PER MINUTE

GUH GAS UNIT HEATER

G.C. GENERAL CONTRACTOR

HGB HOT GAS BYPASS

HW S/R HOT WATER SUPPLY/RETURN

HWP HOT WATER PUMP

HWUH HOT WATER UNIT HEATER

IN INCHES

IN WG INCHES WATER GAUGE

LAT LEAVING AIR TEMPERATURE

LWT LEAVING WATER TEMPERATURE

M.C. MECHANICAL CONTRACTOR

MBH THOUSANDS OF BTU/HR

(N) NEW

NC NORMALLY CLOSED

NG NATURAL GAS

NO NORMALLY OPEN

N.T.S. NOT TO SCALE

OA OUTDOOR AIR

O&M OPERATIONS & MAINTENANCE

PG PROPYLENE GLYCOL

PSIG POUNDS PER SQUARE INCH (GAUGE)

RA RETURN AIR

RL REFRIGERANT LIQUID

RS REFRIGERANT SUCTION

RTU ROOFTOP UNIT

SA SUPPLY AIR

T.C. TEMPERATURE CONTROL

T.B.D. TO BE DETERMINED

TSP TOTAL STATIC PRESSURE

T-STAT THERMOSTAT

TYP. TYPICAL

U.N.O. UNLESS NOTED OTHERWISE

UH UNIT HEATER

UV UNIT VENTILATOR

VAV VARIABLE AIR VOLUME

VFD VARIABLE FREQUENCY DRIVE

MECHANICAL ABBREVIATIONS

0 1 2 3 4 5 6 7 8 9 10 inches

DRAWING NO.

PKG

NO.

SHEET

OF

PROJECT NO.:

REVISIONS:

DESIGNED

TECH. REVIEW

CADD

DESIGNED SUB SHEET NO. TITLE OF SHEET

THOMAS R.

COBURN

No. 20022 PE

I S

S

E F

O R

P

LANO EN

G

IN

E E R

ON

T

M

ANA

LICENSED

3/ 8/ :1 8:

P M

M0.1

3.10.17C O N S T R U C T

IO

N D O C U M E N T S

MECH NOTES & LEGENDS

16079

ALWRI RENOVATION

FOREST SERVICE / ROCKY MOUNTAIN RESEARCH STATION

EJW

REB

TRC

smoses Text Box smoses Text Box

ACCESSORIES:

1. INCLUDE FUSED DISCONNECT, ECM FAN MOTORS & SPEED CONTROL FOR BALANCING, DOUBLE-WALL

INSULATED CABINET, MOTORIZED ISOLATION DAMPERS ON OA & EA AIR STREAMS, AND 14" INSULATED CURB.

2. PROVIDE MERV-13 FILTER ON OUTDOOR AIR AND MERV-8 FILTER ON EXHAUST AIR, BOTH UPSTREAM OF HEAT EXCHANGER. PROVIDE NEW FILTERS UPON COMPLETION OF WORK, PLUS ONE SET OF SPARE FILTERS.

3. FANS SHALL NOT NEED TO CYCLE FOR DEFROST. DRAIN CONNECTION SHALL NOT BE REQUIRED. NO

LIQUID CONDENSATE SHALL FORM AT HEAT EXCHANGER CORE.

CONTROL:

1. PROVIDE STAND-ALONE CONTROLLER BY MANUFACTURER TO CONTROL BLOWERS, AND OA AND EA DAMPERS, WITH FACTORY-MOUNTED ALARMS.

2. PROVIDE DIGITAL PROGRAMMABLE TIME-CLOCK, WALL-MOUNTED IN MECHANICAL ROOM, BY UNIT MANUFACTURER.

3. PROVIDE TRANSFORMERS AND RELAYS AS REQUIRED FOR LOW VOLTAGE CONTROL.

4. ERV SHALL CONTINUE TO RUN THROUGH LOW AMBIENT CONDITIONS WITHOUT CYCLING TO DEFROST.

DUCT MATERIAL SCHEDULE

DESCRIPTION SHAPE APPLICATION MATERIAL

PRESSURE

CLASS

INSULATION JACKET R-VALUE ADDITIONAL DETAILS

SUPPLY AIR RECTANGULAR INDOOR - CONDITIONED SHEET METAL 2" WRAP FACTORY APPLIED R-5 SEE BELOW

SUPPLY AIR ROUND INDOOR - CONDITIONED SPIRAL SHEET METAL 2" WRAP FACTORY APPLIED R-5 SEE BELOW

RETURN AIR RECTANGULAR INDOOR - CONDITIONED SHEET METAL 2" NONE - - SEE BELOW

RETURN AIR ROUND INDOOR - CONDITIONED SPIRAL SHEET METAL 2" NONE - - SEE BELOW

FRESH SUPPLY AIR FROM ERV RECTANGULAR INDOOR - CONDITIONED SHEET METAL 2" WRAP FACTORY APPLIED R-8 SEE BELOW

FRESH SUPPLY AIR FROM ERV ROUND INDOOR - CONDITIONED SPIRAL SHEET METAL 2" WRAP FACTORY APPLIED R-8 SEE BELOW

5' LENGTH MAX - SUPPLY ROUND INDOOR - CONDITIONED FLEX 2" INTEGRAL FACTORY APPLIED R-5 SEE BELOW

ROOFTOP DUCTWORK - FRESH SUPPLY AIR FROM ERV RECTANGULAR OUTDOOR - UNCONDITIONED SHEET METAL 2"

PROVIDE FACED CLOSED CELL FOAM

INSULATION BOARD WRAPPED WITH

POLYGUARD ALUMAGUARD COOLWRAP.

FACTORY APPLIED R-14 SEE BELOW

GENERAL NOTES:

1. PROVIDE SEISMIC BRACING OF ALL DUCTWORK AS REQUIRED BY LOCAL CODES.

2. ALL SHEET METAL DUCTWORK SHALL BE A MINIMUM OF 24 GAGE SHEET METAL.

3. ALL DUCTWORK SHALL BE CONSTRUCTED AND INSTALLED PER SMACNA GUIDELINES.

4. SEAL AND INSULATED ALL DUCTWORK PER 2012 I.E.C.C.

5. INSULATE EXHAUST DUCTWORK NOT ASSOCIATED WITH ERV WITHIN 10 FT OF PENETRATION THROUGH BUILDING ENVELOPE.

JACKET:

1. FACTORY APPLIED ALL SERVICE JACKETS (ASJ) SHALL BE FOIL SCRIM KRAFT

(FSK). SEAL AT ALL EXPOSED SEAMS/ EDGES/ CORNERS WITH FSK ADHESIVE TAPE,

REFER TO "DUCT INSULATION" SPECIFICATIONS FOR MORE INFORMATION

ROOFTOP TOTAL ENERGY RECOVERY VENTILATOR SCHEDULE

MARK MANUFACTURER

MODEL

NUMBER

TYPE DRIVE

SUPPLY

CFM

SUPPLY

ESP (IN

WG)

SUPPLY

FAN HP

EXHAUST

CFM

EXHAUST

FAN HP

EXHAUST

ESP (IN

WG)

WINTER SUMMER

HEATING

SECTION

COOLING

SECTION

UNIT PHYSICAL DATA

ADDITIONAL

DETAILS

OUTDOOR AIR EXHAUST OUTDOOR AIR EXHAUST

EAT DB / WB (°F) LAT DB / WB (°F) EAT DB / WB (°F) EAT DB / WB (°F) LAT DB / WB (°F) EAT DB / WB (°F) LENGTH (IN) WIDTH (IN) HEIGHT (IN)

WEIGHT

(LBS)

ERV-1 RENEWAIRE HE1XRT

STATIC

PLATE

DIRECT 840 1.5 0.5 725 0.5 1.5 -20 / -21 37.6 / 31.4 70 / 54.4 92.8 / 62.1 81.4 / 59.8 75 / 62.6 NONE NONE 81" 22.6" 39.5" 330 SEE BELOW

ACCESSORIES:

1. UNIT MOUNTED (INTEGRAL) T-STAT

2. INTEGRAL DISCONNECTING MEANS AND OVERLOADS

3. INTEGRAL FAN

ELECTRICAL DATA:

SEE MEP COORDINATION SCHEDULE

FOR STARTER/DISCONNECT AND ALL

OTHER ELEC. DATA.

ELECTRIC UNIT HEATER SCHEDULE

MARK AREA SERVED MANUF. MODEL NUMBER BTU/HR

DIMENSION

MOUNTING ADDITIONAL DETAILS

L (IN) W (IN) D (IN)

ECH-1 ENTRY BERKO FFCH-548 13,700 23.75 23.75 7 CEILING SEE BELOW

EWH-1 STAIR B QMARK MCSSARWH4808 13,648 19.25 15.85 6.25 WALL SEE BELOW

GRILLE, REGISTER AND DIFFUSER SCHEDULE

MARK MODULE SIZE NECK SIZE FUNCTION TYPE MAX CFM

PERFORMANCE DATA AT MAX CFM SELECTION

MATERIAL MOUNTING

ADDITIONAL

DETAILS

NC AT MAX

PRESSURE DROP AT

MAX CFM (IN. W.C.)

