Attachment 2 - Technical Specifications
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| AG-569R-S-17-0002_Solicitation_Document.docx | DOCX document | |
| Attachment__1_-_Specifications_011000_-_SUMMARY_SP.doc | DOC document | |
| Attachment__6_-_Site_Sketch_-_UPPCO_form.pdf | ||
| Attachment__4_-_Wage_Determination_MI116.txt | TXT text file | |
| Attachment__3_-_USFS_Rapid_River_Electrical_Plans_FINAL_10-12-16.pdf | ||
| Attachment__7_-_UPPCO_load_form.pdf | ||
| Attachment__5_-_Experience_Questionnaire_.docx | DOCX document |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
U.S. DEPARTMENT OF AGRICULTURE
U.S. FOREST SERVICE
HIAWATHA NATIONAL FOREST
RANGER DISTRICT OFFICE COMPOUND
ELECTRICAL UPGRADES
RAPID RIVER, MI
UPEA project # U28-16331 October 12, 2016
DIVISION 26 INDEX
ELECTRICAL
SECTION
26 00 00 INDEX
26 05 00 GENERAL ELECTRICAL REQUIREMENTS
26 05 02 ELECTRICAL DEMOLITION
26 05 03 EQUIPMENT WIRING
26 05 19 CONDUCTORS AND CABLES
26 05 26 GROUNDING AND BONDING
26 05 29 HANGERS AND SUPPORTS
26 05 33 RACEWAYS AND BOXES
26 05 53 ELECTRICAL IDENTIFICATION
26 24 16 PANELBOARD
NOTE: Any and all references to a Specification Section number 01 ## ## refers to “Front End” bidding documents created by the U.S. Forest Service.
RANGER DISTRICT OFFICE COMPOUND ELECTRICAL UPGRADES
USDA – FOREST SERVICE, RAPID RIVER, MI
HIAWATHA NATIONAL FOREST
UPEA Project# General Electrical Requirements [U28-16331] 26 05 00 - 1
SECTION 26 05 00
GENERAL ELECTRICAL REQUIREMENTS
PART 1 - GENERAL
1.01 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.
1.02 SUMMARY
A. Section Includes:
1. Electrical equipment coordination and installation.
2. Sleeves for raceways and cables.
3. Sleeve seals.
4. Grout.
5. Common electrical installation requirements.
B. Provide all interior & exterior electric wiring including, but not limited to:
1. Removal and replacement of main electrical service to site and existing buildings as detailed on plans.
2. Removal, replacement and/or modifications to existing electrical panels as indicated on plans.
3. New outside feeders to serve existing building.
4. All new panels, circuit breakers, transformers, conduit and wire as indicated on plans.
5. Feeders to selected equipment as detailed.
6. Electrical Contractor is responsible for locating all existing buried site utilities prior to beginning work, including existing electrical power feeders and branch circuits. (Note that a “MISS DIG” must be called in by the contractor for location of Natural Gas (DTE) and telephone). The contractor is responsible for locating any buried water lines.
7. Electrical Contractor is responsible for temporary construction power; may utilize existing electrical service & panel(s) for construction power & for temporary power until the new permanent electrical service is operational.
1.03 SUBMITTALS
A. Refer to Section 01 33 00 for additional submittal requirements.
B. Shop Drawings: Provide certified shop drawing submittals (approved by the Prime contractor) for the following items and any other items where indicated in other specification sections:
1. Meter/CT cabinet (per utility company requirements)
2. Panelboards
HIAWATHA NATIONAL FOREST
UPEA Project# General Electrical Requirements [U28-16331] 26 05 00 - 2
3. Circuit Breakers
C. Product Data: Provide certified submittals (approved by the Prime contractor) for the following items and any other items where indicated in other specification sections:
1. Panelboards
2. Circuit Breakers
3. Disconnect Switches and Fuses
4. Conduit, boxes, fittings, and support items
5. Wire and Cable
6. For sleeve seals.
1.04 COORDINATION
A. Coordinate arrangement, mounting, and support of electrical equipment:
1. To allow maximum possible headroom unless specific mounting heights that reduce headroom are indicated.
2. To provide for ease of disconnecting the equipment with minimum interference to other installations.
3. So connecting raceways and cables will be clear of obstructions and of the working and access space of other equipment.
B. Coordinate installation of required supporting devices and set sleeves in cast-in-place concrete, masonry walls, and other structural components as they are constructed.
PART 2 - PRODUCTS
2.01 MANUFACTURERS
A. Provide like items from one manufacturer; such as, switches, circuit breakers, transformers, panels, and the like.
B. Provide new electrical materials of the type and quality detailed, listed by UL, bearing their label wherever standards have been established.
C. Provide incidentals not specifically mentioned herein or noted on Drawings, but needed to complete the system or systems, in a safe and satisfactory working condition.
D. Where materials, equipment, apparatus or other products are specified by manufacturer, brand name, type, or catalog number, such designation is to establish standards of desired quality and style and shall be the basis of the bid.
2.02 SLEEVES FOR RACEWAYS AND CABLES
A. Steel Pipe Sleeves: ASTM A 53/A 53M, Type E, Grade B, Schedule 40, galvanized steel, plain ends.
HIAWATHA NATIONAL FOREST
UPEA Project# General Electrical Requirements [U28-16331] 26 05 00 - 3
B. Cast-Iron Pipe Sleeves: Cast or fabricated "wall pipe," equivalent to ductile-iron pressure pipe, with plain ends and integral waterstop, unless otherwise indicated.
C. Sleeves for Rectangular Openings: Galvanized sheet steel.
1. Minimum Metal Thickness:
a. For sleeve cross-section rectangle perimeter less than 50 inches and no side more than 16 inches, thickness shall be 0.052-inch.
b. For sleeve cross-section rectangle perimeter equal to, or more than, 50 inches and 1 or more sides equal to, or more than, 16 inches, thickness shall be 0.138-inch.
2.03 SLEEVE SEALS
A. Description: Modular sealing device, designed for field assembly, to fill annular space between sleeve and raceway or cable.
1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:
a. Advance Products & Systems, Inc.
b. Calpico, Inc.
c. Metraflex Co.
d. Pipeline Seal and Insulator, Inc.
2. Sealing Elements: EPDM interlocking links shaped to fit surface of cable or conduit.
Include type and number required for material and size of raceway or cable.
3. Pressure Plates: Plastic. Include two for each sealing element.
4. Connecting Bolts and Nuts: Stainless steel of length required to secure pressure plates to sealing elements. Include one for each sealing element.
