REVISED Solicitation Pages 4, 9, 28, 29, 30, 32, 33, 34
AG-3K15-S-10-0004 4
04 OPTION ITEM
Retro Commissioning: Includes existing HVAC systems installed in previous construction phases. (Refer to Retro Commissioning specifications and drawings for detailed scope of work).
Phase 1-Power Plant equipment includes but not limited to boilers, chillers, cooling towers, pumps, and controls. Phase 2-Pilot Plant HVAC equipment. Phase 3-7-Chemical Wing laboratories, HVAC equipment.
ALL FOR THE LUMP SUM OF.............................. $
05 OPTION ITEM
Retro Commissioning and Testing and Balancing of existing ,Power Plant, Pilot Plant, and Chemical Wing HVAC Systems - Phases 1 through 7 utilizing drawing volumes 3, 4, and 6 (volume 5 shall be deleted). The effort will include testing and balancing the existing HVAC equipment, installation of variable geometry dampers on the existing exhaust fan stacks, reprogramming existing HVAC equipment for reduced airflows, and retro commissioning."
ALL FOR THE LUMP SUM OF.............................. $___________________
B.3 PERFORMANCE TIME
Five Hundred Forty (540) calendar days after Notice to Proceed (NTP) is issued.
1st NTP will be for submittals and staging, 2nd NTP is for construction and closeout and will be 420 calendar days.
AG-3K15-S-10-0004 9
SECTION F - DELIVERIES OR PERFORMANCE
F.1 COMMENCEMENT, PROSECUTION, AND COMPLETION OF WORK
(FAR 52.211-10) (APR 1984)
The Contractor shall be required to (a) commence work under this contract within 14 calendar days after the date the Contractor receives the notice to proceed (NTP), (b) prosecute the work diligently, and (c) complete the entire work, including any options, ready for use not later than 540 calendar days after receipt of NTP. There will be 2 NTPs, the 1st NTP is for submittals and staging, the 2nd NTP is for construction (420 calendar days). Any option items that will be exercised will be done within 60 calendar days after the effective date of the NTP. The time stated for completion shall include final cleanup of the premises.
F.2 LIQUIDATED DAMAGES - CONSTRUCTION
(FAR 52.211-12) (SEPT 2000)
(a) If the Contractor fails to complete the work within the time specified in the contract, the Contractor shall pay liquidated damages to the Government in the amount of $1,008.00 for each calendar day of delay until the work is completed or accepted.
(b) If the Government terminates the Contractor's right to proceed, liquidated damages will continue to accrue until the work is completed. These liquidated damages are in addition to excess costs of repurchase under the Termination clause.
F.3 TIME EXTENSIONS
(FAR 52.211-13) (SEPT 2000)
Time extensions for contract changes will depend upon the extent, if any, by which the changes cause delay in the completion of the various elements of construction. The change order granting the time extension may provide that the contract completion date will be extended only for those specific elements related to the changed work and that the remaining contract completion dates for all other portions of the work will not be altered. The change order also may provide an equitable readjustment of liquidated damages under the new completion schedule.
F.4 PERFORMANCE OF WORK BY THE CONTRACTOR
(FAR 52.236-1) (APR 1984)
The Contractor shall perform on the site, and with its own organization, work equivalent to at least 20 percent of the total amount of work to be performed under the contract. This percentage may be reduced by a supplemental agreement to this contract if, during performing the work, the Contractor requests a reduction and the Contracting Officer determines that the reduction would be to the advantage of the Government.
AG-3K15-S-10-0004 28
H.24 SAMPLES AND CERTIFICATES
(AGAR 452.236-76) (FEB 1988)
When required by the specifications or the Contracting Officer, samples, certificates, and test data shall be submitted after award of the contract, prepaid, in time for proper action by the Contracting Officer or his/her designated representative. Certificates and test data shall be submitted in triplicate to show compliance with materials and construction specified in the contract performance requirements.
Samples shall be submitted in duplicate by the Contractor, except as otherwise specified, to show compliance with the contract requirements. Materials or equipment for which samples, certifications or test data are required shall not be used in the work until approved in writing by the Contracting Officer.
H.25 KEY PERSONNEL
(AGAR 452.237-74) (FEB 1988)
(a) The contractor shall assign to this contract the following key personnel:
Title(s): Name(s):
Project Manager Site Superintendent Quality Control Manager Health & Safety Inspector
(b) During the first ninety (90) days of performance, the contractor shall make no substitutions of key personnel unless the substitution is necessitated by illness, death, or termination of employment. The contractor shall notify the Contracting Officer within 15 calendar days after the occurrence of any of these events and provide the information required by paragraph (c) below. After the initial 90-period, the contractor shall submit the information required by paragraph (c) to the Contracting Officer at least 15 calendar days prior to making any permanent substitutions.
(c) The contractor shall provide a detailed explanation of the circumstances necessitating the proposed substitutions, complete resumes for the proposed substitutes, and any additional information requested by the Contracting Officer. Proposed substitutes should have comparable qualifications to those of the person(s) being replaced. The Contracting Officer will notify the contractor within 15 calendar days after receipt of all required information of the decision on substitutions. The contract will be modified to reflect any approved changes of key personnel.
H.26 CONSTRUCTION PROGRESS AND PAYMENT SCHEDULE
(a) Within 14 calendar days after the date of receipt of the Notice to proceed, the contractor shall prepare and submit to the Contracting Officer for approval, the original copy of ARS Form 371, Construction Progress and Payment Schedule. This form will serve as a
AG-3K15-S-10-0004 29
Schedule of Estimates, Progress Schedule, and when used with ARS Form 372, it will be the basis for Requests for Partial Payment. The values employed in making the schedule will be used only for determining partial payments and will not be considered as establishing a basis for additions to or deductions from the contract. A copy of the approved schedule will be returned to the contractor.
(b) Samples of both ARS Forms 371 and 372 are available upon request. A supply of these forms together with instruction for completion of ARS Form 371 will be mailed to the contractor with the Notice of Award.
(c) ARS Form 371 is required even though progress or partial payments are not requested.
(d) The need by an offeror for partial or progress payments, when authorized in the payment provisions of this invitation for bids, will not be treated as a handicap in making the award.
H.27 WAGE DETERMINATION
In the performance under this Contract, the Contractor shall comply with the requirements of the applicable U.S. Department of Labor General Wage Decision for the location, including all modifications. See Section J for the applicable Wage Decision.