THROW (FT) VELOCITY (FPM) MANF.

MODEL

NUMBER

THROW

PATTERN

S-1 24" x 24" 10" x 10" SUPPLY

PERFORATED

DIFFUSER

230 13 0.01 11 331 KRUEGER 6200 HORIZ. 4 WAY STEEL CEILING SEE BELOW

S-2 24" x 24" 6" x 6" SUPPLY

PERFORATED

DIFFUSER

80 10 0.01 6 320 KRUEGER 6200 HORIZ. 4 WAY STEEL CEILING SEE BELOW

S-3 12" x 12" 6" x 6" SUPPLY

PERFORATED

DIFFUSER

60 10 0.01 5 240 KRUEGER 6200 HORIZ. 4 WAY STEEL CEILING SEE BELOW

E-1 24" x 24" 8" x 8" EXHAUST

PERFORATED

DIFFUSER

100 10 0.02 --- 225 KRUEGER 6490 RETURN STEEL CEILING SEE BELOW

E-2 12" x 12" 8" x 8" EXHAUST

PERFORATED

DIFFUSER

150 10 0.05 --- 338 KRUEGER 6490 RETURN STEEL CEILING SEE BELOW

R-1 24" x 24" 18" x 18" RETURN

PERFORATED

DIFFUSER

580 10 0.02 --- 258 KRUEGER 6490 RETURN STEEL CEILING SEE BELOW

REMARKS:

1. PROVIDE MANUAL VOLUME DAMPER ON DUCKWORK IN CEILING SPACE.

2. INTEGRAL OPPOSED BLADE DAMPER FOR BALANCING AIRFLOW.

3. SEE PLANS FOR LENGTHS.

4. PROVIDE A MANUAL VOLUME DAMPER AT EACH BRANCH TAKE-OFF.

REMARKS FOR ALL:

1. SEE ARCHITECTURAL REFLECTED CEILING PLAN FOR CEILING TYPES.

2. SUBMITTAL DATA SHALL INCLUDE N.C., THROW, VELOCITY, PRESSURE DROP AS

WELL AS ALL PHYSICAL AND INSTALLATION DATA.

NOTES:

1. PROVIDE WITH DOOR INTERLOCKING DISCONNECT SWITCH, AIR PROVING MEAN & ALL CONTROLS.

2. PROVIDE SCR WITH CONTROL BY THERMOSTAT AND DUCT PROBE.

ELECTRIC POST HEATER SCHEDULE

MARK MANUFACTURER MODEL NUMBER AIRFLOW (CFM) POWER (KW) STAGES DUCT SIZE (W"XH") VOLTAGE PHASE ADDITIONAL DETAILS

PH-1 INDEECO XUB 840 9.0 SCR 14"x14" 208 3 SEE BELOW

0 1 2 3 4 5 6 7 8 9 10 inches

DRAWING NO.

PKG

NO.

SHEET

OF

PROJECT NO.:

REVISIONS:

DESIGNED

TECH. REVIEW

CADD

DESIGNED SUB SHEET NO. TITLE OF SHEET

THOMAS R.

COBURN

No. 20022 PE

I S

S

E F

O R

P

LANO EN

G

IN

E E R

ON

T

M

ANA

LICENSED

3/ 8/ :1 8:

P M

M0.2

3.10.17C O N S T R U C T

IO

N D O C U M E N T S

MECH AIRSIDE SCHEDULES

16079

ALWRI RENOVATION

FOREST SERVICE / ROCKY MOUNTAIN RESEARCH STATION

EJW

REB

TRC

smoses Text Box smoses

NOTES:

1. PROVIDE ASME RATED TANK WITH 125 PSI WORKING PRESSURE AT 500F. PROVIDE WITH 3/4" VENT AND 1" DRAIN CONNECTIONS AND 3/4" TAPPING FOR TEMPERATURE SENSOR AT BOTTOM 1/3 OF TANK.

2. ALL CONNECTIONS SHALL BE FNPT

3. FIELD INSULATE TANK WITH 2" MINERAL FIBER INSULATION AND PVC JACKET.

PUMP SCHEDULE

MARK MANUFACTURER MODEL NUMBER TYPE DESCRIPTION WORKING FLUID FLOW RATE (GPM) HEAD (FT) MOTOR SPEED (RPM) EFFICIENCY

ADDITIONAL

DETAILS

P-1 ARMSTRONG 4380-1.5x1.5x8 MAIN DISTRIBUTION PUMP VERTICAL INLINE 40% PG 46 50 1760 50.5% SEE BELOW

P-2 ARMSTRONG 4380-1.5x1.5x8 MAIN DISTRIBUTION PUMP VERTICAL INLINE 40% PG 46 50 1760 50.5% SEE BELOW

ELECTRICAL DATA:

SEE MEP COORDINATION SCHEDULE FOR

STARTER/DISCONNECT AND ALL OTHER ELEC. DATA.

REMARKS:

1. PROVIDE WALL MOUNTED STAND FOR EA. PUMP

2. PROVIDE VIBRATION ISOLATION PADS UNDER PUMP.

3. PROVIDE TEKMAR CONTROLLERS REQUIRED TO DEAD-LAY AND ALTERNATE LEAD PUMP BASED ON RUNTIME HOURS.

PIPE MATERIAL SCHEDULE

SYSTEM MATERIAL SIZES INSULATION THICKNESS** ADD'L DETAILS

COMBUSTION AIR & VENT PIPING SCHEDULE 40 PVC ALL NONE ADD'L DETAILS

REFRIGERANT PIPING

REFER TO SPECIFICATIONS. ALSO REFER TO DAIKIN

INSTALLATION INSTRUCTIONS.

NATURAL GAS PIPING THREADED BLACK IRON ALL NONE PAINT ORANGE

CONDENSATE DRAIN PIPING SCHEDULE 40 PVC ALL NONE SEE BELOW

HEAT PUMP WATER SUPPLY & RETURN 'L' COPPER / STEEL ALL NONE SEE BELOW

HOT WATER SUPPLY & RETURN 'L' COPPER / STEEL

<=11/2" 11/2" WRAP WITH ASJ

SEE BELOW

>11/2" 2" WRAP WITH ASJ

** BASED ON INSULATION HAVING A CONDUCTIVITY (K) NOT

EXCEEDING 0.27 BTU PER INCH/H*FT^2*DEG F

1. PROVIDE SEISMIC BRACING OF PIPING AS REQUIRED BY LOCAL CODES.

2. INSULATION SHALL BE FIBERGLASS WITH ALL SERVICE JACKET

3. ALL SERVICE INSULATION JACKET IS TO BE SEALED AT ALL SEAMS, EDGES, ETC.

4. PROVIDE PVC COATED JACKET OVER INSULATION FOR MECHANICAL ROOM PIPING.

5. ANY CONNECTIONS THAT ARE DISSIMILAR METALS SHALL REQUIRE BRASS UNIONS OR

FLANGE SEPARATION.

PIPE MATERIAL REMARKS:

GAS-FIRED CONDENSING BOILER SCHEDULE

MARK MANUFACTURER MODEL INPUT (MBH) OUTPUT (MBH) AFUE

COMBUSTION

AIR

FLUE TURNDOWN

GAS

CONNECTION

WORKING FLUID EWT / LWT (°F) WEIGHT (LBS)

ADDITIONAL

DETAILS

B-1 BOSCH ZBR21-3 79.2 74.7 95% 3" 3" 3:1 3/4" 40% PROPYLENE GLYCOL 65° / 105°F 103.6 SEE BELOW

B-1 BOSCH ZBR21-3 79.2 74.7 95% 3" 3" 3:1 3/4" 40% PROPYLENE GLYCOL 65° / 105°F 103.6 SEE BELOW

ACCESSORIES:

1. ZERO CLEARANCE

INSTALLATION

OPTION

REMARKS:

1. ALL UNITS TO BE SEALED COMBUSTION. CONTRACTOR TO

PROVIDE PIPING FOR COMBUSTION AIR AND VENT TO

EXTERIOR. SEE PLANS FOR ROUTING.

2. FURNISH GAS REGULATOR AS REQUIRED - VENT TO

EXTERIOR.

3. INSTALL VENT AIR AND COMBUSTION AIR PER

MANUFACTURERS SPECIFICATIONS.

4. UNITS TO BE INSTALLED PER ZERO SIDE CLEARANCE

INSTALLATION.

5. PROVIDE MOUNTING KIT BY UNIT MANUFACTURER.

6. PROVIDE CONDENSATE PIPING TO NEAREST FLOOR DRAIN.

SEE PLUMBING PLAN.