2.04 GROUT
A. Nonmetallic, Shrinkage-Resistant Grout: ASTM C 1107, factory-packaged, nonmetallic aggregate grout, noncorrosive, nonstaining, mixed with water to consistency suitable for application and a 30-minute working time.
PART 3 - EXECUTION
3.01 COMMON REQUIREMENTS FOR ELECTRICAL INSTALLATION
A. Comply with NECA 1, NFPA 70 (National Electrical Code – current edition), and any local amendments.
HIAWATHA NATIONAL FOREST
UPEA Project# General Electrical Requirements [U28-16331] 26 05 00 - 4
B. Measure indicated mounting heights to bottom of unit for suspended items and to center of unit for wall-mounting items.
C. Headroom Maintenance: If mounting heights or other location criteria are not indicated, arrange and install components and equipment to provide maximum possible headroom consistent with these requirements.
D. Equipment: Install to facilitate service, maintenance, and repair or replacement of components of both electrical equipment and other nearby installations. Connect in such a way as to facilitate future disconnecting with minimum interference with other items in the vicinity.
E. Right of Way: Give to piping systems installed at a required slope.
3.02 SLEEVE INSTALLATION FOR ELECTRICAL PENETRATIONS
A. Electrical penetrations occur when raceways, cables, wireways, cable trays, or busways penetrate concrete slabs, concrete or masonry walls, or fire-rated floor and wall assemblies.
B. Concrete Slabs and Walls: Install sleeves for penetrations unless core-drilled holes or formed openings are used. Install sleeves during erection of slabs and walls.
C. Use pipe sleeves unless penetration arrangement requires rectangular sleeved opening.
D. Fire-Rated Assemblies: Install sleeves for penetrations of fire-rated floor and wall assemblies unless openings compatible with firestop system used are fabricated during construction of floor or wall.
E. Cut sleeves to length for mounting flush with both surfaces of walls.
F. Extend sleeves installed in floors 2 inches above finished floor level.
G. Size pipe sleeves to provide 1/4-inch annular clear space between sleeve and raceway or cable, unless indicated otherwise.
H. Seal space outside of sleeves with grout for penetrations of concrete and masonry
1. Promptly pack grout solidly between sleeve and wall so no voids remain. Tool exposed surfaces smooth; protect grout while curing.
I. Interior Penetrations of Non-Fire-Rated Walls and Floors: Seal annular space between sleeve and raceway or cable, using joint sealant appropriate for size, depth, and location of joint.
Comply with requirements in Division 07 Section "Joint Sealants."
J. Aboveground, Exterior-Wall Penetrations: Seal penetrations using steel pipe sleeves and mechanical sleeve seals. Select sleeve size to allow for 1-inch annular clear space between pipe and sleeve for installing mechanical sleeve seals.
HIAWATHA NATIONAL FOREST
UPEA Project# General Electrical Requirements [U28-16331] 26 05 00 - 5
K. Underground, Exterior-Wall Penetrations: Install cast-iron pipe sleeves. Size sleeves to allow for 1-inch annular clear space between raceway or cable and sleeve for installing mechanical sleeve seals.
3.03 SLEEVE-SEAL INSTALLATION
A. Install to seal exterior wall penetrations.
B. Use type and number of sealing elements recommended by manufacturer for raceway or cable material and size. Position raceway or cable in center of sleeve. Assemble mechanical sleeve seals and install in annular space between raceway or cable and sleeve. Tighten bolts against pressure plates that cause sealing elements to expand and make watertight seal.
3.04 FIRESTOPPING
A. Apply firestopping to penetrations of fire-rated floor and wall assemblies for electrical installations to restore original fire-resistance rating of assembly.
END OF SECTION
HIAWATHA NATIONAL FOREST
UPEA Project No. Electrical Demolition [U28-16331] 26 05 02 - 1
SECTION 26 05 02
ELECTRICAL DEMOLITION
PART 1 GENERAL
1.01 SECTION INCLUDES
A. Electrical demolition.
PART 2 PRODUCTS – Not Used
PART 3 EXECUTION
3.01 EXAMINATION
A. Verify that abandoned wiring and equipment serve only abandoned facilities.
B. Demolition drawings are based on field observation and existing record documents.
C. Report discrepancies to Owner before disturbing existing installation.
D. Beginning of demolition means installer accepts existing conditions.
3.02 PREPARATION
A. Disconnect electrical systems as indicated on plans.
B. Coordinate utility service outages with utility company and Owner.
C. Provide temporary wiring and connections to maintain existing systems in service during construction. When work must be performed on energized equipment or circuits, use personnel experienced in such operations.
D. Existing Electrical Service: Maintain existing system in service until new system is complete and ready for service. Disable system only to make switchovers and connections. Minimize outage duration.
1. Obtain permission from Owner at least 24 hours before partially or completely disabling system.
2. Make temporary connections to maintain service in areas adjacent to work area.
E. See notes on plans and riser diagrams about utilizing existing panels, etc.
3.03 DEMOLITION AND EXTENSION OF EXISTING ELECTRICAL WORK
A. Remove, relocate, and extend existing installations to accommodate construction.
B. Remove abandoned wiring to source of supply.
C. Remove exposed abandoned conduit, including abandoned conduit above accessible ceiling finishes. Cut conduit flush with walls and floors, and patch surfaces.
D. Disconnect abandoned outlets and remove devices. Remove abandoned outlets if conduit servicing them is abandoned and removed. Provide blank cover for abandoned outlets which are not removed.
E. Disconnect and remove abandoned disconnects, circuit breakers, panelboards, and distribution
HIAWATHA NATIONAL FOREST
UPEA Project No. Electrical Demolition [U28-16331] 26 05 02 - 2 equipment.
F. Disconnect and remove electrical devices and equipment serving utilization equipment that has been removed.
G. Disconnect and remove abandoned luminaires. Remove brackets, stems, hangers, and other accessories.
H. Repair adjacent construction and finishes damaged during demolition and extension work.
I. Maintain access to existing electrical installations which remain active. Modify installation or provide access panel as appropriate.
J. Extend existing installations using materials and methods compatible with existing electrical installations, or as specified.
3.04 CLEANING AND REPAIR
A. Clean and repair existing materials and equipment which remain or are to be reused.
B. Panelboards: Clean exposed surfaces and check tightness of electrical connections. Replace damaged circuit breakers and provide closure plates for vacant positions. Provide typed circuit directory showing revised circuiting arrangement and panel label.