H.28 UTILITIES OUTAGE
Any interruption of utilities or services that would interfere with the operation of the facility will be permitted only with prior written approval from the Contracting Officer. Any utilities or service connections made at other than normal working hours will be at no additional cost to the Government. As per specification section 01 11 00, paragraph 1.10.1, permission to make such an interruption shall be requested in writing to the Contracting Officer, at least Fifteen (15) calendar days prior to the day of interruption. Failure by the Contractor to comply with this requirement will cause the Contractor to be subject to liability for actual damages.
H.29 COOPERATION WITH OTHER CONTRACTORS
During the period of construction for the work covered by this contract, other contractors performing work for the Government may be operating concurrently at the site. To minimize interference and delay to the construction progress of all concerned, all contractors shall cooperate with each other and coordinate their construction operations to the fullest extent. As far as practicable, all contractors performing work for the Government at the site shall have equal rights to the use of all referenced facilities. In a dispute regarding the use of such facilities, the matter shall be referred to the Contracting Officer.
H.30 SUBMITTALS AND SHOP DRAWINGS
(a) The Contractor shall submit for approval, shop drawings of all manufactured products required in the construction for which such drawings are hereinafter required. When approved, AG-3K15-S-10-0004 30 one set will be retained; one set forwarded to the Government representative on the job and two sets forwarded to the Contractor. When changes or corrections are necessary, two sets will be returned to the Contractor with such corrections noted thereon, and he shall resubmit revised prints.
(b) Shop drawings shall be marked with the contract number and Work Order Number, project description, name of the Contractor, and accompanied by a letter of transmittal. If the shop drawings show variations from the contract requirements because of standard shop practice or other reason, the Contractor shall make specific mention of such variations in his letter of transmittal.
(c) Approval of shop drawings will be general and will not relieve the Contractor from the responsibility of furnishing material and work required by the contract.
(d) Shop drawings shall be submitted for approval in ample time to permit checking of the drawings, allow the Contractor to make any corrections and resubmit drawings prior to the time construction is started on work covered by an drawings.
(e) Non-approval of equipment due to failure to meet specifications, or non-approval of the Contractor’s drawings due to submission of incomplete or incorrect information cannot be considered as a basis for extension of time for completion of the contract.
(f) The quantity of shop drawings required are subject to change. This will occur only when the Government is under contract with an A-E firm to approve shop drawings. In this respect, A-E will coordinate final quantity required between all interested parties.
H.31 LIST OF MATERIALS
(a) The Contractor shall submit for approval a complete list, in quadruplicate, of brands, type, and make of various equipment and materials proposed to be used. If the Contractor fails to submit such a list, or names of equipment which does not comply with the specifications, or if the manufacturers named are unsatisfactory, the Government reserves the right to reject same and to select satisfactory substitute materials. This selection shall be final and finding upon the Contractor, and the work shall be installed on this basis without change in contract price.
(b) In order to properly identify and to prove compliance with the requirements of the specifications, the Contractor shall give the following data for each product included in the list of materials.
Section heading of the specifications under which material is specified.
Manufacturer’s name and address.
Grade, type, trade or catalog number.
Size, capacity, and other pertinent data.
(c) All materials, fixtures, and equipment furnished and installed under this contract shall be new and of the best quality; shall be standard cataloged products or reputable manufacturers products or of special manufacture, satisfying completely the contract requirements.
AG-3K15-S-10-0004 32
PART II - CONTRACT CLAUSES
SECTION I - CONTRACT CLAUSES
I.1 CLAUSES INCORPORATED BY REFERENCE
(FAR 52.252-2) (FEB 1998)
This contract incorporates the following clauses by reference, with the same force and effect as if they were given in full text. Upon request, the Contracting Officer will make their full text available. Also, the full text of a clause may be accessed electronically at these addresses:
Federal Acquisition Regulations: http://www.arnet.gov/far/ Agriculture Acquisition Regulations: www.usda.gov/procurement/policy/agar.html
I. FEDERAL ACQUISITION REGULATION (48 CFR CHAPTER 1) CLAUSES
CLAUSE
NUMBER DATE TITLE
52.202-1 JUL 2004 DEFINITIONS
52.203-3 APR 1984 GRATUITIES
52.203-5 APR 1984 COVENANT AGAINST CONTINGENT FEES
52.203-7 JUL 1995 ANTI-KICKBACK PROCEDURES
52.203-8 JAN 1997 CANCELLATION, RESCISSION, AND
RECOVERY OF FUNDS FOR ILLEGAL OR
IMPROPER ACTIVITY
52.203-10 JAN 1997 PRICE OR FEE ADJUSTMENT FOR ILLEGAL OR
IMPROPER ACTIVITY