CONTROLS:

ALL UNITS MUST CONFORM TO ASME STANDARD CSD-1 AND THE FOLLOWING:

• TWO HIGH TEMPERATURE LIMIT CONTROLS - ONE WITH MANUAL RESET

• BOILER >400 MBH - HIGH AND LOW GAS PRESSURE - MANUAL RESET

• LOW WATER FUEL CUTOFF SWITCH - MANUAL RESET OR IF LOW WATER SWITCH IS

NOT POSSIBLE (FORCED CIRCULATION) PROVIDE FLOW SWITCH - MANUAL RESET

• COMBUSTION AIR PROOF SWITCH

• EACH BOILER ACCEPTS NATURAL GAS IN PRESSURE RANGE OF 5-10.5 IN W.C.

ELECTRICAL DATA:

SEE MEP COORDINATION SCHEDULE FOR

STARTER/DISCONNECT AND ALL OTHER

ELEC. DATA.

DRY COOLER SCHEDULE

MARK MANUFACTURER MODEL NUMBER

HEAT OF

REJECTION (MBH)

AIR SIDE DATA FLUID SIDE DATA 'WET' WEIGHT

(LBS)

ADDITIONAL DETAILS

CFM # OF FANS FAN HP (EA.) E.A.T. GPM E.W.T. L.W.T. PRESSURE DROP FLUID

DC-1 ECO / LUVATA LFV8012-4H6-2B 220,626 19,353 2 1.75 95°F 46 115 105 11.1 FT W.C. 40% PROPYLENE GLYCOL 1,297 SEE BELOW

1. PROVIDE STAND BY UNIT MANUFACTURER, CONCRETE PAD ON GRADE, AND ANCHOR UNIT PER MANUFACTURER'S RECOMMENDATIONS.

2. COORDINATE W/ E.C. TO PROVIDE HEAT TRACE ON ALL EXPOSED HPWS&R PIPING. ACTIVATE AT 0°F (ADJ.) OR BELOW AMBIENT TEMPERATURE.

3. PROVIDE FACTORY CONTROLS.

ACCESSORIES: ELECTRICAL DATA:

SEE MEP COORDINATION SCHEDULE FOR

STARTER/DISCONNECT AND ALL OTHER ELEC. DATA.

AUTOMATIC GLYCOL FEEDER SCHEDULE

MARK MANUFACTURER MODEL NUMBER TANK VOLUME (GAL) PUMP PERFORMANCE OPERATING WEIGHT ADDITIONAL DETAILS

GLF-1 JOHN WOOD COMPANY JWGP-53-030 30 3.2 GPM @ 54.1 PSIG 390 SEE BELOW

REMARKS:

1. PROVIDE LOCKABLE NEMA 4X CONTROL PANEL AND ELECTRICAL DISCONNECT.

2. PROVIDE DRY CONTACTS TO ALARM CENTRAL CONTROL PANEL IN THE EVEN OF LOW LEVEL.

3. PROVIDE PUMP H/O/A SWITCH, AUTOMATIC PUMP PRESSURE SWITCH, & LOW LEVEL FLOAT & PUMP SHUT-OFF SWITCH.

4. PROVIDE PRESSURE RELIEF VALVE, CHECK VALVE, & STRAINER BY UNIT MANUFACTURER.

ELECTRICAL DATA:

SEE MEP COORDINATION SCHEDULE FOR

STARTER/DISCONNECT AND ALL OTHER

ELEC. DATA.

EXPANSION TANK SCHEDULE

MARK MANUFACTURER MODEL NUMBER TOTAL VOLUME (GAL)

ACCEPTANCE VOLUME

(GAL)

SYSTEM SYSTEM PRESSURE (PSI)

SYSTEM VOLUME

(GAL)

ADDITIONAL DETAILS

ET-1 ARMSTRONG A200-L 53 53 HEATING WATER 27 700 SEE BELOW

BUFFER TANK SCHEDULE

MARK MFGR MODEL

VOLUME

(GAL)

HEIGHT (IN) DIA (IN)

HEAT PUMP WATER

CONNECTION SIZE (NPS)

HEAT PUMP WATER

CONNECTION QTY

REMARKS

BT-1 JOHN WOOD JSTR-22-033 120 64.75 24 2-1/2" 4 SEE NOTES

0 1 2 3 4 5 6 7 8 9 10 inches

DRAWING NO.

PKG

NO.

SHEET

OF

PROJECT NO.:

REVISIONS:

DESIGNED

TECH. REVIEW

CADD

DESIGNED SUB SHEET NO. TITLE OF SHEET

THOMAS R.

COBURN

No. 20022 PE

I S

S

E F

O R

P

LANO EN

G

IN

E E R

ON

T

M

ANA

LICENSED

3/ 8/ :1 8:

P M

M0.3

3.10.17C O N S T R U C T

IO

N D O C U M E N T S

MECH WATERSIDE SCHEDULES

16079

ALWRI RENOVATION

FOREST SERVICE / ROCKY MOUNTAIN RESEARCH STATION

EJW

REB

TRC

smoses Text Box smoses

VRF FAN COIL SCHEDULE

VRF FAN COIL SCHEDULE

MARK MFGR MODEL NUMBER UNIT TYPE

HEAT

RECOVERY

BOX

SUPPLY FAN

CORRECTED COOLING

CAPACITY

CORRECTED

HEATING

CAPACITY

(MBH)

ELECTRICAL DATA

REMARKS

CFM ESP (in W.C.)

TOTAL

(MBH)

SENSIBLE

(MBH)

VOLTAGE PHASE

FC 001A LG ARNU123BGA4 DUCTED HIGH STATIC HRU-2 586 0.23 7.7 6.6 11.3 208 1 SEE NOTES

FC 001B LG ARNU053TRC4 4-WAY CASSETTE HRU-2 265 N/A 3.5 3.0 5.1 208 1 SEE NOTES

FC 001C LG ARNU123TRC4 4-WAY CASSETTE HRU-2 307 N/A 7.9 6.8 11.9 208 1 SEE NOTES

FC 001D LG ARNU123TRC4 4-WAY CASSETTE HRU-1 307 N/A 7.7 6.6 11.3 208 1 SEE NOTES

FC 005A LG ARNU073TRC4 4-WAY CASSETTE HRU-1 265 N/A 4.8 4.1 7.2 208 1 SEE NOTES

FC 005B LG ARNU073TRC4 4-WAY CASSETTE HRU-1 265 N/A 4.8 4.1 7.0 208 1 SEE NOTES

FC 102A LG ARNU183TTC4 1-WAY CASSETTE HRU-6 470 N/A 12.2 10.5 19.1 208 1 SEE NOTES

FC 102B LG ARNU073TUC4 1-WAY CASSETTE HRU-4 290 N/A 4.8 4.2 7.6 208 1 SEE NOTES

FC 102C LG ARNU073SBL4 WALL MOUNTED FAN COIL HRU-5 307 N/A 4.9 4.2 7.8 208 1 SEE NOTES

FC 102D LG ARNU073TUC4 1-WAY CASSETTE HRU-5 290 N/A 4.9 4.2 7.9 208 1 SEE NOTES

FC 103 LG ARNU123TUC4 1-WAY CASSETTE HRU-5 353 N/A 8.0 6.9 12.9 208 1 SEE NOTES

FC 104 LG ARNU073TUC4 1-WAY CASSETTE HRU-6 290 N/A 4.8 4.1 7.4 208 1 SEE NOTES

FC 105 LG ARNU093SBL4 WALL MOUNTED FAN COIL HRU-6 247 N/A 4.8 4.1 7.5 208 1 SEE NOTES

FC 106 LG ARNU073SBL4 WALL MOUNTED FAN COIL HRU-4 247 N/A 4.8 4.1 7.5 208 1 SEE NOTES

FC 107 LG ARNU073SBL4 WALL MOUNTED FAN COIL HRU-4 247 N/A 4.8 4.1 7.5 208 1 SEE NOTES

FC 108 LG ARNU073SBL4 WALL MOUNTED FAN COIL HRU-4 247 N/A 4.8 4.1 7.5 208 1 SEE NOTES

FC 109 LG ARNU073SBL4 WALL MOUNTED FAN COIL HRU-3 247 N/A 4.9 4.2 7.8 208 1 SEE NOTES

FC 110 LG ARNU073SBL4 WALL MOUNTED FAN COIL HRU-3 247 N/A 4.9 4.2 7.8 208 1 SEE NOTES

FC 112 LG ARNU153SBL4 WALL MOUNTED FAN COIL HRU-5 0 N/A 7.6 7.5 11.1 208 1 SEE NOTES

NOTES: COOLING CAPACITIES ARE BASED ON 75F DB / 63F WB ENTERING CONDITIONS. HEATING CAPACITIES ARE BASED ON 70F DB ENTERING CONDITION. EACH FANCOIL SHALL BE CONTROLLED BY A SIMPLE WIRED ROOM CONTROLLER.

MARK MFGR MODEL NUMBER UNIT TYPE

ELECTRICAL DATA

REMARKS

VOLTAGE PHASE

HRU-1 LG PRHR032A THREE PORT 208 1 SEE NOTES

HRU-2 LG PRHR032A THREE PORT 208 1 SEE NOTES

HRU-3 LG PRHR022A TWO PORT 208 1 SEE NOTES

HRU-4 LG PRHR042A FOUR PORT 208 1 SEE NOTES

HRU-5 LG PRHR042A FOUR PORT 208 1 SEE NOTES

HRU-6 LG PRHR032A THREE PORT 208 1 SEE NOTES

NOTES: INSTALL HEAT RECOVERY BOXES TO ALLOW ACCESS FOR MAINTENANCE AND REPAIR.