HIAWATHA NATIONAL FOREST
UPEA Project No. Equipment Wiring [U28-16331] 26 05 03 - 1
SECTION 26 05 03
EQUIPMENT WIRING
PART 1 GENERAL
1.1 SUMMARY
A. Section includes electrical connections to equipment.
B. Related Sections:
1. Section 26 05 19 - Low-Voltage Electrical Power Conductors and Cables.
2. Section 26 05 33 - Raceway and Boxes for Electrical Systems.
1.2 REFERENCES
A. National Electrical Manufacturers Association:
1. NEMA WD 1 - General Requirements for Wiring Devices.
2. NEMA WD 6 - Wiring Devices-Dimensional Requirements.
1.3 SUBMITTALS
A. Section 01 33 00 - Submittal Procedures: Submittal procedures.
B. Product Data: Submit wiring device manufacturer’s catalog information showing dimensions, configurations, and construction.
C. Manufacturer's installation instructions.
1.4 CLOSEOUT SUBMITTALS
A. Section 01 70 00 - Execution and Closeout Requirements: Submittal procedures.
B. Project Record Documents: Record actual locations, sizes, and configurations of equipment connections.
1.5 COORDINATION
A. Section 01 30 00 - Administrative Requirements: Coordination and project conditions.
B. Obtain and review shop drawings, product data, manufacturer’s wiring diagrams, and manufacturer's instructions for equipment furnished under other sections.
C. Determine connection locations and requirements.
D. Sequence rough-in of electrical connections to coordinate with installation of equipment.
E. Sequence electrical connections to coordinate with start-up of equipment.
HIAWATHA NATIONAL FOREST
UPEA Project No. Equipment Wiring [U28-16331] 26 05 03 - 2
PART 2 PRODUCTS
2.1 CORD AND PLUGS
A. Attachment Plug Construction: Conform to NEMA WD 1.
B. Must be UL Listed and Labeled.
C. Configuration: NEMA WD 6; match receptacle configuration at outlet furnished for equipment.
D. Cord Construction: Heavy-Duty Type SO multiconductor flexible cord with identified equipment grounding conductor, oil and water resistant, suitable for use in damp locations.
E. Size: Suitable for connected load of equipment, length of cord, and rating of branch circuit overcurrent protection.
PART 3 EXECUTION
3.1 EXAMINATION
A. Section 01 30 00 - Administrative Requirements: Coordination and project conditions.
B. Verify equipment is ready for electrical connection, for wiring, and to be energized.
3.2 EXISTING WORK
A. Remove exposed abandoned equipment wiring connections, including abandoned connections above accessible ceiling finishes.
B. Disconnect abandoned utilization equipment and remove wiring connections. Remove abandoned components when connected raceway is abandoned and removed. Install blank cover for abandoned boxes and enclosures not removed.
C. Extend existing equipment connections using materials and methods compatible with existing electrical installations, or as specified.
3.3 INSTALLATION
A. Make electrical connections.
B. Make conduit connections to equipment using flexible conduit. Use liquidtight flexible conduit with watertight connectors in damp or wet locations.
C. Connect heat producing equipment using wire and cable with insulation suitable for temperatures encountered.
D. Install receptacle outlet to accommodate connection with attachment plug.
E. Install cord and cap for field-supplied attachment plug.
HIAWATHA NATIONAL FOREST
UPEA Project No. Equipment Wiring [U28-16331] 26 05 03 - 3
F. Install suitable strain-relief clamps and fittings for cord connections at outlet boxes and equipment connection boxes.
G. Install disconnect switches, controllers, control stations, and control devices to complete equipment wiring requirements.
H. Install terminal block jumpers to complete equipment wiring requirements.
I. Install interconnecting conduit and wiring between devices and equipment to complete equipment wiring requirements.
3.4 ADJUSTING
A. Section 01 70 00 - Execution and Closeout Requirements: Testing, adjusting, and balancing.
B. Cooperate with utilization equipment installers and field service personnel during checkout and starting of equipment to allow testing and balancing and other startup operations. Provide personnel to operate electrical system and checkout wiring connection components and configurations.
3.5 EQUIPMENT CONNECTION SCHEDULE
A. Provide electrical connection of equipment (voltage, amperage, fusing, etc.) per equipment manufacturer’s requirements.
HIAWATHA NATIONAL FOREST
UPEA Project No. Conductors and Cables [U28-16331] 26 05 19 - 1
SECTION 26 05 19
CONDUCTORS AND CABLES
PART 1 GENERAL
1.1 SUMMARY
A. Section includes wire and cable; and wiring connectors and connections.
1.2 REFERENCES
A. International Electrical Testing Association:
1. NETA ATS - Acceptance Testing Specifications for Electrical Power
Distribution Equipment and Systems.
B. National Fire Protection Association:
1. NFPA 70 - National Electrical Code.
2. NFPA 262 - Standard Method of Test for Flame Travel and Smoke of Wires and
Cables for Use in Air-Handling Spaces.
C. Underwriters Laboratories, Inc.:
1. UL 1277 - Standard for Safety for Electrical Power and Control Tray Cables with
Optional Optical-Fiber Members.
1.3 SYSTEM DESCRIPTION
A. Product Requirements: Provide products as follows:
1. Stranded conductors.
2. Conductor not smaller than 12 AWG for power and lighting circuits.
3. Conductor not smaller than 16 AWG for control circuits.
B. Conduit:
1. Wire shall be installed in conduit.
2. Conduit may be used in exposed locations only in unfinished spaces (such as mechanical rooms). All conduit in finished spaces shall be concealed in walls and above ceilings, unless otherwise approved by the owner or engineer.
3. MC cable shall not be used.
1.4 DESIGN REQUIREMENTS
A. Conductor sizes are based on copper. DO NOT use aluminum wire.
1.5 SUBMITTALS
A. Section 01 33 00 - Submittal Procedures.
B. Material information.
HIAWATHA NATIONAL FOREST
UPEA Project No. Conductors and Cables [U28-16331] 26 05 19 - 2
1.6 CLOSEOUT SUBMITTALS
A. Section 01 70 00 - Execution and Closeout.
B. Project Record Documents: Record actual locations of components and circuits.
1.7 QUALITY ASSURANCE
A. All materials shall be in accordance with the National Electrical Code.
1.8 QUALIFICATIONS
A. Manufacturer: Company specializing in manufacturing products specified in this section with minimum three years documented experience.
1.9 FIELD MEASUREMENTS
A. Verify field measurements are as indicated on Drawings.
1.10 COORDINATION
A. Section 01 30 00 - Administrative.
B. Where wire and cable destination is indicated and routing is not shown, determine routing and lengths required.
C. Wire and cable routing indicated is approximate unless dimensioned. Include wire and cable lengths within 10 ft of length shown.