52.203-12 SEP 2007 LIMITATION ON PAYMENTS TO INFLUENCE
CERTAIN FEDERAL TRANSACTIONS
52.203-13 DEC 2008 CONTRACTOR CODE OF BUSINESS ETHICS
AND CONDUCT
52.203-15 MAR 2009 WHISTLEBLOWER PROTECTIONS UNDER THE
AMERICAN RECOVERY AND REINVESTMENT
ACT OF 2009
52.204-4 AUG 2000 PRINTED OR COPIED DOUBLE-SIDED ON
RECYCLED PAPER
52.204-7 APR 2008 CENTRAL CONTRACTORS REGISTRATION
52.204-9 SEP 2007 PERSONAL IDENTITY VERIFICATION OF
CONTRACTOR PERSONNEL
52.204-11 MAR 2009 AMERICAN RECOVERY AND REINVESTMENT
ACT REPORTING REQUIREMENTS
52.209-6 SEP 2006 PROTECTING THE GOVERNMENT'S INTEREST
WHEN SUBCONTRACTING WITH
CONTRACTORS DEBARRED, SUSPENDED, OR
PROPOSED FOR DEBARMENT
52.215-2, ALT I MAR 2009 AUDIT AND RECORDS - NEGOTIATIONS
52.215-10 OCT 1997 PRICE REDUCTION FOR DEFECTIVE COST OR
PRICING DATA
AG-3K15-S-10-0004 33
CLAUSE
NUMBER DATE TITLE
52.215-11 OCT 1997 PRICE REDUCTION FOR DEFECTIVE COST OR
PRICING DATA-MODIFICATIONS
52.215-12 OCT 1997 SUBCONTRACT COST OR PRICING DATA
52.215-13 OCT 1997 SUBCONTRACTOR COST OR PRICING DATA –
MODIFICATIONS
52.215-15 OCT 2004 PENSION ADJUSTMENTS AND ASSET
REVISIONS
52.215-17 OCT 1997 WAIVER OF FACILITIES CAPITAL COST OF
MONEY
52.215-21 OCT 1997 REQUIREMENTS FOR COST OR PRICING DATA
OR INFORMATION OTHER THAN COST OR
PRICING-MODIFICATIONS
52.219-8 MAY 2004 UTILIZATION OF SMALL BUSINESS CONCERNS
52.219-9 APR 2008 SMALL BUSINESS SUBCONTRACTING PLAN
52.219-25 APR 2008 SMALL DISADVANTAGED BUSINESS
PARTICIPATION PROGRAM – DISADVANTAGED
STATUS AND REPORTING
52.222-3 JUN 2003 CONVICT LABOR
52.222-4 JUL 2005 CONTRACT WORK HOURS AND SAFETY
STANDARDS ACT – OVERTIME
COMPENSATION
52.222-6 JUL 2005 DAVIS-BACON ACT
52.222-7 FEB 1988 WITHHOLDING OF FUNDS
52.222-8 JAN 2010 (Dev.) PAYROLLS AND BASIC RECORDS
52.222-9 JUL 2005 APPRENTICES AND TRAINEES
52.222-10 FEB 1988 COMPLIANCE WITH COPELAND ACT
REQUIREMENTS
52.222-11 JUL 2005 SUBCONTRACTS (LABOR STANDARDS)
52.222-12 FEB 1988 CONTRACT TERMINATION - DEBARMENT
52.222-13 FEB 1988 COMPLIANCE WITH DAVIS-BACON AND
RELATED ACT REGULATIONS
52.222-14 FEB 1988 DISPUTES CONCERNING LABOR STANDARDS
52.222-15 FEB 1988 CERTIFICATION OF ELIGIBILITY
52.222-21 FEB 1999 PROHIBITION OF SEGREGATED FACILITIES
52.222-26 MAR 2007 EQUAL OPPORTUNITY
52.222-27 FEB 1999 AFFIRMATIVE ACTION COMPLIANCE
REQUIREMENTS FOR CONSTRUCTION
52.222-35 SEP 2006 EQUAL OPPORTUNITY FOR SPECIAL
DISABLED VETERANS, VETERANS OF THE
VIETNAM ERA, AND OTHER ELIGIBLE
VETERANS
52.222-36 JUN 1998 AFFIRMATIVE ACTION FOR WORKERS WITH
DISABILITIES
52.222-37 SEP 2006 EMPLOYMENT REPORTS ON SPECIAL
DISABLED VETERANS, VETERANS OF THE
VIETNAM ERA, AND OTHER ELIGIBLE
VETERANS
AG-3K15-S-10-0004 34
CLAUSE
NUMBER DATE TITLE
52.222-50 FEB 2009 COMBATING TRAFFICKING IN PERSONS
52.222-54 JAN 2009 EMPLOYMENT ELIGIBILITY VERIFICATION
52.223-2 DEC 2007 AFFIRMATIVE PROCUREMENT OF BIOBASED
PRODUCTS UNDER SERVICE AND CONSTRUCTION
CONTRACTS
52.223-3 JAN 1997 HAZARDOUS MATERIAL IDENTIFICATION AND
MATERIAL SAFETY DATA – ALT I (JULY 1995)
52.223-5 AUG 2003 POLLUTION PREVENTION AND RIGHT-TO-
KNOW INFORMATION
52.223-6 MAY 2001 DRUG-FREE WORKPLACE
52.223-14 AUG 2003 TOXIC CHEMICAL RELEASE REPORTING
52.223-15 DEC 2007 ENERGY EFFICICIENCY IN ENERGY-CONSUMING PRODUCTS
52.225-13 JUN 2008 RESTRICTIONS ON CERTAIN FOREIGN
PURCHASES
52.227-1 DEC 2007 AUTHORIZATION AND CONSENT
52.227-2 DEC 2007 NOTICE AND ASSISTANCE REGARDING
PATENT AND COPYRIGHT INFRINGEMENT
52.227-4 DEC 2007 PATENT INDEMNITY – CONSTRUCTION
CONTRACTS
52.228-5 JAN 1997 INSURANCE—WORK ON A GOVERNMENT INSTALLATION
52.228-2 OCT 1997 ADDITIONAL BOND SECURITY
52.228-11 SEP 2009 PLEDGE OF ASSETS
52.228-12 OCT 1995 PROSPECTIVE SUBCONTRACTOR REQUESTS
FOR BONDS
52.229-3 APR 2003 FEDERAL, STATE, AND LOCAL TAXES
52.232-17 OCT 2008 INTEREST
52.232-23 JAN 1986 ASSIGNMENT OF CLAIMS
52.232-27 OCT 2008 PROMPT PAYMENT FOR CONSTRUCTION
CONTRACTS
52.233-1 JUL 2002 DISPUTES
52.233-3 AUG 1996 PROTEST AFTER AWARD
52.233-4 OCT 2004 APPLICABLE LAW FOR BREACH OF CONTRACT
CLAIM
52.242-13 JUL 1995 BANKRUPTCY
52.243-4 JUN 2007 CHANGES
52.244-6 DEC 2009 SUBCONTRACTS FOR COMMERCIAL ITEMS
52.246-21 MAR 1994 WARRANTY OF CONSTRUCTION
52.248-3 SEP 2006 VALUE ENGINEERING – CONSTRUCTION
52.249-2 MAY 2004 TERMINATION FOR CONVENIENCE OF THE
GOVERNMENT (FIXED PRICE) (ALTERNATE I -
SEP 1996)
52.249-10 APR 1984 DEFAULT (FIXED-PRICE CONSTRUCTION)
52.253-1 JAN 1991 COMPUTER GENERATED FORMS
Amendment No. 01 to the referenced Solicitation provides the following:
1. The date for receipt of all bids has NOT been extended. It remains MARCH 10, 2010.
2. 2 p.m., local time. Bids are to be mailed or hand-carried to the following address:
U.S. Department of Agriculture Facilities Division, FCB 5601 Sunnyside Avenue, MAIL STOP 5124 Beltsville, Maryland 20705-5124
3. List of Attachments:
Questions Received from Industry (Attachment A) Changes to Specifications (Attachment B) Changes to Drawings (Attachment C) Added Drawings (Attachment D) Pre Bid Presentation (Attachment E)
ATTACHMENT “A”
Questions Received from Industry
The following questions and answers are provided for clarification.
1. Reference: Specification Section 22 00 00 page 16 Para 2.1.6
Question: Provide acid-resistant DWV pipe, fittings, and couplings of the mechanical, bell & spigot, or fusion type joints. Material for buried piping and aboveground piping shall be ASTM A 518M, silicon-iron composition. (Can below grade and above grade acid resistant piping be plastic fusion weld – such as by Enfield, Orion, or George Fisher?)