NOTES:

1. REFER TO VRV REFRIGERANT PIPING SCHEMATIC FOR

REFRIGERANT LINE SIZES AND ROUTING DETAILS.

2. FOLLOW MANUFACTURER'S INSTALLATION MANUAL

PRECISELY TO ENSURE PROPER OPERATION.

3. FINAL UNIT SELECTIONS NEED TO BE VERIFIED BY

MANUFACTURER PRIOR TO ORDERING EQUIPMENT.

WATER SOURCE HEAT RECOVERY UNIT - VARIABLE REFRIGERANT VOLUME SCHEDULE

MARK MFGR. MODEL # UNITS TYPE

CONDENSER

WATER

FLUID

TYPE

WATER

FLOW

(GPM)

WATER

PRESSURE

DROP

(FT W.C.)

COOLING DATA HEATING DATA

VOLTAGE &

PHASE

MCA REMARKS

CORRECTED

TOTAL

CAPACITY

(BTU/HR)

EWT/LWT

(F)

TOTAL

CAPACITY

(BTU/HR)

EWT/LWT

(F)

HP-1

LG ARWB432BAS4

ARWB072BAS4

WATER SOURCE

VRF HEAT PUMP

40% PROPYLENE

GLYCOL

20.3 3.7

168,000 105 / 111.7 189,000 68 / 56.9

208 V / 3 PH 35.0 SEE BELOW

HP-2 ARWB096BAS4 25.4 5.3 208 V / 3 PH 35.5 SEE BELOW

ELECTRICAL DATA:

SEE MEP COORDINATION SCHEDULE

FOR STARTER/DISCONNECT AND ALL

OTHER ELEC. DATA.

CONTROLS:

1. PROVIDE I-TOUCH CONTROLLER.

2. ROUTE CABLING INFRASTRUCTURE FROM ITOUCH CONTROLLER TO SWITCH

ROOM FOR FUTURE NETWORK CONNECTION.

ACCESSORIES:

1. CONTRACTOR IS RESPONSIBLE FOR PROVIDING ALL NECESSARY ACCESSORIES FOR A

FULLY FUNCTIONING SYSTEM.

2. PROVIDE SHUT-OFF AND SCHRADER VALVE BETWEEN SHUT-OFF AND UNIT FOR ALL

PIPES CONNECTING TO UNIT.

3. PROVIDE ALL REFNET FITTINGS AS REQUIRED IN PIPING NETWORK.

4. FILTER/DRYER.

5. HIGH/LOW PRESSURE SWITCH.

6. CRANKCASE HEATER.

7. EVAP. FREEZE T-STAT.

0 1 2 3 4 5 6 7 8 9 10 inches

DRAWING NO.

PKG

NO.

SHEET

OF

PROJECT NO.:

REVISIONS:

DESIGNED

TECH. REVIEW

CADD

DESIGNED SUB SHEET NO. TITLE OF SHEET

THOMAS R.

COBURN

No. 20022 PE

I S

S

E F

O R

P

LANO EN

G

IN

E E R

ON

T

M

ANA

LICENSED

3/ 8/ :1 8:

P M

M0.4

3.10.17C O N S T R U C T

IO

N D O C U M E N T S

MECH VRF SCHEDULES

16079

ALWRI RENOVATION

FOREST SERVICE / ROCKY MOUNTAIN RESEARCH STATION

EJW

REB

TRC

smoses Text Box smoses

M.E.P. COORDINATION SCHEDULE

MARK DESCRIPTION

ELECTRICAL DATA CONTROL

NOTES

STARTER/DISCONNECT

LOAD VOLT-PH TYPE DIV TYPE DIV

B-1 BOILER 205 W 120V - 1PH INT 23/23 - MSS 26/26

B-2 BOILER 205 W 120V - 1PH INT 23/23 - MSS 26/26

FC 001A HIGH STATIC DUCTED COIL 2.65 FLA 208V - 1PH T 23/23 - MSS (2P) 26/26

FC 001B CASSETTE FAN COIL 0.2 FLA 208V - 1PH T 23/23 - MSS (2P) 26/26

FC 001C CASSETTE FAN COIL 0.2 FLA 208V - 1PH T 23/23 - MSS (2P) 26/26

FC 001D CASSETTE FAN COIL 0.2 FLA 208V - 1PH T 23/23 - MSS (2P) 26/26

FC 005A CASSETTE FAN COIL 0.2 FLA 208V - 1PH T 23/23 - MSS (2P) 26/26

FC 005B CASSETTE FAN COIL 0.2 FLA 208V - 1PH T 23/23 - MSS (2P) 26/26

GLF-1 GLYCOL FEEDER 1/3 HP 115V -1PH INT 23/23 4 NA -

HP-1 HEAT PUMP 28.0 FLA 208V - 3PH INT 23/23 - FD 26/26

HP-2 HEAT PUMP 28.4 FLA 208V - 3PH INT 23/23 - FD 26/26

HRU 1 3 PORT HEAT RECOV.UNIT 0.12 FLA 208V - 1PH INT 23/23 - MSS (2P) 26/26

HRU 2 3 PORT HEAT RECOV.UNIT 0.12 FLA 208V - 1PH INT 23/23 - MSS (2P) 26/26

DWH-1 HOT WATER HEATER 1500 W 120V - 1PH INT 22/22 4 NA 26/26

PP-1 HOT WATER RECIRCULATION PUMP FRAC. HP 120V - 1PH INT 22/22 4 NA 26/26

P-1 MAIN DIST. PUMP 2 HP 208V - 3PH UC 23/23 - MSS (3P) 26/26

P-2 MAIN DIST. PUMP 2 HP 208V - 3PH UC 23/23 - MSS (3P) 26/26

SP-1 ALT. 4 - SUMP PUMP 8 FLA 208V - 1PH INT 22/22 - MSS (2P) 26/26

ECH-1 ELECTRIC CEILING HEATER 19.2 FLA 208V - 1 PH INT 23/23 1 INT 23/26

EWH-1 ELECTRIC WALL HEATER 19.2 FLA 208V - 1 PH INT 23/23 1 INT 23/26

FC 102A 1-WAY CASSETTE 0.3 FLA 208V - 1 PH T 23/23 - MSS(2P) 26/26

FC 102B 1-WAY CASSETTE 0.18 FLA 208V - 1 PH T 23/23 - MSS(2P) 26/26

FC 102C WALL MOUNT FAN COIL 0.16 FLA 208V - 1 PH T 23/23 - MSS(2P) 26/26

FC 102D 1-WAY CASSETTE 0.18 FLA 208V - 1 PH T 23/23 - MSS(2P) 26/26

FC 103 1-WAY CASSETTE 0.18 FLA 208V - 1 PH T 23/23 - MSS(2P) 26/26

FC104 1-WAY CASSETTE 0.18 FLA 208V - 1 PH T 23/23 - MSS(2P) 26/26

FC 105 WALL MOUNT FAN COIL 0.16 FLA 208V - 1 PH T 23/23 - MSS(2P) 26/26

FC 106 WALL MOUNT FAN COIL 0.16 FLA 208V - 1 PH T 23/23 - MSS(2P) 26/26

FC 107 WALL MOUNT FAN COIL 0.16 FLA 208V - 1 PH T 23/23 - MSS(2P) 26/26

FC 108 WALL MOUNT FAN COIL 0.16 FLA 208V - 1 PH T 23/23 - MSS(2P) 26/26

FC 109 WALL MOUNT FAN COIL 0.16 FLA 208V - 1 PH T 23/23 - MSS(2P) 26/26

FC 110 WALL MOUNT FAN COIL 0.16 FLA 208V - 1 PH T 23/23 - MSS(2P) 26/26

FC 112 WALL MOUNT FAN COIL 0.16 FLA 208V - 1 PH T 23/23 - MSS(2P) 26/26

HRU 3 2 PORT HEAT RECOV.UNIT 0.08 FLA 208V - 1 PH INT 23/23 - MSS(2P) 26/26

HRU 4 4 PORT HEAT RECOV.UNIT 0.16 FLA 208V - 1 PH INT 23/23 - MSS(2P) 26/26

HRU 5 4 PORT HEAT RECOV.UNIT 0.16 FLA 208V - 1 PH INT 23/23 - MSS(2P) 26/26

HRU 6 3 PORT HEAT RECOV.UNIT 0.12 FLA 208V - 1PH INT 23/23 - MSS(2P) 26/26

ERV-1 ENERGY RECOVERY VENT. 5.2 MCA 208V - 3PH INT 23/23 - FD 26/26

DC-1 DRY COOLER 11.4 FLA 208V - 3PH INT 23/23 - FD 26/26

PH-1 POST HEATER 9 KW 208V - 3PH T 23/23 - FD 26/26

CONTROL TYPE DIVISION OF RESPONSIBILITIES:

BAS

C

CO

INT

L

PS

T

UC

NA

BUILDING AUTO CONTROL

CARBON MONOXIDE DETECTORS

CONTINUOUS OPERATION

INTEGRAL CONTROLS

LIGHT SWITCH

PRESSURE SWITCH

THEMOSTAT

UNIT CONTROLLER

NOT APPLICABLE

22/22 22/26 23/23 23/26 26/26

FURNISHED AND INSTALLED BY DIV. 22, WIRED BY DIV.