1.11 DEFINITIONS
A. Furnish: To supply and deliver, unload and inspect for damage.
B. Install: To unpack, assemble, erect, mount, apply, place, finish, cure, protect, clean, energize, program, adjust, test and make completely functional and operational.
C. Provide: To furnish and install.
PART 2 PRODUCTS
2.1 BUILDING WIRE
A. Manufacturers:
1. General Cable Co.
2. Rome Cable.
3. Southwire.
B. Product Description: Single conductor insulated wire.
HIAWATHA NATIONAL FOREST
UPEA Project No. Conductors and Cables [U28-16331] 26 05 19 - 3
C. Conductor: Stranded copper.
D. Insulation Voltage Rating: 600 volts.
E. Insulation Temperature Rating: 90 degrees C.
F. Insulation Type: Use XHHW for all sizes AWG #4 and larger. THWN/THHN may be used for all sizes AWG #6 and smaller.
2.2 WIRING CONNECTORS
A. Split Bolt Connectors:
B. Solderless Pressure Connectors:
C. Spring Wire Connectors:
D. Compression Connectors:
2.3 TERMINATIONS
A. Terminal Lugs for Wires 6 AWG and Smaller: Solderless, compression type copper.
B. Lugs for Wires 4 AWG and Larger: Color keyed, compression type copper, with insulating sealing collars.
PART 3 EXECUTION
3.1 EXAMINATION
A. Section 01 30 00 - Administrative Requirements.
B. Verify interior of building has been protected from weather.
C. Verify mechanical work likely to damage wire and cable has been completed.
D. Verify raceway installation is complete and supported.
3.2 PREPARATION
A. Completely and thoroughly swab raceway before installing wire.
3.3 INSTALLATION
A. Route wire and cable to meet Project conditions.
B. Neatly train and lace wiring inside boxes, equipment, and panelboards.
HIAWATHA NATIONAL FOREST
UPEA Project No. Conductors and Cables [U28-16331] 26 05 19 - 4
C. Identify and color code wire and cable. Identify each conductor with its circuit number or other designation indicated.
D. Special Techniques--Wire in Raceway:
1. Pull conductors into raceway at same time.
2. Install building wire #4 AWG and larger with pulling equipment. Pulling equipment shall be equipped with strain gauge. Prepare pulling calculations for all runs #3 AWG and larger with lengths exceeding 200 feet. Provide all pulling calculations to the Owner and Engineer prior to installation.
E. Special Techniques - Cable:
1. Protect exposed cable from damage.
2. Support cables above accessible ceiling, using spring metal clips or metal cable ties to support cables from structure or ceiling suspension system. Do not rest cable on ceiling panels.
3. Use suitable cable fittings and connectors.
F. Special Techniques - Wiring Connections:
1. Clean conductor surfaces before installing lugs and connectors.
2. Make splices, taps, and terminations to carry full ampacity of conductors with no perceptible temperature rise.
3. Tape uninsulated conductors and connectors with electrical tape to 150 percent of insulation rating of conductor.
4. Install split bolt connectors for copper conductor splices and taps, 6 AWG and larger.
5. Install solderless pressure connectors with insulating covers for copper conductor splices and taps, 8 AWG and smaller.
6. Install insulated spring wire connectors with plastic caps for copper conductor splices and taps, 10 AWG and smaller.
G. Install stranded conductors for branch circuits 10 AWG and smaller. Install crimp on fork terminals for device terminations. Do not place bare stranded conductors directly under screws.
H. Install terminal lugs on ends of 600 volt wires unless lugs are furnished on connected device, such as circuit breakers.
I. Size lugs in accordance with manufacturer’s recommendations terminating wire sizes.
Install 2-hole type lugs to connect wires 4 AWG and larger to copper bus bars.
J. For terminal lugs fastened together such as on motors, transformers, and other apparatus, or when space between studs is small enough that lugs can turn and touch each other, insulate for dielectric strength of 2-1/2 times normal potential of circuit.
3.4 WIRE COLOR
A. General:
1. For wire sizes 10 AWG and smaller, install wire colors in accordance with the following:
HIAWATHA NATIONAL FOREST
UPEA Project No. Conductors and Cables [U28-16331] 26 05 19 - 5
a. Black, red, blue for three phase feeders/circuits at 120/208 volts.
2. For wire sizes 8 AWG and larger, identify wire with colored tape at terminals, splices and boxes, or purchase wire with insulation color. Colors are as follows:
a. Black, red, blue for three phase feeders/circuits at 120/208 volts.
B. Neutral Conductors:
1. For 208/120 volts, single- or three- phase system: White.
2. When two or more neutrals are located in one conduit, individually identify each with proper circuit number.
C. Branch Circuit Conductors: Install three or four wire home runs with each phase uniquely color coded.
D. Feeder Circuit Conductors: Uniquely color code each phase/leg.
E. Ground Conductors:
1. For 6 AWG and smaller: Green.
2. For 4 AWG and larger: Identify with green tape at both ends and visible points including junction boxes, or purchase wire with insulation color.
3.5 FIELD QUALITY CONTROL
A. Inspect and test in accordance with NETA ATS, except Section 4.
B. Perform inspections and tests listed in NETA ATS, Section 7.3.1.
HIAWATHA NATIONAL FOREST
UPEA Project No. Grounding and Bonding [U28-16331] 26 05 26 - 1
SECTION 26 05 26
GROUNDING AND BONDING
PART 1 GENERAL
1.1 SUMMARY
A. Section Includes:
1. Rod electrodes.
2. Wire.
3. Mechanical connectors.
4. Exothermic connections.
5. Equipment grounding.
1.2 REFERENCES
A. Institute of Electrical and Electronics Engineers:
1. IEEE 142 - Recommended Practice for Grounding of Industrial and Commercial
Power Systems.
2. IEEE 1100 - Recommended Practice for Powering and Grounding Electronic
Equipment.
B. International Electrical Testing Association:
1. NETA ATS - Acceptance Testing Specifications for Electrical Power
Distribution Equipment and Systems.
C. National Fire Protection Association:
1. NFPA 70 - National Electrical Code.
1.3 SYSTEM DESCRIPTION
A. Grounding systems use the following elements as grounding electrodes:
1. Metal underground water pipe (where present).
2. Metal building frame (where present).
3. Concrete-encased electrode (ufer).
4. Ground ring.
5. Metal underground gas piping system (where present).
6. Rod electrode.
7. Plate electrode.
B. Equipment Ground.
1. Provide separate insulated equipment grounding conductor in each conduit and raceway. DO NOT rely on conduit as the sole means of equipment grounding.