Response: Provide as specified.
2. Reference: Specification Section 22 00 00 page 16 Para 2.1.6
Question: ASTM C 1053, borosilicate glass pipe and fitting to be provided for aboveground piping, except vent piping through and above roofs shall be silicon-iron composition. (Is above ground piping to be borosilicate glass or silicon-iron as stated in sentence before or can it be plastic fusion type?) Provide cleanouts and drains as specified for DWV piping, except material shall be silicon-iron composition. This section is not clear as to what is to be priced and provided.
Response: All above ground piping is to be borosilicate glass, except last four foot section of vent through the roof piping which shall be silicon-iron composition piping.
Cleanouts and drains are to be provided and installed per Part 2 (DWV Piping) of Section
22 00 00, except piping material shall be silicon-iron composition.
3. Reference: Mechanical dwgs
Question: I see boilers B-3 and B-4. Are there a total of two boilers on the upgrade? (gas and No. 2 oil, 150#, 5 sq. ft. , 30-PPM).
Response: One boiler shall be installed in this contract, B-4.
4. Reference: Drawing Sheet M05.01
Question: I am trying to verify the gas pressure to the main fuel train and pilot. I see a gas train schematic on drawing M05.01, but I may be missing the gas pressure.
Response: Gas pressure within Power Plant feeding existing boilers is 10.5 psi.
5. Reference: Mechanical dwgs
Question: What is the steam operating pressure?
Response: Steam operating pressure is 862 kPa, per Phase 9A and 9B - M04.02.
6. Reference: Specifications
Question: In the boiler spec is a reference to pumps and DA (paragraph 2.4). The drawings indicate they will reuse the existing DA. Which one is correct?
Response: Deaerator and associated pumps have been installed in a prior contract and will be reused. Refer to Attachment "B".
7. Reference: Boiler Specifications
Question: I do not know if you are in communication with the consulting engineer, but they have referenced 3 Mil specs that have been obsolete for years (MIL-B-18897, MIL-B-17452, Mil-B-18796). I would normally say take exception to these Mil specs.
Response: Delete reference to "MIL-B-18897F" and replaced with "Federal Specification F-B-
2910". Delete reference to "MIL-B-17452" and replaced with "Federal Specification F- B-2903". Delete reference to "Mil-B-18796" and replaced with "Federal Specification F- B-2910".
8. Reference: Boiler Specifications
Question: Your service group should review Part 3 (Execution) of the boiler spec. There are tests that someone will have to run after the start-up is completed. I see an ASME PTC.4 short form efficiency test. I do not know your group is capable of conducting this testing, or whether the contractor will handle that part.
Response: All tests within Part 3 are to be provided by the contractor.
9. Reference: General
Question: Is it acceptable to submit a “Teaming Agreement” in lieu of a Joint Venture Agreement for two firms submitting the proposal together?
Response: A teaming agreement is acceptable.
10. Reference: General
Question: Would the team members have to register as one entity in the central contractor registry (www.ccr.gov) even if not forming a Joint Venture for the submission?
Response: No. Only one company needs to be CCR. Please provide copy of the signed agreement with your proposal. As a note the contract will be awarded to one company.
11. Reference: General
Question: According to the instructions on page 64 of the Solicitation, we are to submit Three (3) originally signed copies of the signed offer (Sections A through K). This instruction is not clear. Some of the items/documents in Sections A through K do not require signatures or action. Do each of the following documents need to be submitted separately from the Technical and Cost/Business Proposals? Do we need to submit three (3) original bid bonds?
Response: No. Only one company needs to be CCR. Please provide copy of the signed agreement with your proposal. As a note the contract will be awarded to one company.
12. Reference: General
Question: Do we need to submit SF-1442.
Response: Yes, three original signatures.
13. Reference: General
Question: Do we need to submit Section B – Supplies or Services and Price/Cost.
Response: No.
14. Reference: General
Question: Do we need to submit Section K – Representations, Certifications, and other statements of offerors.
15. Reference: General
Question: Do we need to submit Key Personnel, Section H.25.
16. Reference: General
Question: Do we need to submit Bid Bond.
17. Reference: General
Question: Do we need to submit Disclosure of Lobbying Activities (SF-LLL).
18. Reference: General
Question: Do the five (5) projects submitted have to be complete to receive a positive evaluation?
19. Reference: General
Question: The Solicitation states that Federal Government experience is preferred (page 64). Will a firm receive a negative evaluation if neither of the five projects submitted were performed for the Federal Government?
Response: No. It is preferred but not mandatory.
20. Reference: General
Question: Do these forms have to be submitted in sealed envelopes?
21. Reference: General
Question: Are there any SDB participation goals established for this solicitation or are you looking for each firm to propose targets/goals that they believe are achievable?
Response: We are looking for each company to propose targets/goals that are achievable.
22. Reference: General
Question: What counts as one page in the 50 page limit – a single side of a page or both sides?
Response: A single side of 8 ½ x 11 of a piece of paper counts as one page.
23. Reference: Bid Form
Question: Clarify that Option #1, as indicated on Drawing A00.06 and A01.06, is actually Item #3 on the Bid Form (Section B, Page 3).
Response: Option #1, as indicated on Drawing A00.06 and A01.06, is Item #3 on the Bid Form (Section B, Page 3).
24. Reference: Re-Roofing
Question: Clarify the extent of re-roofing required under this option. From keyed Demolition Notes #9 and 18 on Drawing A00.06, it does not appear that the entire roof area between Column Lines 1 and 11 is to be re-roofed. This is contrary to the total re-roof indicated on Dwg. A01.06. Likewise, we do not locate Keyed Note #18 on Drawing A01.06.
Response: Option #1: Re-roofing extends between Col. Line#1 thru Col. Line#11. In demolition dwg. A00.06, note #9 & #18 defines the existing roofing to be removed and in dwg.
A1.06, note #18 explains new roofing materials shall be laid where the existing roofing have been removed.
25. Reference: Re-Pointing
Question: Clarify the intent of Option 1 – General Note “C” on Drawing A00.06 and A01.06. Is it intended that the entire façade between Column Lines 1 and 11 be re-pointed? There are no elevations to indicate this.
Response: Refer to Dwg. A04.01, keyed Note #17 and see Attic elevation portion on both North and
South Elevation showing symbol with 17.
26. Reference: Re-Pointing
Question: Clarify that ALL work designated within the dashed line indicated as Option 1 on Drawing A01.06 is to be priced in the Roofing Option, and not in the Base Bid.