FURNISHED AND INSTALLED BY DIV. 22, WIRED BY DIV.

FURNISHED AND INSTALLED BY DIV. 23, WIRED BY DIV.

FURNISHED AND INSTALLED BY DIV. 23, WIRED BY DIV.

FURNISHED AND INSTALLED BY DIV. 26, WIRED BY DIV.

STARTER/DISCONNECT TYPE NOTES:

FD

CSFD

RVSS

VFD

MSS

MOCP

FW

NA

FUSED DISCONNECT

COMBINATION STARTER/DISCONNECT - HOA

REDUCED VOLTAGE SOLID-STATE

VARIABLE FREQUENCY DRIVE - HOA

MANUAL STARTER SWITCH

MOTOR OVER-CURRENT PROTECTION

FACTORY-WIRED SINGLE PT. CONNECTION

NOT APPLICABLE

1.

2.

3.

4.

5.

6.

7.

INTEGRAL DISCONNECTS AND OVERLOADS

INTEGRAL OVERLOADS

INTEGRAL OVERLOADS, RECEPTACLE

RECEPTACLE

SINGLE POINT CONNECTION

PROVIDE RECEPTACLE AND DATA CONNECTION FOR

PANEL

MOUNT ON UNI-STRUT IN FRONT OF UNIT

GENERAL NOTES:

1. ALL DUCT SMOKE DETECTORS FURNISHED BY DIV. 26, INSTALLED BY DIV. 23 AND WIRED BY DIV. 26. DIV 26 SHALL WIRE

ALL FANS TO SHUT DOWN WHEN ALARM IS INITIATED BY ANY DUCT SMOKE DETECTOR.

0 1 2 3 4 5 6 7 8 9 10 inches

DRAWING NO.

PKG

NO.

SHEET

OF

PROJECT NO.:

REVISIONS:

DESIGNED

TECH. REVIEW

CADD

DESIGNED SUB SHEET NO. TITLE OF SHEET

THOMAS R.

COBURN

No. 20022 PE

I S

S

E F

O R

P

LANO EN

G

IN

E E R

ON

T

M

ANA

LICENSED

3/ 8/ :1 8:

P M

M0.5

3.10.17C O N S T R U C T

IO

N D O C U M E N T S

MEP COORDINATION SCHEDULE

16079

ALWRI RENOVATION

FOREST SERVICE / ROCKY MOUNTAIN RESEARCH STATION

EJW

REB

TRC

smoses Text Box smoses

UP

A

B

(E)

OPEN

OFFICE

AREA

WOMEN'S

RESTROOM

MEN'S

RESTROOM

(E)

MECH.

RM.

2 2

(E)

CONFERENCE

(E)

OPEN

OFFICE

AREA

KEY NOTES:#

A. IT IS THE INTENT OF THIS PROJECT TO DEMOLISH THE ENTIRE EXISTING

MECHANICAL SYSTEMS. COORDINATE ALL UTILITY OUTAGES WITH THE

OWNER PLANNING DESIGN AND CONSTRUCTION THROUGHOUT THE

DURATION OF CONSTRUCTION.

B. ALL EXISTING MECHANICAL EQUIPMENT, DUCTWORK, PIPING SHOWN AS DARK

AND DASHED SHALL BE DEMOLISHED. EXISTING MECHANICAL EQUIPMENT

SHOWN LIGHT WITH SOLID LINES IS TO REMAIN UNCHANGED.

C. PRESENT ALL DEMOLISHED EQUIPMENT TO THE OWNER FOR SALVAGE.

REMOVE ANY UNWANTED EQUIPMENT FROM SITE.

D. COORDINATE WITH THE GENERAL CONTRACTOR TO PATCH AND REPAIR THE

FLOORS, ROOF AND WALLS ASSOCIATED WITH THE MECHANICAL DEMOLITION.

MECHANICAL DEMO NOTES

0 1 2 3 4 5 6 7 8 9 10 inches

DRAWING NO.

PKG

NO.

SHEET

OF

PROJECT NO.:

REVISIONS:

DESIGNED

TECH. REVIEW

CADD

DESIGNED SUB SHEET NO. TITLE OF SHEET

THOMAS R.

COBURN

No. 20022 PE

I S

S

E F

O R

P

LANO EN

G

IN

E E R

ON

T

M

ANA

LICENSED

3/ 8/ :1 8:

P M

MD2.0

3.10.17C O N S T R U C T

IO

N D O C U M E N T S

BASEMENT MECH. DEMO PLAN

16079

ALWRI RENOVATION

FOREST SERVICE / ROCKY MOUNTAIN RESEARCH STATION

EJW

REB

TRC

: 1/4" = 1'-0"MD2.0MD2.0

9 BASEMENT MECHANICAL DEMO PLAN

1. U.N.O., (D) ALL (E) HVAC DUCTWORK, PIPING, EQUIPMENT, AND CONTROLS.

2. U.N.O., (D) ALL (E) BASEBOARD HEATERS, WIRING, & CONTROLS, TYP.

NORTH

smoses Text Box smoses

DN

A

B

STAIR

A

STAIR

B

2 2

KEY NOTES:#

A. IT IS THE INTENT OF THIS PROJECT TO DEMOLISH THE ENTIRE EXISTING

MECHANICAL SYSTEMS. COORDINATE ALL UTILITY OUTAGES WITH THE

OWNER PLANNING DESIGN AND CONSTRUCTION THROUGHOUT THE

DURATION OF CONSTRUCTION.

B. ALL EXISTING MECHANICAL EQUIPMENT, DUCTWORK, PIPING SHOWN AS DARK

AND DASHED SHALL BE DEMOLISHED. EXISTING MECHANICAL EQUIPMENT

SHOWN LIGHT WITH SOLID LINES IS TO REMAIN UNCHANGED.

C. PRESENT ALL DEMOLISHED EQUIPMENT TO THE OWNER FOR SALVAGE.

REMOVE ANY UNWANTED EQUIPMENT FROM SITE.

D. COORDINATE WITH THE GENERAL CONTRACTOR TO PATCH AND REPAIR THE

FLOORS, ROOF AND WALLS ASSOCIATED WITH THE MECHANICAL DEMOLITION.

MECHANICAL DEMO NOTES

0 1 2 3 4 5 6 7 8 9 10 inches

DRAWING NO.

PKG

NO.

SHEET

OF

PROJECT NO.:

REVISIONS:

DESIGNED

TECH. REVIEW

CADD

DESIGNED SUB SHEET NO. TITLE OF SHEET

THOMAS R.

COBURN

No. 20022 PE

I S

S

E F

O R

P

LANO EN

G

IN

E E R

ON

T

M

ANA

LICENSED

3/ 8/ :1 8:

P M

MD2.1

3.10.17C O N S T R U C T

IO

N D O C U M E N T S

1ST FLOOR MECH. DEMO PLAN

16079

ALWRI RENOVATION

FOREST SERVICE / ROCKY MOUNTAIN RESEARCH STATION

EJW

REB

TRC

: 1/4" = 1'-0"MD2.1MD2.1

9 FIRST FLOOR MECHANICAL DEMOLITION PLAN

1. U.N.O., (D) ALL (E) HVAC DUCTWORK, PIPING, EQUIPMENT, AND CONTROLS.

2. U.N.O., (D) ALL (E) BASEBOARD HEATERS, WIRING, & CONTROLS, TYP.

NORTH

smoses Text Box smoses

A

B

KEY NOTES:#

A. IT IS THE INTENT OF THIS PROJECT TO DEMOLISH THE ENTIRE EXISTING

MECHANICAL SYSTEMS. COORDINATE ALL UTILITY OUTAGES WITH THE

OWNER PLANNING DESIGN AND CONSTRUCTION THROUGHOUT THE

DURATION OF CONSTRUCTION.

B. ALL EXISTING MECHANICAL EQUIPMENT, DUCTWORK, PIPING SHOWN AS DARK

AND DASHED SHALL BE DEMOLISHED. EXISTING MECHANICAL EQUIPMENT

SHOWN LIGHT WITH SOLID LINES IS TO REMAIN UNCHANGED.

C. PRESENT ALL DEMOLISHED EQUIPMENT TO THE OWNER FOR SALVAGE.

REMOVE ANY UNWANTED EQUIPMENT FROM SITE.

D. COORDINATE WITH THE GENERAL CONTRACTOR TO PATCH AND REPAIR THE

FLOORS, ROOF AND WALLS ASSOCIATED WITH THE MECHANICAL DEMOLITION.