1.4 SUBMITTALS
HIAWATHA NATIONAL FOREST
UPEA Project No. Grounding and Bonding [U28-16331] 26 05 26 - 2
B. Product Data: Submit data on grounding electrodes and connections.
C. Test Reports: Indicate overall resistance to ground and resistance of each electrode.
1.5 CLOSEOUT SUBMITTALS
A. Section 01 70 00 - Execution and Closeout.
B. Project Record Documents: Record actual locations of components and grounding electrodes.
1.6 QUALITY ASSURANCE
A. Provide grounding materials conforming to requirements of NEC, IEEE 142, and UL labeled.
1.7 QUALIFICATIONS
A. Manufacturer: Company specializing in manufacturing Products specified in this section with minimum three years documented experience.
1.8 DELIVERY, STORAGE, AND HANDLING
A. Section 01 60 00 - Product Requirements.
B. Accept materials on site in original factory packaging, labeled with manufacturer's identification.
C. Protect from weather and construction traffic, dirt, water, chemical, and mechanical damage, by storing in original packaging.
D. Do not deliver items to project before time of installation. Limit shipment of bulk and multiple-use materials to quantities needed for immediate installation.
1.9 COORDINATION
A. Section 01 30 00 - Administrative Requirements.
B. Complete grounding and bonding of building reinforcing steel prior concrete placement.
PART 2 PRODUCTS
2.1 ROD ELECTRODES
A. Manufacturers:
1. Erico, Inc.
2. O-Z Gedney Co.
3. Thomas & Betts, Electrical.
HIAWATHA NATIONAL FOREST
UPEA Project No. Grounding and Bonding [U28-16331] 26 05 26 - 3
B. Product Description:
1. Material: Copper-clad steel.
2. Diameter: 3/4 inch.
3. Length: 10 feet.
C. Connector: Connector for exothermic welded connection.
2.2 WIRE
A. Material: Stranded copper.
B. Foundation Electrodes: match size of service grounding conductor.
C. Grounding Electrode Conductor: Copper conductor bare.
D. Bonding Conductor: Copper conductor bare or insulated.
2.3 MECHANICAL CONNECTORS
A. Description: Bronze connectors, suitable for grounding and bonding applications, in configurations required for particular installation.
2.4 EXOTHERMIC CONNECTIONS
A. Product Description: Exothermic materials, accessories, and tools for preparing and making permanent field connections between grounding system components.
PART 3 EXECUTION
3.1 EXAMINATION
A. Verify final backfill and compaction has been completed before driving rod electrodes.
3.2 PREPARATION
A. Remove paint, rust, mill oils and surface contaminants at connection points.
3.3 INSTALLATION
A. Install in accordance with IEEE 142, all local electrical utility requirements, and the National Electrical Code.
B. Install rod electrodes at locations as required by the local electrical utility, the National Electrical Code, and as indicated on Drawings.
C. Install grounding and bonding conductors concealed from view.
HIAWATHA NATIONAL FOREST
UPEA Project No. Grounding and Bonding [U28-16331] 26 05 26 - 4
D. Install grounding electrode conductor and connect to reinforcing steel in foundation footing in accordance with the National Electrical Code and as indicated on Drawings (for new building construction projects and additions only). Electrically bond steel together.
E. Bond together metal siding not attached to grounded structure; bond to ground.
F. Bond together each metallic raceway, pipe, duct and other metal objects.
G. Provide separate insulated equipment grounding conductor in each conduit and raceway.
Conductor shall be sized per National Electrical Code requirements.
3.4 FIELD QUALITY CONTROL
A. Inspect and test in accordance with NETA ATS, except Section 4.
B. Grounding and Bonding: Perform inspections and tests listed in NETA ATS, Section 7.13.
C. Perform ground resistance testing in accordance with IEEE 142.
D. Perform leakage current tests in accordance with NFPA 99.
E. Perform continuity testing in accordance with IEEE 142.
F. When improper grounding is found on receptacles, check receptacles in entire project and correct. Perform retest.
HIAWATHA NATIONAL FOREST
UPEA Project No. Hangers and Supports [U28-16331] 26 05 29 - 1
SECTION 26 05 29
HANGERS AND SUPPORTS
PART 1 GENERAL
1.1 SUMMARY
A. Section Includes:
1. Conduit supports.
2. Formed steel channel.
3. Spring steel clips.
4. Sleeves.
5. Mechanical sleeve seals.
6. Firestopping relating to electrical work.
7. Firestopping accessories.
8. Equipment bases and supports.
1.2 REFERENCES
A. ASTM International:
1. ASTM E84 - Standard Test Method for Surface Burning Characteristics of
Building Materials.
2. ASTM E119 - Standard Test Methods for Fire Tests of Building Construction and Materials.
3. ASTM E814 - Standard Test Method for Fire Tests of Through-Penetration Fire
Stops.
4. ASTM E1966 - Standard Test Method for Fire-Resistive Joint Systems.
B. FM Global:
1. FM - Approval Guide, A Guide to Equipment, Materials & Services Approved
By Factory Mutual Research For Property Conservation.
C. National Fire Protection Association:
1. NFPA 70 - National Electrical Code.
D. Underwriters Laboratories Inc.:
1. UL 263 - Fire Tests of Building Construction and Materials.
2. UL 723 - Tests for Surface Burning Characteristics of Building Materials.
3. UL 1479 - Fire Tests of Through-Penetration Firestops.
4. UL 2079 - Tests for Fire Resistance of Building Joint Systems.
5. UL - Fire Resistance Directory.
E. Intertek Testing Services (Warnock Hersey Listed):
1. WH - Certification Listings.
HIAWATHA NATIONAL FOREST
UPEA Project No. Hangers and Supports [U28-16331] 26 05 29 - 2
1.3 DEFINITIONS
A. Firestopping (Through-Penetration Protection System): Sealing or stuffing material or assembly placed in spaces between and penetrations through building materials to arrest movement of fire, smoke, heat, and hot gases through fire rated construction.
1.4 SYSTEM DESCRIPTION
A. Firestopping Materials: ASTM E119, ASTM E814, UL 263, UL 1479] to achieve fire ratings as noted on Drawings for adjacent construction, but not less than 1 hour fire rating.