Response: Correct
ATTACHMENT “B”
Changes to Specifications
1. Section 01 11 00 Summary of Work
1.1 Paragraph 1.4.1: Add the following to the end of the paragraph:
"Retro Commissioning and Reduced Airflows:
Retro Commissioning and Testing and Balancing of existing ,Power Plant, Pilot Plant, and Chemical Wing HVAC Systems - Phases 1 through 7 utilizing drawing volumes 3, 4, and 6 (volume 5 shall be deleted). The effort will include testing and balancing the existing HVAC equipment, installation of variable geometry dampers on the existing exhaust fan stacks, reprogramming existing HVAC equipment for reduced airflows, and retro commissioning."
1.2 Paragraph 1.4.1: Delete the following paragraph in its entirety:
"Schedule from Contractor's Notice to Proceed date:"
1.3 Paragraph 1.4.3: Add the following in its entirety:
"Retro Commissioning and Retro Commissioning/Reduced Airflow Schedule:
Retro Commissioning and Retro Commissioning/Reduced Airflow of Phase 1 - 7 of existing HVAC Systems (Bid Option 2 or 3) shall consist of the following sequence:
A. 60 - 90 days from NTP: Submittals to be provided and reviewed by A/E
(Retro Cx Plan, TAB Plan, EVAV-3, and Variable Geometry Dampers).
B. 91 - 135 days from NTP: Retro Cx Preview Phase to select labs and equipment to Retro Cx (see section 23 08 00.00 10 for quantities), TAB of HVAC equipment, DDC Cx Checkout, and VGD and EVAV-3 installation to be completed.
C. 121 - 150 days from NTP: Gov't repairs from Pre Retro Cx Phase findings.
D. 151 - 210 days from NTP: Retro Cx Specialist to complete and internally verify Retro Cx of Phase 1 through 7.
E. 210 - 240 days from NTP: Contracting Officer, User, and Design representatives shall witness the functional performance checklists.
F. After successful completion, witness, and approval of Phase 8, 9A, and 9B functional performance Cx checklists, spot check 25% of Phase 2 initial Retro Cx settings.
The first checks shall be performed within 6 months of Contract Notice to Proceed to ensure the existing HVAC systems are operating per the sequence of operation to establish a baseline. The Contracting Officer, User, and Design representatives shall select and witness the first checks after completion and internal verification by the contractor's retro commissioning specialist. The second checks shall be performed after successful completion and approval of Phase 8, 9A, and 9B Commissioning functional performance checklists to ensure the existing baseline settings and sequence of operations has not changed. The Contracting Officer, User, and Design representatives shall select and witness the second checks. The work described in this Section shall begin only after all work required in related Sections, including Section 23 09 54.00 20 DIRECT DIGITAL
CONTROL SYSTEMS/COMMISSIONING OF EXISTING DDC
SYSTEMS and Section 23 08 00.00.20 HVAC TESTING/ ADJUSTING/ BALANCING, has been successfully completed, and all reports listed in Section 1.1 have been submitted and approved."
1.4 Add the following in its entirety:
"Paragraph 1.13 Preconstruction and Hazardous Material Coordination Meeting Schedule
The preconstruction meeting shall be conducted from 9:30 AM to 12:00 PM, and the Hazard Material Coordination Meeting shall be conducted from 1:00 PM to 3:00 PM on the same day."
2. Section 23 08 00.00 10 Retro Commissioning of Existing HVAC Systems
2.1 PART 1 OVERVIEW: Insert the following after "...new sequences of operation."
"The contractor shall Test and Balance (TAB), DDC Checkout, and retro commission 100% of Phase 1 through 7 HVAC equipment and functional performance checklists. The contractor shall coordinate with the users to ensure a maximum 4 hour HVAC equipment downtime, minimal inconvenience, and a two week look ahead schedule for work within each room is provided. All TAB of HVAC Equipment, DDC Checkout, and functional performance checklists of Phases 1 through 7 shall be completed and verified by the retro commissioning specialist before the Contracting Officer, User, and Design representatives witness the functional performance test checklists. The Contracting Officer shall select and witness the percentages of equipment and/or systems indicated on the functional performance test checklists, and if no percentage is given, then 100% shall be selected and witnessed. Refer to Section 01 11 00 Paragraph 1.4.3 for Retro Commissioning Schedule."
2.2 Paragraph 2.3.1: Delete the second sentence and replace with the following:
"Bid Option No. 2: There is no intent to redesign any portion of the HVAC mechanical systems, except for some minor modifications to the sequences of operation, as identified in the control drawings.
Bid Option No. 3: There is no intent to redesign any portion of Phase 1 and 2 HVAC mechanical systems, except for some minor modifications to the sequences of operation, as identified in the control drawings. Phase 3 through 7 HVAC mechanical systems shall be redesigned to provide reduced airflows in Laboratories and Laboratory support areas."
2.3 Paragraph 2.4;
SD-01 Shop Drawings;:
1). Delete the following from the first sentence: "no later than 28 days"
SD-02 Product Data:
1). Delete the reference in its entirety:" Pre-Functional Performance Test (PFPT) Checklists; G"
2). Delete the following from the first sentence: "no later than 28 days".
SD-04 Certificates:
1). Retro-Commissioning Firm: Delete the following from the first sentence:
"no later than 21 days".
2). Retro-Commissioning Agent: Delete the following from the first sentence:
"no later than 21 days".
SD-05 Retro Commissioning Plan:
1). Delete the following from the first sentence: "within 60 days".
2). Delete the following from the third sentence in the second paragraph "90 days following receipt of notice to proceed" and replace with "two days after deficiency detected." -+
2.4 Paragraph 2.6: Add the following to the end of the second paragraph:
1). "Refer to Section 01 11 00 Paragraph 1.4.3 for Retro Commissioning
Schedule."
2.5 Paragraph 2.7.1.2:
1). Delete the following from the first sentence: "no later than 60 days"
3. Section 23 52 49.00 20 Steam Boilers and Equipment
3.1 Paragraph 2.4:
1). Delete "Paragraph 2.4.2 Deaerator" in its entirety.
3.2 Section 23 52 49.00 20:
1). Delete all references to "MIL-B-18897F" and replaced with "Federal
Specification F-B-2910". Delete all references to "MIL-B-17452" and replaced with "Federal Specification F-B-2903". Delete all references to "MIL-B-18796" and replaced with "Federal Specification F-B-2910".
ATTACHMENT “C”
Changes to Drawings
VOLUME 1
General Drawings:
1. Drawing Sheet T1.01:
1.1. At the end of Bid Option 2). add the following:
1.1.1 "utilizing drawing volumes 3, 4, and 5".