MECHANICAL DEMO NOTES

0 1 2 3 4 5 6 7 8 9 10 inches

DRAWING NO.

PKG

NO.

SHEET

OF

PROJECT NO.:

REVISIONS:

DESIGNED

TECH. REVIEW

CADD

DESIGNED SUB SHEET NO. TITLE OF SHEET

THOMAS R.

COBURN

No. 20022 PE

I S

S

E F

O R

P

LANO EN

G

IN

E E R

ON

T

M

ANA

LICENSED

3/ 8/ :1 8:

P M

MD2.2

3.10.17C O N S T R U C T

IO

N D O C U M E N T S

ROOF MECHANICAL DEMO PLAN

16079

ALWRI RENOVATION

FOREST SERVICE / ROCKY MOUNTAIN RESEARCH STATION

EJW

REB

TRC

: 1/4" = 1'-0"MD2.2MD2.2

9 ROOF MECHANICAL DEMOLITION PLAN

1. (D) (E) PACKAGED ROOFTOP AIR HANDLING UNIT, CURB, AND ALL ASSOCIATED GAS

CONTROLS, WIRING, AND CONDENSATE PIPING. COORDINATE WITH G.C. TO PATCH ROOF.

TYP. 2.

2. (D)(E) ROOF-MOUNTED EXHAUST FAN. COORDINATE WITH G.C. TO PATCH ROOF.

NORTH

smoses Text Box smoses

A

B

(E)

OPEN

OFFICE

AREA

WOMEN'S

RESTROOM

MEN'S

RESTROOM

(E)

MECH.

RM.

HRU-2

(E)

CONFERENCE

6"ø

10"x12"

6"ø

6"ø 6"ø

4"ø

10"x10"

6"ø

6"x6" 6"x6"

FC

001B

FC

001C

FC

001D

FC

005A

FC

005B (E)

OPEN

OFFICE

AREA

(E)

OPEN

OFFICE

AREA

10"ø

E-1

T

FC 001

A,B,C,D

T FC 005A,B

S-1

S-1

E-1

R-1

E-2

E-2

S-3

S-3

6"ø

FC

001A

8"x12"

E-2

33"x7"

41"x8"

18"x8"

6"ø 6"ø

6"ø 8"ø8"ø

8"ø

6"x8"6"x8"

"x

4"ø

4 4

3"ø

3"ø

3"ø

3"ø

"x

8"x8"

"x

B-2

B-1 BT-1

P-1 P-2

HP-1

HP-2

ET-1 GLF-1

HRU-1

DHW-1

KEY NOTES:#

A. IT SHALL BE THE RESPONSIBILITY OF THE MECHANICAL CONTRACTOR TO

FIELD COORDINATE THE ROUTING OF ALL DUCTWORK AND PIPING WITH ALL

OTHER TRADES.

B. BUILDING IN GENERAL HAS LIMITED SPACE AND IS CONGESTED. IT SHALL BE

THE RESPONSIBILITY OF THE MECHANICAL CONTRACTOR TO REVIEW

DRAWINGS FOR ALL DISCIPLINES AND PROVIDE ALL LABOR AND MATERIALS

REQUIRED FOR A COMPLETE INSTALLATION.

C. DO NOT RUN ANY DUCTWORK OR PIPING OVER ELECTRICAL PANELS FROM

PANEL TO STRUCTURE ABOVE AND FROM PANEL ACCESS SPACE TO 80"

ABOVE FINISHED FLOOR.

D. COORDINATE THE INSTALL OF GRILLES, REGISTERS AND DIFFUSERS WITH

THE ARCHITECTURAL REFLECTED CEILING PLANS AND THE ELECTRICAL

LIGHTING PLANS.

E. VERIFY THE LOCATION OF ALL THERMOSTATS AND SENSORS WITH THE

ENGINEER AND ARCHITECT PRIOR TO INSTALLATION. INSTALL THERMOSTATS

48" ABOVE FINISHED FLOOR PER ADA REQUIREMENTS.

F. PROVIDE AND INSTALL SEISMIC BRACING FOR ALL EQUIPMENT, DUCTWORK

AND PIPING PER THE REQUIREMENTS OF THE 2012 INTERNATIONAL BUILDING

CODE.

G. FLEXIBLE DUCTWORK FROM BRANCH DUCTS TO GRILLES, REGISTERS AND

DIFFUSERS SHALL BE LIMITED TO 5FT MAX.

H. PROVIDE AND INSTALL FIRE, SMOKE AND COMBINATION SMOKE/FIRE

DAMPERS WHERE DUCTWORK PASSES THROUGH FIRE RATED ASSEMBLIES.

I. SEAL ALL DUCT AND PIPE PENETRATIONS THROUGH FIRE RATED ASSEMBLIES

WITH A UL APPROVED FIRE STOP SYSTEM.

J. PROVIDE ACCESS DOORS TO ALLOW SERVICE AND INSPECTION OF

EQUIPMENT, VALVES, DAMPERS AND DEVICES INSTALLED ABOVE NON-

REMOVABLE CEILINGS.

K. PROVIDE FLUSH CUP REMOTE DAMPER ACTUATORS FOR BALANCE DAMPERS

INSTALLED IN IN-ACCESSIBLE LOCATIONS.

L. ALL RECTANGULAR DUCTWORK DOWN-STREAM OF VAV BOXES SHALL HAVE

1" ACOUSTIC LINER.

GENERAL MECHANICAL NOTES

0 1 2 3 4 5 6 7 8 9 10 inches

DRAWING NO.

PKG

NO.

SHEET

OF

PROJECT NO.:

REVISIONS:

DESIGNED

TECH. REVIEW

CADD

DESIGNED SUB SHEET NO. TITLE OF SHEET

THOMAS R.

COBURN

No. 20022 PE

I S

S

E F

O R

P

LANO EN

G

IN

E E R

ON

T

M

ANA

LICENSED

3/ 8/ :1 8:

P M

M2.0

3.10.17C O N S T R U C T

IO

N D O C U M E N T S

BASEMENT MECH. HVAC PLAN

16079

ALWRI RENOVATION

FOREST SERVICE / ROCKY MOUNTAIN RESEARCH STATION

EJW

REB

TRC

: 1/4" = 1'-0"M2.0M2.0

9 BASEMENT MECHANICAL HVAC PLAN

NORTH

1. 12"Ø EA DUCT UP IN CHASE. ROUTE AS FAR NORTH IN CHASE AS COORDINATION WITH

PLUMBING & DUCTWORK ALLOWS.

2. 10"Ø OA DUCT UP IN CHASE. AFTER 8"Ø TAKEOFF, TRANSITION TO 8"Ø MAIN AND DROP

UNDER EXHAUST DUCT IN MECHANICAL ROOM AS REQUIRED. ROUTE AS FAR NORTH IN

CHASE AS COORDINATION WITH PLUMBING & DUCTWORK ALLOWS.

3. 3"Ø VENT AND FLUE DOWN IN CHASE TO B-1 & B-2. TERMINATE THROUGH ROOF IN

CONCETRIC VENT KIT IF MANUFACTURER ALLOWS. ROUTE AS FAR NORTH IN CHASE AS

COORDINATION WITH PLUMBING ALLOWS.

4. ALL FAN COILS AND HRUS TO BE LOCATED IN DROP CEILING.

smoses Text Box smoses

A

B

(E)

OPEN

OFFICE

AREA

WOMEN'S

RESTROOM

MEN'S

RESTROOM

(E)

MECH.

RM.

HRU-2

(E)

CONFERENCE

FC

001B

FC

001C

FC

001D

FC

005A

FC

005B

(E)

OPEN

OFFICE

AREA

(E)

OPEN

OFFICE

AREA

3/4"ø CND

1"ø CND

1"ø CND

3/4"ø CND

3/4"ø CND

1"ø CND

1"ø CND

FC

001A

3/4"ø CND

E L E

C T

R

IC

A L

P A

N E

L S

DOOR

SWING

FIRE RISER

SUMP

PUMP

ACCESS

C H

A S

E

W A

T E

R S

E R

V

IC

E

E L E

C D

IS

C

O N

N E

C T

S

B-1 B-2 BT-1

P-1 P-2

HP-1

HP-2

3/4"ø CND 1"ø CND

REFRIGERANT LIQUID, SUCTION

& MIXED GAS PIPING (TYP).

REFRIGERANT LIQUID &

SUCTION (TYP).

3/4"ø CND

GLF-1ET-1DHW-1

HRU-1

KEY NOTES:#

A. IT SHALL BE THE RESPONSIBILITY OF THE MECHANICAL CONTRACTOR TO

FIELD COORDINATE THE ROUTING OF ALL DUCTWORK AND PIPING WITH ALL

OTHER TRADES.

B. BUILDING IN GENERAL HAS LIMITED SPACE AND IS CONGESTED. IT SHALL BE

THE RESPONSIBILITY OF THE MECHANICAL CONTRACTOR TO REVIEW

DRAWINGS FOR ALL DISCIPLINES AND PROVIDE ALL LABOR AND MATERIALS

REQUIRED FOR A COMPLETE INSTALLATION.