B. Firestop interruptions to fire rated assemblies, materials, and components.
1.5 PERFORMANCE REQUIREMENTS
A. Firestopping: Conform to applicable code for fire resistance ratings and surface burning characteristics.
B. Firestopping: Provide certificate of compliance from authority having jurisdiction indicating approval of materials used.
1.6 SUBMITTALS
A. Section 01 33 00 - Submittal Procedures.
B. Shop Drawings: Indicate system layout with location and detail of trapeze hangers.
C. Product Data:
1. Hangers and Supports: Submit manufacturers catalog data including load capacity.
2. Firestopping: Submit data on product characteristics, performance and limitation criteria.
D. Firestopping Schedule: Submit schedule of opening locations and sizes, penetrating items, and required listed design numbers to seal openings to maintain fire resistance rating of adjacent assembly.
E. Design Data: Indicate load carrying capacity of trapeze hangers and hangers and supports.
F. Manufacturer's Installation Instructions:
1. Hangers and Supports: Submit special procedures and assembly of components.
2. Firestopping: Submit preparation and installation instructions.
G. Manufacturer's Certificate: Certify products meet or exceed specified requirements.
HIAWATHA NATIONAL FOREST
UPEA Project No. Hangers and Supports [U28-16331] 26 05 29 - 3
H. Engineering Judgements: For conditions not covered by UL or WH listed designs, submit judgements by licensed professional engineer suitable for presentation to authority having jurisdiction for acceptance as meeting code fire protection requirements.
1.7 QUALITY ASSURANCE
A. Through Penetration Firestopping of Fire Rated Assemblies: UL 1479 or ASTM E814 with 0.10 inch water gage minimum positive pressure differential to achieve fire F- Ratings and temperature T-Ratings as indicated on Drawings, but not less than 1-hour.
1. Wall Penetrations: Fire F-Ratings as indicated on Drawings, but not less than 1-hour.
2. Floor and Roof Penetrations: Fire F-Ratings and temperature T-Ratings as indicated on Drawings, but not less than 1-hour.
a. Floor Penetrations Within Wall Cavities: T-Rating is not required.
B. Through Penetration Firestopping of Non-Fire Rated Floor [and Roof] Assemblies:
Materials to resist free passage of flame and products of combustion.
1. Noncombustible Penetrating Items: Noncombustible materials for penetrating items connecting maximum of three stories.
2. Penetrating Items: Materials approved by authorities having jurisdiction for penetrating items connecting maximum of two stories.
C. Fire Resistant Joints in Fire Rated Floor, Roof, and Wall Assemblies: ASTM E1966 or UL 2079 to achieve fire resistant rating as indicated on Drawings for assembly in which joint is installed.
D. Fire Resistant Joints Between Floor Slabs and Exterior Walls: ASTM E119 with 0.10 inch water gage minimum positive pressure differential to achieve fire resistant rating as indicated on Drawings for floor assembly.
E. Surface Burning Characteristics: Maximum 25/450 flame spread/smoke developed index when tested in accordance with ASTM E84.
1.8 DELIVERY, STORAGE, AND HANDLING
A. Section 01 60 00 - Product Requirements.
B. Accept materials on site in original factory packaging, labeled with manufacturer's identification.
C. Protect from weather and construction traffic, dirt, water, chemical, and mechanical damage, by storing in original packaging.
1.9 ENVIRONMENTAL REQUIREMENTS
A. Section 01 60 00 - Product Requirements.
B. Do not apply firestopping materials when temperature of substrate material and ambient air is below 60 degrees F.
HIAWATHA NATIONAL FOREST
UPEA Project No. Hangers and Supports [U28-16331] 26 05 29 - 4
C. Maintain this minimum temperature before, during, and for minimum 3 days after installation of firestopping materials.
D. Provide ventilation in areas to receive solvent cured materials.
PART 2 PRODUCTS
2.1 CONDUIT SUPPORTS
A. Manufacturers:
1. Allied Tube & Conduit Corp.
2. Electroline Manufacturing Company.
3. O-Z Gedney Co.
B. Hanger Rods: Threaded high tensile strength galvanized carbon steel with free running threads.
C. Beam Clamps: Malleable Iron, with tapered hole in base and back to accept either bolt or hanger rod. Set screw: hardened steel.
D. Conduit clamps for trapeze hangers: Galvanized steel, notched to fit trapeze with single bolt to tighten.
E. Conduit clamps - general purpose: One hole malleable iron for surface mounted conduits.
F. Cable Ties: High strength nylon temperature rated to 185 degrees F. Self locking.
2.2 FORMED STEEL CHANNEL
A. Product Description: Galvanized 12 gage thick steel. With holes 1-1/2 inches on center.
2.3 SPRING STEEL CLIPS
A. Product Description: Mounting hole and screw closure.
2.4 MECHANICAL SLEEVE SEALS
A. Product Description: Modular mechanical type, consisting of interlocking synthetic rubber links shaped to continuously fill annular space between object and sleeve, connected with bolts and pressure plates causing rubber sealing elements to expand when tightened, providing watertight seal and electrical insulation.
2.5 FIRESTOPPING
A. Product Description: Different types of products by multiple manufacturers are acceptable as required to meet specified system description and performance requirements; provide only one type for each similar application.
HIAWATHA NATIONAL FOREST
UPEA Project No. Hangers and Supports [U28-16331] 26 05 29 - 5
1. Silicone Firestopping Elastomeric Firestopping: Single or Multiple component silicone elastomeric compound and compatible silicone sealant.
2. Foam Firestopping Compounds: Single or Multiple component foam compound.
3. Formulated Firestopping Compound of Incombustible Fibers: Formulated compound mixed with incombustible non-asbestos fibers.
4. Fiber Stuffing and Sealant Firestopping: Composite of mineral or ceramic fiber stuffing insulation with silicone elastomer for smoke stopping.
5. Mechanical Firestopping Device with Fillers: Mechanical device with incombustible fillers and silicone elastomer, covered with sheet stainless steel jacket, joined with collars, penetration sealed with flanged stops.
6. Intumescent Firestopping: Intumescent putty compound which expands on exposure to surface heat gain.
7. Firestop Pillows: Formed mineral fiber pillows.
2.6 FIRESTOPPING ACCESSORIES
A. Primer: Type recommended by firestopping manufacturer for specific substrate surfaces and suitable for required fire ratings.
B. Installation Accessories: Provide clips, collars, fasteners, temporary stops or dams, and other devices required to position and retain materials in place.