1.2 After "Bid Options:" insert the following in its entirety:
1.2.1 "3). Retro Commissioning and Testing and Balancing of existing Power Plant, Pilot Plant, and Chemical Wing HVAC Systems - Phases 1 through 7 utilizing drawing volumes 3, 4, and 6 (volume 5 shall be deleted). Chemical Wing HVAC Systems shall incorporate reduced airflows in laboratories and laboratory support areas utilizing variable geometry dampers."
2. Drawing Sheet T01.03:
2.1 Add "Volume 6" to the Index of Drawings. Refer to Attachment D.
VOLUME 2
General Drawings:
1. Drawing Sheet T1.01:
1.1. At the end of Bid Option 2). add the following:
1.1.1 "utilizing drawing volumes 3, 4, and 5".
1.2 After "Bid Options:" insert the following in its entirety:
1.2.1 "3). Retro Commissioning and Testing and Balancing of existing Power Plant, Pilot Plant, and Chemical Wing HVAC Systems - Phases 1 through 7 utilizing drawing volumes 3, 4, and 6 (volume 5 shall be deleted). Chemical Wing HVAC Systems shall incorporate reduced airflows in laboratories and laboratory support areas utilizing variable geometry dampers."
2. Drawing Sheet T01.03:
2.1 Add "Volume 6" to the Index of Drawings. Refer to Attachment D.
3. Drawing sheet E01.01:
3.1 Provide branch circuits for light fixtures shown on the drawing as follows:
3.1.1 All night light fixtures, exit fixtures and emergency battery packs – panel
HBA, circuit 41;
3.1.2 Light fixtures in Locker Room 0032 and Corridor 0200A, B, C - panel HBA, circuit 35; 120 V light fixtures to panel LBS, circuit 16, as shown;
3.1.3 Light fixtures in Offices 0034 and 0202 - panel HBA, circuit 33;
3.1.4 Light fixtures in Laboratory 0201 - panel HBA, circuit 31;
3.1.5 Light fixtures in Laboratory 0205 - panel HBA, circuit 37;
3.1.6 Light fixtures in Laboratory 0207- panel HBA, circuit 39;
3.1.7 Light fixtures in mechanical Room 0204 - panel HBA, circuit 32.
3.2 Connect additional light fixtures as night lights as follows:
3.2.1 Every other light fixture in corridors 0200A, B and C starting with the central fixture in corridor 0200A;
3.2.2 One light fixture in Office 0034;
3.2.3 One light fixture in Office 0202;
3.2.4 One light fixture in Mechanical Room 0204.
3.3 Provide occupancy sensors in addition to those shown on drawing as follows:
3.3.1 Two in Men Toilet 0032;
3.3.2 One in Locker Room 0032.1.
4. Drawing sheet E01.02:
4.1 Provide branch circuits for light fixtures shown on the drawing as follows:
4.1.1 All night light fixtures, exit fixtures and emergency battery packs – panel H1A, circuit 29;
4.1.2 Light fixtures in Offices 1202 and 1204 - panel H1A, circuit 31;
4.1.3 Light fixtures in Laboratory 1201 - panel H1A, circuit 33;
4.1.4 Light fixtures in Laboratory 1203 - panel H1A, circuit 35;
4.1.5 Light fixtures in Laboratory 1205 - panel H1A, circuit 28;
4.1.6 Light fixtures in Laboratory 1207- panel H1A, circuit 41;
4.1.7 Light fixtures in Laboratory 1206- panel H1A, circuit 37;
4.1.8 Light fixtures in Laboratory 1208- panel H1A, circuit 39;
4.1.9 NOTE: Connect 120 V light fixtures in Room 1200D.1 to panel L1R12, circuit 13, as shown.
4.2 Connect additional light fixtures as night lights as follows:
4.2.1 Every other light fixture in corridors 1200B and C;
4.2.2 One light fixture in Office 1202;
4.2.3 One light fixture in Office 1204.
4.3 Provide occupancy sensors in addition to those shown on drawing as follows:
4.3.1 One each in rooms 1201, 1203, 1205, 1207, 1200D.1, 1206 and 1208.
5. Drawing sheet E01.03:
5.1 Provide branch circuits for light fixtures shown on the drawing as follows:
5.1.1 All night light fixtures, exit fixtures and emergency battery packs – panel H2A, circuit 7;
5.1.2 Light fixtures in Corridor and Offices 2202, 2204 and 2206 – panel H2A, circuit 9;
5.1.3 Light fixtures in center of Laboratories 2201 and 2203 - panel H2A, circuit 9;
5.1.4 Light fixtures around edges of Laboratories 2201 and 2203 - panel H2A, circuit 23;
5.1.5 Light fixtures in center of Laboratories 2205 and 2207 - panel H2A, circuit
19;
5.1.6 Light fixtures around edges of Laboratories 2205 and 2207 - panel H2A, circuit 21;
5.1.7 Light fixtures in Laboratory 2208 - panel H2A, circuit 17.
5.2 Connect additional light fixtures as night lights as follows:
5.2.1 One light fixture in Office 2206;
5.2.2 One additional light fixture in Office 2208.
5.3 Provide additional light controls in addition to those shown on drawing as follows:
5.3.1 Two occupancy sensors in Laboratory 2208.
5.3.2 Two 3-way HOA light switches in grouped Laboratories 2201 and 2203, so that center and edge circuits can be switched separately from any door.
5.3.3 Two 3-way HOA light switches in grouped Laboratories 2205 and 2207, so that center and edge circuits can be switched separately from any door.
6. Drawing sheet E01.04
6.1 Provide branch circuits for light fixtures shown on the drawing as follows:
6.1.1 All night light fixtures, exit fixtures and emergency battery packs – panel H3A, circuit 11;
6.1.2 Light fixtures in Corridor and Offices 3202 and 3204 – panel H3A, circuit 13;
6.1.3 Light fixtures in center of Laboratories 3201 and 3203 - panel H3A, circuit 15;
6.1.4 Light fixtures around edges of Laboratories 3201 and 3203 - panel H3A, circuit 17;
6.1.5 Light fixtures in center of Laboratories 3205 and 3207 - panel H3A, circuit 23;
6.1.6 Light fixtures around edges of Laboratories 3205 and 3207 - panel H3A, circuit 25;
6.1.7 Light fixtures in center of Laboratories 3206 and 3208 - panel H3A, circuit 19;
6.1.8 Light fixtures around edges of Laboratories 3206 and 3208 - panel H3A, circuit 21.
6.2 Connect additional light fixtures as night lights as follows:
6.2.1 One light fixture in Office 2206;
6.2.2 One additional light fixture in Office 2208.
6.3 Provide additional light controls in addition to those shown on drawing as follows:
6.3.1 One occupancy sensor each in Corridors 3200 B and C, for a total of two;
6.3.2 One occupancy sensor each in Laboratories 3202 and 3204, for a total of two;
6.3.3 Two 3-way HOA light switches in grouped Laboratories 3201 and 3203, so that center and edge circuits can be switched separately from any door.