C. DO NOT RUN ANY DUCTWORK OR PIPING OVER ELECTRICAL PANELS FROM

PANEL TO STRUCTURE ABOVE AND FROM PANEL ACCESS SPACE TO 80"

ABOVE FINISHED FLOOR.

D. COORDINATE THE INSTALL OF GRILLES, REGISTERS AND DIFFUSERS WITH

THE ARCHITECTURAL REFLECTED CEILING PLANS AND THE ELECTRICAL

LIGHTING PLANS.

E. VERIFY THE LOCATION OF ALL THERMOSTATS AND SENSORS WITH THE

ENGINEER AND ARCHITECT PRIOR TO INSTALLATION. INSTALL THERMOSTATS

48" ABOVE FINISHED FLOOR PER ADA REQUIREMENTS.

F. PROVIDE AND INSTALL SEISMIC BRACING FOR ALL EQUIPMENT, DUCTWORK

AND PIPING PER THE REQUIREMENTS OF THE 2012 INTERNATIONAL BUILDING

CODE.

G. FLEXIBLE DUCTWORK FROM BRANCH DUCTS TO GRILLES, REGISTERS AND

DIFFUSERS SHALL BE LIMITED TO 5FT MAX.

H. PROVIDE AND INSTALL FIRE, SMOKE AND COMBINATION SMOKE/FIRE

DAMPERS WHERE DUCTWORK PASSES THROUGH FIRE RATED ASSEMBLIES.

I. SEAL ALL DUCT AND PIPE PENETRATIONS THROUGH FIRE RATED ASSEMBLIES

WITH A UL APPROVED FIRE STOP SYSTEM.

J. PROVIDE ACCESS DOORS TO ALLOW SERVICE AND INSPECTION OF

EQUIPMENT, VALVES, DAMPERS AND DEVICES INSTALLED ABOVE NON-

REMOVABLE CEILINGS.

K. PROVIDE FLUSH CUP REMOTE DAMPER ACTUATORS FOR BALANCE DAMPERS

INSTALLED IN IN-ACCESSIBLE LOCATIONS.

L. ALL RECTANGULAR DUCTWORK DOWN-STREAM OF VAV BOXES SHALL HAVE

1" ACOUSTIC LINER.

GENERAL MECHANICAL NOTES

0 1 2 3 4 5 6 7 8 9 10 inches

DRAWING NO.

PKG

NO.

SHEET

OF

PROJECT NO.:

REVISIONS:

DESIGNED

TECH. REVIEW

CADD

DESIGNED SUB SHEET NO. TITLE OF SHEET

THOMAS R.

COBURN

No. 20022 PE

I S

S

E F

O R

P

LANO EN

G

IN

E E R

ON

T

M

ANA

LICENSED

3/ 8/ :1 8:

P M

M2.1

3.10.17C O N S T R U C T

IO

N D O C U M E N T S

BASEMENT MECH. PIPING PLAN

16079

ALWRI RENOVATION

FOREST SERVICE / ROCKY MOUNTAIN RESEARCH STATION

EJW

REB

TRC

: 1/4" = 1'-0"M2.1M2.1

9 BASEMENT MECHANICAL PIPING PLAN

NORTH

1. 2-1/2" HPR UP IN CHASE TO DC-1.

2. 1" CONDENSATE DOWN FROM FIRST FLOOR IN CHASE.

3. 1-1/4" CONDENSATE DOWN TO FS-1.

4. REFRIGERANT LIQUID, SUCTION & MIXED GAS PIPING UP TO FIRST FLOOR.

5. REFRIGERANT PIPING SHOWN IS DIAGRAMATIC & IS FOR ILLUSTRATIVE

PURPOSES ONLY. MECHANICAL CONTRACTOR SHALL FIELD VERIFY ALL

REFRIGERANT PIPING LOCATIONS & PROVIDE UPDATED REFRIGERANT PIPING

DIAGRAM BASED ON ACTUAL INSTALLATION LENGTHS.

smoses Text Box smoses

A

B

STAIR

A

RGEG

SCIENTIST

RGEG

SCIENTIST

RGEG

SCIENTIST

ABA

UNI-SEX

RESTROOM

OPEN

OFFICE

AREA

RECEPTION

RGEG

SCIENTIST

OPEN

OFFICE

AREA

102CONFERENCE

ROOM

RGEG

SCIENTIST

RGEG

SCIENTIST

STAIR

B

DIRECTOR

OFFICE

1 2

HRU-3

HRU-4

HRU-5

HRU-6

ENTRY

12"ø 12"ø 10"ø

8"ø

10"ø

8"ø

10"ø

8"ø

8"ø 8"ø

6"ø

6"ø

6"ø

6"ø

E-1

E-2

T

FC 103

TFC 112

TFC 104

T

FC 105

T

FC 106

T

FC 107

T FC 108TFC 109TFC 110

T

FC

102A

T

FC

102B

T

FC

102C

T

FC

102D

6"ø

6"ø6"ø6"ø

6"ø

8"ø

EWH-1

ECH-1

FC

102A

FC

102B

FC

102D

FC

FC

FC

FC

FC

FC

FC

FC

FC

102C

FC

S-2

S-2

S-2

S-2

S-2

S-2

S-2

S-2

S-2

S-2

6"ø

6"ø

8"ø

DC-1

S-2

4 4 4 4

5 5 5

6" CONCRETE HOUSEKEEPING PAD. EXTEND MIN. 6"

BEYOND FOOTPRINT OF EQUIPMENT. SEE

STRUCTURAL FOR INSTALLATION DETAILS. FIELD

COORDINATE EXACT INSTALLATION LOCATION.

A. IT SHALL BE THE RESPONSIBILITY OF THE MECHANICAL CONTRACTOR TO

FIELD COORDINATE THE ROUTING OF ALL DUCTWORK AND PIPING WITH ALL

OTHER TRADES.

B. BUILDING IN GENERAL HAS LIMITED SPACE AND IS CONGESTED. IT SHALL BE

THE RESPONSIBILITY OF THE MECHANICAL CONTRACTOR TO REVIEW

DRAWINGS FOR ALL DISCIPLINES AND PROVIDE ALL LABOR AND MATERIALS

REQUIRED FOR A COMPLETE INSTALLATION.

C. DO NOT RUN ANY DUCTWORK OR PIPING OVER ELECTRICAL PANELS FROM

PANEL TO STRUCTURE ABOVE AND FROM PANEL ACCESS SPACE TO 80"

ABOVE FINISHED FLOOR.

D. COORDINATE THE INSTALL OF GRILLES, REGISTERS AND DIFFUSERS WITH

THE ARCHITECTURAL REFLECTED CEILING PLANS AND THE ELECTRICAL

LIGHTING PLANS.

E. VERIFY THE LOCATION OF ALL THERMOSTATS AND SENSORS WITH THE

ENGINEER AND ARCHITECT PRIOR TO INSTALLATION. INSTALL THERMOSTATS

48" ABOVE FINISHED FLOOR PER ADA REQUIREMENTS.

F. PROVIDE AND INSTALL SEISMIC BRACING FOR ALL EQUIPMENT, DUCTWORK

AND PIPING PER THE REQUIREMENTS OF THE 2012 INTERNATIONAL BUILDING

CODE.

G. FLEXIBLE DUCTWORK FROM BRANCH DUCTS TO GRILLES, REGISTERS AND

DIFFUSERS SHALL BE LIMITED TO 5FT MAX.

H. PROVIDE AND INSTALL FIRE, SMOKE AND COMBINATION SMOKE/FIRE

DAMPERS WHERE DUCTWORK PASSES THROUGH FIRE RATED ASSEMBLIES.

I. SEAL ALL DUCT AND PIPE PENETRATIONS THROUGH FIRE RATED ASSEMBLIES

WITH A UL APPROVED FIRE STOP SYSTEM.

J. PROVIDE ACCESS DOORS TO ALLOW SERVICE AND INSPECTION OF

EQUIPMENT, VALVES, DAMPERS AND DEVICES INSTALLED ABOVE NON-

REMOVABLE CEILINGS.

K. PROVIDE FLUSH CUP REMOTE DAMPER ACTUATORS FOR BALANCE DAMPERS

INSTALLED IN IN-ACCESSIBLE LOCATIONS.

L. ALL RECTANGULAR DUCTWORK DOWN-STREAM OF VAV BOXES SHALL HAVE

1" ACOUSTIC LINER.

GENERAL MECHANICAL NOTES

KEY NOTES:#

0 1 2 3 4 5 6 7 8 9 10 inches

DRAWING NO.

PKG

NO.

SHEET

OF

PROJECT NO.:

REVISIONS:

DESIGNED

TECH. REVIEW

CADD

DESIGNED SUB SHEET NO. TITLE OF SHEET

THOMAS R.