C. General:
1. Furnish UL listed products or products tested by independent testing laboratory.
2. Select products with rating not less than rating of wall or floor being penetrated.
D. Non-Rated Surfaces:
1. Stamped steel, chrome plated, hinged, split ring escutcheons or floor plates or ceiling plates for covering openings in occupied areas where conduit is exposed.
2. For exterior wall openings below grade, furnish modular mechanical type seal consisting of interlocking synthetic rubber links shaped to continuously fill annular space between conduit and cored opening or water-stop type wall sleeve.
PART 3 EXECUTION
3.1 EXAMINATION
A. Verify openings are ready to receive sleeves.
B. Verify openings are ready to receive firestopping.
3.2 PREPARATION
A. Clean substrate surfaces of dirt, dust, grease, oil, loose material, or other matter affecting bond of firestopping material.
B. Remove incompatible materials affecting bond.
HIAWATHA NATIONAL FOREST
UPEA Project No. Hangers and Supports [U28-16331] 26 05 29 - 6
C. Do not drill or cut structural steel members.
3.3 INSTALLATION - HANGERS AND SUPPORTS
A. Anchors and Fasteners:
1. Concrete Structural Elements: Provide precast inserts, expansion anchors, powder actuated anchors and preset inserts.
2. Steel Structural Elements: Provide beam clamps, spring steel clips, steel ramset fasteners, and welded fasteners.
3. Concrete Surfaces: Provide expansion anchors.
4. Hollow Masonry, Plaster, and Gypsum Board Partitions: Provide toggle bolts and hollow wall fasteners.
5. Solid Masonry Walls: Provide expansion anchors.
6. Sheet Metal: Provide sheet metal screws.
7. Wood Elements: Provide wood screws.
B. Inserts:
1. Install inserts for placement in concrete forms.
2. Install inserts for suspending hangers from reinforced concrete slabs and sides of reinforced concrete beams.
3. Provide hooked rod to concrete reinforcement section for inserts carrying pipe over 4 inches.
4. Where concrete slabs form finished ceiling, locate inserts flush with slab surface.
C. Install conduit and raceway support and spacing in accordance with NEC.
D. Do not fasten supports to pipes, ducts, mechanical equipment, or conduit.
E. Install multiple conduit runs on common hangers.
F. Supports:
1. Fabricate supports from structural steel or formed steel channel. Install hexagon head bolts to present neat appearance with adequate strength and rigidity. Install spring lock washers under nuts.
2. Install surface mounted cabinets and panelboards with minimum of four anchors.
3. In wet and damp locations install steel channel supports to stand cabinets and panelboards 1 inch off wall.
4. Support vertical conduit at every floor.
3.4 INSTALLATION - FIRESTOPPING
A. Install material at fire rated construction perimeters and openings containing penetrating sleeves, piping, ductwork, conduit and other items, requiring firestopping.
B. Apply primer where recommended by manufacturer for type of firestopping material and substrate involved, and as required for compliance with required fire ratings.
C. Apply firestopping material in sufficient thickness to achieve required fire and smoke rating.
HIAWATHA NATIONAL FOREST
UPEA Project No. Hangers and Supports [U28-16331] 26 05 29 - 7
3.5 INSTALLATION - EQUIPMENT BASES AND SUPPORTS
A. Provide housekeeping pads of concrete, minimum 3-1/2 inches thick and extending 6 inches beyond supported equipment.
B. Using templates furnished with equipment, install anchor bolts, and accessories for mounting and anchoring equipment.
3.6 INSTALLATION - SLEEVES
A. Exterior watertight entries: Seal with adjustable interlocking rubber links.
B. Conduit penetrations not required to be watertight: Sleeve and fill with silicon foam.
C. Set sleeves in position in forms. Provide reinforcing around sleeves.
D. Size sleeves large enough to allow for movement due to expansion and contraction.
Provide for continuous insulation wrapping.
E. Where conduit or raceway penetrates floor, ceiling, or wall, close off space between conduit or raceway and adjacent work with fire stopping insulation and caulk airtight.
Provide close fitting metal collar or escutcheon covers at both sides of penetration.
3.7 FIELD QUALITY CONTROL
A. Inspect installed firestopping for compliance with specifications.
3.8 CLEANING
A. Clean adjacent surfaces of firestopping materials.
3.9 PROTECTION OF FINISHED WORK
A. Protect adjacent surfaces from damage by material installation.
HIAWATHA NATIONAL FOREST
UPEA Project No. Raceway and Boxes [U28-16331] 26 05 33 - 1
SECTION 26 05 33
RACEWAY AND BOXES
PART 1 GENERAL
1.1 SUMMARY
A. Section includes conduit and tubing, surface raceways, wireways, outlet boxes, pull and junction boxes, and handholes.
1.2 REFERENCES
A. American National Standards Institute:
1. ANSI C80.1 - Rigid Steel Conduit, Zinc Coated.
2. ANSI C80.3 - Specification for Electrical Metallic Tubing, Zinc Coated.
3. ANSI C80.5 - Aluminum Rigid Conduit - (ARC).
B. National Electrical Manufacturers Association:
1. NEMA 250 - Enclosures for Electrical Equipment (1000 Volts Maximum).
2. NEMA FB 1 - Fittings, Cast Metal Boxes, and Conduit Bodies for Conduit and
Cable Assemblies.
3. NEMA OS 1 - Sheet Steel Outlet Boxes, Device Boxes, Covers, and Box
Supports.
4. NEMA OS 2 - Nonmetallic Outlet Boxes, Device Boxes, Covers, and Box
Supports.
5. NEMA RN 1 - Polyvinyl Chloride (PVC) Externally Coated Galvanized Rigid
Steel Conduit and Intermediate Metal Conduit.
6. NEMA TC 2 - Electrical Polyvinyl Chloride (PVC) Tubing and Conduit.
7. NEMA TC 3 - PVC Fittings for Use with Rigid PVC Conduit and Tubing.
1.3 SYSTEM DESCRIPTION
A. Raceway and boxes located as indicated on Drawings, and at other locations required for splices, taps, wire pulling, equipment connections, and compliance with regulatory requirements. Raceway and boxes are shown in approximate locations unless dimensioned. Provide raceway to complete wiring system.