6.3.4 Two 3-way HOA light switches in grouped Laboratories 3205 and 3207, so that center and edge circuits can be switched separately from any door;
6.3.5 Two 3-way HOA light switches in grouped Laboratories 3206 and 3208, so that center and edge circuits can be switched separately from any door.
7. Drawing sheet E02.01
7.1 Provide branch circuits for new devices as follows:
7.1.1 In Room 0204 P-H1 with one motor rated switch to new 25A, 1 pole circuit breaker in panel LBR13, circuit 8; 2-2.5mm2 + 1 - 2.5mm2 ground, 21 mm conduit.
7.1.2 In Room 0203 FC-1 with one motor rated switch to new 20A, 1 pole circuit breaker in panel LBR13, circuit 10; 2-2.5mm2 + 1 - 2.5mm2 ground, 21 mm conduit.
7.1.3 In Room 0203 FC-2 with one motor rated switch to new 20A, 1 pole circuit breaker in panel LBR13, circuit 10; 2-2.5mm2 + 1 - 2.5mm2 ground, 21 mm conduit.
7.1.4 In North end of Corridor 0200D FC-3 with one motor rated switch to new 20A, 1 pole circuit breaker in panel LBR11, circuit 28; 2-2.5mm2 + 1 - 2.5mm2 ground, 21 mm conduit.
7.2 Revise protections and circuits for new devices as follows:
7.2.1 Revise protection and circuiting for SF-7/AC-7 (panel LBR13/37,39,41) as follows: 250 A, 3 poles circuit breaker; 3- 95mm2 + 1 - 25mm2 ground, 63 mm conduit.
7.2.2 Revise protection and circuiting for pumps P1 and P2 (panel LBR13/31,33,35;
25,27,29) as follows: 100 A, 3 poles circuit breakers; 3- 16mm2 + 1 - 6mm2 ground, 35 mm conduit.
7.3 Delete the CAC shown in Room 0204.
8. Drawing sheet E02.03:
8.1 Provide branch circuits for new devices as follows:
8.1.1 In Room 1200D.1 FC-4 with one motor rated switch to new 20A, 1 pole circuit breaker in panel L1R11, circuit 28; 2-2.5mm2 + 1 - 2.5mm2 ground, 21 mm conduit.
9. Drawing sheet E02.05:
9.1 Revise protections and circuits for new devices as follows:
9.1.1 Revise protection and circuiting for AC-1 (panel L2S12/20,22) as follows: 50 A, 2 poles circuit breaker; 3- 6mm2 + 1 - 4mm2 ground, 21 mm conduit.
10. Drawing sheet E02.09
10.1 Revise protections and circuits for new devices as follows:
10.1.1 Revise protection for fan F3 (panel DPLR12/8,10,12) as follows: 50 A, 3 poles circuit breaker.
10.1.2 Revise protection for fan F4 (panel DPLR12/14,16,18) as follows: 50 A, 3 poles circuit breaker.
10.1.3 Revise protection for fan F5 (panel DPLR12/26,28,30) as follows: 25 A, 3 poles circuit breaker.
10.1.4 Revise protection for fan F6 (panel DPLR12/32,34,36) as follows: 25 A, 3 poles circuit breaker.
10.1.5 Revise protection and circuiting for fan F10 (panel DPLR13/8,10,12) as follows: 90 A, 3 poles circuit breaker; 3- 10mm2 + 1 - 4mm2 ground, 27 mm conduit.
10.1.6 Revise protection and circuiting for fan F11 (panel DPLR13/20,22,24) as follows: 90 A, 3 poles circuit breaker; 3- 10mm2 + 1 - 4mm2 ground, 27 mm conduit.
10.2 Delete Fan F16.
11. Drawing sheet E02.10:
11.1 Revise protections and circuits for new devices as follows:
11.1.1 Revise protection for fan F1 (panel DPLR/2,4,6) as follows: 50 A, 3 poles circuit breaker.
11.1.2 Revise protection for fan F2 (panel DPLR/20,22,24) as follows: 25 A, 3 poles circuit breaker.
11.1.3 Revise protection and circuiting for fan F8 (panel DPLR13/2,4,6) as follows:
90 A, 3 poles circuit breaker; 3- 10mm2 + 1 - 4mm2 ground, 27 mm conduit.
11.1.4 Revise protection and circuiting for fan F9 (panel DPLR13/14) as follows: 15 A, 1 pole circuit breaker (was 3 phase); 2- 2.5mm2 + 1 – 2.5mm2 ground, 21 mm conduit.
11.1.5 Revise protection for R4 (panel DPLR13/26,28,30) as follows: 100 A, 3 poles circuit breaker.
11.1.6 Revise protection and circuiting for CU-1 (panel L2S12/24,26) as follows: 25 A, 2 poles circuit breaker; 3- 2.5mm2 + 1 – 2.5mm2 ground, 21 mm conduit.