COBURN

No. 20022 PE

I S S

E F

O R

P

LAN

O EN

G

IN

E E R

ON

T

M

AN

A

LICENSE

D

/1

/2

:0

:5

A

M

M2.2

3.10.17C O

N S

T R

U C

T

IO

N D

O C

U M

E N

T S

1ST FLOOR MECH. HVAC PLAN

16079

ALWRI RENOVATION

FOREST SERVICE / ROCKY MOUNTAIN RESEARCH STATION

EJW

REB

TRC

: 1/4" = 1'-0"M2.2M2.2

9 FIRST FLOOR MECHANICAL HVAC PLAN

NORTH

1. 14"Ø OA DUCT UP TO ERV-1 ON ROOF. TRANSITION TO ERV DISCHARGE

CONNECTION AS REQUIRED. AFTER FIRST FLOOR BRANCH TAKE-OFFS, TRANSITION

TO 10"Ø DOWN IN CHASE. ROUTE AS FAR NORTH IN CHASE AS COORDINATION WITH

PLUMBING & DUCTWORK ALLOWS.

2. 14"Ø EA DUCT UP TO ERV-1 ON ROOF. TRANSITION TO ERV INLET CONNECTION AS

REQUIRED. AFTER FIRST FLOOR BRANCH TAKE-OFFS, TRANSITION TO 12"Ø DOWN IN

CHASE. ROUTE AS FAR NORTH IN CHASE AS COORDINATION WITH PLUMBING &

DUCTWORK ALLOWS.

3. 3"Ø VENT AND FLUE DOWN IN CHASE TO B-1 & B-2. TERMINATE THROUGH ROOF IN

CONCETRIC VENT KIT IF MANUFACTURER ALLOWS. ROUTE AS FAR NORTH IN CHASE

AS COORDINATION WITH PLUMBING ALLOWS.

4. SPRAYFOAM INSULATE ALL STALLS ON EXTERIOR WALLS WHERE CONDENSATE AND

REFRIGERANT IS ROUTED.

5. THERMOSTAT WIRE TO BE RUN TO TRENDWAY "TRENDWALL" CHASE.

6. DUCT ROUTED IN OPEN WEB JOISTS. SPRAY FOAM TO ALLOW CLEAR PASSAGE OF

DUCT WHERE APPLICABLE.

7. DC-1 MOUNTED ON GRADE. MAINTAIN ALL MANUFACTURERS RECOMENDED

CLEARANCES.

smoses Text Box smoses

A

B

STAIR

A

RGEG

SCIENTIST

RGEG

SCIENTIST

RGEG

SCIENTIST

108ABA

UNI-SEX

RESTROOM

OPEN

OFFICE

AREA

RECEPTION

RGEG

SCIENTIST

OPEN

OFFICE

AREA

CONFERENCE

ROOM

RGEG

SCIENTIST

RGEG

SCIENTIST

STAIR

B

DIRECTOR

OFFICE

HRU-3

HRU-4

HRU-5

HRU-6

ENTRY

EWH-1

ECH-1

FC

102A

FC

FC

FC

102B

FC

FC

FC

FC

FC

102C

FC

102D

FC

FC

FC

3/4"ø CND

1"ø CND

1"ø CND

3/4"ø CND

1"ø CND

3/4"ø CND

1"ø CND

3/4"ø CND

3/4"ø CND 1"ø CND

1"ø CND

1"ø CND

3/4"ø CND

DC-1

REFRIGERANT LIQUID,

SUCTION & MIXED GAS

PIPING (TYP).

REFRIGERANT LIQUID

& SUCTION (TYP).

KEY NOTES:#

A. IT SHALL BE THE RESPONSIBILITY OF THE MECHANICAL CONTRACTOR TO

FIELD COORDINATE THE ROUTING OF ALL DUCTWORK AND PIPING WITH ALL

OTHER TRADES.

B. BUILDING IN GENERAL HAS LIMITED SPACE AND IS CONGESTED. IT SHALL BE

THE RESPONSIBILITY OF THE MECHANICAL CONTRACTOR TO REVIEW

DRAWINGS FOR ALL DISCIPLINES AND PROVIDE ALL LABOR AND MATERIALS

REQUIRED FOR A COMPLETE INSTALLATION.

C. DO NOT RUN ANY DUCTWORK OR PIPING OVER ELECTRICAL PANELS FROM

PANEL TO STRUCTURE ABOVE AND FROM PANEL ACCESS SPACE TO 80"

ABOVE FINISHED FLOOR.

D. COORDINATE THE INSTALL OF GRILLES, REGISTERS AND DIFFUSERS WITH

THE ARCHITECTURAL REFLECTED CEILING PLANS AND THE ELECTRICAL

LIGHTING PLANS.

E. VERIFY THE LOCATION OF ALL THERMOSTATS AND SENSORS WITH THE

ENGINEER AND ARCHITECT PRIOR TO INSTALLATION. INSTALL THERMOSTATS

48" ABOVE FINISHED FLOOR PER ADA REQUIREMENTS.

F. PROVIDE AND INSTALL SEISMIC BRACING FOR ALL EQUIPMENT, DUCTWORK

AND PIPING PER THE REQUIREMENTS OF THE 2012 INTERNATIONAL BUILDING

CODE.

G. FLEXIBLE DUCTWORK FROM BRANCH DUCTS TO GRILLES, REGISTERS AND

DIFFUSERS SHALL BE LIMITED TO 5FT MAX.

H. PROVIDE AND INSTALL FIRE, SMOKE AND COMBINATION SMOKE/FIRE

DAMPERS WHERE DUCTWORK PASSES THROUGH FIRE RATED ASSEMBLIES.

I. SEAL ALL DUCT AND PIPE PENETRATIONS THROUGH FIRE RATED ASSEMBLIES

WITH A UL APPROVED FIRE STOP SYSTEM.

J. PROVIDE ACCESS DOORS TO ALLOW SERVICE AND INSPECTION OF

EQUIPMENT, VALVES, DAMPERS AND DEVICES INSTALLED ABOVE NON-

REMOVABLE CEILINGS.

K. PROVIDE FLUSH CUP REMOTE DAMPER ACTUATORS FOR BALANCE DAMPERS

INSTALLED IN IN-ACCESSIBLE LOCATIONS.

L. ALL RECTANGULAR DUCTWORK DOWN-STREAM OF VAV BOXES SHALL HAVE

1" ACOUSTIC LINER.

GENERAL MECHANICAL NOTES

0 1 2 3 4 5 6 7 8 9 10 inches

DRAWING NO.

PKG

NO.

SHEET

OF

PROJECT NO.:

REVISIONS:

DESIGNED

TECH. REVIEW

CADD

DESIGNED SUB SHEET NO. TITLE OF SHEET

THOMAS R.

COBURN

No. 20022 PE

I S

S

E F

O R

P

LANO EN

G

IN

E E R

ON

T

M

ANA

LICENSED

3/ 8/ :1 8:

P M

M2.3

3.10.17C O N S T R U C T

IO

N D O C U M E N T S

1ST FLOOR MECH. PIPING PLAN

16079

ALWRI RENOVATION

FOREST SERVICE / ROCKY MOUNTAIN RESEARCH STATION

EJW

REB

TRC

: 1/4" = 1'-0"M2.3M2.3

9 FIRST FLOOR MECHANICAL PIPING PLAN

1. HPR UP & DOWN IN CHASE TO DC-1.

2. 1" CONDENSATE DOWN IN CHASE TO FS-1.

3. DC-1 MOUNTED ON GRADE. MAINTAIN ALL MANUFACTURERS RECOMENDED

CLEARANCES.

4. REFRIGERANT LIQUID, SUCTION & MIXED GAS PIPING DOWN TO BASEMNET

FLOOR.

5. REFRIGERANT PIPING SHOWN IS DIAGRAMATIC & IS FOR ILLUSTRATIVE

PURPOSES ONLY. MECHANICAL CONTRACTOR SHALL FIELD VERIFY ALL

REFRIGERANT PIPING LOCATIONS & PROVIDE UPDATED REFRIGERANT PIPING

DIAGRAM BASED ON ACTUAL INSTALLATION LENGTHS.

smoses Text Box smoses

B

ERV-1

PH-1

KEY NOTES:#

A. IT SHALL BE THE RESPONSIBILITY OF THE MECHANICAL CONTRACTOR TO

FIELD COORDINATE THE ROUTING OF ALL DUCTWORK AND PIPING WITH ALL

OTHER TRADES.

B. BUILDING IN GENERAL HAS LIMITED SPACE AND IS CONGESTED. IT SHALL BE

THE RESPONSIBILITY OF THE MECHANICAL CONTRACTOR TO REVIEW

DRAWINGS FOR ALL DISCIPLINES AND PROVIDE ALL LABOR AND MATERIALS

REQUIRED FOR A COMPLETE INSTALLATION.

C. DO NOT RUN ANY DUCTWORK OR PIPING OVER ELECTRICAL PANELS FROM

PANEL TO STRUCTURE ABOVE AND FROM PANEL ACCESS SPACE TO 80"

ABOVE FINISHED FLOOR.

D. COORDINATE THE INSTALL OF GRILLES, REGISTERS AND DIFFUSERS WITH

TH…