B. All new wiring shall be in raceway.
1.4 DESIGN REQUIREMENTS
A. Minimum Raceway Size: 3/4 inch unless otherwise specified.
B. Underslab conduit shall be 1 inch minimum.
1.5 SUBMITTALS
HIAWATHA NATIONAL FOREST
UPEA Project No. Raceway and Boxes [U28-16331] 26 05 33 - 2
B. Product Data: Submit for the following:
1. Flexible metal conduit.
2. Liquidtight flexible metal conduit.
3. Nonmetallic conduit.
4. Flexible nonmetallic conduit.
5. Nonmetallic tubing.
6. Raceway fittings.
7. Conduit bodies.
8. Surface raceway.
9. Wireway.
10. Pull and junction boxes.
11. Handholes.
C. Manufacturer's Installation Instructions: Submit application conditions and limitations of use stipulated by Product testing agency specified under Regulatory Requirements.
Include instructions for storage, handling, protection, examination, preparation, and installation of Product.
1.6 CLOSEOUT SUBMITTALS
A. Section 01 70 00 - Execution and Closeout Requirements.
B. Project Record Documents:
1. Record actual routing of conduits larger than 2 inch .
2. Record actual locations and mounting heights of outlet, pull, and junction boxes.
1.7 DELIVERY, STORAGE, AND HANDLING
A. Section 01 60 00 - Product Requirements.
B. Protect conduit from corrosion and entrance of debris by storing above grade. Provide appropriate covering.
C. Protect PVC conduit from sunlight.
1.8 COORDINATION
A. Section 01 30 00 - Administrative Requirements.
B. Coordinate installation of outlet boxes for equipment.
C. Coordinate mounting heights, orientation and locations of outlets mounted above counters, benches, and backsplashes.
PART 2 PRODUCTS
2.1 MANUFACTURERS
A. Carlon Electrical Products.
HIAWATHA NATIONAL FOREST
UPEA Project No. Raceway and Boxes [U28-16331] 26 05 33 - 3
B. Allied Tube.
C. Wheatland.
2.2 METAL CONDUIT
A. Rigid Steel Conduit: ANSI C80.1.
B. Rigid Aluminum Conduit: ANSI C80.5.
C. Intermediate Metal Conduit (IMC): Rigid steel.
2.3 LIQUIDTIGHT FLEXIBLE METAL CONDUIT
A. Product Description: Interlocked aluminum construction with PVC jacket.
B. Fittings: NEMA FB 1.
2.4 ELECTRICAL METALLIC TUBING (EMT)
A. Product Description: ANSI C80.3; galvanized tubing.
B. Fittings and Conduit Bodies: NEMA FB 1; steel or malleable iron, compression type.
2.5 NONMETALLIC CONDUIT
A. Product Description: NEMA TC 2; Schedule 40 or 80 PVC as indicated on the drawings.
B. Fittings and Conduit Bodies: NEMA TC 3.
C. Provide rigid steel elbows for all runs of underground conduit where PVC conduit is used.
2.6 SURFACE METAL RACEWAY
A. Product Description: Sheet metal channel with fitted cover, suitable for use as surface metal raceway.
B. Acceptable Manufacturers:
1. Thomas & Betts
2. Wiremold
C. Size: as required for circuits, conductors, and cables to be installed. DO NOT exceed fill capacity as determined by the National Electrical Code and manufacturer’s requirements.
D. Finish: manufacturer’s standard primer, suitable for field painting.
E. Fittings, Boxes, and Extension Rings: Furnish manufacturer's standard accessories; match finish on raceway.
HIAWATHA NATIONAL FOREST
UPEA Project No. Raceway and Boxes [U28-16331] 26 05 33 - 4
2.7 WIREWAY
A. Product Description: General purpose, oiltight and dust-tight or raintight type wireway as suited for location installed.
B. Knockouts: Manufacturer's standard on bottom only.
C. Size: As indicated on Drawings.
D. Cover: Hinged with full gaskets.
E. Connector: Flanged.
F. Finish: Rust inhibiting primer coating with gray enamel finish.
2.8 OUTLET BOXES
A. Sheet Metal Outlet Boxes: NEMA OS 1, galvanized steel.
1. Luminaire and Equipment Supporting Boxes: Rated for weight of equipment supported; furnish 1/2 inch male fixture studs where required.
2. Concrete Ceiling Boxes: Concrete type.
B. Nonmetallic Outlet Boxes: NEMA OS 2.
C. Cast Boxes: NEMA FB 1, Type FD, cast feralloy. Furnish gasketed cover by box manufacturer. Furnish threaded hubs.
D. Wall Plates for Finished Areas: As specified in Section 26 27 26.
E. Wall Plates for Unfinished Areas: Furnish gasketed cover.
2.9 PULL AND JUNCTION BOXES
A. Sheet Metal Boxes: NEMA OS 1, galvanized steel.
B. Hinged Enclosures: As specified in Section 26 27 16.
C. Surface Mounted Cast Metal Box: NEMA 250, Type 4; flat-flanged, surface mounted junction box:
1. Material: Galvanized cast iron.
2. Cover: Furnish with ground flange, neoprene gasket, and stainless steel cover screws.
D. Concrete composite Handholes: Die-molded:
1. Cable Entrance: Pre-cut 6 inch x 6 inch cable entrance at center bottom of each side.
2. Cover: concrete composite, weatherproof cover with nonskid finish.
HIAWATHA NATIONAL FOREST
UPEA Project No. Raceway and Boxes
[U28-16331] 26 05 33 - 5
PART 3 EXECUTION
3.1 EXAMINATION
A. Verify outlet locations and routing and termination locations of raceway prior to rough-in.
3.2 INSTALLATION
A. Ground and bond raceway and boxes.
B. Fasten raceway and box supports to structure and finishes.
C. Identify raceway and boxes.
D. Arrange raceway and boxes to maintain headroom and present neat appearance.
3.3 INSTALLATION - RACEWAY
A. Raceway routing is shown in approximate locations unless dimensioned. Route to complete wiring system.
B. Use EMT or rigid conduit above suspended ceilings and concealed in walls in interior spaces. Exposed (surface-mounted) conduit is acceptable in mechanical rooms and other unfinished spaces. Obtain approval from Owner prior to installing exposed conduit in finished spaces.
C. Use PVC-40 conduit below slab and buried outside of the building. Provide rigid steel elbows for all conduit runs using PVC conduit.
D. All underground conduits shall be installed in accordance with the National Electrical
Code. Minimum of 36” cover required. .
E. Use rigid steel conduit for all above grade exterior conduit. Obtain approval from Owner for installation/routing of all above grade exterior conduit prior to installation.
F. Arrange raceway supports to prevent misalignment during wiring installation.
G. Support raceway using coated steel or malleable iron straps, lay-in adjustable hangers, clevis hangers, and split hangers.
H. Group related raceway; support using conduit rack. Construct rack using steel channel.
Provide space on each for 25 percent additional raceways.
I. Do…