Solicitation_AG-4431-S-15-0038_Drawings.pdf

PDF 3 MB Posted

Attached to
Install Metal 50' x 20' Metal Building Addition
Solicitation number
AG-4431-S-15-0038
Issued by

About this file

Solicitation No. AG4431-S-15-0038 Drawings

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

BASE BID:

INCLUDES ALL LABOR AND MATERIALS AS REQUIRED TO

ERECT A PRE-ENGINEERED METAL BUILDING STRUCTURE

CONSISTING OF RIGID FRAME, PURLINS, AND METAL ROOF

PANELS. BASE BID ALSO INCLUDES CONCRETE SPREAD

FOOTINGS, INSULATION IN THE WALLS AND ROOF

INTERIOR LINER PANELS, CONCRETE SLAB, ELECTRICAL

SERVICE AND LIGHTING, HEATING, AND VENTILATION

EQUIPMENT.

N H

IG

H L A N D A

V E

S H

IG

H L A N D A

V E

R

IV

E R S

ID

E D

R

AIRWAYS BL

VD

SEED STORAGE BUILDING

CROPPING SYSTEMS AND NEMATOLOGY RESEARCH UNIT

AGRICULTURAL RESEARCH SERVICE

U.S. DEPARTMENT OF AGRICULTURE

JACKSON, TENNESSEE

OE

W

UE

N N

GENERAL SHEET NOTES

LEGEND

ELECTRIC HEATER SCHEDULE

DUST HOOD SCHEDULE

FAN SCHEDULE

DUST EXTRACTION ARM

INTAKE HOOD / LOUVER SCHEDULE

EXISTING PANEL PA

TYPE: SURFACE

MAIN: MCB, BOTTOM FED

LOCATION: VEHICLE SHED

SERVICE: 120/240V, 1PH, 3W RATING: 225A, 22KAIC MCB, 10KAIC BCB

SOURCE: SERVICE

MANF: SQUARE D NQ PANELBOARD FEEDER: 3#4/0

IDENTIFICATION # TRIP

LO

AD

LOAD (VA) LO

AD

TRIP # IDENTIFICATION

PH A PH B

RECEPTACLES 1 20/1 R 360 360 R 20/1 2 RECEPTACLES

RECEPTACLES 3 20/1 R 360 360 R 20/1 4 RECEPTACLES

SPARE 5 20/1 R 1080 1080 R 20/1 6 SPARE

BATTERY CHARGER 7 20/2 N 1920 7500 N 50/2 8 WELDER

SEED STO 9 N 1920 7500 N 10

LTG - SEED STORAGE 11 20/1 L 963 540 R 20/1 12 RCPT - SEED WORK TABLE

LTG - EXTERIOR 13 20/1 L 540 1080 R 20/1 14 RCPT - SEED WORK TABLE

SPARE 15 20/1 L 720 540 R 20/1 16 RCPT - SEED GP RCPT

UNIT HEATER UH-2 17 30/2 H 5000 600 H 20/1 18 SEED CLEANER

19 H 5000 600 H 20/1 20 EXHAUST FAN SEED STO

UNIT HEATERS UH-1 21 30/2 H 5000 0 - - 22 SPACE

23 H 5000 0 - - 24 SPACE

SPACE 25 - - 0 0 - - 26 SPACE

SPACE 27 - - 0 0 - - 28 SPACE

SPACE 29 - - 0 0 - - 30 SPACE

SPACE 31 - - 0 0 - - 32 SPACE

SPACE 33 - - 0 0 - - 34 SPACE

SPACE 35 - - 0 0 - - 36 SPACE

SPACE 37 - - 0 0 - - 38 SPACE

SPACE 39 - - 0 0 - - 40 SPACE

SPACE 41 - - 0 0 - - 42 SPACE

LOADS PHASE A PHASE B CONNECT MULTI DIVERS AMPS

RECEPTACLES (R)

2880 2880 5760 10K+50% 5760

LIGHTING (L)

540 1683 2223 1.25 2779

HVAC (H) LARGEST HEAT OR COOL

10600 10600 21200 1.00 21200

CONTINUOUS OR MOTOR (C), (M)

0 0 0 1.25 0

KITCHEN (K)

0 0 0 0.70 0

NONCONTINUOUS (N)

9420 9420 18840 1.00 18840

LARGEST MOTOR (M)

233 233 466 0.25 117

TOTAL 23673 24817 48490 48696 203

LIGHTING FIXTURE SCHEDULE

FIXTURE

TYPE

STYLE NUMBER MANF OR EQUAL QTY AND TYPE OF LAMP VOLTAGE MOUNTING NOTES

A NL-30A TYPE A LITHONIA IBZ

4-F32T8 4000K 80CRI 1-PRS 0.71BF

BALLAST

120V CHAIN 12FT AFF TO BOTTOM.

E NL-65A LITHONIA WLTU 2-1.5W 9.6V 120V WALL REMOTE CAPACITY. TWIN HEAD REMOTE.

X NL-63 LITHONIA LED 120V WALL CONNECT TO LIGHTING BRANCH CIRCUIT HOT.

EA XL-17 LITHONIA DSXW1 3000 LUMEN 4000K 1000mA 40W 120V WALL INTEGRAL PHOTOCELL. TYPE T2M DISTRIBUTION

T100.pdf
C100
S001
S100
A100
A101
A200
A300
M100
M200
E100
EL101
EP101

File details come from the government source that posted it. Updated .