VOLUME 6
1. Add "Volume 6" in its entirety to the contract documents. Refer to Attachment D.
ATTACHMENT “D”
Added Drawings
The following drawings have been revised or added
Volume 1
General:
1. Drawing Sheet T01.03R
Volume 2
1. Drawing Sheet T01.03R
Volume 6
1. Drawing Sheet RCM3-7-T1.1
Mechanical:
1. Drawing Sheet RCM3-7-M1.1
2. Drawing Sheet RCM3-7-M1.2
3. Drawing Sheet RCM3-7-M1.3
4. Drawing Sheet RCM3-7-M1.4
5. Drawing Sheet RCM3-7-M1.5
6. Drawing Sheet RCM3-7-M1.6
7. Drawing Sheet RCM3-7-M1.7
8. Drawing Sheet RCM3-7-M1.8
9. Drawing Sheet RCM3-7-M1.9
10. Drawing Sheet RCM3-7-M1.10
11. Drawing Sheet RCM3-7-M1.11
12. Drawing Sheet RCM3-7-M1.12
13. Drawing Sheet RCM3-7-M1.13
14. Drawing Sheet RCM3-7-M1.14
15. Drawing Sheet RCM3-7-M1.15
16. Drawing Sheet RCM3-7-M1.16
17. Drawing Sheet RCM3-7-M3.1
18. Drawing Sheet RCM3-7-M3.2
19. Drawing Sheet RCM3-7-M3.3
20. Drawing Sheet RCM3-7-M3.4
21. Drawing Sheet RCM3-7-M3.5
22. Drawing Sheet RCM3-7-M3.6
23. Drawing Sheet RCM3-7-M3.7
24. Drawing Sheet RCM3-7-M3.8
25. Drawing Sheet RCM3-7-M3.9
26. Drawing Sheet RCM3-7-M3.10
27. Drawing Sheet RCM3-7-M4.1
28. Drawing Sheet RCM3-7-M4.2
29. Drawing Sheet RCM3-7-M4.3
30. Drawing Sheet RCM3-7-M5.1
31. Drawing Sheet RCM3-7-M5.2
32. Drawing Sheet RCM3-7-M6.1
33. Drawing Sheet RCM3-7-M6.2
34. Drawing Sheet RCM3-7-M6.3
35. Drawing Sheet RCM3-7-M6.4
ATTACHMENT “E”
Pre Bid Presentation
CENTER WING RENOVATION
Phases 3 and 4
United States Department of Agriculture
Agricultural Research Service
Eastern Regional Research Center (ERRC)
Wyndmoor, Pennsylvania
ERRC Modernization Renovation of Pilot Plant Laboratories Phases 9A, 9B, and Renovation of Power Plant Phase 8
Bernard Johnson Corporation
Construction Phase A/E Team:
Project Manager: Skip Nelson
Project Architect: Rita Sen, RA Assistant Project Architect: Nasima Khan, RA Project Civil Engineer: Nick Prodanov, PE
MEP Manager: Jack Gillan, PE Project Mechanical Engineer: Tom Tate, PE, CEM Project Electrical Engineer: Andrei Neuman, PE
Construction/ Cx Manager: Mike Stutts Retro Cx Engineer: Verle Williams, PE Environmental Engineer: David O’Konski, CIH, CSP
ERRC MODERNIZATION
Site Layout
Pilot Plant wing
Chemical Wing
Admin.
Wing
Power Plant
Typical Floor Plan Utilizing Modular Design Concepts
1. Laboratories/ Lab Support Areas.
2. Central Corridor
3. Office and \ or Lab Spaces
ERRC Modernization
Pilot Plant Renovation:
Phase 9A: Laboratories/ Lab Support Areas/ Mechanical Room/ (Col. 11-14)
Phase 9B: Laboratories/ Office Areas/ Locker Room (Col. 14-17)
Power Plant Renovation:
Phase 8: Boiler, Chiller, Cooling Tower, and associated equipment
Bid Options:
Bid Option 1 – Pilot Plant Wing Roof Replacement and Miscellaneous Upgrades (Col. 1-11)
Bid Option 2 – Retro Commissioning and Test and Balance of Existing Power Plant, Pilot Plant, and Chemical Wing HVAC Systems (Phases 1-7)
PILOT PLANT RENOVATION
Phases 9A and 9B
1. Concurrent Construction with Phase 8 and all Bid Options
2. Gut Renovation
3. Hazardous Abatement
4. Limited Construction Access
5. New Civil Utilities.
6. New Partitions and Finishes
7. New Lab Systems/ Equipment
8. New MEP Lab and Office Systems
9. New Roof
10. Cx of Building Systems
POWER PLANT RENOVATION
Phase 8
Power Plant
Power Plant
1. Concurrent Construction with Phase 9A and 9B, and all Bid Options.
2. Selective Demolition including a Chiller
3. New Chiller and Associated Equipment
4. New Cooling Towers and Structure
5. New Boiler and Associated Equipment
6. Hazardous Material Abatement and Modification of Existing Structural Cat Walk
7. Cx of HVAC Equipment
8. New Screening Wall
Bid Option 1 – Pilot Plant Roof Replacement and
Miscellaneous Upgrades Col. 1 - 11
1. Removal of Roof System, Flashings/ Copings/ Gutters, and Selected MEP Components.
2. New Insulation, TPO Roof, and Flashings/ Copings.
3. Brick Veneer Point Up.
4. New or Reinstall MEP Components.
Bid Option 2 – Retro Commissioning Phases 1 – 7
Phase 1 – Power Plant
Power Plant
Power Plant
1. Retro Cx and TAB of Existing HVAC Building Systems
2. Specific Scheduling Timeframe including Early Contract Submittals
3. Retro Cx Specialist and Team Requirements
4. Retro Cx Plan to be Site Specific detailed.
5. Coordination with Phase 9A, 9B, and 8 Cx Team
Phase 2 – Pilot Plant (Col. 1 – 11)
Phase 9A and 9B
Phases 3 - 7 Chemical Wing (Col. 1 – 18)
Bid Option 3 – Reduced HVAC Airflows in
Chemical Wing Laboratories and Lab Support Areas
| Amendment - 01.pdf |
| Drawings.pdf |
| T1-1-Layout1.pdf |
| M1-1-Layout1.pdf |
| M1-2-Layout1.pdf |
| M1-3-Layout1.pdf |
| M1-4-Layout1.pdf |
| M1-5-Layout1.pdf |
| M1-6-Layout1.pdf |
| M1-7-Layout1.pdf |
| M1-8-Layout1.pdf |
| M1-9-Layout1.pdf |
| M1-10-Layout1.pdf |
| M1-11-Layout1.pdf |
| M1-12-Layout1.pdf |
| M1-13-Layout1.pdf |
| M1-14-Layout1.pdf |
| M1-15-Layout1.pdf |
| M1-16-Layout1.pdf |
| M1-17-Layout1.pdf |
| M3-1-Layout1.pdf |
| M3-2-Layout1.pdf |
| M3-3-Layout1.pdf |
| M3-4-Layout1.pdf |
| M3-5-Layout1.pdf |
| M3-6-Layout1.pdf |
| M3-7.pdf |
| M3-8-Layout1.pdf |
| M3-9-Layout1.pdf |
| M3-10-Layout1.pdf |
| M4-1-Layout1.pdf |
| M4-2-Layout1.pdf |
| M4-3-Layout1.pdf |
| M5-1-Layout1.pdf |
| M5-2-Layout1.pdf |
| M6-1-Layout1.pdf |
| M6-2-Layout1.pdf |
| M6-3-Layout1.pdf |
| M6-4-Layout1.pdf |
File details come from the government source that posted it. Updated .